Viessmann · technician tips

Viessmann service menus, test modes and resets

2692 tips for air handler, boiler, general, heat pump, mini split: access codes, button combinations, test modes and the resets you need at the appliance.

Jump to: Access & passwords (93) · Button combinations (66) · Service & test modes (233) · Reset & cancel (200) · Settings shortcuts (279) · Commissioning (574) · Other (1247)

Access & passwords

Installer and service menu codes, and how to get into them.

Access coding level 1

Boiler · Vitotronic 300

Coding level 1 holds the basic system and boiler codings. Only addresses that fit the system type and equipment are shown.

  1. Press 9 and w together for about 2 seconds to enter coding level 1.
  2. Use the up or down button to select the coding address, then press OK to confirm.
  3. Use the up or down button to change the value, then press OK to confirm.
  4. Press 9 and w together for about 1 second to leave coding level 1.

Applies to: Vitotronic 300 GW2 coding level 1

Source: Vitotronic 300 GW2 installation and service instructions, p. 114. Written in our own words; check the manual for your exact model.

Access coding level 2

Boiler · Vitotronic 300

Coding level 2 holds all boiler, burner, DHW, circuit and general codings. Addresses run in order from system type, through boiler/burner, then the circuits and general codings.

  1. Press w and rw together for about 2 seconds, then press OK to enter coding level 2.
  2. Use the up or down button to select the coding address, then press OK to confirm.
  3. Use the up or down button to change the value, then press OK to confirm. 'Accepted' appears briefly.
  4. Press w and rw together for about 1 second to leave coding level 2.

Applies to: Vitotronic 300 GW2 coding level 2

Source: Vitotronic 300 GW2 installation and service instructions, p. 116. Written in our own words; check the manual for your exact model.

Access the operating and settings levels

Boiler · Versatronik COMO OT

Operating and mode changes are reached by opening the control panel cover. The display shows USER when the user level is active.

  1. Open the control panel cover.
  2. Read the USER level on the display.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 24. Written in our own words; check the manual for your exact model.

Call up Coding 1 addresses

Boiler · Vitotronic 200-H

Opens the Coding 1 level to view and change addresses.

  1. Press the 9 button and the second button simultaneously for about 2 seconds, until the first arrow appears.
  2. Select the coding address with the up or down button and confirm; the value flashes.
  3. Change the value with the up or down button and confirm.
  4. The display briefly shows Adopted and the address flashes again.
  5. Press the 9 button and the second button simultaneously for about 1 second to exit.

Applies to: Vitotronic 200-H programming unit

Source: Vitotronic 200-H HK1M installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

Call up Coding 2 addresses

Boiler · Vitotronic 200-H

Coding 2 is opened with a different button pair. Exit works the same way as Coding 1.

  1. Press the first and second buttons together for about 2 seconds until the first arrow appears, then confirm.
  2. Select the coding address with the up or down button; the address flashes. Confirm to show the value.
  3. Change the value with the up or down button and confirm.
  4. Wait for the Adopted message; the address flashes again.
  5. To pick another address, use the up or down button.
  6. Hold the first and second buttons together for about 1 second to exit.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 42. Written in our own words; check the manual for your exact model.

Call up coding level 2

Boiler · Vitodens 200-W

Coding level 2 gives access to all coding addresses, including those in coding level 1. Codes that are not assigned by the equipment level or by other codes are not shown.

  1. Press OK together with the second key (its symbol is not legible in this extract) for about 4 seconds.
  2. Repeat the same key press for about 4 seconds.
  3. Wait for the 'Coding level 2' display.
  4. Select the coding group: General, Boiler, DHW, Solar, Heating circuit 1/2/3, or All cod. or solar.
  5. Select the coding address, choose the value from the table and confirm with OK.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 52. Written in our own words; check the manual for your exact model.

Call up service parameters on the control unit

Boiler · Vitocrossal 200 CI2

Parameters are grouped as General, Boiler, DHW, Heating circuit and Heating zones. Parameters or values not listed have no function on this product. Some parameters depend on the boiler and connected accessories.

  1. Tap the Service button.
  2. Enter the service password viservice.
  3. Confirm the entry.
  4. Select System configuration.
  5. Select the parameter group.
  6. Select the parameter.
  7. Set the required value using the tables in this manual.
  8. Accept the set value.

Applies to: Vitocrossal 200 CI2 control unit

Source: Vitocrossal 200 CI2 Service Instructions, p. 37. Written in our own words; check the manual for your exact model.

Call up the extended menu

Boiler · Vitodens 200-W B2HB

The extended menu holds less-used settings such as time and holiday programs. Some key symbols did not extract cleanly from this page.

  1. If the screen saver is on, press any key except the help key, then press the key shown in the manual.
  2. If you are already in the menu, press the key shown in the manual.
  3. To return to the standard menu, keep pressing until it appears.

Applies to: Vitodens 200-W B2HB with Vitotronic control

Source: Vitodens 200-W B2HB service instructions, p. 32. Written in our own words; check the manual for your exact model.

Calling up coding level 1

Boiler · Vitotronic 200-H

Coding level 1 is opened from the control unit and holds the heating circuit, General, DHW and Solar code groups.

  1. Press OK together with the second control key shown in the manual for about 4 seconds (key symbol not legible in this text).
  2. Select the coding level 1 entry.
  3. Select the group needed: General, DHW, Solar, Heating circuit 1/2/3, or All codes standard unit.
  4. Select the coding address, choose the value from the tables and confirm with OK.
  5. To reset all codes to factory settings, choose Standard setting in coding level 1; this also resets coding level 2.

Applies to: Vitotronic 200-H HK1B

Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 47. Written in our own words; check the manual for your exact model.

Calling up coding levels

Boiler · Vitocrossal 300 CA3B Dual Fuel

Coding is grouped by General, Burner control unit, DHW, Solar, Heating circuit 1/2/3, Boiler, Cascade and All coding. Level 1 uses the viservice password; level 2 uses viexpert.

  1. From the home screen tap Menu.
  2. Tap Service.
  3. Enter the viservice password.
  4. Tap System configuration.
  5. Tap Coding level 1, or Coding level 2 and enter the viexpert password.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 79. Written in our own words; check the manual for your exact model.

Calling up the extended menu

Boiler · Vitodens 200-W

The extended menu holds less frequently used settings such as time programs and holiday programs. The screen saver turns on after a few minutes without input and dims the display.

  1. If the screen saver is active, press any key except the ? key, then press the key shown in the manual.
  2. If you are already somewhere in the menu, press the key shown in the manual to go to the extended menu.
  3. To return to the standard menu from a zone circuit display, keep pressing the key until the standard menu appears.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 33. Written in our own words; check the manual for your exact model.

Calling up the main menu

Boiler · Vitotronic 300-K

The main menu lets you change the boiler sequence and scan or change cascade settings. It can be reached from the screensaver or from any menu level.

  1. If the screensaver is on, tap the display, then tap the menu button.
  2. From any other menu level, tap the menu button.
  3. Use the footer buttons to go back a level or return to the home screen.

Applies to: Vitotronic 300-K, MW2C cascade control

Source: Vitotronic 300-K MW2C operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Calling up the service level

Boiler · Vitodens 200-W B2HA

Opens the service menu used for diagnosis, resets, brief scan and coding. The button symbol is missing in the manual text, so read the button from the controller.

  1. Press OK and the second button shown on the controller at the same time for about 4 seconds.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.

Change service or coding passwords

Boiler · Vitocrossal 300 CA3B

Service level and Coding level 2 passwords can be changed by the installer. A forgotten or lost password can only be reset with a master password, which must be requested from Viessmann Technical Service.

  1. From the home screen tap Service and enter the viservice password.
  2. Select Change passwords, then choose Service level or Coding level 2.
  3. Enter the current password and confirm.
  4. Enter the new password and confirm.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 117. Written in our own words; check the manual for your exact model.

Change the lock panel password

Boiler · Vitocrossal 200 CI2

New password is 1 to 20 characters. No confirmation of the new password is required.

  1. Open Settings.
  2. Select 'Change password'.
  3. Enter the current password and confirm.
  4. Enter the new password and confirm.
  5. Confirm the prompt.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Change the service menu password

Boiler · Vitocrossal 200 CI2

Factory service password is viservice. Change it after first access.

  1. Tap the first button shown in the manual (symbol not readable in extracted text).
  2. Tap Service.
  3. Enter password viservice and confirm.
  4. Tap Change passwords.
  5. Tap Service menu.
  6. Enter current password and confirm.
  7. Enter new password.
  8. Confirm the new password twice.

Applies to: Vitocrossal 200 CI2 service menu

Source: Vitocrossal 200 CI2 Service Instructions, p. 55. Written in our own words; check the manual for your exact model.

Change the service or coding level 2 password

Boiler · Vitotronic 300 GW6B

Factory passwords are viservice for the service main menu and viexpert for coding level 2. Enter the current password before setting a new one.

  1. From the home screen, tap Menu, then Service.
  2. Enter the viservice password.
  3. Tap Change passwords.
  4. Choose Service level or Coding level 2.
  5. Enter the current password and confirm with OK.
  6. Enter the new password.
  7. Tap OK twice.

Applies to: Vitotronic 300 GW6B boiler control unit

Source: Vitotronic 300 GW6B installation and service instructions, p. 58. Written in our own words; check the manual for your exact model.

Coding addresses

Boiler · Vitodens 200-W

Coding address changes are used to match parameters to the installed system. The coding addresses named in fault codes (e.g. A3, 30, 52:0) are set in the coding levels.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 77-80. Written in our own words; check the manual for your exact model.

Do not change Multi-boiler system

Boiler · Vitotronic 200 and 300-K

This item changes a weather-compensated control into a constant temperature control. Leave it unchanged unless the control type is meant to change.

  1. Do not adjust the "Multi-boiler system" item in the service menu.

Applies to: Vitotronic 200 and 300-K service level

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 28. Written in our own words; check the manual for your exact model.

Enter advanced (extended) parameter settings

Boiler · Vitotron 100 VLN2

Advanced parameters can only be opened when the control is in stand-by. The first parameter group then appears on the display.

  1. Put the control into stand-by by holding the power button for about 3 seconds until the display goes blank.
  2. Confirm the flashing red dot is showing in the bottom right of the blank display.
  3. Press and hold the right arrow button (4).
  4. While still holding the right arrow button, press and immediately release the power button (9).
  5. Release the right arrow button. The first parameter group is now displayed.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 17. Written in our own words; check the manual for your exact model.

Enter boiler service menu and cascade control service levels

Boiler · Vitocrossal 300 CU3A

Access to the boiler service menu and the cascade control's service and coding levels, as printed in the application guide.

  1. On the boiler, hold the OK and menu buttons for 5 seconds to enter the service menu. (The button symbol is not clear in the text.)
  2. On the cascade control, press the menu icon, select Service, and enter password viservice.
  3. For cascade control level 2 coding, select the system configuration icon, select coding 2, and enter password viexpert.

Applies to: Application 8 cascade setup

Source: Vitocrossal 300 CU3A application guide, p. 53. Written in our own words; check the manual for your exact model.

Enter cascade control service level

Boiler · Vitocrossal 300 CU3A

Service level of the cascade control is reached from the menu icon with a service password.

  1. Press the menu icon on the cascade control.
  2. Select Service.
  3. Enter the password viservice.

Applies to: Cascade control, Vitocrossal CU3A multi-boiler systems

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 57. Written in our own words; check the manual for your exact model.

Enter coding level 1

Boiler · Vitocrossal 300

Coding level 1 changes the system codes. Codes not relevant to the installed system are hidden.

  1. Press OK and the second key simultaneously for about 4 seconds (second key symbol not legible in this extract).
  2. Select Coding level 1.
  3. Select the group: General, Boiler, DHW, Heating circuit 1/2/3, or All codes or solar.
  4. Select the coding address.
  5. Select the value and confirm with OK.
  6. To reset all codes to factory settings, select Standard setting in Coding level 1 (this also resets coding level 2).

Applies to: Vitotronic 200-H control unit

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 55. Written in our own words; check the manual for your exact model.

Enter coding level 1 and change a code

Boiler · Vitodens 200-W B2HB

Opens the coding menu to change boiler, system and heating circuit codes.

  1. Press OK and the second menu button together for about 4 seconds (button symbol not legible in this copy).
  2. Select Coding level 1.
  3. Select the group needed: General, Boiler, DHW, Solar, Heating circuit 1/2/3, or All codes std device.
  4. Select the coding address.
  5. Select the value from the tables and confirm with OK.
  6. To reset all codes to factory settings, select Standard setting in Coding level 1. This also resets coding level 2 codes.

Applies to: Vitotronic 200-H, Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB service instructions, p. 42. Written in our own words; check the manual for your exact model.

Enter coding level 1 on Vitotronic 200 in cascade

Boiler · Vitotronic 200

The Vitotronic 200 must be put in cascade mode before coding. Use the boiler Service Instructions for the Vitotronic 200 itself. Parts of the key sequence are not legible in this copy.

  1. Put the boiler in cascade mode first (see the cascade preparation section).
  2. Press OK and the second menu key together for about 4 seconds.
  3. Select 'Coding level 1'.
  4. Select the group: General, Boiler, or All codes std device.
  5. Select the coding address, choose the value, and confirm with OK.
  6. Exit the service menu with the back key when finished.

Applies to: Vitotronic 200 (HO1B) in multi-boiler cascade

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

Enter coding level 1 on Vitotronic 300-K

Boiler · Vitotronic 300-K

Coding level 1 on the 300-K is reached from the service menu. Codes are shown as plain text. Codes that do not apply to the installed system are hidden.

  1. Press OK and the second menu key together for about 4 seconds (the second key is not legible in this copy; check the printed key symbol).
  2. Select 'Coding level 1'.
  3. Select the coding group: General, Cascade, DHW, Solar, Heating circuit 1/2/3, or All codes std device.
  4. Select the coding address, choose the value from the table, and confirm with OK.
  5. When finished, exit with the back key.

Applies to: Vitotronic 300-K, MW2B

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 36. Written in our own words; check the manual for your exact model.

Enter coding level 2

Boiler · Vitodens 200-W

Coding level 2 unlocks all codes, including those in coding level 1. Codes that do not apply to the installed equipment level or to other code settings are hidden.

  1. Press OK plus the second key (symbol not legible on page 51) together for about 4 seconds.
  2. Press OK plus the same key again for about 4 seconds.
  3. Wait for 'Coding level 2' to show on the display.
  4. Select the coding group: General, Boiler, DHW, Solar, Heating circuit 1/2/3, or All cod. or solar.
  5. Select the coding address.
  6. Select the value and confirm with OK.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA service instructions, p. 51. Written in our own words; check the manual for your exact model.

Enter coding level 2 (numerical codings)

Boiler · Vitotronic 200

Coding level 2 gives access to all codings, using numerical addresses.

  1. Press the two buttons together for about 2 seconds, then confirm to enter coding level 2.
  2. Select the coding address with the up/down button and confirm.
  3. Change the value with the up/down button and confirm.
  4. Wait for 'Accepted', then select further addresses as needed.
  5. Press the two buttons together for about 1 second to exit coding level 2.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 27. Written in our own words; check the manual for your exact model.

Enter coding level 2 and reset to factory codings

Boiler · Vitotronic 100, GC1

Coding level 2 holds the full list of boiler and burner codings. Only addresses that match the system and equipment are shown.

  1. Press the two buttons together for about two seconds, then confirm. Two arrows appear in the display.
  2. Select the coding address with the up or down button, then press confirm.
  3. Change the value with the up or down button, then press confirm.
  4. Press the two buttons together for about one second to exit.
  5. To reset all codings, press the two buttons together for about two seconds, then press confirm. The display then shows the boiler water temperature.

Applies to: Coding level 2

Source: Vitotronic 100 GC1 installation and service instructions, p. 117. Written in our own words; check the manual for your exact model.

Enter expert level on Lago FB

Boiler · Versatronik 200

Expert level gives access to codes 1 to 17.

  1. Rotate the mode dial to MODE.
  2. Use the value dial to select PL (expert level).
  3. Use the mode dial to select the parameter, then the value dial to set it.

Applies to: Lago FB remote control

Source: Versatronik 200 installation and operating manual, p. 59. Written in our own words; check the manual for your exact model.

Enter level 2 coding on cascade control

Boiler · Vitocrossal 300 CU3A

Level 2 coding is reached from the system configuration icon with a coding password.

  1. Select the system configuration icon.
  2. Select coding 2.
  3. Enter the password viexpert.

Applies to: Cascade control, Vitocrossal CU3A multi-boiler systems

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 57. Written in our own words; check the manual for your exact model.

Enter the coding level

Boiler · Versatronik 300

Coding level is used for configuration changes. It is entered by holding the ENTER button.

  1. Press and hold ENTER for 5 seconds to enter coding level.
  2. Press ESC to leave coding level.

Applies to: Versatronik 300 user interface

Source: Versatronik 300 Cascade Control manual, p. 27. Written in our own words; check the manual for your exact model.

Enter the service code to open the relay test

Boiler · Versatronik 200

Service tests need a code number. Enter the four digits one at a time, then confirm with OK to open the relay test.

  1. Open the General/Service level.
  2. Set digit 1, press the F button to move to the next digit.
  3. Repeat for digits 2, 3 and 4.
  4. Press the F button OK to activate the code; the relay test then opens.

Applies to: Versatronik 200 service level

Source: Versatronik 200 installation and operating manual, p. 161. Written in our own words; check the manual for your exact model.

Enter the service menu

Boiler · Vitocrossal 200 CI2

Service menu is protected by password. On lag boilers, go via fault display 1, then the service symbol on the next screen. The menu exits on its own after 30 minutes.

  1. Tap the first button shown in the manual (symbol not readable in extracted text).
  2. Tap Service.
  3. Enter password viservice.
  4. Confirm.
  5. Select the required menu section.

Applies to: Vitocrossal 200 CI2 service menu

Source: Vitocrossal 200 CI2 Service Instructions, p. 54. Written in our own words; check the manual for your exact model.

Entering and leaving coding levels

Boiler · Vitotronic 200

Coding level 1 uses plain text and coding level 2 uses numerical addresses. Button symbols for the combinations are not legible in this extract.

  1. To enter coding level 1 (plain text), press the two buttons together for about 2 seconds.
  2. To exit coding level 1, press the two buttons together for about 1 second.
  3. To enter coding level 2 (numerical), press the buttons shown for coding level 2 for about 2 seconds, then confirm.
  4. To exit coding level 2, press the buttons together for about 1 second.
  5. To reset codings to factory defaults, use the reset combination, then choose Yes or No for the factory default prompt and confirm.

Applies to: Vitotronic 200 KW2 control unit

Source: Vitotronic 200 Si service instructions, p. 23-24. Written in our own words; check the manual for your exact model.

Expert level code entry

Boiler · Versatronik 200

Fitter values in the expert level are locked by a code number. Enter the code at the Code-No input. Write down any new code, because it is needed for later changes.

  1. Go to the Expert level and open the Code-No input.
  2. Set each digit, moving to the next with the F button [==>].
  3. Confirm the code with the F button [OK].
  4. To change the code, use Change code (0000 - 9999) and record the new value.
  5. Leave the level with the F button [Cancel].

Applies to: Versatronik 200 controller, expert level

Source: Versatronik 200 installation and operating manual, p. 137. Written in our own words; check the manual for your exact model.

Extended menu may be blocked

Boiler · Vitotronic 300-K

The heating contractor can block the extended menu. In that case only fault messages can be scanned.

  1. Press the extended menu key to open the extended menu.
  2. If it does not open, the contractor has blocked it. Scan fault messages only.

Applies to: Vitotronic 300-K (type MW2B)

Source: Vitotronic 200 and 300-K operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Factory passwords and changing them

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Factory passwords are viservice for the service main menu and viexpert for Coding Level 2. A password can be changed by the technician. Resetting all passwords needs a master password from Viessmann Technical Service.

  1. From the home screen, tap Service and enter the viservice password.
  2. Tap Change passwords.
  3. Choose Service level or Coding level 2.
  4. Enter the current password and confirm.
  5. Enter the new password and confirm.
  6. To reset all passwords, request the master password from Viessmann Technical Service, then choose Reset all passwords and enter it.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Vitocrossal 300 Dual Fuel service instructions, p. 116. Written in our own words; check the manual for your exact model.

Factory passwords and Coding level 2 access

Boiler · Vitocrossal 300 CA3B

Factory passwords are viservice for the service main menu and viexpert for Coding level 2. Coding level 2 is only shown in the menu after the viexpert password has been entered.

  1. Enter viexpert in the service menu to enable Coding level 2.
  2. Tap the return button to go back to the Service main menu.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 116. Written in our own words; check the manual for your exact model.

Flip-down cover and adjustable values

Boiler · Vitotrol 300

Values are changed with the flip-down cover open. Flashing values in the display can be changed. If the heating contractor has locked a setting by coding, the display shows "without function".

  1. Open the flip-down cover of the remote control to make changes.
  2. Check for flashing values; only flashing values can be changed.
  3. If the display shows "without function", the setting is locked by coding and must be changed by the heating contractor.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Gateway web login default

Boiler · Versatronik 505 NR2/BACIP, Versatronik 505D NR2/BACIP

Default gateway configuration login is admin / admin. It can be renamed on the Change Password screen.

  1. Change the default password during commissioning and record the new one.

Applies to: Versatronik 505 BACnet IP gateway configuration pages

Source: Versatronik 505 and 505D BACnet IP manual, p. 18. Written in our own words; check the manual for your exact model.

Home screen and locked panel

Boiler · Vitocrossal 200 CI2

After the control unit starts, the home screen is shown. Factory setting is the heating circuit or continuous operation display. The home screen can be set to show DHW, dashboard or cascade status instead. If operation of the home screen has been blocked, the display shows Panel locked and no adjustments can be made on the home screen or in the main menu.

  1. If the standby display is active, tap anywhere on the screen to wake it.
  2. To reach the home screen from the main menu, tap the home button.
  3. If Panel locked appears, the operator lock is active. Unlock it via the settings described on p. 25.

Applies to: Vitocrossal 200 CI2 control unit

Source: Vitocrossal 200 CI2 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Lag boiler section service displays

Boiler · Vitocrossal 300 CA3B

Service display access depends on which section is in fault or service condition.

  1. For boiler sections B and C, open the lower front boiler panel and control cover.
  2. For boiler section A on a 2nd, 3rd or 4th boiler, open the top front panel and control cover if the fault requires it.
  3. In single boiler applications, no panels need to be opened to set up the controls.

Applies to: Vitocrossal 300 CA3B multi and single boiler applications

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 14. Written in our own words; check the manual for your exact model.

Leave the service menu

Boiler · Vitocrossal 300 CA3B Dual Fuel

The service menu exits automatically after 30 minutes without use.

  1. From the service main menu tap Exit service.
  2. Confirm Terminate service? with OK.

Applies to: Service menu

Source: Vitocrossal 300 CA3B Dual Fuel Service Instructions, p. 116. Written in our own words; check the manual for your exact model.

Lock the controls (Level 1 or Level 2)

Boiler · Vitocrossal 200 CI2

Level 1 keeps all functions on the default displays operable and disables the rest. Level 2 disables all functions. The default password is 'viessmann' and can be changed.

  1. Open Settings.
  2. Select 'Lock panel'.
  3. Select 'Lock everything' or 'Only home screen operable'.
  4. Enter the password 'viessmann'.
  5. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Log in to gateway configuration pages

Boiler · Versatronik 585

The gateway has a built-in web configuration page. Default login is admin / admin. You can rename the password on the Change Password screen.

  1. Connect your computer directly to the gateway BACnet port with no other devices attached.
  2. Set the computer to automatic IP (DHCP), or set its IP address to 192.168.88.90 with subnet mask 255.255.255.0.
  3. Power-cycle the gateway (power off, then on).
  4. Open a browser and go to http://192.168.88.89/admin.
  5. Log in with the default user name and password admin (no quotes), or with your changed password.

Applies to: Versatronik 585 VI/BACIP

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 13. Written in our own words; check the manual for your exact model.

Open access to combustion controller coding

Boiler · Vitodens 200-W B2HA

Coding address 11 must be set to 11:9 before combustion controller coding addresses and the LPG setting (82:1) can be changed. Otherwise those addresses stay locked.

  1. Go to General coding 2.
  2. Set address 11 to 9 to open access to combustion controller coding.
  3. Change the required combustion or LPG addresses.
  4. Set address 11 back to a value other than 9 when finished, if locking is wanted.

Applies to: Vitodens 200-W B2HA, coding access

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 48, 52. Written in our own words; check the manual for your exact model.

Open coding level 1

Boiler · Vitodens 200-W

Codes are displayed as plain text.

  1. Press OK and the service key together for about 4 seconds.
  2. Select 'Coding level 1'.
  3. Select the group: General, Boiler, DHW, Solar, Heating circuit 1/2/3, or All codes std device.
  4. Select the coding address.
  5. Select the value and confirm with OK.

Applies to: Vitodens 200-W B2HA 112–530

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 44. Written in our own words; check the manual for your exact model.

Open coding level 2

Boiler · Vitotronic 200-H

Coding level 2 gives access to every coding address, including the level 1 codes. Enter it from the normal display with the two-step button sequence below.

  1. Press OK together with the second button shown in the manual and hold for about 4 seconds.
  2. Press OK together with the same button again and hold for about 4 seconds.
  3. Confirm that the display shows 'Coding level 2'.
  4. Choose the group you need: General, DHW, Solar, Heating circuit 1/2/3, or All codes standard unit.
  5. Select the coding address, pick the value from the table and confirm with OK.

Applies to: Vitotronic 200-H HK1B

Source: Vitotronic 200-H, HK1B Installation and Service, p. 54. Written in our own words; check the manual for your exact model.

Open coding level 2 on the Vitotronic 300-K

Boiler · Vitotronic 300-K

Coding level 2 shows every coding address, including those from level 1. Addresses that do not apply to the installed equipment or to other settings are hidden.

  1. Press OK and the second button shown on the page together for about 4 seconds (button symbol is not legible in this extract).
  2. Repeat the same button press for about 4 seconds again.
  3. Confirm that the display shows 'Coding level 2'.
  4. Select the coding group needed: General, Cascade, DHW, Solar, Heating circuit 1/2/3, or All codes std device.
  5. Select the coding address, choose the value from the tables, and confirm with OK.

Applies to: Vitotronic 300-K coding

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 49. Written in our own words; check the manual for your exact model.

Open coding level 2 on Vitotronic 200

Boiler · Vitotronic 200, Vitotronic 300-K

Coding level 2 gives access to every coding address, including those in coding level 1. Codes that do not apply to the installed equipment or to other settings are hidden.

  1. Press OK and the second button together for about 4 seconds.
  2. Press OK and the second button together for about 4 seconds again.
  3. Wait for the display to show 'Coding level 2'.
  4. Select the coding group: 'General' or 'Boiler'.
  5. Select the coding address.
  6. Choose the value from the tables and confirm with OK.
  7. To return all codes to factory settings, select 'Standard setting' in coding level 2. This also resets the coding level 1 codes.

Applies to: Vitotronic 200 (Type HO1B) and Vitotronic 300-K (Type MW2B), coding level 2

Source: Vitotronic 200 and 300-K installation and service instructions, p. 44. Written in our own words; check the manual for your exact model.

Open coding levels 1 and 2

Boiler · Vitocrossal 300 CA3B

Coding is reached from the home screen through the Service menu. Coding level 1 uses the service password, coding level 2 uses the expert password. Coding is grouped into General, Burner control unit, DHW, Solar, Heating circuit 1/2/3, Boiler, Cascade and All coding. Indicators shown depend on how the system is configured. The Service and System coding buttons appear on the screen; some button icons are missing from the page text.

  1. From the home screen, open the Service menu.
  2. Enter the service password (viservice).
  3. Open System coding or System configuration.
  4. Choose Coding level 1, or Coding level 2 and enter the expert password (viexpert).
  5. Select the coding group.
  6. Set the value from the table for that address and confirm it.

Applies to: Vitocrossal 300 CA3B, all sizes 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 80. Written in our own words; check the manual for your exact model.

Open information and configuration menu

Boiler · Vitocrossal 300 CA3B Dual Fuel

The information and configuration menus open from the operating display. The menu times out after 20 seconds with no button press. Adjust configuration only when the burner control unit is on standby.

  1. Press and hold button S for more than 2 seconds.
  2. Scroll through menu items with the Y and B buttons.
  3. Press button S to select a menu item. It shows under Service.
  4. Press button S or hold it to exit to the operating display.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner control units

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 22. Written in our own words; check the manual for your exact model.

Open the control panel to reach the menus

Boiler · Versatronik COMO OT

Operating and changing modes are reached by opening the control panel cover. The display shows USER when the cover is open. Use the Plus and Minus keys to move between levels and values, and the Prog key to select or save.

  1. Open the control panel cover. The display shows USER.
  2. Use Plus/Minus to pick the level (User, Display, Time-Day, HTG Prog 1/2, Holiday, Expert).
  3. Press Prog to open the level.
  4. Use Plus/Minus to find the value, then press Prog to select it. A warning triangle appears when the value can be changed.
  5. Change the value with Plus/Minus.
  6. Press Prog to save, or close the cover without pressing Prog to discard the change.
  7. Close the cover once the value is saved; the warning triangle disappears.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT manual, p. 17. Written in our own words; check the manual for your exact model.

Open the expert level menu

Boiler · Versatronik 200

The expert level shows temperatures and status for the circuits and system.

  1. Press the Home button to show the Main Menu.
  2. Turn the rotary dial until Expert Level is shown on the screen.
  3. Press the key beside User to select the menu option.
  4. Select a circuit or menu item to view its temperature and status information.
  5. Press Cancel to leave the current screen.

Applies to: Versatronik 200 expert level

Source: Versatronik 200 installation and operating manual, p. 135. Written in our own words; check the manual for your exact model.

Open the extended menu

Boiler · Vitocrossal 300

The extended menu holds less frequently used functions such as time programs and holiday programs.

  1. If the screen saver is active, press any key except ?, then press the menu key (symbol not legible in this extract).
  2. If you are somewhere in the menu, press the same menu key.

Applies to: Vitotronic control unit, extended menu

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 48. Written in our own words; check the manual for your exact model.

Open the gateway configuration pages

Boiler · Versatronik 515

Default login for the gateway web configuration. Change the password on the Change Password screen.

  1. Connect your computer directly to the gateway BACnet interface with no other devices attached.
  2. Set the computer to automatic IP (DHCP), or set its IP address to 192.168.88.90 with subnet mask 255.255.255.0.
  3. Power the gateway off and on again.
  4. Open a browser and go to http://192.168.88.89/admin.
  5. Log in with user name admin and password admin, then change the password on the Change Password screen.

Applies to: Versatronik 515 NR2/BACIP and 515D NR2/BACIP gateways

Source: Versatronik 515 BACnet IP Type B manual, p. 14. Written in our own words; check the manual for your exact model.

Open the Service menu (password viservice)

Boiler · Vitodens 200-W B2HE

The touchscreen Service menu holds diagnosis, actuator test, parameters, message history and service functions. It closes on its own after 30 minutes.

  1. Menu > Service
  2. Enter the password viservice (factory default)
  3. If passwords were changed and lost, Viessmann Technical Service issues a master password

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Service menu. Written in our own words; check the manual for your exact model.

Open the service menu with password

Boiler · Vitocrossal 200 CI2

Service functions such as message history, test modes and reset are behind the service menu and need the service password.

  1. Open the main menu on the programming unit (button icon not legible in the text).
  2. Select "Service".
  3. Enter password "viservice".
  4. Confirm with the OK button.

Applies to: Vitocrossal 200 CI2 boilers with HMI programming unit

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 57. Written in our own words; check the manual for your exact model.

Open the standard menu

Boiler · Vitodens 222-F

The standard menu holds the most-used settings for the heating circuit shown in the header. If the screen saver is on, press any key except the one marked ?. If you are already inside a menu, keep pressing until the standard menu appears. If the system has 2 or 3 heating circuits, you can choose which circuit (HC1, HC2 or HC3) shows here.

  1. If the screen saver is on, press any key except ?.
  2. If you are inside another menu, keep pressing until the standard menu appears.
  3. To change which heating circuit is shown, use the operating instructions.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 32-33. Written in our own words; check the manual for your exact model.

Open the system coding levels

Boiler · Vitotronic 300 GW6B

Coding is split into groups and two levels. Level 1 uses the viexpert password after viservice.

  1. From the home screen tap Menu.
  2. Tap Service.
  3. Enter the viservice password.
  4. Tap System coding.
  5. Tap Coding level 1 or Coding level 2. For level 1 or 2 enter the viexpert password.
  6. Select the group (General, Combustion controller, DHW, Solar, Heating circuit 1/2/3, Boiler, Cascade or All coding).
  7. Select the coding, tap Edit, then set the value from the coding tables.

Applies to: Vitotronic 300 GW6B control unit

Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 85. Written in our own words; check the manual for your exact model.

Open the user interface programming unit

Boiler · Vitodens 200-W B2HB

The user interface programming unit has two covers, each with a lock. Unlock and slide them open to reach the controls.

  1. Turn both locks to unlock the user interface programming unit covers.
  2. Slide the covers open.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 11. Written in our own words; check the manual for your exact model.

Open the Vitotronic 100 programming unit

Boiler · Vitotronic 100 GC1B

The programming unit sits behind a flap on the control.

  1. Pull the flap from the top edge forward to open it.

Applies to: Vitotronic 100 GC1B

Source: Viessmann Vitotronic 100 GC1B / 300-K MW1B operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Open the Vitotronic 300-K programming unit

Boiler · Vitotronic 300-K (MW1B)

The programming unit sits behind a cover flap on the Vitotronic 300-K.

  1. Pull the flap from its top edge forward to open it.
  2. Use the cursor keys to scroll and set values, OK to confirm or save, the back key to step back or cancel, and the ? key for extra information on the selected option.
  3. Press the extended menu key to open the extended menu.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B Operating Instructions, p. 9. Written in our own words; check the manual for your exact model.

Opening the control unit cover

Boiler · Vitotronic 100 GC1

The control unit sits behind a hinged cover. Open it by pulling the top gently toward you. Close the cover again after use.

  1. Pull the top of the hinged cover gently downward toward you to open it.
  2. Close the cover after use.

Applies to: Vitotronic 100, GC1

Source: Viessmann Vitotronic 100 GC1 operating instructions, p. 4. Written in our own words; check the manual for your exact model.

Opening the programming unit cover

Boiler · Vitocontrol-S

The control unit sits behind a hinged cover. Open it by pulling the top gently toward you, and close it again after use.

  1. Pull the top of the hinged cover gently downward toward you to open it.
  2. Close the cover again after you finish.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 2. Written in our own words; check the manual for your exact model.

Operating levels and the expert level code

Boiler · Versatronik 200

Settings are sorted into levels: Display (read-only sensor and set point values), User, Time program, Time-Date, Service, Expert level (installer), and Expert level IM (BUS heat source values). Installation, DHW, Heating circuit 1/2 and Solar/MF pages sit under these levels. Expert level values are protected by a code number, and changing them incorrectly can damage the system or cause a malfunction.

  1. Use Display level to read values without risk of changing them.
  2. Enter the expert level code before changing expert settings.
  3. Only change expert values if you know the installation requirements.

Applies to: Versatronik 200 System Control menu levels

Source: Versatronik 200 manual, p. 67. Written in our own words; check the manual for your exact model.

Panel removal for lag controls, service displays and emissions test switches

Boiler · Vitocrossal 300 CA3B Dual Fuel

Emissions test switches D, E and F are behind the front top and bottom panels and control covers. For the 2nd to 4th boiler, the lower front panel and control cover must be opened to set up lag control. Single-boiler setups need no panels opened.

  1. Open the front top and bottom boiler panels and control covers to reach the emissions test switches D, E and F.
  2. For lag control on the 2nd to 4th boiler, open the lower front panel and control cover.
  3. For a service condition on B or C, open the lower front panel and control cover.
  4. For a service condition on A, open the top front panel and control cover as needed for the fault.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Reaching coding levels and resetting coding

Boiler · Vitocrossal 300 CA3B Dual Fuel

Coding is reached through the Service menu with a password. Coding level 1 uses the viservice password; coding level 2 uses viexpert. Resetting coding restores factory values for the chosen group.

  1. From the home screen, open Service and enter the viservice password.
  2. Open System coding (or System configuration) and select Coding level 1.
  3. For Coding level 2, enter the viexpert password instead.
  4. To reset, select Reset coding address.
  5. To change a single value, select the group and coding, then choose the required value from the table and accept it.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 79. Written in our own words; check the manual for your exact model.

Read the fault history from the control unit

Boiler · Vitocrossal 300 CA3B Dual Fuel

The 10 most recent faults are stored, including faults already fixed. They are sorted by date.

  1. From the home screen, open the Service menu.
  2. Enter the password viservice.
  3. Open Fault history.
  4. Tap the entry to see more detail on that fault.
  5. Use the delete function to clear the list.

Applies to: Vitotronic control unit with graphical user interface

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 121. Written in our own words; check the manual for your exact model.

Removing and reinstalling the top panel

Boiler · Vitorond 100

The top panel screw can make the panel hard to remove. Moving the screw helps.

  1. Move the top panel screw about 3 in. to the left or right.
  2. Pre-drill the panel with a 1/8 in. bit to make the new mounting hole.
  3. When reinstalling, drill a new 1/8 in. pilot hole through the top back panel and into the back panel, then fit screw P in the new hole.

Applies to: Vitorond 100 boiler casing

Source: Vitorond 100 installation and service instructions, p. 35. Written in our own words; check the manual for your exact model.

Return to the standard menu

Boiler · Vitocrossal 300

Use this to get back to the standard menu from the screen saver or from any point inside the menu.

  1. If the screen saver is active, press any key except the one shown as ?.
  2. If you are somewhere in the menu, keep pressing until the standard menu appears.

Applies to: Vitotronic control unit, standard menu

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 48. Written in our own words; check the manual for your exact model.

Return to the standard menu or open the extended menu

Boiler · Vitocrossal 300 CU3A

Press any key except the info key to leave the screen saver, or keep pressing until the standard menu appears. The extended menu holds less-used settings such as time and holiday programs.

  1. If the screen saver is active, press any key except the info key, then press the menu key to open the extended menu.
  2. If already in a menu, keep pressing the back key until the standard menu appears.
  3. Use the extended menu for other connected heating circuits.

Applies to: Vitocrossal 300 CU3A with Vitotronic control

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 47-48. Written in our own words; check the manual for your exact model.

Scan system information

Boiler · Vitocrossal 300 CA3B

Opens the main information menu. Groups are General, Combustion controller, Heating circuit 1, 2 and 3, DHW, Solar energy, Reset data, Opening source licenses and Service address. Groups shown depend on connected components and settings. Named heating circuits show their assigned name.

  1. From the home screen, open Menu, then Information.
  2. Select the group you need.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Service and expert passwords for coding

Boiler · Vitocrossal 300 CA3B

Coding is reached from the Service menu. The service password is "viservice". Coding level 2 uses the "viexpert" password.

  1. From the home screen, open Service.
  2. Enter the viservice password.
  3. For coding level 1, open System coding or System configuration.
  4. For coding level 2, enter the viexpert password.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 80. Written in our own words; check the manual for your exact model.

Service password for commissioning and service menus

Boiler · Vitocrossal 200 CI2

The Service level password is viservice. It is used to open the Service menu and call up commissioning and test mode.

  1. Open the Service menu.
  2. Enter password viservice and confirm.

Applies to: Vitocrossal 200 CI2 programming unit

Source: Vitocrossal 200 CI2 Service Instructions, pp. 10, 16. Written in our own words; check the manual for your exact model.

Standard and extended menu access

Boiler · Vitocrossal 300

The standard menu covers the primary heating circuit. The extended menu covers all control functions. The heating contractor can block either menu, and if blocked, only service and fault messages can be viewed.

  1. From the screen saver, press OK to open the standard menu.
  2. To open the extended menu from the standard menu, press the menu key.
  3. From anywhere in the menu, hold the key until the standard menu appears to go back.
  4. Select the heating circuit before changing its settings, since settings apply per heating circuit.

Applies to: Vitotronic 200 KW6B

Source: Vitocrossal 300 CU3A operating instructions, pp. 14-15. Written in our own words; check the manual for your exact model.

Standard and extended menu on the Vitotronic 300-K

Boiler · Vitotronic 300-K (MW1B)

The control has two levels: the standard menu and the extended menu. Your heating contractor can block the extended menu, in which case you can only scan fault messages. In the standard menu the boilers are shown in boiler sequence. A solid white icon means the boiler is enabled by the cascade control and running. A solid grey icon means the boiler is available but not enabled. A solid black crossed-out icon means the boiler is not available for heat production. The display returns to the standard menu about 2 minutes after the last setting.

  1. From the screen saver, press OK to reach the standard menu.
  2. From any screen, hold the back key until the standard menu appears.
  3. To reach the extended menu from the standard menu, press the extended menu key.
  4. Expect the extended menu to be locked if the fault scan is the only option shown.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B Operating Instructions, p. 10. Written in our own words; check the manual for your exact model.

Unlock the controls

Boiler · Vitocrossal 200 CI2

When the panel is locked, 'Panel locked' appears after tapping any on-screen button.

  1. Tap any on-screen button. 'Panel locked' is displayed.
  2. Confirm that you want to unlock the operation.
  3. Enter the password 'viessmann' or your own password.
  4. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Unlock user interface and select language

Boiler · Vitodens 200-W B2HA

The control display is in German at commissioning. Unlock the programming unit covers before changing the language.

  1. Turn both locks up to unlock the user interface programming unit covers.
  2. Slide the covers open.
  3. Turn the boiler on with the ON/OFF switch.
  4. On the Sprache (Language) screen, select the language and press OK to accept.
  5. To change later: extended menu, Settings, Language, select, then OK.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 11. Written in our own words; check the manual for your exact model.

Wake the screen and open the home screen

Boiler · Vitocrossal 300 CA3B Dual Fuel

The touchscreen sleeps after a period of no use. Tap the display to wake it. From any menu level, use the home button to return to the home screen.

  1. If the screensaver is on, tap anywhere on the display.
  2. From any menu, tap the home button in the footer.

Applies to: Vitotronic 300 GW6C service display

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Waking the touchscreen and opening the menu

Boiler · Vitocrossal 300 CA3B

The service display has a touchscreen and goes into a screensaver after a period of no use. Wake it by tapping the display, then tap Menu to open the main menu. The main menu is used for settings and scans.

  1. If the screensaver is active, tap the display anywhere, then tap Menu.
  2. From any other screen, tap the home button in the footer, then tap Menu when needed.

Applies to: Vitocrossal 300 CA3B service display

Source: Vitocrossal 300 CA3B operating instructions, p. 16. Written in our own words; check the manual for your exact model.

WiFi access code labels

Boiler · Vitodens 100-W B1HE/B1KE

WiFi access code labels are on the back of the programming unit.

  1. Before installing the programming unit, remove the access code labels from its rear. Three copies are there.
  2. For commissioning, put one label on the front of the boiler.
  3. Put one label where it can be found later, such as the operating instructions.
  4. Switch WiFi on and connect to the router to use the app.

Applies to: Vitodens 100-W with WiFi module

Source: Vitodens 100-W, B1HE/B1KE Combi Installation/Service instructions, p. 41. Written in our own words; check the manual for your exact model.

Default login for configuration pages

General · Versatronik 535 Solar

The default user name and password are both 'admin'. Change the password on the Change Password screen and keep a record of it, since changes made in the configuration pages must be remembered.

  1. Log in at http://192.168.88.89/admin with admin / admin.
  2. Change the password on the Change Password screen and record it.

Applies to: Versatronik 535 Solar gateway

Source: Versatronik 535 Solar BACnet IP manual, p. 12, 13. Written in our own words; check the manual for your exact model.

Default web login for the gateway

General · Versatronik 525

The gateway ships with a default user name and password for its configuration pages. Change the password on the Change Password screen. The Restore Defaults and Change Password screens are basic, so check your entries carefully.

  1. Log in at http://192.168.88.89/admin with the default credentials.
  2. Rename or change the password on the Change Password screen.
  3. Record any changes you make.

Applies to: Versatronik 525 OT/BACIP

Source: Versatronik 525 OT/BACIP manual, p. 9-10. Written in our own words; check the manual for your exact model.

Access the outdoor unit electrical connections

Heat pump · Vitocal 100-AW AM2V

The electrical connection board is behind the access panel. The low voltage grommet and the 3/4 inch power supply knockout are on the same side.

  1. Remove the two access panel retaining screws and set them aside.
  2. Slide the access panel down and pull it out.
  3. Use grommet B for low voltage wiring and knockout C for power supply.

Applies to: Vitocal 100-AW AM2V outdoor unit

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 43. Written in our own words; check the manual for your exact model.

Connect to the control board terminal and reach the installer screen

Heat pump · Vitocal 100-WA

The setup and monitoring screens are reached through a terminal session with the control board in the junction box. The installer screen is password protected.

  1. Connect a Mini-B USB cable from the control board to a computer or tablet.
  2. Open PuTTY and set the baud rate to 250000, 8N1.
  3. Press 1 for Screen 1 (live data) or 2 for Screen 2 (configuration).
  4. On Screen 2, use the cursor keys or w, a, s, d to move, and + and - to change values.
  5. Press $ to open the password prompt, then enter 1010 for the installer section.
  6. Press h on any screen for help, and Escape to return to Screen 1 or 2.

Applies to: Vitocal 100-WA control board

Source: Vitocal 100-WA installation, service and operating instructions, p. 46-47. Written in our own words; check the manual for your exact model.

Enter engineer mode with hand-held remote

Heat pump · Vitocal 100-S

Engineer mode gives access to the inquiry codes and advanced settings. The unit must be in power-on or standby, and the remote must not be locked.

  1. Press On/Off and Fan together for 7 seconds.
  2. The remote shows Auto, Cool, Dry, Heat and the battery icon, plus the current numeric code. Starting code is 0.
  3. Use Up/Down to step through codes 0 to 30.
  4. Press OK to send the code. Code 0 sends the engineer mode entry code.
  5. To step back one level, press On/Off.
  6. To exit, press On/Off and Air speed together for 2 seconds. The mode also ends after 60 seconds with no valid key press.

Applies to: DLCURA system with hand-held remote

Source: DLCURA Service Manual, p. 22. Written in our own words; check the manual for your exact model.

Never use the compressor as a vacuum pump

Heat pump · Vitocal 100-S, DLCURA

The manual warns that the system compressor must not be used to evacuate the system.

  1. Use an external vacuum pump for evacuation.
  2. Always break a vacuum with dry nitrogen.

Applies to: Outdoor unit sizes 18K to 60K

Source: DLCURA installation instructions, p. 15. Written in our own words; check the manual for your exact model.

Open the indoor unit door

Heat pump · Vitocal 100-AW AM2V

The front door gives access to the indoor unit for installation and service.

  1. Remove the two door retaining screws.
  2. Swing the door open to the left.
  3. If more room is needed for piping or wiring, remove the mid jacketing panel (see Preparing for Service, p. 85).

Applies to: Indoor unit

Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 21. Written in our own words; check the manual for your exact model.

Service menu access code

Heat pump · Vitocal 100-AW

The Service menu allows system configuration to suit site conditions and previewing of inputs, outputs and current parameters. It is intended for installers and service contractors and requires an access code.

  1. Obtain the access code from the installer or service contractor before opening the Service menu.

Applies to: Vitocal 100-AW AM2V indoor unit

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 49. Written in our own words; check the manual for your exact model.

Service/Configuration menu access code

Heat pump · Vitocal 100-AW

Changes in the configuration menu require an access code.

  1. Open the Service/Configuration menu.
  2. When prompted, turn the navigation dial to code 987 and press the dial to confirm.
  3. To leave the code screen, hold the navigation dial or wait for automatic return to the main screen.
  4. Choose End to return to the Service menu when finished.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 60. Written in our own words; check the manual for your exact model.

Enter the wired controller settings menu

Mini-split · DLFSDAH and DLFLDAH

Settings menu opens only with the system off. T1, T2, T26, T3 and T4 are thermistor sub-menus; do not select them when setting external static pressure.

  1. With the system OFF, press and hold COPY for about 4 seconds.
  2. Scroll with + or - and select SP or AF with CONFIRM.

Applies to: Wired remote KSACN0501AAA

Source: Vitocal IND-D technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Button combinations

Key presses that open menus, show readouts or switch modes.

Adjust display window contrast

Boiler · Vitotronic 200-H

Adjust the display contrast by holding the setting button while turning the contrast control.

  1. Open the hinged cover on the programming unit.
  2. Press and hold the button shown on the page.
  3. While holding it, press the up or down setting button to adjust contrast.

Applies to: Vitotronic 200-H HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Adjust the display window contrast

Boiler · Vitocontrol-S

Open the programming unit cover, hold the contrast button, and at the same time adjust the contrast with the value selector.

  1. Open the hinged cover on the programming unit.
  2. Press and hold the display contrast button.
  3. While holding it, press the value selector up or down to adjust the contrast.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Basic key functions

Boiler · Vitotrol 300A

Back key cancels or steps back. Cursor keys scroll the menu and set values. OK confirms. ? gives help. Menu key opens the menu. Key symbols are not legible in the source, so use the labels above.

  1. Press any key to go from the display backlight to the standard menu.
  2. Press the menu key to open the extended menu.
  3. Use the cursor keys to set the value, then press OK to save.

Applies to: Vitotrol 300A

Source: Vitotrol 300A operating instructions, p. 5, 7. Written in our own words; check the manual for your exact model.

Call up an acknowledged fault message

Boiler · Vitotronic 100, GC1

Shows the fault code again after it has been acknowledged.

  1. Press the fault button and hold for approx. 2 seconds. The fault code is displayed.
  2. If several faults have occurred, press the up/down button to view each code.

Applies to: Single-boiler and multi-boiler systems

Source: Vitotronic 100, GC1 operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Call up burner status

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Shows the burner status screen. The second button symbol did not extract cleanly, so confirm it on the unit.

