Boiler troubleshooting guides
3066 guides. No heat, noise, pressure and pump problems on hydronic boilers. Each one lists the likely causes and what to check, in order.
All brands (9)
- Condensing/corrosion of conventional boiler
Flue gas is condensing inside a conventional boiler. It rots the heat exchanger and flue. Return water is too cold. - No heat or some zones cold
Boiler fires but a zone stays cold, or the boiler won't fire at all. Two different problems, so sort out which one you have first. - Noise
Over the years the noisy boiler calls I've run turned out to be air, a dry pump, or pipes ticking at tight hangers more often than anything dramatic. - Poor heat / circulation
Poor heat or poor circulation on a hydronic system. Before changing anything, confirm that the boiler is actually reaching its operating temperature a - Relief valve weeps every cycle / pressure climbs
A relief valve that weeps every cycle or a pressure that keeps climbing is telling you the system can't absorb the water as it heats up. Nine times ou - Short cycling / wasted fuel
Short cycling wastes fuel and wears the boiler out. Check what temperature the boiler is set for and what the system is actually asking for on a mild - Symptoms of air in system
Air in a hydronic loop. Pumps fail, rotors run dry, you get gurgling, and rads stay cold. It rots the system from the inside, too. - Uneven heating
Some rooms run hot while others stay cold on a hydronic system. Rule out the simple stuff first (air, a dead circulator, a zone valve or thermostat) b - Won't fire
A boiler that won't fire usually has something in the chain keeping the burner from getting its go signal. In my experience it's the stat or the safet
Beckett (15)
- AFG burner at low firing rate: low firing rate baffle
At firing rates under about 1.00 GPH the AFG may need the low firing rate baffle (LFRB) to cut air flow and pressure. Weil-McLain calls for it on the - AFG burner on biodiesel: analyzer reads CO2 low
Most analyzers have no biodiesel fuel setting, so CO2 is calculated wrong on bio blends. - AFG burner: air in the oil line, priming the pump (SYS light yellow)
After a new install, filter change or running out of oil, the pump needs to be bled. The GeniSys 7565 primary on the AFG has a 4-minute Pump Prime mod - AFG burner: annual service checklist
What to do on the yearly service of an AFG burner. Service once a year, more often in dusty places. - AFG burner: setting combustion with an analyzer
How to set the air on an AFG burner so it has reserve air and zero smoke. - CF375 annual service checklist
Yearly service items for the CF375 burner. - NX burner: air in the oil line, priming the pump (yellow light)
After a new install, filter change or running out of oil the pump has to be bled. The GeniSys 7505 on the NX has a 4-minute Pump Prime mode that ignor - NX burner: annual service checklist
Yearly service list for the NX. Power off before working on it. - NX burner: cad cell resistance check
The NX has a small air tube and a throttle cup with small sight windows, so less light reaches the cad cell and the reading is often higher than on ol - NX burner: Honeywell R7184 primary sequence and lockout
Some NX burners use a Honeywell R7184 primary instead of the GeniSys 7505. Its timing is different. - NX burner: oil supply rules (pump seal leaks, air in line, plugged nozzle)
Most NX oil-side problems come from the supply piping. Check it against these rules. - NX burner: setting combustion with an analyzer
Start-up air settings from Table 1 are only a starting point. Final air must be set with smoke and CO2/O2 readings. - NX burner: start-up settings on Ultra Oil boilers
Nozzle, pump pressure and head/air starting points for each Ultra Oil size. The NX is shipped set for 1.00 GPH on the UO-3. - Priming the CF375 oil pump (air in the oil line)
How to bleed the fuel unit on the CF375 with the GeniSys 7565 control. - Setting CF375 combustion with instruments
Use an analyzer, not your eyes. Run the burner 5-10 minutes first.
Carlin (4)
- Carlin EZ with CAP system shuts down or locks out (blocked air intake)
The CAP system stops the burner when the outside combustion air pipe is blocked. - Checking the Carlin EZ ignitor
Safe way to test the ignitor. - Moving a Carlin EZ burner to high biodiesel blends (above B20 / B100)
Biodiesel cleans sludge out of the tank at first and lowers CO2. Set up before the fuel changes. - Setting Carlin EZ combustion (inside air or ducted air)
Target numbers depend on the incoming air temperature when the air is piped from outside.
Glow Brand (34)
- 0-10 VDC input to modulate firing rate (Mode 5)
Mode 5 on the C95 and C140 combis, a 0-10 VDC input driving the firing rate. It works like Mode 4. The boiler needs at least 2 VDC to wake up, and at - Annual maintenance and inspection
Technician checklist. Service must be done yearly or the warranty is void. - Blank display
If the screen on your C95 or C140 is dark, start with the simple stuff. Is it getting power at all? The ICB, the main control board, has an LED that t - Boiler pressure keeps dropping / FILL shows
Before touching anything, understand what the display is telling you. The B85, B120 and B160 boiler loses system pressure and the display asks for a f - Boiler shows FILL and will not fire
Display shows FILL, burner will not fire. Low water pressure is the lock. - Cleaning the combustion side of the heat exchanger
Annual service or when combustion readings drift, flue temperature climbs or Loc 16 appears. - Cleaning the primary heat exchanger
Clean the combustion chamber. Required after the first year, then at least yearly. Industrial sites may need more often. - Combustion analysis and throttle adjustment
Calibrate burner CO2 at maximum and minimum fire using a calibrated combustion analyzer. - Condensate drain installation
Route condensate to a drain properly so the boiler does not shut down or the trap does not fail. - Condensate trap cleaning
Clean the condensate trap and confirm condensate flow after reassembly. - Display is blank
Glow Brand B85, B120, B160 (NG and LP). LCD is completely blank. No power, no fuse, or a loose display cable. Start at the breaker. - Display normal but DHW not hot enough
Display normal, hot water runs, but it comes out lukewarm at the tap. Usually a setting, sometimes the mixing valve. - Display normal but hot water not hot enough
Glow Brand C95/C140 shows normal on the display but the hot water is not hot enough. Usually it's a setpoint thing or the mixing valve. Scald risk is - Display normal but no domestic hot water
Heating works or display is fine but there is no hot water. - Display normal but no domestic hot water (indirect tank)
The boiler runs for heating but the indirect tank does not get hot. - Display normal but no heat to radiators
The display is lit and normal, but the radiators stay cold. That usually means the boiler is not being asked to heat, or it is waiting on a setpoint o - Display normal but no heat to the space
The boiler looks fine but the heating loop stays cold. - Filling and purging the heating loop
Fill and purge the heating loop before the first start. Air left in the loop gives noisy piping, no flow and cold radiators. - Flow restrictor and screen filter cleaning
Annual cleaning of the flow restrictor screen in the CHB block. Clean more often in poor water areas. Protects the plate heat exchanger from sediment. - Gas line pressure check
Checking gas inlet pressure on the C95 and C140 is done at the line pressure test port with a manometer, before you light the unit. It tells you wheth - General maintenance and inspection (owner check)
These are the checks a homeowner can safely do between technician visits on a C95 or C140 combi. None of it needs tools or opening up gas parts. It is - Heating system preparation and water quality
Stainless steel heat exchanger is damaged by corrosion, debris and hard water. Prepare and protect the heating loop before startup. - Low water cut-off (LWCO) wiring and test
LWCO on the Glow C95/C140. Field wired, then tested. A jumper stays on 1 and 2 only when no switch is fitted. Don't leave a jumper in place of a switc - No DHW - no storage tank
Boiler runs but hot tap water is not produced, direct-fired DHW with no tank. - No DHW - with storage tank (sensor or aquastat)
Boiler does not heat the storage tank. Checks differ for sensor and aquastat setups. - Plate heat exchanger (PHE) cleaning
Removing and cleaning the domestic plate heat exchanger to remove calcium buildup. Clean regularly if the domestic water is not treated. - Re-lighting the unit
When one of these C95 or C140 boilers has gone out, most times it is a lockout after a missed light or a gas supply interruption, and the owner just w - Removing an existing boiler from a common venting system
Use this procedure for each boiler that stays on a common vent after another boiler is removed. The remaining venting is usually too large and must be - Replacing the fan
Fan removal with burner assembly removed from the heat exchanger. - Replacing the gas valve
Gas valve removal and reinstallation with leak and combustion checks. - Safety relief valve test
This is the annual test of the boiler safety relief valve. The valve is the last line of defense against overpressure, so it needs to move freely and - Setting up a CH setpoint above 140°F (60°C)
CH setpoint above 140°F on a Glow C95 or C140, up to 180°F (82°C). Needs CPVC at the boiler and parameter changes. Standard vent pipe will not take th - Vent slope, support and roof termination
Install exhaust and intake piping so condensate drains back toward the boiler and the piping is secured. - Venting rules for intake and exhaust placement
Basic placement rules for the air intake and exhaust terminations. Check the clearance table as well.
HTP (6)
- Boiler overheating lockout (F00, F05, F06)
On an HTP Elite EL, an F00, F05 or F06 lockout means the water is running too hot with the pump on, and in my experience that is a flow problem before - False flame signal with burner off (F11)
F11 on the HTP Elite EL. Flame signal is there with no call for heat. Could be a real flame from a leaking gas valve, or a false signal. Look in the s - Fan speed error (F13)
F13 on an HTP Elite EL means the fan isn't doing what the control asked for. That can be as simple as a loose plug or as big as a failed fan or board. - Flame drops out while running (F10)
F10 on the HTP Elite EL: the burner lit but lost flame three times on one call. Check the flame signal in the status menu and watch the gas pressure u - Lockout on ignition (F09, no flame)
If your HTP Elite EL boiler tries to light four times on one call for heat and then locks out with F09, it never proved flame. That tells you the prob - Thermostat calling but boiler not firing
The thermostat is calling for heat but the HTP Elite EL burner stays off. Before assuming a failure, read the message on the display, because the boil
Navien (190)
- Accessing the control board terminals
The control board (PCB) terminals are behind the front cover. Electrical shock can cause serious injury or death, so disconnect power before any work - Add device profiles in web configurator
Select the profile for each attached device and assign its Node-ID. Repeat for all devices. - Adjust gas/air ratio (CO2) with combustion analyzer
Check and adjust CO2 at MIN and MAX firing using the emissions port. - Adjust gas/air ratio with digital manometer
Alternate method to check the gas/air ratio when no analyzer is available. - Air handler and cooling coil piping
When the boiler feeds heating coils in air handlers that may be exposed to chilled air, the coil piping must prevent cooling fluid from entering the b - Air handler interface operation
With a thermostat and air handler, the boiler's A/H contacts stop air handler operation when space heating is not running because of DHW demand, boile - Air handler piping arrangements
Air handlers with internal pumps must be piped either with a connecting pipe to the air handler, or in a primary/secondary arrangement with the boiler - Air handler system piping
Piping layout for a boiler feeding an air handler, with expansion tank, pressure relief valve, air separator and pressure reducing valve. - Air handler system with RS-485 communication
Air handler piping with the boiler linked by a COMM cable to a thermostat and outdoor sensor. - Air handler wiring - system pump
Wiring of the system pump when the boiler is connected to an air handler. - Air removal from the system piping
Air vents and bleeders must be placed around the system to purge air during commissioning. An air separator or air eliminator must be fitted, usually - Annual service checklist - Navien NHB-H
Annual start-up and service items for the boiler from the User's Information Manual maintenance schedule. - Apply propane or high altitude conversion labels
After the CO2 or offset values are confirmed, complete and attach the conversion labels next to the rating plate. - Assembling the common vent collar kit on the boiler
Fit the common vent collar kit to the boiler exhaust before running a common vent. - Assembling the foot bar
Builds each foot bar on the base frame. - Assembling the middle bar
Fits the middle fixed bar between the two post bars. - Assembling the pipe support brackets
Mounts heating supply, heating return and gas pipe supports. - Assembling the upper bar
Fits the upper fixed bar and boiler mounting bracket. - Assembling the wye joint on the common vent
Build the vent run from the collar using wye fittings. Tees can be used instead of wyes. - Attaching a boiler to the frame
Hang and secure the boiler on the rack bracket. - Attaching an extension kit (in-line setup)
Adds rack sections for more boilers in an in-line layout. - Before working on controls or wiring
Electrical and commissioning precautions when servicing the boiler. - Cascade piping considerations
General piping rules for a cascade system. Diagrams are for concept only. - Cascade system roles and operating rules
Cascade system with one NCB700 combi-boiler and up to 15 Navien NPE-A2 or NPE-S2 water heaters. - Change gateway IP on wired Ethernet port
Set the gateway IP over the Ethernet port through the FS-GUI network settings. - Change gateway IP over wired Ethernet
Set a static or DHCP IP address for the wired network connection. - Change primary network connection
Choose which connection the gateway uses when both Ethernet and Wi-Fi Client are available. Ethernet is the default. - Check and adjust gas valve offset at low fire
Check the gas valve offset at low fire against the altitude kit table. Adjust only if the reading is out of range. - Check and adjust gas/air ratio at low fire
Verify CO2 or offset at low fire and adjust the gas valve set screw if needed. - Check CO2 at high fire and verify gas orifice
Verify CO2 at high fire. If it does not match the table, do not change the gas valve. Check the gas orifice instead. - Check common vent collar damper through maintenance port
Periodic check of the damper plate inside the Navien common vent collar kit to confirm it opens and closes properly. - Checking vent connections with the Vent Installation Detector (VID)
The VID helps detect vent pipe separation at the collar, but it does not detect every leak or blockage. - Choosing an approved vent termination
Only use the vent terminations and vent components the manual lists for this boiler. Use the same manufacturer's termination as the vent system. Follo - Choosing an installation location
Location checks before mounting the boiler indoors. - Choosing the installation location
Pick a site that has room for the boiler, proper venting, a condensate drain, and access to gas, water and power. Do not install outdoors, in an RV or - Cleaning the boiler exterior and remote controller
Clean only with the unit off and power disconnected. The boiler stays hot for several minutes after shutdown, so let it cool before servicing. The rem - Cleaning the combination boiler and remote controller
Cleaning must be done with the boiler off and power disconnected. The boiler and its parts can stay very hot for several minutes after shutdown, so le - Cleaning the DHW cold water inlet filter
Clean the domestic hot water cold inlet filter if flow is poor. Have a bucket ready for draining water. - Cleaning the intake air filter
A dust- or pollen-blocked intake air filter stops the boiler and shows Error code 10. Clean it every 3 to 4 months. - Cleaning the space heating strainer
The strainer filters debris from the heating circuit. Clean it when heating performance drops. - Closed loop system requirements and air removal
The boiler is only for pressurized closed loop heating systems that are free of air and debris. Open systems are not approved. - CO2 does not match Table 2 at high fire
After orifice and DIP switch setting, CO2 at high fire is outside the target range. - Combi pre-heat for DHW
Pre-heat mode keeps the boiler warm so hot water arrives quickly when there is no external recirculation loop. It is on by default. - Combustion air and room conditions
Keep the air clean and free of chemicals that can damage the burner and vent. - Combustion air location and contaminant avoidance
Choose the combustion air source and location to avoid contaminated air. Use direct venting (outside air) where contaminants are present. Carbon monox - Common vent installation requirements
Core rules for a shared vent system. Backflow dampers and the cascade cable are required, and the common vent is only approved for altitudes up to 4,5 - Common vent system overview (up to 7 NPE water heaters)
One NCB700 and up to 7 NPE water heaters can share one common vent, using shared intake and exhaust pipes. This is a Category IV appliance that runs w - Compromised venting system
Improper venting can cause carbon monoxide build-up, which can cause brain damage or death. Shut the boiler down if the venting is damaged. - Condensate drain connection
Condensate must drain from the 3/4 in condensate outlet, and the trap must be primed with water. - Condensate drain disposal and connection
Condensate is acidic (pH 3-5). Follow local codes. Draining into a laundry tub is recommended because detergent neutralizes the acid. Options: direct - Condensate drain installation
Condensate is acidic, with a pH of 3 to 5. Drain it to a laundry sink or through a neutralizer, or pump it if the drain is far or below the boiler out - Condensate drain piping
Route the condensate line from the boiler's 1/2 in NPT drain fitting at the bottom of the unit. Use only corrosion-resistant pipe such as PVC or CPVC, - Condensate neutralizer kit installation and maintenance
Use a neutralizer when condensate is discharged through an approved neutralizing agent. The agent must be replaced periodically, and the boiler's firi - Condensate neutralizer maintenance
Check neutralizer media and outlet pH regularly. Test once a year with pH strips or an electronic meter. Replace the media when pH falls below the loc - Configuring a zone system from the front panel
The NCB700 can control up to 3 zones using zone valves or zone pumps. Zones must be set on the front panel after the system is installed. - Connect NFB-301C/399C boiler to gateway R1 port
Wire the boiler's front-panel 3-pin terminal block to the gateway R1 Phoenix connector. Keep R1 Switch 4 OFF and bond RS-485 GND per standard practice - Connect PC to gateway over Wi-Fi access point
When first powered, the gateway runs its own Wi-Fi access point for direct connection. - Connect PC to gateway via Ethernet
Connect a laptop directly to the gateway Ethernet port for local setup. - Connect the NFB-301C/399C boiler to the gateway R1 port
The R1 port takes the boiler RS-485 link through a 3-pin Phoenix connector that plugs into the boiler terminal block on the right side of the front pa - Connecting main trunk pipes and fitting the vent end
Join the trunk runs between wye assemblies and finish the open ends of the intake and exhaust. - Connecting Ready-Link communication cables
Connect the cascade units with Ready-Link cables. All units must be powered off before connecting. - Connecting Taco zone valves
Example connections for Taco 570/571 and Taco Sentry zone valves. - Connecting the boiler power supply
The boiler runs on a dedicated 110-120V AC supply with a breaker. It must not be connected to 220-240V. Only licensed professionals should make the co - Connecting the vent pipe to the common vent collar
Seat the vent pipe fully in the collar and secure it so the joint is gas-tight. - Connecting the vent pipe to the vent collar
Correct insertion and clamping of the exhaust pipe onto the boiler collar. - Connecting to a Navien SmartZone+ zone pump controller
The SmartZone+ controller runs systems with more than 3 zones. It connects by RS-485 over the Ready-Link cable so the controller and boiler share oper - Convert NFC-H boiler from natural gas to propane
Procedure to convert an NFC-H combi-boiler to propane, including gas valve outlet adapter removal, DIP switch setting and gas/air ratio check. - Determine the common vent length
Total vent length is horizontal width plus vertical height. Use the total BTU/H of all units to read the allowed length from the table. - DHW external recirculation with dedicated return line
DHW recirculation using a dedicated return line with a check valve and recirculation pump. - DHW piping guidelines
Use only fittings and components approved for potable water. Keep hot water piping short. Do not add pressure control valves, flow restrictors or mech - Direct vent termination layouts
Layouts for vertical and horizontal direct vent terminations and for routing intake and exhaust to different locations. - Domestic hot water (DHW) mode operation
The user controls domestic hot water. The boiler heats water on demand and only produces hot water while it is being used. - Domestic hot water flow control
The NCB700 has a water flow adjustment valve that works with the flow sensor, and a mixing valve that keeps domestic hot water temperature stable. Ext - Domestic hot water relief valve installation
Install an approved 3/4 in domestic hot water relief valve with a maximum pressure rating of 150 psi on the DHW outlet. No separate high-limit safety - Draining the combination boiler
Have a bucket ready to catch water. The manual's figure shows the drain points, and the text reads some drain fittings as "coke" (likely cock or valve - Electrical connections
Power and external control connections on the main PCB. - Enable gateway Wi-Fi access point
Allow a PC to connect to the gateway over its own Wi-Fi network. - Error E001 - heat exchanger overheat
Heat exchanger overheat fault. - Exhaust direction and cold-weather plume
Site the exhaust so it does not blow into openings and so the visible vapour is accepted. - Exhaust venting installation
Vent per the approved Category IV system and keep the termination clearances. - External low water cutoff (LWCO) installation
A separate external LWCO is needed only if local code requires it. The internal device is factory installed. - External LWCO wiring
Typical wiring for a terminal-type low water cutoff (LWCO) where the boiler supplies 24 VAC to the LWCO power terminals. - External recirculation with HotButton and NaviCirc
DHW recirculation controlled by a wired HotButton, with a NaviCirc valve and recirculation pump. - External recirculation with HotButton or aquastat and dedicated return
Dedicated return DHW recirculation controlled either by a HotButton push button or by an aquastat, not both. - External recirculation with NaviCirc
DHW recirculation loop using a NaviCirc valve on the faucet furthest from the boiler and a recirculation pump. - External water fill connection
An external water fill can be fitted to the system piping where an application needs it. The example system includes an air separator, relief valve, p - Field communication problems
Checks for the Ethernet/field side when communication fails. - Fill and leak test the water system
Fill test to confirm the water system is installed correctly before firing the burner. - First-time lighting and gas shutdown procedure
Pilotless boiler with electronic ignition. Smell for gas before every start, and never light the burner by hand. The gas control knob is turned by han - Fixing the frame to the location
Secures the rack to the floor before the boiler is hung. - Flexible polypropylene or stainless vent installation
Flexible vent pipe is only allowed in a vertical run through the roof with indirect venting. Horizontal terminations are not allowed. - Freeze, pressure, electrical and thermostat protection
During the heating season an internal sensor starts a safety heating cycle to protect against freezing. With no gas supply, the circulation pump runs - Gas orifice change for LP or high altitude
Procedure to swap the gas orifice and convert the boiler. - Gas smell response
Safety action if gas is smelled near the boiler. Do not attempt to light any appliance. - Gas smell: what to do
Treat any gas smell as an emergency. Do not operate the boiler or any faucet, and do not try to light any appliance. Gas is heavier than air and can s - Gas supply connection and leak test
Gas supply must be connected by a licensed professional using the gas type and pressure on the rating plate. The boiler cannot be converted between na - Gas supply sizing and piping
Gas meter capacity must cover all connected appliances. The boiler should be the first appliance on the gas line. - Gas type, propane and high altitude conversion
The boiler leaves the factory set for natural gas. Propane or high altitude operation needs the Navien propane and high altitude conversion kit. Field - Hardwiring the boiler directly to the power supply (no plug)
Used only where local code requires direct wiring. Remove the factory plug and splice the boiler leads to a field-supplied 110-120V supply. - Heating loop flow direction and accessory placement
Water must flow through the manifold in one direction, and accessories go on the heating supply side. - Heating system piping, expansion tank and fill
Flush the whole system before connecting piping and keep debris out of the lines. Expansion tank and fill connection must be placed correctly. - High altitude derate and conversion
Above 2,000 ft the boiler derates. Natural gas needs an orifice change above 5,400 ft. Propane needs the propane conversion kit at any elevation the u - Hot water scald risk and DHW temperature setting
Domestic hot water temperature above 52 °C (125 °F) can cause instant severe burns or death. The factory setting is 49 °C (120 °F). Children, disabled - Hot water turns cold or no hot water at the tap
Hot water runs for a while then goes cold, or there is no hot water. - Hydronic piping requirements for applications
These diagrams show the piping concept only. Local codes, building codes and the expansion tank sizing in the manual take priority. Air must be able t - Ignition failure from flame rod or igniter buildup
Ignition failures can happen when dirt or white powdery residue builds up on the flame rod. If ignition keeps failing, clean the flame rod. A new igni - Ignition, flame and power-loss protection
If ignition fails, the boiler shuts off gas and flashes a 2-digit code on the room thermostat; see the troubleshooting section. If the flame drops out - Indoor vent termination clearances
Clearances for two-pipe, concentric and low-profile indoor venting. The exhaust and intake terminations must stay apart, and concentric sidewall termi - Install outdoor temperature sensor
Mount and wire the outdoor temperature sensor used by the outdoor reset control. - Install the Common Vent Collar Kit on the boiler
The collar kit has a backdraft damper that blocks flue gas and cold air when the fan is off. It also has a maintenance port for checking the damper pl - Install the heating system relief valve
Install the relief valve vertically on the boiler outlet through the universal adapter, with a vent on the adapter. The valve must be ASME approved. - Install the primary manifold on the boiler
Mount the manifold between the boiler's heating connections and the system piping, with the boiler already mounted on the wall. - Installing the condensate neutralizer kit
A Navien neutralizer kit is recommended when condensate goes through a neutralizing agent. Flue gases must never pass through the neutralizer. Only on - Installing the condensate siphon loop on a cascade system
The condensate drain forms a siphon loop that must be primed with water before the boiler runs. - Installing the DHW pressure relief valve
A DHW pressure relief valve must be fitted by a licensed professional. It is not supplied with the boiler and is required. Approved examples listed: W - Installing the Modbus RTU wiring
Field wiring of the Modbus RTU board to the building automation system (RS-485 network). Power off the boiler before opening it. - Installing the pressure relief valve
The relief valve protects the heating circuit from overpressure and must be sized, placed and discharged correctly. - Installing the PRV-air vent adapter on a boiler
The adapter lets one boiler connection take the pressure relief valve, the air vent and an external LWCO. - Installing the PRV-Air vent adapter on the boiler PRV connection
The PRV-Air vent adapter lets you mount the pressure relief valve, the air vent and an external LWCO on the boiler's PRV connection. The adapter fits - Leak testing the common vent
Test every joint on the common vent before the boiler is put into service. - Log in to gateway web configurator
Open the web app and log in to reach the Configure tab. - Lost or incorrect gateway IP address
Find the gateway on the network with the FieldServer Toolbox and correct its IP. - LP gas conversion procedure (NCB-H)
Convert the boiler from natural gas to propane, then verify combustion. - Measuring and adjusting inlet gas pressure
Check inlet gas pressure during the commissioning run and adjust the regulator if needed. - Measuring inlet gas pressure
Procedure to measure the gas inlet pressure at the boiler under maximum firing. Only a licensed professional should do this. - Measuring inlet gas pressure at maximum firing rate
Licensed professional only. Read the inlet gas pressure with a digital manometer at the pressure port while the boiler is at full fire. - Mount gateway on DIN rail
Use the DIN rail bracket on the back of the unit. - Mounting the wall bracket and boiler
Wall mount the boiler using the bracket from the L box. Use the fastener that suits the wall type. Do not mount on drywall without reinforcement. - NaviClean magnetic filter: annual service
NaviClean is an in-line magnetic/dirt filter (made by ADEY) for hydronic systems. Best spot is after the last zone and before the boiler. It needs a y - No communication on Modbus RTU side
Field check when the Tx/Rx LEDs are not flashing rapidly. - No hot water, or hot water turns cold and stays cold
Basic FAQ troubleshooting. - No space heat - Navien NHB-H / NFB-H
Thermostat calls for heat but the boiler does not heat the zones and shows no error code. - No water at all when the hot water tap is opened
Basic FAQ troubleshooting. The flow chart layout is hard to read, so the checks below are grouped by likely cause. - No water at the hot water tap
Hot tap opened but no water comes out. - Non-direct (single pipe) venting setup
Single pipe operation draws combustion air from the room. Negative pressure can back-draft cold air and freeze the heat exchanger, and freeze damage f - Open FS-GUI network settings
Path to the FieldServer GUI page used for IP and Wi-Fi settings. - Power gateway from the boiler PCB
The gateway can take power from the boiler controller's gateway power terminal instead of the supplied power supply. - Power gateway from the supplied power supply
Use the power supply included in the box instead of the boiler PCB. - Preparing and cleaning the heating piping
Flush the whole heating circuit before connecting it to the boiler to remove debris, flux, solder, sediment and scale. - Preventing freeze damage
Freeze protection needs electricity and runs whether the remote controller is ON or OFF. Direct vent installation reduces air movement inside the unit - Reach gateway in local browser by changing PC subnet (Windows 10)
Give the PC a static address on the gateway's default 192.168.1.xxx subnet. Use only one access method, either this or the FieldServer Toolbox. - Recirculation with a DHW return line installed
External recirculation can only be connected to and controlled by NPE-A2 water heaters. - Recirculation without a DHW return line
Used when no recirculation return line is installed. HotButton mode cannot be used in this layout. - Recover a lost gateway password
Support must issue a temporary password before a new one can be set. - Refilling the space heating side with the auto feeder
The built-in automatic feeder fills the space heating side and stops on its own. Bleed air and check for leaks before restarting. - Relief valve discharging - Navien NHB-H / NFB-H
The pressure relief valve drips or discharges, or pressure climbs high when the boiler heats. - Removing cascade communication settings
Returns the water heaters to independent operation. - Selecting a vent type
All NCB700 boilers are Category IV and are set at the factory for direct (sealed) venting. Direct venting is recommended whenever possible. - Set BACnet Network Number for multiple gateways
Required when more than one gateway is on the same subnet. - Set up gateway passwords
Restrict gateway access with Admin and User accounts. - Set up Wi-Fi client connection
Connect the gateway to a local wireless access point as a Wi-Fi client. - Set Wi-Fi client connection to a local access point
Connect the gateway to a site wireless access point and make it the primary connection. - Setting up cascade communication
Assign the NCB700 as main unit and allocate each NPE water heater as a sub unit. - Space heating does not work while DHW is running
The heating side stays off while the unit is heating domestic hot water. - Space heating mode operation
Space heating water is controlled by a thermostat. The thermostat either holds a room temperature or a heating water temperature. The installing contr - Space heating water piping and pressure relief valve
A pressure relief valve must be installed on the space heating supply. Use threaded connections only. - Start installation over by clearing profiles
Deletes all profiles found or added through the web configurator so the unit can be reinstalled. - Take a diagnostic capture from FS-GUI
Capture network and serial traffic from the gateway web page. No software download is needed. Works only on FieldServers with BIOS released November 2 - Take a diagnostic capture with FieldServer Toolbox
Capture a log and configuration snapshot before calling support. - Understanding the Vent Installation Detector (VID)
The VID only confirms the pipe is inserted at least 2-3/4 in into the collar. It is not a gas leak or CO detector and will not catch joints that come - Unit does not run or heat
No heating or hot water from the unit. - Update gateway firmware
Load new firmware through the web browser. - Valves, unions and check valves on heating circuit
Full-port ball valves are required. Check valves are recommended but must not sit between the close-spaced T connections and the expansion tank. - Vent pipe pitch and solvent cement joints
Horizontal runs must slope up toward the termination. Use approved primer and cement and keep the work area ventilated. - Vent termination and clearances
Keep the termination clear of snow, ice and blockages. The building owner must keep the intake and exhaust free and schedule maintenance. - Ventilation and clearance safety
Safety rules for combustion air and venting. Operating without proper venting can cause fire or carbon monoxide poisoning. - Venting requirements (Category IV, positive pressure)
The boiler is a Category IV appliance and needs a special vent system. The vent operates under positive pressure. Improper venting can cause high carb - Verify device communications
Confirm the gateway is talking to the attached device without errors. - View gateway diagnostic connection errors
Check the Connections page for communication errors. - Wall mounting the boiler
Mount the upper bracket on studs, then hang the boiler and secure the bottom. - Water is not hot enough
Basic FAQ troubleshooting. - Water is too hot
Basic FAQ troubleshooting. - Wire gateway R2 port to the BMS RS-485 field network
Connect the building management system RS-485 bus to the 3-pin connector on the R2 port. - Wire the R2 port to the RS-485 field (BMS) network
The R2 port carries the field protocol to the building management system. Ethernet connection is covered in section 5. - Wiring a 3-zone zone pump system
Dry contact zone pumps, with or without 24 VAC thermostat power, plus optional DHW recirculation. - Wiring a generic zone controller
Generic zone controller wiring for zone valve and zone pump systems on the NCB700. - Wiring a zone valve system
Zone valves are powered from the boiler's 24 VAC supply, which is limited by the 75 VA transformer. - Wiring DHW recirculation with 24 VAC powered thermostats
Same DHW recirculation options as the dry-contact layout, with 24 VAC powered thermostat and aquastat inputs. - Wiring the Navien SmartZone+ zone controller
The SmartZone+ talks to the boiler over an RS-485 link through the Ready-Link connection. This lets the two share operating data and reduces unneeded - Wiring zone pumps and dry-contact thermostats (no 24 VAC supplied)
The NCB700 supports up to 3 heating zones. The zone pump and boiler pump connectors are dry contacts; the thermostats are wired without 24 VAC supplie - Wiring zone pumps with 24 VAC powered thermostats
Same zone pump layout as the dry-contact system, but the thermostats are powered by 24 VAC from the boiler. - Wiring zone pumps with domestic hot water (DHW) recirculation
The NCB700 can run 3 zone pumps and DHW recirculation together. Recirculation can be set to a timer, aquastat or HotButton input, or the boiler can co - Wiring zone valves (no 24 VAC supplied to valves)
A 3-zone valve system uses zone valves instead of zone pumps. Zone pump 3 terminal is used for the system pump. Each zone valve has a normally open (N - Wiring zone valves with 24 VAC powered thermostats
Same zone valve layout, with thermostats powered by 24 VAC. The boiler's internal 24 V transformer (75 VA) powers the zone valves, LWCO switches and t - Zone pump system wiring (up to 3 zones)
Wiring for a zone pump system with up to 3 zones using dry contact or thermostat connections. - Zone pump wiring - thermostats with 24VAC power
Dry contact zone pump connections where the thermostats supply 24VAC power, with zone pumps 1 to 4 and the boiler internal pump. - Zone pump wiring for up to four zones
Wiring notes for running up to four zone pumps from the boiler. Each zone output is rated for a maximum of 2.5 A. - Zone system with pumps (primary/secondary piping)
Example layout with up to three zones, each on its own pump, with a common air separator, expansion tank, pressure relief valve, pressure reducing val - Zone system with zone valves (primary/secondary piping)
Example layout with zone valves on each zone, a system pump, air separator, expansion tank, pressure reducing valve, backflow preventer and make-up wa - Zone valve system piping (primary/secondary)
Piping layout for a multi-zone system using zone valves, with an air separator, expansion tank, pressure reducing valve and backflow preventer.
NTI (55)
- Access the low voltage wiring connections
Anytime you wire a room thermostat or chase a low voltage problem on the TRX150, you have to get into the control panel first. What I usually see is p - Blocking errors versus lockout errors
There are two kinds of error on this boiler and they act differently, so it helps to know which one you are looking at. A blocking error clears by its - Blower not running
The Trinity Tft boiler gets a call for heat but the blower does nothing. Power off the boiler before touching the connectors, and be careful with any - Blower runs at high speed with burner off
Trinity Tft blower stuck at high speed with the burner off. It won't idle down in standby. Usually the signal cable or no 24 VAC to the control. Shut - Boiler bangs or hisses; Lockout 81 delta T
Banging, hissing and Lockout 81 delta T on a Trinity Tft all point at not enough water flow through the heat exchanger. The water boils locally and th - Burner not running on a call for heat
If there's a heat call and the boiler just sits there, don't panic. It's often not broken. The control may think the demand is already met, or it's ho - Check inlet gas pressure at the boiler
Use a manometer on the line pressure test point to confirm the inlet gas pressure is within the minimum and maximum for the gas type. Loosen the bolts - Check the burner
Burner check on the TRX150. Combustion assembly is out of the heat exchanger, so look it over while you can. Gaskets do not get reused. - Check the condensate drain
Dry trap on the TRX150. Flue gas coming out of the condensate drain. Trap has to hold water or the seal is gone. Not a guess-and-go item, since it is - Check water and gas piping
With the cover off the TRX150, I always walk the piping before anything else. Most callbacks I see on boilers trace back to a slow weep at a fitting o - Circulator (CH or DHW) not running
If your NTI Trinity Tft boiler isn't moving water to the zones or the DHW tank, the circulator output isn't powering the pump. It can be a blown fuse, - Clean the condensate trap
Clean the siphon cap, cone and ball. If the boiler has a condensate neutralizer kit, check it at the same time. - Clean the DHW filter (combi models only)
If you have a combi and the hot water has gone weak or lukewarm, or the boiler will not see the flow, the first thing to look at is the DHW inlet filt - Clean the heat exchanger and combustion chamber
Cleaning requires a nylon brush and an FDA-approved liquid lime scale remover. Insulation contains ceramic fiber. Wear a NIOSH-certified N95 respirato - Clean the heat exchanger combustion chamber
Remove the combustion assembly, clean the heat exchanger tubes, then reassemble with new seals. Use a nylon brush and an FDA approved lime scale remov - Condensate drain setup
A condensing boiler like this one wrings the heat out of the flue gas, and what drips out is acidic condensate. That water has to go somewhere safe, i - Condensate line blocked (display error)
Boiler shows an error and won't run when the condensate line is blocked. No error code number is printed on these pages. Condensing boilers have to ge - Connect 120 V power for CH and DHW circulators
Field wiring for the central heating and domestic hot water pumps at the boiler junction box. The 120 V circulator cables land on CN5 for the CH pump - Display is blank
A blank touchscreen on a Trinity Tft is often just the display timing out, so touch it before anything else. If it stays dark, you are dealing with ei - Display shows System Disconnected! constantly
Display lit but says System Disconnected! all the time. Display has power, it just can't talk to the controller. Look at the comm wiring and the 24 VA - Drain the domestic hot water system and indirect tank
DHW side and indirect tank on the TRX150. Drain it any time freezing is a risk. Empty means empty, no pockets left to split a pipe. - Drain the heating system
Draining the TRX150 and its heating circuit is done for service or to protect the system from freezing. Confirm the boiler is isolated and cold before - Excess flow valve (EFV) in the gas line
Undersized EFV starves the boiler. Check its flow rating against the TRX150 input. - Exhaust vent and intake pipe installation rules
General rules for routing and joining vent pipe. - Flame signal too low or flame loss
The control reads the flame signal in parameter 8.7.9. It needs a signal above 18 to detect flame at start, and it calls a flame loss if the signal fa - Functional test after maintenance
Last job before handing the TRX150 back. Fill, purge, power up, check. - Gas leak check before startup
First thing I do on any gas appliance startup is use my nose. Before and during the first start, smell at the floor and around the boiler. If there is - Gas line installation requirements
Gas line work must be done by a licensed professional. Confirm the boiler gas type matches the rating plate. This boiler must be converted for propane - Ignition failure - Lockout 109 / Hold 110
Burner goes through its ignition trials without proving flame. - Inform the user after service
After a service call I always sit down with the owner for a few minutes. Most of the nuisance calls I got on boilers came from people who did not know - Install exhaust vent or intake pipe into the boiler collar
Putting the vent or intake pipe into the boiler collar on an NTI TRX is simple, but the joint has to seal or you will have flue gas leaks. It uses a g - Installation checklist sign-off (commissioning)
What I usually see at handover is a boiler that runs fine but nobody wrote anything down. This checklist is the sign-off that fixes that. It covers wi - Lockout 138 - flame too low
On a Trinity Tft boiler, Lockout 138 means the flame signal fell below what the control needs. What I usually find is a fouled flame sensor or a partl - Low water cutoff / ILK OFF lockout (67)
Display shows ILK OFF, lockout 67, burner won't fire. That is the interlock string open on the NTI Trinity Tft. Low water or an open external limit. C - No power - checking 120 VAC and 24 VAC at the boiler
Nothing on the display or no response to a heat call; confirm the power supplies first. - Operate the primary pressure relief valve (test)
Test the relief valve to make sure it seats and does not weep. Check the discharge line is piped to a safe place first. - Outdoor temperature alert (Alert 248)
Alert 248 on an NTI Trinity Tft says the controller expects an outdoor sensor, because outdoor reset is switched on from the factory. It's an alert, n - Piping without an external central heating circulator (TRX150 / TRX199 and TRX199C)
Experienced guys will tell you this layout works but has limits. The boiler's internal circulator feeds the heating system directly, so there's no ext - Prepare the boiler before replacing components
Before you replace any component on the TRX150, isolate everything: electrical, gas and water. Confirm each one is actually off rather than assuming. - Pressure test the gas supply
Most of the time a gas line gets pressure tested on a new install or after piping changes, and the boiler gets caught in the middle of it. The NTI TRX - Primary/secondary piping for TRX150 / TRX199 with separate central heating circulator
Use when the boiler's internal circulator cannot give enough flow to the secondary circuits. - Remove the cabinet cover and control panel housing
Getting the front cover and control panel housing off the TRX150 for qualified service work. - Replace the burner
Burner swap on the TRX150 means pulling the cover, the combustion assembly and then the burner. Replace every seal that looks damaged, because reused - Replace the fan and mixer
The fan and mixer on the TRX150 come off as one assembly, and that is how I usually do it. The thing that bites people is the fuel setup. The gas diap - Replace the gas valve
Swapping the gas valve on the TRX150 is a straightforward job if you take it in order, but it is gas, so it belongs to a licensed technician. You get - Replace the main heat exchanger
Drain the boiler and disconnect the heating piping, relief valve pipe, air purger and return pipe before removing the heat exchanger. - Replace the main PCB
New main board on the TRX150. Swap it, then set the parameters from the kit sheet. Skip that and it will not run right. - Sidewall concentric or low profile exhaust location
Sidewall concentric or low profile termination, layout rule. Exhaust and intake spacing matters here. Wrong spacing means flue gas gets pulled back in - Stack limit lockout (Lockout 82)
Lockout 82 on a Trinity Tft means the flue temperature went past the stack limit. Typically I find a dirty combustion chamber or heat exchanger, since - System water fill, purge and test
Fill and purge on the TRX150. Do it at install and after any service that opens the loop. Air in the system means noise, no flow, cold rads, pump cavi - Thermostat circuit check (no voltage allowed)
This check confirms the thermostat, zone valve and relay wiring is sending no voltage to the boiler's low voltage thermostat terminals TT1/TT2. Those - User maintenance checks
Checks the owner can do between annual service visits. - Venting below an overhang (sidewall snorkel)
Sidewall snorkel venting under an overhang on an NTI TRX is the one that gets installers in trouble. The exhaust has to drop below the overhang by a s - Venting below grade and outdoor vent piping
Vent pipe that leaves the building below grade, or runs outside the wall before it terminates, has tighter limits than a normal indoor run. Before tou - Wire a room thermostat
Connecting a room thermostat to the TRX150 is a low voltage job, but it is done inside the control panel, so the power needs to be off and the panel o
Riello (5)
- Purge air from the Riello 40 pump
How to bleed the pump on gravity (one-pipe) and lift (two-pipe) systems. - Riello 40 burner in lockout (red lamp on)
The 530 SE/C primary control locks out when it does not see flame after the oil valve opens. The lockout lamp is in the reset button. - Riello 40 F5 start-up settings on Ultra Oil boilers
Starting settings from the Weil-McLain set-up chart. Final set-up must be done with a combustion analyzer. - Riello 40 F5 will not run or air shutter will not close
The electronic air shutter runs on 120 V. The burner motor will not start until the shutter is fully open. - Riello 40 pump seal leaking or failed
The pump shaft seal is easy to damage by the wrong oil line set-up.
Rinnai (86)
- Air filter cleaning
Check the air filter for lint and dust. Clean with mild dish soap and a soft bristle brush. Replace the filter assembly if it is damaged. - Annual maintenance checklist
Yearly service checks for the boiler. Vent and screens, fan and motor, controller, pressure, relief valve, dirt trap, DHW filter, expansion tank, cond - Annual maintenance checks
Yearly service tasks for owner and licensed professional. - Basic DHW piping arrangement
The suggested arrangement shows the cold water supply, hot water supply, heating supply and return, and condensate drain. Some fittings are optional. - Boiler Does Not Start Heating With a Heating Demand
Heating demand is present but the boiler does not start CH. - Boiler filling, air purge and commissioning
Commissioning must be done by a licensed professional with calibrated instruments. Fill the heating side, check leaks, and deaerate before firing. The - Burner flame visual inspection
The flame must cover the burner surface and burn clear, blue and stable. A yellow or green flame is unsatisfactory. Check the flame through the view p - Cannot Change the DHW Set Point (Combi Only)
DHW set point cannot be changed during DHW production. - Cannot Set Up Lock
Lock function cannot be set. - Cannot Turn Off ECO Mode
ECO mode cannot be turned off. - Central heating common components
Parts the central heating loop needs around the boiler. Sizing and ratings are as listed in the manual. - Central heating return and supply connections
Connect the heating circuit to the two bottom connections of the boiler. Purge the system first, because debris and air in the lines will damage the b - Central heating works, no domestic hot water
On the Rinnai E50CRN, E75CRN, E75CRP, E110CRN and E110CRP boilers, central heating runs but there is no domestic hot water. Start with the settings an - CH Capacity Is Insufficient
Heating output is lower than expected. - Change parameter A2 to allow higher exhaust temperatures
Set A2 to b only for CPVC, listed PP or stainless steel venting. Do not do this with PVC. - Check burner flame appearance
A correct flame is visible through the sight window above the burner. A yellow flame means the burner needs maintenance. - Choose a vent termination location
Termination clearances for concentric and twin pipe venting. Exact clearances are in the vent clearance setting. Local codes and the gas supplier can - Choose a venting option (direct vent or non-direct vent)
Direct vent uses concentric pipe, where exhaust exits the inner pipe and combustion air enters the outer pipe, or twin pipe, with separate air and exh - Choose an installation location
Confirm the location meets clearances, air quality, water quality, electrical and vent length limits before mounting. - Combustion air requirements for confined and unconfined spaces
Sizing rules for combustion air openings based on the appliance Btu input. - Common vent spillage test when a boiler is removed
Required by ANSI Z21.13 when an existing boiler is taken off a common vent. The remaining appliances on the vent must be checked to confirm they still - Condensate drain installation
Rules for routing the condensate drain so it does not freeze, clog, or back up. Do not share the drain with the pressure relief valve or an AC evapora - Condensate drain line installation
The boiler has an integrated condensate trap and the drain must be installed to prevent damage and freezing. - Connect the condensate drain pipe
Threads the 1/2 in. NPT drain fitting onto the boiler and prepares for the pump safety wiring. - Convert the boiler from natural gas to propane
The boiler is set up for natural gas only from the factory. Conversion must be done by a qualified service agency using the conversion kit instruction - Crossover mode recirculation setup
Uses the cold water line for hot water recirculation. Requires a thermal bypass valve at the furthest fixture. - Decreasing or Fluctuating DHW Water Flow (Combi Only)
DHW flow volume drops or varies with no code. - Dedicated mode recirculation setup and flow
Used when the plumbing has a dedicated hot water return line. The boiler decides when the pump runs based on time intervals and DHW setpoint. - Descale the plate heat exchanger with vinegar and rinse
Vinegar flush for lime scale on the plate heat exchanger, followed by a rinse. Use undiluted food-grade white vinegar, about four gallons. Flush the b - DHW heat exchanger flush with vinegar
Flush the plate heat exchanger when the LC reminder shows or in hard water areas. Failure to flush can damage the plate heat exchanger. Lime damage is - DHW Recirculation Does Not Begin (Combi Only)
Recirculation pump does not start. - DHW temperature drops
On the Rinnai E50CRN, E75CRN, E75CRP, E110CRN and E110CRP boilers, hot water starts out fine and then fades during a draw. What I usually find is cros - Domestic hot water plumbing connections
DHW piping and components must be approved for potable water. Water connections must follow state and local plumbing codes. An approved pressure relie - Enable simultaneous central heating and domestic hot water
By default the boiler gives domestic hot water priority. Simultaneous operation divides flow between the DHW plate heat exchanger and the central heat - External pump and multi-thermostat zone wiring
Example wiring for an external pump and zoned thermostats on the PC board. Each thermostat connects to a T/T connection using C, R and W. The diagrams - First-time settings using Bluetooth (recommended)
Sets gas type and venting from a phone or tablet with the Rinnai Central app. The boiler is set for natural gas and PVC venting as default, so these m - Fluctuating DHW Outgoing Temperature (Combi Only)
DHW outlet temperature varies with no code. - Gas odor response
Safety instruction printed in the front matter. Applies to any gas smell near the boiler or in the building. - Gas supply connection and leak check
Gas connection must be done by a licensed professional. Confirm gas type and supply pressure before connecting. Convert the gas type with the included - Glycol antifreeze check
Use only glycol formulated for hydronic use with multi-metal inhibitors. Maximum allowed concentration is 40 percent. Test the fluid at least once a y - Heating system warms without a call
The radiators or baseboard feel warm or even hot while the thermostats aren't calling. Two things cause it most of the time: the pump is set to run co - Hot water works, no central heating
Rinnai E50CRN, E75CRN, E75CRP, E110CRN, E110CRP. Hot water fine, no space heating. Check the call for heat first, then the diverter. - Hydraulic separation and primary/secondary piping
Rinnai requires hydraulic separation between the boiler and the central heating system so that two or more circulators can run independently. - Install and wire a remote temperature controller
The MC-601 is an optional accessory bought separately. Its installation instructions come with it. - Install concentric vent pipe and termination
Concentric vent installation for the I-Series Plus. Follow the vent manufacturer's instructions and the termination diagrams in the manual. - Install the outdoor temperature sensor for outdoor reset
Mounts the outdoor sensor so the boiler can adjust supply temperature to outdoor conditions. Keep the sensor away from direct sun and artificial heat. - Installation completion checklist
Every item must be answered YES before installation is complete. Any NO means the installation is not finished. - Insufficient hot water quantity
Low DHW flow on a Rinnai E50CRN, E75CRN, E75CRP, E110CRN or E110CRP boiler. Hot water comes out, but not enough of it. Usually an install detail or sc - Manual CH plumbing flush and purge
Flush the heating system with approved cleaner before adding a new boiler when replacing an existing one. Clean the dirt trap, then purge the boiler a - Massachusetts requirements for side wall horizontal gas venting
For gas models sold in Massachusetts with a side wall horizontal vent terminal less than 7 ft above finished grade, including over decks and porches. - Monthly owner maintenance checks
Monthly checks for area, piping, venting and boiler condition. - Mount the boiler to the wall
Hang the wall bracket and boiler on a wall that can carry the full weight. - Nothing Happens When DHW Water Flow Is Activated (Combi Only)
No burner firing when hot water is drawn, with no code shown. - Outdoor vent cap not permitted
The RX Series outdoor vent cap is not approved for the I-Series Plus. The boiler may only be installed indoors with venting run to the outdoors. - Piping with refrigeration, air handler coils and multiple zones
Requirements for installations where the boiler is near cooling equipment or has several zone valves. - Power supply and grounding requirements
Power supply, grounding and disconnect rules for the boiler. The boiler needs 120 VAC, 60 Hz from a grounded circuit. Do not use extension cords or ad - Pre-power wiring checklist
Checks to finish before applying power to the boiler's terminals. - Pressure relief valve installation
The relief valve is required by ANSI Z21.13 and the ASME Boiler and Pressure Vessel Code. It must be accessible for service. An ASME 30 PSI valve is s - Program cascade communication and secondary IDs
Sets up the Primary boiler and assigns an ID to each secondary water heater in the cascade. - Pump lock check
The boiler runs a pump lock operation at least every 48 hours for all system pumps. A locked pump can be freed by hand. - Pump or Fan Runs With No Demand
Pump or fan runs even when there is no heat or DHW demand. - Radiators not hot enough or slow to heat
Radiators on a Rinnai E50CRN, E75CRN, E75CRP, E110CRN or E110CRP boiler are not getting hot enough, or take too long to warm up. Check settings before - Replacement gas valve assembly comes with a propane orifice
Service gas control assembly 806000089 for the I-Series Plus 175K and larger ships with the propane (LP) orifice installed. On a natural gas unit the - Room air combustion air vent installation
Installs the combustion air vent pipe and vent screen when the boiler draws room air. A room air screen is available as an accessory for dusty rooms. - Room air corrosive environment restrictions
Limits on using room air where combustion air contains acid-forming or corrosive chemicals. - Room air installation sequence
Install room air combustion air and exhaust with the room air screen, as required for the site. - Room air multiple boiler vertical termination
Exhaust termination spacing for room air installations with multiple boilers. - Room air vent piping configurations
Approved room air venting uses 2 in or 3 in Schedule 40 PVC/CPVC or ABS, or 4 in B-vent pipe. Flexible venting (PP flex or Ubbink) is only approved fo - Set up DHW recirculation through the PC board
Enables and configures the DHW recirculation function using the left PC board button. - Simultaneous DHW and CH Is Not Functional (Combi Only)
Boiler does not run DHW and CH at the same time. - Supply Temperature Differs From Controller Setting
Supply temperature does not match the controller set point. - Test the condensate pump safety switch
Confirms the boiler faults when the reservoir float closes the circuit and clears once the pump runs again. The switch is normally open and faults whe - Test the ignition safety shutoff device
Simulates a flame loss by disconnecting the flame rod. The boiler should lock out with code 110 after the last start-up attempt. - Testing a common vent when removing an existing boiler
Removing a boiler from a shared vent can leave that vent oversized for the appliances still connected. Use this check on the remaining appliances (ANS - Turn gas on or off to the appliance
The boiler has no pilot. It uses direct ignition and lights the burner automatically. The manual gas valve at the inlet is turned by hand only. - Twin pipe horizontal and vertical termination layout
Termination spacing for twin pipe vertical and sidewall terminations, as shown on the layout figures. - Twin pipe vent installation sequence
Connect the combustion air and exhaust pipes to the boiler using the supplied screws. Seal and seat each pipe properly. - Vent termination location rules
Terminations must be at least 12 in. above ground or the expected snow level. Keep them away from dryer vents, commercial cooking exhaust and air inle - Vent termination near an openable window or door (Canada, TB-200)
Rinnai bulletin TB-200 (10/2024) changed Reference B in the I-Series Plus termination clearance tables for Canadian installs to match CSA B149.1. Olde - Venting general guidelines
Direct vent or non-direct vent (room air) are both allowed. Non-direct vent must use Category IV vent of a type listed by a recognised testing agency. - Venting slope and pressure plane rules
Slope rules for horizontal venting and rules against mixing vent pressure planes or sharing pipes. - Water quality and snow check
Check water quality against the water quality guidelines. DHW must be potable and free of corrosive chemicals, sand and dirt. Damage from water qualit - Wire DHW recirculation pump
External recirculation pump connects to the Pump 4 terminal on the PC board when DHW recirculation is used. If four CH zone pumps are used, an externa - Wire the air handler output (OPU) to the boiler
Air handler call uses the boiler's OPU output on the zone 3 thermostat connections. - Wire the cascade cables
Connects the boiler and tankless water heaters with cascade cables for shared operation. - Wire the condensate pump safety switch
Wires the pump's normally open contacts into the boiler so the boiler shuts down if the pump fails. Wiring must follow local codes and NEC.
