Checking burner gasket and flame body assembly

Vitodens 100-W B1HE/B1KE

What is going on

Inspect the flame body, electrodes, insulation ring and gasket. Replace only parts that are damaged or worn. If the flame body is replaced, also replace its gasket and fixing screws.

Check in this order

  1. Disconnect the ignition electrode plug and remove the electrodes.
  2. Remove the flame body fixing screws, holding the flame body while doing so.
  3. Remove the flame body with gasket and thermal insulation ring and check for damage.
  4. Fit the new burner door gasket with the tab aligned per the diagram.
  5. Refit the insulation ring and flame body, aligning the door pin with the hole in the flame body.
  6. 85/120 tighten the Torx screw to 27 lb.in (3.0 Nm).
  7. 150/199 tighten the 4 Torx screws to 40 lb.in (4.5 Nm). Place the insulation mats, then secure the insulation ring with 3 hex screws to 35 lb.in (4 Nm).
  8. Check the insulation ring is firmly seated.
  9. Refit the electrodes, check gaps, and tighten to 40 lb.in (4.5 Nm).

Applies to: B1HE/KE 85/120 and 150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 51-52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.