  1. Press and hold the two buttons shown together for about 4 seconds.

Applies to: Vitodens 100-W B1HE and B1KE control unit

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 11. Written in our own words; check the manual for your exact model.

ECO key: interrupt heating time

Boiler · Versatronik

The ECO key sets how long heating runs at economy temperature. Pressing it briefly shows the current setting for about 3 seconds. Each press changes the duration by one hour. Holding it for 3 seconds switches to economy for the rest of the day.

  1. Press the ECO key to show the set interruption for about 3 seconds.
  2. Press the key again to add or remove one hour per press.
  3. Hold the key for 3 seconds to switch the heating circuit to economy mode for the rest of the day. The display briefly shows ECO.
  4. To end the function, press the mode selector switch.

Applies to: Versatronik COMO OT ECO key

Source: Versatronik COMO OT manual, p. 16. Written in our own words; check the manual for your exact model.

ECO key: interrupt the heating time (economy mode)

Boiler · Versatronik COMO OT

Sets how long the heating circuit stays in economy temperature. Each press adds or removes one hour. A 3-second press puts the circuit in economy mode for the rest of the day. The display briefly shows ECO. The Mode selector switch ends the function.

  1. Press the ECO key to show the current interruption time for about 3 seconds.
  2. Press the ECO key again to start setting, then press + or - to change it by one hour per press.
  3. Hold the ECO key for 3 seconds to switch to economy mode for the rest of the day.
  4. To cancel, press the Mode selector switch.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT manual, p. 16. Written in our own words; check the manual for your exact model.

Enter coding level 1 (plain text codings)

Boiler · Vitotronic 200

Coding level 1 holds the main codings in plain text. The button icons are not legible in this copy, so use the two buttons shown in the manual's graphic.

  1. Press the two buttons together and hold for about 2 seconds to enter coding level 1.
  2. Select the coding address with the up/down button and confirm.
  3. Change the value with the up/down button and confirm.
  4. Wait for 'Accepted' to show briefly; the address then flashes again.
  5. Select further addresses with the up/down button as needed.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 26. Written in our own words; check the manual for your exact model.

Enter service functions menu

Boiler · Vitodens 200-W

Entry point to the service functions and coding menus on the Vitotronic programming unit.

  1. Press OK and the second key (symbol not legible in the text) together for about 4 seconds.
  2. Select 'Service functions' or 'Coding level 1' as needed.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 37 and p. 39. Written in our own words; check the manual for your exact model.

Enter service scan mode on Vitotronic 100 GC1

Boiler · Vitotronic 100 GC1

Service scans are entered with a button combination on the programming unit. Scan selection then uses the arrow buttons and confirmation uses OK.

  1. Press 9 and rw together for about two seconds.
  2. Select the required scan with the arrow buttons.
  3. Press OK.

Applies to: Vitotronic 100 GC1 boiler control

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 104. Written in our own words; check the manual for your exact model.

Enter temperature and coding card scan

Boiler · Vitotronic 300

Opens the diagnosis level that lists boiler temperatures, coding cards and scans 1 to 7. Exit the same way with OK.

  1. Press the 9 and rw buttons together for about 2 seconds.
  2. Use the arrow buttons to select the value to scan.
  3. Press OK to exit the diagnosis level.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 72-73. Written in our own words; check the manual for your exact model.

Enter the boiler service menu

Boiler · Vitocrossal 300 CU3A

Hold the OK button together with a second button for 5 seconds to enter the service menu on the boiler. The second button is not legible in the extracted text.

  1. Press and hold OK and the second button shown in the manual for 5 seconds.
  2. Confirm the service menu is open on the boiler display.

Applies to: Vitocrossal CU3A boiler control

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 57. Written in our own words; check the manual for your exact model.

Enter the service functions menu

Boiler · Vitodens 222-F

Press OK and menu together for about 4 seconds to open Service Functions. Filling, venting and the set-up wizard are listed there.

  1. Press OK and menu together for about 4 seconds.
  2. Select Service functions.
  3. Select the required program (Filling, Venting or Set-up Wizard).

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 14-16. Written in our own words; check the manual for your exact model.

Entering the information and configuration menu

Boiler · Vitocrossal 200 CM2

The information and configuration menus are reached from the operating display. The menu times out after 20 seconds without a key press.

  1. Press S for longer than 2 seconds. The menu item flashes.
  2. Scroll through menu items 1 to 6 with the Y and B keys.
  3. Press S to select the item, which then shows under Status.
  4. Menu 1 shows continuous start-up and run hour meters. Menu 2 shows resettable meters. Menu 3 shows the software version. Menu 4 shows the fault history of the last 10 fault codes.
  5. Menu 5 shows process information. Menu 6 changes configuration parameters. Only change them with the burner control on standby.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 44. Written in our own words; check the manual for your exact model.

Entering the service menu

Boiler · Vitodens 100-W, B1HE, B1KE

Opens the service menu used for actuator tests, maintenance display and parameters. The two button names are missing from the extracted text.

  1. Press the two buttons shown on the page at the same time for about 4 seconds, then release.
  2. Use the selector to choose the required menu item, then press OK.

Applies to: Vitodens 100-W

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words; check the manual for your exact model.

Establish internet connection

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Starts the internet connection from the home screen.

  1. On the home screen, press and hold OK for about 4 seconds.

Applies to: Vitodens 100-W B1HE and B1KE control unit

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Exit coding level 1

Boiler · Vitotronic 200

Leave coding level 1 with the button combination shown in the manual.

  1. Press the two buttons together for about 1 second to exit coding level 1.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 26. Written in our own words; check the manual for your exact model.

Fault history access

Boiler · Vitotronic 200-H

Opens the stored fault history. Details are on page 29.

  1. Press the rw and OK keys together for about 2 seconds to open.
  2. Press OK to exit.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Heat domestic hot water outside the programmed time

Boiler · Vitotronic 300

Starts a one-off DHW heating cycle without changing the time program.

  1. Press the heating circuit selector button until it lights up.
  2. Press the DHW button (marked g in the manual) twice, 2 to 3 seconds apart.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Jump to system overview from a menu

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Press and hold the Back button from inside any menu to jump straight to the system overview.

  1. From any menu, press and hold the Back button for about 4 seconds.

Applies to: Vitodens 100-W B1HE and B1KE control unit

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Load and end coding set 1

Boiler · Vitotronic 200-H

Loads coding set 1 (coding page 50).

  1. Press the 9 and w keys together for about 2 seconds to load.
  2. Press the 9 and w keys together for about 1 second to end.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Load and end coding set 2

Boiler · Vitotronic 200-H

Loads coding set 2 (coding page 53).

  1. Press the w and rw keys together for about 2 seconds to load, then confirm with OK.
  2. Press the 9 and rw keys together for about 1 second to end.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

OK + menu hold to open service functions

Boiler · Vitodens 200-W B2HA

Holding OK and menu together for about 4 seconds opens the service functions menu, which includes the set-up wizard.

  1. Press OK and menu together for about 4 seconds.
  2. Select Service Functions.

Applies to: Vitodens 200-W B2HA 112, 150, 399, 530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 14. Written in our own words; check the manual for your exact model.

One-off DHW heating outside the programmed times

Boiler · Vitotronic 200-H

Starts a single DHW heating cycle outside the set program.

  1. Press the DHW boost button (g) twice, 2 to 3 seconds apart.

Applies to: Vitotronic 200-H DHW heating

Source: Vitotronic 200-H operating instructions, p. 19. Written in our own words; check the manual for your exact model.

One-time DHW boost outside the cycles

Boiler · Vitotrol 300

Pressing the party key twice, about 2 to 3 seconds apart, gives one-time DHW production outside the programmed cycles.

  1. Press the party mode key once.
  2. Wait 2 to 3 seconds.
  3. Press the party mode key again to start one-time DHW production.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Open service functions or coding level 1

Boiler · Vitodens 200-W

Press OK and the second button shown in the manual at the same time for about 4 seconds to open the service menu. Coding level 1 is also opened this way.

  1. Press OK and the second button shown in the manual together for about 4 seconds.
  2. Select 'Service functions' or 'Coding level 1' from the menu.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 41. Written in our own words; check the manual for your exact model.

Open Service screen on Viessmann control

Boiler · Versatronik 501

Press OK and Menu together to bring up the Service screen. Hold for about 2 seconds, then use the arrow keys to reach Service Functions.

  1. Press OK and Menu together and hold for about 2 seconds.

Applies to: Vitotronic 300-K and related controls

Source: Versatronik 501 NR2/LON communication manual, p. 17. Written in our own words; check the manual for your exact model.

Open the Service menu

Boiler · Versatronik 505 NR2/BACIP, Versatronik 505D NR2/BACIP

Hold OK and Menu together to open the Service screen on the boiler control.

  1. Press OK and Menu together for about 2 seconds.

Applies to: Viessmann boiler controls behind the Versatronik gateway

Source: Versatronik 505 and 505D BACnet IP manual, p. 16-17. Written in our own words; check the manual for your exact model.

Open the short help guide

Boiler · Vitotronic 300-K

A short guide explains the controls and heating circuit selection.

  1. If the screen saver is active, press the help key.
  2. From anywhere in the menu, press the back key until the standard menu shows, then press the help key.

Applies to: Vitotronic 300-K (type MW2B)

Source: Vitotronic 200 and 300-K operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Panel buttons: power, scroll and adjust

Boiler · Vitotron 100 VLN2

The panel uses three buttons: power (9), scroll (4) and up/down (5/6).

  1. Press the power button 9 to turn the panel on or to return to the main view.
  2. Press the scroll button 4 to move through the working parameters.
  3. Press the up or down buttons 5/6 to change the highlighted value.

Applies to: Vitotron 100 VLN2 control panel

Source: Vitotron 100 VLN2 installation and service instructions, p. 12-13. Written in our own words; check the manual for your exact model.

Party key: extend heating time

Boiler · Versatronik

The Party key sets how long heating is extended at comfort temperature. Pressing it briefly shows the current extension for about 3 seconds. Each press changes it by one hour. Holding it for 3 seconds keeps heating on until the next day.

  1. Press the Party key to show the current extension for about 3 seconds.
  2. Press the key again to add or remove one hour per press.
  3. Hold the key for 3 seconds to keep heating at comfort until the next day. The display briefly shows PARTY.
  4. To end the function, press the mode selector switch.

Applies to: Versatronik COMO OT Party key

Source: Versatronik COMO OT manual, p. 16. Written in our own words; check the manual for your exact model.

Party key: extend the heating time (comfort mode)

Boiler · Versatronik COMO OT

Extends the comfort heating period by one hour per press. A 3-second press keeps the heating circuit at comfort until the next day. The display briefly shows PARTY. The Mode selector switch ends the function.

  1. Press the Party key to show the current extension for about 3 seconds.
  2. Press the Party key again to start setting, then press + or - to change it by one hour per press.
  3. Hold the Party key for 3 seconds to heat until the next day.
  4. To cancel, press the Mode selector switch.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT manual, p. 16. Written in our own words; check the manual for your exact model.

Put the boiler into summer (stand-by) mode

Boiler · Vitotron 100 VLN2

Keep the power on between heating seasons. Hold the power button for about 3 seconds to switch to stand-by. The panel goes off, only the stand-by dot blinks, and the heating elements stay off while the pump runs on a daily timer.

  1. Leave the 120 VAC and 240 VAC supply on.
  2. Press and hold the power button (9) for 3 seconds.
  3. Confirm the panel is off and only the stand-by dot is blinking.

Applies to: Vitotron 100 VLN2, all models 04 to 14.4

Source: Vitotron 100 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Remote reset of boiler error

Boiler · Versatronik COMO OT

Some boilers allow a remote reset of their errors from this controller.

  1. During a fault, press ECO and PARTY together for several seconds.
  2. Check that the error message disappears.
  3. If the fault repeats, call the installation technician.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 31. Written in our own words; check the manual for your exact model.

Return the boiler to winter (heating) mode

Boiler · Vitotron 100 VLN2

Bring the boiler back out of stand-by so the heating elements can run again.

  1. Press and hold the power button (9) for 3 seconds.
  2. Check that the panel lights up and the heating mode indicators show.

Applies to: Vitotron 100 VLN2, all models 04 to 14.4

Source: Vitotron 100 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Service level button combinations overview

Boiler · Vitotronic 100

Summary of how to open each service level and how to exit it.

  1. Temperatures, boiler coding cards and scans: press 9 and the rw buttons together for about 2 seconds; exit with OK (page 93).
  2. Relay test: press 9 and OK together for about 2 seconds; exit with OK (page 89).
  3. Participant check with LON: press w and OK together for about 2 seconds; press them together for about 1 second to start the check; exit by the same method (page 88).
  4. Operating status information: press the arrow button; exit with the arrow button (page 97).
  5. Service display: press OK to exit (page 98).

Applies to: Vitotronic 100 GC1 service levels

Source: Vitotronic 100 GC1 installation and service instructions, p. 92. Written in our own words; check the manual for your exact model.

Set maximum heating input (service functions)

Boiler · Vitodens 200-W B2HA

The heating input can be limited through the modulation range. The upper limit is set by the boiler coding card. DHW input is limited separately through coding 6F in coding level 2.

  1. Press OK and the second button named in the manual together for about 4 seconds.
  2. Select Service functions.
  3. Select Maximum output.
  4. Select Change? and choose Yes.
  5. A value flashes (for example 85, which is 100% of rated input in factory setting). Select the required value.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 19. Written in our own words; check the manual for your exact model.

Set the maximum heating output

Boiler · Vitodens 222-F

The heating output can be limited through the modulation range. The value shown is a percentage of rated output.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Service functions, then Maximum output.
  3. Select Change? and then Yes.
  4. A value flashes on the display (for example 85, which is 100% of rated output in the factory setting). Select the required value.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 21. Written in our own words; check the manual for your exact model.

Show acknowledged fault messages

Boiler · Vitotronic 200-H

Recalls faults that were already acknowledged. Details are on page 37.

  1. Press and hold OK for about 2 seconds.
  2. Press OK to exit.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Start and end participant check (LON)

Boiler · Vitotronic 200-H

Used with a LON system to check participants. Details are on page 15.

  1. Press the w and OK keys together for about 2 seconds to start.
  2. Press the w and OK keys together for about 1 second to end.

Applies to: Vitotronic 200-H with LON system

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Start and end relay test

Boiler · Vitotronic 200-H

Opens the relay test menu. Details are on page 16.

  1. Press the 9 and OK keys together for about 2 seconds to start.
  2. Press OK to end.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Start and end the participant check

Boiler · Vitocontrol-S VD2/CT3/CM2

Button sequence to start and end the LON participant check on the fault manager. The second button symbol is not legible in the extract.

  1. Press the w button and the second button (symbol not legible) at the same time for about 2 seconds to start the participant check.
  2. To end the participant check, press the w button and the second button together for about 1 second.

Applies to: Vitocontrol-S VD2/CT3/CM2 used as fault manager

Source: Viessmann Vitotronic 100 / Vitocontrol-S installation and service instructions, p. 92, p. 94. Written in our own words; check the manual for your exact model.

Start the filling program

Boiler · Vitodens 200-W B2HA

Runs the filling function from the service menu.

  1. Press OK and menu together for about 4 seconds.
  2. Select 'Service functions', then 'Filling'.
  3. Press OK or the back key to end the filling function.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 16. Written in our own words; check the manual for your exact model.

Start the venting function from the service menu

Boiler · Vitodens 222-F

Enter the service functions menu with a button combination, then select the venting function.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Service functions.
  3. Select Venting (bleeding). The venting function is enabled.
  4. To end venting, press OK or the back button.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 16. Written in our own words; check the manual for your exact model.

Switch between winter and summer mode

Boiler · Vitotron 100 VLN2

Holding the power button for 3 seconds changes the operating mode.

  1. Press and hold the power button 9 for 3 seconds to go into summer (stand-by) mode.
  2. Press and hold the power button 9 for 3 seconds to return to winter (heating) mode.

Applies to: Vitotron 100 VLN2 control panel

Source: Vitotron 100 VLN2 installation and service instructions, p. 13, 16. Written in our own words; check the manual for your exact model.

Switch off DHW heating

Boiler · Vitocrossal 300 CA3B

Turns off DHW heating by setting the DHW temperature to the lowest value.

  1. From the home screen, open Menu, then DHW.
  2. Open DHW temperature.
  3. Select 50°F (10°C).
  4. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Switch WiFi on or off

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

The WiFi module can be toggled with a two-button press. The first button symbol did not extract cleanly from the PDF, so confirm it on the unit.

  1. Press and hold the first button together with OK for about 4 seconds.
  2. Confirm the WiFi state on the display.

Applies to: Vitodens 100-W B1HE and B1KE control unit

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Use party mode

Boiler · Vitotrol 300

Party mode keeps space heating and DHW on outside the set cycles for a short time. The room is heated to the party temperature, which is set separately. Party mode ends at the next automatic switch to normal room temperature, or it can be cancelled early.

  1. Press the party mode key; the key lights and the party icon shows.
  2. To change the party temperature, open the cover and press the party key so the temperature flashes.
  3. Use the up/down keys to set it, then confirm.
  4. To end early, press the party key again; the light goes off.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Activate access point mode

General · Vitoconnect

Access point mode is used for Wi-Fi setup, licence access and router changes. It turns on automatically at first power-up and stays on until commissioning is complete.

  1. Press the operating button for longer than 5 seconds, but not longer than 30 seconds.
  2. Confirm the Wi-Fi LED is illuminated green.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Deactivate access point mode

General · Vitoconnect

Access point mode turns off by itself after 5 minutes. It can also be turned off manually.

  1. Wait 5 minutes for automatic deactivation, or
  2. Press the operating button for longer than 5 seconds, but not longer than 30 seconds.
  3. Confirm the LED is no longer illuminated.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Re-enter configuration

General · Vitotrol

To return to configuration, press the two buttons together for about 4 seconds. The button icons are not legible in the text extract, so confirm the buttons on the unit.

  1. Press the two buttons together and hold for about 4 seconds.

Applies to: Vitotrol 300A

Source: Vitotrol 300A installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Enter and exit Inquiry Mode

Heat pump · Vitocal 100-S

Opens the Inquiry Mode on the remote so you can read the unit values listed in the inquiry codes table.

  1. Press and hold the On/Off and Fan buttons together for 8 seconds to enter Inquiry Mode.
  2. Press UP or DOWN to step through codes 0 to 30.
  3. Press OK to send the value to the unit as well.
  4. Press and hold On/Off and Fan together for 2 seconds to exit.
  5. If no button is pressed, the remote leaves Inquiry Mode after 1 minute.

Applies to: DLCSRB with remote control

Source: DLCSRB Service Manual, p. 23. Written in our own words; check the manual for your exact model.

Forced operation (unit off)

Heat pump · Vitocal IND-O

Forced modes run without the remote. Protections and remote control still work in forced operation.

  1. With the unit off, press TOUCH to start FORCED AUTO at 75.2°F (24°C).
  2. Press TOUCH again within 5 seconds to start FORCED COOLING.
  3. Press TOUCH in any forced mode to turn the unit off.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH service manual, PDF p. 9. Written in our own words; check the manual for your exact model.

Enter AP mode to configure Wi-Fi

Mini-split · Vitocal Ind-O

Used to set up the wireless network on units with the Wi-Fi interface kit.

  1. Continuously press LED seven times within 10 seconds.

Applies to: Units with WiFi module (Wi-Fi interface kit KSAIF0301AAA sold separately)

Source: Viessmann DLFSOAH Owner's Manual, p. 10. Written in our own words; check the manual for your exact model.

Forced operation (no remote)

Mini-split · Vitocal IND-F

Used when the unit is off and no remote is available. Press TOUCH to start FORCED AUTO (75.2°F / 24°C setpoint). Press TOUCH again within five seconds for FORCED COOLING. Press TOUCH in any forced mode to turn the unit off. General protections and remote control remain active.

  1. With unit off, press TOUCH once for FORCED AUTO.
  2. Within 5 seconds, press TOUCH again for FORCED COOLING.
  3. Press TOUCH to turn the unit off.

Applies to: Indoor unit TOUCH button

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 10. Written in our own words; check the manual for your exact model.

Manual switch on the indoor unit

Mini-split · Vitocal IND-F

The manual switch on the indoor unit runs the unit without the remote. Pressing it once energises the unit; pressing it twice more switches it off.

  1. Open the indoor unit's front panel.
  2. Press the manual switch once to start manual operation.
  3. Press it twice more to return the switch to OFF after testing.

Applies to: All sizes

Source: DLFSFA and DLFLFA installation instructions, p. 13. Written in our own words; check the manual for your exact model.

SLEEP mode

Mini-split · Vitocal IND-F

SLEEP saves energy in COOL, HEAT or AUTO. It is not allowed in DRY or FAN.

  1. Press SLEEP to start it.
  2. In COOLING, the set point rises 1°C after one hour, then another 1°C after a second hour, and the fan runs on low.
  3. In HEATING, the set point is lowered 1°C from the normal setting.
  4. The unit shuts off 5 hours after SLEEP is set.
  5. Pressing MODE, TEMP, FAN, TIMER or ON/OFF cancels SLEEP.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 12. Written in our own words; check the manual for your exact model.

Start or stop FOLLOW ME memory

Mini-split · Vitocal Ind-O

The remote keeps measuring room temperature at its location. Memory mode stays on through ON/OFF, MODE and indoor unit power failure.

  1. Press and hold BOOST for 7 seconds to start or stop FOLLOW ME MEMORY.
  2. Check the display: 'ON' shows for 3 seconds when started, 'OFF' when stopped.

Applies to: Wireless remote with FOLLOW ME

Source: Viessmann DLFSOAH Owner's Manual, p. 10. Written in our own words; check the manual for your exact model.

Start vertical louver auto swing

Mini-split · DLFSDAH, DLFLDAH

Holding the SWING button for 2 seconds starts the vertical louver auto swing. A short press starts and stops horizontal louver movement.

  1. Press SWING briefly to start or stop horizontal louver movement.
  2. Hold SWING for 2 seconds to start vertical louver auto swing.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-D Owner's Manual, p. 4. Written in our own words; check the manual for your exact model.

Switch display between °F and °C

Mini-split · Vitocal Ind-O

Default unit is °F. Hold both temperature set point buttons together to change it.

  1. Point the remote at the unit.
  2. Press and hold the + and - temperature buttons together for about 3 seconds.

Applies to: Wireless remote, all modes

Source: Viessmann DLFSOAH Owner's Manual, p. 9. Written in our own words; check the manual for your exact model.

Switch remote between °F and °C

Mini-split · DLFSDAH, DLFLDAH

Press and hold both TEMP buttons together for about 3 seconds to change the remote display between °F (default) and °C.

  1. Press and hold TEMP up and TEMP down together for about 3 seconds.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-D Owner's Manual, p. 7. Written in our own words; check the manual for your exact model.

Switch temperature display between °F and °C

Mini-split · Vitocal IND-O

Hold the two temperature buttons together to toggle the display units.

  1. Press the two TEMP buttons together and hold for 3 seconds.
  2. Confirm the display shows the new unit (°F or °C).

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-O DLFSOAH owner's manual, p. 4. Written in our own words; check the manual for your exact model.

Switch the temperature display between °F and °C

Mini-split · Vitocal IND-F

Hold the two temperature buttons together to toggle the display units. The default is °F.

  1. Press and hold TEMP up and TEMP down together for about 3 seconds.
  2. Release when the display changes between °F and °C.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 5. Written in our own words; check the manual for your exact model.

TURBO mode

Mini-split · Vitocal IND-F

TURBO heats or cools the room quickly and cancels itself.

  1. Press TURBO. A beep confirms it if the indoor unit supports it. The fan runs on super high speed.
  2. Press TURBO again to cancel early. Otherwise it ends automatically after 20 minutes and the unit returns to its previous setting.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 12. Written in our own words; check the manual for your exact model.

Service & test modes

Forced fan, low and high fire, test and diagnostic modes, error history and live data.

Access to emissions test switches

Boiler · Vitocrossal 300 CA3B

Emissions test switches D, E and F are behind the boiler front panels on multi-section boilers.

  1. Open the front top and bottom boiler panels and the control covers.
  2. Use switches D, E and F for the emissions test.

Applies to: Vitocrossal 300 CA3B, all sizes 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 14. Written in our own words; check the manual for your exact model.

Activate the filling and venting program

Boiler · Vitodens 200-W B2HB

Starts the venting (bleeding) program in service functions. The burner stays off while the circulation pump cycles.

  1. Press OK and the menu button together for about 4 seconds.
  2. Select Service functions.
  3. Select Filling.
  4. Press OK or the back button to end the filling function when done.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 16. Written in our own words; check the manual for your exact model.

Actuator test access

Boiler · Vitotronic 300

Opens the actuator test to switch individual outputs on or off for testing.

  1. From the home screen tap Menu.
  2. Tap Service.
  3. Enter the viservice password.
  4. Tap Actuator test.

Applies to: Vitotronic 300 GW6B

Source: Vitotronic 300, GW6B installation and service instructions, p. 53. Written in our own words; check the manual for your exact model.

Actuator test for low and high fire

Boiler · Vitodens 200-W

Used during combustion checks to hold the burner at low or high fire.

  1. Open the service menu by pressing OK and the key shown in the manual at the same time for about 4 seconds, then select Actuator test.
  2. Select Base load OFF to run low fire.
  3. Select 'all actuators off' to end the test.
  4. Select Full load OFF to run high fire.
  5. Press the exit key to leave the actuator test.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB service instructions, p. 30-31. Written in our own words; check the manual for your exact model.

Actuator test for low fire and high fire combustion check

Boiler · Vitodens 200-W B2HA

Use the Service menu actuator test to hold the burner at low fire or high fire for combustion checks. The key combination symbols are missing in the source text.

  1. Connect a flue gas analyzer to the test port on the vent pipe adaptor.
  2. Open the gas shut-off valve, start the boiler and create a heat demand.
  3. Open the Service menu by pressing OK and the key shown (symbol not legible) together for about 4 seconds.
  4. Select Actuator test.
  5. For low fire, select Base load OFF so Base load ON appears, then measure CO2 and O2.
  6. For high fire, select Full load OFF so Full load ON appears, then measure CO2 and O2.
  7. Select all actuators off to end the test, and record values in the Maintenance Record.

Applies to: Vitodens 200-W B2HA

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 31. Written in our own words; check the manual for your exact model.

Actuator test of outputs

Boiler · Vitocrossal 300 CA3B

Each output can be switched on or off individually. All actuators are switched off before a new one is selected. Only outputs that match the installed equipment and control unit configuration (lead or service control) will respond.

  1. From the home screen tap Service and enter the viservice password.
  2. Select Actuator test.
  3. Select the output to test, for example DHW tank primary pump, Htg circ pump HC2, Mixing valve HC3 or Solar circuit pump.
  4. Check that the actuator responds as listed in the actuator table.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 119. Written in our own words; check the manual for your exact model.

Actuator test on the boiler group

Boiler · Vitodens 100-W, B1HE, B1KE

Runs the actuator test for the Boiler group from the service menu.

  1. Open the service menu (see the button combination tip).
  2. Select Actuator test and press OK.
  3. Select the Boiler group and press OK.

Applies to: Vitodens 100-W

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words; check the manual for your exact model.

Actuator test overview

Boiler · Vitocrossal 200 CI2

The actuator test lets you switch individual outputs on and off from the service menu. Which outputs are available depends on the system equipment level. Groups: gas condensing boiler (burner modulation, minimum and maximum output, burner 1 and 2 where fitted, ventilation air supply, hydraulic shut-off valve), heating group (primary circuit pump speeds and on/off, mixer open/stop/close for HC2 and HC3 and the second HC3 entry as printed, heating zone pumps 1 to 3, circulation pump speed in %, heating circuit pump speeds), and DHW group (circulation pump, DHW tank heating, DHW recirculation pump).

  1. Enter the service menu (see access tip) and open the actuator test.
  2. Select the output group and the function to test, such as "Minimum heating output" or a pump On/Off.
  3. For mixers, use Open, Stop or Close and check the valve moves as expected.

Applies to: Vitocrossal 200 CI2 with the relevant equipment level

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 56. Written in our own words; check the manual for your exact model.

Actuator test: drive fan, burner, pump and 3-way valve by hand

Boiler · Vitodens 200-W B2HE

Each actuator test function runs for 30 s: fan rpm, burner Off / Min / Max heating / Max DHW, 3-way valve Heating / Centre / DHW, pump speeds, mixers, zone pumps.

  1. Service menu > Actuator test
  2. Pick the group (Boiler, Heating, DHW, Solar) and the function
  3. Function stays active 30 s, then drops out

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Actuator test. Written in our own words; check the manual for your exact model.

Adjust CO2 at full load

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Adjusts the CO2 level at upper heating input.

  1. Set the service display to 100 (100%) for upper heating input.
  2. Check the CO2 level at the flue pipe.
  3. If the CO2 is out of range, remove cap B and turn adjusting screw A in small steps with a 3 mm Allen key.
  4. Turning clockwise lowers CO2 (less gas). Turning counter-clockwise raises CO2 (more gas).
  5. Record the reading in the maintenance report on page 158.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 66. Written in our own words; check the manual for your exact model.

Adjust CO2 at partial load

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Adjusts the CO2 level at lower heating output and returns the boiler to operating mode.

  1. Press the button until the service indicator shows 0 (lower heating output).
  2. Measure CO2 at the flue gas pipe.
  3. If needed, unscrew cover cap B and turn adjustment screw A in small steps with a Torx 40 driver. Clockwise increases CO2; counter-clockwise decreases CO2.
  4. Record the reading in the maintenance record on page 158.
  5. Start the upper and lower heating outputs again via the burner control unit and recheck.
  6. Press the two buttons together for more than 2 seconds to return the burner to operating mode.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.

Bleeding air program

Boiler · Vitodens 200-W

Bleeds air from the system. The pump cycles the same way as the venting program and the burner is off.

  1. Activate the program as described in the Venting the heating system section.
  2. The pump runs alternately on and off for 30 seconds each over 20 minutes.
  3. Burner remains off during the program.

Applies to: Vitodens 200-W B2HA 80 to 100

Source: Vitodens 200-W B2HA Service Instructions, p. 91. Written in our own words; check the manual for your exact model.

Brief scan

Boiler · Vitodens 200-W

The brief scan shows temperatures, software versions and connected components on 9 lines with 6 fields each.

  1. Press OK and the second key together for about 4 seconds.
  2. Select 'Diagnosis', then 'Brief scan'.
  3. Press OK to view the 9-line display.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 73. Written in our own words; check the manual for your exact model.

Brief scan (Vitotronic 200)

Boiler · Vitotronic 200

The brief scan shows temperatures, software versions and connected components in 4 lines with 6 fields each. The field-by-field table on the source page is partly garbled in this copy, so check the original page for exact field meanings.

  1. Press OK and the second button until the control is in service mode.
  2. Select Diagnosis.
  3. Select Brief scan.
  4. Press OK.
  5. Read the 4 lines of values.

Applies to: Vitotronic 200

Source: Vitotronic 200 and 300-K Installation and Service, p. 69. Written in our own words; check the manual for your exact model.

Brief scan (Vitotronic 300-K)

Boiler · Vitotronic 300-K

The brief scan shows 9 lines with 6 fields each: system type, software versions, KM BUS participants, LON addresses and connected remote controls per heating circuit. The field table is partly unreadable in this copy.

  1. Press OK and the second button until the control is in service mode.
  2. Select Diagnosis.
  3. Select Brief scan.
  4. Press OK.
  5. Read the 9 lines; check the remote control entries for each heating circuit.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service, p. 70. Written in our own words; check the manual for your exact model.

Brief scan of boiler values

Boiler · Vitodens 200-W, Vitotronic 200, Vitocrossal 300

Brief scan shows 9 lines of 6 fields with setpoint and actual boiler temperature, software versions, burner control unit type, flow sensing state and LON/KM BUS details. Field meanings are given per line in the manual table; read the manual for the exact line and field layout.

  1. Enter the service level.
  2. Select "Diagnosis", then "Brief scan".
  3. Tap OK to show the 9-line display and page through the brief scan entries.

Applies to: Vitodens 200-W and Vitocrossal 300 CU3A with Vitotronic 200

Source: Viessmann Vitotronic 200 Operating Instructions, p. 13. Written in our own words; check the manual for your exact model.

Brief scan of operating data

Boiler · Vitodens 200-W

Shows temperatures, software versions and connected components on 9 lines with 6 fields each. A sensor that is faulty shows "- - -" on the display.

  1. Enter the service level.
  2. Select "Diagnosis", then "Brief scan".
  3. Press OK. The display shows 9 lines with 6 fields each.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA service instructions, p. 72. Written in our own words; check the manual for your exact model.

Brief scan of system data

Boiler · Vitotronic 200-H

The brief scan shows temperatures, software versions, connected components and LON/KM BUS counts over 9 lines of 6 fields each. The field layout in the manual is hard to read in this extract, so check the printed table for exact field meanings. Fields 3 and 5 show the same values.

  1. Press OK together with the second button for about 4 seconds.
  2. Select 'Diagnosis', then 'Brief scan'.
  3. Press OK to view the 9 lines of fields.

Applies to: Vitotronic 200-H HK1B

Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

Brief scan of system information

Boiler · Vitocrossal 300 CA3B

The brief scan gives an overview of system schemes, control unit and extension software versions, remote control type, KM BUS participants, LON address and communication module versions.

  1. From the home screen tap Service and enter the viservice password.
  2. Select Diagnosis, then Brief scan.
  3. Read the required line in the overview table (11 lines, 6 fields).

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 118. Written in our own words; check the manual for your exact model.

Brief scan of temperatures and components

Boiler · Vitodens 200-W

Shows temperatures, software versions and connected components on 9 lines with 6 fields each.

  1. Press OK and the second button shown in the manual together for about 4 seconds.
  2. Select "Diagnosis".
  3. Select "Brief scan".
  4. Press OK.

Applies to: Vitodens 200-W diagnosis

Source: Vitodens 200-W B2HA service instructions, p. 72. Written in our own words; check the manual for your exact model.

Brief scan of temperatures, versions and components

Boiler · Vitodens 200-W B2HA

Shows 9 lines with 6 fields each: temperatures, software versions and connected components.

  1. Enter the service level.
  2. Select Diagnosis.
  3. Select Brief scan.
  4. Press OK. The display shows 9 lines of 6 fields.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 66-68. Written in our own words; check the manual for your exact model.

Bring back an acknowledged fault

Boiler · Vitotronic 200

Lets you look again at a fault that was already acknowledged.

  1. Hold the scan button for about 3 seconds.
  2. Select the acknowledged fault with the arrow buttons.
  3. Read the fault shown on the display.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

Burner fault codes

Boiler · Vitocrossal 300 CA3B

Burner faults show on the control unit display. The manual sends burner fault details to the burner section of the service instructions, which is not in these pages.

  1. Use the burner section of the service instructions for burner-side fault work.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 128. Written in our own words; check the manual for your exact model.

Call up and change Coding 1

Boiler · Vitotronic 100 GC1

Enter Coding 1 on the Vitotronic 100 control to view or change coding addresses.

  1. Press the 9 and w keys together for about two seconds, until the first arrow appears in the display.
  2. Select the coding address with the arrow keys. The address flashes. Confirm to see the value flash.
  3. Change the value with the arrow keys and confirm. The value stays steady for about 2 seconds, then the display flashes again.
  4. Select further addresses with the arrow keys if needed.
  5. Press the 9 and w keys together for about one second to exit.

Applies to: Vitotronic 100 GC1, Coding 1

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 154. Written in our own words; check the manual for your exact model.

Call up and change Coding 2

Boiler · Vitotronic 100 GC1

Enter Coding 2 on the Vitotronic 100 control to view or change coding addresses.

  1. Press the w and rw keys together for about two seconds, until the first two arrows appear in the display. Confirm.
  2. Select the coding address with the arrow keys. The address flashes. Confirm to see the value flash.
  3. Change the value with the arrow keys and confirm. The value is saved and stays steady for about 2 seconds, then the display flashes again.
  4. Select further addresses with the arrow keys if needed.
  5. Press the w and rw keys together for about one second to exit.

Applies to: Vitotronic 100 GC1, Coding 2

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 156. Written in our own words; check the manual for your exact model.

Call up coding level 1

Boiler · Vitodens 200-W B2HA

Coding level 1 groups codes by General, Boiler, DHW, Solar, Heating circuit 1/2/3 and All codes std device.

  1. Press OK and the second key together for about 4 seconds.
  2. Select Coding level 1.
  3. Select the group of the code you need.
  4. Select the coding address.
  5. Choose the value from the table and confirm with OK.
  6. To reset all codes to factory setting, select Standard setting in Coding level 1 (this also resets level 2 codes).

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 39. Written in our own words; check the manual for your exact model.

Call up fault memory

Boiler · Vitocrossal 300 CA3B Dual Fuel

The ten most recent faults are stored. The list scrolls from the newest to the oldest. The display closes automatically after 20 seconds with no key press. A non-lockout fault with no code may still show its cause here.

  1. Hold the S button for more than 2 seconds until the indicator flashes.
  2. Press Y until "4" shows under Service.
  3. Press S. "4" shows under Status.
  4. Press Y or B to choose: 1 = display fault codes, 2 = detail fault codes, 3 = clear fault memory.
  5. Press S to open the selected view.
  6. Press Y or B to scroll through the fault codes.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 27. Written in our own words; check the manual for your exact model.

Call up the commissioning assistant later

Boiler · Vitodens 100-W B1HE/B1KE

Use this to finish commissioning after the boiler has already been switched on.

  1. Press the two buttons shown on the control panel together with OK for about 4 seconds, then release.
  2. Select Basic settings and press OK.
  3. Select Commissioning assistant and press OK.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W, B1HE/B1KE Combi Installation/Service instructions, p. 41. Written in our own words; check the manual for your exact model.

Calling up and changing coding 1

Boiler · Vitotronic 300-K MW1S

Coding 1 is opened with the 9 and w buttons. Each address and value is confirmed one at a time.

  1. Press 9 and w together for about 2 seconds.
  2. Select the address with the up or down button; confirm to make the value flash.
  3. Change the value with the up or down button and confirm.
  4. The display briefly shows Adopted and the address flashes again.
  5. Select further addresses as needed.
  6. Press 9 and w together for about 1 second to exit.

Applies to: Vitotronic 300-K, MW1S

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 148. Written in our own words; check the manual for your exact model.

Calling up and changing coding 2

Boiler · Vitotronic 300-K MW1S

Coding 2 is opened with the w and rw buttons. Addresses are scrolled in the order shown in the address map.

  1. Press w and rw together for about 2 seconds and confirm.
  2. Select the address with the up or down button; confirm to make the value flash.
  3. Change the value with the up or down button and confirm.
  4. The display briefly shows adopted and the address flashes again.
  5. Select further addresses as needed.
  6. Press w and rw together for about 1 second to exit.

Applies to: Vitotronic 300-K, MW1S

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 151. Written in our own words; check the manual for your exact model.

Change altitude setting on burner control

Boiler · Vitocrossal 200 CM2

Set the burner for low or high altitude. The burner must be in standby (Status 0, Service 0).

  1. Press button S and hold for more than 2 seconds until the display area flashes.
  2. Press button Y or E until 6 appears in the Service display.
  3. Press button S until 6 appears in the Status display.
  4. Press button Y or E until 3 appears in the Service display.
  5. Press button S until 3 appears in the Status display.
  6. Current altitude shows in the Service display: 0 = low altitude, 1 = high altitude.
  7. Press Y/E or B/G until 1 (high altitude) appears, then press S to confirm. Repeat if 0 appears.
  8. Press S to exit setting mode.
  9. Press button R for more than 2 seconds to restart and apply settings.
  10. Fill out and apply the Altitude Conversion label next to the rating plate, and complete the conversion report.

Applies to: Vitocrossal 200 CM2 burner control

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 13. Written in our own words; check the manual for your exact model.

Change gas type on burner control

Boiler · Vitocrossal 200 CM2

Set the burner to natural gas or LPG. The burner must be in standby (Status 0, Service 0).

  1. Press button S and hold for more than 2 seconds until the display area flashes.
  2. Press button Y or E until 6 appears in the Service display.
  3. Press button S until 6 appears in the Status display.
  4. Press button Y or E until 2 appears in the Service display.
  5. Press button S until 2 appears in the Status display.
  6. Current gas type shows in the Service display: 0 = NG, 1 = LPG.
  7. Press Y/E or B/G to set 0 for NG or 1 for LPG.
  8. Press S to confirm. Repeat if 0 appears when 1 was expected.
  9. Press S to exit setting mode.
  10. Press button R for more than 2 seconds to restart and apply settings.

Applies to: Vitocrossal 200 CM2 burner control

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 13. Written in our own words; check the manual for your exact model.

Check and reverse mixing valve motor rotation

Boiler · Vitodens 200-W B2HA

The boiler runs a self-test at power-up in which the mixing valve opens and closes again. Use this with a manual test to confirm the motor direction. The motor direction is reversed by switching two core wires at a plug.

  1. Disconnect main power before opening the boiler.
  2. Watch the mixing valve during the self-test after switching on.
  3. Set the mixing valve manually to Open and check that the flow temperature sensor reads higher.
  4. To reverse the motor, remove the upper casing cover of the extension kit.
  5. At plug gS, switch the cores at terminals "|" and "~".
  6. Refit the casing cover and recheck operation.

Applies to: Extension kit with mixing valve

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 80. Written in our own words; check the manual for your exact model.

Check fault messages without burner fault

Boiler · Vitodens 100-W B1HE/B1KE

Use this to read a non-burner fault number so the contractor knows what to look for. The message facility turns back on the next day at 07:00 if troubleshooting is delayed.

  1. Tap OK to confirm.
  2. Press and hold the menu button for about 4 seconds, then tap OK.
  3. Select Error message, then tap OK to confirm.
  4. Select the required message, then tap OK to confirm.
  5. Write down the fault number shown, for example F.14.
  6. Use the back button to return a step, or select further messages.
  7. Select Contractor to view the heating contractor's contact details if entered.
  8. Hold the exit button for about 4 seconds to leave the menu.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Check flue gas temperature sensor and fixed high limit

Boiler · Vitodens 100-W, WB1B

Use the resistance curves to check the flue gas sensor. If the boiler cannot be reset after an F2 shutdown while water is below about 203°F (95°C), check the fixed high limit.

  1. Pull the leads from the flue gas temperature sensor and check its resistance against the curve; replace it if the deviation is severe.
  2. Pull the leads from the fixed high limit and check continuity with a multimeter.
  3. Replace the fixed high limit if it has no continuity.
  4. Coat the new fixed high limit with heat conducting paste and install it.
  5. Reset the control (see page 76).

Applies to: Vitodens 100-W WB1B

Source: Vitodens 100-W WB1B installation and service instructions, p. 80. Written in our own words; check the manual for your exact model.

Check maintenance messages

Boiler · Vitocrossal 200 CI2

Maintenance messages show on the display when service intervals or limits are reached. The red indicator flashes in this case.

  1. Open the message lists from the main menu.
  2. Select "Service" to view the maintenance messages.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 57. Written in our own words; check the manual for your exact model.

Check mixing valve motor direction

Boiler · Vitocrossal 300 CA3B

During an actuator test of a mixing valve the supply temperature must rise when the valve opens. If it falls, the motor is turning the wrong way or the valve set is fitted incorrectly.

  1. Run the mixing valve open test in the actuator test.
  2. Watch the supply temperature. It must rise as the valve opens.
  3. If the temperature drops, check the motor rotation and the valve set fitting against the mixing valve installation instructions.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0 with mixing valves

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 119. Written in our own words; check the manual for your exact model.

Check operating data

Boiler · Vitocrossal 200 CI2

Operating data is grouped in the diagnosis menu. Heating circuits with mixing valves only show data if those components are installed. A faulty sensor shows as dashes.

  1. Enter the service menu.
  2. Select Diagnosis.
  3. Select the required group, for example General.

Applies to: Vitocrossal 200 CI2 service menu

Source: Vitocrossal 200 CI2 Service Instructions, p. 55. Written in our own words; check the manual for your exact model.

Check sensor readings

Boiler · Vitotronic 200-H

Each sensor is shown on the display with its own number. Scan the actual temperature of each one.

  1. Press the sensor scan button (symbol not legible in the source).
  2. Scroll through the sensors with the up or down arrow and read the actual temperature.
  3. Press OK to finish.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Check sensor temperatures

Boiler · Vitotronic 200-H

Puts the control in scanning mode to read actual sensor temperatures. See page 23 for scanning operating conditions.

  1. Press the scan key to start scanning operating conditions.
  2. Scroll through the actual temperatures with the arrow keys.
  3. Press the confirm key to finish scanning.

Applies to: Vitotronic 200-H sensors

Source: Vitotronic 200-H installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Check sensor temperatures in Diagnosis

Boiler · Vitocrossal 300 CA3B

Scan the live temperature of a sensor from the service menu to check it against the actual reading.

  1. From the home screen, open Service and enter the 'viservice' password.
  2. Open Diagnosis.
  3. Select the sensor group.
  4. Scan the actual temperature of the sensor you are checking.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 120. Written in our own words; check the manual for your exact model.

Check sensor temperatures on Vitotronic 300-K

Boiler · Vitotronic 300-K

Use the diagnosis menu to read the actual temperature of each sensor, grouped by sensor type.

  1. Press OK and the second menu key together for about 4 seconds.
  2. Select 'Diagnosis'.
  3. Select the sensor group (group list is on page 68 of the manual).
  4. Read the actual temperature of the sensor you need.

Applies to: Vitotronic 300-K, MW2B

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

Check sensors (Vitocontrol-S)

Boiler · Vitocontrol-S VD2/CT3/CM2

Scans actual temperatures in the operating-conditions scan mode.

  1. Press the button shown to start sensor scanning (scanning is active, see page 111).
  2. Scan the actual temperature with the up or down button.
  3. Press the button shown to finish. Scanning is completed.

Applies to: Vitocontrol-S VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 99. Written in our own words; check the manual for your exact model.

Check sensors (Vitotronic 100)

Boiler · Vitotronic 100 GC1

Scans the actual temperatures while the unit is in operating-conditions scan mode.

  1. Press the button shown to start sensor scanning (scanning is active, see page 106).
  2. Scan the actual temperature with the up or down button.
  3. Press the button shown to finish. Scanning is completed.

Applies to: Vitotronic 100 GC1

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 98. Written in our own words; check the manual for your exact model.

Check sensors and test relays

Boiler · Vitotronic 200-H

Access the diagnosis and actuator test functions from the control.

  1. Press OK and hold together with the second button for about 4 seconds.
  2. To check sensors: select Diagnosis, then select the group (see page 31), then read the actual temperature of the sensor.
  3. To test relays: select Actuator test and switch the outputs as listed in the actuator test table.

Applies to: Vitotronic 200-H HK1B

Source: Vitotronic 200-H HK1B installation and service manual, p. 28. Written in our own words; check the manual for your exact model.

Check service messages

Boiler · Vitodens 100-W B1HE/B1KE

Read the service message number so the contractor can prepare before visiting. The contractor sets the service intervals, and Active messages appears when one is overdue.

  1. Tap OK to confirm.
  2. Select Active messages, then tap OK.
  3. Select Maintenance, then tap OK.
  4. Select the required message, then tap OK.
  5. Write down the service message number shown, for example P.1.
  6. Tap OK to confirm, then tell the contractor.
  7. Hold the exit button for about 4 seconds to leave the menu.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Check Vitotronic 200-H (LON connection)

Boiler · Vitodens 200-W B2HA

The Vitotronic 200-H accessory connects to the control unit over LON. Test the link with a participant check on the boiler control unit.

  1. Disconnect main power before opening the boiler.
  2. Run the participant check at the boiler control unit (see page 37 of the manual).

Applies to: Vitotronic 200-H accessory

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 80. Written in our own words; check the manual for your exact model.

Checking active maintenance messages

Boiler · Vitodens 100-W, B1HE, B1KE

Shows any maintenance messages that are currently active.

  1. Use the selector to choose the active messages menu, then press OK.
  2. Select Maintenance and press OK.
  3. Existing messages are shown on the display.

Applies to: Vitodens 100-W

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words; check the manual for your exact model.

Checking sensor temperatures

Boiler · Vitotronic 300

Reads the actual temperature of a sensor from the diagnosis menu.

  1. From the home screen tap Menu.
  2. Tap Service.
  3. Enter the viservice password.
  4. Tap Diagnosis.
  5. Select the group.
  6. Read the actual temperature of the required sensor.

Applies to: Vitotronic 300 GW6B

Source: Vitotronic 300, GW6B installation and service instructions, p. 54. Written in our own words; check the manual for your exact model.

Clear the fault memory

Boiler · Vitocrossal 200 CM2

Deletes all stored fault entries from the operating display.

  1. Press and hold S for longer than 2 seconds until the symbol flashes.
  2. Press Y until 4 shows under Service, then press S. 4 shows under Status.
  3. Press Y until 3 shows under Service.
  4. Press S. 1 shows under Status and dEL under Service.
  5. Press S to confirm. 1 under Service means deleted, 0 means it failed.
  6. Press S to return to the operating display.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 49. Written in our own words; check the manual for your exact model.

Coding 8F: menu lock and emissions test mode

Boiler · Vitodens 200-W

Address 8F controls whether the standard and extended service menus are available and whether emissions test mode can be enabled. The new value only takes effect after you exit the service menu.

  1. Open coding address 8F and select the menu access level needed (0, 1 or 2).
  2. Exit the service menu so the change takes effect.
  3. Use emissions test mode only where the setting allows it (8F:1 or 8F:2).

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 58. Written in our own words; check the manual for your exact model.

CSD-1 field test of fixed high limit

Boiler · Vitocrossal 300 CU3A

Where required by law, test the fixed high limit by simulating an overheat. Viessmann is not responsible for damage caused by overheating during this test. A tripped fixed high limit needs a manual reset of the control.

  1. Run the boiler to high fire using the relays test.
  2. Throttle the boiler valve until the burner runs with as little flow as possible.
  3. When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  4. Let the boiler temperature keep rising until the fixed high limit trips.
  5. After the fixed high limit trips, slowly open the boiler valve to cool the boiler down.
  6. Reset the boiler control manually.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 7. Written in our own words; check the manual for your exact model.