Viessmann (1767)
- "2" flashing and "Fault" shown on Vitotronic 300-K
A heating system fault is active. - "2" shown on Vitotronic 200 (fault)
A heating system fault is active. - "Central Control" shown on Vitotronic 300-K
Heating and holiday program settings come from the heating circuit set to central control. - "Controls Locked out" shown on Vitotronic 300-K
The function is disabled by a block set in the controls. - "External Hook-up" shown on Vitotronic 300-K
The heating program was changed by an external switching device. - "External Program" shown on Vitotronic 300-K
The heating program was changed by the Vitocom communication interface. - "Fault" is displayed
A heating system fault has been detected. The red fault indicator flashes on the control unit enclosure. - "Fault" shown on the display
The boiler shows a fault on the display. The manual's cause is a heating system fault. - "OFF" shown on Vitotronic 200
The heating program is switched off or the boiler is shut down by an external signal. - "Service" is displayed
A scheduled service is due. - "Service" shown on the display
The display shows "Service" because the service interval set by the heating contractor has come due. - 'Fault' flashing in the display
A heating system fault is present. - 'Fault' flashing in the display window
The Vitocontrol-S display shows 'Fault' flashing. - 'Without Function' appears in the display
A button was pressed that has no function on this system. - 'Without function' shown in the display
The button pressed has no function on this system. - 2 flashes and Fault is displayed
A heating system fault has occurred. - Access the burner and disconnect the burner control
Preparation steps before working on the burner. - Access the control electrical connections box
Opens the control box so external cables can be connected. - Access the control unit and external accessories box
Opening the connection box and control unit to reach the terminals and main PCB. - Access the control unit connections
Opening the external accessory connection box and the control console to reach the terminals. - Accessing the control electrical connections box
Steps to open the boiler so the control electrical connections can be reached for sensor and fuse checks. - Accessing the user interface programming unit
Covers protect the user interface programming unit and must be opened to reach it. - Accessory DIN terminal wiring
Accessory terminals are push-in type and must be opened before inserting or removing wire. - Accessory power supply and cabling
Accessory power is connected at the control and switched by the system on/off switch. The Vitotronic 200-H HK1B mixing valve control, the mixing valve - Acknowledge and clear maintenance display after service
Maintenance messages are cleared by acknowledging them and resetting the related counters and codings. - Acknowledged fault comes back
On the Vitodens 200-W B2HE (85, 120, 150, 199), a fault that was acknowledged but not actually fixed will come back. It is shown again the next day at - Activate boiler as last in the boiler sequence
A dry contact on plug aVD makes this boiler the last one to fire in the sequence. - Activating and ending comfort mode
Comfort mode heats the rooms to a set target outside the normal time program. The DHW is heated first if the contractor has not changed the settings, - Active messages is displayed
Shown when a service is due or a system fault is present. - Actuator test
Each actuator can be switched on separately to check it. Before an actuator is selected, all actuators are switched off. Tests run at the relay output - Actuator test procedure
Actuators are switched on one at a time from the service menu. The service level exits automatically after 30 minutes. - Adjust CO2 at full load (upper heating input)
Set CO2 at full load first, then check partial load. - Adjust CO2 at partial load (lower heating output)
Check and correct CO2 at lower heating output, then recheck full load. - Adjust heating curve slope and shift
Set the heating curve for each heating circuit to match the system type. - Adjust the adjustable high limit from 95°C to 100°C
The adjustable high limit ships at 95°C. It can be raised to 100°C (212°F) by breaking off cams on the stop dial. Note the coding address 06 setting a - Adjust the adjustable high limit to 100°C
Field change of the adjustable high limit from the factory 95°C to 100°C. - Adjust the adjustable high limit to 100°C / 212°F
The adjustable high limit leaves the factory at 95°C. The adjustable range is 75 to 100°C / 167 to 212°F. Note the setting of coding address 06 before - Adjust the fixed high limit to 99°C / 210°F
The fixed high limit leaves the factory at 110°C / 230°F. It is required to be set to 99°C / 210°F for the Vitocrossal 300. Once set to 99°C / 210°F i - Adjust the heating curve for a heating circuit
Set slope and shift so the supply temperature follows the outside temperature for the system type. Factory slope is 1.4 and shift is 0. Underfloor sys - Adjust the heating curve slope or shift
Changes heating characteristic when room temperature does not meet requirements over a prolonged period. Make changes gradually and observe results ov - Air vent and expansion tank
The air vent sits on top of the heat exchanger. The expansion tank is on the back housing and has a Schrader valve accessible from the bottom. - Alarm output (dry contact) activated
The control has a dry contact alarm output rated 24 VAC/DC, 1 FLA. It closes for any of the faults below and clears automatically when the fault is co - All indicators on the control panel are off
The panel has no power, or the manual high limit has tripped. - Allocating heating circuits to a remote control
Vitotrol 200A and Vitotrol 300A must be assigned to a heating circuit when commissioning. One heating circuit can be assigned to the Vitotrol 200A. Up - Alternative DHW tank connection (downstream of low-loss header)
Alternative DHW tank connection that applies to system layouts 2, 5, 6 and 8. The boiler control pump logic must be programmed in the service instruct - Annual cleaning of the boiler
The boiler must be cleaned at least once a year by a qualified heating contractor or service agency. The manual lists the wear parts used for cleaning - Annual heating contractor service
Service work to be done at least once a year by a qualified heating contractor. Any deficiencies must be corrected immediately. - Annual heating contractor service checklist
Annual service must be done by qualified personnel. Correct any deficiencies right away. - Annual heating technician checks
Service work the heating technician should complete at least once a year. - Annual heating technician service checks
Annual inspection and test list for the heating technician. Combustion test must be done by a qualified heating technician. - Annual maintenance before the heating season
Checklist from the maintenance record that a licensed heating contractor should complete before each heating season. - Annual maintenance checklist before the heating season
Items a licensed heating contractor must complete each year. - Annual service by heating contractor
Performed by a qualified heating contractor or service agency at least once a year. - Annual service by heating technician
Annual inspection and test items for a qualified heating technician. - Annual service checks by heating technician
Annual service and testing. Owner ensures the service is done at least yearly and corrects deficiencies right away. - Annual service: burner, combustion, venting and fuel checks
Annual checks of the burner, flue and gas or oil supply. The combustion test must be done by a qualified service technician. - Annual service: safety, controls and water system checks
Annual checks by the heating contractor covering high limits, low water cut-off, pressure relief, water quality and the door switch. - Antifreeze and corrosion protection
Sealed systems generally do not corrode if installed and run correctly. Chemical corrosion inhibitors must be approved for boilers with single-wall DH - Appliance or gas control has been under water
Do not operate the appliance if any part has been under water. The control system and any gas control that was under water must be replaced by a quali - Application 1 notes: high mass boiler, dry contact zone thermostat
Application 1 uses a high mass boiler with a single system loop, so primary/secondary piping is not needed. The zone thermostat must be a dry contact - Application 3: single fixed-setpoint zone with no pump output
Single-temperature zone. A thermostat call goes through the multi-zone control to the DE1 input of the EA1 boiler, which then runs a fixed zone setpoi - Application 3: single-temperature zoning with zone pumps and indirect DHW
Four-zone single-temperature system with an indirect water heater. A thermostat call energizes that zone's pump through the multi-zone control. The he - Application 4: two heat circuits, ZC1 low-temperature and air handler on HC2
Two circuits at different temperatures. ZC1 is a low-temperature circuit and the air handler is a mid/high-temperature circuit. A thermostatic mixing - Application 4: wiring and piping notes for air handler and radiant loop
Application CU3I 2ZC2ZP.01. The CU3A is a high-mass boiler, so primary/secondary piping is not required. A thermostatic mixing valve protects the radi - Application 4: ZC1 setpoint demand with ZC2 weather compensated
ZC1 is a low-temperature on/off circuit with an outdoor reset curve during a thermostat call. ZC2 (air handler) runs a fixed setpoint. A thermostatic - Application 5: how the low temperature and DHW circuits operate
The system has a low temperature circuit on a 3-way mixing valve, a high temperature zone ZC1 (or ZC2), and an indirect DHW tank controlled by an aqua - Application 5: low-temperature HC2 with 3-way mixing valve plus high-temperature ZC1
A low-temperature heat circuit uses a 3-way mixing valve and a high-temperature zone circuit ZC1. Space heating and DHW can run at the same time, so s - Application 5: radiant loop, DHW tank and boiler sizing notes
Application CU3I 3HC/Z3ZP.01 with HC2, ZC1 and ZC2 circuits and an indirect DHW tank. A thermostatic mixing valve may be needed on the radiant loop wh - Application example 1: one direct-connected heating circuit without mixing valve
Boiler controlled by Vitotronic 200 with one heating circuit that has no mixing valve. Optional domestic hot water tank. Single-stage burner is standa - Application Example 5 system layout
One direct-connected boiler circuit without a mixing valve, plus two mixing-valve heating circuits, with a DHW tank. The Vitotronic 300 runs the boile - Application suitability for Vitocrossal 300 CU3A
The recommendation matrix rates the Vitocrossal 300 CU3A against emitter types: baseboard or fan coil, cast iron radiator, panel radiator, radiant flo - Apply strain relief to external cables
Use the strain relief method that matches the cable type. - Assembling the boiler base
Steps to set up the base and crossbar before fitting the cast iron sections. - Assembling the cast iron sections
Disassembly and reassembly steps for boilers shipped in individual sections. Skip the disassembly steps if the boiler arrives assembled. - AUX 0-10 VDC input wiring
The 0-10 VDC input lets a BMS set the common supply set point. The control runs to the higher of this set point and the outdoor reset set point. - AUX heat demand input wiring
The AUX input takes a potential-free dry contact. Closing the contact requests heat at a fixed set point. It can be used with outdoor reset or on its - Avoiding contaminated combustion air
Chemicals and dust in the boiler room can produce poisonous byproducts in combustion and damage the boiler. Areas like new construction, garages with - Barometric draft regulator placement
The regulator must be placed in the vent close to the boiler breeching outlet. - Before contacting the heating contractor for shutdown planning
Gather boiler and control details so the contractor can set up frost protection and pressure correctly. - Bleed air from boiler heat exchanger
Purge air from the boiler heat exchanger by flushing it through the boiler supply and return with isolation valves closed. - Bleed air from the boiler heat exchanger
Vent the heat exchanger on the boiler side. Do not use the heating side pressure relief valve for this, as it can damage the equipment. - Bleed air from the heating system
Vent the heating system with the gas shut off and the control unit on. - Blinking circulating pump indicator (low flow)
A blinking pump indicator means flow is too low or absent, and the heating elements are off. - Blinking heating status indicator
A blinking heating status means the boiler is held back by a control input or a temperature limit. - Block a lag boiler externally (aVD plug)
Use the aVD plug to take a boiler out of the sequence from outside the control. Only applies to lag boilers. - Blower not at stand-still before a call for heat
On a call for heat the blower must read below 300 rpm within 51 seconds. Otherwise the start-up sequence cannot begin. - Boiler activation contact for external modulation controller
Wiring and behaviour of the boiler activation dry contact on plug aVH (Vitocrossal 300, CT3). - Boiler and DHW tank maintenance intervals
Routine owner-level maintenance intervals as printed in the manual. - Boiler and DHW tank sensor connection
The boiler sensor is installed with the boiler insulation. The DHW tank sensor is used only on systems with domestic hot water heating and must not be - Boiler cleaning and efficiency check
Contamination raises flue gas temperature and energy loss, so the boiler must be cleaned at set intervals. - Boiler cleaning and efficiency loss from contamination
Boilers must be cleaned at set intervals. As contamination builds up, flue gas temperature and energy loss rise. A high flue gas temperature can also - Boiler cleaning and flue gas check
Rising flue gas temperature shows contamination or poor burner adjustment and reduces efficiency. A flue gas temperature sensor (accessory) can monito - Boiler connection points overview
Connections are heating supply and return (BS and BR), fill and drain (BF and BD), gas connection (GC), pressure relief valve (PRV), and DHW connectio - Boiler control housing and enclosure installation
Mount the boiler control housing on the side panel, route the capillaries and boiler sensor, then close up the enclosure panels. - Boiler control housing installation
Mount the control housing on the side panel and route capillaries and the boiler sensor away from heat sources. Electrical connections are covered in - Boiler control is not active (green power LED off)
The control shows no power indication. - Boiler control not active (green power LED off)
The control shows no power. Check the power switch first, then the supply to the control, then the control fuse. - Boiler control power supply, 120 VAC 1 PH
Main supply to the control. Overcurrent protection and disconnect must follow local codes. The control must be grounded. - Boiler control power supply, 120 VAC single-phase (VD2/VD2A/CT3)
Supply the control through a disconnect and overcurrent protection. The main supply must have overcurrent protection rated at most 15 A and a 2-pole d - Boiler disable external control
A dry contact on the plug aVD takes the boiler out of the boiler sequence. - Boiler does not fire although the control calls for heat
The Versatronik 300 can demand the exhaust or damper device without the boilers firing. If the boiler water temperature is already above its actual op - Boiler does not start up
No burner start and no heat from the boiler. - Boiler does not start up (multi-boiler)
The boiler in a multi-boiler system does not start. - Boiler has been under or exposed to water
Do not run the boiler after any part has been under or exposed to water. The control system and any gas control that was wetted must be replaced. - Boiler hot but heating circuit pumps not running
Check whether the pump is being called on, then check voltage and fuses. - Boiler hydrostatic pressure test
The boiler must be leak tested and hydrostatically pressure tested before connection to piping or power. Test pressure is between 110 and 120 psig (68 - Boiler in heating/cooling application
When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler using valves that keep chilled mediu - Boiler in heating/cooling application with chiller
When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler. Valves must stop chilled water from - Boiler location and direct vent clearances
The boiler is direct vent and can be installed for room-air independent (sealed combustion) operation regardless of room size or ventilation. It can g - Boiler location, venting and flue temperature
The CU3A is a direct vent appliance and can be sealed-combustion in any room size or ventilation type. It can go in living areas, unventilated utility - Boiler maintenance requirements
Keep the boiler and room clear and have it cleaned at least once a year by a qualified heating technician. - Boiler not firing
The boiler does not fire. The manual points the technician to the boiler for the main diagnosis. - Boiler off during freezing weather
The boiler is not designed to protect water pipes from freezing. Safety devices can shut it down, so pipes may freeze if the building is left unattend - Boiler or controls have been under water
Caution for a boiler that has been submerged or flooded. - Boiler piped into a heating/cooling system with chiller
When the boiler is used with a chiller, the chilled water must be piped in parallel with the boiler using valves, so chilled water cannot enter the bo - Boiler pressure test before connecting piping and power
Leak and hydrostatic test on the installed boiler with supply and return headers in place. The boiler must pass before it is connected to piping or po - Boiler pump runs continuously after changing to multi-boiler operation
When switched from single boiler to multi-boiler operation, coding address 30:0 may reset to 30:3, causing the boiler pump to run continuously. - Boiler pump runs continuously after multi-boiler change
When a Vitodens 200 B2HB goes from single to multi-boiler operation, coding address 30:0 can reset to 30:3, which keeps the boiler pump running contin - Boiler room conditions
The room must be free of halogenated hydrocarbons from aerosols, paints, solvents and cleaning agents, free of high dust levels, and not permanently h - Boiler section status circle and flame display
The programming unit shows each boiler section with a circle and a flame. The circle shows whether the section is enabled, available or unavailable, a - Boiler sequence and ECO thresholds
The control picks boiler sequence from the cascade codes and internal calculations. ECO thresholds can block or enable each boiler based on outside te - Boiler short-cycling from undersized pump or piping
Short-cycling and poor DHW supply can come from an undersized field-supplied pump or undersized piping. Pump sizing matters most in mixing-valve layou - Boiler short-cycling or inadequate DHW supply
Likely caused by DHW piping that is too small or by a DHW coil whose pressure drop is too high for the boiler pump head. - Boiler temperature control sequence
The boiler water temperature is controlled by a two-stage or modulating burner. The set point comes from Vitocontrol-S. Three sensors monitor the boil - Boiler temperature tripped the fixed high limit (F2)
Shown when the boiler water temperature reaches the fixed high limit setting of 210°F (99°C) during a test or fault. This is a manual reset limit. - Boiler venting route
The boiler comes with a pre-installed vent adaptor. The venting may be single-wall or coaxial and must be routed through a side wall or roof. - Boiler was under or exposed to water
Do not run a boiler that has been under or exposed to water. The control system and gas control that were wet must be replaced. - Boiler water temperature control
Burner modulates to hold the set boiler water temperature. The setpoint is the highest demand from heating circuits, LON, external demand, or DHW. - Boiler water temperature sensor resistance (3A and 3B)
Sensor 3A is an NTC 10 k-ohm sensor on terminals 1 and 2. Sensor 3B is an NTC 20 k-ohm sensor on terminals 3 and 4. The temperature versus resistance - Boiler water temperature too high or too low
Check whether the setpoint is wrong or whether the temperature measurement is at fault. - Boiler water too hot in transitional seasons but fine in cold weather
The heating curve is too steep for mild weather. Adjust the curve so the boiler water temperature drops in spring and autumn while the cold-season per - Boiler will not reset after F2 fault shutdown
If the burner control unit will not reset after a fault shutdown (F2) even though boiler water is below about 203°F (95°C), check the fixed high limit - Boiler with remote low water cut-off
A remote-mounted low water cut-off, supplied by the field, may be required by local codes. Do not install an isolation valve between the boiler and th - Boilers not communicating or not staging
Boiler communication depends on unique LON addresses. A boiler that does not appear to be communicating is started last. - Brief scan (short query) overview
The short query shows 11 lines and 6 fields with system identification, KM BUS participants, software versions, remote control type, LON and heating c - Brief scan line contents
Each brief scan line shows system details. Fields 1 to 6 are read left to right. - Brief scan overview
The brief scan shows an overview of 11 lines and 6 fields with software versions, CU-ID, KM BUS participant count, connected plug status (contact open - Burner adjustment and CO check
Carbon monoxide build-up from incorrect burner adjustment is a serious health risk. A CO test is required before and after any work on the gas applian - Burner calibration and combustion analysis
Verify factory burner settings at the final site with calibrated combustion equipment and adjust for local conditions. - Burner connection and burner control wiring (CM2, plug-in burner)
For burners with plug-in connection. Burner cables come with the Vitotronic. Connect the burner per local codes. Terminal 1 is the phase from the fixe - Burner connection with plug-in cables (CM2)
The burner cables come with the Vitotronic. Terminal codes: L1 is phase via the fixed high limit to the burner; N is neutral to the burner; T1 and T2 - Burner control unit fault lamp on after start-up
The fault lamp on the control unit lights and the display on the burner control unit blinks. This is usually a reset issue. If the fault returns, the - Burner control via eBUS does not respond
The controller communicates with the burner control unit (FA) over eBUS, connected at the FA eBUS terminals. The controller sends a heat request and t - Burner control wiring (generic drawing)
Generic connection drawing for the control unit to the burner. It is not the actual connection for a specific burner, so the burner manufacturer's Vie - Burner control wiring with generic drawing
The generic drawing is not a wiring diagram for a specific burner. Write terminal numbers on the drawing for reference. Burner power supply is not sho - Burner control wiring with plug-in connection, CM2
Same plug-in wiring method as the VD2/VD2A/CT3 layout. Burner cables come with the Vitotronic, and the burner side connects to a burner interface. - Burner control wiring with plug-in connection, VD2/VD2A/CT3
Burner cables come with the Vitotronic. Connections are made to the counter plugs and to the burner, following applicable codes. The burner control ci - Burner does not respond due to accessory defect
A connected accessory is preventing burner operation. - Burner does not respond with power venter fitted
Control calls for heat but the burner does not respond when a power venter is used. - Burner does not start and red fault indicators are on
The control unit fault indicator flashes and the red fault lamp is lit on the burner after a faulty start. - Burner does not start or starts intermittently (red fault LED flashes)
The burner does not light, or it cycles on and off with the red fault LED flashing. - Burner does not start or starts intermittently (red fault LED flashing)
Burner fault LED flashes and the burner starts and stops. - Burner does not start, red fault indicator flashes
Faulty burner start. Red fault indicator flashes on the control unit and the red fault lamp is lit on the burner. - Burner does not start, red fault indicator flashing (faulty start)
Red fault indicator flashes on the control unit and the red fault lamp is lit on the burner. - Burner does not start, red fault lamp on burner and control unit flashing (multi-boiler)
The burner fails to start after a faulty start attempt. The red fault indicator on the control unit flashes and the red fault lamp on the burner is li - Burner does not start, red fault lamp on control unit and burner lit
The burner has a faulty start. The red fault indicator flashes on the control unit and the red fault lamp is on at the burner. - Burner does not switch off at the correct time
Burner keeps running past the programmed heating time. - Burner does not switch on
Burner does not light even though the boiler is requested. - Burner does not switch on (multi-boiler)
Boiler is requested but the burner does not fire. - Burner does not switch on (single-boiler)
Boiler is running but the burner does not fire. - Burner does not switch on (Vitotronic 100, GC1)
The boiler burner stays off. Check the heating program first, then the draught device and flue damper. - Burner does not switch on or only switches on erratically
The burner does not light or cycles unpredictably. - Burner fault is displayed
The display shows Burner fault and gives prompts to follow. - Burner fault: burner control unit locked out
The display shows that the burner control unit is locked out. Ignoring the message keeps the burner locked out, so the fault must be read and reported - Burner faults without a specific message
Burner output fluctuates or the burner faults without showing a code. The usual cause is incorrect air setting. - Burner harness and cable strap routing
Secure the burner harness to the side panel with the supplied cable straps. Leave no slack so the burner door can swing open without unplugging the ha - Burner heat demand wiring
Terminals 29 and 30 call for heat from stage 1. Terminals 32 and 33 call for stage 2 of a 2-stage boiler, or the second boiler in a lead-lag setup. Bo - Burner lock-out after failed ignition
If the flame is not established after 3 ignition trials, the burner locks out and needs a manual reset. - Burner lock-out with blocked vent safety switch
If the burner locks out, check the blocked vent safety switch operation first. - Burner lockout with Beckett GeniSys control
Burner lockout on the Beckett NX burner with GeniSys control. - Burner locks out after 3 ignition trials
If no flame is established after 3 ignition trials, the flame safeguard locks out the burner and it must be reset manually. - Burner motor power supply, 120 VAC 1-phase in conduit
Power the burner motor from 120 VAC single phase using the factory-supplied cable and conduit. - Burner motor power supply, 120 VAC 1-phase with plug-in cable
Power the burner motor from 120 VAC single phase using the factory-supplied soft cable with plug. - Burner motor power supply, 240 VAC 1 PH
For burners with 240 VAC single-phase supply and conduit connection. Fuse and wire sizing come from the burner manual. - Burner motor power supply, 240 VAC 1-phase
For burners with a 240 VAC single-phase motor supply run in conduit. Use the burner manual for correct fuse and wire sizing and for connections to Vie - Burner motor power supply, 240 VAC 1-phase in conduit
Power the burner motor from 240 VAC single phase using the factory-supplied cable and conduit. - Burner motor power supply, 240 VAC 1PH (VD2/VD2A/CT3)
Wiring of the burner motor when the burner runs on 240 VAC single-phase power through a conduit connection. - Burner motor power supply, 240 VAC single-phase (VD2/VD2A/CT3)
For burners fed with 240 VAC 1-phase power run in conduit. Use the burner manual for correct fuse and wire gauge sizing and for the connections specif - Burner motor power supply, 3 PH 208, 460 or 575 V
For burners with three-phase supply at 208, 460 or 575 V. Fuse and wire sizing come from the burner manual. - Burner motor power supply, 3-phase 208, 460 or 575 V
Power the burner motor from a 3-phase supply. The motor rotation must be checked during commissioning. - Burner motor power supply, 3-phase 208, 460 or 575 V (VD2/VD2A/CT3)
For burners fed with 3-phase power at 208, 460 or 575 V. Use the burner manual for fuse and wire sizing and the Viessmann-specific connections. - Burner motor power supply, 3PH 208/460/575 V (VD2/VD2A/CT3)
Wiring of the burner motor for three-phase burners at 208, 460 or 575 V, including the rotation check. - Burner mounting on the combustion chamber door
Mount the burner with the spacer bolts, gasket and nuts supplied. Use the insertion length table on page 41 for the correct air tube depth. - Burner not running and boiler cold (no fault shown on display)
Fault behaviour with no code on the programming unit. Work through the cases by what the display and pumps are doing. - Burner reassembly and CO2 check after cleaning
Tighten fasteners to specified torque and check gas tightness before starting. Leak detection spray can cause faulty operation. - Burner reassembly and final CO2 check
Reassemble the burner and confirm combustion and gas tightness after dismantling. - Burner reassembly and final combustion check
Reassembly torques and the required combustion check after burner work. - Burner running but no hot water (DHW tank)
Applies only to systems with a domestic hot water tank. - Burner runs but no domestic hot water (DHW tank systems)
Systems with a DHW tank show burner operation but no hot water. - Burner selection and fuel requirements
The burner must be ordered for the specific fuel, and only approved oil or gas burner types may be used. The boiler must run with positive pressure in - Burner service: start-up after work
Checks to complete after burner service before the boiler goes back into operation. Avoid leak spray on electrical contacts because it can cause a mal - Burner shuts off below set-point and restarts repeatedly (cycling)
Burner switches off while boiler water is still below the set-point and then restarts again. - Burner start-up safety precautions
Safety rules to follow before and during burner start-up and calibration. - Burner will not switch on
Burner does not start on a heat demand. - Burners run but no domestic hot water
Applies to systems with a DHW tank. - Bus communication problems
Controller and bus devices do not communicate correctly. - Calculate the heating curve slope
Slope = (design supply temperature - WWSD temperature) divided by (WWSD temperature - design outdoor temperature). Worked example from the manual: des - Calibrate the burner and perform combustion analysis
Verify factory settings and adjust for local conditions using calibrated equipment. - Calibrate the burner with combustion analysis
Measure at the final site with calibrated equipment and adjust the burner to local conditions. - Carry out a LON participant check
The participant check tests communication between the fault manager and the devices connected to it. - Cascade control: set supply temperature and control types
The cascade regulates the supply temperature by starting or stopping burners or burner stages. The set supply temperature comes from the heating circu - Cascade strategy: gross calorific (coding 3C: 0)
Operates as many boilers as possible at the lowest output for the best condensing effect. Gives long burner run times. Boilers are started by output s - Cascade strategy: net calorific 1 (coding 3C: 1)
Conventional boilers run at their upper output range to prevent condensate from low return temperatures. Fewest boilers are active. - Cascade strategy: net calorific 2
An extra boiler starts only when all active burners at maximum output cannot reach the set supply temperature. A boiler shuts down when its burner is - Cast iron section assembly
Field assembly of a boiler shipped in separate sections. Only needed when the boiler arrives in individual sections. Hardware is in the accessory pack - Category I venting requirements (natural gas or propane)
Category I venting is the standard option for this boiler on gas. Use Type B or Type L vent for the whole run where possible. B-vent is not allowed on - Category III positive pressure venting (Vitorond 200)
The Vitorond 200 is a Category III positive pressure non-condensing boiler. Each boiler must have its own vent. The chimney must be gas tight. - Central fault message output wiring
The central fault message output is rated 120VAC, max 2 A. - Change filter in combustion air filter box (room air independent operation)
Change the filter in the combustion air filter box for room air independent operation. After installing the new filter with the filter monitoring kit, - Change heating curve slope and level
Sets the heating curve slope or level in the extended menu to match the system requirements. - Change heating curve slope and shift
Slope changes the steepness of the curve. Shift moves the curve up or down in parallel. - Change heating curve slope or shift
Slope and shift are adjusted per heating circuit in the extended menu. - Change mixing valve motor rotation and set valve manually
Reverse the motor rotation if the valve moves the wrong way, or set the valve by hand. - Change normal room temperature (day)
Sets the daytime room temperature for the heating circuit. - Change or delete a DHW time phase
Edit changes the start or end time of an existing phase. Delete removes a phase entirely. On the B1KE, deleting all time phases switches off the DHW c - Change or scan the space heating time program
Set the on and off times for space heating phases. Scanning shows the preset phases without changing them. - Change reduced room temperature (night)
Sets the night-time room temperature. A value of 3°C / 37°F makes the display show freeze-up protection. - Change rotational direction of mixing valve motor
Set the motor's rotation direction to suit the piping layout. The motor is delivered wired for the standard examples, so only change the wiring if the - Change the adjustable high limit
Factory setting is 95 °C / 203 °F. Limit range is set by breaking off stop cams on the selector dial. Range A gives 75 to 195 °C (167 to 203 °F), rang - Change the domestic hot water temperature
Sets the DHW temperature on the control. Not possible if DHW comes from a central DHW tank. - Change the heating curve slope or shift
Adjust the heating curve from the programming unit. Use slope for the overall steepness of the curve and shift to raise or lower it. Check the change - Changeover contact 66 for fault output or external boiler demand
Contact 66 can report a fault or request heat from an external boiler. With supplemental enabled, it closes when full-load operation fails to reach se - Changing a time phase start point
Change one time phase on a given day without rebuilding the program. - Changing heating times F1 and F2 on Lago FB
Set the heating periods for each heating program on the remote. - Changing slope and level of the heating curve
Slope changes how strongly the flow temperature responds to outside temperature. Shift moves the whole curve up or down. Watch the effect over several - Changing the display language
English is the factory language. The display shows the outside temperature first while scanning. - Changing the heating curve slope and shift
Slope and shift are set separately for each heating circuit from the control unit display. - Changing the mixing valve motor rotation direction
Reverses the open and closed direction of the mixing valve motor. - Changing the rotation direction of the mixing valve motor
Only do this if the rotation direction is wrong. Disconnect main power before opening the boiler. - Check a service message
When service is due, the display shows a service symbol and the word Service. If several fault messages are active, a Service messages option appears. - Check all water connections for leaks
Required at commissioning and after any maintenance work on the heating water or DHW side. - Check an NTC 10 kΩ sensor (outside, supply, DHW, return)
Check a Viessmann NTC 10 kΩ sensor against the resistance curve. The temperature-resistance table values are not legible in the extracted text. - Check and adjust CO2 at lower heating output
Set the boiler to low fire and adjust CO2 with the lower-output screw. Recheck both points after any change. - Check and adjust CO2 at upper heating input
Set the boiler to full load and adjust CO2 with the gas valve adjusting screw. - Check and adjust ignition and ionization electrodes
Electrode type depends on size: C is up to 35 kW (125 MBH), D is from 45 kW (160 MBH). - Check and clean condensate trap and drain
A blocked condensate drain makes condensate build up in the bottom of the boiler and causes a burner shut-down with a fault message. - Check and clean ignition and ionisation electrodes
Check electrode wear, contamination and clearances. - Check and clean ignition and ionization electrodes
Check electrodes for wear and contamination, clean them and check the gaps. - Check and clean the burner tube
Cleaning or replacing the burner gauze and gaskets. Keep insulation fibres out of the combustion chamber. - Check and clean the burner tube and gauze
Clean or replace the burner gauze and check the insulation ring. Use new gaskets on reassembly. - Check and replace burner refractory and cylinder burner
Inspect the refractory ring and cylinder burner assembly. - Check and replace burner refractory ring and cylinder burner
Inspect the burner refractory ring and cylinder burner assembly for damage. Replace if damaged. - Check and replace burner refractory, cylinder burner and fan flapper
Inspect the burner refractory and cylinder burner, and clean or replace the flue gas flapper. - Check and service the neutralisation unit (if fitted)
Applies when a neutralisation unit accessory is installed. The granulate is used up as it neutralises the condensate. - Check boiler room air supply and barometric draft regulator
Confirm combustion air and draft control work during operation. - Check boiler temperature sensor and fixed high limit
Boiler water temperature sensor and fixed high limit. Drain the boiler before replacing the sensor because the sensor sits in hot heating water. - Check boiler water temperature sensor
Measure the boiler sensor resistance and compare it with the current boiler water temperature. - Check boiler water temperature sensor, DHW tank sensor or supply/low-loss header sensor
Check sensor resistance and compare with the curve. Sensor type is NTC 10 kΩ. Only one supply temperature sensor or low-loss header sensor may be used - Check boiler water, DHW or flow temperature sensor
Sensors are NTC 10 kΩ. Compare measured resistance with the curve and replace the sensor if the deviation is severe. - Check boiler, DHW tank and flow or low-loss header temperature sensors
Check the resistance of these NTC 10 kOhm sensors and compare it with the temperature curve. Drain the boiler before replacing the boiler temperature - Check boiler, DHW tank or supply/low-loss header temperature sensor
Test the NTC 10 kΩ sensors by measuring resistance and comparing it with the sensor curve. Drain the boiler before replacing the boiler temperature se - Check boiler, DHW tank, flow and low-loss header temperature sensors
Sensor type is NTC 10 kΩ. Compare measured resistance with the curve (curve not reproduced in this extract). Drain the boiler before replacing the boi - Check burner door gasket and burner gauze assembly
Replace the burner gauze and gasket if damaged. - Check burner flue gas flapper
Inspect the flapper and its gasket for dirt and damage. - Check burner refractory ring and cylinder burner
Check the burner refractory ring and cylinder burner assembly for damage and replace if needed. - Check burner refractory, cylinder burner and flue gas flapper
Inspection and replacement of the burner refractory, cylinder burner assembly and flue gas flapper. - Check CO2 and O2 at low and high fire
Run the boiler in actuator test at low fire and high fire and check the combustion readings at each. - Check CO2 and O2 at start-up and service
The burner is factory set for natural gas and needs no adjustment. Only check CO2 and O2 at the vent adaptor. - Check CO2 and O2 at the boiler vent using the actuator test
Used at initial start-up and maintenance. The burner is forced to the lower and upper outputs so the flue readings can be checked at each. - Check CO2 setting at low and high fire
Verify combustion by measuring CO2 and O2 at low fire and high fire using the actuator test. - Check coaxial venting for leaks
Simplified leak test by measuring CO2 or O2 in the combustion air in the coaxial gap of the air intake pipe. - Check coaxial venting for leaks (air gap measurement)
Simplified leak test by measuring combustion air in the coaxial gap of the air intake pipe. - Check combustion air openings and intake
For room air operation, check the filter and the combustion air openings. For room air independent direct vent operation, also check the combustion ai - Check combustion air supply and barometric draft regulator
Confirm the boiler room has adequate combustion air and the draft regulator moves freely. - Check combustion air supply and vent system
Confirm enough combustion and ventilation air reaches the boiler and that the venting and draft regulator are working. - Check combustion air, venting and draft devices
Make sure the boiler has enough combustion air and the vent works properly. - Check combustion quality
Measure the CO2 or O2 content of the flue gas, then use the air factor table to find the air factor. The result should fall within λ 1.24 to 1.44. - Check condensate drain and clean condensate trap
Condensate must drain freely. If it does not, it builds up in the bottom of the boiler and causes a burner shut-down fault. - Check condensate drain and neutralizing unit
If condensate does not drain, it builds up in the boiler and the burner shuts down with a fault message. - Check condensate drain and trap
Keeps condensate draining freely to avoid a burner shutdown. - Check condensate neutralization unit
Check the condensate pH and refill the neutralization granulate. Field-supplied pH measuring strip required. - Check connections and safety devices
Confirm the heating and domestic hot water connections are tight and safety devices work. - Check connections for leaks and perform combustion analysis
Confirm all heating and domestic hot water connections are pressure tight, then record combustion values. - Check control unit fuse F1
Fuse F1 on the boiler control unit, checked with the power off. - Check control unit fuse F4
Check the fuse on the control unit. - Check control unit fuses
Check fuse F1 on the control unit and fuses F1 and F2 in the external accessories connection box. - Check cylinder burner assembly
Inspect the cylinder burner mesh and replace the assembly if damaged. - Check DHW tank temperature sensor
Measure the DHW sensor resistance and compare it with the current DHW temperature. - Check diaphragm expansion tank and system pressure
Perform with the system cold. - Check direct vent (coaxial) system tightness
Simplified leak test during start-up, measuring air in the coaxial gap of the air intake adaptor. - Check electrical connections
Confirm plug-in connectors and strain reliefs are seated properly. - Check expansion tank and system pressure
Check the diaphragm expansion tank pressure against the static water fill pressure on a cold system. - Check expansion tank and system water pressure
Check the cold-system fill pressure, the diaphragm expansion tank pre-charge and the safety header. Do all checks on a cold system. - Check expansion tank, low water cut-off and pumps
Confirm water system components are working and the system is charged. - Check expansion vessel pre-charge and system pressure
Carry out this check on a cold system and follow the expansion vessel manufacturer's instructions. Permissible operating pressure is 80 psi (5.5 bar). - Check fixed high limit
Check the fixed high limit if the burner control cannot be reset after a fault shutdown, although the boiler water temperature is below approx. 167°F - Check flue gas collector and boiler body for leakage
Flue gas leaks must be ruled out during commissioning at full load. Gaskets can be checked with a dew point hygrometer. Condensed water on the outside - Check flue gas collector seals, lip seal and insulation
Look for leaks at the flue gas collector and the boiler flue connection. Condensate on the outside of the collector also indicates a leak. - Check flue gas flapper
Check the flue gas flapper and its gasket for dirt and damage. - Check flue gas temperature sensor
Measure the flue gas sensor resistance and compare it with the flue gas temperature. - Check flue side for leaks
Check the flue gas collector, boiler body and gaskets for leaks. Use a dew point hygrometer at full load. Condensed water on the outside of the flue g - Check flue side gaskets and seals
Check the flue gas collector seal to the boiler. Leaks show as condensate on the outside of the collector. - Check fuse F1
Procedure to check the 120 V control fuse F1 in the junction box. - Check fuses (control unit and external accessories box)
Use this to check the control unit fuse and the fuses in the external accessories connection box. - Check fuses in external accessories connection box
Fuses F1 and F2 in the external accessories connection box. - Check fuses on the control unit and external accessories box
Use this to check the control unit fuse and the fuses in the external accessories connection box. - Check gas connections for leaks
Check all gas fittings with a certified leak detection fluid. Do not let spray touch electrical parts. - Check gas pipes and fittings for leaks
Gas supply must be leak tested before the boiler is put into operation. - Check gas side connections for leaks
Use new gaskets on all gas fittings separated on site. Do not use leak detection spray near electrical contacts, as it can cause faulty operation. - Check gaskets, sealant rope and combustion chamber door refractory
Look for worn or damaged seals and insulation at the chamber door. - Check gaskets, sealant rope and refractory
Inspect the combustion chamber door seal and insulation. - Check gaskets, sealant ropes and door insulation
Replace any worn items found during the check. - Check gaskets, seals and insulation
Look for damage that could cause leaks or heat loss. - Check heating control, mixing valve and low temperature protection
Check that the control, mixing valve motor and low temperature protection package work correctly. - Check heating system, safety devices and water side
Routine checks of pressure, relief valve, expansion tank, low water cut-off and pumps. - Check heating water side connections for leaks
Check all heating water connections, including control equipment and the minimum pressure monitor (low-water cutoff). Open heating water connections o - Check ignition and ionization electrodes
Check gap and condition relative to the cylinder burner. - Check mixing valve and gas line for leaks
Check the gas mixing valve for smooth operation and leaks. Gas joints must be pressure tight at normal operating pressure. - Check mixing valve extension kit rotation and direction
The boiler runs a self-test after power-up in which the mixing valve opens and closes again. The flow sensor must read higher when the valve is opened - Check mixing valve for ease of operation and leaks
Check the mixing valve handle for smooth movement and for leaks. Replace the O-ring seals if the mixer leaks. - Check mixing valve motor rotation direction
After power-up the boiler runs a self-test that opens and closes the mixing valve. Then the valve is set manually to Open to confirm the flow temperat - Check mixing valve motor rotation for extension kit
The boiler runs a self-test on power-up that opens and closes the mixing valve. If the flow temperature drops when the valve should open, the motor ru - Check neutralization unit
The granulate is used up as it neutralizes the condensate. The red mark shows the minimum fill level. A field-supplied pH strip is needed. - Check neutralization unit (if fitted)
Granulate is consumed as it neutralizes the condensate. The red mark shows the minimum fill level. A field-supplied pH strip is required. - Check neutralization unit condensate pH
Only applies where a neutralization unit is installed. The granulate is used up as it neutralizes the condensate. - Check neutralizing system flow with burner removed
With the burner removed, pour water into the combustion chamber. Water must drain freely from the condensate drain pipe without backing up. - Check oil door safety switch (oil burners only)
The door safety switch must be checked on oil-fired boilers. - Check on-site gas connections for leakage
Gas connections are checked during commissioning after the new gaskets are installed and before the boiler is put into operation. Check at the gauge c - Check or change rotational direction of mixing valve motor
After power-up the boiler runs a self-test that opens and closes the mixing valve. If the flow temperature drops when the valve is opened, the motor d - Check or replace the plate type heat exchanger (CombiPLUS)
Check the DHW side for scale and the heating water side for contamination. Clean or replace the plate type heat exchanger as needed. - Check outdoor temperature sensor
Test the outdoor sensor resistance and compare it with the actual outdoor temperature. - Check outdoor temperature sensor (NTC)
Test the outdoor sensor across plug terminals 1 and 2 and compare the result with the NTC curve. If the reading is far off, test the sensor again with - Check outlet temperature sensor (CombiPLUS)
Check the DHW outlet temperature sensor resistance against the curve in the manual. The curve did not come through legibly in the extract. - Check outputs (relay test) and sensors
Use the relay test to energise outputs one at a time, and use the scan function to read sensor temperatures. - Check outside temperature sensor
Resistance check of the outside temperature sensor and its lead. The lead is 2-wire, up to 115 ft (35 m), 16 AWG (1.5 mm2). - Check power pump module fuse F1
Check the fuse on the power pump module. - Check primary and secondary circuit connections for leaks
Check heating system and domestic hot water connections where applicable. - Check return temperature sensor
Strap-on or immersion sensor for boiler return temperature. Plugs into socket 17A or 17B. - Check room temperature sensor
Test the separate room temperature sensor used when the remote control cannot be mounted in a suitable place. - Check room temperature sensor (Part No. 7133 379)
Measure the sensor resistance at its terminals and compare it with the current room temperature. Scan the current room temperature on the control firs - Check rotational direction of mixing valve motor (extension kit)
The boiler runs a self-test at power-up, during which the mixing valve opens and closes. If the flow temperature drops when the valve is opened, the m - Check running supply pressure (NG or LPG)
Measure supply pressure with the burner at maximum output. Use a gauge with at least 0.04 in w.c. resolution. Do not open any flame near the boiler. - Check safety valves, low water cut-off and pumps
Routine checks of safety and circulation equipment during service. - Check safety valves, low water cut-offs and pumps
Check that the safety devices and pumps work correctly. - Check safety valves, pumps and electrical connections
Routine checks of the safety devices, pumps and electrical plugs. - Check safety valves, pumps and expansion vessel
Confirm low water cut-offs, pressure relief valve and pumps work correctly. Check the pressure gauge, air vent and pressure relief valve. Refer to the - Check safety valves, pumps and gas/electrical connections
Start-up and service checks for safety devices, pumps, electrical connectors and gas joints. - Check safety valves, pumps and low water cut-offs
Confirm the pressure relief valve, pumps and any low water cut-offs work correctly. - Check sensors
Scan the actual temperature of the sensor from the Diagnosis menu. Service limits are set in codings 21 and 23 in the Boiler group. - Check sensors and actual temperatures
Read the live sensor temperatures and operating information from the control unit. - Check sensors and actuators
General check of the sensor and actuator wiring when the system malfunctions. - Check sensors and scan actual temperatures
Use the scan function to read the live temperature of each sensor and confirm it matches the reference reading. - Check sight glass, insulation blanket and mixing valve
Check the insulation fit and control operation. - Check static and running gas supply pressure
Measure at the inlet test nipple on the gas combination valve. All readings are taken under high fire. - Check static gas pressure
Confirm the static gas pressure at the inlet test connector. Maximum is 14 in w.c. - Check strap-on or immersion supply/return sensor
Check resistance of the supply or return temperature sensor and compare with the displayed temperature. - Check supply or return temperature sensor
Strap-on or immersion sensor for supply or return temperature. Connection is shown on pages 58 and 59. - Check supply temperature sensor or low-loss header sensor
Only one of these sensors may be used. - Check supply, tank or room temperature sensor (NTC)
Test an NTC sensor against its resistance curve. The room temperature sensor is wired to terminals 3 and 4 in the Vitotrol 300. The supply sensor can - Check supply/return water temperature sensor
Measure the strap-on sensor resistance and compare it with the water temperature. - Check tank, supply or low loss header temperature sensor
Resistance check of the NTC 10 kOhm tank, supply or low loss header sensor. - Check the boiler and DHW tank temperature sensors
Compare the sensor resistance against the temperature. Replace the sensor if the value differs significantly. - Check the boiler temperature sensor
Test the boiler water sensor against the actual water temperature. - Check the burner flue gas flapper
Inspect the flapper and gasket for dirt and damage. - Check the condensate drain and clean the siphon
If condensate cannot drain freely it builds up in the bottom of the boiler and the burner shuts down with a fault message. - Check the fixed high limit (FHL)
Test of the fixed high limit on the Vitotronic 100. The adjustable high limit is bypassed during the test. - Check the fixed high limit (STB)
Test of the fixed high limit on the Vitotronic 100. The adjustable high limit is bypassed during the test. - Check the fixed high limit (TÜV TEST)
Test the boiler's fixed high limit cut-out by bridging the adjustable high limit while the boiler heats up. - Check the fixed high limit via the TUV button
The adjustable high limit R is bridged for this check. A minimum supply is needed during the test. Recirculated water should be at least 10% of the ra - Check the flue gas flapper
Inspect the flapper behind the fan. - Check the flue gas temperature sensor
Applies to VD2, VD2A and CT3 only. The sensor plugs into socket 15 on the boiler control. - Check the flue gas temperature sensor (VD2/VD2A/CT3 only)
Monitors flue gas temperature against a selected limit. Plugs into socket 15. - Check the ignition and ionization electrodes
Check that the electrodes are undamaged and at the correct distance from the burner tube. - Check the neutralization unit
Checks condensate acidity and granulate level. - Check the neutralization unit (if fitted)
Applies only where a neutralization unit is installed. The granulate is used up as it neutralizes the condensate. The red marking shows the minimum fi - Check the outdoor temperature sensor
Check the sensor resistance against the outdoor temperature. Replace the cable or sensor if the readings are far from the curve. - Check the return temperature sensor
Use this to check a strap-on or immersion return temperature sensor against the actual temperature. - Check the return temperature sensor (strap-on or immersion)
The return sensor plugs into socket 17A or 17B on the control unit. Check it by resistance against the current return temperature. - Check the room temperature sensor
Use this check when the room temperature shown on the display seems wrong and the remote Vitotrol cannot be used. - Check the room temperature sensor (Part No. 7133 379)
Test the room sensor resistance and compare it with the room temperature shown on the control. - Check the rotary damper setting
Check the damper position at standstill and during start-up. Factory settings must not be changed. - Check the supply temperature sensor
Use this to check a strap-on or immersion supply temperature sensor against the actual temperature. - Check the supply temperature sensor (strap-on or immersion)
The supply sensor plugs into socket ? on the control unit. Check it by resistance against the current supply temperature. - Check vent termination clearances before commissioning
Confirm the vent termination meets height and spacing limits from the manual. - Check Vitotronic 200-H (accessory) connection
The Vitotronic 200-H connects to the control unit over the LON bus. - Check Vitotronic 200-H connection
The Vitotronic 200-H accessory connects to the control unit via LON. - Check Vitotronic 200-H connection (accessory)
The Vitotronic 200-H is connected to the control unit through the LON bus. The connection is tested with a participant check at the boiler control uni - Check water fill pressure and safety devices
Perform these checks on a cold system. A low fill pressure usually means water loss from a leak, and all leaks must be fixed. - Check water hardness and system water quality
Test water in areas with high mineral content or hardness and treat it if needed. - Checking air intake in installation room
Visual check of filter and air intake during room-air-dependent operation. - Checking air intake in the installation room
Visual check of the filter and air intake during room-air-dependent operation. - Checking and cleaning the burner tube
Service procedure for inspecting and cleaning the burner tube and burner gauze assembly. Work only on a cold system with the gas shut-off closed. - Checking and cleaning the burner tube and gauze
Cleaning or replacing the burner gauze and inspecting the insulation ring. - Checking and correcting the rotation direction of the mixing valve motor
The boiler runs a self-test at power-up that opens and closes the mixing valve. If the supply sensor temperature drops when the valve should be openin - Checking boiler, DHW tank, and flow/low-loss header temperature sensors
Resistance check of the boiler water sensor, fixed high limit, DHW tank sensor and flow sensor for the low-loss header. Sensor type NTC 10 kΩ. The res - Checking buffer storage tank temperatures
Buffer tank values only show when a buffer storage tank is installed. The three readings cover the discharge area, the charging area and the infeed of - Checking burner gasket and flame body assembly
Inspect the flame body, electrodes, insulation ring and gasket. Replace only parts that are damaged or worn. If the flame body is replaced, also repla - Checking CO2 level at upper heating input
Set the burner to maximum output and check CO2 at the flue pipe. Adjust only if outside range. - Checking combustion quality (CO2 or O2 and CO)
Test CO2 or O2 and CO at the lower and upper heating output. Allow about 50 seconds after start before testing, since the controller calibrates itself - Checking control unit fuses
