Viessmann · Boiler troubleshooting
"External Hook-up" shown on Vitotronic 300-K
What is going on
The heating program was changed by an external switching device.
Likely causes
- Heating program changed by an external switch.
Check in this order
- No remedy required.
Applies to: Vitotronic 300-K
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Operating Instructions, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.