Diagnosis and service scans

Boiler · Vitodens 200-W

Service scans show live values such as outdoor temperature, boiler and DHW setpoints and actual temperatures, supply temperatures, system type, software versions, LON and KM BUS participants, remote control type and pump type. A brief scan shows lines 1 to 8 with fields 1 to 6. The page does not show the button used to start scans, so check the control display.

  1. Use the scan function on the control to show values. Read the value names on the display and match them to the scan table.
  2. Use "D" to reset the adjusted outdoor temperature to the actual outdoor temperature where the display offers it.
  3. Use the brief scan (lines 1 to 8) to check system type, software versions, and communication participants.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Viessmann Vitodens 200-W B2HB service instructions, p. 72-73. Written in our own words; check the manual for your exact model.

Diagnosis and service scans (brief scan lines 1 to 8)

Boiler · Vitodens 200-W

The control unit can scan a set of values in numbered lines. Which values appear depends on the installed system. Lines 1 to 8 cover system type, software and appliance version, burner control unit, flow rate sensor, and LON addressing. Line 9 covers remote control type, line 10 covers pump type, and line 11 covers mixing valve extensions. The manual's scan table is partly jumbled in this extract, so check the full table on the original page.

  1. Use the diagnosis scan on the control unit to read the values.
  2. Line 1: system type (01 to 10), control unit software version, programming unit software version.
  3. Line 2: appliance version and device identification.
  4. Line 4: burner control unit type and version.
  5. Line 6: flow rate sensor switching state (flow rate too low or not present).
  6. Line 9: remote control type (0 none, 1 Vitotrol 200 series, 2 Vitotrol 300 series or Vitohome) and its software version for each heating circuit.
  7. Line 10: internal and external pump type (0 none, 1 Wilo, 2 Grundfos) and variable speed pump status.
  8. Line 11: mixing valve extension present for heating circuits M2 and M3.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB service instructions, p. 72-73. Written in our own words; check the manual for your exact model.

Download the fault history (last 10 faults)

Boiler · Vitotronic 200-H

The control saves the 10 most recent faults, sorted by date. Fault 1 is the newest. All saved faults can be cleared with 'D'.

  1. Press the two keys shown in the manual together for about 2 seconds (key symbols unclear in this text).
  2. Scroll through the saved faults with the up or down key.
  3. To clear the whole history, select 'D'.
  4. Press the confirm key to exit.

Applies to: HK1S, HK3S

Source: Vitotronic 200-H installation and service instructions, p. 29. Written in our own words; check the manual for your exact model.

Emissions (flue gas) test mode

Boiler · Vitocrossal 300 CU3A

For use only by a certified technician during the annual inspection. The burner runs, the pumps start, mixing valves stay in control, and the temperature controller regulates boiler water temperature. Start-up can be delayed, for example by fuel oil preheating. It can be started even if the heating contractor has locked the controls.

  1. Open the extended menu.
  2. Choose Test mode.
  3. Choose Flue gas test °C ON.
  4. To end the test, wait for the automatic stop after 30 minutes or press OK.

Applies to: Vitocrossal 300 CU3A with Vitotronic 200 KW6B

Source: Vitocrossal 300 CU3A operating instructions, p. 35. Written in our own words; check the manual for your exact model.

Emissions test function

Boiler · Vitocrossal 300 CA3B Dual Fuel

Enable the emissions test on all control units. It starts the burner, starts all pumps and keeps the mixing valve on control. Short runs go to full output; long runs drop to modulating so the boiler does not cycle.

  1. Enable the emissions test function on all control units.
  2. For runs under 30 min, the burner runs at 100% until the temperature limiter in the burner control unit switches it off, then cycles at 100% around the limiter value.
  3. For runs over 30 min, the boiler water is held at its maximum set value (example 194 °F / 90 °C) and the burner modulates.

Applies to: CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 38. Written in our own words; check the manual for your exact model.

Emissions test mode

Boiler · Vitotronic 200

Holds the boiler at a steady temperature for a short flue gas test.

  1. Activate the emissions test switch on the Optolink/emissions test board.
  2. Burner switches on, and all pumps run.
  3. Mixing valve stays in its control mode.
  4. Boiler water is controlled by the adjustable high limit, which is set to 167 °F / 75 °C by default.
  5. Take flue gas readings during the short test window.

Applies to: Boiler control board

Source: Vitotronic 200 service instructions, p. 64. Written in our own words; check the manual for your exact model.

Emissions test mode (flue gas measurement)

Boiler · Vitotronic 200

The emissions test switch on the optolink/emissions board runs the boiler at a constant water temperature for a short time for flue gas measurement. The burner starts, all pumps run, the mixing valve stays in control mode, and boiler water temperature is held by the adjustable high limit.

  1. Set the emissions test switch to its test position.
  2. Confirm the burner is firing and all pumps are running.
  3. Measure flue gas at the test point.
  4. Return the switch to normal operation when finished.

Applies to: Vitotronic 200 KW2 boiler

Source: Vitotronic 200 Service Instructions, p. 64. Written in our own words; check the manual for your exact model.

Emissions test mode (flue gas test)

Boiler · Vitocrossal 300 CA3B

Used to test flue gas with briefly raised boiler water temperature. Only the heating contractor should activate it, during the annual inspection. The emissions test switch position symbols are not legible in this copy, so the exact switch positions are not stated here.

  1. Set the emissions test switch on each boiler section to the test position (A boiler section 1, B boiler section 2, C boiler section 3, depending on model).
  2. Check that the burner runs, the pumps start and the electronic temperature controller regulates boiler water temperature.
  3. Mixing valves stay under control function during the test.
  4. To end emissions test mode, set the emissions test switch back to the normal position.

Applies to: Boiler model 2.5 to 4.0 (switch A and B) and 5.0 and 6.0 (switch A, B and C)

Source: Vitocrossal 300 CA3B operating instructions, p. 37. Written in our own words; check the manual for your exact model.

Emissions test mode (service technician only)

Boiler · Vitotronic 200, Vitotronic 300-K

Raises boiler water temperature briefly to test flue gas. Only the service technician should use it, during the annual inspection. It must be activated on the Vitotronic 200 of the boiler being tested, and on the Vitotronic 300-K cascade control for heat transfer.

  1. Press the keys shown to open test mode.
  2. Select "test mode".
  3. Use the arrow keys to select "ON".
  4. Confirm with OK.
  5. Press the exit key to leave the menu.
  6. To end: open settings, scroll until "S" flashes, confirm with OK so "OFF" flashes, then confirm again with OK.
  7. Test mode also ends automatically after 30 minutes.

Applies to: Vitotronic 200 type H01B (printed as HO1B) and Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 34. Written in our own words; check the manual for your exact model.

Emissions test mode for flue gas testing

Boiler · Vitotronic 300-K

Briefly raises boiler water temperature for flue gas testing. Only the service technician should activate it, during the annual inspection.

  1. Set the emissions test switch on the Vitotronic 300-K to the test position.
  2. The pumps start and the mixers stay in control function.
  3. Enable emissions test at the control unit of each boiler. The burner comes on and the boiler circuit pump starts.
  4. To end: set the emissions test switch back, or close the cover flap.
  5. Disable emissions test at the control unit of each boiler.
  6. Follow the applicable boiler operating instructions.

Applies to: Vitotronic 300-K MW2C multi-boiler cascade

Source: Vitotronic 300-K MW2C operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Emissions test switch

Boiler · Vitocontrol-S

The Vitocontrol-S has an emissions test switch on the front. The full emissions test procedure is described on page 34 of the manual, which is not on these pages.

  1. Locate the emissions test switch on the Vitocontrol-S front panel.
  2. Refer to page 34 of the manual before using it.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Emissions test switch and status LEDs on Main PCB LV

Boiler · Vitotronic 200, Vitotronic 300-K

The Main PCB LV legend marks S3 as the emissions test switch on the board. Two indicators are also shown: a red fault indicator (V1) and a green ON indicator (V2).

Applies to: Vitotronic 200 HO1B / 300-K MW2B main PCB LV

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 88. Written in our own words; check the manual for your exact model.

Emissions test switch for temporary operation after a control fault

Boiler · Vitotronic 100, GC1

Only use after consulting the heating contractor. The boiler then runs temporarily at constant boiler water temperature.

  1. Consult the heating contractor first.
  2. Leave the cover open and turn emissions test switch S to h.

Applies to: Single-boiler and multi-boiler systems

Source: Vitotronic 100, GC1 operating instructions, p. 13 and p. 15. Written in our own words; check the manual for your exact model.

Emissions test switches are behind the front panels

Boiler · Vitocrossal 300 CA3B

The emissions test switches D, E and F are only reached by opening the top and bottom front boiler panels and the control covers.

  1. Remove the top and bottom front boiler panels.
  2. Open the control covers to reach the emissions test switches D, E and F.

Applies to: Vitocrossal 300 CA3B all sizes

Source: Vitocrossal 300 CA3B operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Enable emissions test mode

Boiler · Vitodens 200-W B2HA

Coding 8F:1 or 8F:2 allows emissions test mode to be enabled. Coding 8F:0 keeps full menu access. The setting takes effect only when the service menu is exited.

  1. Set coding 8F to 1 or 2 in the service menu.
  2. Exit the service menu so the coding is active.
  3. Enable emissions test mode from the service menu.

Applies to: Vitodens 200-W B2HA, emissions test

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 53. Written in our own words; check the manual for your exact model.

Enter CO2 test mode (relay test and modulation)

Boiler · Vitocrossal 200 CM2

Burner test mode used to hold the burner at a set output for combustion checks.

  1. Open the gas shut-off valve.
  2. Start the burner with the emissions test switch enabled on the boiler control unit.
  3. Press button S and button B together and hold for more than 2 seconds.
  4. Status display shows P (relay test). Service display shows modulation level in %.
  5. Use 100 for 100% (upper heating input) and 0 for 0% (lower heating input).

Applies to: Vitocrossal 200 CM2 burner control

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

Enter coding 1 (system design and multi-boiler addresses)

Boiler · Vitocontrol-S VD2/CT3/CM2

Coding 1 holds the system design and multi-boiler addresses. The button symbols in this part of the text are partly garbled, so confirm the keys on the unit before starting.

  1. Press the 9 key and the w key together for about 2 seconds.
  2. Select the coding address with the up or down key. The address flashes.
  3. Confirm with the selection key. The value flashes.
  4. Change the value with the up or down key and confirm. 'Adopted' shows briefly and the address flashes again.
  5. To view more addresses, use the up or down key.
  6. Press the 9 key and the w key together for about 1 second to leave coding.

Applies to: Vitocontrol-S VD2/CT3/CM2 coding 1

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 164. Written in our own words; check the manual for your exact model.

Enter coding 2 (general, pump, LON and fault settings)

Boiler · Vitocontrol-S VD2/CT3/CM2

Coding 2 covers the remaining addresses. Addresses are scrolled in sequence: system circuit A1 first, then mixing valve circuits M2 and M3.

  1. Press the w key and the rw key together for about 2 seconds, then confirm.
  2. Select the required address with the up or down key. The address flashes.
  3. Confirm. The value flashes.
  4. Change the value with the up or down key and confirm. 'Adopted' shows briefly.
  5. To view more addresses, use the up or down key.
  6. Press the w key and the rw key together for about 1 second to leave coding.

Applies to: Vitocontrol-S VD2/CT3/CM2 coding 2

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 167. Written in our own words; check the manual for your exact model.

Enter coding level 2 and change coding addresses

Boiler · Vitocrossal 300 CU3A

Coding level 2 shows all codes, including level 1 codes. Codes not assigned by the system equipment level are hidden.

  1. Press OK and the second button together for about 4 seconds (second button name is not printed on the page).
  2. Press OK and the second button together for about 4 seconds again to reach coding level 2.
  3. Select the group: General, Boiler, DHW, Heating circuit 1/2/3, or All codes or solar.
  4. Select the coding address.
  5. Select the value and confirm with OK.
  6. To reset all codes to factory setting, select Standard setting in Coding level 2. This also resets level 1 codes.

Applies to: Vitocrossal 300 CU3A boilers

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 62. Written in our own words; check the manual for your exact model.

Enter emissions test (relay test) mode

Boiler · Vitocrossal 300 CA3B

Opens the service display for combustion testing on the GW6C burner control.

  1. Start the burner with the emissions test switch enabled at the control unit.
  2. At the same time, press the two buttons shown as S E and B D and hold for more than 2 seconds.
  3. Status shows P (relay test). Service shows modulation level in %.
  4. 100 means upper heating input and 0 means lower heating input.

Applies to: CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.

Enter emissions test mode

Boiler · Vitocrossal 200 CM2

Test mode lets you run the burner at high or low fire for combustion checks. The status display shows P (relay test) and the service display shows modulation level in percent: 100 is upper input, 0 is lower input.

  1. Open the gas shut-off valve.
  2. Enable the emissions test switch on the boiler control unit.
  3. Start the burner.
  4. At the same time press the S F and B G buttons and hold for more than 2 seconds.

Applies to: Vitocrossal 200 CM2 186 to 311

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

Enter extended parameters on Vitotron 100 VLN2

Boiler · Versatronik 503

Extended parameters can only be reached with the boiler in standby. Standby is confirmed by the flashing red dot in the bottom right of the blank display.

  1. Press and hold the power button for about 3 seconds until the display goes blank, then release it.
  2. Confirm standby by checking for the flashing red dot in the bottom right corner.
  3. Press and hold the right arrow button.
  4. While still holding the right arrow, press and immediately release the power button.
  5. Release the right arrow when the first parameter group appears.
  6. Use the up and down arrows to change a value. Press the right arrow to move to the next parameter.
  7. When finished, press and hold the power button until the display returns to standby (blank with intermittent red dot).
  8. Press the power button to turn the boiler back on.

Applies to: Vitotron 100 VLN2

Source: Versatronik 503 NR2/Analog Bridge installation and operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Enter flue gas test mode

Boiler · Vitodens 200-W B2HA

Test mode is used to bring the burner up to high fire for the fixed high limit tests.

  1. Open the extended menu in the operating manual.
  2. Select 'Test mode', then 'flue gas test ON'.
  3. Press OK. The burner starts a firing cycle and gradually goes to high fire.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Enter service display and manual mode

Boiler · Vitocrossal 300 CA3B Dual Fuel

The burner must be running to open the service display and manual mode. The service display shows the current modulation level in %.

  1. With the burner running, hold the B and S buttons together for more than 2 seconds.
  2. The burner switches to manual mode. A 'P' shows under Status and the modulation level flashes under Service.
  3. Press B to lower the heating output until '0' shows under Service.
  4. Press Y to raise the heating output until '100' shows under Service.
  5. Hold B and S together for more than 2 seconds to return the burner to modulating mode.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 24. Written in our own words; check the manual for your exact model.

Enter service functions for filling, venting and max output

Boiler · Vitodens 200-W

Service functions are entered from the control panel. Use the menu to pick Filling, Venting or Maximum output. End the function with OK or the back key.

  1. Press OK and the second key together for about 4 seconds.
  2. Select Service functions.
  3. Select Filling, Venting or Maximum output as needed.
  4. Press OK or the back key to end the function.

Applies to: Vitodens 200-W B2HB 19 to 125

Source: Vitodens 200-W B2HB service instructions, p. 16-17, 22. Written in our own words; check the manual for your exact model.

Enter service level and start test mode

Boiler · Vitocrossal 200 CI2

Service menu access and test mode. The button icons are missing from the text, so the tap sequence is partly unclear. Use the text items and confirm on the control.

  1. Tap the menu button (icon not shown in text).
  2. Tap Service.
  3. Enter password viservice.
  4. Confirm.
  5. Select Test mode.
  6. Confirm to start test mode.
  7. Exit test mode with the stop button (icon not shown in text).

Applies to: Vitocrossal 200 CI2 programming unit

Source: Vitocrossal 200 CI2 Service Instructions, p. 10. Written in our own words; check the manual for your exact model.

Enter service menu and actuator test

Boiler · Vitodens 200-W

The service menu actuator test forces the burner to base load (low fire) or full load (high fire) for combustion checks.

  1. Press OK and the key shown on the page at the same time for about 4 seconds to enter the service menu.
  2. Select Actuator test.
  3. Select Base load OFF / ON for low fire, or Full load OFF / ON for high fire.
  4. Select 'all actuators off' to end the test.
  5. Press the exit key to leave the actuator test.

Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 30. Written in our own words; check the manual for your exact model.

Enter service menu and run actuator test

Boiler · Vitodens 222-F, B2TB

Used to force the burner to low fire or high fire for combustion testing. The key pressed with OK is not legible in the source text.

  1. Press OK and the second key together for about 4 seconds to open the service menu.
  2. Select Actuator test.
  3. Select Base load OFF to run low fire, or Full load OFF to run high fire.
  4. Select all actuators off to end the test.

Applies to: Service menu, actuator test

Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 30. Written in our own words; check the manual for your exact model.

Enter service mode for test and setting functions

Boiler · Vitodens 100-W WB1B

Entering SERV mode is the first step for all manual service functions on this boiler.

  1. Turn both selector dials to the centre position together. SERV appears on the display.
  2. Complete the next step while SERV is still shown, or the mode will not accept changes.

Applies to: Service menu entry

Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 59, 64. Written in our own words; check the manual for your exact model.

Enter the emissions/relay test mode

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Starts the CO2 test mode and shows the relay test status.

  1. Open the gas shut-off valve.
  2. Start the burner with the emissions test switch enabled at the boiler control unit.
  3. While the burner runs, press the two buttons shown on page 66 together and hold for more than 2 seconds.
  4. Status shows "P" (relay test). Service shows the modulation level in %: 100 = upper heating input, 0 = lower heating input.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner control unit

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 66. Written in our own words; check the manual for your exact model.

Enter the relay test for emissions measurement

Boiler · Vitocrossal 300 CA3B Dual Fuel

Used to hold the burner at set output while measuring combustion. Only one burner may run during adjustment; the other boiler burners must be off.

  1. Open the gas shut-off valve.
  2. Start the burner with the emissions test switch enabled at the boiler control unit.
  3. Press buttons S, E and D together and hold for more than 2 seconds.
  4. Check the display: Status shows P (relay test) and Service shows modulation in % (100 = upper output, 0 = lower output).

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 66. Written in our own words; check the manual for your exact model.

Enter the service level

Boiler · Vitotronic 300-K, Vitotronic 200

Service level is entered by holding OK together with a second button (symbol not legible in this copy) for about 4 seconds. Service level exits automatically after 30 minutes.

  1. Press OK and the second button together for about 4 seconds to enter the service level.
  2. Use the service menu overview to reach Diagnosis, Actuator test, Coding level 1 or Coding level 2 as needed.

Applies to: Vitotronic 200 and Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service, p. 67. Written in our own words; check the manual for your exact model.

Extended menu layout and Test mode entry

Boiler · Vitocrossal 300 CU3A, Vitotronic 200 KW6B

The extended menu's main branches are Heating, DHW, Information, Settings, Test mode, Solar energy and General. Heating and DHW hold the heating circuit, time program and temperature setpoint entries. Settings holds the clock, language, display and unit options, and the Reset data entry is also here. Test mode is a separate branch on the same menu. Some entries appear only if the matching equipment is installed.

Applies to: Vitocrossal 300 CU3A boilers with Vitotronic 200 KW6B control

Source: Vitocrossal 300 CU3A 26 to 199 Operating Instructions, p. 40. Written in our own words; check the manual for your exact model.

Field test the fixed high limit (CSD-1)

Boiler · Vitodens 100-W WB1B

Where required by law, the fixed high limit can be tested in the field. The fixed high limit trip produces a fault that needs a manual reset. Viessmann is not responsible for damage caused by overheating during this test.

  1. Method 1: close the boiler valve and jump the flow switch. Run the boiler at high fire, setting coding address 06 to max on WB2B models, and let the temperature rise until the fixed high limit trips. Then slowly open the boiler valve to cool it.
  2. Method 2: throttle the boiler valve so the burner runs with minimal flow. Run the boiler to high fire using the relay test. When the burner shuts down on the electronic limit, close the ball valve to stop flow and let the temperature rise until the fixed high limit trips. Then slowly open the valve to cool it.
  3. Method 3: disconnect one wire from the limit switch. This creates a control fault that requires manual reset.
  4. Reset the boiler control manually after the test.

Applies to: Vitodens 100/200 boilers

Source: Vitodens 100-W WB1B installation and service instructions, p. 5. Written in our own words; check the manual for your exact model.

Fill program

Boiler · Vitodens 200-W B2HA

Code 2F:2 starts the pump when the system is filled with the control unit on. The burner shuts down if this function is enabled through coding address 2F. The program turns off automatically after 20 minutes and 2F resets to 0.

  1. Set code 2F:2 at the control unit to start the fill pump.
  2. Fill the system.
  3. Wait for the program to end after 20 minutes, or confirm that coding address 2F has returned to 0.

Applies to: System fill with control unit on

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 86. Written in our own words; check the manual for your exact model.

Fill program (system filling with control unit on)

Boiler · Vitodens 222-F

Runs the circulation pump to help fill the system. The burner shuts down if this function is enabled.

  1. Switch the control unit on.
  2. Set coding address 2F to 2 (code 2F:2) to start the pump.
  3. Note that the burner shuts down while the function is enabled through coding address 2F.
  4. The program turns off by itself after 20 minutes and coding address 2F resets to 0.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F B2TB service instructions, p. 93. Written in our own words; check the manual for your exact model.

Filling program (service function)

Boiler · Vitodens 200-W B2HA

The filling program is started from the service menu. Its button combination is not legible in the source extraction.

  1. Press OK and the marked button together for about 4 seconds.
  2. Select Service functions.
  3. Select Filling.
  4. To end the function, press OK or the marked button.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 13. Written in our own words; check the manual for your exact model.

Flow switch check

Boiler · Vitodens 222-F

The B2TB has a flow sensing device. If flow is too low the switch opens, the burner shuts down, and it will not restart until adequate flow returns.

  1. Throttle the water flow to or from the boiler.
  2. Confirm the boiler shuts down once flow drops below its safe operating set point.
  3. Restore flow and confirm the burner restarts.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB service instructions, p. 7. Written in our own words; check the manual for your exact model.

Flue gas test mode

Boiler · Vitodens 200-W B2HA

Test mode is found in the extended menu of the operating manual. Flue gas test ON starts a firing cycle that goes to high fire.

  1. Open the extended menu and select 'Test mode'.
  2. Select 'flue gas test ON' and press OK.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 7. Written in our own words; check the manual for your exact model.

Flue gas test mode from the extended menu

Boiler · Vitodens 200-W B2HB

Test mode with flue gas test ON makes the burner start and ramp to high fire. Used for combustion checks and for the high limit test.

  1. Open the extended menu on the boiler control.
  2. Select Test mode, then select flue gas test ON.
  3. Press OK to start the firing cycle.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 7. Written in our own words; check the manual for your exact model.

Front panel indicators and switches

Boiler · Vitocrossal 200 CM2

The front panel has a green ON indicator, a red fault indicator, an emissions test switch (service use only) and the ON/OFF switch. MCBs/fuses are also located here.

  1. Check the green ON indicator to confirm the boiler is powered and on.
  2. Check the red fault indicator when the boiler is not running.
  3. Use the emissions test switch for service purposes only.

Applies to: Vitocrossal 200 CM2 186 to 620

Source: Vitocrossal 200 CM2 operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Functional checks of high limits

Boiler · Vitotronic 300 GW2

The fixed high limit is checked with the TEST button. The adjustable high limit is checked through emissions test mode.

  1. Fixed high limit: use the TEST button (7819 314) to run the functional check.
  2. Adjustable high limit: run the functional check in emissions test mode.

Applies to: Fixed and adjustable high limits

Source: Vitotronic 300 GW2 installation and service instructions, p. 98. Written in our own words; check the manual for your exact model.

Heat generator bus scan after restart

Boiler · Versatronik 200

After a restart or new configuration the controller scans the bus for heat generators for about 1 minute. The display shows SCAN. Manual output entries are blocked during this time.

  1. Wait for the SCAN to finish (about 1 min).
  2. Check the list of detected boilers. An X shows a heat generator that answered on the bus.
  3. Check each output value. If a heat generator gave no output, 15 kW is entered; change it if needed.
  4. If the list is correct, save it with Config OK.

Applies to: Versatronik 200 cascade controller

Source: Versatronik 200 installation and operating manual, p. 142. Written in our own words; check the manual for your exact model.

Heat rooms without DHW

Boiler · Vitotronic 300-K

Lets the rooms heat while DHW is not wanted, by lowering the DHW set temperature to the minimum value.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select "Heating".
  4. Select "Heating program" and choose "Heating and DHW".
  5. Go back until the menu shows "DHW".
  6. Select "DHW", then "Set DHW temperature".
  7. Set the value to 50° F (10° C).

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 22. Written in our own words; check the manual for your exact model.

High limit safety cut-out test

Boiler · Vitocrossal 200 CI2

Tests the high limit safety cut-out. Make sure there is adequate heat transfer before testing. On lag boilers the test mode is only reachable through the software tool, and you exit with the chimney sweep button on the home screen.

  1. Open the service menu and enter password "viservice".
  2. Go to "Service", then "Test mode", then "Test mode".
  3. Confirm with OK. Ensure adequate heat transfer.
  4. Use the exit button to end the test.
  5. On a lag boiler, exit with the chimney sweep button on the home screen.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 57. Written in our own words; check the manual for your exact model.

Ionization current acceptance limit

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Minimum ionization current needed for a stable flame.

  1. Confirm the ionization current reaches at least 3 µA for approx. 2 to 3 sec after the combination gas valve opens and while in operation.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 68. Written in our own words; check the manual for your exact model.

Maintenance display and service messages

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The maintenance display can be confirmed from the home screen. If several faults are active, a Service messages list appears in orange.

  1. On the maintenance display, tap Confirm.
  2. If several fault messages are active, tap Service messages to see the orange list.

Applies to: Boiler control display

Source: Vitocrossal 300 Dual Fuel service instructions, p. 119. Written in our own words; check the manual for your exact model.

Manual mode and service display

Boiler · Vitocrossal 300 CA3B Dual Fuel

The burner must be running to use the service display and manual mode. The service display shows the current modulation level in %.

  1. With the burner running, press B and S together for more than 2 seconds. The burner enters manual mode, P shows under Status, and the modulation level flashes under Service.
  2. Press B to lower the heating output, down to 0.
  3. Press Y to raise the heating output, up to 100.
  4. Press B and S together for more than 2 seconds to return to modulating mode.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 24. Written in our own words; check the manual for your exact model.

Mixing valve moves during relay test

Boiler · Vitotronic 200

The control unit opens and closes the mixing valve during the relay test, so you can confirm motor operation there.

  1. Run the relay test on the control unit.
  2. Watch the mixing valve open and close.

Applies to: Vitotronic 200 KW2 mixing valve motor

Source: Vitotronic 200 service instructions, p. 73. Written in our own words; check the manual for your exact model.

Open the information and configuration menu

Boiler · Vitocrossal 300 CA3B Dual Fuel

The information and configuration menu is opened from the operating display. It times out after 20 seconds with no button press. Menu item 5 shows process information and item 6 is used to change operating parameters. Make changes only when the burner control is on standby.

  1. Hold button S for more than 2 seconds until the menu indicator blinks.
  2. Scroll through the menu items with the Y/B buttons.
  3. Press button S to select an item. It is shown under Service.
  4. Make changes only when the burner control unit is on standby.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 22. Written in our own words; check the manual for your exact model.

Open the service actuator test

Boiler · Vitocrossal 200 CI2

Access the actuator test used for burner output selection and test firing.

  1. Tap the service button.
  2. Enter the service password "viservice".
  3. Confirm with the check button.
  4. Select "Actuator test" and confirm.

Applies to: Vitocrossal 200 CI2 control unit

Source: Vitocrossal 200 CI2 service instructions, p. 25. Written in our own words; check the manual for your exact model.

Override switch for flue gas testing

Boiler · Vitotronic 100

The override switch on the Optolink/override board lets you run the boiler at constant water temperature for a short time, for flue gas measurement.

  1. Set the override switch to the h position.
  2. Expect the burner to start (it can be delayed by a fuel preheater or flue gas damper).
  3. Expect all pumps to run.
  4. Expect boiler water temperature to be held by the adjustable high limit R.

Applies to: Vitotronic 100 GC1 Optolink/override switch board, Part 7820 165

Source: Vitotronic 100 GC1 installation and service instructions, p. 110. Written in our own words; check the manual for your exact model.

Override switch function

Boiler · Vitotronic 100

In the up position the override switch turns the boiler pump on and enables stage 1 and 2 calls for heat. The boiler then runs to the adjustable high limit temperature. In the down position the system runs normally.

  1. Set the override switch up to force pump run and stage 1 and 2 heat calls for testing.
  2. Return the switch down to normal operation when testing is finished.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 11. Written in our own words; check the manual for your exact model.

Override switch position h

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

Position h on the override switch is used to analyze flue gas with a briefly raised boiler water temperature.

  1. Set the override switch to position h.
  2. Confirm all pumps start.
  3. Confirm the mixing valve is in control function.

Applies to: Printed circuit board override switch

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 140. Written in our own words; check the manual for your exact model.

Override switch position h (manual operation)

Boiler · Vitotronic 100 GC1

In position h the control runs the burner and pumps and controls boiler water temperature by the adjustable high limit. Use it for flue gas measurement with briefly raised boiler temperature.

  1. Set the override switch to position h.
  2. Expect burner start, which can be delayed by fuel oil pre-heating or accessories.
  3. Confirm all pumps start.
  4. Watch boiler water temperature, which is controlled by the adjustable high limit.

Applies to: Vitotronic 100 GC1 optolink/override switch

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 135. Written in our own words; check the manual for your exact model.

Participant check (LON)

Boiler · Vitotronic 300

Checks LON participants. Only works with the LON communication module installed.

  1. Press the w and OK buttons together for about 2 seconds to start.
  2. Press the w and OK buttons together for about 1 second to exit.

Applies to: Vitotronic 300 GW2 with LON module

Source: Vitotronic 300 GW2 installation and service instructions, p. 72, 66. Written in our own words; check the manual for your exact model.

PCB extension LED and emissions test switch

Boiler · Vitocrossal 300 CA3B Dual Fuel

The PCB extension for heating circuits 2 and 3 has a red fault display, a green operating mode display and an emissions test switch.

  1. Check the red fault display (V1) for a fault.
  2. Check the green operating mode display (V2) for operating status.
  3. Use the emissions test switch (S3) on the PCB extension for emissions testing.

Applies to: PCB extension for heating circuits 2 and 3 with mixing valve

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 135. Written in our own words; check the manual for your exact model.

Perform LON participant check

Boiler · Vitodens 222-F

Tests communication between the fault manager and the connected LON devices. Requires the control unit set as fault manager (code 79:1), participant numbers set in all units, and an up-to-date participant list.

  1. Press OK together with the second service key (symbol not legible on the page) for about 4 seconds.
  2. Select Service functions.
  3. Select Participant check.
  4. Select the participant to test, e.g. participant 10.
  5. Read the result: OK means passed, Not OK means failed.
  6. To run a new check, create a new participant list using Delete list in the menu.

Applies to: Vitotronic fault manager on LON system

Source: Vitodens 222-F B2TB service instructions, p. 45. Written in our own words; check the manual for your exact model.

Read a fault code from the remote control

Boiler · Vitotrol 300

When a fault occurs the display shows it with the flip-down cover closed. The fault source is shown in clear text and as a fault code. Give the fault code to the heating contractor.

  1. Open the flip-down cover of the remote control.
  2. Select the fault search key. The fault source appears in clear text and as a code.
  3. Confirm the fault.
  4. Use the up/down keys to answer yes or no for acknowledgment.
  5. Confirm. The display returns to the time.
  6. Close the flip-down cover.
  7. If the fault is not corrected, the message returns at 07:00 hrs the next morning.

Applies to: Vitotrol 300 remote control, fault indication

Source: Vitotrol 300 operating instructions, p. 22. Written in our own words; check the manual for your exact model.

Read and acknowledge fault codes on Vitotronic 100

Boiler · Vitotronic 100 GC1B

A flashing fault symbol and the red fault indicator show a fault. The fault code is shown on the display. If several faults are stored, they can be scanned in sequence.

  1. Note the fault code and tell the heating contractor.
  2. Acknowledge the fault with OK; the fault symbol stops flashing.
  3. To view an acknowledged fault again, press and hold OK for about 4 seconds.
  4. If several faults are stored, scan them with the selector keys.
  5. If the fault is not fixed, it shows again the next day and any buzzer is switched on again.

Applies to: Vitotronic 100 GC1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Read and acknowledge fault messages on Vitotronic 300-K

Boiler · Vitotronic 300-K MW1B

A flashing fault symbol and the red fault indicator show a fault, and the display shows Fault. The cause text and fault code are shown together.

  1. Press OK to show the cause of the fault.
  2. Press the help key to see information on system functions and simple measures the operator can take.
  3. Note the cause and the fault code shown with it.
  4. Acknowledge the message by following the instructions in the menu; it then moves to the fault menu.
  5. To view an acknowledged fault later, open the extended menu and select Fault.
  6. If the fault is not fixed, it shows again the next day and any buzzer is switched on again.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 30. Written in our own words; check the manual for your exact model.

Read brief scan operating data

Boiler · Vitodens 222-F

The brief scan shows temperatures, software versions and connected components in 9 lines with 6 fields each.

  1. Enter the service level.
  2. Select 'Diagnosis', then 'Brief scan'.
  3. Press OK. The display shows 9 lines of values.
  4. Read '- - -' as a faulty sensor.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F B2TB service instructions, p. 70. Written in our own words; check the manual for your exact model.

Read fault codes and the error history on Vitocontrol-S

Boiler · Vitocontrol-S VD2/CT3/CM2

Faults can be shown as codes or in plain text. The manual gives the plain-text names for each sensor and device that can fault.

  1. Scroll through active faults to read the code and the plain-text name.
  2. Recall acknowledged faults by holding the key for about 3 seconds.
  3. Use the error history to find repeat faults.

Applies to: Vitocontrol-S VD2/CT3/CM2 programming unit

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 117. Written in our own words; check the manual for your exact model.

Read fault history (last 10 faults)

Boiler · Vitodens 200-W

The control unit stores the 10 most recent faults, including resolved ones, sorted by date. Detailed codes are shown as a sub-code in the fault history.

  1. Press OK and the button symbol shown in the manual at the same time for about 4 seconds.
  2. Select 'Fault history'.
  3. Select 'Display?'.
  4. Press OK to show the fault code. Look up the code in the fault code tables.
  5. For some faults, the type of fault is also shown in plain text.
  6. After servicing, select code 24:0 to reset the service-required indication (code 0F).

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB service instructions, p. 75. Written in our own words; check the manual for your exact model.

Read ionization current

Boiler · Vitocrossal 300 CA3B

Shows the ionization current in the process information menu. The value displays in 1/10 μA, so 30 means 3.0 μA.

  1. Press and hold button S for more than 2 seconds until it blinks.
  2. Press button Y until 5 shows under Service.
  3. Press button S. A 5 shows under Status.
  4. Press button Y until 3 shows under Service.
  5. Press button S. A 3 shows under Status and the ionization current shows under Service during operation.
  6. To exit, press and hold S for more than 2 seconds, then press Y until 5 shows under Service and press B until 0 shows.
  7. Press button S to return to the operating display.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.

Read ionization current from the burner control

Boiler · Vitocrossal 300 CA3B

Ionization current must be read through the burner control, not with a meter.

  1. Press the S button for about 2 seconds until the indicator blinks.
  2. Press the button until 5 shows under Service, then press S. 5 shows under Status.
  3. Press the button until 3 shows under Service, then press S. The ionization current appears under Service (for example 30 = 3.0 µA).
  4. Start the burner with the emissions test switch on the GW6C control.
  5. Read and record the ionization current.
  6. To exit, press S for about 2 seconds, set Service to 5 then S, set Service to 0 then S. The operating display returns.

Applies to: CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 69. Written in our own words; check the manual for your exact model.

Read ionization current on the control unit

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Shows the flame ionization current through the burner control unit. A multimeter or Testomatic Gas cannot measure it.

  1. Press the service button for about 2 sec until the indicator blinks.
  2. Set Service to 5, press the button, then set Status to 3 and confirm.
  3. The ionization current in operation appears under Service (for example 30 = 3.0 µA).
  4. Start the burner with the emissions test switch on the GW6C control and read the value.
  5. Record the reading in the maintenance record on page 158.
  6. Exit the menu: press the service button for about 2 sec, set Service to 5, confirm, set Service to 0 and confirm.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner control unit GW6C

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 68. Written in our own words; check the manual for your exact model.

Read key brief scan lines

Boiler · Vitodens 200-W B2HA

Line 1: system type 01 to 10 and control unit software version. Line 2: appliance version and device ID. Line 4: burner control unit type and version. Line 9: remote control (0 none, 1 Vitotrol 200/200A/200 RF, 2 Vitotrol 300/300A/300 RF or Vitohome). Line 10: variable speed pump (0 none, 1 Wilo, 2 Grundfos). Line 11: mixing valve extension present (0 = none). A field showing '- - -' means that scanned sensor is faulty.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 66-68. Written in our own words; check the manual for your exact model.

Read operating data (Diagnosis)

Boiler · Vitodens 200-W, Vitotronic 200, Vitocrossal 300

Operating data is grouped into six areas. A "- - -" reading means a sensor that was scanned is faulty. Mixing valve and solar data only show if those components are installed.

  1. Enter the service level.
  2. Select "Diagnosis".
  3. Select the required group, for example "General".

Applies to: Vitotronic 200 service level

Source: Viessmann Vitotronic 200 Operating Instructions, p. 12. Written in our own words; check the manual for your exact model.

Read operating data (Diagnostics)

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Operating data is grouped by area. Sensors that are faulty show a dashed placeholder.

  1. Enter the service menu.
  2. Select Diagnostics, then OK.
  3. Select the required group, then OK.
  4. Select the required information.
  5. If the sensor is faulty, - - - is shown on the display.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 67. Written in our own words; check the manual for your exact model.

Read system temperatures and operating status

Boiler · Vitotrol 300

Scan current values on the remote control. Available values depend on installed components and coding. Sensor-based values only appear if the sensor is installed.

  1. Open the flip-down cover of the remote control.
  2. Select the scan function. The outside temperature is shown.
  3. Use the up/down keys to scan through the values.
  4. End scanning. The display returns to the time.
  5. Close the flip-down cover.

Applies to: Vitotrol 300 remote control, system readings

Source: Vitotrol 300 operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Read the fault display and fault history

Boiler · Vitocrossal 300 CA3B

Active faults flash red on the control unit. Acknowledged faults can be listed, and the last 10 faults (including cleared ones) are kept in the fault history, sorted by date.

  1. When a fault flashes red, tap the fault button to list acknowledged faults. Several faults show as a red list in date order.
  2. For history, go to Service, enter the 'viservice' password, then open Fault history.
  3. Tap the information option on a fault to see more detail.
  4. Use the delete option to clear the history list.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 121. Written in our own words; check the manual for your exact model.

Read the fault history

Boiler · Vitotronic 200

Shows every stored fault, starting with the most recent one. Entry 1 is the newest and entry 10 is the oldest.

  1. Press the two indicated buttons together for about 2 seconds to open the error history.
  2. Use the arrow buttons to step through entries 1 to 10.
  3. Press the back button to leave the history.
  4. To delete all stored fault codes, press the delete button while in the history.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Read the fault history (last 10 faults)

Boiler · Vitodens 222-F

The control keeps the 10 most recent faults, including resolved ones, sorted by date.

  1. Press OK and the second button shown together for about 4 seconds.
  2. Select 'Fault history'.
  3. Select 'Display?' and press OK to show the code.
  4. Use the fault code tables in the manual to read the explanation. Some faults also show plain text.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 73. Written in our own words; check the manual for your exact model.

Read the fault history and clear the fault memory

Boiler · Vitotronic 200-H

All faults are saved. Position 1 is the most recent fault and position 10 is the tenth fault in memory.

  1. Press r and the arrow button together for about 2 seconds.
  2. Call up each saved fault code with the arrow buttons.
  3. To delete all saved fault codes, press D.
  4. Press OK to exit.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 30. Written in our own words; check the manual for your exact model.

Read the fault memory

Boiler · Vitocrossal 200 CM2

The last 10 faults are stored and can be scrolled from newest to oldest. The display exits on its own if no key is pressed for 20 seconds. A burner that will not start without a displayed code may still show the cause here.

  1. Press and hold S for longer than 2 seconds until the symbol flashes.
  2. Press Y until 4 shows under Service.
  3. Press S. 4 shows under Status.
  4. Press Y or B to scroll through the fault memory.
  5. Press S to open the selected fault memory display.
  6. Press Y or B to scroll through the stored fault codes.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 49. Written in our own words; check the manual for your exact model.

Recall acknowledged fault messages

Boiler · Vitotronic 200-H

Use this to review faults that were already acknowledged. The next fault only shows if two or more faults have occurred.

  1. Press and hold the fault button for about 2 seconds.
  2. Press the arrow buttons to show further faults.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Recall acknowledged faults

Boiler · Vitotronic 200-H

Acknowledged faults can be viewed again from the fault list.

  1. Press and hold the fault key for about 2 seconds.
  2. Select the acknowledged fault with the up or down key.

Applies to: HK1S, HK3S

Source: Vitotronic 200-H installation and service instructions, p. 25. Written in our own words; check the manual for your exact model.

Recall an acknowledged fault

Boiler · Vitotronic 300

Used to view previously acknowledged faults. The up and down arrows only appear when two or more faults have occurred.

  1. Press the fault button for about 2 seconds.
  2. Press the up or down arrow to show further faults.

Applies to: Fault history

Source: Vitotronic 300 GW2 operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Relay status and test menu

Boiler · Versatronik 200

Relay status and test is reached from the Service menu. The menu structure overview is shown as a diagram on the next page and is not transcribed here.

  1. Open the Service menu as described for viewing information.
  2. Select Relay Test or Relay status and test.
  3. Refer to the menu structure overview diagram for the full path.

Applies to: Versatronik 200 service mode

Source: Versatronik 200 Installation and Operating Manual, p. 159-160. Written in our own words; check the manual for your exact model.

Relay test

Boiler · Vitotronic 200

Forces each relay output on or off to check wiring and components. Relays can be switched with a delay of up to 1 minute. Some outputs only show if the matching module is connected.

  1. Press the two buttons together for about 2 seconds to start the relay test.
  2. Select the relay output with the up/down button: burner ON, burner stage 1 ON, burner modulation up or down or stop, burner stage 1+2 ON, heating pump ON, mixing valve open or closed, DHW tank pump ON, DHW recirculation pump ON, or compiled fault indicator ON.
  3. Check the matching LED and the component.
  4. Press the button shown in the manual to end the relay test.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 30. Written in our own words; check the manual for your exact model.

Relay test and sensor test menus

Boiler · Versatronik 300

The Menu holds a relay test and a sensor test. Use them to check outputs and inputs by hand.

  1. Open Menu and select Relay Test.
  2. Switch Pump, AUX or Fault between Off and On to test each output.
  3. Open Menu and select Sensor Test to view S1 (outdoor), S2 (supply), S3 (return), INT (interlock) and AUX (input).

Applies to: Versatronik 300 menu

Source: Versatronik 300 Cascade Control manual, p. 29. Written in our own words; check the manual for your exact model.

Relay test display indications

Boiler · Vitotronic 100 GC1

Relay test displays show which output is being energised. Button symbols are not clear on these pages, so confirm with the unit.

  1. Display 11: burner or stage 1 ON.
  2. Display 12: burner stage 1 and 2 ON or modulation up.
  3. Display 13: burner modulation neutral.
  4. Display 14: burner stage 1 ON, modulation down.
  5. Display 15: output 20 ON.
  6. Display 16: output 29 ON.
  7. Display 17: output 52 open.
  8. Display 18: output 52 neutral.
  9. Display 19: output 52 close.

Applies to: Vitotronic 100, GC1 relay test

Source: Viessmann Vitotronic 100/300-K installation and service manual, p. 80. Written in our own words; check the manual for your exact model.

Relay test of mixing valve motor direction

Boiler · Vitotronic 200-H

The relay test of the control unit drives the mixing valve to Open and Closed, which is used to confirm rotation direction.

  1. Start the relay test on the control unit.
  2. Watch the mixing valve move to Open and then Closed.

Applies to: Mixing valve motor

Source: Vitotronic 200-H Installation and Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Relay test of outputs and pumps

Boiler · Vitotronic 200-H

Forces individual relay outputs and mixing valve motors on or off to confirm wiring and operation. Selectable outputs include output 20, output 52 (open, hold, closed), DHW pump, DHW re-circulation pump, heating circuit pumps M2 and M3, mixing valve M2 and M3 open/closed, and fault messaging. The illuminated heating circuit selector shows which circuit is active. To reverse the mixing valve motor rotation, refer to page 41.

  1. Press 9 and OK together for about 2 seconds to start the relay test.
  2. Use the arrow keys to switch the relay output on or off.
  3. Press OK to finish the relay test.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Relay test of the mixing valve

Boiler · Vitotronic 300-K MW1S

The relay test on the control unit drives the mixing valve open and closed.

  1. Start the relay test on the control unit.
  2. Confirm the mixing valve moves to open and then to close.

Applies to: Mixing valve motor

Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 128. Written in our own words; check the manual for your exact model.

Retrieve fault history (error memory)

Boiler · Vitotronic 100

All past faults are stored. Scanning starts with the most recent fault and runs back through the stored list (up to 10 entries, numbered 1 to 10 with 1 as the last fault).

  1. Press the two buttons together and hold for about 2 seconds to start error history scanning.
  2. Use the up or down button to step through the stored fault codes, starting with the most recent.
  3. Press the button shown after the scan step to end scanning.
  4. To delete all stored faults, press the delete button shown in the manual while scanning is active, then end the scan.

Applies to: Vitotronic 100 GC1 fault memory

Source: Vitotronic 100 GC1 installation and service instructions, p. 104. Written in our own words; check the manual for your exact model.

Retrieve fault history (fault memory)

Boiler · Vitotronic 200

All past faults are stored and can be scanned from the most recent one backwards. Button names are not legible in the extracted text, so confirm the buttons on the unit or the programming unit.

  1. Press the two buttons shown together for about 2 seconds to enter error history scan mode.
  2. Read the first entry, which shows the most recent fault.
  3. Use the up or down button to step through the stored codes, up to 10 entries back.
  4. Press the exit button to leave error history scan mode.
  5. To delete all stored fault codes, press the button shown in the manual while in scan mode.

Applies to: Vitotronic 200 KW2 fault memory

Source: Viessmann Vitotronic 200 service instructions, p. 40. Written in our own words; check the manual for your exact model.

Retrieving the fault memory (error history)

Boiler · Vitotronic 100

Stored faults are kept and can be scanned, starting with the most recent. Up to 10 stored codes can be reviewed and the whole list can be cleared.

  1. Press the two buttons together for about 2 seconds to start error history scanning.
  2. Scroll through the stored codes with the up or down button. Code 1 is the most recent.
  3. Press the exit button to leave scanning.
  4. To delete all stored codes, use the delete function while in scanning mode.

Applies to: Vitotronic 100 GC1 programming unit

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 104. Written in our own words; check the manual for your exact model.

Run a brief scan

Boiler · Vitodens 200-W B2HB

Brief scan shows temperatures, software versions and connected components on 9 lines with 6 fields each.

  1. Press OK together with the second control button for about 4 seconds.
  2. Select Diagnosis.
  3. Select Brief scan.
  4. Press OK to view the 9 lines of data.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB service manual, p. 71. Written in our own words; check the manual for your exact model.

Run a relay test

Boiler · Vitotronic 100

Forces individual relays on to check outputs. It overrides all other control functions.

  1. Set dial switch S2 to the relay test position needed (see the dial switch table).
  2. Check the output responds as expected.
  3. Return S2 to position 0 for normal operation.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation, start-up and service instructions, p. 29. Written in our own words; check the manual for your exact model.

Run LON participant check

Boiler · Vitodens 200-W

Tests communication with the devices connected to the fault manager. Results show as OK or Not OK per participant.

  1. Confirm the control is fault manager (code 79:1) and the participant list is up to date.
  2. Press OK and the second key (symbol not legible in the text) together for about 4 seconds.
  3. Select 'Service functions'.
  4. Select 'Participant check'.
  5. Select the participant (for example participant 10).
  6. Read the result: OK means passed, Not OK means failed.

Applies to: LON fault manager control

Source: Vitodens 200-W B2HA service instructions, p. 37. Written in our own words; check the manual for your exact model.

Run the actuator test

Boiler · Vitocrossal 200 CI2

Forces outputs to check actuators. When the test starts, all actuators are disabled and valves move to their central position. Functions stay active for 30 seconds. If a function cannot run because of the current process, it is interrupted and a prompt appears. If max heating output is restricted by parameter 596.0, the boiler is skipped in the test.

  1. Enter the service menu and select Actuator test.
  2. Confirm the security prompt.
  3. Select the required group.
  4. Tap the required actuator function. Several can run at once.
  5. Confirm if prompted. Functions run for 30 seconds.
  6. End the actuator test with the exit option.

Applies to: Vitocrossal 200 CI2 service menu

Source: Vitocrossal 200 CI2 Service Instructions, p. 55-56. Written in our own words; check the manual for your exact model.

Run the operating conditions scan

Boiler · Vitotronic 200-H

Reads live operating values such as outdoor, return, supply and room temperatures, plus clock data.

  1. Press the scan button (symbol not legible in source).
  2. Select the operating condition with the arrow buttons.
  3. Press OK to view it.
  4. To leave, press the button shown in the source (symbol not legible).

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 27. Written in our own words; check the manual for your exact model.

Run the relay test

Boiler · Vitotronic 200-H

The relay test switches individual outputs on and off so you can confirm the wiring and the mixing valve actuator.

  1. Press the 9 button and the second button (symbol not legible in the source) together for about 2 seconds to start the relay test.
  2. Use the up or down arrow to select the relay output.
  3. Press OK to finish the relay test.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 18. Written in our own words; check the manual for your exact model.