Procedure to check the control unit fuse F1 and the accessory connection box fuses F1 and F2. - Checking DHW, supply and room temperature sensors
Check NTC 10 kΩ sensors by resistance against the curve. The supply sensor can be used as contact or immersion sensor. - Checking domestic hot water values
DHW values show the measured tank temperatures, the current set values and the state of the heating request, charge pump and release. - Checking expansion tank and system pressure
Confirm the cold fill pressure matches the diaphragm expansion tank pressure. Carry out on a cold system only. - Checking extension kit mixing valve rotation
After power-on the boiler runs a self-test, opening and closing the mixing valve. If the flow temperature sensor reading drops when the valve should o - Checking flue gas leakage at full load
Check the flue gas collector and boiler body for leakage with the boiler at full load. Flue gas may contain carbon monoxide, so all flue gases must be - Checking flue gas temperature sensor
Flue gas sensor locks the appliance when the maximum flue gas temperature is exceeded. Unlock by pressing reset button R after the vent system has coo - Checking fuse F1 in the control unit
Check fuse F1 in the control unit (see wiring diagram). - Checking fuses in the External Accessories Connection Box
Check fuses F1 and F2 (see wiring diagram) in the External Accessories Connection Box. - Checking gas equipment for leaks at operating pressure
Leak test all gas joints and valves under normal operating pressure before the boiler is started. - Checking heat generator and outside temperature values
The system shows outside temperature, boiler temperatures, boiler on/off state, return flow temperatures and burner relay status. Use these to see whe - Checking heating circuit values
Heating circuit values show room, flow and pool temperatures plus pump and release status. Room temperature only shows when a sensor or remote room un - Checking heating water connections and flue gas for leaks
Work on pressure-loaded parts only when the boiler is unpressurized. Under-pressure can damage the boiler, so drain only with open venting and a sucti - Checking heating water connections for leaks
Check all heating water connections, including the control equipment connections and the minimum pressure monitor (low-water indicator). Only open the - Checking ignition and ionization electrodes
Check the electrode block once the burner plate is removed. - Checking mixing valve movement and leak tightness
Mixing valve is checked with the motor lever disengaged. - Checking on-site gas connections for leaks
Check the on-site gas connections and the gas valve sealing points for leakage at the gauge connections. Do not use leak detection spray near electric - Checking outside temperature sensor
Resistance test of the outside temperature sensor. Sensor type NTC 10 kΩ. The resistance curve chart is not legible in this extract. - Checking safety valve, low water cut-offs and pumps
Maintenance checks on the relief valve, pressure gauge, air vent, low water cut-offs and pumps. - Checking solar and multifunction relay status
Solar and multifunction values only show for functions that are implemented and activated. Collector pump status is only configured when two collector - Checking static and supply pressure
Measure gas static pressure and running (supply) pressure at the test nipple. Do not adjust the inlet pressure switch; it is factory set to 4 in. w.c. - Checking static gas pressure
Static pressure is measured with the gas valve closed and then opened again. Do not remove the measuring connector screw. - Checking the boiler fuse
Check fuse F1 on the boiler. - Checking the boiler temperature sensor
Resistance check of the boiler temperature sensor against the curve in the manual. - Checking the boiler temperature sensor (dual sensor)
Resistance check of the dual supply temperature sensor against the temperature curve. - Checking the boiler, DHW tank, supply or low-loss header temperature sensors
Warning: the boiler temperature sensor is in the heating water (scalding risk), so drain the boiler before replacing it. Sensor type is NTC 10 kΩ. Onl - Checking the condensate drain and cleaning the siphon trap
A dry or unfilled siphon trap lets flue gas escape. Route the drain hose with no bends and a constant fall. - Checking the DHW flow limiter and filter (gas condensing combi)
Inspect and clean or replace the DHW flow limiter and sieve on the combi boiler. Drain the DHW side first. - Checking the DHW tank temperature sensor
Resistance check of the DHW tank temperature sensor against the displayed temperature. - Checking the DHW tank, supply and room temperature sensors
Test the NTC 10 kΩ sensors used for DHW tank, supply and room temperature. Measure across the plug terminals 1 and 2. - Checking the DHW, low loss header, heating circuit or room temperature sensor
Resistance check of these sensors against the curve in the manual. - Checking the electrical connect module fuses
Check the fuses on the power/pump connection interface and on the Integrate EA1 module. - Checking the expansion tank and system pressure
Set the expansion tank precharge and the system fill pressure with the system cold, then record the minimum fill pressure. - Checking the fixed high limit
Check this if the burner control cannot be reset after a fault shutdown while the boiler water temperature is below about 167°F (75°C). - Checking the fixed high limit (STB test)
Test the fixed high limit (STB) on the Vitotronic 100 with the TÜV test button held. The adjustable high limit is bypassed during the test, so the bur - Checking the flue gas flapper
Back flue gas flapper in the burner mixing shaft. Check the damper and gasket for dirt or damage. - Checking the flue gas temperature sensor
The flue gas temperature sensor locks out the boiler when the permissible flue gas temperature is exceeded. The interlock must be reset after the flue - Checking the ignition and ionization electrodes
Inspect and replace the electrodes after removing the burner plate. - Checking the mixing valve motor rotation direction
After power-up the boiler runs a self-test that opens and closes the mixing valve. The supply temperature sensor should read a higher temperature when - Checking the outdoor temperature sensor
Resistance check of the outdoor sensor and cable. - Checking the outlet temperature sensor
Sensor type is NTC 10 kΩ. Compare the measured resistance with the temperature curve. Resistance curve values are in a chart that is not readable in t - Checking the outside temperature sensor
Sensor type is NTC 10 kΩ. Compare the measured resistance with the temperature curve. Resistance curve values are in a chart that is not readable in t - Checking the outside temperature sensor (NTC 10 kΩ)
Test the outside sensor resistance and compare it with the sensor curve. The curve values are not printed on these pages. - Checking the plate heat exchanger
Drain the boiler on the heating water and DHW sides first. Small amounts of water may trickle out during removal. - Checking the room temperature sensor
The room temperature sensor measures the actual room temperature when the remote control cannot be installed in a suitable location. For connection, s - Checking the strap-on and immersion temperature sensors
Resistance check of the supply and return temperature sensors. - Checking the tank and outlet temperature sensors
Resistance check of the DHW tank and outlet temperature sensors. - Checking the Vitotronic 200-H connection
The Vitotronic 200-H accessory connects to the boiler control unit over the LON cable. - Checking Vitotronic 200-H accessory
The Vitotronic 200-H connects to the control unit via LON. - Checks before commissioning the flue gas connection
Confirm the flue and combustion air path is sound before the boiler is started. - Chemical and dust contamination of combustion air
Chemicals and dust in the combustion air can damage the boiler and cause corrosion. Common sources include laundry chlorine products, paint removers, - Chimney and vent requirements
Improper sizing, termination or blockage can send flue gases into the living space and cause carbon monoxide poisoning. - Chimney and venting general requirements
All combustion products must go outdoors through a chimney sized and insulated for this boiler's low flue gas temperatures. Oversized or uninsulated c - Chimney height and termination
Chimney flue must extend above the roof contact point and nearby roof structures as set out below. Only up to 8 in (200 mm) of flue above the cap coun - Choose an outdoor reset heating curve
Pick one of 9 heating curves so the supply temperature matches the outdoor temperature. Use the offset to fine-tune the room temperature. - Choose and prepare the boiler room
Boiler room air must be clean, unrestricted and never under negative pressure. Exhaust, attic or dryer fans can pull air faster than the structure can - Choose and prepare the mechanical room
The boiler needs a heated indoor room near a floor drain and as close as possible to an outside wall, so the vent is easy to run. Combustion and venti - Choosing a boiler installation location
Pick a heated indoor spot near a floor drain and as close to an outside wall as practical, so venting is easy to run. The wall must carry 155 lb (72 k - Choosing a location for the Vitotrol 200 remote control
Pick a room-sensing spot that reads true room temperature. Mount it on an inside wall of the main living area about 1.5 m (5 ft) above the floor. Keep - Choosing a location for the Vitotrol 200A room sensor
The remote unit has a built-in room sensor for room temperature control. Mount it on an internal wall in the main living space, about 5 ft (1.5 m) abo - Choosing the boiler control
Pick the control to match the system. Single boiler with weather compensation: Vitotronic 300 GW2/GW2B, or Vitotronic 100 GC1/GC1B with a Vitocontrol - Choosing the boiler location
Place the boiler in a heated indoor space, close to a floor drain and as near to an outside wall as practical so the vent is easy to run. - Choosing the boiler location and room conditions
The boiler must sit in a heated indoor space near a floor drain and as close to a wall as possible, ideally on an outside wall so the vent is easy to - Circuit diagram 1: single boiler with Therm-Control and three-way mixing valve
Single-boiler system with a Therm-Control temperature sensor and a three-way mixing valve, used with a Vitorond 200, VD2A boiler. A heating circuit wi - Circulation pump connection
Pumps can be hard-wired to the Power Pump Module terminal strip, or Viessmann pre-wired pumps can be plugged into the Rast-5 terminals. Only Viessmann - Circulator pump connections and zone pump limits
Pump outputs are assigned in the start-up wizard. The boiler supports a maximum of two zone circuit pumps; more pumps need an AM1 extension module. - Clean combustion chamber and heat exchanger
Clean the stainless steel heat exchanger without chemicals. Keep water away from the refractory. - Clean combustion chamber and heat exchanger surface
Remove debris and sediment from the combustion chamber and stainless steel heat exchanger. Discoloration of the heat exchanger is normal and does not - Clean combustion chamber and heating surfaces
Cleaning of the combustion chamber and heat exchanger surfaces. For CI2 1500 and 2000, clean both combustion chambers. - Clean condensate drain pipe and condensate trap
Clean the inside of the condensate drain pipe and condensate trap at least once a year. - Clean condensate siphon (P-trap)
Keep the condensate siphon clear so condensate drains freely. - Clean condensate trap and check condensate drain
If condensate does not drain freely it builds up in the bottom of the boiler and causes a burner shut-down (fault message). Keep the drain and trap cl - Clean heat exchanger and flue pipe
Remove sediment from the heat exchanger and flue path. - Clean heat exchanger, flue collar and chimney connection
Remove all combustion residue from the heat passages and flue path. - Clean heat exchanger, flue gas collar and chimney connection
Remove combustion residue from the heat exchanger, combustion chamber, flue collar and chimney connection. Check the gaskets and insulation at the sam - Clean heat exchanger, flue pipe and flue gas collector
Remove soot and sediment from the heat transfer path. - Clean the burner and gauze assembly
Cleaning and inspection of the burner. Same procedure for 399/500 and 750/1000 MBH burners, with the 750/1000 unit also having a burner baffle plate. - Clean the burner and venturi
Clean the burner components with low-pressure air and vacuum. Use compressed air carefully. - Clean the burner fan and Venturi mixing tube
Clean the fan and check the gasket and gas connections on reassembly. - Clean the combustion chamber and heat exchanger
Periodic cleaning of the combustion chamber and heating surfaces after the burner is removed. Use only non-metallic tools and a cleaner that is safe f - Clean the condensate drain system, siphon and neutralizer
Annual cleaning of the condensate drain system, which includes the flue collector, siphon, neutralizing system and hoses in between. Water must drain - Clean the condensate trap and drain pipe
Clean at least once a year. - Clean the control unit
Clean the control unit with ordinary household cleaners. Do not use abrasive cleaners. - Clean the DHW storage tank
Visual inspection and cleaning must be done no later than two years after commissioning and then as needed. Do not use hydrochloric acid based cleaner - Clean the heat exchanger and refit the burner
Clean the stainless steel heat exchanger without metal brushes. Discolouration is normal and does not affect function. - Cleaning the brazed plate heat exchanger (B1KE)
Chemical cleaning of the DHW side of the plate heat exchanger using a circulating pump and cleaning solution. - Cleaning the burner fan, Venturi tube and burner tube
Cleaning the fan and burner assembly and checking for gas leaks after reassembly. - Cleaning the burners
Clean the fan and burner tube from the gas valve side, then reassemble and check for gas leaks. - Cleaning the burners (fan, venturi and burner tube)
Clean the burner fan and burner tube. Close the central gas shut-off valve before any work. - Cleaning the combustion chamber and heating surfaces
Clean the stainless steel heat exchanger and combustion chamber without damaging the surfaces. Discoloration of the heat exchanger is normal and does - Cleaning the condensate drainage system
Keep condensate flowing freely; a blocked drain causes the boiler to shut down on a fault. - Cleaning the heating surfaces and combustion chamber
Do not brush the heat exchanger. Scratches cause corrosion and brushing lodges deposits between coils. Discoloration is normal and does not affect fun - Clear the Service message after maintenance
Used when the Service display and red fault indicator flash because a service limit was reached. Coding address 24 holds the service timer and must be - Clearances and DHW piping requirements
Keep at least 2 in. (51 mm) clearance from non-insulated hot water pipes to combustible construction. With suitable pipe insulation the clearance can - Clearances to combustibles and service access
Values read from the clearance tables. The printed table layout is jumbled in the text, so confirm each figure against the page before use. - Clearances to combustibles and service space
The boiler is listed for zero clearance to combustibles when vented with an approved single-wall special venting system (AL-29-4C) or UL/ULC-listed CP - Clearances to combustibles and venting
The Vitodens 100-W is listed for zero clearance to combustibles on the sides, top, front, rear and vent pipe when vented with a single-wall AL-29-4C s - Clock symbol not shown on display
The clock symbol should appear on the display. If it does not, the controller is not talking to the boiler. - Clock the natural gas meter to verify input
Time the meter to check the boiler gas input. Only use this method at low altitude. Get the heating value from the gas supplier before timing. - Clocking the natural gas meter to verify burner input
Time the meter to calculate the boiler input in Btu/h and confirm it is correct. A boiler under-fired by 5% is acceptable. Do not over-fire the boiler - Close Ash Door is shown on the display
The display asks for the ash door to be closed. - Close Charge Door is shown on the display
The display asks for the charge door to be closed. - Close power pump module and reinstall control unit
Reinstall the covers in order and check that no cables touch hot components. Cables can be damaged by heat, so keep them within their maximum permissi - Close the boiler control unit and refit the front panel
Reassemble the control after the cascade module is in place. - Close the combustion chamber door
Reassemble after cleaning or inspection. - Close the combustion chamber door after service
Reassemble the chamber and make sure the door seals. - Close the control unit cover
Reinstall the control board cover after wiring is complete. - CO formed or burner very sooty
Burner produces CO or heavy soot with no fault code shown. - CO formed or burner very sooty (no fault display)
Carbon monoxide is produced or the burner is sooting. - CO2 content too low
Combustion CO2 reading is below target with no fault code shown. - CO2 content too low (no fault display)
Flue CO2 reads below target. - Coastal or marine installation
Salt spray and humidity corrode the exposed metal casing and fan housing in damp marine areas. - Coco OT module overview and wiring
The Coco OT module translates the Versatronik 200 CAN signal to OpenTherm for each OT-enabled boiler. Each boiler needs its own Coco OT module, and th - CoCo OT module wiring and layout
Each OpenTherm boiler needs one CoCo OT module. The module converts CAN communication from the control to OpenTherm for the boiler. It can be mounted - Coco OT single boiler DIP setting and connection
Single boiler installations use one Coco OT with DIP switch setting for a single boiler. The Coco OT is wired to the CAN connections, and DHW can be h - Cold during the day but warm at night
The room is cold during the day and warm at night. - Combustion air damper connection
Wire a combustion air damper with an end switch through a field-supplied relay. - Combustion air damper on multiple boiler systems
Damper wiring when a common combustion air interface is used. - Combustion air damper with relay and end switch
Wiring a combustion air damper through a field relay and end switch. - Combustion air device adaptor wiring (CM2)
Connecting the combustion air blower on the CM2 control, which uses the TR terminals. - Combustion air device adaptor wiring (VD2/VD2A/CT3)
Connecting the combustion air blower through the adaptor to the control. - Combustion air device connection (CM2)
Connect a combustion air blower through the adaptor in the boiler junction box. - Combustion air device connection (VD2/VD2A/CT3)
Connect a combustion air blower through the combustion air device adaptor. - Combustion air duct requirements
Outdoor air ducts must meet these size rules. Sizing for openings is in the combustion air opening table. - Combustion air intake for direct vent
Room air independent (direct vent) operation requires the combustion air intake kit. Room air dependent operation draws air through screens on the sid - Combustion air interlock (CAI) for motorized ventilation air supply
A motorized ventilation air supply with or without feedback connects to the CAI plug. The burner does not start until feedback is present. - Combustion air supply requirements
Combustion and ventilation air must be sufficient at all times, and the boiler room must never be under negative pressure. - Combustion analysis and heating circuit leak check
Required before and after work on gas appliances. - Combustion and ventilation air supply
The boiler room needs adequate fresh combustion and ventilation air. Negative pressure and blocked air openings can cause flue gases to enter the livi - Combustion and ventilation air supply (room air dependent)
The boiler needs fresh air for safe operation and must be in a mechanical room with adequate combustion and ventilation air. The room must not be unde - Combustion chamber door and sight glass installation
Hang and secure the combustion chamber door, then fit the sight glass. - Combustion fault through pulsation
Pulsation noise or unstable combustion with no fault code shown. - Combustion fault through pulsation (no fault display)
Burner pulsates or runs noisy, with no fault code shown. - Combustion fault: pulsation
Burner pulsates during operation with no fault code shown. - Combustion faults caused by pulsation
Pulsating combustion can come from gas flow, air balance, condensate or flue problems. - Combustion values out of range
CO2 or O2 reading is outside the target range. - Commissioning when system is not filled with softened water
If the system is filled with water that meets the hardness table but is not fully softened, start up gently to limit scale on the heating surfaces. - Communication interruption on 2-wire BUS or LON module
The control shows a message when data exchange with a linked unit is interrupted. - Condensate disposal and neutralization
Condensate from the boiler is acidic. Neutralize it before disposal if local rules require it. - Condensate drain connection
Drain must use a P-trap or siphon, be inspectable, and terminate in an open or vented drain close to the boiler. A condensate pump is needed if the bo - Condensate drain installation
Route condensate through a P-trap or siphon so flue gas cannot enter the room. The boiler has a field-installed condensate trap, so no external trap i - Condensate drain installation and neutralization
Condensate from the boiler and flue pipe is acidic (pH 3 to 4). It must go to the drain through a trap, and a neutralizer is used where local code req - Condensate not draining, burner shuts down
Condensing boilers make water as they burn, and it has to leave through the siphon and drain hose. If it can't, it backs up into the lower part of the - Configuring a multi-boiler cascade system
Coding order for a multi-boiler system with a Vitotronic 300-K and boiler control units. - Connect 1st stage burner switch (plug aVD, terminals 1 and 2)
Dry contact that switches the basic-load burner stage. - Connect a 120V valve actuator
Wire a 120V motor for a boiler isolation valve, mixing valve or heating circuit. - Connect a 24 VAC room thermostat through a switching relay
A normally open dry contact from a switching relay (T-T) connects to the EA1 module. When the thermostat contact closes, burner operation is load-depe - Connect a 24 VAC thermostat through a switching relay
A thermostat drives a dry-contact switching relay that feeds the EA1 module. With the contact closed, burner output is load-dependent and the supply w - Connect a burner with plug-in connections
Burner cables come with the Vitotronic. Connect the burner plugs to the boiler control counter plugs and to the burner. - Connect a low gas pressure switch or external shut-off at terminal aBA
Use a dry contact to switch the boiler off through the aBA terminals. - Connect a low water cut-off device
Wire the LWCO switch contact into the safety circuit at plug aBÖ. - Connect a return mixing valve or modulating valve actuator (CM2 only)
Wire a 120 V or 24 V valve actuator through a valve adaptor on the DIN rail inside the connection enclosure. - Connect an external 0-10 V boiler temperature signal
An external 0-10 V signal sets the maximum boiler water temperature. The signal must match the chart in the manual. - Connect boiler activation contact (plug aVH, terminals 2 and 3)
Dry contact that controls preheat, isolation valve and modulation on external modulation setups. - Connect boiler return mixing or isolation/modulating valve actuator (CM2)
Use a 120 V or 24 V valve adaptor. Valve run time is set by coding 40 between 5 and 199 seconds. - Connect boiler return mixing or isolation/modulating valve actuator (VD2/VD2A/CT3)
Use a 120 V or 24 V valve adaptor. Valve run time is set by coding 40 between 5 and 199 seconds. - Connect burner to control
Standard burner cable connection using the Viessmann quick-connect plug system. - Connect burner to plug-in connection
Use the burner cables supplied with the Vitotronic for a burner with plug-in connection. - Connect burner with plug-in connection (VD2/VD2A/CT3)
The burner cables come with the Vitotronic. The 7-pole plug goes to the 1st stage and the 3-pole plug to the 2nd stage or modulation. The burner conne - Connect cascade via CAN bus
Connect the previous and following heat generator cables to plug lA. Wrong connection causes malfunctions. - Connect CombiPLUS cables to the boiler power pump module
Wiring of the control cable Q and pump cable R inside the power pump module. - Connect CombiPLUS flex pipes
The flex pipes must be bent because of the offset between the boiler and CombiPLUS fittings. The bent lengths for the 7 in and 12 in flex pipes are no - Connect CombiPLUS flex piping to the boiler
Connect the flex pipes between the boiler bottom tees and the CombiPLUS extension fittings. - Connect combustion air blower through common interface
Wire the shared blower on a multiple boiler system. - Connect combustion air damper
Damper wiring with end switch and optional relay. - Connect combustion air damper (single boiler)
Wire a combustion air damper through the adaptor, with a field-supplied relay where the damper needs one. - Connect combustion air damper through common interface
Wire the shared damper on a multiple boiler system, with a field-supplied relay. - Connect combustion air device adaptor (single boiler)
Wire a combustion air blower to the Vitotronic through the adaptor board in the connection enclosure. - Connect compiled failure alarm
Wire a visual or audible alarm to the boiler control's alarm terminal strip. - Connect compiled failure alarm (CM2)
Wire a 120 VAC visual and/or audible alarm to the CM2 boiler's compiled failure output. - Connect compiled failure alarm (VD2/VD2A/CT3)
Wire a 120 VAC visual and/or audible alarm to the boiler's compiled failure output. - Connect compiled failure alarm indicator (CM2)
Alarm output for a visual and/or audible device. Rated 120 VAC, 60 Hz, maximum 2 FLA. Use AWG 14 wire. - Connect compiled failure alarm indicator (VD2/VD2A/CT3)
Alarm output for a visual and/or audible device. Rated 120 VAC, 60 Hz, maximum 2 FLA. Use AWG 14 wire. - Connect DHW storage tank temperature sensor
The DHW tank sensor is needed when a stand-alone DHW storage tank is used with the boiler. Only the sensor is supplied; other piping is field supplied - Connect external safety equipment at plug aBÖ
Add low water indicators, minimum or maximum pressure limiters or other safety devices in series. - Connect external shut-off (aBÖ) and emergency operation
A dry contact at terminals 16 and 17 gives a controlled switch-off when opened. Use it for safety switch-off only, for example through a limit thermos - Connect flue gas and combustion air
Connect the flue and combustion air pipes with the shortest practical run and secure them. The boiler flue collector cannot carry the venting weight. - Connect flue outlet to venting
Connect the flue collar to the venting so that no load or torque is on the boiler collar. Install a flue gas adaptor if the stainless vent does not fi - Connect gas supply and manual shutoff
Gas piping must be sized for the full connected load of the home, with no noticeable pressure drop when any appliance lights or runs. Piping must not - Connect gateway at 120VAC to Vitocontrol-S (CT3/VD2A) or Vitotronic 300-K MW1B
Wiring layout for a 120VAC gateway. Vitocontrol-S needs a LON card fitted before connection. - Connect gateway at 120VAC to Vitocontrol-S MW2, Vitodens WB2B or Vitotronic 300-K MW2B
Wiring layout for a 120VAC gateway on MW2 controls. A communication card is required for Vitocontrol-S on MW2 (Vitodens WB2B). - Connect gateway at 120VAC to Vitodens 200 WB2B, HO1 or B2HA
Wiring layout for a 120VAC gateway on Vitodens 200 WB2B, HO1 and B2HA. The LON card is installed inside the boiler control. - Connect gateway at 120VAC to Vitotronic 100, GC1/GC1B, 300 GW2 or 300 GW5B
Wiring layout for a 120VAC gateway on these controls. The LON card goes in the control, and the gateway is linked to it by the supplied cable. - Connect gateway at 24VAC to Vitocontrol-S (CT3/VD2A) or Vitotronic 300-K MW1B
Wiring layout for a 24VAC gateway with a field-supplied power source. - Connect gateway at 24VAC to Vitocontrol-S MW2, Vitodens WB2B or Vitotronic 300-K MW2B
Wiring layout for a 24VAC gateway on MW2 controls with a field-supplied power source. - Connect gateway at 24VAC to Vitodens 200 WB2B, HO1 or B2HA
Wiring layout for a 24VAC gateway on Vitodens 200 WB2B, HO1 and B2HA. - Connect gateway at 24VAC to Vitotronic 100, GC1/GC1B, 300 GW2 or 300 GW5B
Wiring layout for a 24VAC gateway on these controls. Power comes from a field-supplied 24VAC source. - Connect gateway to Vitocontrol-S CT3/VD2A (120VAC)
Vitocontrol-S needs the LON card installed. The gateway connects through the CAT-5 cable and field Modbus wiring. - Connect gateway to Vitocontrol-S CT3/VD2A (24VAC)
Same connection as the 120VAC version, with the gateway powered from a field-supplied 24VAC supply. - Connect gateway to Vitocontrol-S MW2 for Vitodens WB2B (120VAC)
A communication card is required for this Vitocontrol-S MW2 configuration. The gateway connects through the CAT-5 cable and Modbus wiring. - Connect gateway to Vitocontrol-S MW2 for Vitodens WB2B (24VAC)
Same connection as the 120VAC version, with the gateway powered from a field-supplied 24VAC supply. - Connect gateway to Vitodens 200 WB2B / HO1 (120VAC)
The LON communication card goes inside the boiler control. Refer to the boiler manual for the card installation. - Connect gateway to Vitodens 200 WB2B / HO1 (24VAC)
Same connection as the 120VAC version, with the gateway powered from a field-supplied 24VAC supply for the Versatronik gateway. - Connect gateway to Vitotronic 100 GC1 or 300 GW2 (120VAC)
Gateway is connected to the boiler control through the LON communication card and the supplied CAT-5 cable. The gateway is powered by the plug-in 120V - Connect gateway to Vitotronic 100 GC1 or 300 GW2 (24VAC)
Same LON and CAT-5 connection as the 120VAC version, but the gateway is powered from a field-supplied 24VAC source. - Connect gateway to Vitotronic control on 120 VAC
Connection for GW6B and MW2C controls when the gateway is powered from 120 VAC. The lead and cascade control need the LON card. - Connect gateway to Vitotronic control over LON and BACnet/IP
Wire the gateway to the boiler control and the building network. Use the connection diagram that matches the control and supply voltage. - Connect low loss header sensor TS1
Low loss header sensor goes to the MZIO module, plug TS1. On cascades, connect it to the lead boiler. - Connect low water cut-off device (CM2)
Wire the external LWCO into the CM2 control. The factory jumper between 21 and 22 must be removed first. - Connect low water cut-off device (VD2/VD2A/CT3)
Wire the external LWCO into the control terminals. The factory jumper between 12 and 15 must come out first. - Connect power supply
Supply is 120 VAC, 1 PH, 60 Hz. The control must be grounded. - Connect several remote control units (Version 1)
Several Vitotrol remote controls are connected through a terminal box installed on site. - Connect several remote control units with other BUS participants (Version 2)
Remote controls and additional KM BUS participants are connected through an on-site terminal box. - Connect several remote controls
Use an on-site terminal box when more than one remote control is connected. The total KM BUS cable length should be limited, and each remote branch sh - Connect several remote controls and BUS participants via a terminal box (version 2)
Use an on-site terminal box when several remote controls and additional KM BUS participants are connected. - Connect several remote controls via a terminal box (version 1)
Use an on-site terminal box when more than one remote control is connected to the control unit. - Connect the 120VAC gateway to a Vitotronic 300 GW5B or GW6B
Confirm the boiler control has its LON communication card fitted before wiring. Use the boiler control manual for the card location. - Connect the 120VAC gateway to the boiler control
The gateway is wired to the control's LON card with the supplied CAT-5 cable and to the BACnet IP network by RJ45. The control's LON card must be inst - Connect the 24VAC gateway to a Vitotronic 300 GW5B or GW6B
Confirm the boiler control has its LON communication card fitted before wiring. - Connect the condensate drain
Route the condensate drain so it does not siphon the boiler, and ensure it can drain freely. - Connect the control unit to the LON system
Set up the LON participant number and check the LON data exchange on a multi-unit system. - Connect the control unit to the Viessmann 2-wire BUS system
Set the BUS address and matching coding when the control shares a system with a boiler control or other Vitotronic. - Connect the DHW sensor to a stand-alone storage tank
The DHW tank sensor is needed when a stand-alone storage tank is used with this boiler. - Connect the gateway to a Vitotronic 100 / 300 GW2 / 300 GW5B control
The gateway links to the control through a CAT-5 cable and sends the LON network out on terminals A and B. The control needs its LON communication car - Connect the gateway to the boiler control and network
The gateway links to the boiler control over a supplied CAT-5 cable and to the BMS over BACnet IP. The LON communication card must be fitted in the co - Connect the low-loss header sensor
Use this sensor only if a low-loss header is installed. - Connect the low-loss header sensor to the X3 plug
The low-loss header sensor connects to the boiler control board on terminals X3.4 and X3.5. The control unit cover must be removed to reach the X3 plu - Connect the neutralizing system (accessory)
A neutralizing unit is an accessory. The condensate trap hose goes to the neutralizer, and the drain must sit lower than the trap. - Connect the outdoor temperature sensor
Wire the outdoor sensor to the boiler control board and mount it on the building. - Connect the vent to the boiler
Venting must be short and straight with a supported horizontal run. Use the factory vent adaptor on the flue gas collar. - Connect the Vitotronic control and run its cables
Connect the Vitotronic plug-in cable to the burner and route all sensor and power cables inside the boiler without touching the heat exchanger. - Connect two or more remote controls
Use the KM-BUS Expansion Module or a field-supplied junction box when connecting two or more remote controls. - Connect two-stage or modulating burner
Wiring for two-stage or modulating burners via the 2-stage/modulating extension. - Connecting 120V external pumps
Pump wiring depends on the pump's electrical draw and voltage. Larger pumps and non-120V pumps need a field-supplied contactor or relay. - Connecting a 24 VAC thermostat through a switching relay
Use a switching relay with a normally open, potential-free dry contact (T-T). Wire the contact to input DE1, DE2 or DE3 on extension module EA1 in the - Connecting a low water cut-off (LWCO)
The LWCO switching contact is wired in place of the factory jumper. Use the diagram in the LWCO device manual for interconnection details. - Connecting a mixing valve actuator
A 120V or 24V valve adaptor on the DIN rail links the control to the mixing valve actuator. Power to the control must be off during the work. - Connecting a stand-alone DHW storage tank
Vitodens boilers can supply a Viessmann stand-alone DHW storage tank. Size the tank to the building's forecast DHW use. The tank needs field-supplied - Connecting an external heat demand contact
Potential-free contact for external heat demand. Use socket X5 for stages 1 and 2 (two-stage burners only) or socket X6 for minimum boiler water tempe - Connecting boiler pumps (shunt, boiler circuit, DHW)
Pump wiring to the boiler control. Line-voltage pumps are switched through a contactor or motor starter. - Connecting combustion air device (blower and proving switch)
Wiring a 120 VAC combustion air blower through the Combustion Air Device Adaptor, with a proving switch. - Connecting control unit power supply
The control must be grounded. L, N and G must not be interchanged. The supply is 120VAC, 1 phase, 60 Hz, 12 A full load. - Connecting external burner disable
Disables burner activation when the contact is closed. - Connecting external safety equipment (plug aBÖ)
External safety devices such as pressure limiters are wired to plug aBÖ. Contacts must be potential-free and must not be live. - Connecting low water cut-off device
Wiring of an external low water cut-off into the control's safety circuit. - Connecting several remote control units
Several remote controls and additional KM BUS users are connected through a junction box installed on site. Version 1 is for remote controls only; ver - Connecting the boiler control to a LON system
Boiler control is linked to Vitotronic 200-H mixing valve controls and a Vitocom LON module. The LON communication module is an accessory and must be - Connecting the burner or vent system cable
The Vitotronic 200 is prewired with plug-in connectors. If a venting system is installed, the 7-pole plug goes to the wall vent system and not directl - Connecting the central fault message facility
The central fault message output is a relay for signalling faults. - Connecting the compiled fault indicator
Potential-free output for visual or audible alarm equipment. - Connecting the external 0-10 V signal
Wiring an external 0-10 V demand signal that sets the maximum boiler water temperature. - Connecting the flue gas pipe
The flue collector is not designed to carry the weight of the vent system. Connections must be free of load and torque. - Connecting the KM-BUS Expansion Module
The KM-BUS Expansion Module lets you connect remote controls, remote monitoring devices and the Switching Module-V to the Vitotronic control unit. - Connecting the LON gateway to the boiler control
Wiring and power connections for the Versatronik gateway on the Vitotronic and Vitodens controls. Refer to the manual for the specific boiler control - Connecting the neutralization system
The neutralization kit is an accessory. The boiler siphon must be filled with water, and the drain must sit lower than the siphon to prevent flue gas - Connecting the Vitotrol 200A to the boiler control
Connect the two-wire communication cable from the remote to the control unit. The remote can connect to a 2- or 3-pole plug on the Vitotronic control - Connecting two remote control units
Up to 2 remote controls can connect to one boiler control unit, and this can be one Vitotrol 200A with one Vitotrol 300A. Connect them through a field - Connecting Vitodens 200 WB2B with Vitotronic 200 HO1 to the Versatronik 300
Boilers are daisy-chained from control to control with CAT5e cable using RJ45 ends (non-crossover). Plug the cable into the J1 receptacle in the upper - Connecting Vitodens B2HA with black GUI to the Versatronik 300
Same CAT5e daisy-chain method as the HO1 version. The boiler needs its outdoor temperature sensor connected, and the boiler coding addresses differ. - Connection error shown on programming unit
The HMI programming unit has lost communication with the HMU heat management unit. - Connection error shown on the display
Shown when the HMI programming unit cannot communicate with the HMU heat management unit. - Connection points on the 24VAC DIN rail gateway
The 505D has four connection points: BACnet IP RJ45, control LON RJ45, a paralleled bus connection and 24VAC power. - Continuous burner call
The burner keeps calling for heat and does not stop. - Control and junction box installation (CM2)
Capillaries and cables must not touch hot metal parts. Do not bend or kink the capillaries, because damaged capillaries cause malfunction. The ground - Control calls for heat but burner does not respond
The control is calling for heat but the burner or power venter does not run. Work through the burner, the power venter and the accessories. - Control calls for heat but the burner does not respond
The control is calling for heat but the burner stays off. - Control module overview
Modules in the Vitodens 100-W control system as shown on the wiring diagram overview. - Control unit power supply connection
Power input to the control unit. The control must be grounded and the line, neutral and ground must not be swapped. - Controls Locked Out is displayed
The control unit is blocked. The cause is mapped from the manual's layout on p. 38, which is jumbled. - Conversion to liquid propane gas (LPG)
Convert the burner from natural gas to LPG using the LPG kit supplied with the burner. Escaping gas is an explosion risk, so check all fittings for le - Conversion to natural gas (NG)
Convert the burner from LPG back to natural gas. No separate orifice is needed for natural gas. - Convert boiler from natural gas to liquid propane
Factory set to natural gas (coding 82 = 0). Conversion uses coding level 2 and a gas valve adjustment. Fuel conversion labels must be applied. - Convert boiler from natural gas to LPG
Field conversion of the gas valve and control settings. Use the fuel conversion kit instructions and label. - Convert from natural gas to liquid propane gas
The boiler is factory set for natural gas. Coding address 82 is 0 for natural gas. Coding 11 must be set to 9 before 82 can be changed. - Convert fuel type from natural gas to liquid propane
Field conversion of both gas valves and coding for LPG operation. - Convert fuel type from natural gas to liquid propane gas
Coding and gas valve change to run the boiler on LPG. The factory setting is natural gas. - Convert the boiler from natural gas to LPG
Gas type change is done in the control settings; the gas solenoid valve is not mechanically adjusted. - Converting from natural gas to LPG
Gas type is changed in the commissioning assistant. A conversion kit and its labelling are needed for the hardware change. - Copy a DHW time program to other days
Copies one day's program to other days. The same method works for the DHW circulation pump program. - Copying a time program to other days
Copy a finished day's time program to other days of the week instead of entering each day. - Corrosion protection and chemical additives
Sealed correctly installed and operated systems normally do not corrode. Where plastic pipe makers recommend additives, use only corrosion protection - CSD-1 field test of fixed high limit (where required by law)
Field test procedure for the fixed high limit on Vitodens boilers. Viessmann is not responsible for damage caused by overheating during this test. A t - CSD-1 field test of fixed high limit switch
Where required by law, this test simulates a fixed high limit trip. The fixed high limit needs a manual reset of the boiler control once it trips. Vie - CSD-1 fixed high limit fault simulation #1 (pump removed)
Test of the fixed high limit switch, required where CSD-1 applies. Viessmann is not responsible for damage caused by overheating during this test. - CSD-1 fixed high limit fault simulation #2 (flow switch jumpered)
Alternate high limit test with the boiler valve closed and the flow switch bypassed. Viessmann is not responsible for damage caused by overheating dur - CSD-1 fixed high limit field test (simulation #1)
Field test of the fixed high limit where required by law. Viessmann is not responsible for damage caused by overheating the system during this test. - CSD-1 fixed high limit field test (simulation #2)
Alternate CSD-1 high limit test using the relays test and a throttled boiler valve. - CSD-1 fixed high limit field test (simulation #3)
Wire-removal test that creates a fault in the control which needs a manual reset. - CSD-1 fixed high limit test (fault simulation #1 and #2)
Field test of the fixed high limit as required by CSD-1 where the law requires it. Viessmann is not responsible for any overheating damage caused by t - CSD-1 fixed high limit test, simulation #1 (boiler pump off)
Field test of the fixed high limit using the flue gas test mode with the boiler pump disconnected. Only do this where required by law and accept that - CSD-1 fixed high limit test, simulation #2 (closed boiler valve)
Alternate field test of the fixed high limit with the boiler valve closed. Overheating is possible. - Damaged connecting cables
Damaged appliance or external electrical accessory cables must be replaced. - Dangerous condition at the boiler
Use this response when there is a dangerous condition at the boiler. - Dangerous conditions
Emergency shutdown when a dangerous condition exists at the boiler. - Dangerous conditions at the boiler
Immediate emergency actions if a dangerous condition exists at the boiler. - Designed temperature differential for radiant systems
Radiant floor systems are typically designed for a 10°F to 20°F temperature differential between supply leaving the boiler and return entering the rad - Detaching the upper burner section
Removing the burner needs a lifting mechanism. Refer to the lifting device instructions and the service instructions when refitting. - Determine values for a two-stage burner
Measure maximum and basic burner output so the values can be entered in coding 1. - Dew-point protection with two-stage burner and Vitotronic control
With a Vitotronic control in modulating mode, the burner must be able to reach full input to protect the boiler from dew-point corrosion. - DHW is too hot
DHW temperature setting is too high, solar may be heating the tank, or test mode is on. - DHW not heating as expected
Checklist for when hot water is not heated when required. The control unit is set so DHW heating applies to all heating circuits by default. - DHW storage tank sensor and tank connection
Sensor and tank setup needed when using a stand-alone DHW storage tank. - DHW tank temperature sensor connection
Connect the DHW tank sensor to the boiler control board. - Diagnose a fault
A fault shows in the display and makes the red fault lamp flash. The display shows the error source in plain words and as a fault code, including the - Diagnosis screen values (scan list)
Values that can be scanned in the Diagnosis menu, depending on the installed system. - Digital inputs DE1 to DE3 wiring and function options
External contacts must be floating. Follow the safety category II spacing: 8.0 mm air and creep path, or 2.0 mm insulation thickness to live parts. Ea - Direct vent combustion air intake and filter
The combustion air intake can be fitted with a field supplied filter. Keep the intake diameter the same through the whole duct. The boiler inlet does - Direct vent sidewall termination height
Vent termination must be at least 12 in (305 mm) above the anticipated snow level and placed so snow cannot block it. The termination must be installe - Disconnecting burner wiring
Disconnect the burner harness before removing the burner from its casing. Plug labels on the printed page are partly garbled. - Disconnecting the burner
Prepare the burner for removal by disconnecting its electrical connections. - Dismantle the burner
Removing the upper burner section and then the burner tube assembly. A lifting device is needed for the burner. - Dismantle the upper burner section
Remove the upper burner section to reach the burner tube, gauze and electrodes. Follow the service preparation steps on page 51 first. - Dismantling the burner
Removing the upper burner section and the burner tube. - Display illumination is defective
The display backlight does not work. The batteries are normally the cause. - Drain the boiler on the DHW side
Drain the domestic hot water circuit through the drain valve. Make sure the DHW pipework is well ventilated. - Draining the boiler on the heating water side
A drain hose is loosely stored in the heat exchanger compartment. On later models a factory-installed sediment valve is fitted and the drain hose is f - Edit a heating time block on the controller
Set the weekday, time block and start/end times for a heating time program. Programs are available for heating circuits 1 and 2 (Prg1 and Prg2), DHW l - Electric boiler does not heat
The boiler is not heating even though the panel is working. Causes include the utility off-peak signal and sensor or panel failures. - Electrical connection points on the Versatronik 503
The board has a 120 VAC supply with a 6 ft convenience plug, two LON jacks (LON1 and LON2), a 0-10 VDC setpoint output to the boiler (BLR CMD), a faul - Electrical installation checklist
Electrical work must follow local codes and be done by a qualified electrician. - Emergency shutdown
In an emergency, cut the power supply first, unless there is a gas smell. For gas systems, close the gas shut-off valve. Use a suitable extinguisher f - Emissions test mode (flue gas testing)
Emissions test mode briefly raises the boiler water temperature so the flue gas can be tested. It should only be activated by the heating contractor d - Emissions test switch left in test position
The emissions test switch is in test mode, which the page lists as a cause of a problem. - Enclosure installation sequence
Build the jacket around the boiler in order. Components are supplied in the jacket carton and insulation mounting parts come with the insulation. - Ending central heating
Stops central heating for the primary circuit or for all circuits. DHW heating continues in Only DHW mode, or frost protection stays active in Standby - Energy saving mode for short unoccupied periods
Energy saving mode lowers the preset room temperature for a short time. It only works in the heating and DHW program. - Enlarge burner opening for Carlin EZ-LF-1HP
Required when installing the Carlin EZ-LF-1HP burner. - Enter coding level 1 and select a coding group
Opens the coding menu on the Vitotronic control to change installer settings. - Erase a DHW time phase
Clear one DHW phase so it no longer runs. - Erase a space heating time phase
Clear one heating phase by setting its start and end times to blank. - Excessive flue gas temperature (no fault display)
Flue gas runs hotter than normal and no fault code is shown. - Extended shut-down and freeze protection
Preparation for summer shutdown or freezing conditions. - External 0-10 V boiler water temperature setpoint
An external 0-10 V signal sets the maximum possible boiler water temperature. The voltage-to-temperature chart is not reproduced on this page, only on - External 0-10 V signal connection for boiler water setpoint
A 0-10 V signal from an external controller sets the maximum boiler water temperature. Example from the manual: 8 VDC equals 176 ºF (80 ºC). The full - External blocking
External contact blocks heating operation. A version with fault message input is also available. - External blocking via DIS input
A closed contact at DIS shuts the burners down in a controlled way. Choose the combustion air device option that matches the installation. - External blocking via dry contact
A closed contact shuts the burner down and switches off the boiler circuit pumps. The system has no frost protection while blocked, and the boiler is - External blocking via output contact (EA1 extension)
A potential-free contact can block the boiler. When it closes, the burner of each boiler section shuts down, the boiler circuit pump and system pump s - External blocking via switching contact
Blocks the boiler or cascade from an external floating contact. Connection is on plug aVD.2/aVD.3, or on the EA1 extension for cascade control units. - External boiler activation contact (isolation valve open/closed)
Dry contact at plug aVH controls boiler activation. Essential on multi-boiler systems. Lead boiler contact must stay closed. - External changeover between staged and modulating burner
A dry contact on plug aVH switches the burner between two-stage and modulating operation. - External changeover of staged/modulating burner
Dry contact at plug aVH selects modulating or two-stage operation. - External contacts A, B and C on A2
Dry contacts on A2 for heating program change, external disable and external heat demand. Heating circuit allocation uses coding addresses 91, 9A, 99 - External control: switch on 1st stage burner
Dry contact at plug aVD starts the first burner stage. - External control: switch on 2nd stage burner
Dry contact at plug aVD starts the second burner stage. - External demand
External contact requests heat and can enforce a minimum boiler water temperature. - External demand via dry contact
A closed dry contact runs the burner load-dependent. Supply water is heated to the set value in coding address 9B (General group) on the Vitotronic 30 - External demand via plug aVH
A floating contact on plug aVH switches the burner on based on load. - External demand via switching contact
Starts the burner on an external floating contact, subject to load. Connection is on plug aVH.2/aVH.3, or on the EA1 extension. - External disable / close mixing valves via floating contact (aVD)
A closed floating contact stops the burner in a controlled way or closes the mixing valves. - External extensions AM1 (accessory) overview
Two circulation pump outputs, A1 and A2. Available functions: heating circuit pump (no mixing valve or zone pump), DHW tank heating circulation pump, - External extensions AM1 pump connections
Circulation pumps can be connected to outputs A1 and A2 of the AM1 accessory: heating circuit pump without mixing valve, DHW tank heating pump, or DHW - External heating program changeover
A dry contact changes the heating program. At plug avD, coding 91 (General group) assigns the function to the heating circuits. With extension EA1, se - External heating program changeover (EA1 extension)
A potential-free contact can switch the operating program for heating circuits 1 to 3. Each circuit can be changed over separately. - External Hook-up is displayed
The operating program was changed by an external device. - External mixing valve open / close contacts
A closed contact opens or closes the mixing valves. The open function is assigned to the heating circuits with coding 9A (General group). The close fu - External mixing valve open / closed inputs
Floating contacts on plug aVD that open or close the mixing valve of a heating circuit. - External Program is displayed
The operating program was changed through the Vitocom communication interface. - External shut-off via terminal aBÖ (safety switch-off only)
A dry contact on terminal aBÖ gives a controlled switch-off. Use it only for safety switch-offs, such as a high limit thermostat. - Fault behaviour legend (burner states)
Control mode: boiler/burner fully running; the fault code must be verified and reset. Burner in fault mode: manual reset needed before the burner rest - Fault code F2: fixed high limit tripped
Manual reset over-temperature fault shown when the fixed high limit trips at 210°F (99°C). - Fault diagnosis procedure
Three-step method for working through a fault on the Vitotronic 100 control. - Fault display and acknowledging faults
A fault shows as the red fault indicator flashing, "2" flashing on the display and "Fault" shown. Acknowledged faults stay in the standard menu. If an - Fault display and fault messages
In a fault the red fault display flashes and shows the symbol and Fault. A connected central fault message facility starts. If several faults are acti - Fault display at the programming unit
Any fault turns on the red fault indicator, which flashes for every fault. The display flashes 'Fault' with the fault code, fault number (1 to 10) and - Fault displayed
A heating system fault is present. The red fault indicator flashes on the control unit. - Fault flashes in the display window
The word Fault flashes in the display window. - Fault indication and acknowledging a fault
On a fault, the red fault indicator A flashes and "2" flashes on the display with "Fault" shown. The fault message moves to the standard menu and any - Fault indicator flashing on the boiler
Red fault indicator A flashes, 2 flashes on the display and Fault is shown when a fault occurs. - Fault indicator flashing with code on display
Red fault indicator A flashes, the display shows 2 flashing and Fault. Burner in fault mode needs a manual reset. Burner blocked resumes by itself whe - Fault is displayed
The red fault indicator flashes on the control unit enclosure. - Fault is displayed (heating or DHW)
The display shows Fault and the red fault indicator flashes on the control unit enclosure. This is listed as a cause in the heating and DHW troublesho - Fault lamp on control unit with blinking burner control display
Fault after start-up or during gas supply problems. Reset the burner control unit and check the gas supply. - Fault message BC, BD or BE after remote control allocation changed
Fault messages BC, BD and BE are listed in the manual as appearing when a heating circuit allocation to the remote control is cancelled. The page does - Fault message: scan, record and acknowledge
Fault shown in red with a Faults message and a flashing red fault indicator on the control unit enclosure. Acknowledging silences any connected buzzer - Fault messages are displayed (scanning and acknowledging faults)
The display shows Faults and the red fault indicator flashes on the control unit enclosure. The fault code and its cause must be recorded before the c - Fault on control unit
Fault on the control unit itself. - Fault on heating system (U symbol with fault code)
Fault symbol U appears in the display with a flashing fault code, pointing to a fault in the heating system. - Fault on the boiler control unit (Vitotronic 100, GC1)
The control unit has a fault and the boiler is not running normally. - Fault shown on the display
The control shows 'Fault'. The page gives one cause for this display. - Fault symbol 'U' shown in display with flashing fault code (multi-boiler)
The display shows the fault symbol 'U' with a flashing fault code, meaning a fault on the boiler or heating system. - Fault symbol flashing in the display
The fault symbol on the remote control flashes when the heating system has a fault. - Fault symbol U flashes in the display
A control unit fault. Read the fault code by scanning, then report it to the heating contractor. - Fault symbol U with flashing fault code
A fault has occurred on the heating system or boiler and is shown with the U symbol. - Fault symbol U with flashing fault code (Vitotronic 100, GC1)
The display shows the fault symbol U with a flashing fault code. - Field test of fixed high limit (CSD-1)
Where required by law, the fixed high limit can be tested in the field. The manufacturer is not responsible for damage caused by overheating during th - Field test of fixed high limit, simulation 1 (CSD-1)
Checks the fixed high limit by overheating the boiler with the flow blocked. Only where required by law. Viessmann is not responsible for damage cause - Field test of fixed high limit, simulation 2 (CSD-1)
Checks the fixed high limit by running the boiler with minimal flow and then stopping flow completely. Only where required by law. - Field test of fixed high limit, simulation 3 (CSD-1)
Tests the control's response to a limit switch wiring fault. This produces a fault that needs manual reset. - Field test the fixed high limit (CSD-1, where required by law)
Viessmann is not responsible for damage the test can cause by overheating the system. Three simulations are described. Simulation 1 and 2 test the fix - Field wiring requirements
Wiring must meet the national and local electrical codes listed for the installation. - Field wiring rules for the boiler and controls
Wiring must follow the National Electrical Code (or CSA C22.1 in Canada) and local codes. Use Class 1 wiring, and sheath field-supplied 120 VAC wiring - Field-installed normally closed safety relay
The power/pump interface has a normally closed safety connection (A). A field-supplied normally closed relay can be installed in its place. The relay - Fill and flush heating system
Use clean potable water and flush the piping before filling. Debris can settle in the boiler and cause overheating damage that is not covered by warra - Fill and pressurise the heating system
Set the expansion vessel precharge first, then fill and vent the system at the correct pressure. - Fill condensate trap with water
Fill the condensate trap before start-up so flue gases cannot pass through the drain. Close the main gas supply before removing the front panel. - Fill heating system with water
Flush the system before filling and use potable-quality water. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids. Use - Fill the condensate siphon with water
The condensate siphon must be filled before start-up so exhaust gases cannot escape through the drain. - Fill the condensate trap with water
Prime the siphon before startup so flue gases cannot escape through the drain. - Fill the heating system and vent air
Filling and recording steps before start-up. Water quality limits are on page 92. - Fill the heating system with water
Flush the system before filling to avoid sludge settling in the boiler. Antifreeze may be used where freezing is possible. - Filling the condensate trap
Fill the siphon before start-up so flue gas cannot escape through the trap. - Filling the condensate trap with water
The siphon must be filled before start-up, otherwise flue gas can escape through the drain. - Filling the heating system
Fill and vent the heating system with the expansion vessel and fill pressure set correctly. - Filling the heating system and venting
Fill with softened water and open and close the isolation valves at each boiler section. - Final checks: pressure relief valve and CO2 test
Test the pressure relief valve for proper operation. Escaping gas can cause an explosion, so always complete these steps. After the burner has been re - Fire at or near the boiler
Fire at the boiler is a risk of burns and explosion. Only trained people should attempt to fight it. - Fire at the boiler
Response to fire at or around the boiler. - Fire in or around the boiler
If fire is coming from the appliance there is a risk of burns and explosion. - First-stage burner enable contact (basic load)
Dry contact on plug aVD that switches the first-stage burner on or off. - Fit the condensate trap
The condensate trap is included with the boiler. Its float closes the trap when there is no water, which keeps flue gas out of the room. - Fit the control unit top section
Assemble the top of the control unit onto the bottom and secure the hinged support bar. - Fitting and removing the Vitotrol 200A interface on the mounting plate
The interface clips onto the mounting plate. To remove it, release the top from the plate with a flat-head screwdriver, then unhook the base. The remo - Fitting the control unit front
Reassemble the control front and cover after wiring. - Fitting the front panels
Do not operate the boiler without the front cover in place. - Fitting the LON end-of-line resistor
One end-of-line resistor ships with the Versatronik 300. It goes into the last boiler on the LON communication network. Its RJ45 plug fits the LON com - Fitting the programming unit at the top
Procedure when the programming unit is mounted at the top; see page 16 for the mounting panel. - Fittings, gaskets and leak checks
Every connection on the boiler needs a new gasket any time it is opened or loosened. When commissioning and after any maintenance, check all water-sid - Fixed high limit adjustment (JUMO 100 ºC version)
Same purpose as the Etheco/EGO adjustment, for the JUMO limit. Step order is shown in the manual graphic, which is not readable in the extracted text. - Fixed high limit has tripped (lockout)
The fixed high limit shuts the boiler down with lockout when the water temperature reaches its limit. It is reset manually. It also locks out on a cap - Fixed high limit test
Field test of each boiler section's fixed high limit. Per CSD-1, the test is done where required by law. Viessmann is not responsible for damage cause - Fixed high limit test #1 (boiler pump disconnected)
CSD-1 field test of the fixed high limit using the boiler pump. Manufacturer disclaims damage from overheating during this test. - Fixed high limit test #1 (CSD-1 field test, pump unplugged)
Field test of the manual reset fixed high limit. Only do this where required by law. Viessmann is not responsible for damage caused by overheating the - Fixed high limit test #1 (F2 simulation with boiler pump disconnected)
Test that trips the manual reset high limit by running the burner with the boiler pump disconnected. Viessmann is not responsible for damage caused by - Fixed high limit test #2 (flow switch jumpered)
Alternative test that trips the fixed high limit with the boiler valve closed and the flow switch jumpered. Only do this with the boiler monitored and - Fixed high limit test #2 (valve closed, flow switch jumpered)
Alternate high limit test. The boiler is run at high fire with the boiler valve closed. Jumpering the flow switch may be needed for testing. Only do t - Fixed high limit test (CSD-1)
Used to check the manual reset fixed high limit. The fixed high limit should trip at 210 °F (99 °C) and produce an F2 fault. The manufacturer is not r - Fixed high limit test (per boiler section)
Each boiler section has its own fixed high limit and each must be tested individually. The test raises the boiler water temperature until the fixed li - Fixed high limit test (RTD sensors)
Test the fixed 210°F (99°C) high limit by forcing a call for heat and throttling water flow. The burner should lock out at the limit. Viessmann is not - Fixed high limit test by jumper (alternate method)
Alternate CSD-1 method that runs the boiler at high fire with the boiler valve closed until the fixed high limit trips. - Fixed high limit test simulation #1
Tests the fixed high limit by stopping boiler pump flow while the burner is firing. Follow this only where required by law and accept that overheating - Fixed high limit test simulation #2
Tests the fixed high limit with the boiler valve closed and the flow switch jumpered. - Fixed high limit test, method 1 (boiler pump disconnected)
Simulates an over-temperature condition to check the manual reset fixed high limit. Results in an F2 fault. Do not exceed the limit temperature. - Fixed high limit test, method 1 (CSD-1)
Simulates an over-temperature to check the fixed high limit. Only do this where required by law. The manufacturer is not responsible for damage caused - Fixed high limit test, method 2 (closed boiler valve)
Alternative over-temperature test that relies on the fixed high limit to trip. Only use with care, because the boiler will keep heating. - Fixed high limit test, method 2 (CSD-1)
Second way to test the fixed high limit by running the boiler at high fire with no flow. Only do this where required by law. - Fixed high limit test, simulation #1 (flue gas test with boiler pump unplugged)
Test of the fixed high limit (manual reset) using the flue gas test mode. Pump plug disconnected to let temperature rise. Observe the temperature and - Fixed high limit test, simulation #2 (jumpered flow switch, boiler valve closed)
Alternate high limit test. Boiler valve closed and flow switch jumpered so the boiler overheats until the fixed high limit trips. - Fixed high limit test: manual reset required
After the fixed high limit trips, the boiler control needs a manual reset. - Flame extinguishes during operation (gas strainer)
Flame goes out while the burner is running with no fault code shown. - Flame extinguishes during operation (inlet strainer)
Flame drops out while running with no fault code shown. - Flame extinguishes during operation (no code)
Flame goes out while running with no fault code shown. - Flame goes out during operation (no fault display)
The flame extinguishes while running and no fault code is shown. - Flame still present after shutdown
If a flame is present for more than 15 seconds during the gas valve proof of closure test after shutdown, the flame safeguard goes into permanent lock - Flow rate outside boiler limits or unknown
System flow is above the boiler maximum, below the minimum, or not known. Viessmann recommends a low-loss header in this case. - Flow switch / flow sensor test
The boiler has two flow sensing devices. If flow is too low, they shut the burner down and block restart until flow is restored. - Flow switch test
The boiler has a flow sensing device. If flow is too low, the switch opens, the burner shuts down and it will not restart until adequate flow returns. - Flow switch test (B2HA series)
The flow sensing device opens when flow is too low. The burner shuts down and will not restart until adequate flow is restored. Use this to verify the - Flue blockage or vent leak check
Routine check for conditions that can push flue gas into the structure. - Flue CO2 reading outside range
Measured CO2 is more than 1% outside the target range for the fuel. - Flue gas and supply temperature sensors (self-check)
Both flue gas and supply temperature sensors are double sensors. The control compares the two readings continuously, so a manual check is not needed. - Flue gas odour
Flue gas contains carbon monoxide and can cause life-threatening poisoning. - Flue gas smell
Response when flue gas odour is noticed. - Flue gas temperature switch installation (CM2, PP collectors)
Mandatory on CM2 boilers with PP material collectors. - Flue gas temperature switch wiring (CM2, mandatory for PP material collectors)
Required on CM2 controls with polypropylene collectors. The 150 plug on the control is replaced with the new plug supplied with the switch. - Flue outlet and flue gas test point
Connect the flue outlet to the chimney and provide a test point for combustion analysis. - Flue outlet connection
Connect the flue outlet with the shortest practical run and a slight upward slope toward the chimney. Flue outlet is 12 in. (300 mm) outside diameter. - Flue products entering living space
Improper installation, adjustment, service or maintenance can let flue products flow into the living space. Flue gas contains carbon monoxide. - Flue system and flue gas temperature protection
Approved PPS concentric flue systems for sealed combustion and side wall venting are certified with the boiler. Vertical room-air-dependent venting us - Flue system conditions before commissioning
Commissioning may only start when the flue and air supply conditions are met. - Frame (free-standing) mounting
A boiler stand is used for free-standing installation of one boiler. The stand must be anchored to the floor, and the wall location for the frame, bra - Frame mounting and levelling the boiler
Free-standing installation on the boiler stand or frame. The wall location for the frame, bracket and vents is not supplied and must be calculated in - Frame mounting the boiler on the wall bracket
Steps to mount the boiler to the bracket and frame and level it before connecting piping. - Free-standing boiler stand
The boiler stand is for free-standing installation of one boiler. The wall location for the frame, bracket and vents must be calculated in the field, - Free-standing boiler stand installation
The stand is for a single boiler placed free-standing in the mechanical room. No mounting template is supplied, so the wall location for the frame, br - Free-standing installation on boiler stand
Use the boiler stand when the boiler is free-standing in the mechanical room. No mounting template is supplied; locations must be calculated in the fi - Freeze protection and draining
If the system sees freezing temperatures and is not protected with antifreeze, drain the system including the boiler. Close the valve before the autom - Freeze protection when the system is not filled with antifreeze
If the system can see freezing temperatures and has no antifreeze, the boiler and system must be drained. - Frost protection and central control
Frost protection keeps the supply on the heating curve for the reduced room temperature but never below 50°F (10°C). Central control with coding 7a ap - Frost protection function
Frost protection applies to all heating programs and runs on the outdoor temperature. - Frost protection on heating circuits
Supply temperature follows the heating curve for reduced room temperature, but not below 50°F (10°C). - Fuel and nozzle selection for oil burners
Only use #2 fuel oil. Use the burner supplied by Viessmann, and use only the fuel stated on the burner rating plate. Never use gasoline, crankcase dra - Gas connection and gas train
A field-supplied service gas pressure regulator is required for all installations. Additional components may be required per local code (248-CMR-7:00, - Gas connection and piping
Connect gas per the national or provincial fuel gas code and local rules. Size the pipe for the whole building, including all appliances. - Gas connection and piping installation
Gas piping must be sized for the whole residence. Install the shutoff and drip leg before the boiler and make the gas connection at the 1 in. NPT boil - Gas connection and shutoff valve installation
Set up the gas supply to the boiler with the required shutoff and drip leg. - Gas ignition protection and CO detectors
Local rules govern carbon monoxide detector installation. Ignition components must be kept dry during operation and service. - Gas line connection and purge
Connect and purge the gas supply to the burner gas valve before commissioning. - Gas odor detected at the appliance
Stop all ignition and operation if gas is smelled. Gas is heavier than air and can collect near the floor. - Gas odor response before operating
Safety procedure from the lighting label. Use if gas is smelled near the appliance. Smell low near the floor because LP and natural gas can settle the - Gas odour in the boiler room
Immediate actions if gas is smelled near the boiler. Escaping gas can cause an explosion. - Gas odour procedure
Gas can settle near the floor because it is heavier than air. Do not light any appliance if gas is smelled. - Gas or flue gas smell
Immediate actions when a gas or flue gas smell is detected at the boiler. - Gas piping installation and leak test
Size the gas pipe from the run length, number of fittings, gas type and total input of all gas appliances, following CAN/CSA B149.1 and .2 or NFPA 54 - Gas piping layout and installation
Gas line sizing and installation requirements before connecting the boiler to the gas supply. - Gas piping leak and pressure test
Test the gas supply piping before putting the boiler in service. Isolate the boiler correctly for the test pressure used. - Gas piping leak test and purge
Test the gas supply piping for leaks and purge air before first firing. Never use an open flame to find leaks. - Gas piping pressure and leak test
Tests above 14 in. w.c. (1/2 psig) require the boiler and its shutoff valve to be disconnected from the supply. At or below that level, isolate the bo - Gas piping pressure test
Test gas piping and remove air before the boiler is put into operation. - Gas piping pressure test and leak check
Protect the boiler from high test pressures and check the gas train for leaks after it is connected. - Gas pressure switch 2 fault shutdown (leak test of safety valves)
Gas pressure switch 2 (red, VPS pressure) checks the gas safety valves for leakage each time the burner starts. Excessive leakage causes a fault shutd - Gas shut-off valve connection
Connect the gas supply to the boiler with a manual shutoff valve and close it after the connection is made. - Gas shut-off valve connection and electrical supply
Gas connection sequence at the boiler and the power requirement for the accessory box. - Gas smell
Immediate safety actions if gas is smelled near the boiler. - Gas smell - what to do
If there is a gas smell, do not smoke, do not create flames or sparks, and do not switch lights or electrical appliances on or off. Open windows and d - Gas smell emergency
Response when someone smells gas near the boiler. - Gas smell in the building
Customer-level response when gas is smelled near the boiler. Do not operate any ignition or electrical switches. - Gas smell or flue gas smell
Owner instructions for gas or flue gas odor, to be checked on site with the owner. - Gas smell or gas-leak response at the boiler
Standard response if gas is smelled during start-up or service. Do not operate any switch or phone in the building. - Gas smell procedure
Follow this if gas is smelled at any point, including during lighting. - Gas smell response
If gas is smelled near the appliance, do not light or operate anything. Get people out and call for help from outside the building. - Gas static pressure check
Measure the static gas pressure at the boiler inlet with the burner off. - Gas supply pressure out of range
Running pressure at high fire is outside the allowed band. - Gas train components (NG and LPG)
The gas train includes a manual shut-off valve for each fuel, a combination gas valve assembly, a low and a high gas pressure switch, a fan pressure s - General fault diagnosis procedure
Basic order for working through a fault on the Vitotronic 200 before using the code tables. - General troubleshooting method
Follow this order when the boiler or control is faulty. - General venting installation steps
Route the vent as straight and direct as possible with few bends. Condensate must drain from the flue back to the boiler. Use the vent maker's install - Generic burner control wiring drawing (VD2/VD2A/CT3)
Generic drawing only. Power supply to the burner is not shown. Burner connections must follow the burner manufacturer's connection drawings for Viessm - Generic burner control wiring overview
Generic burner wiring drawing covering the control unit power, 1st and 2nd stage burner, hours counter, fault indicator and safety circuits. It is not - Handling fiberglass wool and ceramic fiber parts
Fiberglass wool and ceramic fiber materials in the boiler can cause cancer risk through inhalation and cause respiratory, skin and eye irritation. - Hang the boiler on the wall bracket
Remove the external accessories connection box cover, loosen the bottom screws without fully removing them, remove the front enclosure panel, hang the - Hang the programming unit in service position (CI2 1500 and 2000)
Frees the interface so it does not get in the way during burner work. - Hanging the boiler on the wall bracket
The boiler is hung on the bracket and then levelled. It must be level both ways so condensate drains correctly. - Heat does not circulate through the boiler
The boiler is blocked by air or the pump or flow sensor has failed. - Heat-up time reduction after reduced operation
When switching from reduced to standard room temperature, the boiler or supply temperature is temporarily raised. - Heating and cooling piping arrangement
Boiler piping when the same system also provides chilled water. - Heating circuit behavior during DHW tank heating
Depends on the DHW priority setting (coding a2). - Heating circuit behaviour during DHW tank heating (priority settings)
How the heating circuits react while the DHW tank is being heated depends on the priority setting. Priority is set at coding a2 in the Heating circuit - Heating circuit control overview (mixing valve circuit)
The desired supply temperature comes from outdoor temperature, set room temperature, operating mode and heating curve. The mixing valve opens or close - Heating circuit control, quick heat-up and quick setback
Heating circuits with mixing valve adjust supply temperature. Quick heat-up and setback apply when room temperature must change by at least 4°F (2 K). - Heating circuit does not start up (Vitocontrol-S)
The heating circuit stays off. - Heating circuit frost protection
With outdoor temperatures below 34 F / 1 C the control keeps the supply temperature at 59 to 72 F / 15 to 22 C for frost protection. The frost thresho - Heating circuit pump behaviour in heating programs
In the reduced or frost-protection programs the heating circuit pumps are switched off when outdoor temperature rises more than 1 °C (1.8 °F) above de - Heating circuit pump economy logic
Heating circuit pump switches off (supply set point 32°F (0°C)) when one of the following is met. Requires no frost risk and coding b0 set to 0. - Heating circuit pump economy shutdown
The heating circuit pump is switched off and the supply set to 32°F (0°C) when one of the economy criteria is met. - Heating circuit remains cold
The heating circuit stays cold even though the system is powered. - Heating circuit supply control and DHW priority
Heating circuit supply is set from the outdoor temperature, set room temperature, operating mode and heating curve. The DHW priority setting decides w - Heating curve basics
The heating curve links outdoor temperature to boiler water or supply temperature. The colder it is outside, the higher the supply temperature. Factor - Heating program enabled or boiler shut down externally
DHW is too hot because the heating program is active or the boiler is shut down by an external device. - Heating pump off after high limit aquastat trip
The aquastat switches the heating circuit pump off when the set limit is exceeded. Because the supply temperature falls only slowly, the system may ta - Heating status is off
The boiler is not receiving a heat call or the control board has failed. - Heating system design version 4: return temperature control with three-way mixing valve
Multi-boiler cascade with a Vitocontrol-S controlling Vitotronic 100 GC1 boiler controls via LON. Used for older heating systems, systems in nurseries - Heating system design version 5: return temperature control with low loss header and three-way mixing valve
Vitorond 200 boilers with Vitotronic 100 GC1, controlled by Vitocontrol-S VD2/CT3/CM2, with a low loss header and a three-way mixing valve. Sensor T1 - Heating system design version 6: heating circuit plus one low temperature heating circuit
Vitocrossal 300 CT3 boilers with Vitotronic 100 GC1, controlled by Vitocontrol-S VD2/CT3/CM2 with outdoor reset, modulating boiler water temperature a - Heating system design version 7: heating circuit plus low temperature circuit with Vitorond on shunt pump
Vitocrossal 300 CT3 as lead boiler and Vitorond 200 VD2 as lag boiler, operated by a Viessmann control system with outdoor reset, modulating boiler wa - Heating system does not start up
The system shows no start-up after power or a switch is applied. - Heating system does not start up (single-boiler)
Boiler and heating system stay off. - Heating system fault on Vitotronic 100
Heating system fault is shown on the Vitotronic 100. - Heating system fault on Vitotronic 300-K
Heating system fault is shown on the Vitotronic 300-K. - Heating system fill water and antifreeze
Treat boiler water where minerals or hardness are high. The boiler suits only closed hot water systems with pumps. Antifreeze is allowed up to a 50/50 - Heating system is off
No heat although the boiler should be running. - Heating system is off while DHW is heating
With DHW heating active, the DHW tank may be heating up first, which holds back central heating. - Heating system on but no domestic hot water
The heating runs but the DHW tank does not supply hot water. - Heating system pressure too low at start-up
Check the system pressure on the pressure gauge before starting. Pressure is too low when the needle is below 15 psi or below the red band. - Heating water and DHW connections
Flush the heating system before connecting the boiler, especially when adding it to an existing system. Field-supplied nipples and tees are used for t - Heating water connections
Flush the system before connecting the boiler, then connect water lines. Do not exceed the maximum operating or test pressure. - Heating water connections and flushing
Flush the heating system thoroughly before connecting, especially on an existing system. Connect supply, return, DHW and drain/fill points as labelled - Heating/cooling changeover with Hydrostat 3250-Plus
Piping example where the boiler is used for both heating and cooling, with a water chiller and changeover valves. - Hydronic piping layout and safety header
Piping rules for the boiler water connections. - Hydrostatic leak test of the boiler
Test before the boiler is connected to piping or power. Do not exceed 1-1/2 times the maximum operating pressure. - Hydrostatic pressure test after section assembly
Mandatory after assembly and before any other piping, controls or safety devices are connected to the pressure vessel. - Hydrostatic pressure test before connecting power and piping
Leak test the boiler water side before it is connected to piping or electrical supply. - Hydrostatic pressure test of the boiler
Pressure test the boiler before it is connected to piping or power. Hold 4 bar (60 psig) for 15 minutes and look for leaks. - Hydrostatic pressure test of the boiler before startup
The boiler must be leak tested before piping or power is connected. Test at no more than 1.5 times the maximum operating pressure. Do not exceed the l - Hydrostatic pressure test of the pressure vessel
Mandatory test after assembly and before any other piping, controls or safety devices are connected to the pressure vessel. Install the sensor well an - Immersion sensor installation in a well
Immersion sensors (KF H / SPF F) are not polarity sensitive. Use them in DHW tank or boiler wells. Smaller wells take only one sensor. - Individual burner combustion air intake ducting
Each burner has its own combustion air intake. Size the ducting from the single intake pipe with the longest equivalent length, which is the one shade - Indoor temperature too hot or too cold at all outdoor temperatures
If the indoor air is too hot or too cold across the full outdoor range, the WWSD setting is probably wrong. The WWSD dial shifts the whole heating cur - Initial BACnet/IP gateway configuration
Connect a laptop directly to the gateway on an isolated network, then open the configuration pages in a browser. - Initial start-up checklist
Complete these checks before starting the system. - Initial system fill and bleed
Flush the heating system before connecting the boiler. Fill with suitable water, bleed all air, and check for leaks before the insulation is fitted. - Initial system fill and freeze protection
Fill and purge the system with the spring-loaded flow check valves open, then close them. Antifreeze use requires care. - Initialization bar keeps running
The remote control cannot communicate with the Vitotronic control unit. - Input variables writable to the gateway
Points the BMS can write to the NR2/LON gateway. Main points are nciMaxSendtime (heartbeat), nciNR2Config (addressing bytes), and zone/cascade DHW set - Insert the boiler coding card
Use only the coding card supplied with the boiler. - Inserting cables and applying strain relief
Cables with moulded strain relief can be used directly. For on-site cables, strip the insulation up to 4 in (100 mm) before installing strain relief. - Inserting the boiler coding card
Only the boiler coding card supplied with the boiler may be used. Otherwise the control will not match the boiler. - Inspect and clean gas inlet filter
The gas connector has a tapered mesh filter. Inspect it visually and clean it carefully. - Inspect and replace burner gasket and cylinder
Check the burner gasket and burner cylinder for damage. Replace the cylinder assembly if damaged. - Inspect and replace burner mesh assembly and refractory
Replace the burner mesh assembly if the wire mesh is damaged. - Inspect or replace air filter accessory
Inspect the air filter visually. If needed, clean it with compressed air or wash it from the outside with soapy water and rinse with clean water. Let - Inspection and maintenance intervals
Service intervals for the boiler, DHW tank and accessories as listed by Viessmann. - Install and check DHW tank temperature sensor
The sensor measures DHW tank temperature. Leave it unconnected on systems without DHW heating. - Install and check the boiler temperature sensor
The boiler water sensor is fitted with the boiler insulation and plugs into socket 3 on the boiler control. Check it by resistance against the tempera - Install and check the DHW tank temperature sensor
Sensor for single-boiler systems with DHW heating. Do not connect it on systems without DHW heating. - Install and check the return temperature sensor
Strap-on or immersion sensor that measures boiler return temperature. Plugs into socket 17A or 17B. - Install and connect the outdoor temperature sensor
Mount and wire the outdoor sensor so it reads outdoor air correctly and is kept away from line voltage. - Install auxiliary low gas pressure switch
Fit and wire the auxiliary low gas pressure switch on the gas line, then set it and leak test. - Install boiler pressure relief and air vent
Set up the safety header and discharge piping on the boiler. - Install boiler safety devices and pressure relief discharge piping
Fit the factory pressure relief valve and air vent, then run the discharge pipe to a floor drain. The discharge must never go outdoors. - Install common combustion air interface on multiple boiler system
Share one combustion air device across several boilers using a common interface. - Install control unit front
Reassembly of the front housing after wiring. - Install DHW pressure relief valve and scald danger label
The DHW relief valve protects the domestic hot water side from pressure built up during DHW heating. The system must be leak tested first, per the boi - Install drain valve and boiler fill / expansion tank
Install the sediment drain valve and the automatic fill with precharged expansion tank as shown in the diagrams. - Install flue gas temperature switch (CM2 only)
Mandatory when PP material collectors are used. The switch is wired through a plug on the control. Replace the existing plug with the one supplied wit - Install flue gas temperature switch (CM2, mandatory for PP material collectors)
Required on CM2 installs that use PP material collectors. - Install modulating valve adaptor and actuator
Use the 120V or 24V valve adaptor matching the actuator. - Install pressure relief valve and high limit (Hydrostat 3250-Plus)
Install the factory supplied pressure relief valve per its own instructions. - Install supply to return bypass on large water content systems
Needed on systems with more than about 1 US gal (3.8 L) of water per 13,000 Btu/h of boiler input, such as older gravity systems with large free-stand - Install the boiler coding card
Only the coding card supplied with the boiler may be used. Without it the control shows fault b7 on the Vitotronic 200 KW2. - Install the boiler return mixing valve or modulating valve actuator (VD2/VD2A/CT3 only)
A 120 V or 24 V valve adaptor is mounted on the DIN rail inside the connection enclosure. Operating time is set on coding address 40 (5 to 199 sec). - Install the boiler water drain valve on each section
A drain valve must be fitted to each boiler section before filling so the heat exchanger can be drained. - Install the cascade communication module
The cascade communication module ships with the system. One module must be fitted into every Vitotronic 200 in the cascade. It links to the Vitotronic - Install the condensate drain
The boiler has a built-in condensate trap, so no external trap is needed when using flexible discharge tubing. Drain must be sloped and must not sipho - Install the condensate drain and siphon
The boiler has a built-in condensate trap. The field drain must be inspectable and must not be fed by other appliances. - Install the control unit front (CM2)
Reattaching the front housing of the CM2 control. - Install the control unit front (VD2/VD2A/CT3)
Reattaching the front housing of the Vitotronic 100 GC1 after wiring. - Install the DHW tank temperature sensor
Fit the sensor on single-boiler systems that heat domestic hot water. Systems without DHW heating must not have this sensor connected. - Install the LON communication module
The LON module plugs into the boiler control board and connects to the LON cable. Remove the control cover first. - Install the RDAC module
If the Versatronik 503 came with an optional RDAC module, fit it before installing the panel. - Install the safety header
Build the safety header with the pressure relief valve, low water cutoff, automatic air vent and temperature/pressure gauge on the boiler outlet. - Install valve actuator adaptor and wire valve
Fit the 120 V or 24 V valve adaptor and connect the actuator. - Install valve adaptor for boiler return mixing or modulating valve
Wiring a 120V or 24V valve actuator through the valve adaptor. - Installation example: DHW storage tank with three zone circuits
Boiler with a DHW storage tank and three zone circuits. Zone 1 is switched from the boiler board, zones 2 and 3 use the AM1 extension module. Outdoor - Installation example: low-loss header with mixing valve circuits
Boiler with a low-loss header, several heating circuits using mixing valves, one circuit without a mixing valve, and a DHW tank. Designs of this type - Installation example: multiple boilers with low-loss header
Up to eight boilers with a low-loss header, several heating circuits with mixing valves, and a DHW storage tank. The piping layout is conceptual only - Installation example: multiple boilers with system pump and isolation valves
Up to eight boilers with a system pump and power-open spring-return boiler isolation valves. The piping layout is conceptual only and must be verified - Installation in marine (salt air) environments
Boilers in damp, salty coastal areas corrode faster on exposed metal parts such as the casing and fan housing. Do not use a direct vent (outdoor air) - Installing a 3-way mixing valve actuator adaptor
Install a 120V or 24V valve adaptor on the DIN rail inside the connection enclosure, then wire the actuator through it. The actuator runtime is set wi - Installing and wiring the outdoor temperature sensor
Mounting and wiring the outdoor sensor to the boiler control board, including cable limits and placement rules. - Installing boiler panels
Panels are installed in a fixed order, starting with the front covers and finishing with the right side panels. - Installing boiler safety devices
Fit the pressure relief valve, drain valve and isolation valve, then pipe the relief discharge to a floor drain. - Installing control and junction box (CM2)
Route cables and capillaries from the control to the junction box and mount the control on the panel. - Installing the boiler panels
Panel reinstallation order after service. - Installing the burner
Reverse of burner removal. Torque values are critical. Check all gas fittings for leaks before startup. - Installing the control modules and programming unit
Mount the control modules on the DIN rail inside the control panel. The layout is shown in the manual. Connect the modules with the supplied cables fo - Installing the KM-BUS Expansion Module
Mount the module near the boiler, connect the accessories, and link the module to the Vitotronic control unit. - Installing the LON module
Fitting the LON communication module to the boiler control board. - Installing the LON module on the boiler control board
The LON module plugs into the boiler control board and connects to the LON cable. Refer to the Vitotronic 200-H HK1B installation instructions for the - Installing the safety (pressure relief) valve
Fit the factory relief valve and gauge on the boiler using a brass adapter. - Installing the safety relief valve discharge piping
The boiler has an ASME approved 30 psi relief valve. The discharge must not be blocked. - Installing the Switching Module-V and connecting it to the control unit
Mount the module above cable ducts using the cable entries in the housing, then connect it to the control unit. - Insufficient heat output
The boiler runs but does not produce full output. - INT boiler disable interlock wiring
The INT input takes a potential-free dry contact. The plant shuts down when the contact is open. Closing the contact allows operation. - Integrating control unit into LON
The LON communication module is factory installed on the Vitocrossal 300 control unit. The Vitotronic 200-H needs the LON module accessory. Cascade co - Interconnection overview of the control inputs and outputs
The overview lists the main connections between the Versatronik 10.WB1, the Vitodens boiler, the DHW tank, the zone controller and the optional Versat - Internal extension EA1 inputs and outputs overview
EA1 has a PCB with fuse F1, digital inputs DE1 to DE3, a 0-10 V input, a power supply for extra accessories (40A), a central fault message output aBJ, - Internal extensions EA1 wiring overview
The EA1 PCB provides digital inputs DE1 to DE3, a 0-10 V input, a power supply for accessories, and output aBJ for a central fault message, feed pump - Isolate the equipment before any work
Before working on the equipment or heating system, switch off the power and stop anyone switching it back on. On gas-fired systems also close the gas - Isolating the boiler before service work
Shut the boiler down and make it safe before opening any panels or components. - Keep combustion and ventilation air free of contaminants
Air used for combustion or room ventilation must not carry corrosive chemicals. Do not install the boiler where chemical exposure is likely. Common so - Keeping lead boiler section valves open
When the burners are off and all boiler section valves are closed, system venting is no longer guaranteed. The lead boiler's section valves can be hel - Known sources of combustion air contaminants
Chemicals and areas that can contaminate combustion air and cause corrosive by-products. Avoid placing the boiler where these are present. - Lag boilers lose contact with lead boiler (cascade)
On a Vitodens 200-W B2HE (85, 120, 150, 199) cascade, the lag boilers lose contact with the lead boiler. What you usually see is that after about 60 s - Layout 1: hydraulic and electrical reference
Example Layout 1 uses a Vitotronic 200 type KW6B control with DHW heating from the boiler and from a solar thermal system. Hydraulic scheme ID 4605300 - Layout 2: hydraulic and electrical reference
Example Layout 2 combines one unmixed heating circuit, one mixed heating circuit with 3-way mixing valve, DHW tank (dual mode) and optional solar DHW. - Layout 3: hydraulic and electrical reference
Example Layout 3 combines one unmixed heating circuit, two mixed heating circuits with 3-way mixing valves, DHW tank (dual mode) and optional solar DH - Leak test on boiler and flue gas path
Check gaskets and components that carry flue gas for leaks while the boiler runs. - Leak testing gaskets and flue gas path
Gaskets on the burner plate and flue gas components can be checked during operation with an inspection mirror. Condensate traces on the flue gas colle - Level and position the boiler
Oil ignition components must be protected from water spray or splashing during operation and service. - Level and site the boiler
Set the boiler level on its adjustable feet. - Lighting and operating instructions (gas appliance with ignition device)
Procedure from the owner label for lighting the boiler and shutting off gas. The boiler has no pilot and lights automatically. - Lighting and operating instructions (gas boiler)
Boiler has no pilot; the ignition device lights the burner automatically. Never try to light the burner by hand. Before operating, smell around the bo - Lighting and operating procedure
The appliance has no pilot. It uses an electronic ignition that lights the burner automatically. - Lighting and shutting off gas to the appliance (label procedure)
Label procedure for the gas supply. The appliance has no pilot; it uses an electronic ignition. Never light the burner by hand and never use tools on - Lighting and starting the appliance
Start-up sequence from the lighting label. The appliance has an ignition device and has no pilot, so do not light it by hand. - Lighting the appliance (ignition device)
This boiler has no pilot. An ignition device lights the burner automatically. Never try to light the burner by hand. - Limit maximum heating input
Heating input can be capped through the modulation range. This does not affect domestic hot water heating. - Limit maximum heating output
Set a cap on heating output using the modulation range. Make sure the heat transfer and flow rate are adequate before you set the limit. Factory setti - LON bus wiring
The Viessmann LON system is a line bus with a terminator at each end (accessories). Viessmann equipment connects with RJ45 plugs. The system uses core - LON bus wiring and cable limits
LON runs in line topology with a terminator at each end. Use only one cable type per LON. - LON bus wiring to the Vitotronic NR2 daisy chain
The Versatronik 503 is wired into a Vitotronic NR2 LON daisy chain. It has two RJ45 (8P8C) jacks that are connected internally, so either port can be - LON cabling for longer runs (continued)
Continuation of the LON layouts with on-site cable and LON plugs or junction boxes. - LON communication interrupted
The control unit shows when LON communication between control units is interrupted. Terminal resistors are required on the first and last control unit - LON communication module installation
The LON module plugs into the boiler control board and connects to the Vitotronic 200-H HK1B system. Refer to the Vitotronic 200-H HK1B installation i - LON daisy chain wiring to Vitotronic NR2
The Versatronik 503 connects into the Vitotronic NR2 LON daisy chain through one of its two RJ45 (8P8C) jacks. Both jacks are linked internally, so ei - LON extension with on-site cable and junction boxes
For extensions up to 900 m / 3000 ft using on-site cable. Up to 99 participants are allowed. - LON network wiring
Viessmann LON uses line BUS topology with end-of-line resistors at both ends. The two wires and shielding are always required; wires are interchangeab - LON participant check
The participant check tests communication between the fault manager and the devices on the LON system. The control must be the fault manager (code 79: - LON participant number and participant list update (single-boiler)
Single-boiler systems only. The LON communication module accessory must be fitted (see p. 111). The LON participant number is set with coding address - LON wiring in line topology
The Viessmann LON system uses line bus topology with an end-of-line resistor at both ends. Two wires plus shielding are always required; the wires are - LON wiring of the gateway to a Vitotronic 300 control
Connect the gateway to the boiler control over LON and supply power. The manual gives 24VAC and 120VAC power options. Use the wiring diagram for the s - LON wiring, 120VAC gateway, Vitotronic 100 / 300 GW2 / 300 GW5B
Wiring layout for the 120VAC gateway on a Vitotronic 100 (GC1/GC1B), 300 GW2 or 300 GW5B control. - LON wiring, 24VAC gateway, Vitotronic 100 / 300 GW2 / 300 GW5B
Wiring layout for the 24VAC gateway on a Vitotronic 100 (GC1/GC1B), 300 GW2 or 300 GW5B control. - LON wiring, Vitocontrol-S CT3/VD2A or Vitotronic 300-K MW1B
Wiring layout for the 120VAC and 24VAC gateway on a Vitocontrol-S CT3/VD2A or Vitotronic 300-K MW1B. The 300-K needs the LON card fitted. - LON wiring, Vitocontrol-S MW2 or Vitotronic 300-K MW2B (Vitodens 200 / WB2B)
Wiring layout for the 120VAC and 24VAC gateway on a Vitocontrol-S MW2 for Vitodens 200 WB2B, or a Vitotronic 300-K MW2B. A communication card is requi - LON wiring, Vitodens 200 WB2B / HO1 / B2HA
Wiring layout for the 120VAC and 24VAC gateway on Vitodens 200 WB2B, Vitotronic 200 HO1 or Vitodens 200 B2HA. - Long shut-down of the boiler
For shut-down over a long period, such as after the heating season, clean the combustion chamber, flue gas collector and vent pipe to prevent corrosio - Long shutdown of the boiler
For a long shutdown, such as after the heating season, clean the boiler to prevent corrosion. - Long shutdown procedure
For a long shutdown, such as after the heating season, clean the combustion chamber, flue gas collector and vent pipe to avoid corrosion. The system m - Louver sizing for combustion air openings
If the free area of louvers is unknown, assume 20% free area for wood and 60-75% for metal louvers. Openings must be made larger to allow for louver r - Low temperature protection packages
A Viessmann low temperature protection package is required. It is normally selected before delivery, so the correct package must be specified at order - Low temperature protection with a 100% boiler flow package
Used in single- and multiple-boiler installations. Confirm pump sizing with the system designer. - Low temperature protection with a 30% boiler flow package
Typical package for single-boiler installations. Required for Vitorond 200 boilers. - Low water cut-off (LWCO) connection, CM2
Wiring of an external low water cut-off device on the CM2 control. - Low water cut-off (LWCO) connection, VD2/VD2A/CT3
Wiring of an external low water cut-off device. The factory jumper must be removed before the device is connected in series. - Low water cut-off (LWCO) wiring
A low water cut-off device is wired to the Power Pump Module. Its jumper must be removed first, and the function must be tested after installation. - Low water cut-off and water connections
A low water cut-off may be required by local codes. If the boiler is above radiation level, an approved low water cut-off must be installed in all cas - Low water cut-off connection (CM2)
Wire an external low water cut-off device to the control. - Low water cut-off connection (VD2/VD2A/CT3)
Wire an external low water cut-off device to the control. - Low water cut-off installation (field supplied)
Some local codes require a remote low water cut-off. The boiler's built-in flow switch may be accepted in its place. Mount the boiler above or below r - Low water cut-off installation (remote-mounted, field supplied)
Some local codes require a low water cut-off (LWCO) on the boiler. The boiler has a built-in flow switch that some local codes accept in place of an L - Lower the fixed high limit to 212 ºF / 100 ºC
Field adjustment of the fixed high limit. Remove power first. Adjustment is permanent. - Main power, pump and room thermostat connections
Main supply is 120V, 60Hz, single phase. Pump, DHW and room thermostat terminals are on the power pump module. The room thermostat anticipator is set - Maintenance message (code 0F)
Maintenance is due. Code 0F appears in the fault display only as a maintenance message and is kept in the error history. - Maintenance message comes back on Monday morning
After a service, the maintenance message can return on the next Monday morning if coding 24 is not reset. This applies to both control units when the - Maintenance schedule overview
Scheduled service for the boiler and boiler room. The boiler must be cleaned at least once a year by a qualified heating technician or service agency. - Make heating water connections
Connect the boiler to the heating system with the supplied fittings. Keep all piping free of load and torque stress. - Making space for accessory adaptors on the DIN rail (CM2 only)
Remove the four spare DIN terminals to free rail space for accessory adaptors. - Manually adjust mixing valve
Use manual adjustment to move the mixing valve by hand. - Manually adjusting the mixing valve
Move the mixing valve by hand, with the motor disconnected. - Manually adjusting the mixing valve motor
Move the mixing valve by hand when the motor is not in use. - Marine or coastal installation venting choice
Boilers in damp, salty coastal areas corrode faster on exposed metal. Do not use direct vent systems that draw outdoor air in these locations. Use a r - Marine or coastal installations
In damp, salty coastal areas, sea spray chlorides plus humidity corrode the casing and fan housing. Do not use a direct vent system that draws outdoor - Massachusetts installation requirements
Special requirements apply when installing in the Commonwealth of Massachusetts. - Match control to a modulating burner
Measure burner output range on a running burner and enter the values in coding 1. The burner must be adjusted first. Keep minimum output as low as the - Match control unit to modulating burner
Measures burner output at the set points and enters the values into coding. The burner must already be adjusted. Set the minimum output as low as poss - Maximum boiler water temperature and mixing valves
Maximum boiler water temperature for space heating and DHW is 194°F (90°C). Use a maximum boiler supply of 194°F (90°C) to reduce distribution losses. - Maximum boiler water temperature and supply design
Maximum boiler water temperature for space heating and DHW is 165 F (74 C) for models 19 and 68, and 180 F (82 C) for models 26 to 57 and 94 to 199. T - Measure gas static and running pressure
Check the gas supply pressure at the gas combination valve before and during startup. Record the readings in the Maintenance Record on page 96. - Measure static and running gas pressure
Check supply pressure at the gas combination valve inlet port A before and during operation. - Mechanical room and installation area conditions
Install the boiler in a heated indoor space near a floor drain and as close to an outside wall as practical so the vent can be run outside. The wall m - Mechanical room prep before installing the boiler
Checks the room and site must meet before the Vitocrossal 200 CI2 boiler is set and connected. - Mixing valve controller accessory kit connection
Accessory kit for a heating circuit with a mixing valve. Only for wall-mounted gas-fired hot water heating boilers that use a weather-responsive contr - Mixing valve extension kit communication lost (emergency mode)
If the PlusBus link to a mixing valve extension kit fails, the affected heating circuit switches to emergency mode after 20 minutes. Until then, the e - Mixing valve motor direction check
During the actuator test, the supply temperature must rise when the mixing valve opens. If it drops, the motor is turning the wrong way or the mixing - Mixing valve motor fault
The mixing valve motor is faulty, so the valve will not control on its own. - Mixing valve motor rotation check
When the mixing valve opens, the supply temperature must rise. If it drops, the motor is turning the wrong way or the valve set is fitted incorrectly. - Mixing valve motor rotation for installation examples
The factory-supplied motor rotation may need to be changed to suit the piping layout. Terminals and pipe labels: HR heating return, HV heating supply, - Mixing valve motor turns in the wrong direction
Mixing valve on an extension kit heating circuit does not respond correctly. The flow temperature rises or falls in the wrong way during the valve che - Mixing valve movement and leak check
Check the mixing valve handle for free movement and for leaks. - Mixing valve moves the wrong way (flow temperature drops when valve is opened)
During a manual test of the mixing valve on an extension kit, the flow temperature sensor reads lower instead of higher when the valve is set to Open. - Mixing valve reduction for return temperature (Circuit Diagram 6)
When return temperature falls below the minimum, the mixing valves are partly or fully closed via sensor T1. - Mixing valve rotation check
During an actuator test of a mixing valve, the supply temperature must rise when the valve opens. If it drops, the motor is turning the wrong way or t - Mixing valves in condensing boiler systems
Low return temperatures are needed for condensing. Avoid mixing valves in the heating circuit when possible. If required (multi-circuit or underfloor) - Modulating valve actuator connection
Actuator for mixing valves. Connect the gS input on A3 or A4 per the overview on pages 58 and 59. - Monthly checks by owner/operator
Monthly inspection items the owner or operator should check. - Monthly operational checks
Routine checks the operator or service contractor should carry out every month. - Monthly operational checks of the heating system
Checks the owner or service person should carry out every month to keep the heating system running safely and efficiently. - Monthly owner checks
Owner or operator performs these checks. - Monthly owner/operator checks
Routine checks the owner or operator should do each month. Record any deficiency for the heating technician. - Monthly owner/operator maintenance checks
Monthly checks performed by the owner or operator. - Mount and wire the 24VAC DIN rail gateway (581D)
The 581D mounts on a DIN rail inside an enclosure. Connection points: 1) control RJ45, 2) paralleled BUS connection, 3) LON terminals A and B, 4) 24VA - Mount and wire the outdoor temperature sensor
Place the sensor where it reads outdoor air and not heat from the building. - Mount oil burner on combustion chamber door
Mount the flange and burner per the burner instructions. For Riello tube insert adjustment, see the calibration chart on p. 38. - Mount the 120VAC gateway (581)
Mount the 120VAC unit near the boiler control it connects to. - Mount the 120VAC Versatronik 501 gateway
Wall-mounted gateway with a plug-in 120VAC power cord, mounted near the boiler control. - Mount the 120VAC Versatronik 505 gateway
Mount the gateway near the boiler control, using the two screws on the base to remove the cover. Fasten the base to the wall with field-supplied faste - Mount the 120VAC wall-mount gateway
Mount the 515 near the connected boiler control. Use field-supplied fasteners. Complete all 120VAC and low-voltage wiring, then refit the cover. - Mount the 24VAC DIN rail Versatronik 501D gateway
DIN rail version that sits inside an enclosure near the boiler controls and is powered from 24VAC. - Mount the 24VAC DIN rail Versatronik 505D gateway
Mount the 505D on a DIN rail inside an enclosure near the boiler controls, then make all connections including the field-supplied 24VAC supply. - Mount the 24VAC DIN-rail gateway
Install the 515D on a DIN rail inside an enclosure close to the boiler controls, then make all connections including the field-supplied 24VAC supply. - Mount the boiler on wall bracket or free-standing frame
Install the wall bracket or stand first, then hang the boiler and level it. The B2HB has no mounting template, so the wall positions for the frame, br - Mount the boiler onto the bracket
Prepare the boiler and hang it on the bracket. Keep the minimum clearances in mind if a CombiPLUS kit is also being installed. - Mount the CombiPLUS on the wall
Use the supplied template and hardware, and set the position to match the flex pipe length in use. - Mount the communication module
Mount the panel near the One Base boiler and wire it with the cover off. - Mount the oil burner on the boiler
Fit the burner to the combustion chamber door using the factory flange, spacer bolts and gasket. Set the burner tube insertion as the burner manufactu - Mount the outdoor temperature sensor
Mount the sensor on a north or north-west wall, 2 to 2.5 m (6.5 to 8 ft) above ground. On multi-storey buildings use the upper half of the second stor - Mount the Vitotronic 300-K control unit
The control mounts on a metal backplate, with a mid plate and connection enclosure between the backplate and the control rear section. - Mount the wall bracket on concrete or brick
The enclosed screws and plastic anchors suit concrete only. Other materials need fixings rated for 115 lb (52 kg). - Mount the wall bracket on wood or metal studs
Wood or metal studs may need a cross bar or frame for reinforcement. The wall and studs must carry at least 115 lb (52 kg). The metal stud pilot hole - Mounting boiler on wall bracket
Hang the boiler on the levelled wall bracket and level it before connecting piping. - Mounting the control
Mount the control on a wall or flat surface near the boiler plant, within reach of a grounded 120 VAC receptacle for the power cord. Do not mount it w - Mounting the control unit
Mounting sequence for the Vitotronic 200-H control unit on a wall. - Mounting the electric boiler
Mount the unit vertically on an even wall with the plumbing connections at the bottom. Keep the required clearances from the mounting diagram. - Mounting the front part of the control unit (CM2)
Reattach and wire the front housing of the CM2 control unit. - Mounting the front part of the control unit (VD2 / VD2A / CT3)
Reattach and wire the front housing of the control unit. - Mounting the front part of the control unit (VD2/VD2A/CT3)
Refit the front housing after wiring. Keep the flat cable and programming unit cable routed through the cable guides in the cover. - Mounting the Versatronik 10.WB1 device
Mount the device on an adjacent wall. The cover comes off by loosening the two screws on either side of the base. Pull out the knockouts you need for - Mounting the Versatronik 300 control
Wall-mount the control near the connected boiler controls, then wire it with the 120 VAC and low-voltage connections before refitting the cover. - Mounting the Versatronik 503 communication module
Mount the module near the One Base boiler, then fasten its base to a wall or the boiler back. Remove the cover to make connections and refit it when w - Mounting the Vitocontrol-S control unit
Wall mounting sequence for the control unit, connection enclosure and midplate on the metal backplate. - Mounting the wall base and fitting the room controller
Mount the base at about eye level and wire it to the boiler OT-BUS. Terminals 1+2 are the bus and can be swapped because the connector is polarity-pro - Mounting the wall base and room controller
Mount the base on the wall at about eye level, wire it to the boiler OT-BUS and optional accessories, then clip the controller top onto the base. Use - Mounting the wall bracket on concrete
The enclosed screws and rawlplugs are for concrete only. Other materials need fixings rated for 155 lb (72 kg). - Mounting the wall bracket on wood or metal studs
Studs must support 155 lb (72 kg). A cross bar or frame may be needed for reinforcement. The metal-stud pilot hole size is not legible in this copy. - Move and unpack boiler without carrying handles
Use this method if the Viessmann carrying handles are not available. Avoid lifting or pushing against panels. - Move the programming unit to the maintenance position
Used to access certain service tasks. Depends on whether the HMI is mounted at the top or bottom. - Multi-boiler return temperature protection (circuit diagram 5)
Shunt pump and isolation valve arrangement for multi-boiler systems with manifold close to the boilers. - Multi-circuit layout with mixing valves and one unmixed circuit
Layout for a boiler with DHW tank, low-loss header, several heating circuits with mixing valves and one circuit without a mixing valve. Viessmann reco - Multiple boiler cascade piping
Cascade systems can have up to 16 Vitocrossal 200 CI2 boilers. Each boiler must be isolatable from the heating system with its own boiler isolation va - Multiple boiler installation (up to eight units) with mixing valves and low-loss header
Multi-boiler layout for models B2HB 45, 57, 160 and 199, with a Vitotronic 300K controller, a low-loss header, a DHW tank and a high-temperature and a - Multiple boiler system (up to eight boilers)
Piping layout for up to eight boilers with mixing-valve heating circuits and a low-loss header. The layout is conceptual only, so piping and component - Multiple boiler system (up to eight units)
Multi-boiler layouts with mixing-valve circuits and a low-loss header need the multiple-Vitodens technical documents and the Viessmann sales represent - No central heating
Causes and checks for when the rooms get no heat. - No DHW (domestic hot water)
Check power, fuel and DHW settings. Also check for a fault display. - No domestic hot water (DHW)