Run the temperatures and quick scan

Boiler · Vitotronic 200-H

Use this to read live temperatures and software or device data from the control unit.

  1. Press 9 and r together for about 2 seconds.
  2. Select the scan you need with the arrow buttons.
  3. Press OK to view it.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 25. Written in our own words; check the manual for your exact model.

Safety temperature limiter (FHL) test

Boiler · Versatronik 200

The FHL test checks the safety temperature limiter of the heat generator.

  1. Start the FHL test with the F button.
  2. Use the shaft encoder to find the boiler and select it with the F button.
  3. Read the heat generator temperature on the display.
  4. Press and hold the Start button until the STL activates; the burner runs, all pumps stop and all mixing valves close.
  5. Watch the temperature on the display during the test.

Applies to: Heat generator with safety temperature limiter

Source: Versatronik 200 installation and operating manual, p. 164. Written in our own words; check the manual for your exact model.

Scan central heating time phases at a glance

Boiler · Vitocontrol-S, VD2/CT3/CM2

Shows all preset central heating phases on a time slot graphic (0 to 24 h scale).

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the two time program buttons together; the preset phases appear on the time slot graphic.
  4. Close the hinged cover.

Applies to: Central heating time program

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Scan current information (300-K)

Boiler · Vitotronic 200 and 300-K

The extended menu groups information as General, Heating circuit 1, 2 and 3, DHW, Solar and Reset data. Named heating circuits show their custom name.

  1. Open the extended menu.
  2. Select "Information".
  3. Select the group.
  4. Select the required scan.

Applies to: Vitotronic 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Scan current system information

Boiler · Vitotronic 300-K

Groups available in the main menu: General, Burner, Heating circuit 1, 2 and 3, DHW, Solar energy, Reset data and Service address. Available groups depend on the connected components and settings. Detailed scan options are in the Scanning options chapter (p. 32).

  1. Press Menu, then Information.
  2. Select the required information group.

Applies to: Control

Source: Vitotronic 300-K MW2C operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Scan groups on Vitotronic 300-K

Boiler · Vitotronic 300-K MW1B

Scan values are split into groups. If heating circuits have names, the name is shown instead of HC1 to HC3.

  1. Open the extended menu.
  2. Select Information.
  3. Select the group: General, Heating circuit 1, Heating circuit 2, Heating circuit 3, DHW, Solar or Reset data.
  4. Select the required scan value.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Scan heating time cycles on a time line

Boiler · Vitotronic 300

Shows the preset heating cycles as a time line graphic without changing them.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the heating time program button and the 'Central Htg.' button together; the time line appears.
  4. Close the hinged cover.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Scan operating conditions (Vitotronic 100)

Boiler · Vitotronic 100 GC1

Scans live readings from the Vitotronic 100 display. Which values show depends on the system layout. Scan readings include boiler temperature, sensor 17A and 17B temperatures, flue gas temperature, burner run hours for stage 1 and 2, and burner starts. The run hours and burner starts can be reset to 0.

  1. Press the scan button.
  2. Select the required scan with the up or down button.
  3. Press OK to view the value.
  4. Read the value. Flue gas and sensor 17A/17B readings only show when that sensor is fitted.
  5. To reset run hours or burner starts, use the reset button shown on the scan screen.

Applies to: Vitotronic 100, GC1

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 88. Written in our own words; check the manual for your exact model.

Scan operating conditions (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1S

Scans status readings such as participant number, holiday program status, outdoor, boiler, sensor, DHW, supply and return temperatures, room temperature, time and date, output states, pump states, mixing valve state and language. Items shown depend on equipment level.

  1. Press the scan button.
  2. Select the required scan with the up or down button.
  3. Press OK to view the value.
  4. Check pump ON/OFF states, output states and mixing valve open/closed.
  5. Check the displayed position in percent for valve or output positions where shown.

Applies to: Vitotronic 300-K, MW1S

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 93. Written in our own words; check the manual for your exact model.

Scan operating data

Boiler · Vitotronic 200 and 300-K

Operating data can be read in six areas. Data for mixing valve circuits and solar only shows if those components are installed. A "- - -" reading means a sensor that was scanned is faulty.

  1. Enter the service level.
  2. Select "Diagnosis".
  3. Select the required group, for example General.
  4. Check the readings. Treat "- - -" as a faulty sensor.

Applies to: Vitotronic 200 and 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 28. Written in our own words; check the manual for your exact model.

Scan operating data by area

Boiler · Vitodens 200-W B2HB

Operating data is grouped in six areas under Diagnosis. Data for heating circuits with mixing valves and solar only shows when those components are installed. A sensor that is faulty shows - - - on the display.

  1. Enter the service level.
  2. Select Diagnosis.
  3. Select the required group, for example General, and read the values.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB service manual, p. 71. Written in our own words; check the manual for your exact model.

Scan operating data by group

Boiler · Vitocrossal 300 CA3B

Operating data is grouped (General, Cascade, DHW, Heating circuit, Solar energy). A sensor reading of - - - means that the scanned sensor is faulty.

  1. From the home screen tap Service and enter the viservice password.
  2. Select Diagnosis.
  3. Select the group, for example General, and read the values.
  4. If a value shows - - -, check that sensor and its wiring.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 117. Written in our own words; check the manual for your exact model.

Scan operating status information

Boiler · Vitotronic 200

Shows the operating status data for the selected heating circuit. Items depend on the system equipment and coding. Includes holiday program dates, outdoor, supply, boiler, DHW, flue gas, return and room temperatures, burner operating hours, number of burner starts, fuel consumption, time, date, and pump and mixing valve status. Burner hours, starts and fuel consumption can be reset after maintenance.

  1. Select the heating circuit with its selector button.
  2. Press the operating status button once to enter the scan mode.
  3. Scroll through the data with the up/down button.
  4. After maintenance, reset burner operating hours, number of burner starts and fuel consumption to zero with the button shown in the manual.
  5. Press the button shown in the manual to exit the scan mode.
  6. Press the language button to set the permanent display language if needed.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 31. Written in our own words; check the manual for your exact model.

Scan temperatures and boiler coding cards (diagnosis level)

Boiler · Vitotronic 200

Diagnosis level shows live values for the selected heating circuit. Items only appear if the matching sensor or remote is connected. Scan items: damped and current outdoor temperature, desired and current supply, boiler, DHW, return water and room temperatures, max and current flue gas temperature, boiler coding card, and scans 1 to 4.

  1. Select the heating circuit with its selector button.
  2. Press the two buttons together for about 2 seconds to enter the diagnosis level.
  3. Scroll through the values with the up/down button.
  4. Press the reset button shown in the manual to set damped outdoor temperature or max flue gas temperature to the current value.
  5. Press the button shown in the manual to exit the diagnosis level.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 28. Written in our own words; check the manual for your exact model.

Scan temperatures and operating data

Boiler · Vitotronic 100, GC1

Lets you read actual temperatures and run data. Only the values for connected sensors are displayed.

  1. Press the scan button. The first value appears on the display.
  2. Press the up/down button to step through the other values (see scanning table).
  3. Press the scan button again to exit. The display returns to the boiler temperature.

Applies to: Single-boiler and multi-boiler systems

Source: Vitotronic 100, GC1 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Scanning operating data (Diagnosis)

Boiler · Vitodens 200-W

Operating data can be scanned in six groups. Mixing valve and solar data only show if those components are installed. A dashed display '- - -' means a scanned sensor is faulty.

  1. Press OK and the second key together for about 4 seconds.
  2. Select 'Diagnosis'.
  3. Select the required group, e.g. 'General', and press OK and the second key together for about 4 seconds.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 73. Written in our own words; check the manual for your exact model.

Scanning operating data by group

Boiler · Vitodens 200-W

Operating data is grouped into six areas. Groups for mixing-valve heating circuits and solar only show values if those components are installed.

  1. Enter the service level.
  2. Select "Diagnosis".
  3. Select the required group, for example "General".

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA service instructions, p. 72. Written in our own words; check the manual for your exact model.

Scanning operating status values

Boiler · Vitotronic 100

Operating status values can be scanned in turn, showing temperatures, burner hours and starts. Some values only appear when the matching sensor or module is connected.

  1. Press the info button.
  2. Select the required status item with the up or down button.
  3. Press the scan button to start operating status scanning.
  4. Exit scanning when finished.

Applies to: Vitotronic 100 GC1 programming unit

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 97. Written in our own words; check the manual for your exact model.

Scanning system data on Vitocontrol-S

Boiler · Vitocontrol-S, VD2/CT3/CM2

Scan system values: participant number, holiday program with departure and return dates, outdoor temperature, boiler sequence, common supply temperature, boiler temperatures for boilers 1-4, flue gas temperature, sensors aJA and aJB, domestic hot water temperatures, supply temperature, room temperatures per heating circuit, time, date, outputs 20, 29 and 52, pump and mixing valve states, solar pump status and run hours, and LON equipment number. Only items with connected sensors or enabled functions appear.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button; the button lights up.
  3. Press the scan button; the Participant No. appears.
  4. Press the button(s) to scan the other data.
  5. Press the exit button to leave scanning mode; the display returns to the boiler temperature.
  6. Close the hinged cover.
  7. To scan the active heating program, party or energy saving mode, press the heating circuit selector button; the active program button lights up.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Scanning temperatures and burner data on Vitotronic 100 GC1

Boiler · Vitotronic 100, GC1

Scan actual temperatures and run data. Available items depend on the connected components. Burner hours and burner starts can be reset to 0.

  1. Open the hinged cover.
  2. Press the scan button; the first temperature appears.
  3. Press the button(s) to scan the other data.
  4. To reset burner hours or burner starts, press the button marked D while the value is shown.
  5. Press the exit button to leave scanning mode; the display returns to the boiler water temperature.

Applies to: Vitotronic 100, GC1 boiler controls

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Scanning temperatures and operating status

Boiler · Vitotronic 300

Read actual temperatures and operating status without changing any settings. Some items only appear when the related sensor, pump, output or function is installed or enabled. The manual's conditions for each item are printed out of order, so check the wiring and settings if an item is missing. Items include outdoor, boiler, flue gas, sensor 17A and 17B, DHW temperatures, supply and room temperature, burner hours and starts, fuel consumption, time and date, burner and pump states, mixing valve position and language.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button; the button lights up.
  3. Press the scan button; the outdoor temperature appears first.
  4. Press the up or down arrow to scroll through the other values.
  5. Press the back or exit button to leave scan mode; the display returns to the boiler temperature.
  6. Close the hinged cover on the programming unit.

Applies to: Vitotronic 300 GW2 scan mode

Source: Vitotronic 300 GW2 operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Scanning the fault display

Boiler · Vitotronic 200-H

Faults show as a flashing fault symbol U. Scanning reveals the fault number so the contractor can prepare before the call.

  1. Press the troubleshooting key to scan the fault.
  2. Read the fault number (example: 1, 1, 8).
  3. Press acknowledgement to clear the message from the display.

Applies to: Vitotronic 200-H fault display

Source: Vitotronic 200-H operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Search for other stored faults

Boiler · Vitotronic 300

Other fault codes stored in the control can be called up from the fault display.

  1. Press the search button once.
  2. Use the up or down button to scroll through other stored fault codes.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 80. Written in our own words; check the manual for your exact model.

Service and diagnostic functions overview

Boiler · Vitotronic 200

Functions reached through button combinations on the control. Exact button symbols are not legible in this extract.

  1. Temperatures, boiler coding cards and scans: use the listed button combination and press to enter.
  2. Relay test: use the listed button combination and press to enter.
  3. Error history: use the listed button combination and press to enter.
  4. Operating status: press the operating status button immediately to view.
  5. Service scan: press when Service is flashing on the display.
  6. Fault search: press when Fault is flashing on the display.
  7. Display contrast: press the combination to darken, or the other combination to brighten the display.

Applies to: Vitotronic 200 KW2 control unit

Source: Vitotronic 200 Si service instructions, p. 24. Written in our own words; check the manual for your exact model.

Service due reminder limits

Boiler · Vitocrossal 300 CA3B

The service reminder is driven by coding 21 and 23 in the Boiler group. When either limit is reached, Service and the service symbol appear on the display.

  1. Set the hours-run limit in coding 21 in the Boiler group.
  2. Set the time interval limit in coding 23 in the Boiler group.
  3. When a limit is reached, the Service message and symbol will show.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 120. Written in our own words; check the manual for your exact model.

Service level overview

Boiler · Vitotronic 300

Button combinations to reach the service functions.

  1. Temperatures, boiler coding cards and scans: menu and reset buttons together for about 2 seconds, exit with OK (p. 73).
  2. Relay test: menu and OK together for about 2 seconds, exit with OK (p. 68).
  3. LON participant check: w and OK together for about 2 seconds, exit by pressing w and OK for about 1 second (p. 66).
  4. Operating status information: press the status button (p. 77).
  5. Service scan (when Service is flashing): press OK (p. 74).

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 72. Written in our own words; check the manual for your exact model.

Service level summary (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1S

Quick list of service functions on the Vitotronic 300-K and how to enter and exit each one. Button symbols on the source page are partly garbled, so check the button layout on the unit or the manual before use.

  1. Adjust display contrast: press OK and + together to darken, or OK and - together to lighten.
  2. Participant check: hold the flagged buttons together for about 2 seconds; exit by pressing them for about 1 second (page 76).
  3. Relay test: hold the flagged buttons for about 2 seconds, then press OK; exit with OK (page 81).
  4. Boiler sequence: hold the flagged buttons for about 2 seconds, then press OK; exit with OK (page 81).
  5. Temperatures and scans: hold the flagged buttons for about 2 seconds, then press OK (page 91).
  6. Operating status: press the flagged button to enter and exit (page 93).
  7. Maintenance requirement indication: press OK when maintenance flashes (page 94).
  8. Troubleshooting: press the flagged button to enter, then OK (page 99).
  9. Error history: hold the flagged buttons for about 2 seconds, then press OK (page 105).
  10. Reset codings to factory settings: hold the flagged buttons for about 2 seconds, press the flagged button, then confirm with OK (page 147).
  11. Coding 1: hold the flagged buttons for about 2 seconds; exit after about 1 second (page 148).
  12. Coding 2: hold the flagged buttons for about 2 seconds, confirm with OK; exit after about 1 second (page 151).

Applies to: Vitotronic 300-K, MW1S

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 90. Written in our own words; check the manual for your exact model.

Service menu overview

Boiler · Vitodens 200-W B2HA

Service level menus: Diagnosis, Actuator test, Coding level 1, Brief scan, Coding level 2, Fault history, Service functions, Terminate service, plus General, Heating circuit 1/2/3, DHW, Solar, Reset data, Participant check, Service PIN, Service reset, Filling, Venting, Maximum output, Enter Vitocom PIN code and Multi-boiler system.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 66. Written in our own words; check the manual for your exact model.

Service messages on Vitotronic 100

Boiler · Vitotronic 100 GC1B

A flashing service symbol means the system is due for service. Service can be triggered by time (e.g. 12 months), flue gas temperature (e.g. 302° F / 150° C, GC1B only) or burner hours (e.g. 2500 hr). Vitotronic 300-K has no service interval, so it shows no service message.

  1. Notify your heating contractor of the service message.
  2. Acknowledge the message by pressing OK.
  3. If the service is postponed, the message comes back after 7 days.
  4. To view an acknowledged service message again, press and hold OK for about 4 seconds.

Applies to: Vitotronic 100 GC1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Service operation display (j)

Boiler · Versatronik 200

In service operation the boiler set point is coded 8, the pump runs, and the mode turns off after 15 minutes.

Applies to: Lago FB remote control

Source: Versatronik 200 installation and operating manual, p. 57. Written in our own words; check the manual for your exact model.

Setting lower and upper heating output for combustion testing

Boiler · Vitodens 100-W, B1HE, B1KE

Forces the burner to run at minimum or maximum heating output through the burner modulation menu.

  1. Open the service menu with the button combination on page 60.
  2. Select Burner mod. set value and press OK.
  3. Select Minimum heating output and press OK. The burner runs at low output.
  4. Select Maximum heating output and press OK. The burner runs at high output.
  5. Ensure adequate heat transfer while testing.

Applies to: Vitodens 100-W

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words; check the manual for your exact model.

Simulate a room thermostat call on the R-Stat input

Boiler · Versatronik 10.WB1

The manual says a room thermostat call is made by shorting the R-Stat terminals X3.1 and X3.2. This is the normal-mode way to start the space heating pump and boiler call for testing.

  1. Short terminals X3.1 and X3.2 (R-Stat) to simulate a room thermostat call.
  2. Confirm the space heating pump output turns on.
  3. Remove the short to end the call.

Applies to: Versatronik 10.WB1 space heating call

Source: Versatronik 10.WB1 installation and operating manual, p. 23. Written in our own words; check the manual for your exact model.

Start emissions test mode

Boiler · Vitodens 100-W B1HE/B1KE

For certified contractors only. Test mode is started from the service menu and is best done during the heating season.

  1. Call up the home screen and open the menu.
  2. Select Settings, then tap OK.
  3. Select Service, then tap OK.
  4. Select Test mode, then select Yes and tap OK.
  5. Select Test mode again and tap OK.
  6. Select Start and tap OK.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Start filling or venting function

Boiler · Vitodens 200-W B2HA

Enter the service functions to start the Filling or Venting function. The second button symbol is not shown in the text.

  1. Press OK and the second button shown in the manual at the same time for about 4 seconds.
  2. Select Service functions.
  3. Select Filling (for fill) or Venting (for air purge).
  4. End the function by pressing OK or the arrow button.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 13. Written in our own words; check the manual for your exact model.

Start the relay test

Boiler · Vitotronic 100 GC1, Vitotronic 300-K MW1S

Enter the relay test to switch each output on or off for checking wiring and actuators. The button symbol for the first key is missing in this text; check the manual's button graphic before use.

  1. Press the 9 button and the second button shown in the manual together for about two seconds.
  2. Select the relay output with the up or down arrow.
  3. Press OK to activate the output.
  4. Press OK again or exit the test to return to normal operation.

Applies to: Vitotronic 100 GC1 and Vitotronic 300-K MW1S

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 80. Written in our own words; check the manual for your exact model.

Start the venting program

Boiler · Vitodens 200-W

Service menu access for the venting program used to purge the boiler and system.

  1. Press OK and the second button shown together for about 4 seconds.
  2. Select 'Service functions'.
  3. Select 'Venting'.
  4. Confirm that the venting function is enabled.
  5. Press OK or the back button to end the venting function.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 17. Written in our own words; check the manual for your exact model.

Temperatures and brief scans (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1S

Shows live temperatures, outputs and states. Items shown depend on what is connected, such as sensors, DHW tank sensors, supply temperature sensor and remote control.

  1. Hold the flagged buttons together for about 2 seconds.
  2. Select the required scan with the up or down button.
  3. Press OK to view it.
  4. Read the outdoor temperature (actual and dampened), boiler sequence, boiler output percentage and integral, boiler temperatures 1 to 4, sensor 17A and 17B values, DHW and supply temperatures, and room temperature.
  5. To reset the dampened outdoor temperature to the actual value, use the reset button shown on the scan screen.
  6. Negative integral values mean start-up integral, positive values mean shutdown integral.

Applies to: Vitotronic 300-K, MW1S

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 91. Written in our own words; check the manual for your exact model.

Test and manually adjust the mixing valve motor

Boiler · Vitotronic 300-K MW1S

Use the control unit relay test to run the mixing valve open and closed. For manual adjustment, disengage the motor drive before moving the valve by hand.

  1. Run the relay test on the control unit so the mixing valve moves open and closed.
  2. To adjust by hand, lift the motorized lever up.
  3. Unhook the mixing valve handle.
  4. Remove plug A from the motor.
  5. For 24V actuators, follow the instructions supplied with the actuator.

Applies to: Mixing valve motor 7133 390

Source: Viessmann Vitotronic 300-K MW1S installation and service instructions, p. 128. Written in our own words; check the manual for your exact model.

Test relay outputs (actuator test)

Boiler · Vitodens 222-F

Use the actuator test to switch individual outputs on and check them.

  1. Enter the service level.
  2. Select 'Actuator test'.
  3. Select the output to test and check that it switches as listed in the actuator test table.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F B2TB service instructions, p. 72. Written in our own words; check the manual for your exact model.

Test the fixed high limit (FHL)

Boiler · Vitotronic 200

Functional check of the fixed high limit. Boiler and burner must be watched the whole time.

  1. Deactivate low-temperature floor heating, with or without mixing valves, before starting.
  2. Isolate attached DHW tanks and confirm the expansion tank will take the water expansion.
  3. Let boiler water cool to 140 °F / 60 °C before activating any heat distribution system.
  4. Press and hold the FHL test switch. Never tape or otherwise hold it in place.
  5. The adjustable high limit is bypassed, so the burner runs until the fixed high limit trips.
  6. When the burner shuts off, release the test switch.
  7. Wait until boiler water is 27 °F / 15 °C below the selected safety temperature, then press the reset button.

Applies to: Fixed high limit

Source: Vitotronic 200 service instructions, p. 66. Written in our own words; check the manual for your exact model.

Test the fixed high limit with the test button

Boiler · Vitotronic 100 GC1

The test button on the fixed high limit checks that it works. The full test description is on page 72 of the manual.

  1. Press the test button on the fixed high limit.
  2. Check that the limit shuts the boiler down with lockout.
  3. Reset the limit manually after the test.

Applies to: Fixed high limit

Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 121. Written in our own words; check the manual for your exact model.

Test the high limit safety cut-out

Boiler · Vitodens 100-W B1HE/B1KE

Checks the high limit safety cut-out from the service menu. Settings and functions in the service section are covered in the installation and service instructions.

  1. Call up the home screen and open the menu.
  2. Select Settings, then tap OK.
  3. Select Service, then tap OK.
  4. Select Yes, then tap OK.
  5. Select Test high limit safety cutout, then tap OK.
  6. Select Yes and tap OK.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Testing the mixing valve motor with the relay test

Boiler · Vitocontrol-S VD2/CT3/CM2

The control unit relay test drives the mixing valve open and closed.

  1. Start the relay test on the control unit.
  2. Confirm the mixing valve moves to open and then to close.

Applies to: Mixing valve circuit extension kit

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 144. Written in our own words; check the manual for your exact model.

Update LON participants

Boiler · Vitotronic 200-H

Only possible when all users are connected and the control unit is programmed as fault manager (code 79:1). The participant list is updated after about 2 minutes.

  1. Press the w key and the second key together for about 2 seconds to start the participant check.
  2. Press D to update the participant list.
  3. Wait about 2 minutes for the update to complete.

Applies to: Vitotronic 200-H LON fault manager

Source: Vitotronic 200-H installation and service instructions, p. 13. Written in our own words; check the manual for your exact model.

Update the LON participant list

Boiler · Vitotronic 300-K MW1S

The participant list can only be updated when all participants are connected and this control is the fault manager (coding 79 : 1, factory default). Only one Vitotronic in a system can be the fault manager. Button symbols are not clearly printed here.

  1. Press the two buttons shown on the page together for about 2 seconds to start the participant check.
  2. Press the button shown on the page.
  3. Wait about 2 minutes. The participant list is updated and the check is complete.

Applies to: Vitotronic 300-K, MW1S

Source: Viessmann Vitotronic 100/300-K installation and service manual, p. 74. Written in our own words; check the manual for your exact model.

Using the help text

Boiler · Vitocrossal 300

The programming unit has context-sensitive help that explains the selected menu.

  1. If the screen saver is active, press ? to open the short guide.
  2. From anywhere in the menu, hold the key until the standard menu appears, then press ?.

Applies to: Vitotronic 200 KW6B programming unit

Source: Vitocrossal 300 CU3A operating instructions, p. 13. Written in our own words; check the manual for your exact model.

Venting program

Boiler · Vitodens 200-W B2HA

The venting program runs the circulation pump on and off in alternating 30-second periods over 20 minutes. The burner stays off during this program.

  1. Activate the venting program as described in Venting the heating system (not on these pages).

Applies to: Heating system venting

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 85. Written in our own words; check the manual for your exact model.

Verify or change fuel type (natural gas or LPG) in service mode

Boiler · Vitodens 100-W WB1B

Use the selector dials to enter the fuel setting while SERV is shown.

  1. Turn both selector dials to the centre position at the same time. SERV shows.
  2. Within 2 seconds turn selector dial tr counter-clockwise to O. A and the setpoint flash.
  3. Turn the other selector dial to set 0 for natural gas or 1 for LPG.
  4. Wait 15 seconds without touching the dials to save the setting.

Applies to: Gas type change

Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 59. Written in our own words; check the manual for your exact model.

View all DHW time cycles on the time line

Boiler · Vitotronic 300

Shows the preset DHW time cycles as a graphic time line without changing them.

  1. Open the programming unit cover.
  2. Press the heating circuit selector until it lights up.
  3. Press the two buttons shown in the manual at the same time to display the time line.
  4. Close the cover.

Applies to: DHW time program

Source: Vitotronic 300 GW2 operating instructions, p. 17. Written in our own words; check the manual for your exact model.

View and delete the fault memory (error history)

Boiler · Vitotronic 100 GC1

The control keeps the last 10 fault codes, numbered from the most recent. Use this to check for repeat faults.

  1. Press the two keys shown together for about 2 seconds to enter the error history.
  2. Scroll through the saved fault codes with the arrow keys; fault 1 is the most recent.
  3. To clear all saved codes, use the delete key.
  4. Press the exit key to leave the history.

Applies to: Vitotronic 100 GC1 with DBGU programming unit

Source: Vitotronic 100 GC1 installation and service instructions, p. 116. Written in our own words; check the manual for your exact model.

View error history

Boiler · Vitotronic 200

Opens the stored error history. The manual does not show the full procedure on these pages.

  1. Press the two buttons together as shown in the manual to open the error history.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 24. Written in our own words; check the manual for your exact model.

View fault memory

Boiler · Vitocrossal 300 CA3B

The last 10 faults are stored and can be read. The display times out after 20 seconds with no key press. The fault memory can show a cause even when no code is displayed for a non-lockout fault.

  1. Hold the S button for more than 2 seconds until the indicator flashes.
  2. Turn the dial until 4 shows under Service.
  3. Press S. A 4 shows under Status.
  4. Use Y or B to choose 1 Display fault codes, 2 Detail fault codes or 3 Clear fault memory.
  5. Press S to open the selected view.
  6. Use Y or B to scroll through the fault codes.

Applies to: CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 27. Written in our own words; check the manual for your exact model.

View sensor and relay information in Service mode

Boiler · Versatronik 200

Service mode gives access to test and information screens for the circuits. The manual prints the word User on the selection key, which is likely meant to be Service; confirm on site.

  1. Press the Home button to show the Main Menu.
  2. Turn the rotary dial until Service is shown on the screen.
  3. Press the key beside the word shown to select the menu option.
  4. Select the circuit you want to view tests or information for.
  5. Press Cancel to leave the current screen.

Applies to: Versatronik 200 service mode

Source: Versatronik 200 Installation and Operating Manual, p. 159. Written in our own words; check the manual for your exact model.

View solar energy yield graph

Boiler · Vitotronic 300-K MW1B

Shows solar energy yield for the past 7 days as a graph. The flashing line marks the current day, which is not finished yet.

  1. Open the extended menu.
  2. Select Solar energy.

Applies to: Vitotronic 300-K MW1B with solar thermal system

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

View the burner fault memory

Boiler · Vitocrossal 300 CA3B Dual Fuel

The last 10 faults are stored and can be scrolled. The display closes on its own if no key is pressed for 20 seconds.

  1. Hold S for more than 2 seconds until the indicator flashes.
  2. Press Y until '4' shows under Service.
  3. Press S. '4' shows under Status.
  4. Press Y or B to choose '1' (display fault codes) or '2' (detail fault codes).
  5. Press S to open the selected view.
  6. Press Y or B to scroll through the fault codes, from most recent to oldest.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 27. Written in our own words; check the manual for your exact model.

View the fault history

Boiler · Vitotronic 300 GW6B

The 10 most recent faults are stored, including those already fixed, sorted by date. Fault history can be cleared.

  1. From the home screen, tap Menu, then Service.
  2. Enter the viservice password.
  3. Tap History of faults.
  4. Tap ? in a fault to see more information.
  5. Tap Reset to delete the list.

Applies to: Vitotronic 300 GW6B boiler control unit

Source: Vitotronic 300 GW6B installation and service instructions, p. 62. Written in our own words; check the manual for your exact model.

View the fault history (last 10 faults)

Boiler · Vitodens 200-W

The control keeps the 10 most recent faults, including resolved ones, sorted by date. Use this to see what happened before a call.

  1. Press OK and the second service button together for about 4 seconds.
  2. Select "Fault history".
  3. Select "Display?" and press OK to read each fault code.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Viessmann Vitodens 200-W B2HB service instructions, p. 75. Written in our own words; check the manual for your exact model.

View the fault memory (error history)

Boiler · Vitocontrol-S VD2/CT3/CM2

The control unit stores the last 10 fault codes. Each entry shows its order, with 1 being the last fault. Saved codes can be deleted all at once. Button symbols on the printed page are not readable, so the key names are not given.

  1. Press the two keys together for about 2 seconds to open the error history.
  2. Scroll through the entries with the arrow keys to view the individual fault codes.
  3. Press the marked key to delete all saved fault codes.
  4. Press the marked key again to exit.

Applies to: Vitocontrol-S VD2/CT3/CM2 with Vitotronic 100 GC1

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 122. Written in our own words; check the manual for your exact model.

Viewing all time phases at a glance

Boiler · Vitotronic 200-H

Shows the preset time phases on a time-slot graphic without changing them.

  1. Open the hinged cover on the programming unit.
  2. Press the heating time program button and the scan button together.
  3. The preset phases appear on the time-slot graphic.
  4. Close the hinged cover.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Viewing and clearing the fault memory (error history)

Boiler · Vitotronic 300-K MW1S

The control keeps the last 10 fault codes. Each one is shown with its order of occurrence.

  1. Press the two buttons shown on page 105 together for about 2 seconds.
  2. Scroll through the codes with the up or down button. Code 1 is the last fault.
  3. To delete all saved codes, use the delete button shown on page 105.
  4. Press the button shown on page 105 to exit.

Applies to: Vitotronic 300-K MW1S

Source: Vitotronic 300-K MW1S installation and service instructions, p. 105. Written in our own words; check the manual for your exact model.

Viewing ionization current

Boiler · Vitocrossal 200 CM2

Shows the flame ionization current during operation. The reading is shown in 1/10 μA.

  1. Press S for longer than 2 seconds until the menu item flashes.
  2. Scroll with Y until 5 shows under Service, then press S.
  3. Scroll with Y until 3 shows under Service, then press S. The ionization current shows under Service during operation (e.g. 30 = 3.0 μA).

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 45. Written in our own words; check the manual for your exact model.

Re-enter remote control configuration

General · Vitotrol 300A

Configuration can be opened again by holding the two buttons together. The manual's button icons did not come through, so confirm the exact keys on the unit.

  1. Press the two keys shown on the unit together and hold for about 4 seconds.
  2. Go through the configuration steps again.

Applies to: Vitotrol 300A

Source: Vitotrol 300A installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Actuator test menu (code 45)

Heat pump · Vitocal 100-AW

Service menu function that runs the actuator test on the indoor unit (IDU). Requires an access code.

  1. Open the Service menu and select the actuator test.
  2. At the access code prompt, turn the navigation dial to 45 and press the dial to confirm.
  3. Scroll through the test list with the dial and press to select each test.
  4. When finished, select 'End' to return to the Service menu.
  5. To leave the code screen without entering a code, hold the dial or wait for the display to return to the main screen.

Applies to: Indoor unit (IDU) service menu

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 64. Written in our own words; check the manual for your exact model.

Forced defrost

Heat pump · Vitocal 100-S

Manually starts a defrost cycle for testing.

  1. Press and hold AUTO/COOL for 5 seconds to start forced defrost.
  2. The indoor fan stops and the defrost lamp lights.
  3. Use the remote to turn the unit off to end normal defrost.
  4. To leave forced defrost, press and hold AUTO/COOL for 5 seconds again.

Applies to: DLCSRB units with remote control

Source: DLCSRB Service Manual, p. 21. Written in our own words; check the manual for your exact model.

Forced operation (TOUCH button)

Heat pump · Vitocal 100-S

Runs the unit in forced auto or forced cooling without the remote. General protections and remote control stay active.

  1. With the unit off, press TOUCH once to start FORCED AUTO at 75.2°F (24°C).
  2. Press TOUCH again within 5 seconds to start FORCED COOLING.
  3. In FORCED COOLING the compressor runs at F2 and the fan runs at breeze speed for 30 minutes, then the unit goes to AUTO at 75.2°F (24°C).
  4. Press TOUCH to turn the unit off from any forced mode.

Applies to: DLCSRB indoor high-wall units

Source: DLCSRB Service Manual, p. 22. Written in our own words; check the manual for your exact model.

Heat pump module operating conditions (code 65)

Heat pump · Vitocal 100-AW

The Heat Pump Module menu shows heat pump operating conditions and the defrost parameters.

  1. Open the Heat Pump Module menu.
  2. When prompted, turn the navigation dial to code 65 and press to confirm.
  3. View the operating conditions.
  4. Choose End to return to the Service menu.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 64. Written in our own words; check the manual for your exact model.

Heat pump operating conditions view (code 65)

Heat pump · Vitocal 100-AW

Service/Configuration menu item that shows live heat pump operating conditions. Requires an access code.

  1. Open the Service/Configuration menu and select Heat Pump Module.
  2. At the access code prompt, turn the dial to 65 and press to confirm.
  3. Scroll through the readings with the dial and press to select.
  4. Select 'End' to return to the Service menu when done.

Applies to: Heat pump module (outdoor unit data)

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 64. Written in our own words; check the manual for your exact model.

Indoor unit actuator test (code 45)

Heat pump · Vitocal 100-AW

The Service menu gives access to the actuator test function for the indoor unit.

  1. Open the Service menu.
  2. When prompted, turn the navigation dial to code 45 and press to confirm.
  3. Use the actuator test as needed.
  4. Choose End to return to the Service menu.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 64. Written in our own words; check the manual for your exact model.

Outdoor unit point check function (press count readout)

Heat pump · Vitocal 100-S

The outdoor unit display can step through 19 data points by repeated presses of the check function. Press 00 is normal display. The full readout list is in the setting table on the next item.

  1. Use the outdoor unit check function. Press it the number of times shown in the readout table to select the data.
  2. Press 00 (normal display) to return to running frequency, running state or malfunction code.

Applies to: DLCLRC outdoor unit

Source: DLCLRC Service Manual, p. 18. Written in our own words; check the manual for your exact model.

Outdoor unit point check function (SW1)

Heat pump · Vitocal 100-S

Push SW1 on the outdoor PCB while the unit runs. The display cycles through live data for each press. Press 00 returns to normal display.

  1. Press SW1 on the outdoor PCB to step through the displayed values.
  2. Read the value for the needed point (see the point check table).
  3. Press 00 to return to normal display of running frequency, running state or fault code.

Applies to: DLCURA outdoor unit PCB

Source: DLCURA Service Manual, p. 21. Written in our own words; check the manual for your exact model.

Point check (information enquiry)

Heat pump · Vitocal IND-O

Step through the unit's live readings from the remote or display. Each item name shows for about 2 seconds, then the value shows for about 25 seconds.

  1. Press LED DISPLAY or AIR DIRECTION to move to the next or previous item.
  2. Read the item name, then the value as listed in the point check table.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH service manual, PDF p. 11, 12. Written in our own words; check the manual for your exact model.

Reactor resistance check and S-line measuring points

Heat pump · Vitocal IND-A

Use a multimeter to check the reactor with the capacitor disconnected. A good reactor reads around zero ohms; otherwise it has failed. For the S-line DC voltage test, the red probe goes to 2 (L2 or S) and the black probe goes to 3 (N or S). Normal running shows alternating positive and negative values. A constant positive value means an outdoor fault; no change means an indoor fault.

  1. Disconnect the reactor from the capacitor and measure its resistance.
  2. Replace the reactor if the reading is not close to zero ohms.
  3. For the S-line test, connect the red probe to 2 (L2/S) and the black probe to 3 (N/S).

Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK

Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 19-20. Written in our own words; check the manual for your exact model.

Read the Screen 1 live data columns

Heat pump · Vitocal 100-WA

Screen 1 updates once per second. The column order is fixed, so read the sensor and output values in that order when checking the unit.

  1. Check column 2 for the operating state (H, H RL, H RM, H MP).
  2. Check SH and EEV for superheat and expansion valve position.
  3. Check HP and LP (psi) for high and low side pressure.
  4. Check CL, CH, FC, HW, AR, AS, LI and LO for compressor, freeze, tank, air and loop temperatures.
  5. Check column 17 (LFL) for gas percentage or a sensor error code.
  6. Check C, F and W for compressor, fan and water speed in percent of full speed.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 46-47. Written in our own words; check the manual for your exact model.

Read live data with the outdoor check button (SW1)

Mini split · Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor

Each press of SW1 steps through a value on the outdoor display.

  1. Press 1 = number of indoor units talking. 2 = mode (0 off, 1 fan, 2 cool, 3 heat, 4 forced cool, A forced defrost).
  2. Presses 17-21 = T2B per zone, 22-26 = room temp per zone, 27-31 = coil temp per zone, 32 = T3, 33 = T4, 34 = discharge temp.
  3. Press 45 (all sizes) = last fault or protection (00 = none). See the check switch table for the full list; the 18K board uses a slightly different order.

Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)

Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Tables 25-26 p.29-31. Written in our own words; check the manual for your exact model.

Run the automatic wiring / piping correction

Mini split · Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor

The outdoor unit can find and fix crossed wiring vs piping ports by itself.

  1. Outdoor temperature must be above 41 F (5 C). Indoor units do not need to be running.
  2. Hold CHECK (SW1) on the outdoor board about 6 seconds until CE shows (FA may show first, keep holding).
  3. Indoor units go to 76 and the compressor runs for about 5-10 minutes.
  4. When CE changes to 00 it is done. Set each indoor unit back with its remote (they stay at 76).

Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)

Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Automatic Wiring/Piping Correction p.6. Written in our own words; check the manual for your exact model.

Enter and exit Inquiry Mode

Mini-split · DLFSHC

Inquiry Mode shows live sensor and operating values on the indoor display. Codes 0 to 30 are read with the UP and DOWN arrows. Each code shows on the indoor display about 1 second after access. Press OK to send.

  1. Press and hold the On/Off and Fan buttons together for 8 seconds to enter Inquiry Mode.
  2. Press UP or DOWN to step through codes 0 to 30.
  3. Press and hold On/Off and Fan together for 2 seconds to exit.
  4. If no button is pressed, the remote stays in Inquiry Mode for 1 minute.

Applies to: Remote controller and indoor display

Source: DLFSHC service manual, p. 13. Written in our own words; check the manual for your exact model.

Enter and exit Inquiry Mode on the remote

Mini-split · Vitocal 100-S

Inquiry Mode shows live unit readings on the indoor unit display. The remote stays in this mode for 1 minute with no button press. Each code from 0 to 30 is selected with the UP or DOWN arrow. Press OK to send the value to the indoor unit as well.

  1. Press and hold the On/Off and Fan buttons together for 8 seconds to enter Inquiry Mode.
  2. Press UP or DOWN to step through codes 0 to 30. Wait about 1 second for the reading to show on the indoor display.
  3. Press and hold On/Off and Fan together for 2 seconds to exit.

Applies to: DLCSRB outdoor units with remote control

Source: DLCSRB service manual, p. 24. Written in our own words; check the manual for your exact model.

Exit engineer mode

Mini-split · Vitocal 100-S, DLCURA

Engineer mode ends in two ways: by a key combination, or automatically after a period with no key presses.

  1. In engineer mode, press On/Off and Air speed together for 2 seconds.
  2. If no valid key is pressed for 60 seconds, engineer mode ends by itself.
  3. In a channel 1 to 30 setting, press On/Off to go back to the previous engineer mode screen.

Applies to: DLCURA 18-60 indoor/outdoor units

Source: Viessmann DLCURA service manual, p. 24. Written in our own words; check the manual for your exact model.

Forced defrosting mode

Mini-split · DLFSHC

Forced defrost runs the defrost cycle manually. The indoor fan stops and the defrost lamp lights.

  1. Press and hold AUTO/COOL for 5 seconds to enter Forced DEFROSTING.
  2. Use the remote controller to exit and turn the unit off to stop normal defrosting.
  3. To exit Forced DEFROSTING, press and hold AUTO/COOL for 5 seconds again.

Applies to: Indoor unit with AUTO/COOL button

Source: DLFSHC service manual, p. 12. Written in our own words; check the manual for your exact model.

Forced operation with the remote (TOUCH button)

Mini-split · DLFSHC

Forced operation runs without the remote. General protections and the remote remain active during forced operation.

  1. With the unit off, press TOUCH once to start Forced AUTO.
  2. Press TOUCH again within 5 seconds to start Forced COOLING.
  3. In any forced mode, press TOUCH to turn the unit off.

Applies to: Indoor unit with TOUCH button

Source: DLFSHC service manual, p. 12. Written in our own words; check the manual for your exact model.

MANUAL button operation without the remote

Mini-split · Vitocal IND-F

The MANUAL button on the unit runs it when the remote is lost, damaged or out of batteries. Each press changes the mode.

  1. Press MANUAL once to run AUTO mode (heat or cool).
  2. Press MANUAL twice to enter TEST mode, which runs COOLING for 30 minutes and then changes to AUTO.
  3. Press MANUAL three times to turn the system off.
  4. Note the preset conditions: set point 76°F (24°C), fan speed AUTO, discharge direction preset for COOL or HEAT.

Applies to: Indoor unit MANUAL button

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 7. Written in our own words; check the manual for your exact model.

Manual operation button presses (no remote)

Mini-split · DLFSDAH, DLFLDAH

Use the MANUAL button when the remote is lost, damaged or out of batteries. One press runs AUTO (heat or cool). Two presses start TEST mode, which runs COOLING for 30 minutes and then goes to AUTO. Three presses turn the unit OFF.

  1. Press MANUAL once to run AUTO mode (heat or cool).
  2. Press MANUAL twice to start TEST mode: cooling for 30 minutes, then AUTO.
  3. Press MANUAL three times to turn the unit off.

Applies to: Unit manual operation

Source: Viessmann Vitocal IND-D Owner's Manual, p. 7. Written in our own words; check the manual for your exact model.

Manual switch test operation at the indoor unit

Mini-split · Vitocal IND-C

Test the indoor unit with the manual button when the remote is not in use. Preset set point is 76°F (24°C), fan AUTO, discharge direction preset for COOL or HEAT.

  1. Open the indoor unit front panel.
  2. Press the manual switch once to energize the unit.
  3. Confirm preset set point 76°F (24°C), fan speed AUTO, and discharge direction preset for the mode.
  4. Press the manual switch twice more to turn the unit off after the test.

Applies to: DLFSCBH / DLFLCBH indoor unit

Source: DLFSCBH and DLFLCBH installation instructions, p. 15. Written in our own words; check the manual for your exact model.

Open the wired controller setup menu

Mini-split · DLFSDAH, DLFLDAH

Entering the SP/AF menu requires the system to be off. Only SP and AF are needed for airflow setup; the thermistor sub-menus are not for this task.

  1. With the system off, press and hold COPY for about 4 seconds.
  2. Use + or - to move between menu entries.
  3. Choose SP or AF only. Leave T1, T2, T2b, T3 and T4 alone.

Applies to: Wired controller KSACN0701AAA

Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, p. 14. Written in our own words; check the manual for your exact model.

Point check (information enquiry)

Mini-split · Vitocal IND-F

Press LED DISPLAY or AIR DIRECTION to step through the next item. Each item name shows for about 2 seconds, then its value shows for 25 seconds. Use the enquiry tables for names and value decoding.

  1. Press LED DISPLAY or AIR DIRECTION to enter information enquiry.
  2. Press again to move to the next item.
  3. Read the code name for about 2 seconds, then the value for about 25 seconds.
  4. Decode the value with the point check table.

Applies to: Indoor unit display and remote control

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 11-12. Written in our own words; check the manual for your exact model.

Run a test with the indoor unit MANUAL button

Mini-split · DLFSHC

Use the MANUAL button on the indoor unit to run a test without the remote control.

  1. Open the front panel of the indoor unit.
  2. Push MANUAL once to energise the unit. Preset is 76°F (24°C), fan AUTO, and discharge direction preset for the current cool or heat mode.
  3. Push MANUAL twice more to turn manual operation off after the test.

Applies to: Indoor unit

Source: DLFSHC installation instructions, p. 17. Written in our own words; check the manual for your exact model.

Reset & cancel

Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.

194°F manual reset high limit

Boiler · Vitotron 100 VLN2

The boiler has a 194°F manual reset safety high limit. The reset button is in the center of the device.

  1. Find the reset button in the center of the high limit device.
  2. Press the reset only after the cause of the over-temperature has been found and fixed.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 3. Written in our own words; check the manual for your exact model.

Acknowledge a fault

Boiler · Vitotronic 300-K, Vitotronic 200

An acknowledged fault moves to the menu and the connected central fault message facility switches off. If the fault is not fixed, it shows again the next day and the fault message facility restarts.

  1. Follow the on-screen prompts to acknowledge the fault.
  2. Fix the cause before the next day, otherwise the fault repeats and the fault relay restarts.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service, p. 71. Written in our own words; check the manual for your exact model.

Acknowledge a fault and check fault history

Boiler · Vitotronic 200-H

The red fault display flashes and 'Fault' with a 2 is shown when a fault is active. Acknowledged faults are kept in the fault history, which stores the 10 most recent faults including those already fixed. If an acknowledged fault is not fixed, it reappears the next day and the central fault message restarts.

  1. Press OK to show the fault code.
  2. Follow the instructions on the display to acknowledge the fault.
  3. To review past faults, press OK together with the second button for about 4 seconds, then select 'Fault history' and 'Display?'.
  4. Look up the code in the fault code table.
  5. If the fault remains, fix the cause before acknowledging it again.

Applies to: Vitotronic 200-H HK1B

Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 35. Written in our own words; check the manual for your exact model.

Acknowledge a fault and view active faults

Boiler · Vitodens 222-F

On a fault the red fault indicator flashes, '2' flashes on the display and 'Fault' is shown. Acknowledging moves the message to the standard menu and switches off any connected fault message facility. An unresolved fault is shown again the next day and the facility restarts.

  1. Follow the instructions on the display to acknowledge the fault.
  2. To see acknowledged faults, select 'Fault' in the standard menu; the current faults are listed.
  3. If the fault is not remedied, expect it to reappear the next day.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 73. Written in our own words; check the manual for your exact model.

Acknowledge a fault display

Boiler · Vitotronic 200-H

Faults show a fault symbol and a flashing fault code. An acknowledged fault comes back on the display if it is still present at 07:00 the next day.

  1. Scroll through active fault codes with the arrow buttons.
  2. Press the acknowledge button to clear the displayed fault.
  3. Fix the cause, because the fault returns if it is not removed by 07:00 the following day.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 28. Written in our own words; check the manual for your exact model.

Acknowledge a fault message

Boiler · Vitotronic 200-H

Acknowledging confirms the fault has been noted. If the fault is not corrected, it returns at 07:00 the next day and the red fault lamp keeps flashing until the fault is fixed.

  1. Open the programming unit cover and run fault search.
  2. Select Yes on the Acknowledge? prompt and confirm.
  3. Close the cover.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Acknowledge and recall active faults

Boiler · Vitodens 200-W

A fault shows as a flashing red fault indicator A, '2' flashing on the display and 'Fault' shown. Acknowledging moves the message to the standard menu. If an acknowledged fault is not fixed, the message comes back the next day.

  1. When a fault shows, follow the on-screen instructions to acknowledge it.
  2. To view active faults later, select 'Fault' in the standard menu. Current faults are listed.
  3. Fix the cause using the table for that code, then reset if the table calls for it.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB service instructions, p. 75. Written in our own words; check the manual for your exact model.

Acknowledge and recall faults on the Vitotronic 100 GC1

Boiler · Vitotronic 100 GC1

A red fault lamp flashes for every fault. Acknowledging hides the message on screen but the lamp keeps flashing, and the message returns the next morning if the fault is still present.

  1. Scroll through fault codes with the arrow keys.
  2. Acknowledge the displayed fault with the acknowledge key.
  3. To view acknowledged faults again, hold the key for about 2 seconds and select the fault with the arrow keys.
  4. Fix the cause before the following morning to stop the fault returning.

Applies to: Vitotronic 100 GC1 programming unit

Source: Vitotronic 100 GC1 installation and service instructions, p. 113. Written in our own words; check the manual for your exact model.

Acknowledge and reset maintenance messages (Vitotronic 100)

Boiler · Vitotronic 100 GC1

A maintenance message flashes once a set limit is reached. An acknowledged message can be shown again by holding the button for about 3 seconds. If maintenance is done before the message appears, the coding can be reset to clear the limits.

  1. Scan the maintenance messages with the up or down button.
  2. Press OK to acknowledge the message. The display clears.
  3. After maintenance, set coding 24 to 1 and then back to 0 to reset run-hour and period limits.
  4. If required, reset burner run hours and starts from the scan screen.
  5. If required, reset max flue gas temperature with the reset combination shown on page 86.
  6. If coding 24 is not reset, a new message appears on Monday morning.

Applies to: Vitotronic 100, GC1

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 89. Written in our own words; check the manual for your exact model.

Acknowledge and reset service message

Boiler · Vitodens 200-W

Acknowledging the message only clears it for now. An unreset message comes back the following Monday. Reset only after the service is done.

  1. Press OK to acknowledge the service message.
  2. After service is complete, press OK and the second key (symbol not legible in the text) together for about 4 seconds.
  3. Select 'Service functions'.
  4. Select 'Service reset'.
  5. Hours run and time interval restart at 0.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 37. Written in our own words; check the manual for your exact model.