The boiler runs but no hot water is delivered. Check power, fuel, settings and any displayed fault in this order. - No fuel supply
Burner does not run because no fuel reaches the boiler. - No fuel supply to burner
Burner does not fire because fuel is not reaching it. - No fuel supply to the boiler
The burner cannot start because fuel is not reaching it. - No fuel supply to the burner
The burner cannot start because there is no fuel reaching it. - No fuel to burner
The burner has no fuel supply, so it will not light. - No fuel to the burner
The burner does not run because there is no fuel supply. - No hot water
DHW is off because the system is off, settings are wrong, or fuel or a fault is the cause. - No response from the Modbus gateway
The master gets no reply from the gateway. - Oil burner combustion verification
Verify combustion results of the oil burner after start-up. - Oil piping to the burner
Piping must meet local codes, the burner and pump instructions, and CSA B139 in Canada or NFPA 31 in the USA. Oil supply pressure to the fuel unit mus - Open and close the junction box
Procedure to open the junction box to reach the circuit boards, and to reassemble it. - Open the boiler and power pump module for access
Remove the covers to reach the power pump module terminals. - Open the boiler control unit for cascade work
Access the Vitotronic 200 control on each boiler before cascade wiring or module installation. Do this on every boiler connected to the Vitotronic 300 - Open the burner and combustion chamber on CI2 1500 and 2000
Work on the burner only after the gas is shut off and the burner has cooled. - Open the burner and combustion chamber on CI2 399 to 1000
Work on the burner only after the gas is shut off and the burner has cooled. - Open the combustion chamber door
Access the combustion chamber for cleaning or inspection. - Open the control unit
How to open the control for service access. - Open the control unit (CM2)
Access the inside of the CM2 control housing. - Open the control unit (VD2/VD2A/CT3)
Access the inside of the Vitotronic 100 GC1 control housing. - Open the control unit and power pump module
The boiler ON/OFF switch does not disconnect power to the power/pump module. Turn off the main service switch or breaker before opening the module. - Opening the control unit (CM2 only)
Procedure to open the CM2 control housing for wiring or service work. - Opening the control unit (CM2)
Access the inside of the CM2 control unit. - Opening the control unit (VD2 / VD2A / CT3)
Open the control housing for service. - Opening the control unit (VD2/VD2A/CT3)
Access the inside of the control unit for service or wiring. - Opening the external accessories box and control unit
Steps to open the accessory connection box and the control unit for field wiring. - Opening the junction box and moving the control base to service position
Access the wiring area of the control unit. Only needed when the programming unit is at the bottom. - OpenTherm and outdoor sensor connection
OpenTherm is a point-to-point link between the boiler and a room controller. The room unit calculates the heat demand as a water temperature request, - Operating mode overview: weather-compensated vs constant
The contractor sets the operating mode at commissioning. Weather-compensated mode varies supply temperature with outside temperature; constant mode ho - Operating program levels
The operating program is set per heating circuit and has three levels: Heating and DHW, DHW only, and Standby mode. Special programs can be set extern - Outdoor sensor fault appears on Vitodens if sensor is missing
An outdoor temperature sensor fault will always show on the boiler if the sensor is not connected. A resistor can be used in place of the sensor to fa - Outdoor sensor installation
An outdoor sensor enables outdoor reset. Without it, the boiler runs at a fixed setpoint. - Outdoor temperature sensor faults
Boiler operates on a fixed 32°F (0°C) outdoor temperature when the outdoor sensor is faulty. - Outdoor temperature sensor installation
Mount the outdoor sensor 2 to 2.5 m (6.5 to 8 ft) above ground on a north or north-west wall. In multi-storey buildings, mount it in the upper half of - Outdoor temperature sensor installation and wiring
Mount the sensor where it will read outdoor air properly. Use shielded twisted pair if the cable runs near 120/240 VAC wiring, and ground only one end - Outdoor temperature sensor location
Only needed when outdoor reset is used. The sensor is activated only when outdoor reset is enabled in the setup menu. - Outdoor temperature sensor mounting and wiring
Mount the outdoor sensor on the north or northwest wall, away from openings and heat or water sources, and keep it unpainted and unplastered. Keep its - Outdoor temperature sensor wiring
Wire the outdoor sensor to the S1 terminals of the control. - Output variables readable from the gateway
Values the BMS can read from the gateway. These include boiler 1 to 4 actual temperature, return temperature, flue gas temperature, fault code, and re - Outside temperature sensor installation
Mount the outside sensor where it reads true outdoor air. Keep it away from windows, doors and vents, and never cover it. - Outside temperature sensor placement and wiring
Mount the outside sensor on a north or north-west wall about 6.6 to 8.2 ft (2 to 2.5 m) above grade. In multi-storey buildings, use the upper half of - Overheating or gas supply does not shut off
If the boiler overheats or the gas supply fails to shut off, the pump must stay powered. - Overheating or gas supply will not shut off
Emergency shutdown when the boiler overheats or the gas valve does not close. Do not cut power to the pump. Shut off the gas supply at a point outside - Overheating or gas valve fails to shut off
Caution for the case where the boiler overheats or the gas supply does not close. - Overview of electrical connections on the control unit
Main PCB 120 V~ connections: heating circuit pump M1 or primary pump (primary store system), circulation pump for DHW tank heating (accessory), DHW re - Owner instruction checklist
The installer must train the owner on operation, shutdown and the need for maintenance. - Owner monthly checks
Monthly checks by the owner or operator. - Participant check (LON communication test)
Confirms communication between the boiler controls and the Vitocontrol-S system control, one subscriber at a time. - Participant check (single-boiler system, LON error manager)
Checks LON communication between the error manager control unit and the other system units. Only for single-boiler systems with LON. - Perform combustion analysis
Take CO2 readings before and after working on the gas appliance. - Perform combustion analysis and check connections for leaks
Final checks after service or start-up. - Periodic checks by heating technician
Items to check at periodic intervals. - Periodic heating contractor checks
Checks to be made periodically by the heating contractor. - Periodic heating technician checks
Checks to do periodically, not necessarily every year. - Periodic service checks by heating technician
Checks to perform periodically by the heating technician. - Pipe the boiler water connections (Hydrostat 3250-Plus)
Boiler is for closed loop, forced circulation hot water systems only. Flush the system before connecting the boiler, because sludge can settle in the - Piping connections and shutoff valves
Supply and return must not be reversed. Shutoff valves go below the inlet and outlet connections. - Piping example: heating/cooling with Hydrostat 3250-Plus
Boiler used for both heating and cooling with a chiller. Valves v1 and v2 switch between seasons. - Piping examples with Vitotronic controls
Layouts for Vitotronic 100 and 200 controls with and without mixing valves and domestic hot water. - Piping for expansion tank, fill and system layout
The precharged expansion tank and any automatic fill piping may connect to the suction side of the boiler or system pumps. Other placements depend on - Piping for heating and cooling applications
When the boiler is used with a chiller or cooling coils in air handlers, the piping must keep chilled water out of the boiler. - Piping layout: direct-connected heating circuit plus one system-separated circuit
Boiler with one direct-connected heating circuit and one circuit separated by a plate heat exchanger, with DHW storage. The radiator circuit runs off - Piping layout: multiple heating circuits with mixing valves and low-loss header
Boiler with DHW storage tank, low-loss header, several mixing-valve heating circuits and one circuit without a mixing valve. Viessmann recommends cont - Piping layout: three zone circuits with low-loss header
Boiler with DHW storage and three zone circuits. Total zone flow is above the boiler's maximum flow, so a low-loss header is required. - Piping the boiler for heating/cooling (chilled water) use
When the boiler works with a chiller, the chilled medium must be piped in parallel with the boiler using valves that keep chilled water out of the boi - Piping the boiler in a heating/cooling system with a chiller
When the boiler shares a system with a chiller, the chilled water must be piped in parallel with the boiler and isolated by valves so chilled water ca - Placing and levelling the boiler
Set the boiler on its base and level it. - Plain-language fault messages
These faults show as text on the programming unit instead of a code. - Plug in LON communication module
Seat the LON module in the control unit. The LON wiring itself is covered elsewhere in the manual. - Plug in the LON communication module
Insert the LON communication module into the control unit as shown in the illustration. Then make the LON connection. - Plumbing connections and shutoff valves
Inlet return (blue label) and outlet supply (red label) must not be reversed. - Poor WiFi connection to the boiler
Signal can be weakened by walls, ceilings, metal and nearby electronics. - Positioning and levelling the boiler
The boiler must sit on a load-bearing foundation that allows for a neutralisation system connection. Levelling feet must be used once the boiler is in - Power supply connection to the control
The control needs 120 VAC, single phase, 60 Hz, with grounding. Overcurrent protection of at least 6 A and a 2-pole disconnect must be on the supply. - PP(s) and CPVC vent system limits
PP(s) vent is flame-retardant polypropylene rated to a maximum of 230 F (110 C) and must be listed to ULC S636 or UL 1738. Do not mix pipe, fittings, - Pre-start checks before first firing
Checks to complete before the burner is started. - Pre-start-up checklist
Confirm the system and boiler are ready before the first firing. - Pre-test checks before high limit safety cut-out test (CSD-1)
Checks to make before testing the boiler high limit controls. Viessmann says the high limit is set at a fixed 210°F (99°C) and needs a manual reset af - Prepare CombiPLUS connections and fittings
Fit the extension fittings and system connection adaptors to the CombiPLUS before mounting it. - Prepare the power pump module for CombiPLUS
Remove the parts that block CombiPLUS operation and the room thermostat jumper, using static-safe handling. - Preparing heating, gas and DHW connections
Connections are made in the field and need approved pipe sealant or teflon tape. The boiler has heating supply and return, gas (1 in. NPTF), condensat - Preparing the boiler for burner service
Removing top panels and upper frame profiles to access the burner. Screw count differs by model size. - Preparing the boiler for service work
Before any installation, adjustment, service or maintenance, cut all power so the boiler, heating system and external controls cannot start. Shut the - Preparing the install and electrical work
Electrical work must be done by a qualified electrician under local codes. Power and water must be off during installation. - Preparing to work on the system
Make the boiler safe before any service work. Only licensed professionals may work on gas, and qualified electricians on electrical parts. Electronic - Pressure relief valve discharge piping
No valve may be installed between the pressure relief valve and the boiler. Discharge piping must be sized and routed per the ASME code and drained sa - Pressure relief valve installation
Install the factory-supplied approved pressure relief valve on the boiler water supply connection. Do not put an isolation valve between the boiler an - Pressure relief valve piping
Mount the pressure relief valve on the top of the boiler or on the boiler safety supply. Do not install valves, shut-offs or obstructions between the - Preventing oxygen corrosion in the heating water
Oxygen in the heating water causes corrosion. Keep the system sealed and at positive pressure, and avoid gas-permeable components. - Preventing oxygen-related corrosion in heating water
Oxygen in the heating water causes corrosion of ferrous parts. Keep the system pressure above atmospheric at every point, including the pump suction s - Primary circuit flow and low-loss header
The boiler is for closed-loop, forced-circulation hot water systems only. A low-loss header is strongly preferred. - Primary pump placement for DHW storage tank layout
In system layout 3 the primary pump must pump into the boiler, as illustrated in the manual. The boiler is paired with closely spaced tees or a low-lo - Primary/secondary piping arrangement
Use primary/secondary piping when system flow rates are higher than the boiler's stated flow rate. A low loss header is shown in the layout. - Prolonged shutdown: what to expect on restart
Pumps can seize if left unpowered, and the clock may need resetting after a long power-off. - Protecting the building when unattended in freezing weather
The boiler is not designed to prevent water pipes from freezing. If it stays off during cold weather, pipes can burst. - Protecting water pipes when the home is unattended in freezing weather
The boiler is not designed to prevent freezing of water pipes. If it stays off for a long time in cold weather, pipes can freeze and burst. - Protection against freezing
If the system can freeze and is not protected with antifreeze, drain the system and boiler. Close the valve before the automatic feed valve, if fitted - Provisional burner operation with external dry contact (BMS)
Use this to hand heat demand and modulation to an external controller. - Pump connections on A3 and A4
Pump options available on outputs A3 and A4. Wire according to the overview on pages 58 and 59 and the control panel wiring diagram. - Pump outputs and AM1 extension module
The boiler supports a maximum of 2 zone circuit pumps. Any further pumps require the AM1 extension module. Pump output assignment is made in the start - Pump outputs not powered
The unit has power, but the space heating or DHW pump outputs stay off. - Pump sizing and pressure drop check for zone loops
The page shows a pressure drop versus flow chart for CU3A 94/125 and CU3A 160/199 with flow in m3/h and USGPM and pressure drop in inches w.c. and kPa - Pumps do not switch off
Heating pumps keep running when they should stop. - Pumps run continuously
The boiler pump keeps running even without a call for heat. - Raising return temperature with a shunt pump (circuit diagram 3)
Shunt pump control to keep the boiler return temperature above the required minimum. - Re-install boiler, power pump module and CombiPLUS covers
Order for refitting the covers after the CombiPLUS wiring is done. - Read and acknowledge a fault on the programming unit
A fault flashes the red fault indicator and shows 'Fault' on the display. The display shows the fault number (1 to 10), the fault code, the fault symb - Read ionization current through the burner control
A multimeter cannot read ionization current. Use the burner control display sequence instead. The current should be at least 3 μA for 2 to 3 seconds a - Read temperatures and quick scans
Lists the values that can be read, depending on the equipment fitted: slope and shift for M1/M2/M3, outdoor temperature (set and actual), sensor 17B, - Read the boiler section home screen
The home screen shows the header, the actual and set boiler section water temperatures, the boiler section number, and the operating-mode details. The - Read the cascade default display
Cascade display shows each participant, its current and target supply temperature, modulation level and ID number. The lead boiler is marked with a st - Read the main screen and boiler status screens
The main screens scroll through system temperatures and then one status screen per boiler. Each boiler screen shows its LON address, ON or OFF status, - Reading a fault cause on the Vitotronic 300-K
Shows how to read the cause text and fault code on the 300-K. Built-in help gives measures the operator can take before calling the contractor. - Reading a fault code on the control unit
A fault shows in the display and by a flashing red fault indicator. The fault code can be read from the fault search and the display shows the error s - Reading the brief scan
The brief scan shows 9 lines with 6 fields each: software versions, system type, KM BUS participants, mixing valve and remote control types, pump type - Reading the error number on the Display menu
The System display shows an Error number. 00 means no error is present. Any other value points to an active fault that should be looked up in the faul - Reading the home screen and boiler section status
The home screen shows the header with actual and set boiler section water temperatures, the boiler section number, operating mode details, and the foo - Reading the lightguide status
Pulsing slowly: display is in standby. Constant light: control unit is being operated; each input gives a brief flash. Flashing quickly: a fault is pr - Recharge is shown on the display
The display asks for fuel to be added. - Recommended application by supply temperature
The guide rates each emitter type (baseboard, cast iron radiator, panel radiator, radiant floor, indirect DHW, air handlers) by typical supply tempera - Recommended multi-zone hydronic layout with DHW tank and low-loss header
Reference layout for a Vitodens 200-W with a DHW storage tank, a low-loss header and three zone circuits. A low-loss header is strongly recommended an - Reducing boiler height before placement
Steps to lower the boiler height so it fits into the space. Panels, upper frame and burner can be removed. - Refit burner after inspection
Refit the burner in the reverse order of removal (see pages 27 and 28). Tighten to the torque values listed for the burner and gas connections. - Refit burner and check all gas equipment for leaks
Final check after burner refit. Only use approved leak detection products and remove residue afterward. - Refitting the junction box lid, control base, front panel and programming unit (programming unit at bottom)
Reassembly order when the programming unit is mounted at the bottom. - Reinstall burner
Refit the burner with the specified torques, then check the gas connection for tightness. - Reinstall the burner assembly
Refit the burner with the specified torques, then perform a gas leak test. - Reinstall turbulators and close the boiler
Seat the turbulators correctly and close the door evenly. - Reinstalling the boiler panels
Panel install order after service. The top panels use different screw counts depending on size. - Reinstalling the burner after service
Burner refit sequence with torque values and gas connection checks. - Reinstalling the front enclosure panels
Refit the front panels in order. Read and follow the safety labels on the boiler. Do not run the boiler without the front cover in place. - Relay output test and sensor check
Tests the actuators and checks the sensors during start-up. - Relocate top back panel screw for easier removal
Moves the top panel screw so the panel can be removed without problems later. - Remote heating on via telephone switch
A remote contact can force heating on from the controller input. - Remote telephone switch wiring
The remote switch must be a dry, potential-free contact. Applying voltage to it will damage the controller. - Remove and clean turbulators
Turbulators are fitted on VD2-320 to VD2-860 only. - Remove and refit the burner fan
The fan is removed with the Venturi pipe and gas valve attached. - Remove and reinstall the burner assembly
Procedure to remove the burner for service and reinstall it with the correct torque. - Remove and reinstall the top back panel
The top panel screw can make the panel hard to remove. Move the screw to a new hole to make removal easier. - Remove burner and check burner gasket
Burner removal for inspection and cleaning. Hook the burner into its service retainer, not on its dome matrix. - Remove front enclosure panel
Some service steps need the front panel off. Shut off the gas first. - Remove front enclosure panel and fill condensate trap
Required before some service steps. Gas must be shut off first. The condensate trap is filled with water before the first start. - Remove front panel and burner
Isolate power and gas before service. Do not lay the burner on its cylindrical tube. - Remove front panels (CI2 1500 and 2000)
Panel removal sequence on the large models. - Remove front panels (CI2 399 to 1000)
Access to the BCU and control unit on smaller models. - Remove front panels and open the control unit
Some service steps need the front enclosure panel removed. Close the main gas supply line first. - Remove front panels and set the boiler level
Front panels come off in sequence, then the boiler is moved into position and leveled. Level is needed so condensate drains properly. - Remove the boiler front panel
Gives access to the boiler for flue and air connections. - Remove the burner (CI2 399 to 2000)
Burner removal for service. Burner weights: 399/500 MBH 25 lb (11.3 kg); 750/1000 MBH 35.5 lb (16.1 kg). - Remove the burner assembly
Remove the burner for inspection or cleaning. Do not lay the burner on its cylindrical tube or touch the tube mesh. - Remove the burner tube and mounting plate
A lifting device is required. Secure the lifting chains at the 3 marked points on the frame of the upper burner section. - Remove the front enclosure panel
Needed for many service steps. Close the main gas supply valve before starting. - Remove the hydraulic unit (B1HE/KE 150/199)
Procedure to pull the hydraulic unit for repair on the 150 and 199 models. Install in reverse order. - Removing an existing boiler from a common vent
Checks to run when an existing boiler is taken out of a shared vent with other gas appliances, so the remaining appliances still vent safely. - Removing boiler panels
Panel removal order for access to the boiler. Top front panel and cover plate apply to CA3B 5.0 and 6.0 only. - Removing the boiler panels
Panels must be removed in the order the manual gives to avoid damage and to keep the screws organized. - Removing the burner
Burner removal for service. If the programming unit is at the top, lower it into the maintenance position first (see p. 46). Same procedure for B1HE/K - Removing the controller from the wall base
Lift the controller top off the base to service the wiring or base. - Removing the front panels and levelling the boiler
Remove the front panels to reach the connections and the leveling feet. - Removing the hydraulic unit (B1HE/KE 150/199)
Removal sequence for the hydraulic unit on the 150 and 199 models. - Removing the hydraulic unit (B1HE/KE 85/120)
Removal sequence for the hydraulic unit on the 85 and 120 models. - Removing top panels and upper frame for burner access
Panel removal needed before burner work. Screw count differs by size. Upper frame profiles must come off to remove the burner. - Replace 2/2-way solenoid valve (choke valve)
Choke valve on the CM2 186 burner. The solenoid energises for about 5 seconds during ignition to add fan pressure to the gas regulator for a smoother - Replace air pressure switch
Replace the air pressure switch on the burner control bracket. - Replace air pressure switch (LDW1 / LDW2)
LDW1 is the fan air pressure switch and LDW2 is the combustion chamber air pressure switch. Set the new switch to the same value as the old one. - Replace air pressure switch and compensation hose (LDW1/LDW2)
LDW1 is the fan air pressure switch and LDW2 is the combustion chamber air pressure switch. The new switch must be set to the same value as the one it - Replace BCU or HMU
If the burner control unit (BCU) or heat management unit (HMU) is replaced, the replacement must be done with the ViGuide software tool. Incorrect cab - Replace boiler secondary temperature sensor
The secondary sensor sits in a sensor well on the boiler section pressure vessel. Its connecting plugs are at the burner control unit for that section - Replace boiler secondary temperature sensor (15 A / 15 B)
The boiler secondary temperature sensor sits in the pressure vessel of each boiler section. Its connecting plug is at the burner control unit for that - Replace boiler water temperature sensor
Swap the boiler supply sensor and seat it at the correct depth. - Replace boiler water temperature sensor (3A / 3B)
Each boiler section has its own boiler water temperature sensor in a sensor well. Replace the sensor for the affected section. - Replace boiler water temperature sensor (3A/3B)
Each boiler section has its own boiler water temperature sensor in a sensor well. Sensor cable plugs 3A/3B connect it. - Replace burner control coding card
Swap the coding card so it matches the burner control. - Replace burner control programming unit
Swap the programming and display unit. - Replace burner control sub-base
Remove the sub-base and refit it. - Replace burner control unit
Replace the burner control unit on the boiler. Remove the display and programming unit and the coding card to access it. - Replace burner door
Full burner door replacement, including fan, venturi and gas train removal. - Replace burner fan
Burner fan and venturi assembly. Not for the CM2 186. - Replace burner tube
Burner tube and retaining ring with gasket A. - Replace combustion fan
Fan removal with the Venturi pipe and gas valve. - Replace DIN rail fuse F1
Fuse block is on the DIN rail. Check the separate wiring diagram for fuse location. - Replace fan
The fan is removed together with the Venturi pipe and gas valve. Fit the gasket in the correct position. - Replace flow rate sensor
In the event of a fault, both flow rate sensors must be replaced. - Replace fuse F3 on the DIN rail fuse block
Access and replace the 120V line out fuse F3 in the junction box. - Replace gas solenoid valve or BCU on a lag boiler
On lag boilers the gas solenoid valve and the BCU cannot be replaced directly with the ViGuide app. - Replace gas valve
Install the new valve in the same orientation as the original. The gas pressure switches GDW1 and GDW2 are on the valve assembly. - Replace gas valve (LPG)
Gas valve swap on a boiler set up for propane, including the LPG orifice and gaskets. - Replace gas valve (natural gas)
Remove and replace the NG gas valve on the manifold, then leak test. - Replace gaskets and gas valve
Gas valves are replaced at the end of their service life, and a warning is issued when this occurs. Elastomer gaskets on the fan, gas line and flue co - Replace ignition cables
Ignition cables run from the ignition unit to the ignition electrodes. - Replace ignition electrode block
Replaces the ignition electrode block and gasket on the burner door. - Replace ignition unit
The ignition unit is mounted on the burner. Reinstall in reverse order. - Replace ignition unit and ignition cables
Ignition unit removal and ignition cable replacement. - Replace inlet damper linkage
Linkage between the inlet damper bracket and the servomotor. Equipped on CM2 246 and 311 only. - Replace inlet damper servomotor
Servomotor for the burner inlet damper. Equipped on CM2 246 and 311 only. - Replace internal control fuse F3
Fuse F3 sits in the DIN rail mounted fuse block. Check the separate wiring diagram for its location. - Replace ionization electrode block
Replaces the flame sensing electrode block on the burner door. Use only the new parts from the kit. - Replace main PCB
Keep the current settings before swapping the main PCB, then restore the required codings. - Replace motorized burner inlet damper
Removal of the motorized damper together with its servomotor and linkage. Equipped on CM2 246 and 311 only. - Replace plug console with relay
Plug console that carries the relay contactor. - Replace rotary damper and servomotor
For CA3B 3.5 to 6.0, the rotary damper must be fully open when the burner is off and while it runs. An incompletely open damper can cause malfunction - Replace solenoid valve (2/2 directional valve)
Solenoid valve replacement on CA3B 2.5 and 3.0 models. - Replace the adjustable high limit
Replacement procedure for the adjustable high limit. - Replace the boiler temperature sensor
Sensor sits in the boiler supply connection. - Replace the DIN rail fuse F1
Replace fuse F1 on the DIN rail fuse block in the junction box. Check the separate wiring diagram for the fuse location. - Replace the fixed high limit
Replacement procedure for the fixed high limit. - Replace the flow limiter
Water can leak when the flow limiter is replaced. Shut off the cold water supply and drain the DHW line and the plate type heat exchanger (DHW side) f - Replace the ignition cables
Ignition cables connect the ignition unit to the ignition electrodes. - Replace the rotary damper and servomotor
Remove and refit the rotary damper, air pressure switch and servomotor as one assembly. The damper must be fully open when the burner is off and durin - Replacing a boiler water temperature sensor
There is one boiler water temperature sensor on each boiler section. - Replacing the burner control unit
Burner control unit removal and installation. - Replacing the burner door
Removes the fan, venturi, gas train and burner control from the burner door, then swaps the door. Leak test the gas line after reconnecting it. - Replacing the burner door refractory
Removes the refractory, rope seal and insulation from the burner door. Refit with the same torque as the burner door. - Replacing the burner fan
Removing the fan and Venturi pipe with gas valve, then refitting. - Replacing the coding card or display and programming unit
Coding card and display replacement on the burner control unit. - Replacing the display and programming unit or coding card
Access the burner control interface and swap the coding card or display unit. - Replacing the PC board
Procedure for swapping the Vitocontrol-C PC board, including how to restore the model-specific coding. - Replacing the plate heat exchanger (B1KE)
Removal, inspection and refitting of the brazed plate heat exchanger. - Replacing the printed circuit board (cascade electronics)
Replacement of the cascade electronics printed circuit board. Record and restore settings. - Replacing the rotary damper and servomotor
Removing and refitting the air damper assembly on the burner. - Replacing the supply air filter (room-air-dependent operation)
Access and replace the air filter in the top right panel. - Required settings check for central heating
Checklist to confirm before the customer is left with central heating running. - Reset after auxiliary low gas pressure switch fault
The burner stops and fault C1 is shown when gas pressure falls below the switch setting. - Reset all passwords to factory settings
Requires the master password, which must be requested from Viessmann Technical Service. The manual lists the steps in two different orders; follow the - Reset manual reset temperature limit switches
The supply water and flue gas temperature limit switches lock out mechanically when the probe temperature goes over the limit. The switches are factor - Reset the Service display after maintenance
Clears the Service message and resets the service interval. If service is done before 'Service' appears, set coding 24:1 first, then 24:0; this resets - Reset the time and date
Time and date are preset at the factory and can be changed. - Resetting the service display after maintenance
The service display is cleared by changing coding 24. If coding 24 is not reset, the service display comes back on Monday morning. - Restore factory settings
On the 300-K, factory settings can be restored one heating circuit at a time. Restoring them resets the room temperatures, heating program, DHW temper - Retrieve and acknowledge faults
A red fault indicator flashes when a fault is active. The fault display shows the fault message, fault code and fault number (1 to 10). Acknowledging - Return temperature control with shunt pump and return valve
Used where the distributor is close to the boiler and boiler water flow must be reduced. - Return temperature protection with shunt pump (Circuit Diagram 5)
Sensor T2 switches on the shunt pump when return temperature falls below the minimum. If the minimum is still not reached, reduce supply at least 50% - Return valve control for return temperature (circuit diagram 4)
Return valve method for systems with no way to change the downstream heating circuits, such as older systems. - Return valve protection with low-loss header (Circuit Diagram 8)
When return temperature falls below the minimum, the return valve on the boilers closes proportionally via sensor T1 to protect the boiler. - Return valve protection with mixing valve (Circuit Diagram 7)
When return temperature falls below the minimum, the 3-port mixing valve on the boilers closes proportionally via sensor T1 to protect the boiler. - Reverse mixing valve motor rotation direction
Only if the rotation direction is wrong. - Reversing the mixing valve motor rotation
Used when the mixing valve must turn the other way for the installation. The motor plug is turned 180° to reverse rotation. - Reversing the mixing valve motor rotation direction
Use this when the mixing valve turns the wrong way. - Riello burner red wire
The red wire is not used in this application. - Room air dependent combustion air supply
Provide enough fresh combustion and ventilation air in the mechanical room. The room should never be under negative pressure. Exhaust, attic or dryer - Room not warm enough at low outdoor temperature
The room stays too cold when it is cold outside. - Room temperature not satisfactory at low outside temperature
Rooms are too cold when it is cold outside. - Room thermostat dry contacts for zone circuits 1 to 3
Each zone circuit room thermostat connects as a dry contact to the integrated EA1 module in the boiler. - Rooms are too cold
Heating is off or the control or remote settings are wrong, or there is no fuel. - Rooms are too cold or too hot: settings and error check
The page layout does not clearly show which causes belong to too cold and which to too hot. The listed causes are settings and error messages. - Rooms are too hot
Control settings are wrong, a fault is active, or emissions test mode is still on. - Rooms cold during the day and warm at night
The room temperature is reversed relative to the time of day. - Rooms cold during the day but warm at night
The heating timing does not match the day and night pattern. - Rooms cold while burner is operating (multi-boiler)
Burner runs but the rooms do not heat properly. - Rooms cold while burner is operating (single-boiler)
Burner runs but the rooms do not heat properly. - Rooms cold while burners are operating
The heating is running but the rooms stay cold. - Rooms cold while the burner is running
The burner runs but the rooms stay cold, even with a low outdoor temperature. - Rooms not heated although the burner is running
The burner runs but the rooms stay cold. - Rooms stay cold while the burner is operating (multi-boiler)
The burner runs but the rooms do not heat. Two possible causes are a heating program set to '9' or a domestic hot water tank that has priority. - Rooms too cold
Work through these causes in order. The control unit may be off, misset, or faulted, or the mixer motor may be stuck. - Rooms too cold at low outdoor temperature
The room temperature does not rise enough when outdoor temperature is low. - Rooms too hot
Usually a setting problem. A control unit fault or a faulty outside temperature sensor can also cause it. - Rotating segments in the display
The display segments keep rotating and the remote control does not respond normally. - Route and secure connecting cables
Cables must not exceed their rated temperature and must not touch hot components. Low-voltage, 120 V and DHW sensor leads are separated in the box. - Route and secure field wiring to the control base
Field cables go to their areas and are clamped at the existing strain reliefs on the control base. - Route and strain-relieve control cables
Cables run from the junction box into the control unit and need strain relief at the control. - Route boiler flue (venting) through wall or roof
Single-wall or coaxial venting can exit through the side wall or the roof. The boiler ships with a pre-installed vent adaptor. - Route cables and mount the CM2 control and junction box
Installing the CM2 control and its junction box on the control panel and rear panel. - Route PlusBus cable
PlusBus cable must stay away from line voltage. - Route power and pump accessory cables
Power and pump accessory cables come out of the accessory connection modules. - Route the pressure relief valve discharge
The relief valve discharge must be at least the outlet size, run horizontally over the side of the boiler, then drop vertically to about 1 ft (300 mm) - Route wiring into the control unit
Bring field wiring into the control unit through the rear jacket. - Routine cleaning and maintenance
Maintenance intervals from the owner guide. Only qualified or authorised contractors should carry out internal work. - Routine maintenance and cleaning
Cleaning and maintenance schedule for the system. Service is required at least every 2 years by an authorized contractor. - Routine maintenance items for the user and contractor
Maintenance items listed for the system user and heating contractor. - Routing and securing connecting cables
Cables that touch hot components will be damaged, so keep them clear of heat sources and stay within the cable temperature rating. For larger cross-se - Routing and securing field connecting cables
Cable routing rules for low-voltage and 120 V connections inside the control unit. - Routing and strain relief of cables
Route the cables into the control unit and secure each cable so it is not pulled on at the terminals. - Routing low voltage and 120 V cables
Keep control wiring clear of line voltage and hot parts. - Routing power and pump accessory cables
Cables from the accessory connection modules under the boiler run through the boiler frame and out the openings at the back of the jacketing. Cables a - Run a brief scan of system data
Brief scan shows temperatures, software versions and connected components on a 9 line by 6 field display. - Run a LON participant check
Tests communication between the fault manager and the connected system devices. - Run a participant check on the LON network
Confirms that a participant on the LON network answers from the boiler control side. Use it to verify communication after addressing. - Run and connect the oil supply piping
Route the oil line to the burner and tank with the right fittings, so that the tank can settle and the burner door can still swing open. - Run and strain-relieve control cables
Cables run from the connection enclosure into the control unit and must have strain relief. - Running cables and applying strain relief
Cable routing from the connection enclosure into the control unit, with strain relief on each cable. - Safety connections (Vitotronic control)
Install the return water injector combination and the pressure relief valve. Minimum pressure relief valve and discharge pipe size is 3/4 in. The boil - Safety relief valve and discharge pipe installation
Install the factory-supplied pressure relief valve and its discharge piping so it cannot scald people or trap pressure. - Scan operating conditions
Shows the live status of the system. Available items include participant number, holiday program, actual outdoor temperature, sensor 17B, DHW temperat - Scan operating data (Vitotronic 200)
Operating data is scanned in the service menu. Detailed steps are in the Vitotronic 200 operating instructions; the relevant boiler is the Vitodens se - Scan operating data (Vitotronic 300-K)
Operating data is grouped by area. Data for heating circuits with mixing valves and for solar can only be read if those components are installed. A '- - Scan operating data and sensor temperatures
Use the Diagnosis menu to read live values by group. A value of - - - on the display means the scanned sensor is faulty. - Scan temperatures and operating status
Read current temperatures and status values on the control unit. Which items appear depends on the connected components and settings. Items include ou - Scanning and acknowledging fault messages
A fault shows the flashing fault symbol and "Fault" on the display, and the red fault indicator flashes. Record the fault code before acknowledging. - Scanning fault messages
A fault has occurred on the heating system. The fault symbol flashes and Fault appears. Write down the fault code before calling service. - Scanning service messages
A service message is due. The service symbol flashes and Service is displayed. - Seal test for flue gas leaks during operation
Leak check of burner door and flue gas components while the boiler runs. Viessmann says to check with the boiler at operating temperature. - Seasonal valve changeover (heating and cooling)
Valve V1 feeds the boiler for heating and valve V2 feeds the chiller for cooling. Change them at the start of each season. - Select heating circuit before settings or scanning
On systems with two or three heating circuits, the right circuit must be selected before each setting or scan. Otherwise the display asks for it. - Select heating circuit pump and primary piping
Boiler is for closed loop, forced circulation hot water systems only. Pump sizing must be based on accurate flow and pressure drop calculations, inclu - Select the display language
Changes the language shown on the display. - Select the heating circuit before making central heating settings
In systems with several heating circuits, the circuit must be chosen before central heating settings are changed. Single-circuit systems do not offer - Selecting the heating program (winter, summer, DHW only, standby)
Heating program is chosen with the program button. The lit button and a short display message confirm the selection. Each mode is listed below as the - Sensor connections overview
Sensors wired to the control unit in this layout. The two optional DHW and return sensors are not used. - Sensor diagnosis on Vitotronic 300-K
Actual sensor temperatures are read from the diagnosis group. - Separate neutralizing system drain hose
Used when a neutralizing system is installed. - Separate the neutralizing system
Disconnect the neutralizer from the boiler siphon before cleaning the condensate path. - Service (maintenance) display
The Service message and symbol appear once the hours-run or time limits set in coding 21 and 23 in the Boiler group are reached. The limit values are - Service clearances and closet or alcove install
Viessmann recommends the service clearances shown in the manual illustration. The side clearance of 12 in. (305 mm) lets you read the rating plate and - Service display appears on controller
The Service display appears when the hours run or time interval limit set in codes 21 and 23 is reached. The red fault indicator flashes and Service s - Service display: acknowledge and reset
When the hours or time limits in coding 21 and 23 are reached, the red fault indicator flashes and the programming unit shows the Service message. Ack - Service displayed
A scheduled service is due, as set by the heating contractor. - Service due
The service interval set by the heating contractor has been reached. - Service due indicator
A service indicator appears on the Vitotronic 200 when the service time set by the heating contractor has arrived. The indicator symbol itself is not - Service due message (Vitotronic 200)
After a set number of burner hours the service symbol flashes on the display. The Vitotronic 300-K has no service interval setting and shows no servic - Service interval message on the display
After the service limits in coding addresses 21 and 23 are reached, the red fault indicator flashes and the display shows Service with the service sym - Service is displayed
The display shows Service because the service date set by the heating contractor has arrived. - Service menu overview (service level)
Menu items available in the service level, as listed in the service menu overview. - Service menu structure
The service level has these top-level groups: Diagnosis, Actuator test, Coding level 1, Coding level 2, Fault history, Service functions, Terminate se - Service message is displayed
Shown when a service interval set by the heating contractor (e.g. burner hours) has been exceeded. The display shows a service symbol and the word Ser - Service message is shown on the display
The heating contractor sets service intervals, for example by burner hours run. A service message is created when the limit is exceeded. The display t - Service required indicator (code 0F)
Code 0F appears only in the fault history and means service is required. - Service shown on the display
The control shows 'Service' when the service interval set by the heating contractor has been reached. - Service symbol flashes and Service is displayed
A service is due, as set by the heating contractor. - Service symbol shown on Vitotronic 200 (wrench icon)
The service time set by the heating contractor has arrived. - Service the burner refractory and cylinder burner
Check the refractory ring and cylinder burner for damage and replace as needed. - Servicing controls and field wiring
Disconnect power before any boiler service. Wiring errors can cause improper and dangerous operation, so verify correct operation after servicing. - Servicing the control wiring
Wiring errors can cause improper and dangerous operation. Replacement wires must match the originals exactly. - Set a day-specific time program
To use the same time program on every day except one, set the program for the whole week first, then override the one day. - Set a DHW time program
Time phases define when DHW heating is on. Up to 4 time phases per day are allowed. DHW is not heated between phases. Each day of the week can have it - Set a time program for central heating, DHW or DHW recirculation
Time programs are set at the system and lead boiler section control. Up to 4 time phases can be set per day, and each day of the week can be different - Set central heating time program
Set the on and off times for central heating phases 1 to 4. Use 1-7 for identical days or a day name for a single day. - Set CO2 at lower heating output
Adjust CO2 at partial load after setting full load. - Set CO2 at upper heating output
Adjust CO2 at full load. Only the burner being adjusted may run; the other burners must be at standstill. - Set day and night room temperatures
Each heating circuit can have its own normal and reduced room temperature. - Set DHW recirculation pump cycles for individual weekdays
Use this procedure to give each weekday its own recirculation pump cycles. - Set expansion tank and system pressures
Follow the expansion tank maker's instructions. Max operating pressure is 75 psig (5 bar), or 58 psig (3.9 bar) in some Canadian provinces. - Set individual DHW cycles for each day of the week
Each weekday can have its own DHW cycles, up to four per day. - Set individual space heating cycles for each day of the week
Each weekday can have its own heating cycles, up to four per day. - Set jumper SV2 for the RDAC module type
Two RDAC module types are listed. Each one needs jumper SV2 set as shown in the manual's diagram. The diagram is not legible in the text extract, so c - Set LON addresses for a Vitotronic 300 GW6B cascade
The gateway expects the lead boiler at a fixed LON address. The default configuration is 8 GW6B boilers and 3 zones. - Set LON participant number and update LON participant list
Used when the Vitotronic 300 GW2 is connected in a LON BUS system with Vitotronic 200-H. The LON communication module must be fitted first. - Set LON participant numbers and functions
Sets LON participant numbers and related functions through coding level 2 for a single boiler with Vitotronic 200-H, HK1B mixing valve control and Vit - Set maximum output
Limits the maximum heating input through the modulation range. The limit cannot exceed the boiler coding card. - Set room temperature setpoint and setback (outdoor reset)
Changes the room temperature setpoint or setback for the heating circuit through the outdoor reset programming unit. Examples in the manual: setpoint - Set the adjustable high limit to 189 ºF / 87 ºC
Change the dial stop on the adjustable high limit selector knob. - Set the DHW recirculation pump time program
Default: cycle 1 runs every day from 05:30 to 22:00 hrs, and automatic mode is preselected for the other cycles. The pump should only run when hot wat - Set the domestic hot water (DHW) time program
Set DHW heating times, or use automatic mode, which follows the space heating program but starts 30 minutes earlier. The DHW re-circulation pump runs - Set the energy saving holiday mode
Choose a holiday mode before leaving. Stand-by stops space heating and DHW production but keeps frost protection. The holiday program stops DHW produc - Set the fixed high limit (if required)
Fixed high limit depends on the safety equipment installed and local codes. Vitorond 200 is factory set at 120 °C / 248 °F and can be lowered to 110 ° - Set the fixed high limit to 212 F (100 C)
Only do this if needed. The setting cannot be reversed, and the adjustable high limit must not be above 167 F (75 C) afterward. - Set the holiday energy saving program
Reduces energy use while away. With the 'rw' heating program, space heating runs at the reduced room temperature but DHW is off. With the 'w' program, - Set the same DHW heating cycles for every day of the week
DHW has four cycles. Default is cycle 1 from 05:30 to 22:00 every day. The automatic mode is preselected, so DHW heats 30 minutes before the space hea - Set the same space heating cycles for every day of the week
The time program has four heating cycles. Default is cycle 1 from 06:00 to 22:00 every day, with normal room temperature during that time. Allow for t - Set up a Vitodens 200 / B2HA cascade with the Vitotronic 300-K MW2C
The cascade control must be addressed as LON 9 so the boilers can use LON addresses 1 through 8. KMK communication is possible but gives less informat - Set up digital inputs DE1 to DE3
Each digital input can be set to one function: heating program changeover, external blocking, external blocking with fault input, external demand with - Set up LON communication between control units
Steps to set system type, boiler number and LON participant numbers. The LON communication module must be plugged in first. - Setting a central heating time program
Time phases define when rooms heat to standard temperature. Between phases the rooms run at the reduced temperature. Up to 4 phases per day are possib - Setting a normal room temperature
The normal (day) room temperature is set with the rotary selector. - Setting a reduced room temperature
The reduced (night) room temperature is set with the reduced-temperature key. The value flashes while you adjust it and is saved on confirmation. - Setting a time program for central heating (Heating circuit 1 example)
Time programs divide each day into up to 4 time phases. Outside the phases the system heats to the reduced temperature. The same method applies to DHW - Setting a time program for central heating, DHW or DHW recirculation
Time phases define when the system heats to standard temperature. Between phases it heats to the reduced temperature. The same steps apply to DHW heat - Setting heating circuit time program (switching times)
Heating must be selected for the circuit, and normal and reduced temperatures must be set first. Up to four time cycles per day can be programmed, eac - Setting the boiler sequence at the cascade control unit
The boiler sequence depends on the cascade coding and internal control calculations. An ECO threshold can block or release each boiler based on outdoo - Setting the circulating pump speed
The built-in Wilo Star S 21 U 15 pump has three speeds. The speed is set from the system design or a pressure loss calculation. - Setting the coding switch on the remote control circuit board
The coding switch is on the circuit board at the rear of the housing top. Set it to match the heating circuit the remote control serves: heating circu - Setting the date and time
Time and date are set manually on the remote control. The date appears after the time is confirmed. - Setting the operating program
Choose the operating program for a heating circuit from the menu. - Setting time and date
Date and time are set at the factory and can be changed by hand. - Shut down the boiler and open the combustion chamber door for service
Isolate the boiler and open the chamber before any cleaning or inspection. - Shut down the boiler before inspection
Isolate power and fuel and open the boiler before any cleaning or inspection. - Shut down the boiler for service
Isolate power and gas before opening the boiler. - Shut down the heating system before service
Isolate power and fuel before opening the boiler for service. - Shutdown and extended summer shutdown
Shut the boiler down safely and protect it from corrosion during long idle periods. - Shutdown with frost protection monitoring and freeze risk
With frost protection monitoring, select the Standby mode operating program so frost protection stays active for the boiler and DHW tank. Outdoor temp - Shutting down the boiler before service
Isolate power and gas before any maintenance work on the boiler. - Shutting down the boiler for service
Isolate the boiler electrically and at the gas supply before any maintenance. - Shutting down the heating circuit (standby)
Puts the heating circuit in standby. No space heating. Frost protection stays active. The circuit pump still runs for a short time every 24 hours. - Shutting down the heating system
Full shutdown without frost protection monitoring. Use the standby program first if frost protection must stay active. - Shutting off gas to the appliance for service
Use this procedure before service work on the boiler or gas controls. The appliance has no pilot and uses an electronic ignition device. - Side piping - left or right side gas valve and tees
Mount the gas valve, tees and drain valves for the chosen side, using the layout shown for that side. - Side piping installation - gas line and water pipes
Route the flexible factory gas line to the chosen side and connect the water pipes through the side cutouts. - Side piping installation - restraining bar and rings
Mount the restraining bar and rings on the side of the boiler frame before routing pipes. - Sidewall vent location and wind
Locate the sidewall vent termination on the wall least affected by prevailing wind, since high wind can cause flue recirculation, poor combustion, and - Simplified flue system leak check
Checks the balanced flue annular gap for leaks by measuring combustion air. - Simplified leak test of coaxial vent (sealed combustion)
Applies only to sealed combustion with coaxial venting. Not applicable to single-wall venting. - Single combustion air device on multiple boiler systems
Common combustion air interface for several boilers. - Single-boiler vs multi-boiler coding with external controls
Set coding 01 for the system type. Multi-boiler systems need plugs aVD and aVH wired. - Size combustion air openings
Sizes are based on the total input of all oil-fired appliances in the space. Louvers and screens reduce free area, so allow for them. - Sizing the electric boiler
Size the boiler from a heat loss analysis. Do not oversize, since this adds cost to the boiler, wiring and materials. - Slab curing (screed drying) function
Used to dry a new concrete floor slab with a controlled supply temperature profile. Set F1 to 1 to 4 for profile 1 to 4. Profiles run over 30 days wit - Slab curing function (mixing valve circuit)
Slab curing is available only with a heating circuit that has a mixing valve. Four temperature and time curves are selected with coding F1. While acti - Smell of flue gas
Flue gas contains poisonous carbon monoxide. Stop the system and clear the air before further work. - Space heating: how the boiler water setpoint and modulation are set
The control unit sets a boiler water setpoint from outdoor temperature (or room temperature if a room-dependent remote control is connected) and the h - Special display: button has no function (Without function)
The display flashes when a button with no assigned function is pressed. Example: the DHW button flashes when no DHW tank is connected. - Special display: centralized operation
The heating and holiday program setting is accepted by the heating circuit coded for centralized operation. - Special display: heating program changed by external control (Ext. control)
The heating program set on the control unit was switched over by an external control. - Special display: service required (MService)
The control shows a service message asking for a service call. - Special display: settings only possible on remote control
The control unit cannot make this setting. Some settings, such as normal room temperature on the ts selector, can only be changed on the remote contro - Special display: slab curing active
If slab curing is coded, this display stays on until the slab curing function ends. - Stainless steel vent pipe requirements
Stainless vent must be UL/ULC listed for Category IV for horizontal or vertical venting. Check the single-wall parts are correct before installing. - Stand-alone DHW tank temperature sensor installation
Needed only when a stand-alone DHW storage tank is used. Viessmann Vitocell 100 and 300 tanks have a sensor well. - Start-up after extended shutdown and gas odour
Recondition the system before restarting after a long shutdown. If gas is smelled, take emergency action. - Start-up procedure overview
Start-up is done in this order: 1 controls and indicators; 2 check the fixed high limit; 3 integrate the control in the LON BUS (with heating circuits - Start-up with antifreeze in the system (flow reading error)
At low ambient start-up with antifreeze, the flow reading can fail. A special start-up procedure warms the fluid so flow can be read. - Start-up, inspection and maintenance procedure index
Index of the 23 start-up, inspection and maintenance steps. Each step is marked S (start-up), I (inspection) or M (maintenance). The marker columns ar - Starting the heating circuit
Turns the heating circuit on for space heating. With heating on, the circuit heats at normal or reduced room temperature (frost protection) according - Starting the heating system
Start-up sequence for the operator or technician before the boiler is run. - Startup fault: fault indicator on and display flashing
If the fault indicator lights during commissioning and the burner control display flashes, the section has likely lost gas, most often from air in the - Stopping DHW heating
Two options depending on whether the rooms still need heat. - Stopping the heating system with frost protection
Use standby mode to stop heating and DHW while keeping frost protection active on the heating circuits and DHW tank. - Strain relief on plug-in connectors
Each plug-in connector needs strain relief, unless the cable already has a molded clamp. - Strap-on flow sensor installation
The immersion sensor can also be strapped to a pipe. When used for mixing valve sensing, place it on the pipe that carries the mixed temperature out o - Summer operation (heating program w)
In summer mode the burner only fires when DHW is called for by the DHW tank sensor. - Supply and return temperature sensor installation
The supply sensor goes in an immersion well. The return sensor is optional and only lets the user see the temperature difference; it has no control lo - Switch between staged and modulating burner externally
A floating contact on plug aVH changes the burner between modulating and two-stage operation. - System Example 01: cascade control for modulating boilers
Cascade controller for modulating OT boilers 1 to 8. The boiler set point comes from the heating system manager and the boiler modulates to reach it. - System Example 02 overview: cascade controller for modulating boilers with DHW
Cascade controller for up to 8 OpenTherm boilers. The boilers get their set point from the heating system manager and modulate their own burners to re - System Example 02: cascade control with DHW
Same cascade layout as System Example 01 for modulating OT boilers 1 to 8, with outdoor reset and common supply sensor, and no low loss header. This e - System Example 03 overview: cascade controller for modulating boilers, no DHW
Cascade controller for up to 8 OpenTherm boilers. Boiler set point comes from the heating system manager and each boiler modulates its burner to reach - System Example 04 overview: cascade controller for modulating boilers with DHW and common supply pump
Cascade controller for up to 8 OpenTherm boilers. Boiler set point comes from the heating system manager and each boiler modulates its burner to reach - System Example 1 components
Basic hydraulic example with one to three heating circuits and a DHW tank. Components include the outside temperature sensor (ATS), DHW tank temperatu - System Example 2 components (underfloor heating with heat exchanger)
Underfloor heating circuit with a heat exchanger, controlled as heating circuit M1 when supply and return sensors are used. Heating circuit 1 includes - System layout 1 - direct heating circuit with integrated DHW
Radiator heating circuit with DHW produced by the built-in tank, controlled by the boiler control. - System Layout 1: boiler with DHW tank and one heating circuit
Boiler feeds a DHW storage tank and one heating circuit directly. An external boiler controller with room thermostat connection is field supplied. A p - System layout 1: DHW tank, mixing valve and radiator loops
Layout 1 uses one boiler with a DHW storage tank, one heating circuit without a mixing valve, and two heating circuits with a mixing valve: a high-tem - System layout 1: direct radiator circuit with DHW
Boiler with direct-connected radiator (high temperature) heating circuit and DHW production. Outdoor reset via Vitotronic 200 KW6B control. - System Layout 1: direct-connected heating circuit with DHW
Radiator (high-temp.) heating circuit and DHW production. Flow in the heating circuit is less than the boiler maximum flow. - System layout 1: direct-connected radiator circuit with DHW
Boiler with a direct-connected high-temperature radiator circuit and DHW production from a storage tank. - System layout 1: one heating circuit
Basic layout with the boiler and one heating circuit. Heating circuit should be designed for 30 to 40 F (16.7 to 22.2 C) rise. For a lower design rise - System layout 2: DHW storage tank with low-loss header
Layout with DHW storage tank, low-loss header and one heating circuit, controlled by an external boiler/DHW controller. - System Layout 2: DHW tank with low-loss header
Boiler with DHW storage tank, low-loss header and one heating circuit with heating circuit pump P2. Low-loss header is an accessory. - System layout 2: multiple boilers on a low-loss header
Layout 2 connects up to eight boiler sections to a low-loss header with multiple heating circuits, mixing valves and a DHW tank. A common supply tempe - System layout 2: one heating circuit with low-loss header
Radiator circuit with a low-loss header, used when the heating circuit flow is greater than the boiler's maximum water flow. The boiler pump is used a - System layout 2: radiator circuit with low-loss header
Radiator circuit with a low-loss header and DHW production. Used when heating circuit flow exceeds the boiler maximum. - System Layout 2: radiator circuit with low-loss header and DHW
Vitodens 200-W B2HB with one heating circuit and a low-loss header, plus DHW. Used when heating circuit flow is above the boiler maximum water flow. - System layout 2: underfloor circuit with mixing valve and system separation
Low-temperature underfloor heating isolated by a plate heat exchanger, with DHW production. Required where non-oxygen-barrier tubing is used. - System layout 2: underfloor heating with mixing valve and system separation
Low-temperature underfloor circuit with 3-way mixing valve and plate heat exchanger for system separation, plus DHW. - System layout 3: DHW storage tank with closely spaced tees
Layout with DHW storage tank and one heating circuit using closely spaced tees instead of a low-loss header. Viessmann prefers a low-loss header. - System Layout 3: DHW tank with closely spaced tees
Boiler with DHW storage tank and one heating circuit, hydraulically separated by closely spaced tees. A low-loss header is strongly preferred by Viess - System layout 3: direct radiator circuit plus underfloor mixing circuit with DHW
Combines a direct-connected radiator circuit with an underfloor circuit served by a 3-way mixing valve, plus DHW. - System layout 3: radiator circuit plus underfloor circuit with mixing valve
Direct radiator circuit and a low-temperature underfloor circuit with 3-way mixing valve, plus DHW. - System Layout 3: underfloor circuit with mixing valve and system separation
Vitodens 200-W B2HB with DHW storage tank and one underfloor circuit (low-temperature) using a 3-way mixing valve and plate heat exchanger for system - System layout 3: underfloor circuit with system separation
Underfloor heating (low-temperature) circuit with a 3-way mixing valve and a plate heat exchanger for system separation, plus DHW. Needed when using n - System Layout 4: B1KE with one heating circuit, direct connection
B1KE boiler feeds one heating circuit directly with DHW tempering valve and domestic water sediment filter supplied in the field. Water softener equip - System layout 4: direct radiator circuit plus system-separated underfloor circuit
Radiator circuit fed by the boiler pump 20 and an underfloor circuit isolated by a plate heat exchanger with a 3-way mixing valve. - System layout 4: radiator and underfloor circuits with DHW
One direct radiator circuit and one underfloor circuit with a mixing valve, plus DHW storage. Radiator circuit flow must be at least 30% greater than - System layout 4: radiator circuit plus underfloor circuit with mixing valve
Direct radiator circuit combined with an underfloor circuit on a 3-way mixing valve, plus DHW. The radiator circuit flow must be at least 30% greater - System Layout 4: radiator circuit plus underfloor mixing circuit
Vitodens 200-W B2HB with DHW, one direct radiator circuit and one underfloor circuit with 3-way mixing valve. - System Layout 4: underfloor and radiator circuits with DHW
Underfloor circuit with mixing valve plus a radiator circuit, with DHW production. Heating circuit flow is less than boiler maximum. - System Layout 5: B1KE with low-loss header
B1KE boiler with low-loss header and one heating circuit. No LLH temperature sensor is available for the B1KE. - System layout 5: DHW tank, low-loss header and mixing-valve circuits
Example piping for one CU3A boiler with a DHW storage tank, a low-loss header, several heating circuits with mixing valves and one circuit without a m - System layout 5: DHW with three zone circuits
Multiple boilers feed DHW and three zone circuits. Zone circuits are called by thermostats on dry contacts. Zone 2 and 3 use the AM1 extension module. - System layout 5: low-loss header with multiple mixing-valve circuits
Multi-circuit layout with a low-loss header, several mixing-valve circuits and one circuit without a mixing valve, plus DHW. The manual states this la - System Layout 5: mixing and non-mixing circuits with low-loss header
Underfloor circuit with mixing valve and a radiator circuit without mixing valve, plus DHW. Total flow of the two circuits is greater than boiler maxi - System layout 5: mixing-valve circuit plus direct circuit with low-loss header
Underfloor circuit on a mixing valve and a second radiator circuit without a mixing valve, used when the total flow is greater than the boiler maximum - System layout 5: radiator and mixed underfloor circuits with low-loss header
One mixing-valve underfloor circuit and one radiator circuit without a mixing valve, with a low-loss header. Used when combined flow is above boiler m - System Layout 5: radiator and underfloor mixing circuits with low-loss header
Vitodens 200-W B2HB with DHW, one mixing-valve underfloor circuit and one direct radiator circuit. Total circuit flow is above the boiler maximum. - System Layout 6: B1KE with closely spaced tees
B1KE boiler with closely spaced tees and one heating circuit. A low-loss header is strongly preferred. - System layout 6: DHW and three zone circuits
Example for one or more CU3A boilers with a DHW storage tank and three zone circuits. Zone 1 uses boiler output 157. Zones 2 and 3 use the AM1 extensi - System Layout 6: one non-mixing and two mixing circuits with low-loss header
One radiator circuit without mixing and two underfloor circuits with mixing valves, plus DHW. Total flow is greater than boiler maximum. - System Layout 6: radiator circuit plus two underfloor mixing circuits with low-loss header
Vitodens 200-W B2HB with DHW, one direct radiator circuit and two underfloor circuits with 3-way mixing valves. Total circuit flow is above the boiler - System layout 6: two mixing-valve circuits with low-loss header
One radiator circuit without a mixing valve and two underfloor circuits with 3-way mixing valves, with a low-loss header and DHW storage. Used when co - System layout 7: direct circuit plus system separation
One direct-connected radiator circuit plus an underfloor circuit with system separation through a plate heat exchanger. Boiler pump supplies the radia - System Layout 7: direct circuit with system separation
Radiator circuit connected directly to the boiler and an underfloor circuit with system separation, plus DHW. Total flow is less than boiler maximum. - System Layout 7: direct radiator circuit plus system-separated underfloor circuit
Vitodens 200-W B2HB with a direct radiator circuit and an underfloor circuit with system separation. The boiler pump 20 supplies the radiator circuit - System layout 7: up to eight boilers with mixing circuits and low-loss header
Piping example for up to eight CU3A boilers with a Vitotronic 300K MW2C, a low-loss header with common supply temperature sensor, a DHW storage tank, - System layout 8: DHW plus three zone circuits with low-loss header
Multiple Vitodens 200-W boilers with a low-loss header feeding three zone circuits through a thermostat-controlled zone arrangement, using the AM1 ext - System Layout 8: DHW with low-loss header and three zone circuits
Vitodens 200-W B2HA/B2HB with DHW storage tank, low-loss header and three zone circuits controlled by thermostats (dry contact). Zones 2 and 3 use an - System layout 8: multiple boilers with system pump and isolation valves
Piping example for up to eight CU3A boilers with a Vitotronic 300K MW2C, a common supply temperature sensor, a system pump, a DHW storage tank with DH - System layout 8: multiple mixing-valve circuits with low-loss header
Complex layout with a low-loss header, DHW storage, several mixing-valve circuits and one circuit without a mixing valve. Viessmann asks for contact w - System layout with multiple heating circuits, mixing valves and low-loss header
Piping layout for a DHW storage tank, a low-loss header, several mixing-valve heating circuits and one circuit without a mixing valve. Contact the Vie - System layout with three zone circuits and low-loss header
Layout for DHW production plus three zone circuits. Total flow of the circuits can exceed the boiler's maximum flow, so a low-loss header is strongly - System layout: boiler with low loss header
Boiler pump is connected to the boiler pump module. The Versatronik runs the space heating pump and DHW pump and receives the DHW demand and the boile - System layout: diverter valve
Dedicated boiler pump with no low loss header. A power-open, spring-return diverter valve sends the flow to the tank on a DHW call, and DHW has priori - System layout: multizone with low loss header
Zones are controlled by thermostats, and DHW has priority from the Versatronik pump module. The boiler has a dedicated pump connected to the Vitodens - System layout: no low loss header
There is no low loss header and no dedicated boiler pump. The Vitodens pump module output signal goes to the Versatronik, which gives DHW priority ove - System type 1: single boiler with shunt pump to raise return temperature (modulating boiler)
Single-boiler system with a shunt pump, used with a Vitorond 200, VD2 boiler. The boiler and DHW tank connect to the Vitotronic, and a heating circuit - System type 5: single boiler with Vitocrossal 200 and mixing circuits
Recommended layout for a single condensing boiler with a Vitocrossal 200 and a mixing-valve heating circuit. The boiler runs modulating water temperat - System version 10: heating circuit with low temperature circuit and Vitorond with shunt pump
Vitocrossal 200 (CM2) and Vitorond 200 (VD2) with Vitotronic 100 GC1 and Vitocontrol-S control. Includes a motorized isolation valve A1, a shunt pump - System version 1: direct connection to heating circuit loop
Heating circuit is connected directly to the loop from supply and return manifolds. The control runs the heating circuit pump through the power/pump m - System version 1: Vitorond 200 VD2A with Therm-Control and 3-way mixing valve
Boiler with a Therm-Control temperature sensor and a 3-way mixing valve for return temperature control. Includes a heating circuit with mixing valve, - System version 2: shunt pump for return temperature control
Used where the distribution manifold is close to the boiler. The boiler water flow is reduced by the motorized isolation valve. T2 switches on the shu - System version 2: underfloor heating with heat exchanger
Underfloor heating is separated from the boiler circuit by a heat exchanger. A high limit aquastat limits the maximum temperature downstream of the mi - System version 3: common supply pump and low pressure manifold
Used when the distribution manifold is in a remote location (more than 20 m / 65 ft). T1 reduces or closes the mixing valves when the minimum return t - System version 4: return temperature control with 3-way mixing valve
Suited to older systems or where downstream heating circuits cannot be controlled. T1 closes the 3-way mixing valve in proportion when the minimum ret - System version 4: return temperature control with low loss header and three-way mixing valve
Vitorond 200 boiler with Vitotronic 100 GC1 on each boiler and one Vitotronic 300-K MW1S. The return temperature is controlled with a three-way mixing - System version 5: heating circuit with one low temperature circuit
Vitocrossal 300 controlled by a Viessmann boiler control with outdoor reset, modulating boiler water temperature and load-dependent sequential control - System version 6: heating circuit, low temperature circuit and Vitorond with shunt pump
Vitocrossal 300 as lead boiler and Vitorond 200 as lag boiler, controlled by a Viessmann control system with outdoor reset, modulating boiler water te - System version 7 design: three-way mixing valve with several heating circuits
Lead boiler is a Vitocrossal 300 with lag Vitorond 200 boilers, run by an outdoor-reset control with modulating boiler water temperature and load-base - System version 7: three-way mixing valve with several heating circuits and one low temperature circuit
Vitocrossal 300 with Vitorond 200 (125 kW to 500 kW) controlled by a Viessmann system with outdoor reset, modulating boiler water temperature and load - System version 7: Vitocrossal 300 lead boiler with Vitorond 200 lag boiler and shunt pump return control
Vitocrossal 300 (CT3) is the lead boiler and Vitorond 200 (VD2) is the lag boiler, run by a Viessmann outdoor-reset cascade control with modulating bo - System version 8: three-way mixing valve return control with several heating circuits
Vitocrossal 300 (CT3) lead boiler and Vitorond 200 (VD2) lag boiler with a three-way mixing valve, several heating circuits and one low-temperature ci - System version 9: heating circuit and one low temperature circuit with motorized isolation valve
Vitocrossal 200 (CM2) with Vitotronic 100 GC1 boiler control, Vitocontrol-S (VD2/CT3/CM2) system control, a DHW tank, a mixing valve circuit, and a mo - Tank temperature sensor or Aquastat connection
Tank sensor or dry contact thermostat connects to wiring panel terminals 3 and 4. - Temperature aquastat for maximum temperature limiting
Electro-mechanical aquastat using the liquid expansion principle. It switches the heating circuit pump OFF when its set value is exceeded. The supply - Test and analysis equipment
Use only calibrated equipment. - Test fixed high limit (simulation #1, pump unplugged)
Field test of the manual reset high limit. Only do this where required by law, and the manufacturer is not responsible for damage from overheating dur - Test fixed high limit (simulation #2, valve closed)
Alternate high limit test that uses a closed boiler valve and a jumpered flow switch. - Test flow switch (flow sensing device)
The flow switch opens when flow is too low, shuts the burner down, and blocks restart until flow returns to a safe level. - Test gas solenoid valve seals for leaks
On 750/1000 MBH burners the burner control unit automatically checks both coaxial safety valves for leaks at startup. If there are no leaks, the burne - Test the flow switch
The B2HA series has a flow sensing device. Low flow opens the switch, the burner shuts down and it will not restart until adequate flow returns. - Testing the fixed high limit (FHL)
Checks that the FHL cuts out above its setting. Involves 120 VAC. - Testing the flow switch (flow sensing device)
The boiler has a flow sensing device. When flow is too low the switch opens, the burner shuts down, and it will not restart until flow is adequate aga - Testing the flow switches / flow sensors
Both flow sensing devices shut the burner down on low flow and block restart until flow is restored. The test is done by throttling the water flow to - The DHW is too hot
Domestic hot water is hotter than wanted. - There is no DHW
Domestic hot water is not being supplied. - There is no DHW (domestic hot water)
Boiler does not supply domestic hot water. - There is no hot water
No domestic hot water (DHW) is being supplied. - Thermoacoustic or combustion noise
Noise from the combustion process with no fault code shown. - Thermostat, off-peak and secondary pump wiring
Call-for-heat and off-peak inputs use voltage-free contacts. A secondary pump can be run from Pump 2. - Tools needed for service
Basic hand tools and cleaning supplies for boiler service. - Top back panel screw relocation
The top panel screw can be hard to remove. Move it about 3 in to the left or right and drill a new pilot hole. The source text for the drill bit size - Top panel screw relocation for removal
The top panel screw can be moved about 3 in. left or right to make the top panel easier to remove. The drill bit size for the pilot holes is not legib - Trade fair mode is displayed
Trade fair mode is active, so neither central heating nor DHW heating runs. - Turn off gas to the boiler for service
Owner/service shutdown sequence from the operating instructions for turning off gas to the appliance. - Turning off gas to the appliance
Shutdown procedure for service work. - Turning the boiler system off before service
Isolate the boiler electrically and shut off the gas supply before any service work. - Two-boiler control strategy example
Example system: two boilers, each 100 kW rated output, basic load adjusted to 33 %. Compares gross calorific strategy (coding 3C: 0) and net calorific - Two-stage burner dew-point protection
The burner should go to full (second-stage) input when boiler water falls below the minimum to protect against condensation and corrosion. The burner - Underfloor heating and large water volume circuits
Underfloor heating and heating circuits with a very large water volume must connect to the boiler through a 3-way mixing valve, following the applicab - Underfloor heating and oxygen diffusion barrier
Use underfloor plastic tubing with an oxygen diffusion barrier. Without that barrier, separate the underfloor system from the boiler with a heat excha - Underfloor heating limit aquastat and electronic limits
The control's electronic high limit does not replace a separate limit aquastat required for underfloor heating. The aquastat switches the heating circ - Unit does not power up
The Versatronik 10.WB1 shows no power at all. Start with the supply and the F1 fuse. - Unpacking and rolling the boiler off the skid
The boiler is on a wooden pallet with wheels for placement. It can be lifted by crane only while still packed on the skid. Ramp length depends on mode - Update participant list (Vitocontrol-S cascade)
Run this after all communication connections are made, with the Vitocontrol-S coded as error manager (default). Each gateway needs a unique LON partic - Vacuum relief damper on vertical sealed vents
A rare vacuum can form in a vertical sealed vent when the burner is at full fire and suddenly stops, for example during a power failure. A Viessmann v - Valve and flange leak test
Check the valve and flange connections for leaks. Recommended as part of scheduled maintenance; only trained licensed heating contractors should perfo - Vent pipe installation
Use approved vent material only. Keep the run short with few elbows. Support horizontal runs so they do not sag, and keep them as short as possible. - Vent termination location requirements - Canada
Vent must follow local rules plus CAN/CSA-B149.1 or .2. Flexible vent is only for vertical runs. Key limits: not less than 7 ft (2.13 m) above a paved - Vent termination location requirements - USA
Vent must follow local rules plus ANSI Z223.1 or NFPA 54. Flexible vent is only for vertical runs. Key limits: not less than 7 ft (2.13 m) above a pav - Venting - Category I (chimney) and Category III (positive pressure)
The boiler is approved as a Category I appliance when vented to a chimney, and as a Category III positive pressure non-condensing boiler when using th - Venting and combustion air safety requirements
Improper venting or combustion air can allow flue products with carbon monoxide into the living space. The boiler must never run without an installed - Venting and electrical connection overview
Venting details are in the separate venting system installation instructions. The boiler needs a dedicated 120 VAC supply, and accessories are wired a - Venting Category III requirements
The Vitorond 200 is a Category III positive pressure, non-condensing boiler. Each boiler needs its own vent. - Venting choice in damp or salty coastal areas
Metal casing and fan housing corrode faster near sea spray and humid air. In these locations, do not use a direct vent system that draws outdoor air. - Venting code and approval requirements
Vent the oil-fired boiler under the local code. Where there is no local code, use CSA B139 in Canada or NFPA 31 in the US. Masonry, concrete or metal - Venting connection and vent routing
Vent pipe routing and piping support rules for the boiler venting connection. - Venting option #2 (Category III) requirements
The Vitorond 200 is a Category III positive pressure, non-condensing boiler and must be vented individually. The vent system and chimney must be desig - Venting safety requirements and draft checks
The vent must carry all combustion products safely outdoors and must never pass through return, supply, ventilating or combustion air ducts. The boile - Venting through an insulated chase or masonry flue
Vent material may extend beyond the outside wall only inside an enclosed, insulated, waterproof chase for outdoor use. Space around a chimney liner or - Verify burner input by clocking the gas meter
Check actual gas input by timing the meter with all other gas appliances on the same meter switched off. Do not overfire the boiler. Running 5% under- - Verify gas input by clocking the gas meter
Time how long the boiler takes to burn a set amount of gas and compare with the nameplate input. Other gas appliances on the meter must be off during - Verify gas type before installation
Confirm the gas on the rating plate matches the site, then record it in the maintenance record. - Vertical piping installation (boiler connections)
Connect the water and DHW pipes from the top of the boiler, then secure the bottom connections and gas line. - Vertical vent termination location and roof passage
Vent termination must be kept out of reach of snow and must not be blocked by drifting snow. Special positive pressure vent systems through a roof nee - View temperatures and status information
Read circuit temperatures and status values from the display mode. Displayed values depend on the system selection and the accessories installed. - Viewing fault codes from the fault memory (error history)
Reads the saved fault history on the Vitotronic 100 GC1. Up to 10 codes are stored, with 1 being the last fault. - Vitodens 200 WB2B with Vitotronic 100 HC1 communication wiring
Same CAT5e non-crossover LON cable, daisy-chained from control to control. - Vitodens 200 WB2B with Vitotronic 200 HO1 communication wiring and outdoor sensor
Same CAT5e non-crossover LON cable. The outdoor sensor must be connected or an outdoor sensor fault will always show. - Vitotronic 100 GC1 / GC1B communication wiring
The control talks to the boiler over CAT5e cable with RJ45 ends. It is a non-crossover cable and is daisy-chained from control to control. - Vitotronic 200 cascade coding entry
The Vitotronic 200 is coded from the boiler control. The boiler must already be in cascade mode before coding. - Vitotronic 200 sensor check
Sensor values are read from the service menu on the Vitotronic 200. - Vitotronic 300 GW5B communication wiring
Same CAT5e non-crossover LON cable as the other boiler controls, daisy-chained from control to control. - Vitotronic 300-K electrical connection overview
Main board connections include the 120V power supply, central fault message, heating circuit pump, DHW pump, DHW recirculation pump, system pump, and - Wall and frame mounting of the boiler
Free-standing or wall-mounted install using the boiler stand or wall bracket. No mounting template is supplied, so the wall positions for the frame, b - Wall mount boiler on bracket (B2HB 19, 26, 35, 68, 94, 125)
Mount the boiler to the wall bracket with the boiler held level so condensate drains correctly. Bracket must be fastened tightly to the wall. - Wall mount boiler with levelling screws (B2HB 45, 57, 160, 199)
Same mounting sequence as the smaller models, with levelling screws used to set the boiler level and a holding bracket fitted to the frame above the b - Wall mounting bracket on concrete, wood and metal studs
The boiler mounts on a wall bracket. The supplied screws and rawl plugs are only for concrete. Other materials need bolts and anchors rated for 196 lb - Wall mounting on concrete and studs
Use the enclosed screws and rawl plugs only on concrete. Other materials need bolts and anchors rated for 220 lb (100 kg). On concrete, drill 12 mm ho - Wall mounting the boiler (B2HB 19, 26, 35, 68, 94, 125)
Secure the wall bracket tightly before hanging the boiler. A loose boiler is a severe hazard. The boiler must be level both ways so condensate drains - Wall mounting the boiler bracket and CombiPLUS
Mount the boiler bracket and CombiPLUS securely; loose mounting is a severe safety hazard. - Wall mounting the boiler bracket and CombiPLUS on studs
Mount the boiler bracket and CombiPLUS kit level on wall studs, with fixings centred in each stud. Wood and metal studs need different fixings. - Water connections and system pressure
The boiler works in any fully pumped hot water heating system. Minimum system pressure is 1 bar (14 psig). - Water distribution pipe and drain assembly
Build the water distribution pipe from the rod sections, fit the supply nipple and fill/drain valve, and set the R 2 in. plugs so they do not stick ou - Water quality and scale
Water quality affects the life of the whole heating system. Use a water treatment system against corrosion and lime. Avoid hard water (calcium carbona - Water quality and scale prevention
Hard water causes scale on the heat exchanger. Soften fill and top-up water where the alkaline earth content exceeds the standard value or where large - Water quality and treatment
Consider water treatment where mineral content or hardness is high. In freezing areas, antifreeze can protect the system, following the antifreeze mak - Water side connections and flow protection
The boiler is only for forced circulation hot water systems. Connect supply and return headers and safety piping while keeping air venting and check v - Water side piping (Hydrostat 3250-Plus)
Closed loop forced circulation systems only. Flush the system before connecting the boiler, because sludge can settle in the boiler and cause overheat - Water side piping (Vitotronic control)
Closed loop forced circulation systems only. Sludge left in the boiler causes overheating and failure, which is not covered by warranty. - Water side piping with Hydrostat 3250-Plus control
This boiler is for closed loop, forced circulation heating systems only. Flush the system before connecting the boiler, since sludge can cause overhea - Water side piping with Vitotronic control
Use a spring-loaded flow-check valve in heating circuits without mixing valves, to prevent gravity circulation of heat into the system in summer. Flus - Water supply and back flow protection
Water supply feed or pressure reducing valve must meet local code. - Weather-compensated heating circuit does not give the right room temperature
Weather-dependent control sets the boiler or flow temperature from the outdoor temperature and the set heat slope. The heat slope has to be set exactl - What the Versatronik 503 module does
Lets a boiler with a One Base control join an existing NR2/LON cascade. On the LON side the module acts like any other cascade boiler. The cascade sen - WiFi and LAN network setup
Place the boiler close to the WiFi router for a good connection. Walls, ceilings, metal and nearby electronics weaken the signal, and WiFi repeaters c - Wire 240 VAC or 3-phase pump through contactor
Pumps of this rating must not be wired direct to the control. - Wire a 240 VAC single-phase burner motor in conduit
For burners with a 240 VAC 1-phase supply run in conduit. Use the burner manual for fuse and wire size and the specific Viessmann connections. - Wire a 24V mixing valve adaptor
Use this when the mixing valve is driven through the 24V adaptor instead of a 120V actuator. - Wire a boiler return mixing valve or isolation/modulating valve (CM2)
Connect a 120 V or 24 V valve actuator for the CM2 boiler, using the 120 V L out supply. - Wire a boiler return mixing valve or modulating valve actuator (VD2/VD2A/CT3)
Connect a 120 V or 24 V valve actuator through a valve adaptor on the control's DIN rail. - Wire a combustion air blower on a common interface
Wire the combustion air blower motor, proving switch and power through the Common Combustion Air Device Interface. - Wire a combustion air damper
Wire the combustion air damper to the boiler control through the combustion air device adaptor in the connection enclosure. Use the damper manual for - Wire a combustion air damper on a common interface
Wire the combustion air damper motor, proving switch and power through the Common Combustion Air Device Interface. - Wire call-for-heat input lH
lH is an optional normally open dry contact that can give a call for heat, block the boiler, or trigger a DHW recirculation pump run. - Wire circulation and heating pumps
Wiring depends on pump voltage. Pump outputs differ between VD2/VD2A/CT3 and CM2 controls; see the pump terminal table. - Wire circulation pumps to P1 and P2 by priority
P1 and P2 have priority rules for DHW, heating circuit and recirculation pumps. - Wire combustion air blower through adaptor
Blower is powered through the combustion air device adaptor and needs a proving switch. - Wire DHW, pool or spa demand to zone controller
For multiple DHW, pool or spa demands, or an elevated boiler water temperature demand. The boiler pump connects to the Vitodens pump module, which sen - Wire one combustion air device to several boilers through the common interface
A single combustion air device on a multiple boiler system needs a Common Combustion Air Interface. Each boiler gets its own adaptor. - Wire pumps drawing more than 2FLA
Pumps above the direct output rating must be switched through a contactor. - Wire room thermostats for up to three zone circuits
Each zone circuit uses a dry-contact room thermostat wired to the integrated EA1 module. - Wire space heating pump output to zone controller (outdoor reset with Como OT)
For a Vitodens 100-W (WB1A/B) with Versatronik Como OT for outdoor reset and no room thermostat. The 120 VAC space heating pump output feeds the zone - Wire the boiler power supply
Electrical work must follow the National Electrical Code (US) or the Canadian Electrical Code (Canada) and local rules. The control must be grounded. - Wire the CombiPLUS control and pump cables
Route and connect the control cable and pump cable to the CombiPLUS, then to the boiler power pump module. - Wire the compiled failure alarm
Connect a visual and/or audible alarm device to the boiler control's compiled failure alarm terminal strip. - Wire the Hydrostat 3250-Plus burner control
Field wiring for the Hydrostat 3250-Plus control with a Beckett, Carlin or Riello burner. Power comes in on L1 and N to the high limit control. - Wire the low water cut-off (LWCO)
Wire the LWCO switching contact and its power supply to the boiler DIN rail. Use the LWCO harness supplied with the boiler, and follow the LWCO manufa - Wire the push-in DIN terminals in the junction box
The L, N, G terminals use push-in clamps. Wire sizes are limited. - Wire zone controller dry contact to R-Stat input (no outdoor reset)
Boiler runs from zone controller heat demand, not outdoor reset. The Como OT cannot be used in this setup. When a zone thermostat calls, its dry conta - Wiring 120VAC gateway to Vitocontrol-S
Wall-mount 120VAC gateway with a Vitocontrol-S. The Vitocontrol-S needs a LON card and a field LON connection to the gateway. - Wiring 120VAC gateway to Vitodens 200 (WB2B, HO1 or B2HA)
Wall-mount 120VAC gateway connected to a Vitodens boiler that has a LON communication card fitted. - Wiring 120VAC gateway to Vitotronic 100, GC1/GC1B, 300 GW2 or 300 GW5B
Wall-mount 120VAC gateway connected to a Vitotronic control that has a LON communication card fitted. - Wiring 24VAC gateway to Vitodens 200 (WB2B, HO1 or B2HA)
DIN-rail 24VAC gateway connected to a Vitodens boiler that has a LON communication card fitted. - Wiring 24VAC gateway to Vitotronic 100, GC1/GC1B, 300 GW2 or 300 GW5B
DIN-rail 24VAC gateway connected to a Vitotronic control that has a LON communication card fitted. - Wiring a floating call for heat contact
A dry contact on terminals 5 and 6 of plug lH sets the boiler demand. - Wiring a mixing valve extension module
A 145 communication bus connects the mixing valve extension module to the boiler. The wiring table is garbled in the source, so terminal-to-terminal v - Wiring and mounting the wall mount base and remote control
Use 2-wire cable, AWG 18 copper. Strip the cable and pull it through the bushing into the wall mount base, then mount the base on an even wall. Watch - Wiring boiler return mixing or isolation/modulating valve actuator
Install the 120V or 24V valve adaptor and connect the valve actuator through it. - Wiring for DHW priority in system layout 4
Wiring diagram for system layout 4. Power is supplied through a disconnect and overload protection. DHW priority is set through the Honeywell relays a - Wiring pumps that draw more than 2 FLA
Pumps drawing over 2 FLA on 120V, 240V or 208/460/575V 3-phase circuits should not be run straight from the control. Switch them through a field-suppl - Wiring pumps that draw more than 2 FLA or are 3-phase/240V
Pumps above 2 FLA, 208/460/575V three-phase pumps and 240V pumps must be switched through a field-supplied contactor or relay rated 120VAC 1A, fed fro - Wiring the 0-10 V input extension module
Module powered from 120 V / 60 Hz, with a 0 to 10 V input, KM-BUS link to the control unit, a zero-volt contact and a T 250 mA fuse. - Wiring the room controller to Viessmann Vitodens 100-W, WB1A
The 4-pole plug on the boiler control provides the connection. The OT communication wires go to terminals 1 and 2 on the controller sub-base and are n - Wiring the room controller to Viessmann Vitodens 100-W, WB1B
The OT communication wires go to the 6-pole terminal block harness. The outdoor sensor can be wired either to the boiler 6-pole connector or to termin - Wiring the Versatronik 10.WB1 to a space heating zone controller
The Versatronik space heating pump output is used as a control signal to the field zone controller. Zone pumps or valves only run on a zone call while - Wiring the Vitodens 100-W WB1A/WB1B boiler to the Versatronik 10.WB1
Interconnect the boiler pump module with the Versatronik for the low voltage DHW and room thermostat signals and for the 120VAC pump supply and pump s - Without function appears in the display
The button pressed has no function on this system. - Zone circuit or mixing valve accessory kit connection
The accessory kit for zone circuits or a heating circuit with mixing valve connects to the boiler. It can replace a Vitotronic control HK1B. The mixin - Zone circuit room thermostats with dry contacts
Each zone circuit has its own dry-contact room thermostat. The zone thermostats connect to the EA1 module built into the boiler. - Zone circuit setpoint: fixed or weather compensated
With one zone circuit, choose the zone set point method. Fixed setpoint: enter the target boiler water temperature used on a zone call. Weather compen - Zone control wizard setup
Run the zone control wizard from the service menu after power-up and clock setting. Pick the number of zone circuits (1, 2 or 3), then set each zone c - Zone control wizard: single zone with fixed setpoint and 157 pump output
One zone circuit with a fixed setpoint. A low-temperature circuit uses a 3-way mixing valve, a high-temperature circuit ZC1, and an indirect DHW tank - Zone thermostat connections (dry contact, EA1)
Each zone circuit has its own room thermostat dry contact. The contacts wire to the integrated EA1 module, which is inside the boiler. Zone circuits 1 - Zone valve multi-zone option (Application 3 alternative)
The zone valve arrangement from Application 2 can also be built using the multizone control shown in Application 3. - Zone valve power and transformer sizing (Application 2)
Zone valves and thermostats rely on the boiler for power, so they go dead when the boiler is shut off for service.
Weil-McLain (895)
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
The control can output a 0-10 VDC signal to modulate another heat source. Maximum rating is 10 VDC and 108 µA. - 0-10 Vdc output for lead/lag and variable speed pump
The 0-10 Vdc output (J16 terminals 7 and 8) can drive a lead/lag partner or a variable speed boiler pump. The output follows the firing rate. - 0-10 VDC remote modulation input
A 0-10 VDC signal can be used for remote modulation. It uses the INPUT 2 heat demand, so the same input cannot be used for a dry contact. The remote t - 0-10 VDC remote modulation input wiring and setup
Remote modulation from an external controller on P15-5/6 (positive on terminal 6, common on terminal 5). This works only with a single boiler, not a b - 0-10 VDC remote target input wiring and setup
Optional remote target. A 0-10 VDC signal on P15-5/6 (positive on terminal 6, common on terminal 5) adjusts the supply target temperature through the - 0-10VDC output for lead/lag and variable speed pump
The 0-10VDC output can drive lead/lag systems or a variable speed boiler pump. - 120 VAC power supply connection to terminal strip T1
Steps for bringing 120 VAC power to the boiler and grounding it. - A sensor is missing from the list at power-up
When power comes on, the screen lists every sensor the control detects. A sensor that is not listed is not connected right. - Access and clean exchanger, Ultra-155, -230, -299 and -399
Removes the blower, venturi, gas valve and cover plate as one assembly; the burner is removed from the cover plate for cleaning. - Access and clean heat exchanger, Ultra-80 and Ultra-105
Removes the blower, venturi, gas valve and cover plate as one assembly for pin-side cleaning. - Add a DHW secondary connection for high-flow or high pressure-drop DHW
Use this layout when DHW circuit flow exceeds what the boiler allows, or when a coil-type DHW tank has high pressure drop. DHW water flows only throug - Add antifreeze to the system
Use only antifreeze listed by WM Technologies for ECO Tec boilers. - Add Sentinel X100 inhibitor
X100 is recommended for all SlimFit boilers to protect the heat exchanger. It is required when softened water is used. - Additional heat demand dry contacts (P16 pins 6 and 7)
Dry contacts can call a second heat source for extra heat. Contacts are rated 24VAC or less and 0.5 A or less. - Additional high temperature limit in ASME systems
ASME installations may need a manual reset high temperature limit in the supply piping between the boiler and its isolation valve. Its setting must st - Additional limit controls and external limit wiring
ASME installations may need a manual reset high temperature limit in the supply piping. Systems with low-temperature circuits should protect them with - Additional limits and low water protection
The control provides high limit and low water protection. Some jurisdictions require external limits. - Adjust boiler bypass valves (high water content systems)
For high water content systems such as converted gravity systems. Not for radiant panel systems. Does not protect against high supply temperature. - Adjust gas valve throttle screw to correct combustion
Only for a qualified technician using calibrated combustion test instruments. Do not adjust the throttle screw at low fire; only check low fire values - Adjust high fire CO2 at the gas valve throttle screw
Set the high fire CO2 to the target in the combustion table using the throttle screw. - Adjust low fire CO2 at the offset screw
Set the low fire CO2 using the offset regulating screw under the 4mm cap. - Adjust system bypass valves (primary/secondary bypass)
Used for high water content, radiant or low-return-temperature systems. Adjust valves to raise return water temperature to the boiler. - Air vent and fill valve placement
Do not use an automatic air vent with a closed-type expansion tank, because it lets air out and waterlogs the tank. The fill valve must always connect - Annual service inspection
Service technician inspection done at the start of each heating season, before start-up. - Annual service inspection steps
Routine checks that go with the annual startup. Electrical power must be off before service, except where the manual states otherwise. - Annual shut-down procedure
Shut the boiler down for an extended period while protecting the piping from freezing. - Annual start-up checklist
Service technician annual start-up for Ultra Series 4 boilers. Start-up checkout continues at Startup, fill the system (p. 35). - Annual startup and general maintenance checklist
Service technician checklist for the yearly startup. - Annual startup and inspection
Service technician annual checks. Start with the reported problems and work down the list. - Annual startup and maintenance schedule
Service technician tasks for the annual startup, plus owner tasks that run daily, monthly, every six months and at end of season. - Annual startup: check boiler relief valve
Operate the relief valve lever to confirm the waterway is clear. Relief valve reinspection is also required on a set schedule. - Annual startup: check boiler wiring and control settings
Final wiring and settings check during annual startup. - Annual startup: check expansion tank
Confirm the expansion tank type is correct, its fill level or charge is right, and it is sized for the system. - Annual startup: check ignition cable and ground wiring
Check ignition cable resistance and ground continuity from the ignitor to the ground terminal strip. - Annual startup: check the boiler area, air openings and venting
Confirm the room and air supply are clear and that the venting is sound before starting the boiler. - Annual startup: check water system and cold fill pressure
Check that the water system is correct and that pressure stays within limits while the boiler heats. - Annual startup: check wiring and control settings
Part of annual startup before the flame and combustion checks. - Annual startup: clean the condensate trap
Clean the condensate trap during the yearly startup if debris has collected in the reservoir or trap. - Annual startup: inspect and clean the air inlet box screen
Check the air inlet screen for debris. In direct vent installs, the air inlet box is reached by removing the cover on the air pipe inspection tee. - Annual startup: inspect boiler area, interior and door gaskets
Confirm the area and the interior are clear before the burner work. - Annual startup: inspect flame sense assembly
The flame sensor is the shorter rod with a pink ceramic insulator. It mounts on the piping end section. - Annual startup: inspect ignition electrode
The ignition electrode is the longer rod with a brown ceramic insulator. It mounts on the burner end section. - Antifreeze limits and precautions
Antifreeze concentration must not exceed 50% by volume. Higher concentrations can cause sludge and heat exchanger damage. - Application B2 thermostat interface unit and U-Control wiring
Shows the boiler 120 Vac input, the TIU (SR-503-5) and the U-Control connections for the Primary/Secondary layout. The TIU handles the main heating en - Application B3 piping and circulator requirements
Multi-zone space heating with boiler-only DHW, used with the Ultra easy-up manifold. Piping must be primary/secondary. The boiler must sit downstream - Application B3 piping layout
Piping diagram for the B3 layout on an easy-up or field-fabricated manifold. The legend lists the boiler, heat pump, relief and drain valves, circulat - Application B3 wiring to boiler and TIU
Wiring for the B3 layout. The boiler connects to the 120 Vac input. The TIU main end switch handles heating. Zone circulators and the boiler circulato - ASME high temperature limit installation
If the install must meet ASME requirements, an external high limit is needed. Set it at least 20°F above the operating setpoint. The external limit ca - Assemble condensate PVC fittings
Solvent-weld joints must be cleaned, primed and cemented in the order given. The gasket seals the jacket at the condensate outlet. - Assemble pedestal floor stand and mount boiler
Assemble the two stand sections, attach them to the boiler cabinet, then level the boiler. Hardware differs by model, so check the mounting hole desig - Assemble PVC or CPVC vent and air pipe joints
Gluing procedure for plastic vent and air piping on SlimFit boilers. Dry fit everything first. - Assemble solvent-cement vent and air piping
Dry-fit the full run first, then cement each joint so it seals and does not leave excess cement inside. - Assemble the pedestal floor stand
Assemble the floor stand kit 383-800-245 and attach it to the boiler cabinet before setting the boiler upright. - Automatic air vent check
Applies only to systems with diaphragm-type expansion tanks. Automatic air vents must not be used with other tank types. - Basic control setup procedure
Set up the control in order: decide inputs/outputs, install the boiler, wire the control, then use the Wizard or enter settings manually. - Basic field wiring checklist
Turn off power at the service entrance panel before any connection. Wiring must follow the National Electrical Code or the CSA C22.1 Canadian Electric - Basic single boiler setup order
The manual gives a four-step order for a single boiler with the basic control. Install the boiler first, then set up the control. Use the Wizard or se - Before servicing the boiler
Safety checks to complete before any maintenance work on the Ultra boiler. - Before troubleshooting
Confirm the supply and inputs before diagnosing any fault. Use the recommended tools. - Before troubleshooting: power and wiring checks
Basic checks before diagnosing a boiler that will not fire. Always turn off all power before servicing; the ON/OFF switch does not remove all power. - Black water condition
Dark, dirty boiler water caused by oxygen corrosion. - Blower calibration at first startup
The control calibrates the blower motor to the vent length and other installation factors so blower speed is right for all operation. Calibration runs - Blower calibration will not start
Blower calibration in Boiler Settings re-learns the blower for best performance. It only runs with the boiler in standby. - Blue banner or wrench symbol on the display
The maintenance timer ran out (12 months by default). It only shows in standby and the boiler keeps running normally. A blue banner during a heating c - Boiler 120VAC power supply wiring
Main boiler power feed on terminal strip T1. Models 110/155 draw under 12 A. Models 220-399 need the load worksheet to size the supply. - Boiler and system circulator relay requirement
An external relay with external power is required for the boiler circulator when its load exceeds 2.2 A FLA, 3.6 A locked rotor, or 16.4 A inrush. An - Boiler circulator location and flow limits
The boiler circulator must be supplied by the installer, placed only on the return piping. Wrong placement or sizing causes unreliable operation and n - Boiler circulator wiring in primary/secondary piping
The boiler circulator runs in the boiler loop. Primary/secondary piping is recommended to keep proper flow through the heat exchanger. - Boiler does not start
Checklist from the start-up section when the boiler fails to light. - Boiler does not start correctly
Check these items first if the boiler fails to start. - Boiler does not start – initial checks
Work through these checks before going to the troubleshooting section. - Boiler drain connections
If no drain valve is installed off the return piping, two 1-1/2 inch FNPT boiler drain connections are available. One is at the lower front of the hea - Boiler exposed to water (flood or submersion)
Do not start a boiler, burner or control that has been sprayed or submerged. Damaged electrical parts and salt contamination cannot be trusted. - Boiler exposed to water or saltwater
If any part of the boiler, burner or controls was sprayed or submerged, do not run it. Replace or fully repair, inspect and confirm all components are - Boiler fires or pumps run with no call for heat
Two built-in functions can do this. Freeze protection starts the chosen circulators when the heat exchanger sensors drop below 45°F, fires the burner - Boiler location and installation checks
Check the site before setting the boiler. Gas controls must be protected from dripping or spraying water and rain. - Boiler needs make-up water often, popping noise or black water
Make-up water keeps going into the boiler. Fresh water brings in minerals and oxygen, which cause popping/percolating noise in the sections (lime) and - Boiler receptacle on right side panel
120VAC receptacle on the right side panel, rated 2 A max, intended for a condensate pump. - Boiler relief valve testing and replacement
Keep the relief valve working. Replace it if it weeps or will not seat. Do not set the boiler limit control above 10 PSIG. - Boiler room combustion air openings
Direct exhaust boilers take combustion and ventilation air from the boiler room. Openings must be sized for all appliances and air movers in the room. - Boiler shut down by blocked air or vent
The control shuts the boiler down when combustion air or vent is blocked and tries to restart within about an hour. - Boiler shut down or locked out by an external limit on J20
J20 has two limit circuits, each shipped with a jumper. Pins 1-2 are manual reset: if a limit there opens, the boiler locks out, the alarm contacts cl - Boiler stays in standby and display shows WWSD
Boiler will not fire because outdoor temperature is above the warm weather shut down setting. This is normal operation. - Boiler that has been flooded or sprayed with water
Do not operate a boiler whose burner, controls or any part has been wet or submerged. Saltwater and polluted water contamination also leads to warrant - Boiler that has been submerged or flooded
Water-damaged boilers and electrical components are not safe to start. - Boiler that was submerged or sprayed with water
If any part of the boiler, burner or controls was sprayed or submerged, the boiler must not be run until replaced or fully repaired and inspected. Sal - Boiler water chemistry and system flushing
The aluminum heat exchanger needs controlled water chemistry. Sediment and hard water scale can damage it. - Boiler will not fire with a flow switch or damper on J18
The proof-of-closure circuit on J18 comes with a jumper. A flow switch or combustion air damper end switch can replace it, and the boiler only fires w - Boiler will not light / repeated ignition failure
The control retries ignition after a failed flame check. After five failures it locks out for 60 minutes. Display banner turns red on an error or limi - Boiler will not start - startup checks
Work through these checks in order before going to the troubleshooting section. - Bolt the boiler down to mounting blocks (seismic or code requirement)
Where the boiler must be anchored, remove the casters and bolt the base to mounting blocks through the existing base holes. - Build separate-pipe vertical and sidewall terminations
Terminations use bird screens (bought separately) and fixed dimensions. Air intake and vent outlet must face the right way and sit at the right height - Burner access, cleaning and replacement
Remove the mixing tube assembly to reach the burner. - Burner flame and flame signal check
Check the flame and the flame signal reading in the U-Control. - Burner short cycles (turns on and off often)
The burner keeps starting and stopping on short cycles. On these boilers it is usually the thermostat or the limit setting, not the burner itself. - Burner tries to light, then waits about an hour before the next try
Each call gets up to 5 light-off tries. After a failed try the gas valve closes, the blower runs a postpurge and the control starts over. After the 5t - Category II (negative pressure) vent requirements
SlimFit boilers can be installed as Category II with a designed vent system. The vent must hold negative pressure, and flue temperature must stay unde - Category II draft control devices
Because the SlimFit runs cooler flue gas, it may not create enough draft. Add draft control and safety devices as recommended to keep negative pressur - Category II negative pressure aids: fan, damper and spill switch
Where natural draft cannot keep the required negative pressure at the boiler outlet, Weil-McLain recommends added draft or flow control devices. Impro - Category II venting requirements
The SVF 1500 to 3000 can run as Category II (negative pressure, likely to condense) in addition to Category IV. Category II needs an engineered vent s - CGa boiler does not start (no fault shown)
Quick checks before going into the fault table. - CGa display backlight colours
The colour of the display tells you what the control is doing. - CGa pilot ignition sequence and lockout reset
What the control does on a call for heat, so you know where it is stuck. - Check air openings and flue/air piping
Confirm combustion air is unobstructed and vent and air piping is sealed. - Check air pressure switch setting with manometer
Confirm the air pressure switch closes at the correct draft reading during ignition attempts. - Check all piping for leaks
Verify water and gas piping is leak-free. - Check automatic air vent operation
Test a system air vent before relying on it. The discharge water may be very hot. - Check automatic air vents
Only applies to systems with diaphragm-type expansion tanks. Water from the vent can be very hot. - Check blower speeds
Compare blower RPM at each firing rate with the blower speed table (Figure 79, page 88). - Check blower speeds at low fire, ignition and high fire
Compares blower RPM with the altitude tables for the installed fuel and altitude. - Check blower speeds at low, ignition and high fire
Run manual test mode at each firing rate and compare blower RPM to Figure 121. Enable high altitude only above 5,500 ft. - Check blower speeds at low, medium and high fire
Compare blower RPM at each firing rate against the reference table. Altitude setting affects this check. - Check blower speeds in manual test mode
Confirm blower rpm at low, ignition and high fire against the firing rate tables. - Check boiler piping for leaks and gas odor
Check gas lines and water piping on a regular basis. Any gas odor or leak needs immediate shutdown and a qualified service technician. - Check boiler relief valve
Verify the relief valve is clear and seats properly. - Check boiler wiring and control settings at annual startup
Final wiring and settings check before the boiler is put back in service. - Check burner flame
Inspect the flame through the observation window at high and low fire. - Check burner flame (annual startup)
Inspect the flame through the observation window. Clean or replace the burner if the flame is poor at high or low fire. - Check burner flame at high and low fire
Visual flame check through the observation window, then combustion check with instruments. - Check burner flame at high fire and low fire
Judge flame quality through the observation window at both firing rates. - Check burner flames
A proper pilot flame is blue with the inner cone engulfing the pilot flame sensor, and the sensor glows cherry red. A proper main burner flame may sho - Check call for heat and control inputs
Use when the boiler does not start on a call for heat. - Check call for heat, limits, connectors and gas pressure
Basic checks when the boiler does not fire. Gas pressure limits are from the manual. - Check combi DHW function, 3-way valve and brazed plate
Verify the combi boiler switches between space heat and domestic hot water. - Check control fuses
Use this before replacing the control or major components. - Check control module and circulator/blower fuses
Check fuses before replacing the control module or major components such as the blower. A blown fuse can keep the control or components from running. - Check control module and expansion module fuses
Check fuses before replacing the control module or major components such as the blower. A blown fuse can stop the control or other components. - Check control module fuses
Check both fuses before replacing the control module or major components such as the blower. - Check control settings and perform startup checks
Final verification after the mechanical checks. - Check expansion tank
Confirm the tank is the correct type, size and charge. - Check expansion tank(s)
Confirm the expansion tank is sized and charged correctly. - Check external thermostat circuit for stray voltage