Acknowledge and reset the service display

Boiler · Vitodens 200-W

The service display appears when the hours or time limits in coding 21 and 23 are reached. An acknowledged message that is not reset will come back on the following Monday. Resetting restarts the hours run and time interval at 0.

  1. Press OK to acknowledge the service message.
  2. After the service is done, press OK and the second button together for about 4 seconds.
  3. Select 'Service functions'.
  4. Select 'Service reset'.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 41. Written in our own words; check the manual for your exact model.

Acknowledge and reset the service message

Boiler · Vitocrossal 300

When a service limit from coding addresses 21 or 23 is reached, the red fault indicator flashes and Service shows on the display. An acknowledged service message that is not reset comes back the following Monday.

  1. Press OK to acknowledge the service message.
  2. After the service is done, press OK and the second button together for about 4 sec.
  3. Select Service functions, then Service reset.
  4. Hours run and the time interval restart at 0.

Applies to: Service interval reminder

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 82. Written in our own words; check the manual for your exact model.

Acknowledge fault display

Boiler · Vitocrossal 200 CI2

Acknowledging stops any connected central fault facility. If the fault is not fixed it comes back the next day at 07:00 and the central facility restarts.

  1. Tap the acknowledge button to acknowledge the fault display.
  2. Fix the fault. Otherwise it will reappear the next day at 07:00.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 58. Written in our own words; check the manual for your exact model.

Acknowledge maintenance display (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1S

The Vitotronic 300-K shows a maintenance message only when it is set as fault manager (coding 79:1) and a maintenance message is active on a connected Vitotronic 100.

  1. Press the scan button to open maintenance messages.
  2. Scan the messages with the up or down button.
  3. Press OK, then confirm the acknowledge prompt with OK.
  4. Acknowledge the matching message on the Vitotronic 100 (see page 89).
  5. If coding 24 on the Vitotronic 100 is not reset after maintenance, the message returns on the following Monday morning.

Applies to: Vitotronic 300-K, MW1S

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 94. Written in our own words; check the manual for your exact model.

Acknowledge maintenance messages

Boiler · Vitocrossal 200 CI2

An acknowledged maintenance message that was not reset comes back the following Monday.

  1. Open the maintenance message list.
  2. Acknowledge the maintenance message and confirm.
  3. Reset the service counter (see reset service tip) so the message does not return.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 57. Written in our own words; check the manual for your exact model.

Acknowledge service message

Boiler · Vitodens 200-W B2HB

A Service message shows when the burner hours or time interval limit is reached. The red fault indicator flashes.

  1. Press OK to acknowledge the Service message.
  2. If not reset, the message comes back on the following Monday.

Applies to: Vitotronic 200-H, Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB service instructions, p. 40. Written in our own words; check the manual for your exact model.

Acknowledging and recalling faults

Boiler · Vitotronic 100

A fault is acknowledged from the programming unit. The red fault light keeps flashing until the cause is fixed. An acknowledged fault that is not fixed within 24 hours shows up again on the display. Acknowledged faults can be recalled, and a fault from another LON unit shows as its participant number with EE for external fault.

  1. Press the acknowledge button to clear the displayed fault.
  2. To recall an acknowledged fault, press and hold the button for about 2 seconds.
  3. Use the up or down button to select the fault and view it.

Applies to: Vitotronic 100 GC1 programming unit

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 100. Written in our own words; check the manual for your exact model.

Automatic return to standard menu

Boiler · Vitodens 222-F

Two minutes after the last change, the display goes back to the standard menu. The screen saver starts after a few minutes without setting changes and dims the display.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 32-33. Written in our own words; check the manual for your exact model.

Basic setting D resets heating circuit values

Boiler · Vitotronic 200-H

Basic setting D returns all modified heating circuit values to the factory defaults. Use it only when you want to undo all custom settings.

  1. Select basic setting D.
  2. Confirm the reset.
  3. Re-enter any custom times and temperatures afterwards.

Applies to: Vitotronic 200-H HK1M

Source: Vitotronic 200-H operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Burner control unit fault and lockout reset

Boiler · Vitocrossal 300 CA3B Dual Fuel

If the fault lamp on the control unit is lit and the display on the burner control unit is blinking, reset the burner control unit with its reset button R. If the fault returns, the supply side of the combination gas valve may be blocked from gas pipe work. Air in the gas line can also cause a fault on first start-up.

  1. Press reset button R on the burner control unit.
  2. If the fault continues, check for a blocked supply side of the combination gas valve after gas pipe work.
  3. On first start-up with a fault from insufficient gas, ventilate the gas line again.
  4. Reset the burner control unit again.
  5. Allow for the 3 minute delay before the burner starts.

Applies to: CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 33. Written in our own words; check the manual for your exact model.

Burner fault on first start-up (air in gas line)

Boiler · Vitocrossal 300 CU3A

Air in the gas supply pipe, especially with LPG, can cause a burner fault on initial start-up. Ignition is direct spark.

  1. Wait about 5 seconds after the fault.
  2. Press the "R" button to reset the burner.
  3. The ignition sequence repeats automatically.

Applies to: Vitocrossal 300 CU3A initial start-up

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 18. Written in our own words; check the manual for your exact model.

Calling up an acknowledged fault message

Boiler · Vitotronic 100, GC1

An acknowledged fault stays retrievable. The fault message returns the next day if the fault is not fixed, and the red fault lamp keeps flashing until the fault is corrected.

  1. Press the fault button and hold for about 2 seconds; the fault code is displayed.
  2. Press the button(s) to view each fault code if several faults occurred together.
  3. Press the confirm button; the display returns to the boiler temperature.

Applies to: Vitotronic 100, GC1 boiler controls

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Cancel energy saving mode

Boiler · Vitotronic 300

Energy saving mode ends automatically when the preset program next switches to reduced room temperature. To cancel immediately, use the steps below.

  1. Press the heating circuit selector button.
  2. Press the energy saving button again; the button goes out.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Cancel or delete a holiday program

Boiler · Vitocrossal 300 CA3B

Deletes the holiday program by setting the return date equal to the departure date.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Holiday program.
  4. Set the return date to the same date as the departure date.
  5. Tap OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Cancel or delete the holiday program

Boiler · Vitocrossal 300

Use the extended menu path for 'Holiday program' under Heating to cancel or delete an active holiday program. The manual text is cut off after step 3, so the final step is not shown on these pages.

  1. Open the extended menu.
  2. Select 'Heating'.
  3. Select 'Holiday program'.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Cancel or erase the holiday program

Boiler · Vitotronic 200-H

Ends the holiday program before the return date or clears it during setup.

  1. Press j again.
  2. Confirm 'Erase? Yes'.

Applies to: Vitotronic 200-H holiday program

Source: Vitotronic 200-H operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Cancel party mode

Boiler · Vitotronic 300

Party mode ends automatically the next time the preset heating program switches to normal room temperature. To stop it immediately, use the button combination below.

  1. Press the heating circuit selector button.
  2. Press the party mode button again; the button goes out.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Cancel relay test

Boiler · Vitodens 100-W WB1B

The relay test ends on its own after 30 minutes if not cancelled.

  1. Switch the boiler OFF, then back ON to cancel the relay test.

Applies to: Burner test

Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 63. Written in our own words; check the manual for your exact model.

Cancelling a heating circuit assignment

Boiler · Vitotrol 200A

If the heating circuit assignment is removed, the coding address of that circuit must also be cleared at the control unit. Otherwise fault messages bC, bd or bE can appear.

  1. At the Vitotronic control unit, set coding address A0 for this heating circuit back to 0.

Applies to: Vitotrol 200A remote control with Vitotronic control unit

Source: Vitotrol 200A Installation, Operating and Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Cancelling a time phase change before saving

Boiler · Vitotronic 300-K

Use the cancel control to stop a time phase adjustment that has not been confirmed.

  1. Tap the cancel control in the time phase setting to cancel the adjustment or change in progress.
  2. Use the footer back button to go up one menu level if needed.

Applies to: Time program editing, Vitotronic 300-K

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 11. Written in our own words; check the manual for your exact model.

Cancelling Economy mode

Boiler · Vitocrossal 300 CU3A

Economy mode lowers the room temperature during standard heating mode. It cancels automatically when the time program switches to reduced heating, or when set to OFF. The displayed room temperature setting does not change.

  1. Open the extended menu, select Heating, select the circuit, then Economy mode.
  2. Set Economy mode to OFF to cancel it.

Applies to: Central heating heating circuits

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Cancelling party mode

Boiler · Vitotronic 200-H

Party mode ends automatically at the next scheduled switch to normal-temperature heating.

  1. To cancel immediately, press the party button again; the light goes off.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Cancelling the holiday program

Boiler · Vitocrossal 300 CA3B Dual Fuel

The holiday program is cancelled by setting the return date equal to the departure date.

  1. Go to Menu > Heating > required heating circuit > Holiday program.
  2. Set Return date to the same date as Departure date.
  3. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Changed value not saved if cover closed before Prog

Boiler · Versatronik COMO OT

If the cover is closed while the warning triangle is still showing, the new value is discarded. The control shows a caution that the change was not saved.

  1. After changing a value, press Prog before closing the cover to keep it.
  2. If the caution message appears, reopen the cover and re-enter the value.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT manual, p. 17. Written in our own words; check the manual for your exact model.

Clear a maintenance message on Vitocontrol-S

Boiler · Vitocontrol-S VD2/CT3/CM2

A maintenance message from a connected Vitotronic 100 GC1 is shown on the Vitocontrol-S display. Acknowledge it here, then clear it on the Vitotronic. Button symbols are not legible in the text layer, so the key names are left out.

  1. Open the maintenance display and scroll through the messages with the arrow keys.
  2. Select the acknowledge option and confirm that the display shows Acknowledge: Yes.
  3. Acknowledged messages can be shown again by holding the key for about 3 seconds.
  4. Acknowledge the maintenance message on the Vitotronic 100 GC1 (see page 107).
  5. If coding address 24 on the Vitotronic is not reset after maintenance, set it to 0 or the message returns the next Monday morning.

Applies to: Vitocontrol-S VD2/CT3/CM2 acting as fault manager (coding 79: 1)

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 112. Written in our own words; check the manual for your exact model.

Clear a service reminder

Boiler · Versatronik 200

Service reminders can be set by date or by operating hours. Clear them by setting the value back to Off or to 00.

  1. For a date reminder, set the year value to Off in the General/Service/Customer Service level.
  2. For an hours reminder, set the operating hours value to Off in the same level.
  3. To clear the displayed maintenance message, press F, set the repeat value to 00 and confirm with F button OK.

Applies to: Versatronik 200 service messages

Source: Versatronik 200 installation and operating manual, p. 164. Written in our own words; check the manual for your exact model.

Clear fault memory

Boiler · Vitocrossal 300 CA3B

Deletes all stored faults from the burner control unit.

  1. Hold the S button for more than 2 seconds until the indicator flashes.
  2. Turn the dial until 4 shows under Service.
  3. Press S. A 4 shows under Status.
  4. Turn the dial until 3 shows under Service.
  5. Press S. A 1 shows under Status and dEL under Service.
  6. Press S to confirm. A 1 under Service means deleted, 0 means it failed.
  7. Press S to return to the operating display.

Applies to: CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 27. Written in our own words; check the manual for your exact model.

Clear the burner fault memory

Boiler · Vitocrossal 300 CA3B Dual Fuel

Deletes all stored faults from the fault memory.

  1. Hold S for more than 2 seconds until the indicator flashes.
  2. Press Y until '4' shows under Service.
  3. Press S. '4' shows under Status.
  4. Press Y until '3' shows under Service.
  5. Press S. '1' shows under Status and 'dEL' under Service.
  6. Press S to confirm the deletion. '1' under Service means success, '0' means it failed.
  7. Press S to return to the operating display.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 27. Written in our own words; check the manual for your exact model.

Clear the service message (P.1 / P.8)

Boiler · Vitodens 200-W B2HE

A service message you acknowledge without resetting comes back the next Monday. Reset it through parameter 1411.0.

  1. Service menu > System configuration > Boiler
  2. Set parameter 1411.0 Clear maintenance messages to ON
  3. Set the next interval in 521.0 (burner hours) or 522.3 (months)

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Parameters: Boiler; P.1/P.8. Written in our own words; check the manual for your exact model.

Clearing a service required status (code 0F)

Boiler · Vitodens 200-W

Code 0F means service is required. After servicing, enter code 24:0 to clear it.

  1. After servicing the boiler, select coding code 24:0.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 77. Written in our own words; check the manual for your exact model.

Comfort mode end conditions

Boiler · Vitocrossal 300 CA3B

Comfort mode ends automatically when the system returns to standard heating per the time program, or after 8 hours. Ask the local heating contractor before changing this.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Delete a central heating time phase

Boiler · Vitotronic 300-K, Vitotronic 100

Removes a time phase by making its end time equal to its start time.

  1. Select the time phase to delete in the central heating time program.
  2. Set the end time to the same time as the start time.
  3. The display shows "- - : - -" for the removed phase.

Applies to: Vitotronic 300-K, MW1B and Vitotronic 100, GC1B

Source: Vitotronic 100/300-K operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Delete a DHW time phase

Boiler · Vitotronic 200 and 300-K

To remove a time phase, set its end time equal to its start time. The display then shows the phase as empty.

  1. Set the end time of the phase to the same time as the start time.
  2. Confirm that the display shows the phase as "- - : - -".

Applies to: Vitotronic 200 and 300-K DHW time program

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Delete a holiday program

Boiler · Vitotronic 300-K

Clears the stored holiday period so the normal time program applies again.

  1. Open the extended menu.
  2. Select "Heating".
  3. Select "Holiday program".
  4. Select "Delete program".

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 19. Written in our own words; check the manual for your exact model.

Delete hours run meter reading

Boiler · Vitocrossal 300 CA3B Dual Fuel

Use the information menu item 2 to clear the resettable hours run meter. Status 6 is the deletion item. 1 under Service means it worked, 0 means it failed.

  1. Press and hold button S for more than 2 seconds until it flashes.
  2. Press button Y until 2 shows under Service.
  3. Press button S. 1 shows under Status.
  4. Press button Y until 6 shows under Status.
  5. Press button S to confirm the deletion.
  6. Press button S to return to the operating display.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner control units

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 22. Written in our own words; check the manual for your exact model.

Delete the message history list

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Clears the saved message list.

  1. Enter the service menu.
  2. Select Message history, then OK.
  3. Select Delete message list, then OK.
  4. Confirm the prompt with OK.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 69. Written in our own words; check the manual for your exact model.

Deleting a heating time phase

Boiler · Vitotrol 300A

Set the end time equal to the start time. The display then shows the phase as empty.

  1. Select the time phase to remove.
  2. Set its end time to match its start time.
  3. Confirm the display shows the phase as empty.

Applies to: Heating and DHW time programs

Source: Vitotrol 300A operating instructions, p. 10, p. 14. Written in our own words; check the manual for your exact model.

Deleting the hours run meter

Boiler · Vitocrossal 200 CM2

Clears the resettable hours run meter from the information menu.

  1. Press S for longer than 2 seconds until the menu item flashes.
  2. Scroll with Y until 2 shows under Service.
  3. Press S. 1 shows under Status.
  4. Scroll with Y until 6 shows under Status (hours run meter delete item).
  5. Press S to confirm. 1 under Service means deleted, 0 means it failed.
  6. Press S to return to the operating display.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 44. Written in our own words; check the manual for your exact model.

Economy mode (setback)

Boiler · Vitotrol 300A

Lowers the room temperature during standard heating mode to save energy. It ends automatically when the time program switches to reduced heating, or when set to OFF.

  1. Open the extended menu and select Setback mode (Economy mode).
  2. Select the heating circuit if needed.
  3. To end early, set Setback mode to OFF.

Applies to: Energy saving function

Source: Vitotrol 300A operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Economy mode: start and end

Boiler · Vitotronic 300-K

Economy mode is an energy saving function that can only be enabled while the system is in standard heating mode. It ends automatically when the time program switches to reduced heating mode.

  1. Start: Menu, Heating, Heating circuit 1/2/3, Economy mode, select the white frame, tap OK.
  2. End: Menu, Heating, Heating circuit 1/2/3, Economy mode, the white frame resets, tap OK.

Applies to: Central heating for each heating circuit

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 16. Written in our own words; check the manual for your exact model.

End economy mode

Boiler · Vitotronic 300-K

Economy mode ends automatically at the next reduced heating phase, or it can be turned off manually.

  1. Open the extended menu.
  2. Select "Economy mode".
  3. Set "Economy mode" to "OFF".

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 18. Written in our own words; check the manual for your exact model.

End emissions test mode early

Boiler · Vitodens 200-W B2HA

Manual shutdown of the emissions test mode from the settings menu. It also ends by itself after 30 minutes.

  1. Open settings; the settings indicator starts flashing.
  2. Scroll until the "S" entry flashes.
  3. Confirm with OK; "OFF" flashes.
  4. Confirm again with OK to finish.

Applies to: Vitotronic 200 on Vitodens 200-W B2HA

Source: Vitotronic 200 Operating Instructions, p. 16. Written in our own words; check the manual for your exact model.

End party mode

Boiler · Vitotronic 300-K

Party mode ends automatically when the system returns to standard heating mode per the time program, or it can be turned off by hand.

  1. Open the extended menu.
  2. Select "Party mode".
  3. Set "Party mode" to "OFF".

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Ending Economy mode

Boiler · Vitocrossal 300 CA3B Dual Fuel

Economy mode can only be enabled in standard heating mode. It ends manually or automatically when the time program switches to reduced heating mode.

  1. Go to Menu > Heating > required heating circuit > Economy mode > Economy mode.
  2. Press OK to confirm.
  3. Economy mode also ends automatically at the reduced heating time in the time program.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Energy saving mode: lower the room temperature briefly

Boiler · Vitocontrol-S

Energy saving mode lowers the preset room temperature for a short time. It is possible only in the rw heating program.

  1. Select the heating circuit.
  2. Press the energy saving key so the button lights and the mode display shows briefly.
  3. To cancel, press the heating circuit selector and the energy saving key again. Mode ends automatically at the next switch to reduced room temperature.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 13. Written in our own words; check the manual for your exact model.

Erase central heating time phases

Boiler · Vitocontrol-S, VD2/CT3/CM2

Clears a central heating phase by setting its finishing time to blank.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the time program button; the central heating time program display appears.
  4. Press until the required 'Central heating phase OFF' shows.
  5. Press until the finishing time shows '– – : – –'.
  6. Confirm until the display returns to the boiler temperature.
  7. Close the hinged cover.

Applies to: Central heating time program

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Erase DHW time cycles

Boiler · Vitotronic 300

Clears a chosen DHW cycle by setting its finish time to blank.

  1. Open the programming unit cover and press the heating circuit selector until it lights up.
  2. Press the time program button until the required 'DHW cycle OFF' appears.
  3. Press until the finish time shows '– – : – –'.
  4. Confirm until the display returns to the boiler temperature.
  5. Close the cover.

Applies to: DHW time program

Source: Vitotronic 300 GW2 operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Erase DHW time phases

Boiler · Vitocontrol-S, VD2/CT3/CM2

Clears a DHW phase by setting its finishing time to blank. Scanning uses the same display procedure without the adjust buttons.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the time program button; the DHW time program display appears.
  4. Press until the required 'DHW phase OFF' shows.
  5. Press until the finishing time shows '– – : – –'.
  6. Confirm until the display returns to the boiler temperature.
  7. Close the hinged cover.

Applies to: DHW time program

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Erasing time phases

Boiler · Vitotronic 200-H

Clears one or more heating phases so that no switching occurs in that window.

  1. Open the hinged cover on the programming unit.
  2. Press the heating time program button until the display shows the required 'Heating phase OFF'.
  3. Press to step to the finishing time until the display shows '-- : --'.
  4. Confirm until the basic display returns.
  5. Close the hinged cover.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Exit a settings level

Boiler · Versatronik 200

Use the F button marked Cancel to leave the current level.

  1. Press the F button [Cancel] to exit the level.

Applies to: Versatronik 200 expert settings

Source: Versatronik 200 Installation and Operating Manual, p. 153. Written in our own words; check the manual for your exact model.

Exit expert level on Lago FB

Boiler · Versatronik 200

Leave expert level when done.

  1. Use the mode dial to select Entry/Return. The display shows PL.
  2. Use the value dial to exit expert level.

Applies to: Lago FB remote control

Source: Versatronik 200 installation and operating manual, p. 59. Written in our own words; check the manual for your exact model.

Exit the service level

Boiler · Vitotronic 300-K, Vitotronic 200

Leave service mode through the Terminate service option, or wait for the automatic exit after 30 minutes.

  1. Select Terminate service? in the menu.
  2. Select Yes.
  3. Confirm with OK.

Applies to: Vitotronic 200 and Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service, p. 67. Written in our own words; check the manual for your exact model.

Exit the time program setting mode

Boiler · Vitocontrol-S, VD2/CT3/CM2

Leave the setting mode at any time without changing the rest of the program.

  1. Press the exit button; the display shows 'Exit? Yes'.
  2. Press confirm; the display returns to the boiler temperature.

Applies to: Time program setting mode

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Exit time program setting mode

Boiler · Vitotronic 200-H

You can leave the time program setting at any stage.

  1. Press the heating time program button; the display asks 'Exit? Yes'.
  2. Confirm to return to the basic display.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Exiting the service level

Boiler · Vitodens 200-W B2HA

The service level also exits automatically after 30 minutes.

  1. Select Terminate service.
  2. Select Yes.
  3. Confirm with OK.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.

Factory reset

Boiler · Versatronik 300

The Menu has a Factory Reset item. It resets the control to factory settings, so note any custom settings first.

  1. Write down custom settings before resetting.
  2. Open Menu and select Factory Reset.
  3. Choose Yes to reset or No to cancel.

Applies to: Versatronik 300 menu

Source: Versatronik 300 Cascade Control manual, p. 29. Written in our own words; check the manual for your exact model.

Factory settings button resets all values

Boiler · Vitocontrol-S

The factory settings button resets every changed value back to factory settings. Use it only when you intend to lose all custom settings, as nothing is kept.

  1. Press the factory settings button only if you want all altered values reset.
  2. Re-enter any site-specific settings afterwards.

Applies to: Vitocontrol-S and Vitotronic 100, GC1

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 6, p. 8. Written in our own words; check the manual for your exact model.

Fault messages that are not rectified

Boiler · Vitocrossal 300 CA3B

Unrectified faults can have life threatening consequences. Repeated acknowledgement hides the problem.

  1. Do not acknowledge fault messages several times in quick succession.
  2. Notify the heating contractor if a fault recurs so the cause can be analysed and rectified.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 33. Written in our own words; check the manual for your exact model.

Fixed high limit trip needs manual reset

Boiler · Vitodens 100-W WB1B

A tripped fixed high limit locks out the boiler control and must be reset by hand after the boiler has cooled.

  1. Let the boiler cool down before resetting.
  2. Reset the boiler control manually.

Applies to: Vitodens 100-W WB1B

Source: Vitodens 100-W WB1B installation and service instructions, p. 5. Written in our own words; check the manual for your exact model.

Gas supply fault during commissioning

Boiler · Vitocrossal 300 CA3B Dual Fuel

The system can lock out during commissioning if the gas supply line has too little gas. The fault indicator lights on the control unit.

  1. Purge the gas supply lines again.
  2. Reset the burner control unit.
  3. Remove air from the gas line with an approved gas purge burner, or vent it outdoors.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 18. Written in our own words; check the manual for your exact model.

Leave a time program early or skip a cycle

Boiler · Vitotrol 300

Any time program setting can be ended early, and a single cycle can be skipped without changing the others.

  1. To end the setting, press the exit key; the display returns to the current time.
  2. To skip one cycle, press the skip key and move on to the next cycle.
  3. Once the last setting is confirmed, the display shows the current time.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Manual reset after burner lockout

Boiler · Vitodens 200-W B2HA

A burner lockout after failed ignition trials requires a manual reset before the burner will run again.

  1. Clear the cause of the failed ignition.
  2. Reset the burner manually.

Applies to: Vitodens 200-W B2HA 45 and 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 88. Written in our own words; check the manual for your exact model.

Read and acknowledge faults (Vitotronic 100)

Boiler · Vitotronic 100 GC1

Fault codes flash on the display, and the red fault lamp A flashes for all faults. Acknowledging hides the message but the lamp keeps flashing. A fault message that is not cleared by the next morning shows again. Where another LON device has a fault, it appears on the left side of the display.

  1. Read the fault number, fault code and LON participant number shown on the display.
  2. Use the up or down button to see further fault codes.
  3. Press the acknowledge button to hide the message. Red lamp A keeps flashing until the fault is cleared.
  4. To view an acknowledged fault, hold the button for about 3 seconds and select it with the up or down button.
  5. Use the remedy column on the fault table to fix the cause.

Applies to: Vitotronic 100, GC1

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 95. Written in our own words; check the manual for your exact model.

Redisplay an acknowledged maintenance message

Boiler · Vitotronic 100 GC1

An acknowledged maintenance message can be shown again if needed.

  1. Press the indicated button and hold it for about three seconds.

Applies to: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 107. Written in our own words; check the manual for your exact model.

Release a burner fault shutdown

Boiler · Vitocrossal 300 CA3B

Fault shutdowns from the fan or combustion chamber air pressure monitoring can be released with the reset button R on the burner control unit, after the cause is cleared.

  1. Clear the cause of the fault first.
  2. Press the reset button R on the burner control unit.

Applies to: CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 61. Written in our own words; check the manual for your exact model.

Reset a locked burner from the home screen

Boiler · Vitodens 100-W B1HE/B1KE

Use this to unlock a burner that is locked out by a fault. Do not reset the burner several times in quick succession.

  1. Select Unlock on the home screen.
  2. Tap OK twice to confirm.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Reset a locked burner from the submenu

Boiler · Vitodens 100-W B1HE/B1KE

Alternative reset path through the Active messages submenu.

  1. Call up the home screen and open the menu.
  2. Select Active messages, then tap OK.
  3. Select Burner fault, then tap OK.
  4. Select Unlock, then tap OK.
  5. Tap OK to acknowledge the information.
  6. Hold the exit button for about 4 seconds to leave the menu.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Reset a tripped fixed high limit

Boiler · Vitotronic 100

The FHL can be reset by hand once it has tripped. You will hear a click if it had tripped.

  1. Push in the pin labelled "E" on the FHL using a ballpoint pen.
  2. Listen for a click to confirm the limit had tripped.

Applies to: Vitotronic 100 KW10B fixed high limit

Source: Vitotronic 100 KW10B installation manual, p. 17. Written in our own words; check the manual for your exact model.

Reset after air in gas line at first start

Boiler · Vitodens 200-W B2HA

The burner may show a fault on initial start-up because of air in the gas supply, especially with LPG. The boiler uses direct spark ignition.

  1. Wait about 5 seconds after the fault.
  2. Press the R reset button.
  3. The ignition procedure repeats automatically.

Applies to: Initial start-up, especially LPG

Source: Vitodens 200-W B2HA service instructions, p. 20. Written in our own words; check the manual for your exact model.

Reset after air in the gas line at first start

Boiler · Vitodens 200-W B2HB

Liquid propane gas lines can hold air, which causes a fault on first start.

  1. If a fault appears on initial start-up, wait about 5 seconds.
  2. Press reset button R.
  3. The ignition sequence repeats.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 20. Written in our own words; check the manual for your exact model.

Reset after flue gas over-temperature lockout

Boiler · Vitocrossal 200 CI2

The flue gas temperature sensor locks out the boiler if the permissible flue gas temperature is exceeded.

  1. Let the flue system cool down.
  2. Reset the burner on the programming unit.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 77. Written in our own words; check the manual for your exact model.

Reset after ignition fault on first start-up

Boiler · Vitodens 200-W

Air in the gas supply line, especially with LPG, can cause a fault during first start-up. The burner then ignites automatically after a safety time.

  1. Wait about 5 seconds after the fault appears.
  2. Press the R reset button to restart the ignition procedure.

Applies to: Vitodens 200-W B2HB 19 to 125

Source: Vitodens 200-W B2HB service instructions, p. 20. Written in our own words; check the manual for your exact model.

Reset all altered values to factory settings

Boiler · Vitotronic 200-H

The factory settings button resets every value the user has changed back to the factory default.

  1. Press the factory settings button.
  2. Check the time, date and programs afterwards, since they are reset as well.

Applies to: Vitotronic 200-H HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Reset all codes to factory setting

Boiler · Vitotronic 200, Vitotronic 300-K

Use this to return every coding address to its factory value. It also resets coding level 2.

  1. Open 'Coding level 1' in the coding menu.
  2. Select 'Standard setting'.
  3. Confirm the reset. Recheck any site-specific codes afterwards.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

Reset all codes to factory settings

Boiler · Vitotronic 300-K

This resets every coding address, including the ones changed in coding level 1, so record the current values first.

  1. Enter coding level 2.
  2. Select 'Standard setting' in 'Coding level 2'.
  3. Re-enter any site-specific values afterwards.

Applies to: Vitotronic 300-K coding

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 49. Written in our own words; check the manual for your exact model.

Reset all coding to factory default

Boiler · Vitotronic 200-H

Restores the factory coding values. Key symbols were not legible in the extracted text, so keys are named by their printed letters.

  1. Press the w and rw keys together for about 2 seconds.
  2. Press D.
  3. Confirm 'Standard setting? Yes' with the confirm key.
  4. Use the up or down key to choose 'Standard setting? Yes' or 'Standard setting? No' as needed.

Applies to: Vitotronic 200-H coding

Source: Viessmann Vitotronic 200-H installation and service instructions, p. 50. Written in our own words; check the manual for your exact model.

Reset all coding to factory setting

Boiler · Vitodens 200-W B2HA

Clears every coding address in coding level 1 and level 2 back to the factory defaults.

  1. Open Coding level 1.
  2. Select Standard setting.
  3. Confirm the reset. Level 2 codes are reset as well.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 39. Written in our own words; check the manual for your exact model.

Reset all coding to factory settings

Boiler · Vitotronic 300 GW6B

Restores all coding values to the factory condition.

  1. From the home screen tap Menu.
  2. Tap Service.
  3. Enter the viservice password.
  4. Tap System coding.
  5. Tap Coding level 1 or Coding level 2 and enter the viexpert password.
  6. Tap Reset coding.

Applies to: Vitotronic 300 GW6B control unit

Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 85. Written in our own words; check the manual for your exact model.

Reset all codings to factory default

Boiler · Vitotronic 200-H

Restores every coding address to its factory setting. Any custom codings are lost, so write them down first.

  1. Press the first and second buttons together for about 2 seconds until the first two arrows appear.
  2. Press the D button.
  3. Check the codings afterwards, because all addresses return to defaults.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

Reset all codings to factory setting

Boiler · Vitotronic 100

This resets all codings on the Vitotronic 100 to the factory values. Button symbols are not fully legible on the extracted pages.

  1. Press w and rw together for about 2 seconds.
  2. Press D.
  3. Confirm Base setting Yes with the confirm button.
  4. Select Base setting Yes or Base setting No with the up or down button.

Applies to: Vitotronic 100, GC1

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 147. Written in our own words; check the manual for your exact model.

Reset all codings to factory settings

Boiler · Vitotronic 300

Resets all codings in coding level 2 to factory values. Burner type code 03 (oil-fired) cannot be reset this way.

  1. Press w and rw together for about 2 seconds to enter coding level 2.
  2. Press the menu button.
  3. Press OK to confirm 'Factory setting? Yes'. Select 'No' with the up or down button to cancel instead.
  4. Re-check the codings afterwards, as the factory values come from the boiler coding card.

Applies to: Vitotronic 300 GW2 coding level 2

Source: Vitotronic 300 GW2 installation and service instructions, p. 117. Written in our own words; check the manual for your exact model.

Reset all codings to factory settings (input module)

Boiler · Vitotronic 100, GC1

Resets the codings on the 0-10 V input module. The button symbols in the source are not legible, so button names are described by position only.

  1. Press the two buttons together for about two seconds until the first two arrows appear in the display.
  2. Press the confirm button D.

Applies to: 0-10 V input module 7134 561

Source: Vitotronic 100 GC1 installation and service instructions, p. 114. Written in our own words; check the manual for your exact model.

Reset all operating parameters to factory settings

Boiler · Vitocrossal 300 CA3B Dual Fuel

Restores every operating parameter to factory values through the service menu.

  1. Hold S for more than 2 seconds until the indicator flashes.
  2. Press Y until '6' shows under Service.
  3. Press S. '6' shows under Status.
  4. Press Y until '0' shows under Service.
  5. Press S. '1' shows under Status and 'dEL' under Service.
  6. Press S to confirm. '1' under Service means success, '0' means it failed.
  7. Press S to return to the operating display.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 24. Written in our own words; check the manual for your exact model.

Reset all values to factory default

Boiler · Vitotrol 300

The factory default button resets every adjustable value on the remote control, not just one setting. Write down any custom settings first.

  1. Press the factory default button (icon not legible in text) only if all values should be reset.
  2. Re-enter date, time, room temperatures and heating cycles after the reset.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Reset all values to factory settings (Vitotronic 100)

Boiler · Vitotronic 100 GC1B

Resets all changed values at once. Factory settings include heating program (blank setting on display) and temperature unit °C.

  1. Press the settings key until its symbol flashes.
  2. Press the selector key until the reset symbol flashes.
  3. Press OK to confirm; the reset symbol flashes.
  4. Press OK again to confirm; the factory settings are restored.

Applies to: Vitotronic 100 GC1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Reset burner after a start-up fault caused by air in the gas line

Boiler · Vitodens 222-F

On first start-up, air in the gas supply pipe (especially with LPG) can cause a fault. The direct spark ignition retries after a reset.

  1. Wait about 5 seconds after the fault.
  2. Press the R reset button to reset the burner.
  3. The ignition procedure repeats.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 19. Written in our own words; check the manual for your exact model.

Reset burner control unit after a fault

Boiler · Vitocrossal 300 CA3B Dual Fuel

Correct the fault first, working through the measures in the order listed. Then reset the unit.

  1. Correct the fault using the measures for the displayed code (pages 28 to 31), in the order given.
  2. Press reset button R for longer than 0.5 seconds.
  3. The operating display returns and the burner control unit is reset.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 27. Written in our own words; check the manual for your exact model.

Reset burner hours or burner starts to zero

Boiler · Vitotronic 100, GC1

Done from the scanning mode. The burner hours shown are approximate values only.

  1. Scan to the burner hours (1st or 2nd stage) or burner starts.
  2. Press the D button while that value is shown to reset it to 0.

Applies to: Single-boiler and multi-boiler systems

Source: Vitotronic 100, GC1 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Reset burner hours, fuel consumption and solar data

Boiler · Vitocrossal 300

Clears the stored data counters. Options are burner hours, fuel consumption, solar energy yield, solar circuit pump hours and output 22 hours, or all of them together.

  1. Open the extended menu.
  2. Select 'Information'.
  3. Select 'Reset data'.
  4. Choose the counter to reset.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Reset burner hours, fuel consumption or solar data

Boiler · Vitocrossal 300 CA3B

You can reset burner hours run, fuel consumption, and in solar systems the solar energy yield, solar circuit pump hours and output hours. You can also reset all data at once. Select the item or All details, then confirm.

  1. From the home screen, open Menu, then Information.
  2. Open Reset data.
  3. Select the required data point or All details.
  4. Tap OK to confirm.
  5. Tap Confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Reset burner operating time and burner starts

Boiler · Versatronik 200

Burner run time and start counts are shown per stage and can be reset per boiler.

  1. Select Burn operat time with the F button to show the current values.
  2. Use the F button to select the boiler and level.
  3. Select Reset with the F button.
  4. Press Cancel to leave the level.

Applies to: Cascade and multi-stage heat generators

Source: Versatronik 200 installation and operating manual, p. 164. Written in our own words; check the manual for your exact model.

Reset burner run hours and burner starts

Boiler · Vitotronic 100 GC1

Burner run hours and burner starts can be cleared from the scan display after service work.

  1. Open the operating condition scan (page 106).
  2. Select the run hours or burner starts display.
  3. Press D to reset the value to 0.

Applies to: Vitotronic 100 GC1 boiler control

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 106. Written in our own words; check the manual for your exact model.

Reset button location

Boiler · Vitotronic 200

The red fault indicator, green ON indicator, reset button and ON/OFF switch are on the boiler controls. On Vitodens 200-W the reset button is under the open side panels. On Vitocrossal 300 CU3A it is under the open panel covers.

  1. Open the side panels (Vitodens 200-W) or panel covers (Vitocrossal 300 CU3A).
  2. Find the reset button next to the fault indicator.
  3. Only reset after the fault cause has been corrected.

Applies to: Vitodens 200-W and Vitocrossal 300 CU3A

Source: Vitotronic 200 operating instructions 5838 962-03, p. 8. Written in our own words; check the manual for your exact model.

Reset central heating phases to factory settings

Boiler · Vitocontrol-S, VD2/CT3/CM2

If different phases were set per weekday, selecting '1-7' again resets all phases to their factory settings.

  1. While '1-7' is showing, press the confirm button to reset all time phases to factory settings.

Applies to: Central heating time program

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Reset codes to factory default

Boiler · Vitotronic 200-H

Restores the factory default settings.

  1. Press the w and rw keys together for about 2 seconds.
  2. Press D.
  3. Confirm with OK.

Applies to: Vitotronic 200-H

Source: Vitotronic 200-H installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Reset codings to factory default

Boiler · Vitotronic 200-H

Restores the factory coding values.

  1. Press the two buttons shown on the programming unit simultaneously for about 2 seconds, until the first two arrows appear.
  2. Press the D button.

Applies to: Vitotronic 200-H programming unit

Source: Vitotronic 200-H HK1M installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

Reset codings to factory setting

Boiler · Vitotronic 300-K MW1S

Use this to return the coding addresses to their factory values.

  1. Press the w and rw buttons together for about two seconds, until the first two arrows appear in the display.
  2. Press the D button to confirm.

Applies to: Vitotronic 300-K MW1S input module and control unit codings

Source: Vitotronic 300-K MW1S installation and service instructions, p. 137. Written in our own words; check the manual for your exact model.

Reset data (solar and all data)

Boiler · Vitotronic 300-K

Resets solar energy yield, solar pump hours run and output 22 hours run, or all data at once. Only the solar items apply when a solar thermal system is present.

  1. From the home screen, open Information.
  2. Tap Reset data.
  3. Select the required data point or All data.
  4. Confirm.

Applies to: Solar thermal systems and general data reset

Source: Vitotronic 300-K MW2C operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Reset DHW time phases to factory settings

Boiler · Vitotronic 200-H

If different times were set for individual days, you can return all phases to the factory settings.

  1. With the display showing '1-7', press the reset button.
  2. All DHW time phases return to factory settings.

Applies to: Vitotronic 200-H DHW time program

Source: Vitotronic 200-H operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Reset faults with the tr rotary selector

Boiler · Vitodens 100-W, WB1B

Turning the tr selector to the reset position clears a fault. If no fault is present, the boiler goes into relay test mode instead. Turn the boiler off and back on to exit.

  1. Turn the tr rotary selector to "U Reset".
  2. Pause until "SERV" appears on the screen.
  3. Within 2 seconds, turn tr back into the control range.
  4. To leave relay test mode, turn the boiler off and back on.

Applies to: Vitodens 100-W WB1B

Source: Vitodens 100-W WB1B installation and service instructions, p. 76. Written in our own words; check the manual for your exact model.

Reset heating time cycles to factory settings

Boiler · Vitotronic 300

If days have been set individually, selecting all days again resets every time cycle to the factory default.

  1. With '1-7' showing in the heating time program display, press the reset button shown in the manual.
  2. Confirm the reset as prompted.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 13. Written in our own words; check the manual for your exact model.

Reset Input Module codings to factory setting

Boiler · Vitocontrol-S VD2/CT3/CM2

Restores the 0 to 10 V Input Module codings to factory values.

  1. Press the w and rw keys together for about two seconds, until the first two arrows appear in the display.
  2. Press the D key to confirm.

Applies to: Input Module 0 to 10 V, Part No. 7134 561

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 153. Written in our own words; check the manual for your exact model.

Reset manual reset temperature limit switch

Boiler · Vitocrossal 300 CA3B Dual Fuel

The supply water and flue gas temperature limit switches lock out mechanically when the probe temperature exceeds the limit. They are factory preset and must not be adjusted. The switch can only be reset after the temperature has dropped about 14°F (8°C) below the limit.

  1. Unscrew the reset cap and set it aside.
  2. Reset the switch.
  3. Reinstall the reset cap.
  4. If the switch cannot be reset, replace the switch.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 60. Written in our own words; check the manual for your exact model.

Reset max flue gas temperature

Boiler · Vitotronic 300

Resets the stored maximum flue gas temperature to the current value after maintenance.

  1. Press the 9 and rw buttons together for about 4 seconds.
  2. Press D to reset max flue gas temperature to the current value.
  3. Press the exit button.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 78. Written in our own words; check the manual for your exact model.

Reset maximum flue gas temperature

Boiler · Vitotronic 100 GC1

The stored maximum flue gas temperature can be set back to the actual value.

  1. Press 9 and rw together for about four seconds to enter the maximum flue gas temperature display.
  2. Press D to reset the maximum flue gas temperature to the actual value.

Applies to: Vitotronic 100 GC1 boiler control

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 107. Written in our own words; check the manual for your exact model.

Reset operating data (hours run etc.)

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Saved operating data such as hours run can be set back to 0. The dampened outdoor temperature value resets to the actual outdoor value.

  1. From the home screen, tap Service and enter the viservice password.
  2. Tap Diagnosis, then Reset data.
  3. Select the required value, or All data.
  4. Note: the service menu exits automatically after 30 min.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Vitocrossal 300 Dual Fuel service instructions, p. 116. Written in our own words; check the manual for your exact model.

Reset operating data (Vitotronic 200)

Boiler · Vitotronic 200

Operating data reset on the Vitotronic 200 is covered in the boiler operating instructions.

  1. Refer to the Vitodens operating instructions for the reset procedure.

Applies to: Vitotronic 200

Source: Vitotronic 200 and 300-K Installation and Service, p. 68. Written in our own words; check the manual for your exact model.

Reset operating data counters

Boiler · Vitocrossal 300 CA3B

Saved operating data such as hours run can be reset to 0. The dampened outdoor temperature is reset to the actual value.

  1. From the home screen tap Service and enter the viservice password.
  2. Select Diagnosis, then Reset data.
  3. Select the required value or All data.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 117. Written in our own words; check the manual for your exact model.

Reset operating parameters to factory settings

Boiler · Vitocrossal 300 CA3B Dual Fuel

All operating parameters can be returned to their factory settings through menu item 6.

  1. Hold button S for more than 2 seconds until the menu indicator blinks.
  2. Press Y until 6 shows under Service.
  3. Press S. 6 shows under Status.
  4. Press Y until 0 shows under Service.
  5. Press S. 1 shows under Status and dEL shows under Service.
  6. Press S to confirm. 1 under Service means success, 0 means it failed.
  7. Press S to return to the operating display.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 24. Written in our own words; check the manual for your exact model.

Reset parameters to factory values

Boiler · Versatronik 200

User, expert and time program values can each be restored to factory settings separately.

  1. Select the Reset function with the F button.
  2. Set it to On with the shaft encoder.
  3. Press OK to load the standard values for that level.
  4. Press Cancel to exit, or use the Home button.

Applies to: Versatronik 200 service level

Source: Versatronik 200 installation and operating manual, p. 164. Written in our own words; check the manual for your exact model.

Reset recorded data to 0 (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1B

Resets solar energy yield and solar pump hours, or all the above data together.

  1. Open the extended menu.
  2. Select Information, then Reset data.
  3. Select the data to reset: solar energy yield and hours run for solar circuit pump and output 22, or all data at once.

Applies to: Vitotronic 300-K MW1B with solar thermal system

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Reset saved operating data

Boiler · Vitotronic 200 and 300-K

Saved operating data such as hours run can be set back to 0. The adjusted outdoor temperature is reset to the actual outdoor temperature.

  1. Enter the service level.
  2. Select "Diagnosis", then "Reset data".
  3. Select the value to reset (for example "Burner starts") or "All details".

Applies to: Vitotronic 200 and 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 28. Written in our own words; check the manual for your exact model.

Reset saved operating data (Vitotronic 300-K)

Boiler · Vitotronic 300-K

Saved operating data such as hours run can be reset to 0. The adjusted outside temperature value resets to the actual value.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Diagnosis.
  3. Select Reset data.
  4. Select the required value, for example Solar circuit pump, or All details.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service, p. 68. Written in our own words; check the manual for your exact model.

Reset scan data (burner hours, fuel use, solar data)

Boiler · Vitocrossal 300 CA3B

Operator-level reset of stored counters from the Information menu. Solar items only apply with a solar thermal system.

  1. From the home screen, open Information.
  2. Choose Reset data.
  3. Select the data point to clear, or All data.
  4. Confirm, then tap Confirm again.
  5. Check that the footer shows the confirmation.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Reset service counter after maintenance

Boiler · Vitocrossal 300 CA3B

Resets the hours-run and interval counters after service has been done. If not reset, the Service message comes back on the following Monday.

  1. From the home screen, open Service and enter the 'viservice' password.
  2. Open Service functions.
  3. Select Reset service. This sets the hours-run and interval counters to 0 and sets coding 24 in the Boiler group to 24:0.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 120. Written in our own words; check the manual for your exact model.

Reset service display after service

Boiler · Vitodens 222-F

Resets the hours-run and time interval counters so the service display restarts at 0.

  1. Press OK together with the second service key (symbol not legible on the page) for about 4 seconds.
  2. Select Service functions.
  3. Select Service reset.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F B2TB service instructions, p. 45. Written in our own words; check the manual for your exact model.

Reset service interval after maintenance

Boiler · Vitocrossal 300 CA3B Dual Fuel

After maintenance, the service counter for hours run and interval restarts. Coding 24 in the Boiler group returns to 24:0. If service was done early, set coding 24:1 to 24:0 so the interval restarts; otherwise Service appears again the following Monday.

  1. From the home screen tap Menu, then Service.
  2. Enter the viservice password.
  3. Tap Service functions, then Reset service.
  4. If the service was carried out early, set coding 24:1 in the Boiler group to 24:0.

Applies to: Maintenance service reminder

Source: Vitocrossal 300 CA3B Dual Fuel Service Instructions, p. 119. Written in our own words; check the manual for your exact model.

Reset service interval after service

Boiler · Vitodens 200-W B2HB

Clears the hours run and time interval counters after the burner is serviced.

  1. Press OK and the second menu button together for about 4 seconds (symbol not legible in this copy).
  2. Select Service functions.
  3. Select Service reset.
  4. Hours run and time interval restart at 0.

Applies to: Vitotronic 200-H, Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB service instructions, p. 40. Written in our own words; check the manual for your exact model.

Reset service maintenance counters

Boiler · Vitocrossal 200 CI2

Clears maintenance messages. The selected hours-run and time-interval counters restart at 0. On multi-boiler systems this is done with the software tool.

  1. Open the service menu and enter password "viservice".
  2. Go to "System configuration", then "Boiler".
  3. Select parameter 1411.0 "Clear maintenance messages" and set it to "ON".

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 57. Written in our own words; check the manual for your exact model.

Reset solar energy and hours run data

Boiler · Vitotronic 200 and 300-K

With a solar system, the solar energy yield and the hours run for the solar circuit pump and output 22 can be reset to 0, or all of the above data can be reset together.

  1. Open the extended menu.
  2. Select "Information", then "Reset data".

Applies to: Vitotronic 300-K with solar thermal system

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Reset solar yield and pump run-hour data to 0

Boiler · Vitotronic 300-K

Resets the solar energy yield and run hours for the solar circuit pump and output 22. Can also reset all of these data at once.

  1. Open the extended menu.
  2. Select "Information".
  3. Select "Reset data".
  4. Choose the data to reset.

Applies to: Vitotronic 300-K with solar thermal system

Source: Vitotronic 200 and 300-K Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Reset stored burner hours, fuel consumption or other data

Boiler · Vitocrossal 300 CA3B

Burner hours run, fuel consumption, solar yield and solar pump hours can be cleared from the display. Data can be reset one at a time or all at once.

  1. From the home screen tap Menu.
  2. Tap Information.
  3. Tap Reset data.
  4. Select the data point required, or All details.
  5. Tap OK to confirm.
  6. Tap Confirm. The footer then shows the reset confirmation.

Applies to: Vitocrossal 300 CA3B, all boiler sections

Source: Vitocrossal 300 CA3B operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Reset the burner after an air-in-gas-line fault at start-up

Boiler · Vitodens 200-W B2HA

Air in the gas supply pipe, especially with LPG, can cause a fault on first start-up.

  1. Wait about 5 seconds after the fault appears.
  2. Press the "R" button to reset the burner.
  3. The ignition procedure repeats automatically.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 17. Written in our own words; check the manual for your exact model.

Reset the burner control unit after a fault

Boiler · Vitocrossal 200 CM2

Fix the fault first, following the fault code measures in the listed order. Then reset the control with the reset button.

  1. Correct the fault using the measures for the displayed code, in the order given.
  2. Press and hold reset button R for longer than 0.5 seconds.
  3. Confirm the operating display returns.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 49. Written in our own words; check the manual for your exact model.

Reset the burner hours run counter

Boiler · Vitotronic 300

The burner hours run counter can be set back to zero from the scan display.

  1. Scan to the burner hours run item while the display is on.
  2. Press the D button to reset the burner hours run to 0.

Applies to: Burner hours run counter

Source: Vitotronic 300 GW2 operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Reset the burner service display after maintenance

Boiler · Vitotronic 100

Coding 24 makes the service display appear. It does not clear itself after maintenance and must be reset by hand.

  1. Complete the burner maintenance.
  2. Reset the service display manually on the control unit.
  3. Confirm coding 21 or 23 if a new service interval is needed.

Applies to: Vitotronic 100 GC1, codings 21, 23 and 24

Source: Vitotronic 100 GC1 installation and service instructions, p. 120. Written in our own words; check the manual for your exact model.

Reset the fixed high limit

Boiler · Vitotronic 300 GW2

After the fixed high limit has cut out, it resets only once the water has cooled.

  1. Wait until the boiler water temperature has fallen about 15 K below the shut-down temperature.
  2. Press reset button E on the front of the programming unit.

Applies to: Fixed high limit 7820 036

Source: Vitotronic 300 GW2 installation and service instructions, p. 98. Written in our own words; check the manual for your exact model.

Reset the fixed high limit (FHL)

Boiler · Vitotronic 100

The FHL is a manual reset limit. A click when it is pressed in shows it had tripped.

  1. Find the FHL reset pin, labelled with an E, on the control.
  2. Push the pin in with a ballpoint pen.
  3. If a click is heard, the limit had tripped and is now reset.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B operating manual, p. 8. Written in our own words; check the manual for your exact model.

Reset the fixed high limit after a cut-out

Boiler · Vitotronic 100, GC1

The fixed high limit locks out. It can only be reset after the water has cooled.

  1. Let the boiler water temperature fall about 15 K below the shut-down temperature.
  2. Press reset button E on the front of the programming unit.

Applies to: Fixed high limit 7820 036

Source: Vitotronic 100 GC1 installation and service instructions, p. 113. Written in our own words; check the manual for your exact model.

Reset the hours run meter

Boiler · Vitocrossal 300 CA3B Dual Fuel

The resettable hours run meter is cleared through menu item 2 and the status submenu.

  1. Hold button S for more than 2 seconds. The indicator blinks.
  2. Press Y until 2 shows under Service.
  3. Press S. 1 shows under Status.
  4. Press Y until 6 shows under Status.
  5. Press S to confirm. 1 under Service means the meter was deleted, 0 means it failed.
  6. Press S to return to the operating display.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 22. Written in our own words; check the manual for your exact model.

Reset the manual reset limit switches

Boiler · Vitocrossal 300 CA3B Dual Fuel

The supply water and flue gas temperature limit switches lock out mechanically once tripped. They are factory set and must not be adjusted. A switch can only be reset after the probe has cooled about 8 °C (14 °F) below its limit.

  1. Let the probe cool to about 8 °C (14 °F) below the limit temperature.
  2. Unscrew the reset cap and set it aside.
  3. Press to reset the switch.
  4. Reinstall the reset cap.
  5. If the switch will not reset, replace the switch.

Applies to: Supply water temperature limit switch (B) and flue gas temperature limit switch (C)

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 60. Written in our own words; check the manual for your exact model.

Reset the Service display

Boiler · Vitotronic 300

Clears the Service message after maintenance. If coding 24 is not reset, the message comes back at 07:00 on Monday.

  1. If service is done before the Service message shows, set coding 24: 1, then set 24: 0.
  2. Press the scan button to start the service scan.
  3. Scroll through service messages and confirm Acknowledge: Yes with OK.
  4. Press the exit button to end the service scan.
  5. After maintenance, set coding 24 from 1 back to 0.
  6. Reset burner hours, starts and fuel use from the operating status scan if needed.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 78. Written in our own words; check the manual for your exact model.

Reset the service display after service

Boiler · Vitodens 200-W B2HA

When coding 24:1 is set, the Service display appears at the service interval. The address is set automatically and must be reset by hand after service is done.

  1. Complete the burner service.
  2. Reset the Service display manually in the service menu.
  3. Confirm the service interval (21 or 23) is set as required.

Applies to: Vitodens 200-W B2HA, service interval

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 54. Written in our own words; check the manual for your exact model.

Reset the service interval

Boiler · Vitotronic 300 GW6B

Resetting restarts the hours-run and interval counters at 0 and sets coding 24 in the Boiler group to 24:0.

  1. From the home screen, tap Menu, then Service.
  2. Enter the viservice password.
  3. Tap Service functions, then Reset service.

Applies to: Vitotronic 300 GW6B boiler control unit

Source: Vitotronic 300 GW6B installation and service instructions, p. 61. Written in our own words; check the manual for your exact model.

Reset the service interval after maintenance

Boiler · Vitocrossal 300 CA3B

Resetting the service interval sets hours run and the interval back to 0 and coding 24 in the Boiler group to 24:0. If service is done early, set coding 24:1 back to 24:0; otherwise Service will show again the following Monday. Service limits are set in codings 21 and 23 in the Boiler group.

  1. From the home screen tap Service and enter the viservice password.
  2. Select Service functions, then Reset service.
  3. If maintenance was done early, set coding 24:1 in the Boiler group to 24:0.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 120. Written in our own words; check the manual for your exact model.

Resetting a burner fault shutdown

Boiler · Vitocrossal 200 CI2

Gas pressure switch and burner faults are cleared by resetting the burner control unit from the control unit.

  1. Reset the burner control unit from the control unit.
  2. Restart the burner and watch for repeat faults.

Applies to: Vitocrossal 200 CI2 burner control

Source: Vitocrossal 200 CI2 service instructions, p. 92. Written in our own words; check the manual for your exact model.

Resetting all altered values to factory settings

Boiler · Vitotronic 200-H

The factory settings button resets every changed value to its default.

  1. Press the factory settings button to reset all altered values.
  2. Re-check time programs and temperatures afterwards, since they return to defaults.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Resetting coding to factory settings

Boiler · Vitocrossal 300 CA3B

Restores the coding levels to their factory values.

  1. From the home screen, open Service and enter the viservice password.
  2. Open System coding (coding level 1) or System configuration.
  3. For coding level 2, enter the viexpert password.
  4. Select Reset coding.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 80. Written in our own words; check the manual for your exact model.

Resetting operating parameters to factory settings

Boiler · Vitocrossal 200 CM2

Restores all operating parameters to the delivered condition. Make sure the burner control is on standby first.

  1. Press S for longer than 2 seconds until the menu item flashes.
  2. Scroll with Y until 6 shows under Service, then press S. 6 shows under Status.
  3. Scroll with Y until 0 shows under Service.
  4. Press S. 1 shows under Status and dEL under Service.
  5. Press S to confirm. 1 under Service means reset, 0 means it failed.
  6. Press S to return to the operating display.
  7. Press R to reset the unit and apply settings.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 46. Written in our own words; check the manual for your exact model.

Resetting saved operating data

Boiler · Vitodens 200-W B2HA

Resets stored operating data such as hours run. The adjusted outdoor temperature is also reset to the actual value.

  1. Open the service level.
  2. Select Diagnosis, then Reset data.
  3. Select the required value, for example Burner starts, or All details.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.

Resetting scan data (burner hours, fuel use, solar)

Boiler · Vitocrossal 300 CA3B Dual Fuel

You can reset burner hours run, fuel consumption, and with a solar thermal system the solar energy yield, solar circuit pump hours and hours run output 22. All data can also be reset at once.

  1. From the home screen, tap Menu.
  2. Tap Information.
  3. Tap Reset data.
  4. Select the required data point or All details.
  5. Tap OK to confirm.
  6. Tap Confirm.

Applies to: Vitocrossal 300 CA3B Dual Fuel boiler

Source: Vitocrossal 300 Dual Fuel Operating Instructions, p. 33. Written in our own words; check the manual for your exact model.

Resetting stored data

Boiler · Vitocrossal 300 CU3A

You can reset burner hours run, fuel consumption, and (with solar) solar yield, solar pump hours and output 22 hours, or all of them together.

  1. Open the extended menu.
  2. Choose Information.
  3. Choose Reset data.
  4. Select the data to reset.

Applies to: Vitocrossal 300 CU3A with Vitotronic 200 KW6B

Source: Vitocrossal 300 CU3A operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Resetting the maintenance display

Boiler · Vitodens 100-W, B1HE, B1KE

Clears the service message after maintenance has been done.

  1. Open the service menu with the button combination.
  2. Select Reset service messages and press OK.

Applies to: Vitodens 100-W

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words; check the manual for your exact model.

Restart or reset the controller

Boiler · Versatronik COMO OT

A restart and a reset to default values are done with the reset button using a pointed tool. Reset to defaults keeps the heating programs and hot water program.

  1. To restart, press the reset button with a straightened paper clip.
  2. To load default settings, press Prog and Reset together, release Reset, and keep Prog held until EEPROM appears.
  3. Re-enter any values that were changed by the reset.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 30. Written in our own words; check the manual for your exact model.

Restart the controller after a fault

Boiler · Versatronik 200

The system must be restarted after a fault is fixed. A RESET is a brief shutdown of the controller, which restarts and keeps the values already set.

  1. Remedy the fault.
  2. Switch the controller off briefly at the mains switch.
  3. Check that the controller restarts and runs with its stored values.
  4. If needed, reset the User, Expert or Time program values separately in the Service level.

Applies to: Versatronik 200 controller

Source: Versatronik 200 installation and operating manual, p. 165. Written in our own words; check the manual for your exact model.

Restart the start-up wizard

Boiler · Vitocrossal 300 CU3A

Use after an entry error or after adding system components. Some settings may reset, so record them first.

  1. Record current settings.
  2. Press OK and menu together for about 4 seconds.
  3. Select Service Functions.
  4. Select Set-up Wizard.
  5. Select Yes.
  6. Press OK to restart the wizard.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A service instructions, p. 15. Written in our own words; check the manual for your exact model.

Restore factory settings for a heating circuit

Boiler · Vitocrossal 300 CA3B

Resets the values for one heating circuit to factory settings. Heating circuit names stay. The reset must also be done on the main user interface and on all service displays.

  1. From the home screen, open Menu, then Settings.
  2. Open Factory settings.
  3. Select heating circuit 1, 2 or 3.
  4. Tap OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 30. Written in our own words; check the manual for your exact model.

Restore factory settings for one heating circuit

Boiler · Vitotronic 300-K

Factory settings can be restored one heating circuit at a time. This resets the set room temperatures, operating program, DHW setpoint, all time programs, heating curve slope and shift, and the comfort and energy saving functions. A custom circuit name is kept.

  1. From the home screen, open 'Settings' and select 'Factory settings'.
  2. Select the required heating circuit.
  3. Confirm to restore, or cancel to keep the current values.

Applies to: Vitotronic 300-K, MW2C

Source: Vitotronic 300-K, MW2C operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Restore factory settings per heating circuit

Boiler · Vitocrossal 300

Resets all changed values for one heating circuit at a time. Heating circuit names are not reset.

  1. Open the extended menu.
  2. Select 'Settings'.
  3. Select 'Standard setting'.
  4. Choose 'Heating circuit 1', 'Heating circuit 2' or 'Heating circuit 3'.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Restore identical time phases for all days

Boiler · Vitocontrol-S

If different phases were set for individual days, you can reset all days to one common schedule. This also resets all time phases to factory settings.

  1. In the central heating time program, press up/down until 1-7 shows.
  2. Confirm to apply the same time phases to all days.
  3. Note that all time phases return to factory settings.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Restoring factory settings

Boiler · Vitotrol 300A

Factory settings can be restored for each heating circuit separately. Resets set room temperature, set DHW temperature, time programs for central heating, DHW and DHW recirculation pump, and ends party mode, economy mode and holiday program.

  1. Open the extended menu.
  2. Select Settings, then Standard setting.
  3. Select Heating circuit 1, 2 or 3.

Applies to: Vitotrol 300A remote control

Source: Vitotrol 300A operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Restoring factory settings for a heating circuit

Boiler · Vitocrossal 300 CA3B

Restores the values of one heating circuit to factory settings. Heating circuit names are kept. The reset must be done on the main user interface and on all service displays.

  1. From the home screen, select Settings.
  2. Select Factory settings.
  3. Select Heating circuit 1, 2 or 3.
  4. Confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 30. Written in our own words; check the manual for your exact model.

Restoring factory settings per heating circuit

Boiler · Vitocrossal 300 CA3B Dual Fuel

Each heating circuit's modified values can be reset individually. Assigned heating circuit names are kept.

  1. Go to Menu > Settings > Factory settings.
  2. Select Heating circuit 1, 2 or 3.
  3. Press OK to confirm.
  4. This must be done on the main interface and on all service displays.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Return to main view

Boiler · Vitotron 100 VLN2

The panel goes back to the main view by itself after one minute with no button presses.

  1. Press the power button 9 to return to the main view immediately.
  2. Wait one minute with no button presses to return automatically.

Applies to: Vitotron 100 VLN2 control panel

Source: Vitotron 100 VLN2 installation and service instructions, p. 12-13. Written in our own words; check the manual for your exact model.

Return to standard menu

Boiler · Vitodens 200-W B2HA

The display reverts to the standard menu automatically 2 minutes after the last setting change.

  1. Wait 2 minutes after the last change for automatic return to the standard menu.
  2. If the screen saver is on, press any key except the one marked '?'.
  3. If elsewhere in the menu, keep pressing the back key until the standard menu appears.

Applies to: Menu navigation

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 28-29. Written in our own words; check the manual for your exact model.

Screen saver and power failure behavior

Boiler · Vitocrossal 300

The screen saver turns on after a few minutes without key presses and dims the display. All settings are kept during a power failure. After a long power-off, the date and time must be reset.

  1. Press OK to wake the screen and return to the standard menu.
  2. After a prolonged power-off, reset the date and time (see operating instructions, p. 30).

Applies to: Vitotronic 200 KW6B programming unit

Source: Vitocrossal 300 CU3A operating instructions, pp. 9, 15. Written in our own words; check the manual for your exact model.

Service message display and reset

Boiler · Vitodens 200-W B2HB

The Service display with a wrench symbol appears when the limits in coding 21 and 23 are reached. The red fault light flashes.

  1. Press OK to acknowledge the service message.
  2. If not reset, the message returns on the following Monday.
  3. After service is done, press OK and the scroll key together for about 4 seconds.
  4. Select Service functions, then Service reset.
  5. Hours run and time interval restart at 0.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB service instructions, p. 40. Written in our own words; check the manual for your exact model.

Stop central heating

Boiler · Vitotronic 300-K, Vitotronic 200

Two options stop central heating while keeping other functions. Choose summer mode to keep DHW, or standby to keep only frost protection.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select Heating, then Heating program.
  4. Select Only DHW for summer mode, or Standby mode for frost protection monitoring.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 19. Written in our own words; check the manual for your exact model.

Stop DHW and room heating

Boiler · Vitotronic 300-K

Turns off both DHW heating and room heating, leaving only frost protection monitoring active.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select "Heating".
  4. Select "Heating program".
  5. Choose "Standby mode" (frost protection monitoring).

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 22. Written in our own words; check the manual for your exact model.

Stop DHW heating

Boiler · Vitotronic 300-K, Vitotronic 200

Used when neither DHW nor central heating is wanted. Standby mode keeps only frost protection active.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select Heating, then Heating program.
  4. Select Standby mode (frost protection monitoring).

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Stop or prevent DHW heating

Boiler · Vitotronic 300-K

Lowering the DHW temperature setpoint to 50°F (10°C) stops DHW heating during standard operation.

  1. Press Menu, then DHW, then DHW temperature.
  2. Set the value to 50°F (10°C).
  3. Press OK to confirm.

Applies to: DHW tank

Source: Vitotronic 300-K MW2C operating instructions, p. 20. Written in our own words; check the manual for your exact model.

System shutdown

Boiler · Vitocrossal 300 CA3B Dual Fuel

Shut the system down by switching off the main power and all related switches, then closing the system valves. Refer to the system control documentation for other controls.

  1. Turn off the main power switch.
  2. Turn off all additional switches for pumps or controls, including the burner main switch.
  3. Close all valves in the system.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Turn off comfort mode

Boiler · Vitocrossal 300 CA3B

Ends comfort mode manually. It also ends on its own when the system switches to standard heating mode under the time program, or after 8 hours. Contact the heating contractor if you want to change the automatic end.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Comfort mode and select Comfort mode again so the white frame resets.
  4. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Turn off economy mode

Boiler · Vitocrossal 300 CA3B

Ends economy mode manually. It also ends automatically when the time program switches the system to reduced heating mode.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Economy mode and select Economy mode again so the white frame resets.
  4. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Turn off gas to the boiler

Boiler · Vitodens 100-W B1HE/B1KE Combi

Use this shutdown sequence when the boiler is to be serviced or left off.

  1. Set the thermostat or control to lowest setting.
  2. Turn off all electric power to the boiler if service is to be performed.
  3. Turn off the control gas switch.

Applies to: B1HE and B1KE Combi boilers

Source: Vitodens 100-W B1HE/B1KE Combi installation/service manual, p. 125. Written in our own words; check the manual for your exact model.

Undo a premature service reset

Boiler · Vitocrossal 300 CA3B

If service was reset early, the counters can be restarted with the service coding.

  1. Set coding 24 in the Boiler group from 24:1 back to 24:0.
  2. This restarts the hours-run and time interval counters at 0.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 120. Written in our own words; check the manual for your exact model.

Viewing and acknowledging fault messages

Boiler · Vitotronic 300-K

Red fault indicator flashes on the control enclosure when a fault is present. Acknowledging silences any alarm equipment.

  1. Tap the fault symbol in the footer to open the list.
  2. Tap ? to see information and self-help tips for the fault.
  3. Note the fault code and cause, for example f0 Combustion controller.
  4. Tap Acknowledge.
  5. Notify the heating contractor.
  6. If several service messages are active, tap Faults to show the fault list.

Applies to: Vitotronic 300-K MW2C

Source: Vitotronic 300-K MW2C operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Wake the display and cancel a setting

Boiler · Vitotronic 300-K (MW1B)

After a few minutes without input the screen saver starts and display brightness drops. The back key cancels a setting that has been started and takes you to the previous menu step. Holding a key down ends a multi-step entry early.

  1. From the screen saver, press OK to wake the display.
  2. Press the back key to cancel an unfinished setting.
  3. If you want to end a time phase entry early, keep pressing back until the wanted screen appears.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B Operating Instructions, p. 11. Written in our own words; check the manual for your exact model.

Wake the screen saver

Boiler · Vitotronic 300-K

The screen saver starts after a few minutes without changes on the programming unit and the display brightness is reduced.

  1. Press OK to return to the standard menu from the screen saver.
  2. To open the extended menu from the screen saver, press OK and then the extended menu key.

Applies to: Vitotronic 300-K (type MW2B)

Source: Vitotronic 200 and 300-K operating instructions, p. 11-12. Written in our own words; check the manual for your exact model.

When comfort mode ends

Boiler · Vitocrossal 300 CA3B

Comfort mode ends automatically when the system switches to standard heating mode under the time program, or after 8 hours. Contact your heating contractor if you want to change this.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Acknowledge a fault

General · Vitotrol

Acknowledge the fault by following the instructions on the display.

  1. Follow the on-screen instructions to acknowledge the fault.

Applies to: Vitotrol 300A

Source: Vitotrol 300A installation and service instructions, p. 9. Written in our own words; check the manual for your exact model.

Activate Configuration saves and reboots

General · Versatronik 535 Solar

Changes do not take effect until Activate Configuration is confirmed. Choosing SAVE at that prompt stores the settings and reboots the gateway. The Restore Defaults and Change Password screens are basic.

  1. Press SAVE on every configuration screen where a change is made.
  2. Confirm Activate Configuration and select SAVE to apply and reboot.

Applies to: Versatronik 535 Solar gateway

Source: Versatronik 535 Solar BACnet IP manual, p. 13. Written in our own words; check the manual for your exact model.

Reset to factory settings

General · Vitoconnect

Resets all changed values to their factory settings.

  1. Press the Reset button for at least 30 seconds until the LED flashes red.
  2. Press the Reset button again within 5 seconds.
  3. Confirm the LED is off; the Vitoconnect restarts.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Reset Vitoconnect to factory settings

General · Vitoconnect OPTO2

Resets all changed values back to factory settings.

  1. Press the Reset button for at least 30 seconds until the LED flashes red.
  2. Press the Reset button once more within 5 seconds.
  3. Wait until the LED goes out. The Vitoconnect restarts.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Restart the Vitoconnect

General · Vitoconnect

Restart after a fault has been fixed.

  1. Press the Reset button and the operating button together for about 15 seconds.
  2. Wait for the green LED (start-up can take up to 2 minutes).
  3. Wait for the white LED, which means the Vitoconnect is ready.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Auto-restart after power failure

Heat pump · Vitocal 100-S

The indoor unit remembers the last settings through an auto-restart module.

  1. After power returns, the unit resumes the last setting (the swing function is not restored) about 3 minutes later.
  2. If the last mode was FORCED COOLING, the unit runs cooling for 30 minutes and then goes to AUTO at 75.2°F (24°C).

Applies to: DLCSRB indoor high-wall units

Source: DLCSRB Service Manual, p. 22. Written in our own words; check the manual for your exact model.

One-key recovery on hand-held remote

Heat pump · Vitocal 100-S

Resets remote control settings to factory defaults.

  1. Enter engineer mode and select code 16.
  2. Press On/Off for 2 seconds to start One-Key Recovery. Display shows rS.
  3. Press OK to send the recovery code.
  4. Mode returns to COOLING and HEATING, minimum temperature to 16 °C and maximum to 30 °C.
  5. Press On/Off for 2 seconds to exit.

Applies to: DLCURA hand-held remote (some models)

Source: DLCURA Service Manual, p. 23. Written in our own words; check the manual for your exact model.

Power cycle to clear a flashing or error state

Heat pump · Vitocal IND-F

A power cycle can clear an indicator or error state that does not resolve on its own.

  1. Wait about 10 minutes for the problem to resolve itself.
  2. Disconnect the power.
  3. Reconnect the power and turn the unit on.
  4. If the problem persists, disconnect the power and contact customer service.

Applies to: Indoor unit window display

Source: Vitocal IND-F DLFSFBH operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Reset of manual-reset faults on the outdoor unit

Heat pump · Vitocal 100-AW AM2V

Some faults need a manual reset before the unit restarts.

  1. Shut off the breaker for the outdoor unit.
  2. Turn the breaker back on.

Applies to: Outdoor unit fault codes requiring manual reset

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 84. Written in our own words; check the manual for your exact model.

Restoring factory settings

Heat pump · Vitocal 100-AW

The Factory Settings option in the System Information menu restores the heat pump to its factory settings.

  1. Open the System Information menu.
  2. Select Factory Settings.
  3. Record any custom settings first, since they will be replaced by the factory defaults.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 58. Written in our own words; check the manual for your exact model.

One-key recovery of remote control defaults

Mini-split · Vitocal 100-S, DLCURA

Restores the remote's default mode and temperature limits. Some models only.

  1. Press On/Off for 2 seconds to enter One-Key Recovery. The display shows rS.
  2. Press OK to send the One-Key Recovery code.
  3. Check that the mode is back to COOLING and HEATING, minimum temperature 16°C and maximum 30°C.
  4. Press On/Off for 2 seconds to exit.

Applies to: DLCURA 18-60 (some models)

Source: Viessmann DLCURA service manual, p. 24. Written in our own words; check the manual for your exact model.

Remote battery handling

Mini-split · Vitocal IND-F

Use two AAA 1.5V alkaline batteries of one type only. Removing batteries erases all remote settings. Average life is about 6 months.

  1. Do not mix old and new batteries or different battery types.
  2. Remove the batteries if the remote will not be used for several weeks to avoid leakage damage.
  3. Reprogram the remote after installing new batteries.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 7. Written in our own words; check the manual for your exact model.

Remote control battery removal and reset

Mini-split · Vitocal IND-F

Removing the batteries erases the remote's current settings and returns it to the initial settings.

  1. Replace both remote batteries at the same time.
  2. After removing the batteries, press ON/OFF to wake the remote from standby.
  3. For extended shutdown, remove the remote batteries.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 12, p. 14. Written in our own words; check the manual for your exact model.

Remote control reset after battery removal

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Removing the remote batteries clears all current settings and returns the remote to its initial state in standby.

  1. Remove the remote batteries.
  2. Reinstall batteries (replace both at the same time).
  3. Press ON/OFF to wake the remote and set the unit again.

Applies to: Wireless remote

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 10-11. Written in our own words; check the manual for your exact model.

Reset air grille after filter cleaning

Mini-split · Vitocal Ind-O

Resets the air grille after the filter is reinstalled.

  1. Re-install the air filter.
  2. Press UP on the remote controller to reset the air grille (model A).
  3. On model B, re-install the air grille with the two screws and close the two screw covers.

Applies to: Model A and model B air grille

Source: Viessmann DLFSOAH Owner's Manual, p. 15. Written in our own words; check the manual for your exact model.

Reset horizontal louver position

Mini-split · Vitocal Ind-O

Louver Angle Memory restores the previous louver angle after power failure. Keep the angle from being set too short to avoid condensation dripping into the unit.

  1. Press the MANUAL button to reset the horizontal louver settings.

Applies to: Models with louver angle memory

Source: Viessmann DLFSOAH Owner's Manual, p. 13. Written in our own words; check the manual for your exact model.

Stop one-off DHW heating early

Water heater · Vitodens 100-W B1HE/B1KE

Use this only if the one-off DHW heating must end before the target temperature is reached.

  1. Call up the home screen.
  2. Select DHW, then confirm with OK.
  3. Select One-off heating (shown as active), then confirm with OK.
  4. Select Stop, then confirm with OK.
  5. Acknowledge the information with OK.

Applies to: One-off DHW heating

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Switch off the DHW hygiene program

Water heater · Vitodens 100-W B1HE/B1KE

Stops the scheduled hygiene heating cycle.

  1. Call up the home screen.
  2. Select DHW, then confirm with OK.
  3. Select Time program, then confirm with OK.
  4. Select DHW, then confirm with OK.
  5. Select DHW, then confirm with OK.
  6. Select Hygiene program, then confirm with OK.
  7. Select Stop, then confirm with OK.
  8. Acknowledge the information with OK.

Applies to: DHW hygiene program

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Settings shortcuts

Where the useful parameters live and what they are set to from the factory.

Access outdoor reset menu and adjust slope, shift, WWSD

Boiler · Versatronik 300

Outdoor reset must be enabled to use slope, shift and WWSD. Slope, shift and WWSD are the three adjustments.

  1. Press and hold ENTER for about 5 seconds.
  2. Use the arrow up or down key to select the Outdoor Reset menu.
  3. Press ENTER to select the value to change. EDIT appears on the screen.
  4. Use the arrow keys to set the new value.
  5. Press ENTER to accept the value, or ESC to exit to the main menu.

Applies to: Versatronik 300 cascade control

Source: Versatronik 300 Cascade Control manual, p. 37. Written in our own words; check the manual for your exact model.

Access the standard and extended menus

Boiler · Vitodens 200-W B2HA

The standard menu has the frequent settings. The extended menu has less-used settings such as time and holiday programs.

  1. If the screen saver is on, press any key except the one marked ? to wake the display.
  2. To reach the standard menu from elsewhere in the menu, keep pressing the back key until it appears.
  3. To reach the extended menu from the screen saver, press any key except ?, then press the key shown in the manual (not legible in extract).
  4. To reach the extended menu from elsewhere in the menu, press the key shown in the manual (not legible in extract).

Applies to: Programming unit navigation

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 29. Written in our own words; check the manual for your exact model.

Activate and end comfort (party) mode

Boiler · Vitotrol 200A

Temporarily changes the room temperature for several hours. DHW is boosted to the temperature set at the Vitotronic control unit. A changed room temperature is kept after party mode ends.

  1. To use a different room temperature, first set it with +/- and confirm with OK.
  2. Press the party mode key to start comfort mode.
  3. To end it early, press the party mode key again.
  4. Otherwise it ends automatically after 8 hours, or when the system switches to standard heating mode under the time program on the Vitotronic.

Applies to: Vitotrol 200A remote control

Source: Vitotrol 200A Installation, Operating and Service Instructions, p. 11. Written in our own words; check the manual for your exact model.

Activate and end economy mode

Boiler · Vitotrol 200A

Lowers the room temperature during standard heating mode to save energy. The economy symbol must be visible in the display.

  1. Press the economy mode key to start economy mode.
  2. Press the economy mode key again to end it.
  3. Otherwise it ends automatically when the system switches to reduced heating mode under the time program on the Vitotronic.

Applies to: Vitotrol 200A remote control

Source: Vitotrol 200A Installation, Operating and Service Instructions, p. 11. Written in our own words; check the manual for your exact model.

Activate economy mode

Boiler · Vitotronic 300-K

Lowers the room temperature during standard heating mode to save energy, for example when the building is empty for a few hours.

  1. Open the extended menu.
  2. Select "Heating".
  3. Select the heating circuit if needed.
  4. Select "Economy mode".

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Activate energy saving mode

Boiler · Vitotronic 300

Only available in the 'rw' heating program. Lowers the preset room temperature for a short time to heat more economically.

  1. Press the heating circuit selector button so it lights up.
  2. Press the energy saving button; the button lights and the energy saving display shows briefly.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Activate party mode

Boiler · Vitotronic 300

Gives heating and domestic hot water (if a DHW tank is fitted) for a short time, independent of the preset heating and time programs.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the party mode button; the party display appears and the party temperature flashes.
  4. Press the up or down button to change the party temperature if needed.
  5. Press OK to confirm and store the value.
  6. Close the hinged cover.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Activate the holiday program

Boiler · Vitocrossal 200 CI2

Holiday mode runs from 00:00 on the first day to 23:59 on the last day. Heating circuits in Heating mode drop to the reduced temperature. Circuits in Standby keep only frost protection. DHW heating is off, with frost protection active. In Apartment building mode, DHW stays on unless all circuits are in holiday mode. Not available for heating zones or for systems with a DHW tank with temperature switch (such as an Aquastat).

  1. Open the Holiday program function.
  2. Select the heating circuit.
  3. Set the First holiday and Last holiday dates.
  4. Confirm.
  5. To switch off, open Holiday program, select the heating circuit, and deselect.

Applies to: Heating circuits and DHW heating

Source: Vitocrossal 200 CI2 Operating Instructions, p. 22. Written in our own words; check the manual for your exact model.

Adjust display backlighting

Boiler · Vitocrossal 300 CA3B

Sets brightness separately for standby and for control use.

  1. From the home screen, open Menu, then Settings.
  2. Open Screen.
  3. Select Brightness standby or Brightness control.
  4. Choose the required value.
  5. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Adjust display contrast and brightness

Boiler · Vitotronic 300-K

Changes display contrast, and brightness for the control texts or the screen saver.

  1. Open the extended menu.
  2. Select "Settings".
  3. Select "Contrast" and set the value, or select "Brightness".
  4. For brightness, choose "Control" to make menu text clearer, or "Screen saver" to change the screen saver brightness.
  5. Set the required brightness.

Applies to: Vitotronic 300-K, MW1B only

Source: Vitotronic 100/300-K operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Adjust display contrast on Vitocontrol-S

Boiler · Vitocontrol-S VD2/CT3/CM2

The display contrast can be darkened or lightened with button combinations.

  1. Press OK and + together to darken the display.
  2. Press OK and - together to lighten the display.

Applies to: Vitocontrol-S VD2/CT3/CM2 control unit

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 108. Written in our own words; check the manual for your exact model.

Adjust heating curve slope and shift for a heating circuit

Boiler · Vitotronic 300 GW6B

Slope and shift are set separately for each heating circuit. Shift moves the curve up or down in parallel. The example graph on the page is not transcribed here.

  1. From the home screen, tap Menu.
  2. Choose Heating circuit 1, 2 or 3.
  3. Tap Heating.
  4. Tap Heating curve.
  5. Use +/- to set the required Slope or Shift value.
  6. Tap OK to confirm.

Applies to: Vitotronic 300 GW6B boiler control unit, all heating circuits

Source: Vitotronic 300 GW6B installation and service instructions, p. 56. Written in our own words; check the manual for your exact model.

Adjust normal and reduced room temperature

Boiler · Vitotronic 200-H

Normal (day) room temperature is chosen with the rotary dial and is applied automatically after about 2 seconds. Reduced (night) room temperature is set separately.

  1. For normal room temperature, turn the rotary dial to the desired day temperature.
  2. For reduced room temperature, press the night temperature button (symbol not legible in the source).
  3. Change the value with the up or down arrow.
  4. Confirm with OK.
  5. Example: changing normal temperature from 20°C to 26°C / 68°F to 79°F; changing reduced temperature from 5°C to 14°C / 41°F to 57°F.

Applies to: Vitotronic 200-H heating circuit

Source: Vitotronic 200-H installation and service instructions, p. 23. Written in our own words; check the manual for your exact model.

Adjust room temperature and heating program in the standard menu

Boiler · Vitocrossal 300 CU3A

The standard menu covers the most-used settings for the heating circuit shown in the header. Heating programs are standby with frost protection, DHW only, and heating plus DHW. The display returns to the standard menu about 2 minutes after the last change.

  1. Set the room temperature with the arrow keys, then press OK to confirm.
  2. Select the heating program with the arrow keys, then press OK to confirm.

Applies to: Vitocrossal 300 CU3A with Vitotronic control

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 47. Written in our own words; check the manual for your exact model.

Adjust room temperature setback

Boiler · Vitodens 200-W

Example from the manual: changing the setback from 41 F to 57 F (5 C to 14 C). Steps 1 and 8 are not legible in the text.

  1. Select 'Heating'.
  2. Select the heating circuit.
  3. Press OK.
  4. Select the red room temperature setpoint (setback), then press OK.
  5. Change the value with the arrow keys.
  6. Accept with OK.

Applies to: Heating circuits with room temperature control

Source: Vitodens 200-W B2HA service instructions, p. 36. Written in our own words; check the manual for your exact model.

Adjust room temperature setpoint

Boiler · Vitodens 200-W

Example from the manual: changing the setpoint from 68 F to 79 F (20 C to 26 C). Steps 1 and 8 are not legible in the text.

  1. Select 'Heating'.
  2. Select the heating circuit.
  3. Press OK.
  4. Select 'Room temperature setpoint', then press OK.
  5. Change the value with the arrow keys.
  6. Accept with OK.

Applies to: Heating circuits with room temperature control

Source: Vitodens 200-W B2HA service instructions, p. 36. Written in our own words; check the manual for your exact model.

Adjust the heating curve slope and shift

Boiler · Vitocrossal 200 CI2

Adjust slope and shift in weather-compensated operation. The graph updates as you change the values.

  1. Open the "Heating" function.
  2. Select the heating zone or heating circuit.
  3. Open "Heating curve".
  4. Set the required Slope and Shift values.
  5. Confirm.

Applies to: Weather-compensated operation

Source: Vitocrossal 200 CI2 Operating Instructions, p. 21. Written in our own words; check the manual for your exact model.

Adjusting display contrast

Boiler · Vitotronic 200-H

Contrast of the display window can be changed from the programming unit.

  1. Open the hinged cover on the programming unit.
  2. Hold the contrast key and press the up or down button at the same time to adjust contrast.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Boost heating and rapid setback

Boiler · Vitotronic 200-H

Temporary room temperature changes that stop when the set room temperature is reached.

  1. Boost heating: raise set room temperature by at least 2 K with the party key. It also starts on change from reduced to standard temperature and at start-up optimisation.
  2. Rapid setback: lower set room temperature by at least 2 K with the energy saving key. It also starts on change from standard to reduced temperature and at shut-down optimisation.

Applies to: HK1S, HK3S

Source: Vitotronic 200-H installation and service instructions, p. 31. Written in our own words; check the manual for your exact model.

Button use: scrolling, editing and exiting

Boiler · Versatronik 300

The control has four buttons: ESC, Arrow Up, Arrow Down and ENTER. Arrows scroll screens and menu items. ENTER opens the menu and edits values.

  1. Use UP and DOWN to scroll the main screens or menu items.
  2. Press ENTER on a setting to edit it.
  3. Press ENTER again to make the new value take effect.
  4. Press ESC to exit a screen or menu and return to the ST (supply temperature) screen.

Applies to: Versatronik 300 user interface

Source: Versatronik 300 Cascade Control manual, p. 27-29. Written in our own words; check the manual for your exact model.

Call up and change coding 1 addresses

Boiler · Vitotronic 200-H

Method for coding 1. Key symbols were not legible in the extracted text.

  1. Press the 9 and w keys together for about 2 seconds.
  2. Select the coding address with the up or down key; the address flashes. Confirm to show the value.
  3. Change the value with the up or down key and confirm.
  4. The display briefly shows 'Accepted', then the address flashes again.
  5. Select further addresses with the up or down key.
  6. To exit, press the 9 and w keys together for about 1 second.

Applies to: Vitotronic 200-H coding 1

Source: Viessmann Vitotronic 200-H installation and service instructions, p. 50. Written in our own words; check the manual for your exact model.

Call up coding 1

Boiler · Vitotronic 100 GC1

Entry to the coding 1 address list.

  1. Press 9 and w together for about two seconds, until the first arrow appears in the display.
  2. Select the coding address with the up or down arrow; the address flashes. Confirm to make the value flash.
  3. Change the value with the up or down arrow and confirm. The value is stored and stops flashing after about 2 seconds.
  4. Select further addresses with the arrows.
  5. Press 9 and w together for about one second to exit.

Applies to: Vitotronic 100 GC1 coding 1

Source: Vitotronic 100 GC1 coding, p. 138. Written in our own words; check the manual for your exact model.

Call up coding 2

Boiler · Vitotronic 100 GC1

Entry to the coding 2 address list.

  1. Press w and rw together for about two seconds, until the first two arrows appear in the display; confirm.
  2. Select the coding address with the up or down arrow; the address flashes. Confirm to make the value flash.
  3. Change the value with the up or down arrow and confirm. The value is saved and stops flashing after about 2 seconds.
  4. Select further addresses with the arrows.
  5. Press w and rw together for about one second to exit.

Applies to: Vitotronic 100 GC1 coding 2

Source: Vitotronic 100 GC1 coding 2, p. 140. Written in our own words; check the manual for your exact model.

Calling up system configuration parameters

Boiler · Vitodens 100-W, B1HE, B1KE

Route to the parameter groups General, Boiler and DHW. Parameters can also be set with the Vitoguide mobile software tool.

  1. Open the service menu with the button combination.
  2. Select System configuration and press OK.
  3. Select the required group (General, Boiler or DHW) and press OK.
  4. Select the parameter, press OK, set the value and press OK to confirm.

Applies to: Vitodens 100-W

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 61. Written in our own words; check the manual for your exact model.

Calling up the main menu on the programming unit

Boiler · Vitocrossal 300 CA3B Dual Fuel

The main menu gives access to all settings, scans, heating defaults and time programs available at the system and lead control unit. The footer buttons return to the home screen, go back one menu level or cancel a setting, open help text, show fault or service messages, and scroll the menu.

  1. If the screensaver is on, tap the display, then tap Menu.
  2. From anywhere in the menu, tap the menu button, then tap Menu.
  3. Use the footer buttons to go home, go back, open help, view faults or service messages, or scroll.

Applies to: Vitocrossal 300 CA3B Dual Fuel programming unit and service display

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 15. Written in our own words; check the manual for your exact model.

Central control of heating circuits

Boiler · Vitotronic 300 GW6B

Coding 7a in the General group sets one heating circuit as the central control. Its operating and holiday program then applies to all other heating circuits. Those circuits show 'Central control' on the display. Any holiday programs already set on them are deleted. Party and economy modes cannot be enabled on every control unit.

  1. Set coding 7a in the General group to program central control to one heating circuit.
  2. Check the other circuits show 'Central control' to confirm.

Applies to: Multiple heating circuits on one system

Source: Vitotronic 300 GW6B installation and service instructions, p. 78. Written in our own words; check the manual for your exact model.

Change and save advanced parameters

Boiler · Vitotron 100 VLN2

Move through the parameters with the right arrow, change values with the up and down arrows, then save by leaving advanced settings.

  1. Use the up and down arrows (5, 6) to select the value you want.
  2. Press the right arrow button (4) to move to the next parameter.
  3. When finished, press and hold the power button (9) until the display returns to blank stand-by with the intermittent red dot.
  4. Press the power button (9) to turn the boiler back on.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 17. Written in our own words; check the manual for your exact model.

Change AUX input mode to 0-10 VDC

Boiler · Versatronik 300 Cascade Control

The AUX input is set to DEMAND from the factory and must be changed to 0-10 VDC for BMS control.

  1. Press and hold ENTER for 5 seconds.
  2. Press the up arrow until Specifications appears and press ENTER.
  3. Press the up arrow until AUX Mode shows and press ENTER to set 0-10 VDC mode.
  4. Press ESC to exit to the set point screen.

Applies to: Versatronik 300 Cascade Control, AUX input

Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 12. Written in our own words; check the manual for your exact model.

Change boiler water temperature

Boiler · Vitotronic 100, GC1

Single-boiler systems only. In a multi-boiler system the tr button has no function and the current boiler temperature stays on the display.

  1. Press the tr button. The previous boiler water temperature setting flashes.
  2. Press the up/down button until the required temperature shows.
  3. Confirm with the confirm button (its symbol is not legible in the extract). The value stops flashing and is stored.

Applies to: Single-boiler systems

Source: Vitotronic 100, GC1 operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Change calorific value or correction factor

Boiler · Vitocrossal 200 CI2

Changes the calculated gas consumption data. The consumption value is not suitable for billing purposes. Not valid for systems with a DHW tank with a temperature switch (such as an Aquastat).

  1. Open Settings, then 'Energy cockpit'.
  2. Select 'Calorific value' or 'Correction factor'.
  3. Enter the value.
  4. Confirm.

Applies to: Energy cockpit

Source: Vitocrossal 200 CI2 operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Change display language

Boiler · Vitotronic 200, Vitotronic 300-K

The display may start in German at commissioning. The language is changed through the extended menu.

  1. Open the extended menu.
  2. Select Settings, then Language.
  3. Pick the required language with the selector.
  4. Press OK to accept.

Applies to: Vitotronic 300-K and Vitotronic 200

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 27. Written in our own words; check the manual for your exact model.

Change domestic hot water temperature

Boiler · Vitotronic 100, GC1

Not available in multi-boiler systems, where the Vitotronic 100 cannot control a DHW tank.

  1. Press the DHW button. The previous DHW temperature setting flashes.
  2. Press the up/down button until the required temperature shows.
  3. Confirm with the confirm button. The value stops flashing and is stored.

Applies to: Single-boiler systems with DHW tank

Source: Vitotronic 100, GC1 operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Change heating curve slope and level (extended menu)

Boiler · Vitodens 200-W

Changes the heating curve to suit the system. Use the extended menu.

  1. Enter the extended menu.
  2. Select 'Heating' and press OK.
  3. Select the heating circuit and accept with OK.
  4. Select 'Heating curve' and press OK.
  5. Select 'Slope or level' and press OK.
  6. Change the value with the control dial.
  7. Select the heating curve that matches the system requirements.
  8. Exit.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Change heating curve slope and shift (extended menu)

Boiler · Vitodens 222-F

Adjusts the heating curve slope or shift for a heating circuit in the extended menu.

  1. Open the extended menu.
  2. Select Heating, then press OK.
  3. Select the heating circuit.
  4. Accept with OK.
  5. Select Heating curve and press OK.
  6. Select Slope or Shift and press OK.
  7. Change the value with the arrow keys.
  8. Select the heating curve that matches the system requirements.
  9. Exit the menu.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F B2TB service instructions, p. 43. Written in our own words; check the manual for your exact model.

Change heating curve slope or level (extended menu)

Boiler · Vitodens 200-W B2HA

Use the extended menu to change the slope or level of the heating curve so it matches the system.

  1. Open the extended menu.
  2. Select Heating, then press OK.
  3. Select the heating circuit and accept with OK.
  4. Select Heating curve, then press OK.
  5. Select Slope or Level, press OK.
  6. Change the value with the arrow keys and select the curve that fits the system.
  7. Exit the menu.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 36. Written in our own words; check the manual for your exact model.

Change measuring units

Boiler · Vitocrossal 300 CA3B

Switches the display between metric and imperial units.

  1. From the home screen, open Menu, then Settings.
  2. Open Measuring units.
  3. Select Metric or Imperial.
  4. Tap OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 30. Written in our own words; check the manual for your exact model.

Change room temperature and heating program from standard menu

Boiler · Vitodens 200-W

Room temperature and heating program can be changed from the standard menu. Heating programs are standby with frost protection, DHW only, and heating and DHW.

  1. Use the arrow keys to set the required room temperature, then press OK.
  2. Select the required heating program with the arrow keys, then press OK.
  3. Wait 2 minutes or exit to return to the standard menu automatically.

Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 31. Written in our own words; check the manual for your exact model.

Change room temperature and heating program from the standard menu

Boiler · Vitodens 222-F

Room temperature and the heating program are set from the standard menu. Changes are confirmed with OK.

  1. Press the keys to set the room temperature to the required value, then press OK.
  2. Press the keys to select the required heating program, then press OK.
  3. Heating program options: standby with frost protection monitoring, DHW only, or heating and DHW.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 32. Written in our own words; check the manual for your exact model.

Change room temperature or heating program in the standard menu

Boiler · Vitodens 200-W B2HA

The standard menu covers the most-used settings for the heating circuit shown in the header.

  1. Press the keys shown in the manual (not legible in extract) to set room temperature, then press OK to confirm.
  2. Select a heating program: 9 standby with frost protection, w DHW only, or wz heating and DHW.
  3. Press OK to confirm.
  4. The display returns to the standard menu about 2 minutes after the last change.

Applies to: Programming unit standard menu

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 28. Written in our own words; check the manual for your exact model.

Change room temperature set-point

Boiler · Vitodens 222-F

Changes the standard room temperature set-point for a heating circuit using the control unit menu.

  1. Open the heating menu (step 1 icon not legible on the page).
  2. Select Heating.
  3. Select the heating circuit.
  4. Press OK.
  5. Select room temperature set-point and press OK.
  6. Change the value with the arrow keys.
  7. Accept with OK.
  8. Exit the menu.

Applies to: Vitodens 222-F B2TB with Vitotronic control

Source: Vitodens 222-F B2TB service instructions, p. 43. Written in our own words; check the manual for your exact model.

Change room temperature setback

Boiler · Vitodens 200-W

Set the reduced (setback) room temperature. Example in the manual: 41 F to 57 F (5 C to 14 C).

  1. Open the heating menu (button symbols in step 1 and 8 are not legible in the extracted text).
  2. Select 'Heating'.
  3. Select the heating circuit.
  4. Press OK.
  5. Select 'Red. room temperature setpoint' and press OK.
  6. Change the value with the control dial.
  7. Accept with OK.
  8. Exit the menu.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Change room temperature setpoint

Boiler · Vitodens 200-W

Set the comfort room temperature for the heating circuit from the standard menu. Examples in the manual: 68 F to 79 F (20 C to 26 C).

  1. Open the heating menu (button symbols in step 1 and 8 are not legible in the extracted text).
  2. Select 'Heating'.
  3. Select the heating circuit.
  4. Press OK.
  5. Select 'Room temperature setpoint' and press OK.
  6. Change the value with the control dial.
  7. Accept with OK.
  8. Exit the menu.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Change standard room temperature setpoint and setback

Boiler · Vitodens 200-W B2HB

Examples in the manual: setpoint 68F to 79F (20C to 26C); setback 41F to 57F (5C to 14C).

  1. Select Heating from the standard menu.
  2. Select the heating circuit and press OK.
  3. Select room temperature setpoint (or the setback setpoint) and press OK.
  4. Change the value and accept with OK.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB service instructions, p. 39. Written in our own words; check the manual for your exact model.

Change temperature unit

Boiler · Vitodens 200-W, Vitotronic 200, Vitocrossal 300

Factory setting is °C.

  1. Open the extended menu and select "Settings", then "Temperature unit".
  2. Select °C or °F.

Applies to: Vitotronic 200

Source: Viessmann Vitotronic 200 Operating Instructions, p. 11. Written in our own words; check the manual for your exact model.

Change temperature unit between °C and °F

Boiler · Vitotronic 100 GC1B, Vitotronic 300-K MW1B

Factory setting is °C on both controls. Vitotronic 100 uses the key sequence shown on the display; Vitotronic 300-K uses the extended menu.

  1. Vitotronic 300-K: open the extended menu, select Settings, then Temperature unit.
  2. Vitotronic 300-K: select °C or °F.
  3. Vitotronic 100: press the settings key until its symbol flashes.
  4. Vitotronic 100: press the selector key until the temperature unit symbol flashes, then press OK.
  5. Vitotronic 100: choose °C or °F with the selector key, then press OK to save.

Applies to: Vitotronic 100 GC1B and Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Change the adjustable high limit (maximum boiler water temperature)

Boiler · Vitotronic 100

The adjustable high limit caps the boiler water temperature on a call for heat. The default range is 104 to 167 °F (40 to 75 °C). The contractor can raise the range to 104 to 212 °F (40 to 100 °C).

  1. Choose the boiler water temperature the heating contractor recommends.
  2. Turn the selector clockwise to raise the limit.
  3. Turn the selector counter-clockwise to lower the limit.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B operating manual, p. 7. Written in our own words; check the manual for your exact model.

Change the boiler (burner) sequence from the control panel

Boiler · Vitocrossal 300 CA3B Dual Fuel

Boiler lead order is changed from the main menu, not a coding address.

  1. Tap Menu.
  2. Tap Boiler sequence.
  3. Select the required boiler sequence (burner sequence).
  4. Confirm with OK.

Applies to: Cascade boilers controlled by the Vitocrossal 300 control unit

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 45. Written in our own words; check the manual for your exact model.

Change the boiler sequence (burner sequence)

Boiler · Vitocrossal 300 CA3B

Select the boiler sequence from the control unit menu. Button names are not legible in this extract.

  1. Tap the menu buttons shown on the control unit (page image not legible).
  2. Open the "Boiler sequence" entry.
  3. Select the required boiler sequence (burner sequence).
  4. Confirm the selection.

Applies to: Cascade control unit

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 45. Written in our own words; check the manual for your exact model.

Change the default value shown on the scan key

Boiler · Vitotrol 300

Choose which value appears first when the scan key is pressed. Options include outside, supply, boiler water, DHW, return water and room temperature, flue gas temperature, time and date, where the sensor is installed.

  1. Press the scan key. The outside temperature is shown.
  2. Use the up/down keys to select the value.
  3. Confirm the selection.

Applies to: Vitotrol 300 remote control, factory default display

Source: Vitotrol 300 operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Change the DHW temperature

Boiler · Vitocontrol-S, VD2/CT3/CM2

In a multi-boiler system the Vitotronic 100 GC1 has no function for DHW temperature, so it is set on the Vitocontrol-S.