Confirms the external wiring carries no voltage when thermostats, zone valves or relays are closed. - Check flame and combustion at high and low fire
Combustion is checked with calibrated instruments at high fire and low fire, with the firing rate forced in Manual test mode. - Check flame and combustion at high fire
Force high fire, then check the flame and flue gas with calibrated instruments. The flame should be blue and stable, with orange dots over the burner - Check flame and combustion with instruments
Measure combustion at the flue with a calibrated analyzer after the boiler is firing. - Check flame signal
Read the flame signal in Diagnostics/Inputs. It must be at least 20 above the shutdown value for the model (Figure 119). - Check flue gas temperature
Flue temperature check at high fire. - Check flue gas temperature at high fire
Flue gas temperature at high fire should be no more than 54 °F above boiler return temperature. - Check flue gas temperature versus return temperature
Flue gas should not run far above the boiler return temperature at high fire. - Check for contaminated combustion air
Corrosive contaminants in combustion air can damage the boiler. Dust from construction is also a problem. - Check for gas leaks before and during startup
Do not start the boiler if there is any sign of a gas leak. - Check for gas leaks before start-up
Before starting the boiler and during first operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Do not start up - Check gas piping for leaks
Checks for gas leaks during annual service and when a leak is suspected. - Check gas supply pressure and leaks
Check the supply pressure at the gas valve and test the connections for leaks. - Check gas supply pressure at the gas valve
Measure inlet pressure at the 1/8 in Port 2 on the gas valve with a manometer or gauge. Confirm minimum gas pressure while gas is flowing and the boil - Check heat exchanger, vent seals and condensate dish joint
Check for leaks at high fire using an inspection mirror. - Check heat exchanger, vent seals and condensate dish joint for leaks
Find leaks at the top of the boiler using a mirror at high fire. - Check if a reservoir pipe is needed on a steam return
Modern steam boilers steam for less time than older boilers. If the condensate return takes longer than the steaming time, the boiler can overfill wit - Check ignition cable and ground wiring
Verify ignition cable resistance and ground continuity. - Check ignition safety shutoff device
Confirms the boiler locks out when ignition fails. - Check ignition system safety shutoff
Confirms the ignition lockout works. Done after installation. - Check ignition system safety shutoff device
Confirm the ignition safety device locks out when there is no fuel. - Check inhibitor and antifreeze levels yearly
Water chemistry and antifreeze strength change over time, so test them at least once a year. - Check inlet gas pressure
Confirm incoming gas pressure at the boiler's inlet test port. - Check internal circulation pump
Confirm the pump runs and water is flowing during operation. - Check manifold orifice sizing
Confirm the burner orifices match the gas type and altitude before firing. The size is stamped on the orifice spud barrel. - Check natural gas input rate
Compare measured gas input against the boiler rating label. Run the boiler first and turn off other gas appliances. - Check piping, air openings and venting
Leaks, blocked air openings and damaged venting all cause safety and reliability problems. - Check pressure switch sense hoses
Sense lines must be in good condition and on the correct fittings. Wrong or loose lines cause unreliable operation. - Check relief valve and expansion tank
Relief valve and expansion tank checks for a relief valve that weeps. - Check remaining appliances on old common vent when removing a boiler
Before an SVF boiler replaces an older boiler on a common vent, test each appliance left on that vent, one at a time, to confirm it still vents correc - Check system and boiler before and after first start
Check piping, venting and gas odor after the boiler has been started and before final checks. - Check system and boiler before first start
Checks to complete before starting the boiler and before handing it over. - Check temperature sensors
Sensors (flue, outdoor, boiler in, boiler out, return, system) are resistance type. Compare readings to the sensor table. - Check temperature sensors (resistance method)
All boiler sensors (flue, outdoor, return water, supply water) are resistance type. Compare measured ohms with Figure 123. - Check temperature sensors (resistance test)
Sensors are resistance type. Compare measured ohms to the tables at known temperatures. - Check temperature sensors with an ohmmeter
Compare sensor resistance against the reference table. - Check the burner flame
Visual flame check at high and low fire, with burner cleaning if the flame is poor. - Check the control fuses
Check the control fuses before replacing the control or major components. A blown fuse can stop the control or other components from working. - Check the expansion tank
Check tank type, fill and sizing. A relief valve that weeps often points to a waterlogged or undersized tank. - Check the flame signal
The control uses three flame signal thresholds: Boost, Shutdown and Proof of Flame. - Check the high flue pressure switch
Confirms the high flue pressure switch trips and the control locks out as expected. - Check the limit control and extra high limit (oil water boiler)
How to prove the limit stops the burner, and how the optional second high limit is set. - Check the thermostat circuit for stray voltage
The thermostat terminals must never see voltage. Voltage there will damage the control. - Check the water system and automatic air vents
Annual check of fill pressure, pressure rise and air vents. - Check thermostat circuit wiring
Used to find external wiring that is sending voltage to the boiler thermostat terminals. A common cause is 3-wire zone valves. - Check thermostat circuits for stray voltage
Confirm no voltage is fed back into the control from external devices. - Check vent system operation with candle or match test
Check the vent system at least once a month during the heating season. A flame held at the draft hood should burn undisturbed when the vent is working - Check venting system operation (monthly in heating season)
Check the vent system at least once a month during the heating season while the boiler is firing. A proper draft keeps the flame steady when a test fl - Check water and antifreeze concentrations annually
Check pH, inhibitor and antifreeze at least once a year. - Check water chemistry and inhibitor at least yearly
Water and inhibitor are checked after fill and once a year to prevent corrosion. - Check water system pressure and air vents
Confirm cold fill pressure and that system pressure stays in range while heating. - Check water system pressure and automatic air vents
Confirm cold fill pressure and control pressure rise during heat-up. - Checking a damper output during a boiler call
Use this when a combustion air damper, flow switch or interlock output does not act the way the boiler should during a call for heat. The output's tim - Checking boiler temperature sensors
Boiler In, Boiler Out, DHW Out, Flue, Outdoor and System Supply/Return sensors are all resistance type. Compare measured resistance with the sensor re - Checking control fuses
Check all control fuses before replacing the control or major components such as the blower. A blown fuse can stop the control or other components fro - Checking the boiler out (supply) temperature sensor
Resistance-type sensor. Check its value against the reference table and confirm the control reads temperature correctly. - Checking the boiler out sensor
Check the boiler out resistance-type sensor against Table 16 and confirm the control reads it correctly. - Checking the CGa boiler out temperature sensor
How to test the outlet thermistor and the control's reading. - Checking the limit control on a WTGO boiler
The combination limit control (in the tankless heater plate, with low water cut-off) shuts off the burner on high water temperature but lets the circu - Chemical cleaning of domestic hot water circuit: precautions
Read before any descaling. Water harder than 7 grains must be treated before it enters the combi. Only NSF-approved cleaners safe for consumption and - Chemical cleaning of the domestic hot water circuit
Connect a circulating pump with chemical to the DHW cold inlet and DHW outlet, clean, rinse and restore the boiler. - Chilled water system piping
The chilled medium is piped in parallel with the boiler and kept out of the boiler with valves. - Chilled water system piping (boiler in parallel with chiller)
The chiller is piped in parallel with the boiler. Valves keep chilled medium out of the boiler. - Chiller and air handler piping precautions
If the boiler is near a chilled medium, pipe the chiller in parallel with the boiler and keep the chilled water out of the boiler. If heating coils in - Chimney and vent requirements
Venting must follow Part 7 of the National Fuel Gas Code and local building codes. A chimney or vent without a listed cap must extend at least 3 feet - Chimney and vent termination requirements
Vent must follow NFPA 54 and local codes. Chimneys and non-Type B vents must extend at least 3 ft above the roof penetration and 2 ft above any buildi - Chimney draft venting requirements
Natural draft venting through a vertical vent or chimney, Category I. Vent sizing is a general guide only. Code requirements govern. - Chimney use as a vent chase
A masonry chimney may only be used as a pipe chase for vent and air piping. No other appliance or fireplace may connect to it. - Chimney used as pipe chase
A masonry chimney may only be used as a pipe chase for vent pipe. The vent pipe must be installed per manual with all joints sealed. No other applianc - Choose direct connect or primary/secondary piping
Primary/secondary is recommended and gives the most accurate system temperature. Direct connect is only for eligible heat-only systems. - Choose the vent and air termination method
Vent and air must exit through the sidewall or roof using only one of the methods described in this manual. - Choosing direct exhaust or direct vent
Direct exhaust takes combustion air from inside the boiler room, and the air piping is not connected to the air inlet. Direct vent pipes combustion ai - Circulator control and expansion for more zones
The control can run up to four circulators: the boiler circulator plus three others. - Circulator zoning with a DHW zone
Each zone gets its own circulator. The boiler circulator must serve only the boiler loop. An AQUA PLUS 60 can be wired as zone 1 at the U-Control. - Circulator zoning with primary/secondary piping
Each zone has its own circulator and the boiler loop runs as a secondary off the primary system loop. Optional DHW piping can be added. - Circulator zoning, primary/secondary
For circulator-zoned systems where the boiler loop is a secondary circuit off a primary system loop. Each zone has its own circulator. - Circulator zoning, primary/secondary piping
Each zone has its own circulator. The boiler loop is a secondary circuit off the primary loop. - Clean and test float-type low water cutoff
Clears sediment from the float chamber and checks the float-type low water cutoff shuts the boiler off at low water. - Clean boiler heating surfaces
Remove soot and boiler cement buildup from the heating surfaces and collector hood. - Clean cast aluminum heat exchanger, water side
Water-side cleaning for the aluminum heat exchanger. Trisodium phosphate (TSP) must not be used because it strips the protective oxide layer. - Clean condensate trap
Clean the condensate trap at each annual startup. - Clean heat exchanger pins with cleaning tool and water
Loosen deposits between the heat exchanger pins, then flush them down to the base and out through the condensate line. - Clean heat exchanger, pin side
Procedure to shut down the boiler and open it for pin-side heat exchanger cleaning. Ceramic fiber materials are present. - Clean main burners
Clean the main burners and reseat them correctly. Improper seating can cause serious injury or property damage. - Clean temperature/LWCO sensor
Deposits on the probe reduce boiler performance and must be cleaned at annual inspection. - Clean the aluminum heat exchanger (water side)
The heat exchanger is cast aluminum, so use only the approved cleaner. Trisodium phosphate (TSP) must not be used in systems containing aluminum becau - Clean the condensate trap
Keep the trap clear so flue gas cannot leak through the condensate drain. - Clean the heat exchanger - flue side
Remove the cleanout plate and burner, then clean the flueways. - Clean the heat exchanger - water side
Clean scale from the water side of the aluminum heat exchanger. Do not use trisodium phosphate (TSP); it strips the protective oxide layer from alumin - Clean the heat exchanger flue side interior
Remove the control circuit board first so water does not reach it. Use a strong light to confirm the flue ways are clear. Do not use any solvent on th - Clean the heat exchanger water side
Use this when sediment or corrosion is found in the heating water. The boiler must be isolated from the system, the system must be cleaned of all sedi - Clean the steam gauge glass
Normal steam waterline is halfway up the gauge glass. Clean when needed with pressure low. - Clean the system before filling
Sediment can damage the high-efficiency heat exchanger. - Clean the system to remove sediment
The heat exchanger can be damaged by sediment, so flush the system before the boiler is connected. - Cleaning boiler heating surfaces (annual)
Annual cleaning of the heat exchanger sections, burners and base. Boiler contains ceramic fiber and fiberglass, so handle per the safety instructions - Cleaning main burners
Clean the main burners by vacuuming or brushing off dust and lint. Reseat them correctly when reinstalling, or the boiler can fail to operate safely. - Cleaning the CGa temperature/LWCO sensor probe
Deposits on the probe affect the water temperature and low water readings. Clean it once a year. - Close clearance install: burner off on manual reset temperature switch
In an alcove or closet install with the close clearance kit, a manual reset temperature switch near the ceiling is wired in series with the thermostat - Close-clearance install: boiler off on manual reset temperature switch
Boilers installed with reduced clearances (alcove, closet, under a counter) use close clearance kit 386-500-050. Its manual reset temperature switch i - Closed-type expansion tank piping
Air is in direct contact with the tank water in this layout. Never use an automatic air vent with a closed-type tank, because it removes air and water - Closed-type expansion tank piping (single zone)
Size the closed-type tank for the system volume and temperature. Connect it to the ½-inch NPT tapping behind the supply outlet with ½-inch NPT piping. - Closure switch (flow switch or CAD) interlock wiring
Optional proof-of-closure interlock. Remove the jumper on terminal strip P11 to use a flow switch or combustion air damper (CAD) interlock. No control - Closure switch (flow switch or CAD) lockout
A flow switch or combustion air damper interlock must make before the blower runs. The control allows four minutes for the switch to make, and a locko - Code compliance and venting basics
Venting and combustion air piping must meet the Air for Combustion and Ventilation provisions of NFPA 54 (ANSI Z223.1) or CSA B149.1 sections 8.2 to 8 - Codes and approvals for installation
Installation must follow local, state and national codes, the National Fuel Gas Code (ANSI Z223.1/NFPA 54), ANSI/ASME CSD-1 where the authority having - Codes and pre-install checks before locating the boiler
Confirm the install follows the local codes, the National Fuel Gas Code (NFPA 54 / ANSI Z223.1), the NEC (NFPA 70) and, in Canada, CAN/CSA B149.1 or B - Combustion air and boiler room ventilation
Direct vent is the normal approach; direct exhaust is possible with the approved kit. Air openings depend on the room and other appliances. - Combustion air and contaminant avoidance
Contaminated combustion air can damage the boiler. Keep the air intake away from sources of corrosive contaminants. - Combustion air contamination
Chlorine or fluorine compounds in intake air form acids in the vent and boiler, which corrode them and can allow flue gas spillage. Products to avoid - Combustion air contamination and air intake location
Contaminated combustion air will damage the boiler. Keep the air intake away from sources of chemicals and dust. - Combustion air contamination check
Corrosive contaminants in the boiler room or the combustion air source can damage the burner and heat exchanger. Check the room and the air source bef - Combustion air contamination check before piping air or openings
Corrosive vapours and dust can enter combustion air and damage the burner and heat exchanger. Keep intake areas and boiler room clean. - Combustion air from the boiler room (inside air)
The SVF can use inside air only when no contaminants are present. Where contaminants are likely, install it as direct vent. The boiler room needs open - Combustion air manifold (Category IV, direct vent only)
Several Category IV SVF boilers can share one combustion air duct. Only the air inlet piping may be combined. Vent piping must never be combined. - Combustion air openings to the boiler room
A direct vent boiler alone in a room needs no ventilation openings if the room keeps the minimum service clearances from Figure 2. If it does not, use - Combustion check at high and low fire
Check flame and combustion with calibrated instruments at high and low fire. - Commissioning check-out highlights before handover
Key verifications from the startup checklist. Complete full checklist and certificate on page 140. - Commissioning verification checklist
Confirm all commissioning items are complete before leaving the boiler. The list covers controls, water, air purge, condensate, thermostat wiring, com - Component identification: control module and key parts
The control module receives input from the room thermostat, air pressure switch and limit circuit, and runs the circulator, pilot, gas valve and induc - Concentric 3 in or 4 in sidewall termination: kit and piping rules
The concentric termination kit is purchased separately and must match the materials and adapters in Figure 12. The maximum-length allowance covers one - Concentric termination assembly
Assembling the inner and outer pipe termination kit before installation. - Concentric termination: piping supports and slope
Support the vent and air piping so the weight does not rest on boiler fittings. Pipe must be supported well enough that the termination cannot slip or - Concentric vent/air termination (vertical through roof)
Concentric termination must be assembled and installed before the piping from the boiler is connected. It needs proper roof flashing, supports and a r - Condensate drain check (220/299/300/399)
On larger models, flue gas smell or escaping flue gas at the condensate drain or tee means the trap is dry. The drain line must also run freely. - Condensate line - sizing, pump and materials
Route condensate to drain or pump and keep the line open so it cannot back into the boiler. - Condensate trap check (110/155)
On 110/155 models the condensate trap sits under the boiler with a ball float. The trap must hold water so flue gas cannot enter the room. - Condensate trap has dried out (flue gas at drain)
With the boiler running, flue gas coming out of the condensate drain means the trap is dry and must be refilled. Flue gas in the room is a safety haza - Condensate trap installation
Install the condensate trap in the correct vertical position so flue gas cannot escape through the drain. - Confirm electrical service and sealing before power-up
Field electrical steps before the boiler is energized. - Confirm start-up readiness before operating
Do not run the boiler until the boiler and system are full of water and all earlier procedures are complete. Read the operating instructions first and - Connect 120 VAC power to the boiler
Line voltage supply to the boiler terminal strip, with grounding and surge protection. - Connect and leak-test the gas supply piping
Gas connection work on the 550/750 SlimFit. Support the piping with hangers so the boiler is not carrying the load, and use two wrenches so the boiler - Connect condensate trap line
Hose clamps secure the trap line. The method changes between the smaller Ultra-80 and -105 and the Ultra-155 and larger. - Connect gas supply piping
Gas piping must be supported and leak-tested, and the gas valve outlet must not be adjusted. - Connect gas supply piping and check for leaks
Gas piping connection and leak test procedure at the boiler. - Connect gas supply piping and leak check
Boilers ship set for natural gas only. Install the propane mixer (venturi) and orifice before connecting propane. Pipe dope and leak checks are safety - Connect gas supply piping to boiler
Gas connection is ½ in. NPT male on top of the boiler. Installer supplies the shut-off valve and fittings. - Connect gas supply piping to the boiler
Gas piping must be leak-checked before the boiler is placed in operation. Remove the jacket front panel and follow the gas supply piping layout in Fig - Connect PVC/ABS vent or air pipe to the boiler adapter
Use a smooth, chamfered pipe end so the adapter gasket seals. The clamp only holds the pipe; the seal comes from the internal gasket. - Connect the direct exhaust vent starter
Attach the vent starter to the blower housing outlet and seal it. Sealant method varies by vent brand. - Connect vent and air pipe at the boiler
Work from the boiler outward to the termination. Use the adapters and connection sizes given for the pipe material in use. - Connecting PVC/ABS vent or air pipe to the boiler adapter
Vent and air pipe connect to the boiler with a clamped adapter that seals on an internal gasket. The clamp only holds the pipe. - Constant makeup water, black water or popping noise (water boiler)
Boiler needs water often, water is black, or the block pops and percolates. - Constant makeup water, dirty water or popping noise (steam)
Boiler needs water added often, water looks black or rusty, or the block pops and percolates. - Contaminant sources to avoid for combustion air
Combustion air must not contain chemicals or dust that can corrode the burner or heat exchanger. Keep air intakes and boiler room air away from these - Contaminated combustion air
Corrosive contaminants in the combustion air will damage the boiler. Check the air inlet location and the surrounding area before installing. - Convert natural gas boiler to propane
Propane conversion needs the correct LP kit and a flue gas analyzer. The gas supply must be shut off and power disconnected before starting. The ventu - Convert propane boiler to natural gas
Same process as the propane conversion, using the natural gas kit and with the propane orifice removed. Natural gas boilers have no orifice. - Convert SlimFit boiler from natural gas to propane
Boilers ship set for natural gas. Propane needs a propane orifice, and the Model 750 also needs a blower orifice. The conversion kit is supplied with - Converting the boiler from natural gas to propane
The boiler ships set for natural gas and needs a propane orifice for propane. Use only the orifice in the conversion kit, which is 0.660 inch and mark - Cooling down and draining before servicing the brazed plate heat exchanger
Let the brazed plate exchanger cool before opening it, since water inside may still be hot and can cause severe injury. - Correct system problems when replacing an existing boiler
If a new boiler replaces an old one, find and fix system problems first so the new boiler is not damaged. - Corrosive contaminants and areas to avoid near combustion air
Combustion air must not contain these corrosive contaminants (Table 7). Keep air inlets away from the areas listed below. - Counterflow steam header connection
With a counterflow system, the boiler steam supply must tie into the top of the counterflow header. Figure 22 on the next page shows the arrangement. - Critical setup: boiler model and altitude
Boiler model and altitude are critical settings. Wrong values can cause severe injury, death or property damage. Water temperature must also be set co - Cycle boiler with thermostat
Checks that the boiler responds correctly to the room thermostat at both ends of its range. - Daily check of air openings and boiler area
Check that the combustion and ventilation air paths and the vent discharge are clear. - Daily maintenance checks
Quick daily walk-around of the boiler room and gauges. - Daily owner checks
Quick visual checks the owner or technician makes every day to confirm the boiler is safe to run. - Determine if water treatment is needed and clean the system
Petroleum-based cleaning or sealing compounds must not be used in the boiler system. Leaks must be eliminated because continual fresh makeup water sho - DHW tank connection options
A DHW tank can be piped direct to the boiler or treated as a zone, depending on the layout. - Diagnostics menu run times, counters and lockout history
Read-only history and status items in the DIAGNOSTICS menu. Use them to review past lockouts and operating time. - Diaphragm or bladder expansion tank piping
Air must be removed from the system when a diaphragm or bladder tank is used. - Diaphragm or bladder expansion tank piping (single zone)
The expansion tank must be sized for the boiler and system water volume and temperature. Place it on the boiler return piping as close to the boiler a - Diaphragm or bladder expansion tank piping and pressure
Size the tank for boiler and system water volume and temperature. Undersized tanks lose water through the relief valve and add make-up water, which ca - Direct exhaust boiler room air openings
Size the boiler room openings for combustion and ventilation air when the boiler uses inside air. Openings must also handle the air movement of any ex - Direct exhaust conversion and combustion air openings
Direct exhaust conversion requires the Weil-McLain Direct Exhaust Venting Kit. Boiler room combustion air openings must be sized for all appliances in - Direct exhaust sidewall termination assembly
The termination needs the boiler kit plates plus installer-supplied parts; do not leave exposed vent pipe longer than shown. - Direct exhaust sidewall termination installation
Category IV direct exhaust with the termination through the sidewall. Use only the vent materials and kits listed in Figure 22. Every polypropylene jo - Direct exhaust sidewall termination location
Sidewall terminations must meet the location rules in the code and the clearances in Figure 27. - Direct exhaust sidewall termination location and length
Keep the vent exit where condensate, vapor and flue plume will not cause damage, injury or nuisance, and keep outside vent length within limits to avo - Direct exhaust sidewall termination steps
Use a coupling that butts against the outside wall plate. Choose the left-side configuration unless it fails minimum clearance to grade or snow line, - Direct exhaust sidewall termination, general rules
Installer-supplied termination. Bird screen is not included and must be bought separately. Keep the termination away from anything that can knock it o - Direct exhaust sidewall vent termination: location and clearances
Where the sidewall direct exhaust vent may exit the building. The SF-550 and SF-750 are condensing appliances, so flue products and condensate must be - Direct exhaust vent installation rules
General install rules for direct exhaust venting: no mixed vent materials, sealed joints, correct slope, clearances to combustibles, and approved pene - Direct exhaust vent pipe general rules
Use a 6 in or 8 in vent pipe. Direct exhaust has no minimum vent length. Use one material type throughout and do not join different piping types. Vent - Direct exhaust vent termination location
Locate the vent termination so every clearance is met. Site conditions may require more clearance. - Direct exhaust venting: approved components
Direct exhaust uses inside combustion air and a pressurized Category III vent. Every joint must be sealed. Use only a listed 3 inch vent system. - Direct exhaust vertical termination installation
Category IV direct exhaust through the roof or a vertical termination. Same material and joint rules as the sidewall method. Use flashing and sealing - Direct exhaust vertical termination location
Place the vertical vent termination where it will not be damaged by debris, leaves or sediment, and where snow will not block it. - Direct exhaust vertical vent termination: location and clearances
Clearances for a vertical (roof) direct exhaust termination. The vent must end in a coupling, and all clearances must be met for the roof, walls, open - Direct exhaust: combustion air from boiler room
Direct exhaust boilers draw combustion air from the boiler room through openings to outside or to other spaces, so the room must not have contaminated - Direct vent sidewall termination (vent and air)
Direct vent uses separate vent and air pipes through the sidewall. Vent and air pipe materials must be from Figure 22. Each pipe needs its own penetra - Direct vent sidewall termination with separate air and vent pipes
Termination layout when combustion air and flue are run as separate pipes through the wall. - Direct vent termination clearances (vent and air through roof)
Vent and air terminations through the roof must meet fixed heights and spacings. Air pipe ends in a down-turned 180-degree return bend with its edge a - Direct vent vertical terminations (vent and air)
Vertical direct vent installs use separate vent and air terminations, which can be roof or sidewall for the air side. - Direct vent vertical vent / sidewall air: vent termination
The vent pipe ends in an up-turned coupling with the top at least 1 ft above the air intake. Keep it at least 6 ft from adjacent walls, 5 ft below a r - Direct vent: down-turned air inlet elbow
The air inlet is a direct vent connection, so it is not treated as a forced air intake for spacing from other vents. Its location must keep flow clear - Display banner turned red
A red banner means the control saw an error or a limit event. The home screen shows the fault name with a reset button. - Display banner turns red
A red banner means the control has detected an error or a limit event. - Display blank and no boiler components running
The control is not getting 120 VAC power. - Display blank and no response to call for heat
The control is not getting 24 VAC power. - Display blank but boiler is operating
Display has lost communication with the control while the boiler still runs. - Display blank but boiler operates (display communication lost)
Communication from the control to the display is lost. - Display blank but boiler operating
Communication lost between the U-Control and the display. - Display red or flashing red
A red display means an error or limit event occurred. A flashing red display means lockout. - Display shows WWSD and boiler stays in standby
Warm weather shutdown keeps the boiler from firing when the outdoor temperature is above the WWSD setting. It does not apply to DHW systems and needs - Do not common vent: removing an old boiler from a common vent
The SVF cannot share a common vent with any other appliance, and it cannot use an existing common vent. Removing the old boiler can leave remaining ap - ECO Tec S2 condensate line blocked or frozen
If condensate cannot drain, it can come out of the boiler tee and cause water damage. - ECO Tec S2 direct-connect piping: temperature rise too low
Direct-connect piping (no primary/secondary) only works on the 80/110/150 heating-only models, and the boiler pump must give at least a 20 F rise at h - ECO Tec S2 display banner red, blue or showing a wrench
The banner colour tells you the boiler state. - ECO Tec S2 does not light: 5 tries then 60 minute wait
If no flame is proven, the control shuts the gas valve, post-purges and tries again. After 5 failed tries it waits 60 minutes before trying again. - ECO Tec S2 locked out by an external limit (J20)
External limits can be wired as manual reset (J20 pins 1-2) or auto reset (J20 pins 3-4). A jumper is fitted from the factory on each pair. - ECO Tec S2 manual reset high temperature limit
The control has a manual reset high limit set on the Boiler Settings screen (shown at 200 F on the setting screen in the manual). If boiler water goes - ECO Tec S2 no space heat in warm weather (WWSD)
With Warm Weather Shut Down on, the boiler will not fire for space heating when the outdoor temperature is above the WWSD setting. DHW still works. - ECO Tec S2 power-up shows wrong model or missing sensor
On power-up the screen shows the boiler model and lists the sensors it finds. - ECO Tec S2 will not light after gas conversion
Coarse gas valve settings get the boiler to light. Final set-up must be done with a combustion analyzer in Manual Test Mode. - Electrical installation requirements
Wiring must meet N.E.C. Class 1. The boiler must be electrically grounded per NEC / ANSI/NFPA 70. Comply with NEC and any national, state or local cod - Electrical installation requirements before wiring
Basic rules from the manual that must be met before making any electrical connection. - Electrical supply and line voltage
Line voltage wiring requirements for the U-Control boiler. - Electrical supply and wiring requirements
The boiler ships with controls wired except the spill switch, circulator and vent damper. Wiring must follow NEC Class 1. Always turn off power at the - End of season shutdown
Shut the boiler down at season's end, unless it heats domestic water. - End-of-season shutdown
Seasonal shutdown steps. Domestic hot water boilers must not be shut down. - Example B domestic hot water circulator wiring
On the Shadow 4 boiler, the three DHW calls (DHW 1 to 3) are wired with 24 VAC to their own W, R and C terminals. Each DHW circulator runs from its ow - Example B multi-boiler field wiring (master and shadows)
Power goes to the master boiler at 120 VAC through the L1 hot, neutral and ground terminals. The boiler circulator connects to the BOILER PUMP termina - Example C master boiler field wiring
The master boiler takes 120 VAC power and the boiler circulator on the BOILER PUMP terminals and 2-pin plug at J4-4. Zone 1 and Zone 2 are wired to th - Example C shadow boiler field wiring (Shadows 2 to 4)
Shadow 2 serves Zones 3 to 6 with Circulators 3 to 6. Shadow 3 serves Zones 7 to 10 with Circulators 7 to 10. Shadow 4 serves Zones 11 to 14 with Circ - Example D - field wiring of master and shadow boilers
Master boiler runs the system circulator and the shell-side circulator through the Aux output. Zone 1 and Zone 2 connect to the master, Zones 3 to 6 t - Example D - heat exchanger shell-side and heating circuit requirements
Heat exchanger shell-side and tube-side piping, pumps and sizing must come from the heat exchanger manufacturer. Tube-side flow and temperatures must - Example D control setup and circulator supply
The required settings are in Table 7, which is not on these pages. The ODT setpoint and the activate contact below setpoint must match the design cond - Example D high mass boiler with isolation heat exchanger
Condensing boilers run during low-load periods such as spring and fall. A high-mass boiler is added for high-load periods. The control sequences the h - Example E - field wiring of master and shadow boilers
Master boiler feeds zones 1 to 3 and the boiler isolation valve. Shadow boiler feeds the DHW circulator or DHW valve, zone 4, the bypass valve and the - Example E - purpose and piping with DHW storage tank
Variable-primary piping with a DHW storage tank directly piped to one boiler (Boiler 2). DHW is given priority on Boiler 2, which stops network heatin - Example F - control setting notes and piping requirements
The variable-primary circulator is run by an external controller in the system. Primary valve control on the boiler is described in the Primary Valve - Example F - purpose and piping for variable-primary multi-boiler system
Space heating with multiple zones, using primary piping and a variable speed system circulator. Each boiler has its own isolation valve (Item 17a) and - Example F field wiring between master and shadow boilers
Wiring layout for the master and shadow boilers, including sensors, zone outputs and valves. - Example F multi-boiler piping and circulator notes
Setup notes for the Example F multi-boiler layout with variable primary circulator and isolation/bypass valves. - Excessive sooting in heating surfaces
Heavy soot in the flue pipe, inducer or between sections shows poor gas combustion. - Existing common vent test when replacing a boiler
Required when removing a boiler from a common vent. The SVF must not use the existing common vent and needs its own vent and air piping. This test che - Expansion tank and make-up water
Size the expansion tank for the boiler and system water volume and temperature (boiler water content is in Table 27, page 142). An undersized tank cau - Expansion tank and make-up water piping
Size the expansion tank for the boiler and system water volume and temperature (boiler water content on page 120). An undersized tank lets water blow - Expansion tank and make-up water sizing and piping
An undersized expansion tank lets system water escape through the relief valve and pulls make-up water in through the fill valve. Excess make-up water - Expansion tank and water connections
General piping rules that apply to every layout on pages 16 to 19. - Expansion tank check
Check the expansion tank when the relief valve weeps often or the pressure rises too high on heat-up. - Expansion tank connection (closed-type tank)
Connection details for a closed-type expansion tank. An undersized tank causes water loss at the relief valve and makeup water at the fill valve, whic - Expansion tank connection (diaphragm or bladder tank)
Diaphragm or bladder tank location and air venting. - Expansion tank installation
Expansion tank sizing and location must keep the system from losing water through the relief valve. - Expansion tank piping, diaphragm vs closed type
Size the expansion tank for the boiler and system water volume and temperature. An undersized tank lets system water blow out the relief valve and for - Expansion tank sizing and placement
Size the expansion tank for the total boiler and system water volume and temperature. An undersized tank lets system water blow out the relief valve a - Express Setup overview
The Wizard is the required method for Express Setup so all required settings are made. Electrical, venting and piping must follow the boiler manual. - External high limit setpoint and multi-temperature systems
Some jurisdictions require an added manual reset high limit. The control high limit shuts the boiler at 195 F or lower if set lower. The external manu - External high-limit and low water cutoff requirements
The U-Control provides high limit and low water protection by sensing the heat exchanger temperature. Some codes or jurisdictions require extra extern - External limit lockout and automatic restart
External limits can be wired for manual reset or automatic reset. Manual reset locks the control out and requires a manual reset. Automatic reset rest - Field wiring for 120 VAC power and service switch
The boiler is powered by 120 VAC through the junction box. A fused disconnect or service switch of 15 amp is recommended. Where local code bars a swit - Field wiring: power, circulator and strain relief
Turn off power at the service panel before wiring. Use N.E.C. Class 1 wiring and type 105 C wire if replacing original wiring. Bond and ground the boi - Fill and test the water system
Fill only after the water meets the chemistry limits. Check for leaks at fill and during startup. - Fill boiler and hydrostatic pressure test
Install the test piping first. The relief valve must not be installed until the pressure test is done. Use pipe dope sparingly on all connections. Tes - Fill condensate trap with water
The condensate trap must hold water whenever the boiler runs. If it is dry, flue gas can escape through the condensate drain. - Fill the condensate trap and check condensate lines
The trap must hold water and have its check float in place whenever the boiler runs. An empty trap lets flue gas out the drain. - Fill the system and set cold-fill pressure
Fill only after the water meets the chemistry limits. Check the whole system for leaks. - Final checks before first start
Complete these checks after the system is filled and before the boiler is started. Look for leaks, make sure the vent and air piping are sound, and co - Final checks before starting the boiler
Complete these checks before the first firing. Gas and venting faults can cause severe injury or death. - First-year special inspection
Extra inspection due no later than 12 months after installation. - Flame not detected at ignition
The control retries after a failed flame check and locks out for a period after repeated failures. - Flame not detected during ignition
If flame is not detected, the boiler shuts off the gas valve, postpurges, and starts the cycle again. The SVF 3000 only gets one ignition attempt per - Float type low water cutoff: clean and test
Periodic cleaning and function test of a float type low water cutoff. Boiler pressure and temperature must be low first. - Floor foundation and flooring requirements
Requirements for floor-standing installations using the pedestal kit. - Flow outside Table 5 range
Do not size piping for flow above or below the Table 5 range without using a suitable piping strategy. Too little flow causes nuisance limit outages. - Flow switch or combustion air damper interlock
Proof of closure can be a flow switch or a CAD interlock. Both are wired through the J18 jumper location. - Flush the system before startup
Sediment must be removed from the system before the boiler is started. Sediment can upset chemical treatment and damage components. - Freeze protection fluid rules
Only use freeze-prevention fluid approved by Weil-McLain. Automotive or standard glycol is never allowed. Flush any system that used glycol before fit - Freeze protection operation
With freeze protection enabled, the control fires the boiler at low fire and starts the selected circulators when heat exchanger sensors read below 45 - Freeze protection with antifreeze
Use only antifreeze made for hydronic systems. Inhibited propylene glycol is recommended. - Frequent need to add makeup water
Constant makeup water indicates a leak. Repeated makeup water leaves mineral deposits that can cause section failure. - Frequent release of water through relief valve
Relief valve keeps discharging water, pointing to expansion tank or limit control problems. - Gas leak check and inlet pressure check
Confirm gas supply pressure at the gas valve test port and check for leaks safely. - Gas leak check and pressure testing
Check the boiler and its gas connection for leaks before operating. - Gas leak found during start-up
Stop work and fix any gas leak before the boiler is run again. - Gas piping for multiple manifolded boilers
Layout requirements when several boilers share one gas supply line. - Gas supply for manifolded multiple boilers
Gas piping setup when several boilers share one supply line. - Gas supply pipe sizing and multiple boiler manifolds
Size the gas supply from the meter to the boiler and set up manifolds for multiple boilers. - Gas supply piping connection and sizing
Install a union for servicing when required and a manual shutoff within 6 ft of the boiler, identified by the installer in Canada. Support gas piping - Gas supply piping connection to the boiler
Connect the gas line at the boiler without twisting the factory gas connection. - Gas supply piping installation
Size the gas line for diameter, length, fittings and maximum gas use. Follow the local code and ANSI Z223.1/NFPA 54 or CAN/CSA B149 for pressure drop. - Gas valve adjustment at high fire
Only a qualified technician with calibrated combustion instruments should adjust the valve. - Gas valve adjustment at low fire
Adjust low fire only after confirming low fire RPM. - Gas valve adjustment at low fire (offset)
Only for a qualified technician. Check low fire after high fire has been set. - Gas valve leakage test
Test each gas valve solenoid separately. Do not connect a manometer to the manual or automatic gas valve, because the blower vacuum can pull fluid int - Gas valve leakage test (solenoids V1 and V2)
Test each solenoid one at a time using the gas valve test harness from the envelope kit. Follow the gas valve maker's leak test procedure as well. Do - Gas valve leakage testing
Test each gas valve solenoid on its own. Do not connect a manometer to either gas valve. - Gas valve offset adjustment at low fire
Set low fire after high fire is correct. Use this only when the low fire combustion readings are outside the acceptable range and throttle screw adjus - Gas valve throttle and offset adjustment
Adjust only as needed to meet Table 16. Confirm the correct low fire RPM before touching the offset screw. Adjust in small steps. Only a qualified tec - Gas valve throttle screw adjustment at high fire
Only a qualified technician with calibrated combustion instruments may adjust the gas valve. Adjust only as needed to reach the CO2 values in the acce - Gas valve throttle screw and offset adjustment
Only for a qualified technician with calibrated combustion instruments. Adjust only when combustion tests call for it. Gas valve outlet pressure is fa - Gas-tight leak check at high fire
The system must be sealed gas-tight to prevent flue gas spillage and CO. Leaks show as vapor on the inspection mirror. - General field wiring rules
Electrical connections for the SlimFit control. Work must meet the National Electrical Code and local rules. - General inspection: boiler area, jacket gaskets and interior
Start of each heating season, by a qualified service technician. Correct any owner-reported issues before proceeding. - General venting and combustion air rules
The SVF must be vented and given combustion and ventilation air only with the piping and methods in this manual. Category IV boilers must not be commo - Glue PVC or CPVC vent and air joints
Follow the pipe maker's instructions for prep and cement. The joint must be clean, primed and fully seated. - Handling ceramic fiber and fiberglass insulation
Combustion chamber lining, base panels and jacket insulation contain ceramic fiber or fiberglass that can be hazardous if dust is breathed in. Follow - Handling ceramic fiber sight glass gasket
The sight glass gasket contains ceramic fibre that can release respirable silica dust. Keep the gasket wet while removing it. - Hang the boiler on the wall bracket
Lift the boiler so its mounting bracket clears the wall bracket, then lower it until the brackets engage. - High altitude adjustment
Derate rules and CO2 adjustment at altitude. - High fire and low fire combustion check
Check the flame and combustion at both high fire and low fire. Load devices must be able to take the heat so the boiler does not cycle off during adju - High flow DHW circuit with secondary connection
Use this when DHW flow is higher than the boiler allows or the DHW coil has high pressure drop. DHW flows only through the secondary connection piping - How the 120 VAC relay outputs energize
Each output is paired with an input and a priority. Outputs run only when both conditions are true. - Hydrostatic pressure test before connecting gas or electric
Pressure test the boiler water side before the water piping, gas and electrical supply are permanently attached. Fill with water through a temporary s - Hydrostatic pressure test before connecting gas, water or power
Pressure test the boiler before permanent water or gas piping and electrical supply are connected. Do not exceed 120 psig. - Hydrostatic pressure test before connecting water, gas or power
Pressure test the boiler before permanent water or gas piping and electrical connections. Test pressure is 1½ times the relief valve setting. Examples - Hydrostatic pressure test before gas and electrical hookup
Test the boiler with water before connecting gas piping or power. Use a test gauge of the right range, not the gauge shipped with the boiler. Steam bo - Hydrostatic pressure test before piping
Test the boiler water side before water, gas or electrical hookup. Test pressure limits depend on the relief valve rating. - Hydrostatic pressure test before piping and wiring
Pressure test the boiler before connecting water, gas or electrical supply. The factory test is 1.5 times the maximum allowable working pressure. The - Hydrostatic pressure test of boiler water side
Pressure test the boiler before connecting water or gas piping and before the electrical supply is connected. Relief valve is installed only after the - Hydrostatic pressure test procedure
Pressure test the boiler before connecting permanent piping. Use Figure 2 for the connection layout. - Ignition electrode and ignition wiring check
Annual check of the ignitor, ignition cable and ground wiring. - Ignition safety shutoff device check
Confirm the ignition system safety device locks out when there is no gas. The control makes one retry before lockout, per ASME CSD-1. - Improper main burner flame
Main burner flames may show some yellow-orange streaks caused by dust. Other yellow or large or small flames are faults. - Improper pilot burner flame
A proper pilot is a blue flame, with the inner cone engulfing the pilot flame sensor and the sensor glowing cherry red. Compare the flame to these fau - Indirect DHW aquastat wiring
The DHW aquastat can go on any one input/output pair. That input must be assigned to Priority 1. - Indirect DHW aquastat wiring for priority
Heat only and combi models use different inputs for indirect DHW. - Initial checks before diagnosing a boiler problem
Check these items first when servicing the boiler. Always turn off power before servicing. The boiler ON/OFF switch does not remove all power from int - Initial start-up screen choice (Use or Skip Wizard)
The first screen offers USE WIZARD (recommended) or SKIP WIZARD. Which screen shows depends on the control state. - Inserting PVC or ABS vent or air pipe into boiler connector
Seal comes from the internal gasket, so the clamp only holds the pipe in place. - Inspect and clean burners and base
Check burners and base components. Clean burners if needed. - Inspect and clean the condensate trap
Clean the trap if debris has built up and confirm the drain flows freely. - Inspect and fill the condensate trap
The condensate trap must stay filled with water during operation. An empty trap lets flue gas out of the condensate drain. - Inspect and reinstall heat exchanger cover plate
Check the cover plate gasket and insulation, then tighten the cover plate in the correct pattern. - Inspect base insulation before operation
Base insulation must be secure against all four sides of the base. Ceramic fiber and fiberglass materials are present. - Inspect ignition electrode
Clean or replace the ignition electrode and check the gap. - Inspect ignition electrode and flame sense rod
Clean or replace the electrode and check the ignition wiring. - Inspect ignition electrode and ignition wiring
Clean or replace the electrode and check the ignition cable and ground wiring. - Inspect system piping and base insulation
Inspect all piping for leaks after filling and again after the system has heated up. The base insulation must be secure on all four sides. Ceramic fib - Inspect the combustion chamber
Check the inside of the heat exchanger through the burner opening. - Inspect the ignition electrode and wiring
Igniter and flame sense assembly inspection and cleaning. Boiler must be cold and the gas shut off first. - Inspect the pressure switch sense hose
Sense lines must be in good condition, firmly attached and in the correct locations. Wrong placement or loose lines can cause unreliable operation. - Install AL29-4C stainless vent adapter and joints
Stainless vent piping must use the boiler adapter. - Install and wire outdoor temperature sensor
Required unless exempted in the Energy Act statement on page 184. - Install and wire the outdoor temperature sensor
Optional sensor used for outdoor reset control. - Install boiler relief valve and discharge piping
The relief valve must be on the top boiler pipe only, not the boiler out, and must be above the heat exchanger. The discharge line has to be piped to - Install condensate drain tee assembly
Assemble the condensate drain tee at the jacket. Gasket must seal the jacket. - Install condensate trap and condensate line
The condensate trap bolts to the boiler condensate outlet at the lower front center and its support foot sets the trap level. Use 1 in PVC or CPVC dra - Install condensate trap and drain line
The condensate trap, hose clamp and drain line must be in place during all operation. Condensate is slightly acidic (pH about 3.2 to 4.5), so use a ne - Install direct vent sidewall air and vent terminations
Sidewall direct vent uses corrosion-resistant stop plates sized just over the pipe diameter, sourced only from the vent pipe manufacturer. Vent and ai - Install direct vent vertical terminations
Vertical vent and air terminations need flashing and sealing boots sized for the pipe. Terminations use a coupling or open-end pipe per vent maker gui - Install flow switch or combustion air damper proof of closure
Remove the J18 jumper and wire the device as shown in the wiring diagram. Devices must provide isolated contacts. - Install low water cut-off (LWCO)
LWCO is required and is installer supplied. Use the Weil-McLain LWCO kit where possible. - Install optional outdoor temperature sensor
Optional sensor enables outdoor reset options in the control. - Install pressure/temperature gauge and backflow check
The pressure/temperature gauge goes in a tee on the supply piping. A backflow check valve goes in the cold water supply where local code requires it. - Install propane blower plate on SF-750
The SF-750 natural gas unit has no blower plate. The propane version needs the plate and gaskets shipped with the boiler. - Install propane orifice (SF-550 or SF-750)
The propane orifice sits in the counterbore of the venturi gas flange. The gas train adapter flange is removed to reach it. - Install propane orifice (Ultra-80, -105, -155, -230, -299)
Swap the natural gas orifice for the propane orifice at the gas valve. Isolate the boiler first and cool it if it has been running. - Install propane orifice for conversion
Required for all Ultra models except the Ultra-399 (throttle adjustment instead) and the factory propane Ultra-80LP. Use only the orifice size marked - Install relief valve and discharge piping
The relief valve mounts on the 3/4 inch nipple in the supply tee. Discharge piping must be safe and clear. - Install sidewall concentric vent termination
The concentric kit is bought separately and must be assembled and mounted before the piping runs to the boiler. - Install sidewall direct vent with separate pipes
Vent and air pipes run through two separate sidewall openings. The layout must meet the termination clearances. - Install system supply and return temperature sensors
Recommended for primary/secondary piping. Required for proper control. - Install the condensate trap
Assemble the trap so the float is in place and the connections are sealed. - Install the draft hood on the flue collector hood
A gas-tight joint at the draft hood prevents flue gas spillage. - Install the EG burner drawer assembly
Drawer assembly holds the main burners, gas manifold and pilot burner. Burner seating and orifice sizing are critical. - Install the heating relief valve
Relief valve goes on the top boiler water pipe only, never on the boiler outlet. Discharge must be routed safely. - Install the relief valve and discharge line
The relief valve mounts in a 3/4 in. street elbow on the boiler supply tee. The discharge line must be installed to protect people and property from h - Install the spill switch
Spill switch is fitted on the draft hood on the listed models only. - Install the wall-mount bracket
Bracket must be fastened only to wall studs and must be level before the boiler is hung. - Install the Weil-McLain sidewall vent/air cap
Mark, cut and mount the outside and inside wall plates first, then fit the termination, then run piping to the boiler. - Install vent and air adapters, gaskets and clamps
Installer supplies the manufacturer's SlimFit Vent/Air Adapter for the vent and air connections. Reducers are added as needed for the pipe size used. - Install vent and air pipe from the boiler outward
Build the vent and air system working from the boiler toward the termination. Do not exceed the length limits for either the air or vent pipe. - Install vertical direct vent with separate pipes
Air and vent pipes run up through the roof with separate penetrations. The air inlet must sit well below the vent outlet and well above the roof or sn - Install wall-mount bracket to studs
The bracket must be fastened only into wall studs and must sit level with its slots centered on the studs. - Install Weil-McLain sidewall vent/air plate
Vent and air cap plates use a template and are fastened with screws and anchors. Plates are marked for the exhaust and intake openings. - Installing an optional indirect water heater
Boilers ordered with an internal indirect water heater have a cover plate that must be removed before the heater goes in. Water boilers use a round pl - Installing EG water boiler flue baffles
The installer must fit all flue baffles for correct boiler operation. Each baffle is slid between the sections. - Installing the boiler in a residential garage
Extra precautions when the boiler is in a residential garage. - Installing the boiler on a foundation
Foundation and flooring requirements for the boiler pad. - Installing the relief valve and discharge piping
The relief valve is shipped loose and goes in the 1-1/4 inch coupling (SVF 1500/2000) or 2 inch coupling (SVF 2500/3000) on top of the supply outlet p - Isolation heat exchanger piping for multiple boilers (Example C)
The boilers are piped primary/secondary, with each boiler in a secondary loop. The heat exchanger shell side and the heating system side each need the - Keep direct exhaust vent termination clear of building features
A gas vent through an exterior wall must not end next to the wall or under eaves, parapets, balconies or decks. Figure 11 gives the minimum terminatio - Key components and their functions (quick reference)
Blower pulls air and gas through the venturi and pushes the mix into the premix burner; the air inlet silencer keeps it quiet. The swirl plate/shroud - Ladder wiring notes for spark-ignited pilot boilers
Wiring requirements from the ladder diagrams for CGi-25 to CGi-8 spark-ignited pilot models. - Leveling and placing a floor-mounted boiler
Place the boiler and check it is level before piping. - Limit controls and low water cutoff
The control module has temperature-based high limit and operating limit control, certified to UL353 and ASME CSD-1 and Section IV. The operating limit - Locate the sidewall vent/air termination
Pick a location that keeps flue products, condensate and wind effects away from people, plants, windows and building surfaces. - Locating the direct vent air inlet termination
Pick the air inlet location so it is clear of debris, plants and wind eddies, and is far enough from other vents and openings. - Location checks before setting the boiler
Check the site and existing system before placing the boiler. - Lock-up gas pressure regulator when inlet can exceed 14 in W.C.