  1. Open the hinged cover on the programming unit.
  2. Press the DHW temperature button; the current setting flashes.
  3. Adjust the value with the up or down button.
  4. Confirm; the value stops flashing and is stored.
  5. Close the hinged cover.

Applies to: Desired DHW temperature

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Change the DHW temperature setpoint

Boiler · Vitotrol 300

Set the domestic hot water temperature at the remote control. The temperature value flashes while you edit it.

  1. Open the flip-down cover of the remote control.
  2. Select the DHW temperature. The value flashes.
  3. Use the up/down keys to enter the desired temperature.
  4. Confirm. The value stops flashing and is saved.
  5. Close the flip-down cover.

Applies to: Vitotrol 300 remote control, DHW temperature setpoint

Source: Vitotrol 300 operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Change the display language

Boiler · Vitotrol 300

English is the factory language. Change it from the outside temperature screen.

  1. Open the flip-down cover of the remote control.
  2. Scroll until the outside temperature screen appears.
  3. Press the key until the wanted language shows.
  4. Confirm; the display returns to the time.
  5. Close the flip-down cover.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Change the display language (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1B

Selects the language used on the control display.

  1. Open the extended menu.
  2. Select Settings, then Language.
  3. Select the required language.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Change the heating curve slope and level

Boiler · Vitodens 200-W B2HB

Changed in the extended menu to match the heating system requirements.

  1. Open the extended menu.
  2. Select Heating, then press OK.
  3. Select the heating circuit.
  4. Accept with OK.
  5. Select Heating curve, then press OK.
  6. Select Slope or Level, then press OK.
  7. Change the value with the arrow keys.
  8. Select the heating curve that suits the system requirements.
  9. Exit the menu.

Applies to: Vitodens 200-W B2HB heating circuits

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Change the heating curve slope and shift

Boiler · Vitodens 200-W B2HB

Done from the extended menu under the heating circuit selection.

  1. Call up the extended menu.
  2. Select Heating, press OK, then select the heating circuit.
  3. Accept with OK, then select Heating curve and press OK.
  4. Select Slope or Shift and press OK, change the value, and select the curve matching the system.
  5. Exit the menu.

Applies to: Vitodens 200-W B2HB heating circuits

Source: Vitodens 200-W B2HB service instructions, p. 39. Written in our own words; check the manual for your exact model.

Change the normal (day) room temperature

Boiler · Vitotronic 300

Sets the room temperature used during the normal heating periods. Factory setting is 20°C / 68°F, active from 06:00 to 22:00. Adjustable from 3 to 37°C (37 to 99°F).

  1. Press the heating circuit selector button so it lights up.
  2. Turn the ts selector knob to the required temperature.
  3. Wait a moment; the display returns to showing the boiler temperature.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Change the normal room temperature

Boiler · Vitotrol 300

Normal room temperature is adjustable from 50 to 86 °F (10 to 30 °C). Default is 68 °F / 20 °C from 06:00 to 22:00.

  1. Open the flip-down cover of the remote control.
  2. Press the normal room temperature key; the display shows the setting.
  3. Use the up/down keys to choose the temperature.
  4. Press to confirm; the temperature stops flashing and is saved.
  5. Close the cover.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Change the operating mode from the standard display

Boiler · Versatronik 200

The operating mode can be changed quickly from the standard display. Party and Reducing functions can also be set with the function keys, with the rotary knob setting the length of the increase or interruption.

  1. From the standard display, press the function button under the operating mode line.
  2. Turn the rotary knob to select the mode.
  3. Press OK to save, or End to leave without saving.
  4. For Party or Reducing, press the matching function button and set the duration with the rotary knob.
  5. Turn the knob left to apply Party or Reducing for whole days, for example Reduced 5 Days.

Applies to: Versatronik 200 System Control, operating mode

Source: Versatronik 200 manual, p. 67. Written in our own words; check the manual for your exact model.

Change the operating program for a heating circuit

Boiler · Vitocrossal 300 CA3B

The operating program is set at the system and lead boiler section 1 only. Choose Heating and DHW, DHW only, or Standby mode for each heating circuit.

  1. From the home screen, select Heating circuit 1, 2 or 3.
  2. Open the operating program selection.
  3. Select the required operating program.
  4. Confirm the setting.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B operating instructions, p. 22. Written in our own words; check the manual for your exact model.

Change the reduced (night) room temperature

Boiler · Vitotronic 300

Sets the room temperature used during the reduced periods. Factory setting is freeze-up protection at 3°C / 37°F, active from 22:00 to 06:00. Adjustable from 4 to 37°C (39 to 99°F). Setting 3°C shows 'Freeze-up protection' in the display.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the reduced-temperature button; the current setting flashes.
  4. Press the up or down button until the required value appears.
  5. Press OK to confirm; the value stops flashing and is stored.
  6. Close the hinged cover.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Change the reduced room temperature

Boiler · Vitotrol 300

Reduced room temperature is adjustable from 37 to 99 °F (3 to 37 °C). Default is frost protection at 37 °F / 3 °C from 22:00 to 06:00.

  1. Open the flip-down cover of the remote control.
  2. Press the reduced room temperature key.
  3. Use the up/down keys to choose the temperature.
  4. Press to confirm; the value is saved.
  5. Close the cover.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Change the room temperature set-point

Boiler · Vitodens 200-W

Example: change the set-point from 68 °F to 79 °F (20 °C to 26 °C).

  1. Select 'Heating'.
  2. Select the heating circuit.
  3. Press OK.
  4. Select room temperature set-point and press OK.
  5. Change the value with the selector.
  6. Press OK to accept, then exit.

Applies to: Vitodens 200-W B2HA 112–530

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 41. Written in our own words; check the manual for your exact model.

Change the room temperature setback

Boiler · Vitodens 200-W B2HB

Sets the reduced room temperature setpoint. Example: 41°F to 57°F (5°C to 14°C).

  1. Select Heating.
  2. Select the heating circuit.
  3. Press OK.
  4. Select Red. room temperature setpoint, then press OK.
  5. Change the value with the arrow keys.
  6. Accept with OK.
  7. Exit the menu.

Applies to: Vitodens 200-W B2HB heating circuits

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Change the room temperature setpoint or setback for a heating circuit

Boiler · Vitodens 200-W B2HA

Use the control unit's heating menu to set the day setpoint or the setback (reduced) temperature for each heating circuit. Some steps in the source sequence are missing button symbols, so follow the menu labels.

  1. Select Heating from the menu.
  2. Choose the heating circuit.
  3. Press OK, then select the room temperature setpoint (or reduced setpoint for setback).
  4. Press OK, change the value with the arrow keys, then accept with OK.
  5. Exit the menu.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 36. Written in our own words; check the manual for your exact model.

Change the room temperature with the rotary knob

Boiler · Versatronik COMO OT

In normal mode the system follows the set room temperature (default 20°C/68°F). The knob moves it up to ±5°C/9°F, about 1°C/2°F per dot. The night (economy) temperature is not changed.

  1. Turn the rotary knob clockwise to make the room warmer.
  2. Turn it counterclockwise to make the room colder.
  3. Check that the night (economy) temperature is unchanged after adjusting.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT manual, p. 16. Written in our own words; check the manual for your exact model.

Change the standard room temperature setpoint

Boiler · Vitodens 200-W B2HB

Sets the room temperature setpoint from the standard menu. Example: 68°F to 79°F (20°C to 26°C).

  1. Select Heating.
  2. Select the heating circuit.
  3. Press OK.
  4. Select Room temperature setpoint, then press OK.
  5. Change the value with the arrow keys.
  6. Accept with OK.
  7. Exit the menu.

Applies to: Vitodens 200-W B2HB heating circuits

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Changing heating curve slope and shift

Boiler · Vitotronic 300

Adjusts slope or shift for one heating circuit. Changing the shift moves the curve up or down in parallel.

  1. Tap Menu.
  2. Tap Heating circuit 1, 2 or 3.
  3. Tap Heating.
  4. Tap Heating curve.
  5. Use +/- to set the required slope or shift.
  6. Tap OK to confirm.

Applies to: Each heating circuit, single boiler and cascade

Source: Vitotronic 300, GW6B installation and service instructions, p. 56. Written in our own words; check the manual for your exact model.

Changing slope or shift of the heating curve

Boiler · Vitocontrol-S, VD2/CT3/CM2

Slope changes the steepness of the heating curve. Shift moves the curve up or down. Use the change table as a guide and change one value at a time.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button; the button lights up.
  3. Press the button for Slope or the button for Shift.
  4. Press the button(s) until the required value is displayed.
  5. Press the confirm button; the display shows the boiler temperature.
  6. Close the hinged cover.

Applies to: Vitocontrol-S, VD2/CT3/CM2 heating circuits

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Changing the set room temperature with the dial

Boiler · Versatronik

In Normal mode the set room temperature defaults to 20°C (68°F). The dial changes it by up to ±5°C (±9°F). Each dot is about 1°C (2°F). The night (economy) temperature is not changed.

  1. In Normal mode, turn the dial clockwise to warm the room.
  2. Turn the dial counterclockwise to cool the room.
  3. Read the new set point in the display.

Applies to: Versatronik COMO OT in Normal mode

Source: Versatronik COMO OT manual, p. 16. Written in our own words; check the manual for your exact model.

Changing the space heating time program

Boiler · Vitotronic 200-H

Space heating time phases are set per day or for all days together. Up to 4 phases per day.

  1. Open the hinged cover on the programming unit.
  2. Press the heating time program button; the display shows the heating program.
  3. Press up or down to choose '1-7' (all days) or a single weekday.
  4. Confirm; set the ON and OFF times for heating phase 1 and confirm each.
  5. Set phases 2 to 4 the same way, then close the cover.
  6. After the last confirmation the basic display returns.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 15. Written in our own words; check the manual for your exact model.

Changing the standard display

Boiler · Vitotrol 300A

Show heating circuit 2 or 3 details in the header of the standard display.

  1. Open the extended menu.
  2. Select Settings, then Standard display.
  3. Select the heating circuit.

Applies to: Vitotrol 300A remote control

Source: Vitotrol 300A operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Choose automatic or individual DHW time program

Boiler · Vitotronic 300

Automatic mode runs domestic hot water in parallel with the heating program, starting 30 minutes earlier. The DHW re-circulation pump follows the DHW time program. Individual mode lets you set your own times.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the DHW time program button; 'DHW time program' appears.
  4. Use up or down to select 'Automatic?' or 'Individual?'.
  5. Press OK to confirm.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 15. Written in our own words; check the manual for your exact model.

Coding address groups for temperature and cascade control

Boiler · Vitocontrol-S VD2/CT3/CM2

These coding address groups affect boiler temperature control and cascade control. Full descriptions are in the coding overview.

  1. Boiler temperature control: coding 02 to 06, 08 to 0b and 13 to 1C.
  2. Cascade control: coding 35 to 3F and 41 to 4A.
  3. Boiler sequence is set with coding 2 and the boiler sequence selection.

Applies to: Vitocontrol-S VD2/CT3/CM2 cascade

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 123. Written in our own words; check the manual for your exact model.

Coding addresses for remote control functions

Boiler · Vitotronic 300 GW2

Function changes for Vitotrol 200 and Vitotrol 300 are made through coding addresses A0, b0 to b9, C0 to C2, E1 and E2. E1 sets the room temperature setting range.

  1. Refer to the coding overview in the manual.
  2. Change the required coding address on the control unit.

Applies to: Vitotrol 200 and Vitotrol 300

Source: Vitotronic 300, Model GW2 installation and service instructions, p. 106, 108. Written in our own words; check the manual for your exact model.

Coding addresses referenced in these pages

Boiler · Vitotronic 100 GC1

Coding address 06 holds the high limit setting that was changed. Coding address 40 sets the valve actuator operating time.

  1. After changing the high limit cams, check coding address 06.
  2. Set valve operating time (5 to 199 sec) at coding address 40.

Applies to: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, pp. 40, 47-48. Written in our own words; check the manual for your exact model.

Coding groups

Boiler · Vitocrossal 300 CA3B

Coding is split into groups: General, Burner control unit, DHW, Solar, Heating circuit 1/2/3, Boiler, Cascade, and All coding. All coding lists every item in ascending order, except the Solar group. Heating circuit names change if the circuits were named individually.

  1. Select the group you need.
  2. Select the required value from the tables in the coding section.
  3. Tap the accept button to save.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 80. Written in our own words; check the manual for your exact model.

Codings changeable in coding level 1

Boiler · Vitotronic 200

Only these addresses can be changed in coding level 1. The list may vary with the installed equipment.

  1. Change system type.
  2. Change burner type.
  3. Set maximum boiler water temperature.
  4. Set DHW priority (boiler circuit).
  5. Set summer energy saving mode (boiler circuit).
  6. Set DHW priority (mixing valve circuit).
  7. Set summer energy saving mode (mixing valve circuit).
  8. Set supply low limit (mixing valve circuit).
  9. Set supply high limit (mixing valve circuit).

Applies to: Vitotronic 200 KW2, coding level 1

Source: Vitotronic 200 service instructions, p. 26. Written in our own words; check the manual for your exact model.

Comfort mode on a heating circuit

Boiler · Vitotronic 300-K

Comfort mode heats the rooms to the set comfort room temperature, and DHW is heated first if the contractor has not changed the settings.

  1. From the home screen, select the heating circuit in the header.
  2. Select comfort mode and set it to ON.
  3. Set the required room temperature for comfort mode and confirm.
  4. To end it, set comfort mode to OFF and confirm.

Applies to: Heating circuits on Vitotronic 300-K

Source: Vitotronic 300-K MW2C operating instructions, p. 15. Written in our own words; check the manual for your exact model.

Comfort mode ON/OFF

Boiler · Vitocrossal 300 CA3B

Comfort mode heats the rooms to a set target temperature. When enabled, DHW is heated to its set temperature first, before central heating starts. The DHW recirculation pump runs if installed.

  1. From the home screen, select the heating circuit.
  2. Select Comfort mode.
  3. Set ON to enable it, then set the required room temperature target and confirm, or set OFF to disable it.
  4. Confirm the setting.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Comfort mode: start and end

Boiler · Vitotronic 300-K

Comfort mode heats rooms to a set comfort temperature. DHW is heated first if the contractor has not changed the settings, and the DHW recirculation pump runs if installed. It ends automatically after 8 hours or when the time program switches to standard heating.

  1. Start: Menu, Heating, Heating circuit 1/2/3, Comfort mode, select the white frame, tap OK, set the comfort room temperature, tap OK.
  2. End: Menu, Heating, Heating circuit 1/2/3, Comfort mode, the white frame resets, tap OK.
  3. Repeat for each heating circuit connected to the Vitotronic 300-K.
  4. To stop central heating instead, set the operating program to DHW only or Standby mode and tap OK.

Applies to: Central heating for each heating circuit

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 15. Written in our own words; check the manual for your exact model.

Copy, change or delete time phases

Boiler · Vitocrossal 300 CA3B Dual Fuel

A time program for one day can be copied to other days. Individual time phases can also be edited or removed.

  1. To copy: Menu, Heating, Heating circuit 1, Time program heating, select the source day, tap Copy, select the target days, then press OK.
  2. To change a start point: Menu, Heating, Heating circuit 1, Time program heating, select the day, tap Edit, select the time phase, adjust the start point, then tap OK.
  3. To delete a time phase: Menu, Heating, Heating circuit 1, Time program heating, select the day, tap Edit, select the time phase, tap x, then tap OK.

Applies to: Time program heating, Heating circuit 1

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Deleting a time phase

Boiler · Vitocrossal 300 CU3A

Two ways to remove a time phase in the time program.

  1. Set the end time of the phase to the same time as its start point.
  2. Or set the start point to a time before 00:00 h. The display then shows the phase as - - : - -.

Applies to: Central heating and DHW time programs

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 19. Written in our own words; check the manual for your exact model.

Designate heating circuit names

Boiler · Vitodens 200-W B2HA

Heating circuits default to Heating circuit 1, 2 and 3 (if installed). Names can be changed to suit the system. The text refers to the Operating Instructions for the entry steps.

  1. Refer to the Operating Instructions for entering heating circuit names.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 15. Written in our own words; check the manual for your exact model.

DHW default display controls

Boiler · Vitocrossal 200 CI2

The DHW default display lets you adjust the DHW temperature, turn DHW heating on or off, open the DHW time program and start or stop one-off DHW heating. This display is not available on systems with a storage tank that uses a temperature switch (such as an Aquastat).

  1. Use the up or down buttons to change the DHW temperature.
  2. Use the on/off button to turn DHW heating ON or OFF.
  3. Use the time program button to open the DHW time program.
  4. Use the one-off DHW heating button to start or stop a one-off heat-up outside the time program.

Applies to: Vitocrossal 200 CI2 DHW display, not for Aquastat tank systems

Source: Vitocrossal 200 CI2 operating instructions, p. 15. Written in our own words; check the manual for your exact model.

DHW heating once outside the time program

Boiler · Vitocrossal 300 CA3B

This starts one DHW heating cycle outside the time program. It avoids unintended central heating at standard room temperature.

  1. Make sure the operating program Heating and DHW or DHW only is set for at least one heating circuit.
  2. Enable Comfort mode.
  3. Disable Comfort mode straight away.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

DHW recirculation pump depends on coding address 53

Boiler · Vitodens 200-W B2HA

The function of the DHW recirculation pump in the layouts is set by the coding of address 53. The diagrams flag this with a footnote on each layout.

  1. Set coding address 53 to match the DHW recirculation pump function required by the layout.

Applies to: Vitodens 200-W B2HA 45, 60 DHW recirculation

Source: Vitodens 200-W B2HA 45, 60 installation manual, pp. 33-40. Written in our own words; check the manual for your exact model.

DHW recirculation pump function depends on coding address 53

Boiler · Vitodens 200-W

In the layouts, the DHW recirculation pump 28/20 and the heating circuit pump 28/20 are marked as working according to coding address 53.

  1. Check coding address 53 before setting up a DHW recirculation or 28/20 heating circuit pump.

Applies to: Vitodens 200-W B2HB layouts with 28/20 pumps

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 33. Written in our own words; check the manual for your exact model.

DHW recirculation pump schedule

Boiler · Vitotrol 300A

Automatic mode runs the DHW recirculation pump alongside the DHW heating program. Enabling it is only advisable when DHW is actually drawn, to avoid wasted energy.

  1. Open the extended menu and select DHW.
  2. Select DHW recirc pump schedule.
  3. Choose Automatic, or Individual to set up to four phases per day.
  4. Set start and end times for each phase.

Applies to: Systems with DHW recirculation pump

Source: Vitotrol 300A operating instructions, p. 15. Written in our own words; check the manual for your exact model.

DHW tank aquastat limit

Boiler · Versatronik 10.WB1

The DHW tank aquastat must not be set above 55 °C (131 °F).

  1. Confirm the DHW tank aquastat setting is 55 °C (131 °F) or lower.

Applies to: DHW tank aquastat on Versatronik 10.WB1 systems

Source: Versatronik 10.WB1 installation and operating manual, p. 4. Written in our own words; check the manual for your exact model.

DHW temperature and time program

Boiler · Vitotrol 300A

DHW temperature changes affect all heating circuits. Automatic mode starts DHW reheating half an hour before the standard heating phase. Individual phases can be set instead, up to four per day. Allow heat-up time before the hot water is needed.

  1. Open the extended menu and select DHW.
  2. Select DHW setpoint temperature and set the value.
  3. Select DHW schedule and choose Automatic or Individual.
  4. For individual phases, set start and end times for each phase.

Applies to: DHW heating

Source: Vitotrol 300A operating instructions, p. 13, p. 14. Written in our own words; check the manual for your exact model.

DHW time program

Boiler · Vitotronic 300

Automatic program starts DHW heating 30 minutes before the first heating circuit warm-up. Individual programs allow up to four switching times per day for DHW and the DHW circulation pump. Once started, DHW heating always finishes.

  1. Select automatic or individual program on the timer.
  2. For individual heating circuit timing, set coding 7F.
  3. Set up to four DHW circulation pump times if needed.

Applies to: DHW heating

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 90. Written in our own words; check the manual for your exact model.

DHW time program and heating circuit timing (coding 7f)

Boiler · Vitocrossal 300 CA3B Dual Fuel

Automatic DHW heating starts 30 min before the heating circuit heat-up phase. Individual programs allow up to 4 DHW time phases per day for every weekday.

  1. Detached house, coding 7f:1: heating times for heating circuit 1 are used for all circuits. Individual DHW pump and recirculation phases apply to all heating circuits.
  2. Apartment building, coding 7f:0: each heating circuit uses its own heating times in automatic mode, and individual DHW phases can be set per circuit.
  3. Tank heating cycles always finish regardless of the time program.

Applies to: DHW pump and DHW recirculation pump scheduling

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 43. Written in our own words; check the manual for your exact model.

DHW time program and recirculation pump timing

Boiler · Vitocrossal 300

Between DHW time phases the tank is not heated and only frost protection runs. Allow for the time the tank needs to reach temperature. The DHW recirculation pump can run in Automatic mode or in up to 4 set time phases per day. Only run it when hot water is actually drawn.

  1. Open the extended menu.
  2. Select 'DHW'.
  3. Select 'DHW time program' for DHW heating, or 'DHW circ time prog' for the recirculation pump.
  4. Set the required time phases.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 27. Written in our own words; check the manual for your exact model.

DHW timer schedule for any-time production

Boiler · Vitodens 222-F

If domestic hot water can be made at any time, the timer is set to run all day.

  1. Set the timer schedule as desired.
  2. For any-time DHW production, program the timer from 0:00 to 24:00.

Applies to: Applications 1 and 2

Source: Vitodens 222-F B2TB application guide, p. 33. Written in our own words; check the manual for your exact model.

DIP switch for separate room temperature sensor

Boiler · Vitotronic 300 GW2

When a separate room temperature sensor is connected to a remote control, set the matching DIP switch to ON on the remote control's printed circuit board (rear of top casing).

  1. Vitotrol 200: set DIP switch S6.3 to ON.
  2. Vitotrol 300: set DIP switch S30.3 to ON.
  3. For Vitotrol 300 also set coding switch 3 to ON when using the separate room temperature sensor (see the room temperature sensor section).

Applies to: Vitotrol 200 and Vitotrol 300 with separate room temperature sensor

Source: Vitotronic 300, Model GW2 installation and service instructions, p. 107, 109. Written in our own words; check the manual for your exact model.

Display contrast and brightness

Boiler · Vitotrol 300A

Adjust display contrast, brightness, and whether the backlight stays on in standby.

  1. Contrast: extended menu, Settings, Contrast, then set the contrast.
  2. Brightness: extended menu, Settings, Brightness, Control, then set the brightness.
  3. Standby backlight: extended menu, Settings, Brightness, Standby, then choose on or off.

Applies to: Vitotrol 300A remote control

Source: Vitotrol 300A operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Display contrast, brightness and language

Boiler · Vitocrossal 300

Adjusts the screen for readability. Brightness can be set separately for the control screen and the screen saver. Language is chosen from the menu and accepted with OK.

  1. Open the extended menu.
  2. Select 'Settings'.
  3. For contrast, select 'Contrast' and set the value.
  4. For brightness, select 'Brightness', then 'Control' or 'Screen saver', and set the value.
  5. For language, select 'Language', choose it and press OK.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 29, 30. Written in our own words; check the manual for your exact model.

Economy mode on a heating circuit

Boiler · Vitotronic 300-K

Economy mode is an energy saving function. It can only be turned on while the system is in standard heating mode.

  1. From the home screen, select the heating circuit in the header.
  2. Select economy mode and set it to ON, then confirm.
  3. To end it, set economy mode to OFF and confirm.
  4. It also ends automatically when the time program switches to reduced heating.

Applies to: Heating circuits on Vitotronic 300-K

Source: Vitotronic 300-K MW2C operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Enable economy mode for a heating circuit

Boiler · Vitotronic 300-K

Economy mode is an energy saving function for one heating circuit. It can only be turned on while the system is in standard heating mode.

  1. Press Menu, then Heating.
  2. Choose the heating circuit (1, 2 or 3).
  3. Press Economy mode and select the white frame.
  4. Press OK to confirm.

Applies to: Heating circuits 1 to 3

Source: Vitotronic 300-K MW2C operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Enable or end economy mode for a heating circuit

Boiler · Vitotronic 300-K

Economy mode is a heating circuit energy saving function. It can only be switched on while the system is in standard heating mode. It ends by itself when the time program switches the circuit to reduced heating.

  1. From the home screen, open the header and select the heating circuit (1, 2 or 3).
  2. Select 'Economy mode'.
  3. Choose 'ON' to enable or 'OFF' to end it, then confirm.

Applies to: Vitotronic 300-K, MW2C

Source: Vitotronic 300-K, MW2C operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Enable the INT interlock in Specifications

Boiler · Versatronik 300 Cascade Control

The interlock must be turned on in the control menu before it works. Once it is on, an open contact shows C1 and turns the fault output on.

  1. Press and hold ENTER for 5 seconds.
  2. Press the up arrow to reach the Specifications menu.
  3. Find the Interlock item and press ENTER to set it to Enable.
  4. Press ESC to leave the menu.

Applies to: Versatronik 300 Cascade Control, INT interlock

Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 10. Written in our own words; check the manual for your exact model.

Ending Comfort mode

Boiler · Vitocrossal 300 CA3B

Comfort mode for a heating circuit can be turned off by hand from the home screen. It also ends on its own when the system switches to standard heating mode under the time program, or after 8 hours. Changing the automatic end needs the heating contractor.

  1. From the home screen, select Heating circuit 1, 2 or 3 as required.
  2. Select Comfort mode.
  3. Set it to OFF.
  4. Confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Enter heating timer programs

Boiler · Versatronik COMO OT

Heating timer programs are entered per weekday or block (Mo-Fr, Sa-Su, Mo-Su). Each switch-on and switch-off time must be entered. Use dashes to disable a timer.

  1. Press Plus three times to reach HTGPROG.
  2. Select the weekday or block.
  3. Set the first switch-on time and room temperature, then confirm.
  4. Set the first switch-off time and confirm.
  5. Enter switch-on and switch-off times 2 and 3 the same way.
  6. Select the next weekday or block, or leave with RETURN.
  7. Enter dashes for any time not used to deactivate that timer.
  8. Note that times are saved only after all times for a weekday or block are entered.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 25. Written in our own words; check the manual for your exact model.

Enter holiday program

Boiler · Versatronik COMO OT

The holiday program uses day counts. The start is always taken at 12:00 pm, and the end is also at 12:00 pm.

  1. Open the cover and press Plus six times to reach HOLIDAY.
  2. Press Prog to open START-HOLIDAY and enter the number of days until the holiday starts.
  3. Enter the first holiday day, not the travel day, as the start.
  4. Press Prog to open HOLIDAY-DUR and enter the holiday length in days.
  5. Press Mode selector to end the holiday programming.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 27. Written in our own words; check the manual for your exact model.

Erase heating time cycles

Boiler · Vitotronic 300

Clears a heating cycle by setting its start and finish to blank times.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the heating time program button.
  4. Press up or down until the required 'Heating cycle OFF' appears.
  5. Press up or down until '– – : – –' appears for the finish time.
  6. Press OK until the display returns to the boiler temperature.
  7. Close the hinged cover.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Fixed high limit setting is changed by coding card only

Boiler · Vitocrossal 300 CA3B Dual Fuel

The fixed high limit safety cut-out is preset to 210°F (99°C). It can only be changed by changing the coding card. This is separate from the adjustable max boiler water temperature in menu 6, item 4.

  1. Refer to the control section of the installation instructions before changing the coding card.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 10. Written in our own words; check the manual for your exact model.

Flashing display means settings can be entered

Boiler · Vitotronic 100 GC1

When the data in the display window flashes, new settings can be entered with the value selector buttons and the confirmation button.

Applies to: Vitotronic 100, GC1

Source: Viessmann Vitotronic 100 GC1 operating instructions, p. 5. Written in our own words; check the manual for your exact model.

Functions adjustable from the Vitotrol remote

Boiler · Vitotronic 300-K MW1S

Vitotrol 200 and Vitotrol 300 allow day/normal temperature, reduced temperature, domestic hot water temperature, heating program, holiday program, switching times and economy/party mode to be adjusted. Changes can also be made through coding addresses A0, b0 to b9, C0 to C2, E1 and E2.

  1. Use the remote's controls to set the desired function.
  2. For changes beyond the remote, use the listed coding addresses on the control unit.

Applies to: Vitotrol 200 (p. 130), Vitotrol 300 (p. 132)

Source: Viessmann Vitotronic 300-K MW1S installation and service instructions, p. 130. Written in our own words; check the manual for your exact model.

Gas consumption meter setup

Boiler · Vitocrossal 200 CI2

The boiler has an integral gas meter. Accuracy depends on the gas volume correction factor (parameter 1098.4) and the gross calorific value (parameter 1098.5). Both can be set on the HMI or in ViGuide Web Pro. Get the values from the gas supplier or the gas bill. Lag boiler consumption is set by selecting that boiler's HMU in ViGuide Web Pro.

  1. Get the gas volume correction factor and gross calorific value from the supplier or gas bill.
  2. Enter them at parameters 1098.4 and 1098.5.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 80. Written in our own words; check the manual for your exact model.

Heat rooms only, no DHW

Boiler · Vitotronic 200 and 300-K

Used when the rooms must be heated but domestic hot water is not wanted. The DHW set temperature is lowered to the minimum value shown in the manual.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select "Heating", then "Heating program".
  4. Select "Heating and DHW".
  5. Go back until the menu is shown.
  6. Select "DHW", then "Set DHW temperature".
  7. Set the DHW temperature to 50 °F (10 °C).

Applies to: Vitotronic 200 and 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Heating circuit default display controls

Boiler · Vitocrossal 200 CI2

On the heating circuit or continuous operation default display you can raise or lower the room temperature (weather-compensated) or supply temperature (constant operation). You can also set the Heating or Standby mode, switch Extended heating on or off, and open the central heating time program. The temperature shown is the target room temperature or target supply temperature for the current time phase.

  1. Use the up or down buttons to change the room or supply target.
  2. Use the operating program button to choose Heating or Standby mode.
  3. Use the Extended heating button to switch that function on or off.
  4. Use the time program button to open the central heating time program.

Applies to: Vitocrossal 200 CI2 heating circuit or continuous operation display

Source: Vitocrossal 200 CI2 operating instructions, p. 15. Written in our own words; check the manual for your exact model.

Heating programs in the standard menu

Boiler · Vitodens 200-W B2HB

The standard menu sets room temperature and the heating program for the circuit shown in the header. Programs: standby with frost protection, DHW only, or heating plus DHW. Settings revert to the standard menu after 2 minutes.

  1. Select the required room temperature and confirm with OK.
  2. Select the required heating program and confirm with OK.
  3. If the system has 2 or 3 heating circuits, select HC1, HC2 or HC3 to show in the standard menu.

Applies to: Vitodens 200-W B2HB with Vitotronic control

Source: Vitodens 200-W B2HB service instructions, p. 31. Written in our own words; check the manual for your exact model.

Holiday program

Boiler · Vitocrossal 300 CA3B

The holiday program applies to all heating circuits and runs from 00:00 on the day after departure to 00:00 on the return date. Central heating goes to reduced room temperature in Heating and DHW circuits, and is off with frost protection in DHW only circuits. DHW heating is off with frost protection for the tank.

  1. From the home screen, open Holiday program.
  2. Set the departure date and the return date.
  3. Confirm.
  4. To cancel or delete the holiday program, open Holiday program from the home screen and use the delete option (shown as an icon in the manual).

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Holiday program (energy saving for central heating)

Boiler · Vitocrossal 300

Lowers central heating to the reduced room temperature for the length of an absence. DHW heating is switched off during the holiday, with DHW tank frost protection still active. The program starts at 00:00 on the day after departure and ends at 00:00 on the day of return, so the time program runs on the departure and return days. It applies to all heating circuits. Heating circuits set to 'Only DHW' get no central heating and only boiler and DHW tank frost protection. The set dates can be checked under Information.

  1. Open the extended menu.
  2. Select 'Heating'.
  3. Select 'Holiday program'.
  4. Enter the departure and return dates.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Language and measuring units

Boiler · Vitocrossal 300 CA3B Dual Fuel

Language and units (Metric or Imperial) are set from the Settings menu.

  1. For language: Menu > Settings > Language, pick the language, press OK.
  2. For units: Menu > Settings > Measuring units, pick Metric or Imperial, press OK.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Language selection

Boiler · Vitotrol 300A

Change the menu language.

  1. Open the extended menu.
  2. Select Settings, then Language.
  3. Select the required language.

Applies to: Vitotrol 300A remote control

Source: Vitotrol 300A operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Limit DHW temperature when using the second DHW set-point

Boiler · Vitotronic 100

If coding 58 is used, keep high limit R at least 10 °C / 18 °F above the DHW temperature the extra function reaches. Never let it go above the maximum allowed for the DHW tank.

  1. Check the maximum DHW temperature allowed by the tank installation instructions.
  2. Set coding 58 to the second set-point value.
  3. Set high limit R at least 10 °C / 18 °F above the temperature reached with the extra function, without exceeding the tank maximum.

Applies to: Vitotronic 100 GC1, coding 56 and 58

Source: Vitotronic 100 GC1 installation and service instructions, p. 122. Written in our own words; check the manual for your exact model.

Limit domestic hot water input

Boiler · Vitodens 200-W B2HA

DHW heating input can be limited separately from heating.

  1. Enter coding level 2.
  2. Change coding address 6F to the required limit.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 19. Written in our own words; check the manual for your exact model.

Minimum boiler temperature protection can be enabled or disabled

Boiler · Vitotronic 100

The minimum boiler temperature and freeze-up protection is controlled by the electronic boiler temperature sensor and can be turned on or off with a DIP switch.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B technical data manual, p. 7. Written in our own words; check the manual for your exact model.

Moving the programming unit to the top of the boiler

Boiler · Vitodens 100-W B1HE/B1KE

By default the programming unit sits on the underside of the boiler. For easier access it can be moved to the top. Do not change the cable routing or its fixing point on the casing, since incorrect routing causes heat damage and EMC problems.

  1. Remove the hinges and keep them for reinstallation.
  2. Pull in the tabs to release the control housing.
  3. Pull the control housing forward out of the jacketing.
  4. Disconnect the plug of the connecting cable from the bracket.
  5. Rotate the control housing 180 degrees.
  6. Reconnect the plug on the right-hand side.
  7. Reinstall the control housing into the jacket.
  8. Install the clips into the openings at the bottom of the front cover.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 16. Written in our own words; check the manual for your exact model.

Name heating circuits

Boiler · Vitocrossal 200 CI2

Each heating circuit can be named individually, for example 'Ground floor' (1 to 20 characters). The 1, 2, 3, 4 abbreviations stay in the default display. The name appears in the main menu.

  1. Open Settings.
  2. Select 'Rename heating circuits'.
  3. Select the heating circuit.
  4. Type the name.
  5. Confirm.

Applies to: Heating circuits

Source: Vitocrossal 200 CI2 operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Name heating circuits and choose the standard-menu circuit

Boiler · Vitocrossal 300

Heating circuits can be renamed, but the abbreviations HC1, HC2 and HC3 stay. Each name can be up to the number of characters the display allows. The standard menu can show HC1, HC2 or HC3.

  1. Open the extended menu.
  2. Select 'Settings'.
  3. Select 'Name for heating circ.' and choose the circuit.
  4. Select 'Change?' and enter the name, then press OK.
  5. To pick the circuit for the standard menu, select 'Standard menu' and choose the circuit.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 29, 30. Written in our own words; check the manual for your exact model.

Name heating zones

Boiler · Vitocrossal 200 CI2

Each heating zone can be named individually (1 to 20 characters). The name appears in the main menu.

  1. Open Settings.
  2. Select 'Rename heating zone'.
  3. Tap the required heating zone.
  4. Type the name.
  5. Confirm.

Applies to: Heating zones

Source: Vitocrossal 200 CI2 operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Name the heating circuits

Boiler · Vitotronic 300-K

Each heating circuit can have its own name, up to 32 characters. The name shows in the main menu.

  1. Press Menu, then Settings, then Name for heating circuit.
  2. Select the heating circuit and enter the name.
  3. Press OK to confirm.

Applies to: Heating circuits 1 to 3

Source: Vitotronic 300-K MW2C operating instructions, p. 22. Written in our own words; check the manual for your exact model.

Name the heating circuits (300-K only)

Boiler · Vitotronic 300-K

Heating circuits 1, 2 and 3 can get custom names. The HC1, HC2 and HC3 abbreviations stay in place. Entering a blank name is not covered; reset returns the default "Heating circuit" name.

  1. Open the extended menu.
  2. Select "Settings", then "Name for heating circ.".
  3. Select the heating circuit (1, 2 or 3).
  4. Select "Change?".
  5. Choose each character, moving to the next with the arrow.
  6. Press OK to save all characters and exit.
  7. To return to the default name, select "Reset?".

Applies to: Vitotronic 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 26. Written in our own words; check the manual for your exact model.

Name the heating circuits (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1B

Gives heating circuits HC1, HC2 and HC3 a custom name. The HC abbreviations stay on the display. The default name for HC1 is shown as Ground floor in the example.

  1. Open the extended menu.
  2. Select Settings, then Name for heating circ.
  3. Select Heating circuit 1, 2 or 3, then Change?.
  4. Choose each character with the selector keys; the next key moves to the next character.
  5. Press OK to accept all characters and leave the menu.
  6. To clear a name, use Reset?; the default name for that circuit returns.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Normal and reduced room temperature

Boiler · Vitocontrol-S VD2/CT3/CM2

Set separately for each heating circuit. Changing room temperature also changes the start/stop points of the heating circuit pump when pump logic is active.

  1. Normal day temperature: turn the set value adjuster to the required value. It is applied automatically after about 2 seconds.
  2. Reduced night temperature: press the tm button to call it up.
  3. Change the value with the up or down button.
  4. Confirm with the button shown.

Applies to: Vitocontrol-S VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 102. Written in our own words; check the manual for your exact model.

One-time DHW heating outside the time program

Boiler · Vitotrol 300A

At least one heating circuit must not be in Standby mode. Party mode is used to force DHW heating once. Turn Party mode off afterwards so central heating does not run at standard temperature by accident.

  1. Make sure at least one heating circuit is not in Standby mode.
  2. Open the extended menu and select Heating.
  3. Select the heating circuit if needed.
  4. Select Party mode.
  5. Set Party mode to OFF after the DHW heating is done.

Applies to: DHW heating

Source: Vitotrol 300A operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Open the main menu

Boiler · Vitocrossal 300 CA3B Dual Fuel

The main menu holds all scans and settings. The menu overview is on page 35 of the manual.

  1. If the screensaver is on, tap the display, then tap Menu.
  2. From anywhere in the menu, tap the menu button in the footer, then tap Menu.

Applies to: Vitotronic 300 GW6C service display

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Open the standard menu and the extended menu

Boiler · Vitodens 200-W B2HB

The standard menu is for common settings. The extended menu holds less-used functions such as time programs and holiday programs. If the screen saver is on, the first key press wakes the display. The screen saver turns on after a few minutes without changes and dims the display.

  1. If the screen saver is active, press any key except the ? key to wake the display.
  2. To reach the standard menu from elsewhere in the menu, keep pressing until it appears.
  3. To open the extended menu from the screen saver, press any key except ?, then press the menu key.
  4. To open the extended menu from elsewhere in the menu, press the menu key.

Applies to: Vitodens 200-W B2HB programming unit

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

Open the time and date menu

Boiler · Versatronik 200

Use the main menu to reach the time, date and holiday settings.

  1. Press the Home button to show the Main Menu.
  2. Turn the rotary dial until Time-Date is shown on the screen.
  3. Press the key beside User to select the menu option.
  4. Select the menu item you need: Time, Date, Holiday start, Holiday end, Start summer time or End summer time.
  5. Press Cancel to leave the current screen.

Applies to: Versatronik 200 controller display

Source: Versatronik 200 installation and operating manual, p. 133. Written in our own words; check the manual for your exact model.

Open the time program view from the main menu

Boiler · Versatronik 200

Use the main menu to reach the heating circuit timer information.

  1. Press the Home button to show the Main Menu.
  2. Turn the rotary dial until Time Program is shown on the screen.
  3. Press the key beside User to select the menu option.
  4. Pick the heating circuit to view its timer information.
  5. Press Cancel to leave the current screen.

Applies to: Versatronik 200 controller display

Source: Versatronik 200 installation and operating manual, p. 129. Written in our own words; check the manual for your exact model.

Operating mode selection

Boiler · Vitotronic 300

The program selector buttons choose the operating mode. Freeze-up protection stays active in all modes.

  1. Select heating and domestic hot water for full operation.
  2. Select domestic hot water only to heat only the DHW tank.
  3. Select standby to shut down normal heating while keeping freeze-up protection.

Applies to: Vitotronic 300 operating unit

Source: Vitotronic 300 technical data manual, p. 4. Written in our own words; check the manual for your exact model.

Operating programs for central heating and DHW

Boiler · Vitocrossal 200 CI2

Central heating has two operating programs: Heating (follows room or supply target and time program) and Standby mode (no central heating, boiler frost protection active). DHW has ON (heated per DHW temperature and time program) and OFF (no DHW heating, tank frost protection active). External hook-up means an external device such as an EM-EA1 changed the program, and it cannot be changed at the control unit while that is active.

  1. Select Heating for normal central heating operation.
  2. Select Standby mode to stop central heating for the relevant heating circuit while keeping frost protection.
  3. Set DHW to ON or OFF as needed.
  4. If External hook-up shows, change the operating program at the external device instead.

Applies to: Vitocrossal 200 CI2 central heating and DHW

Source: Vitocrossal 200 CI2 operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Operating programs for summer and absence

Boiler · Vitocrossal 300 CA3B

The operating program selects heating and hot water behaviour. DHW only keeps hot water running with heating off. Standby stops heating and hot water for long periods. Economy mode lowers room temperature for short absences. Holiday program reduces room temperature and turns off DHW.

  1. Select DHW only for summer, when only hot water is needed.
  2. Select Standby mode when no heating or hot water is needed for long periods.
  3. Select Economy mode for short absences.
  4. Select the Holiday program when away for a longer time.

Applies to: Vitotronic 300 GW6C control on Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 13. Written in our own words; check the manual for your exact model.

Outdoor reset slope and shift adjustment

Boiler · Vitodens 222-F

Slope and shift set the heating curve. Adjusting either one changes the displayed curve.

  1. Use the arrow keys to move from slope to shift.
  2. Adjust slope or shift and check the graphed curve change before leaving the screen.

Applies to: Application 4 weather-compensated ZC1

Source: Viessmann Vitodens 222-F B2TB application guide, p. 44. Written in our own words; check the manual for your exact model.

Party mode (DHW or central heating outside the time program)

Boiler · Vitocrossal 300

Party mode gives heating outside the normal time program. Set it to OFF again afterwards so central heating does not keep running at standard room temperature. The manual says at least one system heating circuit must be set to 'Heating and DHW' or 'Only DHW' for this to work. The first step to switch Party mode on is missing from the manual text.

  1. Open the extended menu.
  2. Select 'Heating'.
  3. Select 'Party mode'.
  4. Set 'Party mode' to OFF when the party is over.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Party mode for temporary heating and DHW

Boiler · Vitotronic 200-H

Party mode gives space heating and DHW for a short time outside the preset program. It is only available when set up with the party button.

  1. Open the hinged cover on the programming unit.
  2. Press the party button; the button lights and the party temperature flashes.
  3. Press up or down until the required party temperature shows.
  4. Confirm; the value stops flashing and is stored.
  5. Close the hinged cover.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Party mode: run heating or DHW briefly outside the schedule

Boiler · Vitocontrol-S

Party mode runs central heating and DHW for a short time, outside the preset program. It holds a party temperature value.

  1. Open the hinged cover and select the heating circuit.
  2. Press the party mode key so the button lights and the party temperature flashes.
  3. Adjust the party temperature with up/down, then confirm.
  4. Close the cover.
  5. To cancel early, press the heating circuit selector and the party key again. The light stays on for about 1 minute and the mode stays active until then.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Quick heat-up and quick setback for mixing valve circuits

Boiler · Vitotronic 300-K MW1S

Room temperature influence can be boosted briefly. It acts only when the set room temperature changes by at least 2 °C / 3.6 °F.

  1. Quick heat-up: press the party button, or switch from reduced to normal heating, to raise the room set point by 2 °C / 3.6 °F or more.
  2. Quick setback: press the economy button, or switch from normal to reduced heating, to lower the room set point by 2 °C / 3.6 °F or more.
  3. Quick heat-up and setback stop when the set room temperature is reached.
  4. Use coding b6 for quick heat-up/setback and b2 for room temperature influence.

Applies to: Mixing valve circuits with room temperature input

Source: Vitotronic 300-K MW1S installation and service instructions, p. 114. Written in our own words; check the manual for your exact model.

Quick heat-up, quick setback and economy functions

Boiler · Vitocontrol-S VD2/CT3/CM2

Quick heat-up and quick setback change the room set point by at least 2 K (3.6 °F) until the set room temperature is reached. Economy functions switch the heating circuit pump off and drop the supply set point to 0 °C (32 °F).

  1. Quick heat-up: press the party button or change from reduced to normal heating mode.
  2. Quick setback: press the economy button or change from normal to reduced heating mode.
  3. Economy pump logic: set outdoor cut-off with coding A5.
  4. Extended economy: check outdoor cut-off A6, room set reduction A9, mixing valve economy A7 (12 minutes closed) and room limit b5.

Applies to: Heating circuits with room temperature input

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 131. Written in our own words; check the manual for your exact model.

Reading and changing the boiler sequence

Boiler · Vitocontrol-S, VD2/CT3/CM2

The digits in the basic display show the boiler numbers in the current actual sequence. Hyphens show status: boilers before the first hyphen are activated, boilers between the hyphens are available but not needed, and boilers after the second hyphen are blocked (for example by a fault). The operator-requested sequence can differ from the actual sequence, because faults and the heating contractor's settings can change it. The sequence criteria are set by the heating contractor at start-up, and sometimes no alternative sequence is available.

  1. Open the hinged cover on the programming unit.
  2. Press the button combination to show the alternative operator-requested sequence (shown without hyphens); hold for about 2 seconds.
  3. Press the button(s) until the required boiler sequence appears.
  4. Press the confirm button; the display returns to the actual boiler sequence.
  5. Close the hinged cover.

Applies to: Multi-boiler systems with Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Reduce maximum burner output

Boiler · Vitocrossal 300 CA3B Dual Fuel

The maximum heating output of each burner can be set to 70 to 100% of rated output using the burner control unit.

  1. Hold button S for more than 2 seconds until the menu indicator blinks.
  2. Press button F until 6 shows under Service.
  3. Press button S. 6 shows under Status.
  4. Press button S. 1 shows under Status and the current maximum output (%) shows under Service.
  5. Press button F or D to choose the desired maximum output.
  6. Press button S to confirm. 1 under Service means success, 0 means it failed.
  7. Press button S to change the operating status indicator.
  8. Press button R. The system reboots.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 19. Written in our own words; check the manual for your exact model.

Reduce operational input on burner control

Boiler · Vitocrossal 200 CM2

Limit the maximum burner input between 0% (lower input) and 100% (upper input) if needed.

  1. Make sure the burner is in standby (Status 0, Service 0).
  2. Press button S and hold for more than 2 seconds until the display area flashes.
  3. Press button Y or E until 6 appears in the Service display.
  4. Press button S until 6 appears in the Status display.
  5. Press button S. A 1 appears in the Status display and the current max input (%) shows in the Service display.
  6. Press Y/E or B/G to set the required maximum input.
  7. Press S to confirm. A 1 shows on success; 0 means the adjustment failed.
  8. Press S to return to the operating display.
  9. Press button R for more than 2 seconds to restart and apply settings.

Applies to: Vitocrossal 200 CM2 burner control

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 14. Written in our own words; check the manual for your exact model.

Reducing heat-up time after reduced mode

Boiler · Vitodens 200-W B2HB

When switching from reduced to standard room temperature, the boiler water or supply temperature is raised for a set time to speed heat-up. Example in the manual: 50 °C plus 20% gives 60 °C for 60 minutes.

  1. Set the additional increase of the set boiler water or supply temperature at coding address FA.
  2. Set the duration of the raised temperature at coding address FB.

Applies to: Heating circuit transition from reduced to standard

Source: Vitodens 200-W B2HB service instructions, p. 90. Written in our own words; check the manual for your exact model.

Reset all weekday DHW cycles to a single program

Boiler · Vitotronic 300

If different cycles were set per weekday and you want the same cycles every day again, use the reset from the '1-7' display. This also resets all time cycles to factory settings.

  1. With the display showing '1-7', press the confirm reset option as described in the manual.
  2. Note that all time cycles return to factory settings.
  3. Re-enter the required cycles if needed.

Applies to: DHW time program

Source: Vitotronic 300 GW2 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Return to the standard menu from the outdoor reset programming unit

Boiler · Vitodens 200-W B2HA

Use this to get back to the standard menu from the screen saver or from deeper inside the menu.

  1. If the screen saver is on, press any key except the help key.
  2. If you are somewhere in the menu, keep pressing the back key until the standard menu appears.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

Room-dependent control for small or low-energy homes

Boiler · Vitocrossal 300 CU3A

For apartments under 860 ft2 (80 m2) or low energy houses, room-dependent control gives faster response.

  1. Install the Vitotrol 200A or 300A room control with the boiler.
  2. Use room-dependent control rather than outdoor reset alone for these buildings.

Applies to: Vitocrossal 300 CU3A small or low-energy buildings

Source: Vitocrossal 300 CU3A technical data manual, p. 19. Written in our own words; check the manual for your exact model.

Rotary address dial: leave at 0

Boiler · Versatronik 501, Versatronik 501D

The rotary dial gives an address for installations that use several gateways. For a normal installation it is not adjusted and stays at the factory default of 0.

  1. Check that the rotary dial reads 0.
  2. Only change it when the installation uses several gateways and an address is required.