Protect the boiler gas valve and pressure switches from high supply pressure. - Lockout display behavior: flashing red and gray screen
Automatic and manual reset conditions show on the control display. A constant red screen means a separate condition that the control will clear on its - Lockout on the manual reset high temperature limit
If boiler outlet water goes over the Manual Reset High Temp Limit setting (200°F from the factory), the control shuts the boiler down and locks out. I - Loss of power
On a power failure the whole boiler de-energizes, and the signal relays that command auxiliary devices also lose power and turn off. - Low flame signal
Steps to take when the flame signal stays low. - Low flame signal troubleshooting
Use when the running flame signal stays low. - Low temperature systems: choose the piping method
For radiant or converted gravity systems, primary/secondary piping is preferred because it keeps the heating circuit flow independent of boiler bypass - Low water condition with a heat call
The water temperature/LWCO sensor detects low water by checking conductivity between its housing and the boiler casting. With an active heat call and - Low water cut-off (LWCO) test
The LWCO is built into the Boiler Out sensor at the highest point of the heat exchanger. Two test methods are given. - Low water cutoff lockout screen
The display shows LOW WATER CUTOFF with a RESET button. The lockout cause is not described on these pages. - Low water cutoff wiring
Supplied LWCO sensor is recommended. An alternate LWCO must use an isolated contact. - Low water protection and external low water cut-off
The U-Control uses a dual sensor in the heat exchanger for low water protection. Some jurisdictions require an external low water cut-off. - Low-temperature system: boiler-bypass piping valve setup
Used on converted gravity or radiant systems when primary/secondary piping cannot be applied. Part of the circulator flow is bypassed around the boile - Low-temperature system: primary/secondary bypass valve setup
Preferred piping for radiant or converted gravity systems. Bypass valves 7a and 7b mix hot boiler outlet water with system return water so the boiler - Low-temperature system: system-bypass piping valve setup
Keeps return water to the boiler at 130°F or higher on converted gravity or large-water-content systems. Not for radiant heating, because it gives no - Main burner flame check
Monthly look at the main burner flames. - Main flame lights but does not stay lit
Main burners ignite but go out after starting. - Maintenance schedule (daily, monthly, six-month, end of season)
Owner and service items from Figure 118. Owner items are covered in the Ultra User's Information Manual. - Masonry chimney used as a pipe chase
A masonry chimney may only be used as a chase for the SlimFit vent and air pipe. No other appliance or fireplace may connect to it. - Massachusetts installation requirements
Requirements that apply when the boiler is installed in the Commonwealth of Massachusetts. - Massachusetts side wall vent requirements
Applies to side wall horizontally vented gas equipment in residential buildings where the exhaust termination is under 7 ft above finished grade. - Massachusetts sidewall horizontal vent carbon monoxide and signage requirements
For sidewall horizontally vented gas equipment in residential buildings where the vent termination is less than 7 feet above finished grade, Massachus - Massachusetts sidewall horizontal vent: required safety items
Applies to sidewall horizontally vented gas equipment in residential buildings where the vent terminal is less than 7 feet above finished grade, inclu - Massachusetts sidewall horizontal venting requirements
Required when a sidewall horizontally vented gas boiler is installed in a residential building in Massachusetts, and the vent termination is less than - Massachusetts sidewall-vented installation requirements
Required when a sidewall horizontally vented gas boiler is installed in a dwelling used for residential purposes and the vent termination is less than - Massachusetts venting requirements for sidewall horizontal vent
Applies to sidewall horizontally vented gas equipment in dwellings or residential buildings where the vent termination is under 7 ft above grade. Carb - Massachusetts venting: CO detectors and vent warning sign
Applies to sidewall horizontally vented gas equipment where the vent termination is less than 7 feet above finished grade, in dwellings used for resid - Measure natural gas input
Confirm the calculated input is close to the rating label. - Metal flakes in the flue passages
Flakes of metal are found in the flueways. Either chemicals in the combustion air are attacking the boiler, or flue gas is condensing because the burn - Metal flakes in the flue ways (oil steam boiler)
Flaking or corrosion found in the flue passages or vent. - Metal flakes in the flue ways (oil water boiler)
Corrosion or flaking in the flue passages. - Metal flakes in vent outlet or vent (flueway corrosion)
Metal flakes indicate contaminated combustion air or condensation of flue gases inside the boiler sections. - Monthly air piping check
Confirm the air inlet is open and the full length of air piping is intact with sealed joints. - Monthly automatic air vent check
Confirm each automatic air vent in the system vents freely and does not leak. - Monthly condensate drain and trap check
With the boiler running, flue gas must not come from the condensate drain or tee. A dry trap lets flue products into the boiler room. - Monthly owner maintenance
Monthly checks of venting, air piping, relief valve, condensate drain, air vents and the clock. - Monthly piping, relief valve and air vent checks
Monthly inspection of piping, relief valve and automatic air vents. - Monthly relief valve check
Frequent weeping from the relief valve can mean the expansion tank is not working. - Monthly vent piping check
Look for blockage, leakage or deterioration in the flue gas vent. Problems must be reported to a qualified technician right away. - Monthly venting system inspection
Visual vent check plus draft test on draft hood models. - Motorized air damper interlock on combustion air openings
If combustion air openings have motorized dampers, the boiler must not fire unless the damper is fully open, and must shut down if the damper closes d - Mount and wire controls - EG and PEG steam boilers with float-type low water cut-off
Control box, transformer and relay mounting for EG and PEG steam boilers with float-type low water cut-off. Reference is Figure 43 and the wiring diag - Mount and wire controls - EG and PEG steam boilers with probe-type low water cut-off
Control box, transformer and relay mounting for EG and PEG steam boilers with probe-type low water cut-off. Reference is Figure 42 and the wiring diag - Mount and wire controls - EG-30 to EG-75 water boilers
Control box mounting and wiring for EG-30 through EG-75 water boilers, with or without tankless heater. Figure 40 (no tankless heater) and Figure 41 ( - Multi-boiler RS485 wiring
Boilers communicate over a shielded 3-wire RS485 bus. The Unity 2.0 boiler must be the Master. - Multiple boiler communication (Modbus, connector J12)
The control can communicate with up to eight ECO Tec or Unity boilers in one installation. Boiler-to-boiler wiring uses connector J12. The Modbus conn - Multiple boiler control settings (general)
Setup for multi-boiler systems is given in the control setting tables for each example. Required settings are listed there; other parameters can stay - Multiple boiler direct exhaust sidewall terminations
Terminate each boiler's vent on the wall with the same clearances as a single boiler, following the typical layout. - Multiple boiler gas header and manual shutoff
Gas header requirements when several boilers share a supply line. - Multiple boiler terminations and vent/air clearances
Spacing rules when more than one SlimFit boiler terminates on the same wall or roof. - Multiple boiler vent/air terminations
Several Ultra boilers on one roof or wall need matched terminations and minimum spacing. Wrong heights or spacing can cause severe injury, death or pr - Multiple boilers with an isolation heat exchanger: when to use it
Use an isolation heat exchanger for large systems with high mineral content in the water, systems fed with untreated makeup water, old systems heavily - Multiple zones with circulators
Size each circulator for its own circuit. Do not put a circulator on the boiler except in primary/secondary piping. Balance the zones with isolation v - Multiple zones with zone valves (24 V and isolation relay)
Zone valves need a separate 24 V transformer sized for the total load of all valves. Do not wire 3-wire zone valves directly to the boiler T-T termina - No display and blower running at full speed
Control is not getting 24 V power. - No display and boiler will not respond to call for heat (no 24 V)
Display is blank and the boiler does not respond to a call for heat. The control is not getting 24 V power. - No display and no boiler components operating
Control is not receiving 120 V power. - No display and no response to call for heat
Control is not receiving 24 V power. - No display and nothing operating
Control is not getting 120 V power. - No flame detected during ignition
If no flame is detected, the gas valve closes, the blower runs postpurge, and the control starts the cycle again. After 5 failed attempts the control - No heat: check demand, power and safeties
Work through these checks before replacing components when the boiler does not fire. - No outdoor sensor installed
The outdoor sensor ships with the boiler and is required unless the job meets one of the exemptions. Without it, two settings must be changed. - No space heating in mild weather, display shows WWSD
Warm weather shutdown blocks space heating when the outdoor temperature is above the WWSD setting. The boiler sits in standby and the display shows WW - No space heating in warm weather
Warm Weather Shut Down stops space heating when the outdoor temperature is above the WWSD setting. DHW is not affected. - No spark, system does not work (with vent damper, Chart 2)
Troubleshooting chart for a no-spark condition on steam boilers with a vent damper. Flowchart text is out of order in the extracted pages; the steps f - No spark, system does not work (without vent damper, Chart 1)
Troubleshooting chart for a no-spark condition on steam boilers without a vent damper. The flowchart text is out of order in the extracted pages, so t - Nothing on display and no other components running (no 120 V)
Control is not receiving 120 V power. - Nuisance shutdowns: check system grounding
Chart 4. The pilot assembly and ignition control must share a common ground with the main burner. Poor or erratic ground commonly causes nuisance shut - Oil burner will not fire (steam boiler)
Basic checks before calling it a burner problem. Do not keep hitting the reset on the primary control. - Oil system circulators during maintenance
Oil circulators that need oil. Over-oiling will damage the circulator. - Oil the inducer motor (CGi)
Periodic lubrication of the CGi inducer motor. - Oil water boiler short cycling
Burner turns on and off too often. - Operate and test the boiler relief valve
Test the relief valve so it opens and reseats properly. A metal discharge line must already be piped to a safe drain location, installed by a qualifie - Operate the boiler relief valve (every 6 months)
Manually lift the relief valve lever to confirm it passes water and reseats. - Outdoor reset operation
Outdoor reset adjusts supply target temperature to outdoor temperature. Max target is for design maximum heat loss. Min target is the supply temperatu - Outdoor reset operation (supply temperature follows outdoor temperature)
Target supply temperature is set between Supply Min and Supply Max across an outdoor reset band. - Outdoor sensor installation
Outdoor sensor supplied with the boiler, connected to J19. - Output activation rule for zone and DHW circulators
Each 120VAC output only energizes when its input is calling and that input's priority is active. A zone can call without the pump running if the boile - Owner and service maintenance schedule
Owner checks daily, monthly and every 6 months; service technician annual start-up. - Owner maintenance schedule
Owner checks by interval. An annual startup by a qualified service technician is required before each heating season. - Owner review after annual startup
Points to cover with the owner once the startup is complete. - Perform startup and checks, pressure check
Confirms the water side pressures are correct after startup. - Pilot burner flame check
Monthly look at the pilot flame to confirm correct combustion. - Pilot flame signal lost during operation
During main burner operation the control monitors pilot flame current. If the signal is lost, the boiler re-ignites automatically. - Pilot lights but does not energize main gas valve
The pilot is lit but the main valve does not come on, usually because the flame signal does not register. - Pilot lights but does not energize main gas valve(s)
Pilot is burning but the control does not open the main gas valves. - Pilot lights but main flame does not light
Pilot is established but the main burners do not light. - Pilot lights but main valve will not come on (Chart 3)
Troubleshooting chart for steam boilers where the pilot lights but the main valve does not come on, with or without a vent damper. - Pilot lights, main valve will not come on (ignition control and gas path check)
Chart 3 for steam and water EG/PEG boilers. Work through the checks in order, starting with the control's 24VAC supply and gas pressure, then the spar - Pilot lights, main valve will not come on (pilot and gas valve check)
Chart 5 for steam and water EG/PEG boilers, with or without vent damper. Confirms pilot gas flow, spark gap and gas valve operation. - Pilot sparks but no pilot flame
Ignition attempt where the spark is present but the pilot does not light. - Pipe a closed-type expansion tank
Closed-type tanks rely on an air cushion that must stay in the system. Piping must allow that air to return to the tank. - Piping multiple boilers on Easy-Fit manifolds
Layout rules for header and manifold piping when several Ultra boilers share one system. - Piping multiple boilers to Easy-Fit manifolds
Connect the boilers to the main header through Easy-Fit manifolds, with manifold layout and flow direction set per the piping figures. - Piping with refrigeration (chilled water) systems
Chilled water must not enter the boiler. Cold water circulating through the boiler can damage the heat exchanger. - Place and level the boiler
Move the boiler off the pallet safely and set it level. Do not alter the leg height. - Place and level the boiler on its legs
Set the boiler in position using only the jacket corner posts. Casters are for moving only and must not carry the boiler weight. - Place boiler and set level
Cold storage below 0°F can make plastic parts brittle, so handle the boiler carefully until it reaches room temperature. - Placing and leveling the boiler
Leave the boiler in its carton and on the pallet until the site is ready. Move the carton and pallet next to the location, then remove the carton. Rem - Placing multiple boilers in the boiler room
Set boilers side by side with the spacings in the manual figures, and keep access clearances for venting, air piping, gas piping, expansion tank and p - Popping or percolating noise in boiler
Noise from mineral scale in sections, often from constant makeup water or wrong water pH. - Power polarity fault on control
The control is polarity-sensitive to incoming 120 VAC. With reversed polarity the control shows FAULT L1 POLARITY and will not cycle the boiler. - Pre-start checklist before powering the boiler
Final checks to complete before applying power. - Pre-troubleshooting checks
Check these before diagnosing any fault. - Pre-troubleshooting checks and tools
Basic checks before chasing any fault code on the boiler. - Pre-troubleshooting checks before diagnosing a fault
Basic checks before working on the control or components. Turn off power before servicing and never jumper a device except for momentary testing. - Prepare and open the boiler to access the flue side
Shut the boiler down and let it cool before opening it. Removing the gas valve is optional and only needed for extra clearance. The boiler contains ce - Prepare roof penetrations for vertical vent and air pipes
Size and space the roof holes before setting the terminations. Vent holes need extra clearance around the pipe. - Pressure gauge reads above 24 psig
Gauge reading above 24 psig on a typical 30 psig relief valve installation usually points to a problem with the expansion tank. - Pressure switch sense hose inspection
The pressure switch sense lines must be in good condition and firmly attached to the correct points. Wrong placement or a disconnected line can cause - Prevent combustion air contamination
Chlorine or fluorine products in the boiler air supply form acid in the boiler and can eat through the heat exchanger. Check the intake area before yo - Priority and input/output setup for multiple heat demands
Each input is assigned a priority. The priority sets which system runs first and how long each may run. - Priority operation for multiple systems
Priorities set the order in which systems are served. MAX ON TIME limits how long a priority runs before a lower priority is called. MIN ON TIME sets - Priority timing: MAX ON TIME and MIN ON TIME
Each priority has its own settings. MAX ON TIME limits how long a priority runs before a lower priority's call takes over. MIN ON TIME is the shortest - Probe type low water cutoff: clean and test
Periodic cleaning and function test of a probe type low water cutoff. - Products and areas that contaminate combustion air
Corrosive contaminants in combustion air can cause unsafe operation. Remove the source permanently, or isolate the boiler and supply outside combustio - Proof of closure interlock (flow switch or combustion air damper)
A flow switch or combustion air damper (CAD) end switch can be wired as a proof-of-closure interlock. Doing so requires removing the factory jumper on - Propane conversion procedure
Converts an SVF boiler from natural gas to propane. The boiler ships set for natural gas and needs a propane orifice and propane venturi, sold as a se - Propane gas odorant and leak checks
Propane boilers only. Odorant can fade, and propane settles at floor level. - Protect low-temperature circuits in multi-temperature systems
Circuits that need lower water temperature (radiant slab, for example) should be protected with limit controls wired to an external limit circuit when - Provide access to the boiler air inlet filter
The boiler air inlet filter must stay reachable for periodic inspection and cleaning. Use an 8 in capped tee or route the air piping so it can be disc - Provide room air openings
Air opening rules depend on whether the Ultra is alone in the boiler room or shares the space with other gas or oil appliances. - Pump (circulator) zoning with primary/secondary piping
Each zone gets its own circulator. The boiler circulator cannot be used as a zone pump. - Purge air from the water system
Air is removed zone by zone through the purge valve, then the remaining air vents are opened. - PVC and CPVC exhaust piping rules
PVC may only be used on the exhaust after the first 10 linear feet of CPVC. All fittings in that first 10 feet must be CPVC. Figure 23 shows the layou - PVC and CPVC venting near the boiler
Use CPVC for the first 10 linear ft of exhaust piping. PVC may only be used after the first 10 linear ft of CPVC. All fittings within the first 10 ft - PVC exhaust transition rule
PVC cannot be used on the exhaust directly from the boiler. The first 10 linear feet must be CPVC, then the run can change to PVC. - Radiant heating piping with high limit
The Ultra condenses in radiant service without return water regulation. A high limit protects the radiant tubing from excess supply temperature. - Radiant heating piping with high-limit protection
The boiler works in radiant systems and does not need return water temperature regulation. Supply temperature into the radiant tubing still needs a li - Radiant heating with zone valves, primary/secondary piping
Typical radiant layout. The boiler works in condensing mode, so return water temperature does not need regulating. A high limit protects the radiant t - Radiant heating zoning, primary/secondary
The SVF is suited to radiant heating and can operate in condensing mode. Boiler return water temperature does not need regulating in radiant applicati - Radiators or baseboard cold or noisy (oil water boiler)
Some heat emitters do not heat, or they gurgle. - Radiators or baseboard units do not heat or are noisy
Heat distribution problem usually caused by air in the system or low system pressure. - Rapid cycling: boiler turns on and off frequently
Boiler short-cycles. Usually a thermostat placement, control setting or water flow problem. - Re-check maximum and minimum CO2 and CO
Confirm the combustion settings at both high and low fire after adjustment. - Read the lockout history
The control stores the last three lockouts with the fault name, type, time, date, and the boiler status, temperatures, inputs and outputs at that time - Recheck maximum and minimum CO2 and CO after adjustment
Confirm both firing rates after any gas valve change. - Reducing maximum pipe length for extra elbows
Each elbow beyond the allowed count reduces the maximum vent or air length. Use the pipe manufacturer's figure if it is longer. - Reducing vent and air length for elbows
Each elbow beyond the allowed count reduces the maximum length. The allowed count is more than two elbows in the vent and one elbow in the air piping. - Refrigeration systems: keep chilled water out of the boiler
Chilled medium must not enter the boiler. Pipe the cooling system in parallel with the boiler. - Reinstall burner, cover plate and igniter with torque limits
Use a torque wrench for every fastener. Burner screws must not exceed 20 inch-pounds, cover plate nuts must not exceed 45 inch-pounds, and ignition el - Reinstall cleanout plate and burner assembly
Reinstall the cleanout plate with a new silicone cord gasket and torque the nuts correctly. - Reinstall cover plate, blower, burner and igniter
Reassembly after cleaning. Use a torque wrench and follow the torque values in the torque setting. - Reinstall heat exchanger cover plate, blower, burner and igniter after annual service
Reassembly order for the burner and cover plate after cleaning or inspection. Gas-tight sealing is critical. - Reinstalling air silencer, gas valve and display after flue-side cleaning
Final reassembly steps after the burner and heat exchanger have been cleaned. Gas valve steps apply only if the valve was removed. - Reinstalling the brazed plate heat exchanger and inlet manifold gaskets
Four new gaskets must be used on the DHW inlet and return connections to seal the brazed plate exchanger. - Relief valve installation and discharge piping
Install the relief valve upright in the ¾-inch tapping on the side of the boiler. Discharge piping must be short, full size, pitched down, and end in - Relief valve keeps letting out water
The relief valve opens often. The relief valve is set at 30 psig. Usually the expansion tank is too small or has lost its air cushion. - Relief valve keeps opening (oil water boiler)
Water discharges from the relief valve often. - Remote modulation setup with 0-10VDC input
A 0-10VDC signal drives boiler modulation. Input 2 must be changed to a 0-10V source after the Wizard is done. - Remote modulation via 0-10 VDC on Input 2
Input 2 can be used for remote modulation on single boilers only. Networks cannot use 0-10 V remote modulation. The priority assigned to Input 2 canno - Remote modulation with a 0-10 VDC input (single boiler only)
Use an external 0-10 VDC signal to modulate a single boiler. Not supported for boilers in a network. Using this input replaces Input 1 as the heat dem - Remote target operation (0-10 VDC input)
A remote analog signal sets the supply temperature for a priority. - Remote target operation (0-10 VDC sets supply temperature)
A remote analog signal sets the supply temperature for any priority. - Remote target operation (0-10 VDC) priority settings
Remote target lets an analog input set the supply temperature for any priority, including network priorities. Target vs voltage is shown in Figure 56 - Remote target setup with 0-10VDC input
A 0-10VDC signal adjusts the supply target temperature. It replaces the outdoor sensor as the target modifier. The control does not control the target - Remove and inspect the burner
Burner access for cleaning or replacement. Ceramic fiber materials are present; follow the handling precautions in the manual. - Remove boiler from an existing common vent and test the remaining appliances
The Ultra boiler cannot be common vented with any other appliance. When an old boiler is replaced, the remaining appliances on the old common vent mus - Remove the cover plate and inspect the burner
The cover plate nut count depends on model: four nuts on the 110, five on the 150 and six on the 199. Handle the cover plate and burner assembly caref - Remove the heat exchanger cover plate and burner
Open the heat exchanger for access. Disconnect power and close the gas supply before you start. - Remove, clean and reinstall the burner
Annual service. The boiler contains ceramic fiber material, so handle it with care. - Remove, inspect and clean the burner
Burner is ceramic fiber and must be handled with care. Clean by vacuum or water flush only. - Removing a boiler from an existing common vent (vent system verification)
Once the SlimFit is removed from a shared vent, remaining appliances may not vent properly if the flue is oversized. Test each remaining appliance thi - Removing and cleaning the brazed plate heat exchanger
The gas valve does not need to come off to remove the brazed plate heat exchanger. - Removing boiler from an existing common vent
When an existing boiler is removed from a common vent, check that the remaining appliances still vent properly. Test with the other appliances running - Removing the boiler from a shared common vent
When this boiler leaves a common vent that other appliances still use, each remaining appliance must be checked by itself to confirm it still vents pr - Removing the boiler from the shipping crate
Handling steps for moving the boiler out of its carton without damaging internal plastic parts. - Removing the boiler from the shipping pallet
Handle the boiler carefully and remove it from the pallet in the proper order. - Replace burner orifices
Use this when the orifice size must be changed. Follow with the final check-out. - Replace the flue pressure switch
Replacement procedure for the flue pressure switch. - Replacing a boiler on an existing common vent
The Ultra cannot share a common vent with any other appliance. The old vent may be oversized for the appliances that remain on it, so test them before - Replacing manifold orifices
Replace the burner orifices only when required, with correctly sized orifices for the gas type. Use a 7/16 inch open-end wrench. Run the final check-o - Reset a lockout fault (for example Low Water Cutoff)
When a fault occurs the status changes to LOCKOUT and the screen turns red. The manual's example uses Low Water Cutoff. - Residential garage installation
If the boiler is in a residential garage, follow ANSI Z223.1 precautions: mount the boiler so the burner and ignition devices are at least 18 inches a - Residential garage installation precautions
Special requirements when the boiler is installed in a residential garage. - Restart and test after maintenance
Verify operation after any maintenance by running the full startup procedure. - Review past errors and lockout history
The PAST ERRORS screens show control fault counts and ignition retries. Lockout history records fault name, fault type, time, date and status for each - Review with owner
Final service step to make sure the owner understands the boiler and its maintenance needs. - Roof penetration and vent support for vertical direct exhaust
Size the roof hole at least 0.5 in larger than the vent pipe. For 6 in PVC or PP, use a 7 in hole. Insert a galvanized thimble and use flashing and bo - Route and seal wiring in the cabinet
Line voltage and low voltage use separate knockouts. All entrances must be sealed. - Route and terminate low voltage wiring
Low voltage wiring and cabinet routing steps. - Route condensate drain tubing
The drain line must stay open and unobstructed. A frozen or blocked line can spill condensate and cause water damage. - Route line voltage wiring
Line voltage routing into the control tray. - Route the relief valve discharge line
Discharge piping must be installed to protect people and property. The piping must follow local or state codes and the manufacturer guidelines. - Safe servicing and operation
Basic precautions before and during boiler service. - Schematic wiring diagram: connector and sensor reference
Reference for the factory and field connections on the schematic. Connections shown include the power inputs, circulators, gas valve, flame and spark, - Seal the flue collector hood and rear base panels
Gas-tight seal at the flue collector hood and rear base is required. A leak lets flue gas and carbon monoxide spill into the room. - Seat boiler on wall-mount bracket
Use a reference line to confirm the boiler is fully engaged with the bracket. - Select a circulator for a direct-connected DHW water heater
Size the DHW loop circulator for a water heater piped across the Ultra boiler, using the boiler head loss and piping head loss tables. - Select a DHW circulator for direct-connected piping
Add the boiler pressure drop, the piping pressure drop and the water heater pressure drop to get the total head. Then pick a circulator that delivers - Select and calculate antifreeze amount
Use only freeze-prevention fluids approved by WM Technologies for SVF boilers. Sentinel X500 is approved. Never use automotive or standard glycol. - Sensor missing at power-up
At power-up the screen lists detected sensors. A sensor that is not listed is not being seen by the control. - Sensor wiring and supply/return sensor failure
The control compares return temperature to supply temperature. If the return reads higher than the supply, it assumes a sensor problem and reports it - Sensors and heat demand inputs shipped with the boiler
The boiler ships with three sensors and the wiring plan depends on the sensors installed. - Separate low water cut-off installation
A separate low water cut-off is required and must be supplied by the installer, even though the control has inherent protection. The LWCO mounts on an - Service and maintenance schedule
Owner and service technician schedule for the boiler. Verify proper operation after servicing. - Servicing the domestic water inlet manifold (flow transducer and bypass filter)
Clean the inlet filter, check the O-ring and bypass filter, then reassemble. - Servicing the domestic water outlet manifold (heating cartridge and sanitary shutter)
Clean and inspect the cartridge and shutter, replace worn O-rings and reassemble with the torque values in the torque table. - Set bypass valves for primary/secondary low temperature piping
Valve 7a mixes hot boiler outlet water with cooler return water. Valve 7b controls flow through the boiler secondary loop. Set them so the boiler retu - Set up 0-10 Vdc remote modulation
Used when the boiler's firing rate is driven by an external 0-10 Vdc signal instead of a thermostat contact. Input 2 is replaced by the modulation inp - Set up 0-10 VDC remote modulation from an external controller
Uses an external controller's 0-10 VDC signal to set boiler modulation. Single boiler only. - Set up 0-10 VDC remote target temperature control
Uses a 0-10 VDC signal to set the supply target temperature instead of the outdoor sensor. - Set up a variable speed boiler pump (0-10 Vdc output)
Connect the control 0-10 Vdc output to the pump 0-10 Vdc input and set the pump voltages from the manual test screen. - Set up proof of closure for a flow switch or combustion air damper
Proof of closure must be wired with isolated contacts. The P7 circuit carries 5 VDC. The blower will not start until the switch is closed. - Set up the 0 to 10 VDC remote target input
A 0 to 10 VDC signal adjusts the supply target temperature through the TARGET ADJUST setting. Using it disables Input 1 for heat calls. - Set up the boiler priorities in the Express Setup wizard
Assign each input and output to the priority it serves, then choose the system type. Network priorities are set on the master boiler only. - Setting the boiler on its legs and leveling
Casters are only for moving the boiler into place. Front and piping-end casters swivel, middle casters are fixed. The boiler must be carried on the le - Setting the flue collector hood, rear base and drawer assembly
On PEG boilers the flue collector hood and rear base panels come factory installed. A gas-tight seal is required at the hood and base panels to preven - Setting up the boiler (commissioning order)
Four-step order for control setup from the manual. - Setting up the control: step-by-step
Plan the inputs and outputs first, then wire and start the boiler, then configure the control with the Wizard or manual menus. - Shadow boiler not showing on the multi-boiler network
One ECO Tec master can run up to 8 boilers over RS485. After power-up it can take 30 seconds to 1 minute before the master sees the shadows. - Shared vent removal test for old boiler
When a SlimFit replaces a boiler on a common vent, the remaining appliances on that vent must be tested to confirm they still vent safely. The SlimFit - Shut down boiler before cleaning the heat exchanger (pin side)
Prepare the boiler before opening the heat exchanger for cleaning. - Sidewall air inlet location (vertical vent / sidewall air)
The air inlet is part of a direct vent connection, not a forced air intake. It must be placed to avoid obstructions, wind eddies and recirculation fro - Sidewall concentric termination - support, bird screen and sealing
Finish the concentric termination: support, screen, rain cap and weatherproofing. - Sidewall concentric termination installation
Mounting the concentric kit through a wall with a rain cap that seats on the wall or thimble plate. - Sidewall concentric termination: location and clearances
Pick a termination spot that keeps flue plume away from windows, plants, AC units and people, and out of wind eddies, inside corners and recessed area - Sidewall concentric termination: wall penetration sizes
Size the wall opening so the rain cap ribs seat on a solid stop. A thimble is preferred. - Sidewall concentric vent termination - wall opening and assembly
Prepare the wall penetration and mount the concentric termination so it cannot shift and blocked air passages are avoided. - Sidewall direct vent with separate vent and air pipes: termination location
Choose a sidewall location that meets clearances and gives clean routing from the boiler vent connection. - Sidewall direct vent: build the termination assembly
Assemble the sidewall terminations so the vent and air pipes cannot be pushed inward. - Sidewall direct vent: locate termination and run vent piping
Plan the sidewall vent and air routing before cutting any holes. Use only the vent and air materials listed in the manual's vent kit figure. - Sidewall separate pipes: termination installation
Mounting the vent and air pipes through a sidewall with stop plates and termination elbows. - Sidewall termination clearances
A sidewall termination must stay clear of door and window openings, roof overhangs, forced air intakes and other vent exit points. Do not terminate ab - Sidewall termination with separate vent and air pipes - location and clearances
Clearances for the vent and air terminations on a sidewall. The air inlet must end in a down-turned elbow and the vent in an elbow pointed away from t - Sidewall vent termination location and clearances
Choose a termination spot that stays clear of debris, snow and other terminations. - Sidewall vent termination: approved fittings only
Sidewall vents may only end with the terminations shown in Figure 14. Other terminations can cause nuisance shutdowns and loss of heat. - Sidewall wall penetration and metal cover plates
The cover plates and thimble set the outer stop for the vent elbow. The plate hole sizes are not readable in the extracted text, so check them against - Site check before locating the boiler
Before choosing the boiler location, check the nearby connections and the area around the boiler. The boiler must be placed so its gas controls are pr - Site checks before locating the boiler
Check for nearby system water piping, venting connections, gas supply and electrical power. Keep the area free of combustibles, gasoline and flammable - Six-month boiler piping and leak check
Routine check of the boiler piping, performed every 6 months. Gas odor or leaks are a stop-work condition. - Six-month boiler piping check
Check for gas leaks and water leaks in the boiler and its piping every 6 months. - Six-month relief valve operation test
Lift the relief valve lever to check that it flows and reseats without weeping. Pipe the discharge to a safe place before testing. - Six-monthly owner checks
Checks made every six months on boiler piping and the relief valve. - Size and pipe a diaphragm or bladder expansion tank
A diaphragm or bladder tank must be sized for the total boiler and system water volume and temperature. An undersized tank lets system water blow off - Size gas supply for natural gas
Sizing approach for natural gas supply to the boiler. - Size gas supply for propane
Propane sizing is done with the gas supplier, not from the natural gas table. - Size natural gas supply piping
Sizing method for natural gas piping from the meter to the boiler entrance. - Size propane gas supply piping
Propane sizing is done by the gas supplier, not from the natural gas table. - Size the gas supply piping to the boiler
Boiler gas connection is 1/2 in. NPT. Size the line from the meter to the boiler so it feeds every connected appliance, not just the boiler. Propane s - Sizing a shared combustion air duct
Multiple boilers can share a combustion air manifold. Only air piping may be combined, never vent piping. - Sizing combustion and ventilation air openings
Openings are sized in free area after louver losses. A single opening may be used if it starts within 12 in of the ceiling and meets the clearance and - Skim a new steam boiler to remove oil and grease
Clean newly installed steam boilers to remove oil and grease. Failure to clean can cause violent water level changes, water entering steam mains and h - Smell of gas
Stop immediately if gas is smelled. Do not operate any appliance or electrical switch in the building. - Solvent cementing PVC or CPVC vent and air joints
Make each joint clean and fully cemented so there are no leaks at the vent or air connection. - Solvent-cement joint method for PVC/CPVC/ABS vent and air piping
Joint procedure from the vent and air piping section. Pipe must be clean, dry and dry-fit before any cement is used. - Solvent-weld PVC or CPVC vent and air joints
Follow the pipe manufacturer's instructions for preparation and assembly. - Some radiators do not heat (steam)
Part of the steam system stays cold while the boiler runs. - Some radiators or baseboards stay cold or are noisy
Part of the system does not heat or makes noise while the rest is fine. - Space multiple boiler terminations
When more than one boiler vents through the same wall or roof, terminations must line up and keep minimum spacing. - Startup check-out verification
Final checklist to complete before handing the boiler over after startup. - Startup screen shows OUTDOOR: NOT ATTACHED
The control reports that no outdoor temperature sensor is connected. An outdoor sensor is required by federal rules unless the system is exempt. - Startup verification checklist
Commissioning items to confirm before leaving the boiler. - Steam boiler checks before first firing
Check system piping, venting and gas leaks before the operation verification. Steam boiler checks match the water boiler procedure. - Steam boiler condensate return
A steam system needs adequate condensate return to keep a steady water level in the boiler. - Steam boiler low water cutoff installation
Water line dimensions are measured from the bottom of the boiler section leg where it rests on the floor or foundation. Probe-type and float-type low - Steam boiler operation verification
Verify pilot and main burner flames and the vent damper before releasing the boiler. - Steam boiler piping general rules
Piping must be done correctly or the boiler and building can be damaged. Steam supply goes on the same end as the controls; the return can connect at - Steam boiler short cycling
Burner keeps turning on and off in short bursts. - Steam boiler water level and start-up checks
Water level must be checked before start-up. Steam water level should be no more than half way up the gauge glass and not less than 1/4 in. above the - Steam boiler water treatment considerations
Closed steam systems should not need large amounts of makeup water. Makeup water shortens boiler life through corrosion. Troubleshoot leaks and feeder - Steam condensate return and feed system
Steam heating depends on enough condensate returning to keep a steady water level. Avoid adding raw makeup water. If the return is not adequate, use a - Steam gauge glass cleaning and replacement
Keep the gauge glass clean so the waterline can be read. Normal waterline is halfway up the gauge glass. - Steam relief valve popping
Water or steam keeps coming out of the relief valve. - Surging water line or water carried into the steam mains
Water level jumps around in the gauge glass, or water is pushed into the steam mains (priming). - SVF cascade: member boiler stops when it loses the master
In a cascade, a member boiler shuts down when it loses communication with the master unless it was set up to keep running. The wizard default is No. - SVF header (system) sensor failed
The outdoor sensor and header/system supply sensor connect to the master boiler. If the header sensor fails, the control falls back to the boiler's ow - SVF ignition sequence and manual reset limits
How the SVF lights, so you can see where it stops. Once ignition starts it runs through to main flame even if the heat call ends. - SVF will not start, locks out after 5 minutes waiting on interlock
Before firing, the SVF waits for its start interlocks (combustion air damper end switch, boiler valve end switch) to close. If an interlock does not p - Switching a Weil-McLain oil boiler to B100 biodiesel
Notes from the Weil-McLain B100 addendum for Ultra Oil, WGO, WTGO and SGO boilers. - System return temperature higher than system supply temperature
The U-Control compares return and supply temperatures. If return exceeds supply, the control reports a likely sensor failure on the display. - System supply and return sensor installation
Strap-on sensors on system supply and return piping. The control compares return temperature to supply temperature. - System Type A, Application A1: Unity 2.0 control wiring
Unity 2.0 accepts the heat pump calls on AHD1 (space heating) and AHD2 (DHW). Zone thermostats 2, 3 and 4 wire to the thermostat common and to their z - System Type B, Application B1: boiler direct piped – design requirements
Use primary/secondary piping for the ECO HP. If the boiler runs at the same time as the heat pump, the boiler must be downstream of the ECO HP to prev - Tankless coil hot water goes cold or is always lukewarm
Domestic hot water from the tankless coil runs hot then turns cold, or never gets hot. The coil rating assumes 200°F boiler water. - Tankless coil water goes cold or stays lukewarm (steam boiler)
Domestic hot water from the tankless coil is hot then turns cold, or never gets fully hot. - Tankless coil water goes cold or stays lukewarm (water boiler)
Domestic hot water from the coil is hot then cold, or never hot enough. - Tankless water heater only piping
Boiler can supply an on-demand tankless water heater only, piped as shown in Figure 61. - Termination exposure and condensate protection
Do not extend exposed vent pipe beyond the figure dimensions, since condensate can freeze and block the vent. For sidewall runs, exposed outside pipe - Test boiler limit control
Checks that the boiler limit control shuts the boiler off when pressure reaches its set point. - Test field-installed controls
Checks any additional low water cutoff, high limit or other control added to the boiler. - Test ignition system safety device (gas shutoff)
Confirms the boiler shuts off gas flow when the main gas supply is cut with the burners on and recovers properly. - Test probe-type low water cutoff
Checks that the probe-type low water cutoff stops firing at low water and allows firing once refilled. - Test temperature limit
Confirms the boiler shuts off burners when water reaches the limit setting and restarts when the setting is raised again. - Test the probe-type low water cutoff (steam)
Monthly check that the probe LWCO really stops the burner on low water. - Thermostat and circulator wiring limits (schematic)
Limits on thermostat and circulator wiring shown on the schematic. Exceeding them can damage the control or thermostats. - Thermostat and dry contact heat demand wiring
Inputs 1 to 3 take dry contact calls for heat. They do not supply 24 V. - Thermostat and zone valve wiring
Thermostat circuits are dry contacts. Never apply 24VAC to them. - Thermostat and zone valve wiring problems
Thermostat circuits are dry contact inputs. Power applied to them, or wiring that is not isolated, can damage the control or cause false calls for hea - Thermostat circuit voltage check
There must never be any voltage across the boiler thermostat terminals. Voltage here will damage the control. A common cause is 3-wire zone valves wir - Thermostat or zone input does not start the boiler
Inputs 1-4 are dry-contact inputs. They must never get 24 V from outside. - Thermostat, DHW sensor and anticipator wiring
Default input terminals and wiring precautions for thermostats and DHW tank control. - Tight construction and exhaust fan air rules
Tight buildings and mechanical exhaust can starve the boiler of air. The room must never run under negative pressure unless every appliance is direct - Troubleshooting pre-checks
Do these checks before any troubleshooting. - Two space heating zones plus DHW piped directly to boiler
Input 2 and 3 handle space heating thermostats. Input 1 handles the DHW aquastat and runs at Priority 1. - Two space heating zones using zone valves (no DHW)
Input 1 runs the system circulator. Zone valve systems need a bypass pressure regulating valve because flow can occur with the valves closed. - Ultra Series 3 short cycling or poor heat: check primary/secondary piping
The Ultra must sit on its own boiler loop, piped primary/secondary. Wrong tee connections or undersized loop pipe cause flow problems. - Ultra-399 propane conversion and start-up
The Ultra-399 is converted for propane by adjusting the gas valve throttle screw only; no orifice change. Requires a combustion analyzer. - Ultra-80 or Ultra-105 low output on 2-inch vent/air pipe
The Ultra-80 and 105 allow 2-inch PVC vent and air pipe, but the boiler derates itself because of the extra pressure drop. Lower output is expected, n - Uncrating and moving the boiler
The boiler is heavy and must not be dropped. Remove the shipping brackets from the pallet using the ramp, which needs room for the boiler length plus - Use boiler only in a closed-loop system
Fresh make-up water and leaks shorten boiler life through mineral buildup and internal corrosion. - Use the setup Wizard
The control setup Wizard is opened from the BOILER SETTINGS menu during first startup. It leads through setup for the chosen application. Context-sens - Variable speed boiler pump setup (0-10 VDC output)
The 0-10 VDC output drives a variable speed boiler pump. Voltages are set in Manual Test Mode for each firing rate. - Vent and air configuration check
SlimFit boilers are ANSI Z21.13 Category IV, meaning pressurized venting that is likely to condense in the vent. They must use a special pressurized v - Vent and air pipe assembly rules
Assemble vent and air piping so the joints stay sealed and the pipe runs cleanly. Follow the material and adapter rules in the manual. - Vent and air pipe support, slope and clearance
Support and slope requirements for vent and air piping runs. - Vent and air piping - joints, elbows, slope and supports
General rules for routing vent and air piping from the boiler to the termination. - Vent and air piping installation (general run rules)
General rules for running vent and air pipe from the boiler to the termination. - Vent and air piping requirements
The Ultra needs a special pressurized vent system and a separate air intake line from outside. It is rated Category IV and is direct vent (sealed comb - Vent and air plate - mounting and sealing
Fit, seal and fasten the vent and air termination plate. - Vent and air plate - wall hole layout and cutting
Lay out and cut the wall holes for the Weil-McLain vent and air plate. - Vent and air termination location clearances
Applies to direct vent and direct exhaust terminations. Vent and air terminations must sit at least 12 in above grade and above the snow line. Keep th - Vent damper installation requirements and steps
The boiler will not run without its damper on the models that require one. Only the listed dampers in Table 19 (page 85) are approved for these Univer - Vent pipe assembly and cementing for PVC/CPVC
Dry fit the entire run before cementing. Deburr and chamfer pipe ends, clean and dry the surfaces, then prime and cement each joint. Twist the pipe 1/ - Vent system requirements and category selection
The SVF requires a special vent system. Direct exhaust is ANSI Z21.13 Category II (negative pressure vent, condensate likely in vent), with venting de - Vent termination location clearances
Choose the vent termination location so the plume, condensate and intake are clear of people, openings and other equipment. These apply to vertical te - Venting and combustion air setup requirements
Each SlimFit needs its own vent. Vent and air piping must be airtight, follow the manual, and meet code. Use one of two methods: direct exhaust (room - Verify the remaining appliances on an old common vent
Check each appliance still on the old common vent by itself, with all others off, to confirm the vent can carry it safely. - Vertical concentric termination: roof clearances and multiple boilers
The vent outlet must sit at least 6 ft from adjacent walls and 5 ft below a roof overhang, and at least 7 ft above a public walkway. Keep it at least - Vertical concentric termination: roof penetration
Prepare the roof opening and thimble before running the termination through it. Follow local codes for isolating vent pipe through floors, ceilings an - Vertical concentric vent/air termination installation
Concentric roof termination with the air inlet around the vent pipe. - Vertical direct vent termination with sidewall air inlet (Category IV)
Vent exits through the roof while the combustion air inlet exits through a sidewall, using a down-turned air elbow and a stop-plate assembly. - Vertical direct vent: roof vent and air terminations
Terminate vent and air through the roof or with a sidewall air inlet. - Vertical termination with separate vent and air pipes - location and clearances
Vertical termination layout. The air inlet ends in a down-turned 180-degree return bend and the vent in an up-turned coupling. - Vertical vent with sidewall air termination
Use a sidewall air inlet with a vertical vent through the roof. - Wall and roof penetration preparation
How to cut and seal the openings for the vent and air pipes through the building envelope. - Wall-mounting requirements
The wall must be plumb and able to carry the boiler and piping. Do not use anchors or other fasteners that are not secured into the studs. - Warm weather shutdown (WWSD) behavior
WWSD stops space heating when outdoor temperature is above the WWSD setting. DHW is not affected. - Warm weather shutdown (WWSD) behaviour
Space heating is blocked when outdoor temperature is above the WWSD setting. DHW operation is not affected. WWSD must also be selected during system s - Water boiler (EG) control installation
Install the controls per the control tapping table and Figure 4. On EG water boilers the low water cutoff is built into the control when using the 381 - Water chemistry and inhibitor check
Weil-McLain recommends adding Sentinel X100 inhibitor to protect the heat exchanger. Check water chemistry after filling and leak testing, and again a - Water chiller piping (zone valves, primary/secondary)
The chiller is piped in parallel with the boiler and must be kept from the boiler loop. - Water chiller piping, primary/secondary
For systems using a chilled water loop. The chiller must be piped in parallel with the boiler, and valves must keep chilled medium out of the boiler. - Water level drops out of the gauge glass into the returns
Water leaves the boiler and backs into the return piping while firing. - Water piping and recommended pipe sizing
The boiler has 3 inch Class 150 flanged connections, so use reducers to adapt to the external piping. Use two wrenches when tightening water piping at - When the condensate drain fitting may be omitted
The condensate drain fitting can be left out only under specific conditions. Otherwise the drain fitting is required. - When to use an isolation heat exchanger
An isolation heat exchanger is used for the situations listed below. The manual gives the high-pressure threshold differently on two pages; see notes. - Wire 0-10VDC remote target input
The 0-10VDC signal adjusts the supply target temperature and replaces the outdoor sensor as the target modifier. - Wire 120VAC power supply and grounding
Line voltage power is required. The boiler must be grounded and bonded. - Wire entrances, routing and required connections
Knockout locations and the connections the boiler needs before the zone and system wiring can be made. - Wire external limit with automatic reset
Boiler shuts down when the limit opens and restarts automatically after the limit closes. - Wire external limit with manual reset
Control locks out when this limit opens. A technician or operator must reset the control. - Wire external limits for manual or automatic reset
Factory jumper must be removed before a external limit is wired. Manual reset lockout needs a person at the boiler to reset. Cycling power does not re - Wire remote alarm and additional heat demand contacts
Both are optional. Contact ratings are 24VAC or less and 0.5 A or less. - Wire room thermostats, aquastats and zone valves
Inputs are dry contacts only. Supplying 24 V to the thermostat circuits can damage the control. - Wire the system supply and return sensors
Two strap-on sensors are required for proper control. If the return reads hotter than the supply, the control reports a sensor fault. - Wire thermostats and dry contact inputs
Inputs are dry contacts only. The boiler does not supply 24V to thermostat circuits. - Wiring external limits
Two limit types can be wired to J20, depending on whether the boiler should lock out or restart on its own. - Wiring multiple zones (EG water boilers)
Zone valves or circulators can be used for multiple zones. Each zone needs its own power and control wiring as shown in the wiring diagram. Zoning wit - Wiring multiple zones with zone valves or circulators
Zone valves need their own separate transformer. Zoning with circulators needs one relay per circulator. Do not wire 3-wire zone valves directly to th - Wizard setup order
The Wizard leads through boiler settings, inputs and outputs, priorities, system settings and types, output activation, priority switching, date and t - WMCR circulator zone controller plus boiler-controlled DHW
DHW is piped directly to the boiler. The zone controller calls for space heating on INPUT 2. A relay with a normally closed contact interrupts the zon - WMCR circulator zone controller plus DHW (DHW piped to boiler)
The zone controller provides the space heating call on Input 2. DHW is on Input 1 at Priority 1. - WMZV zone valve controller plus boiler-controlled DHW
DHW is piped directly to the boiler. The zone controller calls for heat on INPUT 2, and the system circulator on OUTPUT 2 runs whenever the zone contr - WMZV zone valve zone controller plus DHW (DHW piped to boiler)
Input 2 takes the space heating call from the zone controller. The system circulator on Output 2 runs on any space heating call. DHW is on Input 1 at - Wrong boiler model shown at power-up
The power-up screen shows the boiler model set in the control. If it does not match the rating plate, the boiler can run unsafely. - WWSD (warm weather shutdown) display and standby
When outdoor temperature is above WWSD, the boiler will not fire. The display shows WWSD and the boiler stays in standby until outdoor temperature fal - Zone valve and multiple zone wiring
Zone valves need their own transformer. Zoning with circulators needs a relay for each circulator. Never connect 3-wire zone valves directly to the bo - Zone valve zoning for high-flow or high-head-loss DHW circuits
Use this layout when the DHW circuit needs more flow than the boiler allows, or when a coil-type DHW tank has high pressure drop. DHW flows only throu - Zone valve zoning with direct connection piping (80/110/150 single boiler)
Use this layout only for zone valve systems that meet the direct connection criteria on page 53. If the system does not qualify, pipe it primary/secon - Zone valve zoning with high-flow DHW circuit (primary/secondary)
Use when the DHW circuit needs more flow than the boiler allows, or with a high pressure-drop coil-type DHW tank. DHW flows only through the secondary - Zone valve zoning with optional DHW piping (primary/secondary)
A primary/secondary boiler loop keeps the boiler circulator head off the zone valves and gives the boiler enough flow. - Zone valve zoning with primary/secondary piping
Zone valves are used with primary/secondary piping so the boiler loop gets enough flow and the boiler circulator head does not reach the valves. - Zone valve zoning with variable primary flow
For systems that use a variable-flow system pump. Figure 15 shows DHW as a zone. Figure 16 shows optional DHW piping. Check the general zone valve zon - Zone valve zoning, general requirements
Applies to all zone valve zoning applications. Use at least the minimum pipe size in Table 6 on all boiler loop piping to and from the primary/seconda - Zone valve zoning, high flow or high head DHW circuits
Use when DHW circuit flow exceeds boiler limits or when a coil-type DHW tank has high pressure drop. DHW water flows only through the secondary connec - Zone valve zoning, high-flow or high-head DHW circuit (alternate)
Used when the DHW circuit flow rate is higher than the boiler allows, or when a coil-type DHW tank has high pressure drop. Only the DHW water flows th - Zone valve zoning, primary/secondary piping
Boiler loop is a secondary circuit off a primary system loop. This keeps sufficient flow in the boiler loop and keeps the boiler circulator head off t - Zone valve zoning, primary/secondary piping (with optional DHW)
Boiler loop is a secondary circuit off the primary system loop. This ensures flow in the boiler loop and keeps the boiler circulator head off the zone - Zone valve zoning, variable primary flow (no DHW piping shown)
Used where a variable flow system pump is installed. - Zone valve zoning, variable primary flow with DHW
Variable flow system with optional DHW piping shown in Figure 17. - Zoning four space heating zones with circulators
Layout for four space heating zones with no indirect DHW, using circulators or 120VAC zone valves. Shown for 110/155 models; 220-399 use the wiring di - Zoning three space heating zones plus indirect DHW piped to boiler
Layout for three space heating zones with an indirect DHW tank piped directly to the boiler. Shown for 110/155 models; 220-399 use the wiring diagram. - Zoning three space heating zones with circulators (no DHW)
Factory defaults assign all three inputs to Priority 2 and fit a three-zone circulator system. - Zoning two space heating zones with zone valves
Layout for two space heating zones using zone valves (120VAC or 24VAC) with a system circulator and no indirect DHW. - Zoning with circulators, three space heating zones
Three thermostat zones with circulators and no DHW. Thermostats are wired to P11-4/5, P15-1/2 and P15-3/4, with circulators on P2. All three inputs de - Zoning with circulators, two zones plus DHW piped to boiler
Two space heating zones on INPUT 2 and INPUT 3, with a DHW aquastat on INPUT 1. INPUT 1 is assigned to PRIORITY 1 (DHW) and INPUTs 2 and 3 stay on PRI - Zoning with circulators: four space heating zones
Four space heating zones with no Indirect DHW, using thermostat inputs and circulator outputs. Shown for Heating Only models. - Zoning with circulators: four space heating zones (no indirect DHW)
Four thermostat-driven heating zones, each run by its own circulator from one boiler control. No indirect DHW on this layout. - Zoning with circulators: three space heating zones plus indirect DHW piped to boiler
Three space heating zones and one indirect DHW aquastat on the boiler control. - Zoning with circulators: three zones plus Indirect DHW
Three space heating zones plus an Indirect DHW tank piped directly to the boiler. Shown for Heating Only models. - Zoning with WMZV zone valve controller plus DHW controlled by boiler
Zone controller call on Input 2, DHW aquastat on Input 1. The system circulator on Output 2 runs on any zone call. - Zoning with zone valves (three zones and system circulator)
Zone valves are controlled by relays from the boiler control outputs. Input 1 is used to run the system circulator, not a thermostat. - Zoning with zone valves, two zones (no DHW)
Two space heating zones with zone valves. INPUT 1 is reserved for the system circulator, so it cannot be used for a wired thermostat. The system must - Zoning with zone valves: two space heating zones
Two space heating zones with no Indirect DHW, using zone valves and a system circulator. Shown for Heating Only models. The system must have a by-pass - Zoning with zone valves: two space heating zones (no DHW)
Two thermostats on Inputs 2 and 3. Input 1 runs the system circulator through AUX PUMP/OUTPUT. - Zoning: four space heating zones, no indirect DHW
Each of the four input and output pairs runs one heating zone with its own thermostat and circulator or zone valve. - Zoning: three space heating zones plus indirect DHW piped to boiler
Input 1 is the DHW aquastat and Inputs 2 to 4 are space heating thermostats. - Zoning: three space heating zones with circulators (no DHW)
Three thermostat zones each with its own circulator, all on PRIORITY 2. - Zoning: two space heating zones plus DHW piped directly to boiler
Two heating thermostats on PRIORITY 2 and a DHW aquastat on PRIORITY 1. - Zoning: WMCR circulator zone controller plus DHW controlled by boiler
Zone controller handles space heating. The boiler controls DHW through a direct-piped aquastat.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.