Applies to: Versatronik 501 and 501D gateways

Source: Versatronik 501 & 501D LON gateway manual, p. 7. Written in our own words; check the manual for your exact model.

Select boiler sequence (300-K only)

Boiler · Vitotronic 300-K

Cascade sequence can be changed. The control offers several sequences based on the set parameters and internal calculations.

  1. Open the extended menu.
  2. Select "Boiler sequence".
  3. Set the required sequence and confirm with OK.

Applies to: Vitotronic 300-K cascade control

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 25. Written in our own words; check the manual for your exact model.

Select display language

Boiler · Vitocontrol-S, VD2/CT3/CM2

Sets the language shown on the Vitocontrol-S display.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the participant number button; 'Participant No.' shows.
  4. Press up or down until the required language shows.
  5. Confirm; the display returns to the boiler temperature.
  6. Close the hinged cover.

Applies to: Display language

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Select language (300-K only)

Boiler · Vitotronic 300-K

Sets the menu language on the 300-K control.

  1. Open the extended menu.
  2. Select "Settings", then "Language".
  3. Select the required language.

Applies to: Vitotronic 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 26. Written in our own words; check the manual for your exact model.

Select the heating circuit before any setting or scan

Boiler · Vitocontrol-S

On systems with two or three heating circuits, pick the right circuit first. Each circuit has its own selector button. On single-circuit systems you can start settings straight away. If you skip this step, the display asks you to select button 1, 2 or 3.

  1. Press the selector button for the heating circuit you want (1 = system circuit, 2 or 3 = circuit with mixing valve).
  2. Confirm the button lights up and shows the current heating program.
  3. Make your setting or scan now. The lights go out after a short time if you make no further input.

Applies to: Vitocontrol-S, VD2/CT3/CM2 with 2 or 3 heating circuits

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Select the heating circuit before changing central heating settings

Boiler · Vitotronic 300-K

In systems with several heating circuits, select the circuit first. Factory names are HC1, HC2 and HC3, and custom names replace them. Selection is not possible in single-circuit systems.

  1. Open the extended menu.
  2. Select Heating.
  3. Select the required heating circuit.

Applies to: Vitotronic 300-K (type MW2B) with several heating circuits

Source: Vitotronic 200 and 300-K operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Select the heating circuit before every setting or scan

Boiler · Vitocontrol-S

On systems with two or three heating circuits, select the correct circuit first. The selected circuit's button lights up along with its current program and any party or energy saving mode. If you skip this, the display asks you to select button 1, 2 or 3. With one circuit, settings can be made straight away.

  1. Press heating circuit button 1 (system circuit), 2 (circuit with mixing valve) or 3 (circuit with mixing valve).
  2. Check that the selected circuit button and its program lights are on.
  3. Make your setting or scan.
  4. If the display asks you to select a circuit, select it before continuing.

Applies to: Vitocontrol-S with two or three heating circuits

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Select the heating program

Boiler · Vitotrol 200A

Chooses between winter mode, summer mode and frost protection standby. The current program symbol flashes while you change it.

  1. Press the heating program key. The symbol for the current program flashes.
  2. Press the program key again until the symbol for the required program flashes.
  3. Press OK to confirm.

Applies to: Vitotrol 200A remote control

Source: Vitotrol 200A Installation, Operating and Service Instructions, p. 10. Written in our own words; check the manual for your exact model.

Select the heating program when the burner or heating is not running

Boiler · Vitotronic 100, GC1

Program 9 is the setting that stops the burner. Program rw or w is the normal running choice (page 6 of the manual).

  1. If the program 9 button is lit, set the rw or w heating program.
  2. Use rw as the setting for multi-boiler systems when the burner does not switch on.

Applies to: Single-boiler and multi-boiler systems

Source: Vitotronic 100, GC1 operating instructions, p. 13, p. 14 and p. 15. Written in our own words; check the manual for your exact model.

Select the language

Boiler · Vitotronic 300-K

Language is chosen from the Settings menu.

  1. Press Menu, then Settings, then Language.
  2. Select the required language and press OK.

Applies to: Control

Source: Vitotronic 300-K MW2C operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Select the operating mode (summer or winter)

Boiler · Vitotrol 300

Pick the mode that fits the season. The indicator light comes on and the chosen mode shows briefly in the display. Space heating and DHW mode: heating follows the heating cycle, DHW follows the DHW cycle, and frost protection stays on. DHW only mode: no space heating, DHW and DHW recirculation pump follow their cycle, frost protection stays on. Shut-off mode: no space heating and no DHW, frost protection stays on. Without a DHW tank the display shows 'Without Function' when this key is pressed. All recirculation pumps run every 24 hours to prevent seizing.

  1. Press the operating mode button for the mode you want.
  2. Check that the indicator light is on and the mode name appears briefly.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Select the operating program for a heating circuit

Boiler · Vitocrossal 300 CA3B Dual Fuel

Choose the operating program for each heating circuit. Make this change only at the system and lead boiler section 1.

  1. From the home screen, tap Menu, then Heating, then the required heating circuit.
  2. Tap Operating program.
  3. Select the program, for example Heating and DHW, DHW only or Standby mode.
  4. Tap OK to confirm.

Applies to: System and lead boiler section 1

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Selecting a heating circuit

Boiler · Vitotrol 300A

Heating circuits are factory named HC1, HC2 and HC3. The contractor may have renamed them at the Vitotronic, and that name then shows in place of HC. Selection is only available when more than one circuit is controlled. Returning to the standard menu sets the header back to HC1.

  1. Open the extended menu.
  2. Select the required heating circuit.
  3. Make the central heating changes for that circuit.

Applies to: Multi-circuit systems

Source: Vitotrol 300A operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Selecting a heating circuit for central heating settings

Boiler · Vitotrol 300A

On systems with more than one heating circuit, pick the circuit before changing its central heating settings. The selection is not offered when only one circuit is controlled.

  1. Open the extended menu.
  2. Select the settings you want to change.
  3. Select the required heating circuit.
  4. Make the central heating changes for that circuit.

Applies to: Multi-circuit systems

Source: Vitotrol 300A operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Selecting the heating circuit

Boiler · Vitotronic 300-K, Vitotronic 200

Systems with several heating circuits need the circuit chosen before any central heating setting is changed. Circuits are factory labelled HC1, HC2 and HC3. If renamed, the custom name appears instead of the default label.

  1. Open the extended menu.
  2. Select Heating.
  3. Select the required heating circuit.

Applies to: Vitotronic 300-K, systems with several heating circuits

Source: Vitotronic 200 and 300-K Operating Instructions, p. 16. Written in our own words; check the manual for your exact model.

Set a DHW time phase

Boiler · Vitotronic 200 and 300-K

Sets start and end times for DHW heating in the extended menu. Set the start and end time for each phase. To cancel a phase mid-setting, keep pressing the back key until the required screen appears.

  1. Open the extended menu.
  2. Select "DHW", then "DHW circ time prog" or the DHW time program.
  3. Select "Individual".
  4. Select the part of the week or the single day.
  5. Select the time phase.
  6. Set the start and end time for that phase.
  7. Press the exit key to leave the menu.

Applies to: Vitotronic 200 and 300-K DHW time program

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Set a heating circuit's room temperature levels

Boiler · Vitocrossal 200 CI2

Select the heating circuit first when the system has several. Then change the reduced, standard or comfort level and confirm.

  1. On the Heating circuit or Continuous operation default display, select the heating circuit if needed.
  2. Select the heating circuit in the menu bar if the screen shows it.
  3. Set the value for Reduced, Standard or Comfort.
  4. Confirm.

Applies to: Multi-circuit systems

Source: Vitocrossal 200 CI2 Operating Instructions, p. 20. Written in our own words; check the manual for your exact model.

Set a holiday program

Boiler · Vitocrossal 300 CA3B

Sets departure and return dates for the holiday program, which applies to all heating circuits. It starts at 00:00 on the day after departure and ends at 00:00 on the return date, so the time program runs on both those days. Contact the heating contractor before changing it. Effect: in Heating and DHW circuits, rooms drop to the reduced temperature. In DHW only circuits, central heating stays off with frost protection for the boiler and DHW tank. DHW heating stops, with frost protection for the DHW tank.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Holiday program.
  4. Enter the departure date and the return date.
  5. Tap OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Set a time program for central heating

Boiler · Vitocrossal 300 CA3B Dual Fuel

Time phases divide the day into blocks. Up to 4 time phases per day can be set, and each day of the week can differ. Settings apply to room heating, DHW heating and the DHW recirculation pump. Make these changes only at the system and lead boiler section 1.

  1. From the home screen, tap Menu, then Heating, then Heating circuit 1.
  2. Tap Time program heating, then tap the day (for example Mo), then tap Edit.
  3. Set the start and end points for time phase 1, then for time phase 2.
  4. Tap OK to confirm.

Applies to: System and lead boiler section 1

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Set altitude for high-elevation installs

Boiler · Vitodens 200-W

The boiler is factory set for altitudes up to 5,000 ft (1,500 m). For higher sites, change the altitude using coding address 93 in coding level 2 (General).

  1. Confirm the site altitude.
  2. Enter coding level 2 (General).
  3. Set coding address 93 to suit the altitude.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 25. Written in our own words; check the manual for your exact model.

Set date and time

Boiler · Vitocontrol-S, VD2/CT3/CM2

Time and date are preset at the factory. Manual reset is not needed when a radio clock receiver accessory is fitted.

  1. Open the hinged cover on the programming unit.
  2. Press the time button; 'Time' shows. Adjust with up or down, then confirm.
  3. The display shows 'Date'. Adjust with up or down, then confirm.
  4. The display returns to the boiler temperature.
  5. Close the hinged cover.

Applies to: Date and time

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Set DHW temperature

Boiler · Vitotronic 300-K, Vitotronic 200

DHW temperature is set in the DHW menu. The factory value is not shown on these pages.

  1. Open the extended menu and select DHW.
  2. Select Set DHW temperature.
  3. Set the required value.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 22. Written in our own words; check the manual for your exact model.

Set display backlighting

Boiler · Vitotronic 300-K

Brightness can be set separately for standby and for control operation.

  1. Press Menu, then Settings, then Screen.
  2. Choose Brightness standby or Brightness control.
  3. Set the required value and press OK to confirm.

Applies to: Control display

Source: Vitotronic 300-K MW2C operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Set display brightness (operation and standby)

Boiler · Vitocrossal 200 CI2

Separate brightness values are set for operation and for standby.

  1. Open Settings, then 'Display setting'.
  2. Select 'Brightness, operation' or 'Brightness, standby'.
  3. Select the required value.
  4. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Set display contrast (300-K only)

Boiler · Vitotronic 300-K

Adjusts the display contrast of the 300-K control.

  1. Open the extended menu.
  2. Select "Settings", then "Contrast".
  3. Set the required contrast.

Applies to: Vitotronic 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 25. Written in our own words; check the manual for your exact model.

Set display language

Boiler · Vitocrossal 200 CI2

Selects the language used on the control screen.

  1. Open Settings.
  2. Select 'Language'.
  3. Select the required language.
  4. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Set display units

Boiler · Vitocrossal 200 CI2

All units can be changed, for example temperature (°C or °F) and date format.

  1. Open Settings.
  2. Select 'Units'.
  3. Select the unit type, e.g. °C for temperature.
  4. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Set heating time cycles

Boiler · Vitotronic 300

Sets the start and finish times of up to 4 heating cycles, either identical for all days or per day of the week.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the heating time program button; 'Htg. Time Program' appears.
  4. Use the up or down button to select '1-7' for all days, or a single day such as 'Mo'.
  5. Press OK to confirm; cycle 1 appears.
  6. Press OK, then set the cycle start time with the up or down button and confirm.
  7. Set the cycle finish time with the up or down button and confirm.
  8. Repeat for cycles 2 to 4; to skip a cycle, press the skip button.
  9. Close the hinged cover.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 13. Written in our own words; check the manual for your exact model.

Set holiday mode on Lago FB

Boiler · Versatronik 200

Holiday mode starts at once and sets the room temperature to 15C/59F for 24 hours.

  1. Set the mode dial to HO.
  2. Use the value dial to set the number of days.
  3. The mode ends on the last day at 24:00.

Applies to: Lago FB remote control

Source: Versatronik 200 installation and operating manual, p. 57. Written in our own words; check the manual for your exact model.

Set increased DHW hygiene (weekly or daily heating above 140°F)

Boiler · Vitocrossal 200 CI2

Heats the DHW tank above 140°F (60°C) once a week or for an hour every day at the set time. Not valid for systems with a DHW tank with temperature switch (such as an Aquastat).

  1. Open DHW, then Hygiene function.
  2. Set the start time.
  3. Select the required day or every day.
  4. Confirm.
  5. To switch off, deselect the day or every day and confirm.

Applies to: DHW tank with sensor control

Source: Vitocrossal 200 CI2 Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Set individual DHW heating cycles for each day of the week

Boiler · Vitotrol 300

Set different DHW heating cycles for each weekday instead of one cycle set for all days. Up to four cycles per day can be set.

  1. Open the flip-down cover of the remote control.
  2. Select 'Time Program DHW' and wait for the display to show it.
  3. Select 'Individual?' and confirm.
  4. Use the up/down keys to choose the weekday to change.
  5. Select 'DHW Heating Cycle 1' and then 'DHW Heating Cycle 1 On'.
  6. Use the up/down keys to set the start time, then confirm. The display switches to 'Cycle 1 Off'.
  7. Use the up/down keys to set the end time, then confirm. The display switches to 'Cycle 2 On'.
  8. Set cycles 2 to 4 the same way.
  9. Close the flip-down cover.
  10. To end settings early, press the back/cancel key again. To skip a cycle, press the skip key.

Applies to: Vitotrol 300 remote control, DHW time program

Source: Vitotrol 300 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Set individual DHW time cycles

Boiler · Vitotronic 300

Sets up to 4 DHW (or DHW re-circulation pump) cycles, either identical for all days or per day.

  1. Select individual DHW time program mode as described above.
  2. Use up or down to select '1-7' for all days, or a single day such as 'Mo'.
  3. Press OK; cycle 1 appears. Press OK again to set its start time, using up or down, and confirm.
  4. Set the finish time with up or down and confirm.
  5. Repeat for DHW cycles 2 to 4; to skip a cycle, press the skip button.
  6. Close the hinged cover.

Applies to: Vitotronic 300 Model GW2

Source: Vitotronic 300 GW2 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Set maximum burner output

Boiler · Vitocrossal 300 CA3B

Changes the maximum operating output of the burner in percent. Stay inside the modulation range given on page 67.

  1. Hold the S button for more than 2 seconds until the indicator flashes.
  2. Turn the dial until 6 shows under Service.
  3. Press S. A 6 shows under Status.
  4. Press S. A 1 shows under Status and the current maximum output (%) shows under Service.
  5. Use Y or B to set the required maximum output.
  6. Press S to confirm. A 1 under Service means success, 0 means it failed.
  7. Press S to return to the operating display.

Applies to: CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 24. Written in our own words; check the manual for your exact model.

Set maximum heating output

Boiler · Vitocrossal 300 CU3A

Limits heating output through the modulation range. The upper limit is also set by the boiler coding card.

  1. Press OK and the second button together for about 4 seconds (button symbol not legible in source).
  2. Select "Service functions".
  3. Select "Max. output".
  4. Select "Change?" then "Yes". A value flashes (e.g. 85), which equals 100% of rated output in the delivered condition.
  5. Set the required value.

Applies to: Vitocrossal 300 CU3A heating output limit

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 19. Written in our own words; check the manual for your exact model.

Set maximum operational burner input

Boiler · Vitocrossal 300 CA3B Dual Fuel

Change the maximum burner output in percent from the burner control unit. The value must stay within the modulation range shown on page 19.

  1. Hold the S button for more than 2 seconds until the indicator flashes.
  2. Press Y until "6" shows under Service.
  3. Press S. "6" shows under Status.
  4. Press S. "1" shows under Status and the current maximum output in % shows under Service.
  5. Use Y or B to set the required maximum output.
  6. Press S to confirm. "1" under Service means success, "0" means it failed.
  7. Press S to return to the operating display.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 24. Written in our own words; check the manual for your exact model.

Set measuring units

Boiler · Vitotronic 300-K

Choose metric or imperial units for the display.

  1. Press Menu, then Settings, then Measuring units.
  2. Select Metric or Imperial.
  3. Press OK to confirm.

Applies to: Control

Source: Vitotronic 300-K MW2C operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Set normal and reduced room temperature

Boiler · Vitotronic 300-K MW1S

Normal room temperature is set with the set value adjuster. Reduced (night) temperature is set separately.

  1. For normal room temperature, turn the set value adjuster to the required day temperature. The value is taken over after about 2 seconds.
  2. For reduced room temperature, call up the reduced night temperature with its button.
  3. Change the value with the arrow buttons.
  4. Press OK to confirm.

Applies to: Vitotronic 300-K MW1S heating circuits

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 84. Written in our own words; check the manual for your exact model.

Set operator-requested boiler sequence

Boiler · Vitocontrol-S, VD2/CT3/CM2

Selects an alternative boiler lead order shown without hyphens. The chosen sequence is a request and may not match the actual sequence.

  1. Open the hinged cover on the programming unit.
  2. Press the two adjust buttons together for about 2 seconds; the requested sequence (no hyphens) shows.
  3. Adjust with up or down until the required sequence shows.
  4. Confirm; the display returns to the actual boiler sequence.
  5. Close the hinged cover.

Applies to: Boiler sequence selection

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Set or cancel the holiday program

Boiler · Vitotronic 300-K

The holiday program applies to all heating circuits. Circuits on 'Heating and DHW' run at the reduced room temperature. Circuits on 'DHW only' get no central heating. In both cases boiler and DHW tank frost protection stays active. DHW heating is off and only tank frost protection runs. The program starts at 00:00 h on the day after departure and ends at 00:00 h on the return date, so the standard time program runs on both those days. Changes to the program are made by the heating contractor.

  1. From the home screen, select 'Holiday program'.
  2. To set it, enter the departure date and the return date, then confirm.
  3. To cancel or delete it, select 'Holiday program' from the home screen and use the delete option.

Applies to: Vitotronic 300-K, MW2C

Source: Vitotronic 300-K, MW2C operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Set standard and reduced room temperature

Boiler · Vitotronic 300-K

The standard room temperature and the reduced room temperature are set in the operating menu. The manual shows example settings: standard 68 to 79°F (20 to 26°C), and reduced 37 to 57°F (3 to 14°C). The adjustment steps are in the Operating Instructions, not this manual.

  1. Refer to the Operating Instructions for the adjustment steps.
  2. Confirm the standard setpoint, for example 68 to 79°F (20 to 26°C).
  3. Confirm the reduced setpoint, for example 37 to 57°F (3 to 14°C).

Applies to: Vitotronic 300-K heating circuits

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 33. Written in our own words; check the manual for your exact model.

Set standard and reduced room temperatures

Boiler · Vitocrossal 300

Example ranges from the manual: standard room temperature changed from 20 C to 26 C (68 F to 79 F); reduced room temperature changed from 5 C to 14 C (41 F to 57 F). The adjustment itself is made as described in the Operating Instructions.

  1. Refer to the Operating Instructions to change the standard room temperature.
  2. Refer to the Operating Instructions to change the reduced room temperature.

Applies to: Heating circuits with room temperature setpoints

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 51. Written in our own words; check the manual for your exact model.

Set target supply temperature for a heating zone or circuit

Boiler · Vitocrossal 200 CI2

Sets the target supply temperature for a selected heating zone or heating circuit.

  1. Open the "Heating" function.
  2. Select the heating zone or heating circuit and confirm.
  3. Adjust the target supply temperature.
  4. Confirm.

Applies to: Heating zones and heating circuits

Source: Vitocrossal 200 CI2 Operating Instructions, p. 21. Written in our own words; check the manual for your exact model.

Set temperature units

Boiler · Vitotronic 300-K

Choose metric or imperial units for displayed values.

  1. From the home screen, open 'Settings' and select 'Temperature units'.
  2. Select 'Metric' or 'Imperial' and confirm.

Applies to: Vitotronic 300-K, MW2C

Source: Vitotronic 300-K, MW2C operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Set the AUX demand set point (DMD SetP)

Boiler · Versatronik 300 Cascade Control

DMD SetP is the fixed set point used when the AUX demand contact is closed. Default input function is demand.

  1. Press and hold ENTER for 5 seconds.
  2. Press the up arrow until Specifications appears and press ENTER.
  3. Press the up arrow until DMD SetP shows and press ENTER to edit.
  4. Use up or down to change the value, then press ENTER to save.
  5. Press ESC to exit. The displayed set point should match the demand set point and an A should show.

Applies to: Versatronik 300 Cascade Control, AUX demand

Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 11. Written in our own words; check the manual for your exact model.

Set the boiler sequence in a cascade

Boiler · Vitotronic 300-K

The control offers several boiler sequences, depending on the coding and the internal control calculations. The sequence is set so the boilers run evenly. Boiler numbers are fixed. The sequence shows the order in which boilers start. The example on the page shows Boiler 5, then Boiler 1, 2, 3 and 4.

  1. Press Menu, then Boiler sequence.
  2. Select New boiler sequence.

Applies to: Multi boiler cascade

Source: Vitotronic 300-K MW2C operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Set the central heating time program

Boiler · Vitotronic 300-K, Vitotronic 100

Sets the start and end of each standard heating time phase for each day or part of the week. Outside these phases the rooms run at reduced temperature.

  1. Open the extended menu.
  2. Select "Heating".
  3. Select the heating circuit if needed.
  4. Select "Heating time program".
  5. Select the part of the week or a single day.
  6. Select the time phase (!, ?, § or $).
  7. Set the start and end times for that phase.
  8. Press to exit the menu.

Applies to: Vitotronic 300-K, MW1B and Vitotronic 100, GC1B

Source: Vitotronic 100/300-K operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Set the date and time

Boiler · Vitotrol 300

Time and date are factory set and can be changed by hand on the remote control.

  1. Open the flip-down cover of the remote control.
  2. Select 'Time' and press to enter the time setting.
  3. Use the up/down keys to set the time, then confirm.
  4. The date is shown next. Use the up/down keys to set it, then confirm.
  5. Close the flip-down cover.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Set the DHW operating program

Boiler · Vitotronic 300-K

The factory setting is Heating and DHW. If no central heating is needed, set DHW only. The operating programs are described in the Terminology section of the manual.

  1. Set the DHW operating program to Heating and DHW, or to DHW only if central heating is not needed.

Applies to: DHW heating

Source: Vitotronic 300-K MW2C operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Set the DHW target temperature

Boiler · Vitocrossal 200 CI2

Do not set DHW below 122°F (50°C) for hygiene reasons. Not valid for systems with a DHW tank with temperature switch (such as an Aquastat).

  1. On the DHW default display, select the target value.
  2. Set the required value.
  3. Confirm.

Applies to: DHW tank with sensor control

Source: Vitocrossal 200 CI2 Operating Instructions, p. 23. Written in our own words; check the manual for your exact model.

Set the DHW temperature

Boiler · Vitotronic 300-K

Sets the stored hot water target temperature.

  1. Open the extended menu.
  2. Select "DHW".
  3. Select "Set DHW temperature".
  4. Set the required value.

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Set the DHW time program

Boiler · Vitotronic 300-K

Automatic mode reheats DHW during standard heating times and starts 30 minutes before the heating phase. Individual mode allows up to 4 phases per day.

  1. Open the extended menu.
  2. Select "DHW".
  3. Select "DHW time prog".
  4. Select "Individual" if automatic mode is not wanted.
  5. Select the part of the week or a single day.
  6. Select the time phase (!, ?, § or $).
  7. Set the start and end times for that phase.
  8. Press to exit the menu.

Applies to: Vitotronic 300-K, MW1B

Source: Vitotronic 100/300-K operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Set the DHW time program (cycles 1 to 4)

Boiler · Vitotronic 300

Sets the start and end times of up to four domestic hot water heating cycles, either the same for all days or per weekday. The DHW re-circulation pump follows the same program.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the DHW time program button and select '1-7' for identical cycles every day, or a single weekday (Mo, Tu, etc.) for different cycles.
  4. Confirm. The display moves to DHW time cycle 1.
  5. Press the button to reach DHW cycle 1 ON, then set the start time and confirm.
  6. Set the finish time for DHW cycle 1 and confirm.
  7. Repeat for DHW cycles 2 to 4 with the same method. Press the skip button to leave a cycle unused.
  8. Close the cover when finished.

Applies to: Vitotronic 300 GW2, DHW time program

Source: Vitotronic 300 GW2 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Set the display brightness

Boiler · Vitodens 100-W B1HE/B1KE

Adjusts the brightness of the control unit display.

  1. Call up the home screen.
  2. Select Settings, then confirm with OK.
  3. Select Display brightness, then confirm with OK.
  4. Select Display, then confirm with OK.
  5. Select the required value, then confirm with OK.
  6. Press and hold the exit button for about 4 sec to leave the menu.

Applies to: Control unit display

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 19. Written in our own words; check the manual for your exact model.

Set the holiday program

Boiler · Vitotronic 300

With the 'rw' heating program, heating continues at the reduced room temperature during the holiday, without DHW heating. With the 'w' program, only freeze-up protection runs, and DHW heats per the time program on departure and return dates. The holiday program applies to all heating circuits unless the installer changes it.

  1. Open the cover on the programming unit.
  2. Press the holiday program button; the holiday display appears.
  3. Press confirm, then use the up or down button to set the departure date and confirm.
  4. Set the return date with the up or down button and confirm.
  5. With 'rw' selected, press the reduced temperature button, set the value and confirm.
  6. Close the cover.

Applies to: Heating program rw or w

Source: Vitotronic 300 GW2 operating instructions, pp. 18-19. Written in our own words; check the manual for your exact model.

Set the home screen (default display)

Boiler · Vitocrossal 200 CI2

Choices are 'Heating circuit' or 'Continuous operation', 'DHW', or 'Device status'. Available options depend on whether the system runs weather-compensated or constant operation.

  1. Open Settings.
  2. Select 'Selecting the default display'.
  3. Select the required display.
  4. Confirm.
  5. Tap the home screen to call up the selected display.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Set the operating program

Boiler · Vitocrossal 300 CA3B

Chooses between DHW only and Heating and DHW for a heating circuit. The default is Heating and DHW.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Operating program.
  4. Select DHW only or Heating and DHW.
  5. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Set the room temperature setback

Boiler · Vitodens 200-W B2HA

Example: change the setback from 41°F to 57°F (5°C to 14°C).

  1. Open the menu.
  2. Select Heating.
  3. Select the heating circuit.
  4. Press OK.
  5. Select the reduced room temperature setpoint and press OK.
  6. Change the value with the arrow keys.
  7. Accept with OK.
  8. Return to the standard menu.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Set the standard room temperature

Boiler · Vitotrol 200A

Sets the room temperature used during standard heating mode. Factory setting is 68°F (20°C).

  1. Press +/- to set the required standard room temperature.
  2. Press OK to confirm.
  3. The display then shows the current (actual) room temperature.

Applies to: Vitotrol 200A remote control

Source: Vitotrol 200A Installation, Operating and Service Instructions, p. 10. Written in our own words; check the manual for your exact model.

Set the standard room temperature and time program

Boiler · Vitocrossal 300 CA3B

The standard room temperature is used when occupied. Reduced room temperature applies at night or when absent. A time program sets phases for day and night. The standard room temperature should not be set above 68°F (20°C).

  1. Set the standard room temperature in the standard menu, no higher than 68°F (20°C).
  2. Set the reduced room temperature for night and absence.
  3. Set the time program so the standard temperature runs during the day and the reduced temperature at night.
  4. Use Comfort mode to heat outside the time program for a set period.

Applies to: Vitotronic 300 GW6C control

Source: Vitocrossal 300 CA3B operating instructions, p. 13. Written in our own words; check the manual for your exact model.

Set the standard room temperature setpoint

Boiler · Vitodens 200-W B2HA

Example: change the room setpoint from 68°F to 79°F (20°C to 26°C).

  1. Open the menu.
  2. Select Heating.
  3. Select the heating circuit.
  4. Press OK.
  5. Select the room temperature setpoint and press OK.
  6. Change the value with the arrow keys.
  7. Accept with OK.
  8. Return to the standard menu.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Set the time and date

Boiler · Vitocrossal 300 CA3B

The time and date are set at the factory. Reset them after the system has been shut down for a long time. Settings can be changed only at the system and lead control boiler section 1.

  1. From the home screen, open Menu, then Settings.
  2. Open Date / Time.
  3. Select Date or Time.
  4. Enter the required value.
  5. Tap OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Set time and date

Boiler · Vitotronic 200, Vitotronic 300-K

At commissioning the time and date are set on the first prompts. After long time out of use the same settings are reached through the extended menu.

  1. At commissioning, set the current time with the selector, then press OK to move to date.
  2. Set the current date with the selector and press OK to complete.
  3. After long downtime, open the extended menu, select Settings, then Time / Date, and set the time and date.

Applies to: Vitotronic 300-K and Vitotronic 200

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 27. Written in our own words; check the manual for your exact model.

Set time and date (Vitotronic 300-K)

Boiler · Vitotronic 300-K MW1B

Time and date are factory set. Set them again after the system has been shut down for a long time.

  1. Open the extended menu.
  2. Select Settings, then Time/Date.
  3. Set the time and date.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Set time and weekday

Boiler · Versatronik COMO OT

Set the clock time and weekday from the TIME-DAY menu. Time changes in 15-minute steps.

  1. Open the cover and press Plus twice to reach TIME-DAY.
  2. Press Prog to open Time and press E, then use Plus/Minus to set the hour and minute.
  3. Press Prog to save, then open Day and press E. Use Plus/Minus to set the weekday.
  4. Press Prog and then Save to store TIME-DAY.
  5. Close the cover to return to the default display.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 24 and p. 32. Written in our own words; check the manual for your exact model.

Set time, date and temperature unit

Boiler · Vitocrossal 300

Time and date are set at the factory. After a long power loss they may need to be set again. The temperature unit can be °C or °F; factory setting is °C.

  1. Open the extended menu.
  2. Select 'Settings'.
  3. Select 'Time/Date' and set the time and date, or select 'Temperature unit' and choose °C or °F.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 30, 31. Written in our own words; check the manual for your exact model.

Set Vitotrol coding switch to heating circuit

Boiler · Vitotronic 200

The remote control's circuit-board coding switch decides which heating circuit it controls. The default setting is for heating circuit 1; heating circuit 2 is the mixing valve circuit.

  1. Open the top of the remote control housing to reach the circuit board coding switch.
  2. Set the switch for the heating circuit the remote control should control.
  3. If a separate room temperature sensor is connected, change the coding switch as the manual shows.

Applies to: Vitotrol 200 and Vitotrol 300 remote controls

Source: Vitotronic 200 service instructions, pp. 76-77. Written in our own words; check the manual for your exact model.

Setting a different program for one day

Boiler · Vitocrossal 300 CU3A

Set the shared program first, then change a single day. Check marks show which days share identical phases. Example: set Monday-Sunday first, then select Monday and adjust it.

  1. Select Monday-Sunday and set the time program.
  2. Select Monday and adjust its time program.
  3. Saturday-Sunday stays checked because it keeps the shared phases.

Applies to: Central heating and DHW time programs

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 19. Written in our own words; check the manual for your exact model.

Setting and ending Economy mode

Boiler · Vitocrossal 300 CA3B

Economy mode is an energy saving function. It can only be switched on in standard heating mode. It ends by hand or automatically when the time program switches to reduced heating mode.

  1. From the home screen, select the heating circuit.
  2. Select Economy mode and set it to ON, then confirm.
  3. To end it, select Economy mode, set it to OFF and confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Setting central heating time phases

Boiler · Vitotronic 300-K, Vitotronic 200

Time phases are set per part of the week or per day. A phase is removed by making its end time equal its start time.

  1. Open the extended menu and select Heating.
  2. Select the heating circuit if needed.
  3. Select Heating time program.
  4. Select part of the week or a single day.
  5. Select the time phase.
  6. Set the start and end times.
  7. Press the exit key to leave the menu.
  8. To cancel a setting early, keep pressing the key until the required display appears.
  9. To delete a phase, set its end time equal to its start time; the display shows '- - : - -'.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Setting Comfort mode

Boiler · Vitocrossal 300 CA3B

Comfort mode heats the rooms to a chosen target temperature. DHW is heated to its set temperature first, before central heating starts, unless the heating contractor changed this. The DHW recirculation pump runs if installed.

  1. From the home screen, select the heating circuit (1, 2 or 3).
  2. Select Comfort mode and set it to ON.
  3. Confirm.
  4. Select the required room temperature target for comfort mode.
  5. Confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Setting date and time

Boiler · Vitocrossal 300 CA3B Dual Fuel

Date and time are factory set. Reset them after the system has been shut down for a long time.

  1. Go to Menu > Settings > Date / Time.
  2. Select Date or Time.
  3. Set the value and press OK.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 30. Written in our own words; check the manual for your exact model.

Setting normal and reduced room temperatures

Boiler · Vitotronic 200

Normal and reduced room temperatures can be set separately for each heating circuit.

  1. Select the heating circuit with the circuit selector buttons.
  2. For normal room temperature, turn the setpoint selector to the desired day temperature. It is accepted automatically after about 2 seconds.
  3. For reduced room temperature, press the reduced temperature button, adjust with the plus or minus button, and confirm.
  4. After confirming, the display returns to showing boiler water temperature.

Applies to: Heating circuits 1 and 2 on Vitotronic 200 KW2

Source: Vitotronic 200 Si service instructions, p. 18. Written in our own words; check the manual for your exact model.

Setting the central heating time program

Boiler · Vitotrol 300A

Up to 4 heating time phases per day are available. Outside the phases, rooms run at the reduced temperature. Allow for heat-up time so rooms reach the setpoint when needed. The current program can be checked under Information.

  1. Open the extended menu and select Heating.
  2. Select the heating circuit if needed.
  3. Select Heating schedule.
  4. Choose the part of the week or the single day.
  5. Choose time phase 1, 2, 3 or 4.
  6. Set the start and end times.

Applies to: Heating time program

Source: Vitotrol 300A operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Setting the maximum operational burner input

Boiler · Vitocrossal 200 CM2

Sets the maximum burner output between 0 and 100% of rated input. Observe the modulation range (see p. 16).

  1. Press S for longer than 2 seconds until the menu item flashes.
  2. Scroll with Y until 6 shows under Service, then press S. 6 shows under Status.
  3. Press S. 1 shows under Status and the current maximum output % shows under Service.
  4. Press Y or B to set the required maximum output.
  5. Press S to confirm. 1 under Service means applied, 0 means it failed.
  6. Press S to return to the operating display.
  7. Press R to reset the unit and apply settings.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 46. Written in our own words; check the manual for your exact model.

Setting the motorized flue damper (flue gas cascade)

Boiler · Vitocrossal 200 CM2

Integrates the flue damper adjust value into the control. Set to 1 when a motorized damper is fitted.

  1. Press S for longer than 2 seconds.
  2. Scroll with Y until 6 shows under Service, then press S. 6 shows under Status and 1 under Service.
  3. Scroll with Y until 7 shows under Service, then press S. 7 shows under Status.
  4. Press Y or B to set the flue damper adjust value to 1.
  5. Press S to confirm. 1 under Service means applied, 0 means it failed.
  6. Press S to return to the operating display.

Applies to: Vitocrossal 200 CM2 burner control unit with motorized flue damper

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 46. Written in our own words; check the manual for your exact model.

Setting the time and date

Boiler · Vitotrol 300A

Time and date are set at the factory. After long storage they may need to be set again.

  1. Open the extended menu.
  2. Select Settings, then Time/Date.
  3. Set the time and date.

Applies to: Vitotrol 300A remote control

Source: Vitotrol 300A operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Standard menu: room temperature and heating program

Boiler · Vitodens 200-W B2HA

Quick adjustments available in the standard menu for the heating circuit shown in the header. Program options are standby with frost protection, DHW only, and heating plus DHW.

  1. Use the arrow keys to set room temperature, then press OK.
  2. Select the heating program with the arrow keys, then press OK.
  3. Program options: standby mode with frost protection monitoring; DHW only; heating and DHW.
  4. If the system has 2 or 3 heating circuits, select HC1, HC2 or HC3 in the standard menu.

Applies to: Standard menu operation

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 28. Written in our own words; check the manual for your exact model.

Standard menu: room temperature and heating programs

Boiler · Vitodens 200-W

Quick settings for the heating circuit shown in the header. Settings return to the standard menu after 2 minutes without input.

  1. Use the arrow keys to set the room temperature, then press OK.
  2. Select the heating program with the arrow keys, then press OK.
  3. Program 9 is standby with frost protection monitoring.
  4. Program w is DHW only.
  5. Program wz is heating and DHW.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB service instructions, p. 31-32. Written in our own words; check the manual for your exact model.

Start one-off DHW heating

Boiler · Vitocrossal 200 CI2

Heats the DHW tank once to its target temperature. This overrides the time program. It is not valid for systems with a DHW tank with temperature switch (such as an Aquastat).

  1. On the DHW default display, tap the one-off DHW heating button.
  2. Confirm.
  3. To stop early, tap the button again.

Applies to: Systems with a DHW tank with sensor control

Source: Vitocrossal 200 CI2 Operating Instructions, p. 17 and p. 23. Written in our own words; check the manual for your exact model.

Stop DHW and central heating (frost protection only)

Boiler · Vitotronic 200 and 300-K

Used when neither DHW nor room heating is wanted. The control stays in standby, which keeps frost protection monitoring active.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select "Heating", then "Heating program".
  4. Select "Standby mode" (frost protection monitoring).

Applies to: Vitotronic 200 and 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Stop DHW heating in standard mode

Boiler · Vitotronic 300-K

Lowering the DHW setpoint to the minimum stops DHW heating during standard operation.

  1. From the home screen, select 'DHW temperature setpoint'.
  2. Adjust the value down to 50°F (10°C).
  3. Confirm.

Applies to: Vitotronic 300-K, MW2C

Source: Vitotronic 300-K, MW2C operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Summer economy mode for DHW

Boiler · Vitotronic 300

In summer economy mode with DHW only selected, the burner runs only when the DHW setpoint calls for heat.

  1. Select the DHW only program with the selector switch in the summer economy position.
  2. Expect the burner to fire only when the DHW tank needs heat.

Applies to: Domestic hot water heating

Source: Vitotronic 300 technical data manual, p. 4. Written in our own words; check the manual for your exact model.

Switch a heating circuit on or off

Boiler · Vitocrossal 200 CI2

Operating program switch for each heating circuit or heating zone.

  1. Open the "Turn on/off" function.
  2. Tap the heating circuit or heating zone to switch it on or off.
  3. Confirm.

Applies to: Heating circuits and heating zones

Source: Vitocrossal 200 CI2 Operating Instructions, p. 20. Written in our own words; check the manual for your exact model.

Switch DHW heating on or off

Boiler · Vitocrossal 200 CI2

Switching DHW heating off stops all water heating, including one-off DHW heating.

  1. On the DHW default display, select the operating button.
  2. Select ON to start DHW heating or OFF to stop it.
  3. Confirm if prompted.

Applies to: DHW heating

Source: Vitocrossal 200 CI2 Operating Instructions, p. 23. Written in our own words; check the manual for your exact model.

Switch DHW scald protection on or off

Boiler · Vitocrossal 200 CI2

With scald protection off, a DHW target above 140°F (60°C) can be selected. This carries a high scalding risk.

  1. Open DHW, then Scald protection.
  2. Select On or Off.
  3. Confirm.

Applies to: DHW heating

Source: Vitocrossal 200 CI2 Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Switch from standalone/weather-compensated to constant temperature control

Boiler · Vitotronic 200

The system example requires a change of control mode on the Vitotronic 200 boiler control. The procedure is on page 12, which is not in these pages.

  1. Switch the control mode from standalone/weather-compensated to constant temperature control as described on page 12.

Applies to: Vitotronic 200 boiler controls in a cascade

Source: Vitotronic 200 and 300-K installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Switch off DHW and central heating (standby)

Boiler · Vitocrossal 300

Standby mode turns off DHW heating and central heating, but frost protection stays active. Use it when the system must be shut down with frost protection on.

  1. Standard menu: select the operating program 'Standby mode' and press OK.
  2. Extended menu: open 'Heating', select the heating circuit, then 'Heating program', and choose 'Standby mode'.

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Switch the Lightguide on or off

Boiler · Vitocrossal 200 CI2

Lightguide is on from the factory. Lightguide pulses slowly in standby, stays constant while the panel is in use, and flashes quickly when there is a fault. Faults still flash even when the Lightguide is off.

  1. Open Settings, then 'Display setting'.
  2. Select 'Lightguide on/off'.
  3. Select 'ON' or 'OFF'.
  4. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Switch WiFi or LAN internet access on or off

Boiler · Vitocrossal 200 CI2

The internet access credentials are on the label on the control unit. Internet access is needed for the app.

  1. Open Settings, then 'Internet'.
  2. Select 'WiFi' or 'LAN'.
  3. Select 'ON' to enable or 'OFF' to disable.
  4. Confirm.

Applies to: Internet connection

Source: Vitocrossal 200 CI2 operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Switching off DHW heating

Boiler · Vitocrossal 300 CA3B

DHW heating can be turned off by setting the DHW temperature to its minimum.

  1. From the home screen, select DHW temperature setpoint.
  2. Use the controls to set 50°F (10°C).
  3. Confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Turn automatic summer/wintertime changeover on or off

Boiler · Vitocrossal 200 CI2

Sets whether the control changes time automatically between summer and winter time.

  1. Open Settings, then 'Date and time'.
  2. Select 'Time changeover'.
  3. Select 'ON' or 'OFF'.
  4. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 27. Written in our own words; check the manual for your exact model.

Turn off DHW heating but keep central heating

Boiler · Vitocrossal 300

Set the DHW temperature to the lowest value to stop DHW heating while the heating circuit still runs. The manual gives 50°F (10°C) for this.

  1. Open the extended menu.
  2. Select 'Heating'.
  3. Select the heating circuit.
  4. Select 'Heating program' and choose 'Heating and DHW'.
  5. Open 'DHW'.
  6. Select 'Set DHW temperature'.
  7. Set the value to 50°F (10°C).

Applies to: Vitocrossal 300 CU3A

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Turn on comfort mode for a heating circuit

Boiler · Vitocrossal 300 CA3B

Starts comfort mode for one heating circuit and sets the room temperature target used during comfort mode. Settings can be changed only at the system and lead control boiler section 1.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit (1, 2 or 3).
  3. Open Comfort mode and select Comfort mode again.
  4. Press OK to confirm.
  5. Select the required comfort mode room temperature target.
  6. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Turn on economy mode for a heating circuit

Boiler · Vitocrossal 300 CA3B

Energy saving function. It can only be enabled while the system is in standard heating mode. Settings can be changed only at the system and lead control boiler section 1.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Economy mode and select Economy mode again.
  4. Press OK to confirm.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Use energy saving mode

Boiler · Vitotrol 300

Only available in the heating operating mode. The room temperature is automatically lowered. The mode ends at the next automatic switch to reduced room temperature, or it can be cancelled early.

  1. Press the energy saving key; the key lights and the icon shows briefly.
  2. To end early, press the key again; the light goes off.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Use Extended heating during a reduced time phase

Boiler · Vitocrossal 200 CI2

Keeps the rooms at the last active standard or comfort temperature during a reduced phase. It ends automatically at the next standard or comfort phase, or can be ended early.

  1. Select the heating circuit in the menu bar if applicable.
  2. Tap the Extended heating button to switch it on.
  3. To end early, select the heating circuit and tap the button again.

Applies to: Heating circuits with time programs

Source: Vitocrossal 200 CI2 Operating Instructions, p. 21. Written in our own words; check the manual for your exact model.

View the heating cycles on the time line

Boiler · Vitotrol 300

The selected cycles are shown on a time line, for all days or for a single day.

  1. Open the flip-down cover of the remote control.
  2. Press the two overview keys together; the cycles for the day appear on the time line.
  3. Close the cover.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Water temperature range from the control panel

Boiler · Vitotron 100 VLN2

The boiler is preset for radiant floor, radiant ceiling, hot water baseboard and water to air applications. Temperatures can be set between 85°F and 140°F.

  1. Set the desired water temperature on the control panel within 85°F to 140°F.
  2. Choose a setting that matches the application (radiant floor, radiant ceiling, baseboard or water to air).

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 3. Written in our own words; check the manual for your exact model.

Where the fault history lives

Boiler · Vitodens 200-W B2HE

The message history keeps the 10 most recent faults with their subscriber numbers (CAN 1 HMU, CAN 50 BCU, CAN 59 HMI, CAN 60 fan, 81 MZIO).

  1. Service menu > Message history

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Message history. Written in our own words; check the manual for your exact model.

Rotary dial address setting

General · Versatronik 535 Solar

The rotary dial sets an address for sites with several gateways. With RESOL controls the dial needs no change and should stay at the factory default of 0.

  1. Leave the rotary dial at 0 for RESOL controls.
  2. Change the dial only if the site uses more than one gateway and an address is required.

Applies to: Versatronik 535 Solar gateway, RESOL controls

Source: Versatronik 535 Solar BACnet IP manual, p. 7. Written in our own words; check the manual for your exact model.

Adjust heating curve shift

Heat pump · Vitocal 100-AW

Shift moves the whole heating curve up or down. Example in the manual uses curve 8 with shifts of -14°F and 50°F (-10°C and 10°C).

  1. From the Circuit 1 or Circuit 2 configuration menu, use the dial to select the heating circuit and press to select.
  2. Use the dial to select 'Shift' and press, then select 'Yes'.
  3. Change the shift value.

Applies to: Heating circuit 1 and 2

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 66. Written in our own words; check the manual for your exact model.

Adjust heating curve slope

Heat pump · Vitocal 100-AW

Slope sets how much the supply water temperature rises as outdoor temperature falls. Curves run from n=4 to n=14. Pick the curve that suits the building, climate and heating system.

  1. From the Circuit 1 or Circuit 2 configuration menu, use the dial to select the heating circuit and press to select.
  2. Use the dial to select 'Slope' and press, then select 'Yes'.
  3. Set the new slope value.

Applies to: Heating circuit 1 and 2

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 65. Written in our own words; check the manual for your exact model.

Display brightness

Heat pump · Vitocal 100-WA

Brightness can be changed through PuTTY software.

  1. Set brightness between 5% and 100% in 1% steps.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 48. Written in our own words; check the manual for your exact model.

Edit a time frame in a schedule

Heat pump · Vitocal 100-AW

Each schedule has up to five time frames, each with a start time, finish time and temperature selection. Changes are kept only when the day program is exited with Save and end.

  1. Select the schedule number and press the dial; the start time flashes.
  2. Turn the dial to set the hour and minutes, pressing to confirm each value.
  3. Set the finish time the same way.
  4. Set the temperature selection and confirm.
  5. Select R to accept the frame, or T to delete it.
  6. To add a frame, select the last frame, move to the command position and choose the add command.
  7. Select Save and end to store the day program.

Applies to: Heating, DHW and schedule menus

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 54. Written in our own words; check the manual for your exact model.

Edit DHW recirculation and cooling time frames

Heat pump · Vitocal 100-AW

DHW recirculation and space cooling schedules only use a start time and finish time per time frame. Outside the frames the recirculation pump or space cooling is not active.

  1. Select the schedule number and set the start time for the frame.
  2. Set the finish time for the frame.
  3. Use R to accept or T to delete the frame.
  4. Select Save and end to store the program.

Applies to: DHW recirculation and cooling schedules

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 55. Written in our own words; check the manual for your exact model.

Mode selection dial

Heat pump · Vitocal 100-AW AM2V

The mode selector dial sets the operating mode: Winter (space heating and DHW), Summer (space cooling and DHW) or Standby (frost protection active).

  1. Turn the mode selector dial to Winter, Summer or Standby.
  2. Use the navigation dial to move through the function screens once a mode is active.

Applies to: Vitocal 100-AW AM2V controller

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 34. Written in our own words; check the manual for your exact model.

Select operating mode with the mode dial

Heat pump · Vitocal 100-AW

The mode selector dial sets the heat pump to Winter (space heating and DHW), Summer (space cooling and DHW) or Standby (frost protection only).

  1. Turn the mode selector dial to Winter, Summer or Standby as required.

Applies to: Vitocal 100-AW AM2V indoor unit user interface

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 49. Written in our own words; check the manual for your exact model.

Silence function

Heat pump · Vitocal IND-O

Reduces noise by keeping compressor frequency below F2 and running the indoor unit at a faint breeze.

  1. Press SILENCE on the remote control to start it.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH service manual, PDF p. 11. Written in our own words; check the manual for your exact model.

Sleep function

Heat pump · Vitocal IND-O

Available in COOLING, HEATING or AUTO. In COOLING the setpoint rises 2°F (1°C) per hour up to 86°F (30°C), then holds. In HEATING it drops 2°F (1°C) per hour down to 62°F (17°C), then holds. The fan is set to low speed. Sleep runs for 7 hours, then the unit powers off. Anti-cold wind has priority in heating.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH service manual, PDF p. 9. Written in our own words; check the manual for your exact model.

Timer function (24-hour range)

Heat pump · Vitocal IND-O

Four timer types: TIMER ON, TIMER OFF, TIMER ON/OFF and TIMER OFF/ON. The timer does not change the running mode. A timer is relative time and exits if the unit has a malfunction.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH service manual, PDF p. 9. Written in our own words; check the manual for your exact model.

Activate heating set back (FP, 46°F / 8°C)

Mini-split · Vitocal Ind-O

Heating-only function that holds a 46°F (8°C) set point while in HEAT mode. Unit runs high fan until space reaches 46°F. Indoor display shows FP. Cancelled by ON/OFF, SLEEP, MODE, FAN or either TEMP arrow.

  1. Set the unit to HEAT mode with the remote pointed at the indoor unit.
  2. Press the down arrow until the set point is 60°F (16°C).
  3. Press the down arrow two times within two seconds.

Applies to: HEAT mode only

Source: Viessmann DLFSOAH Owner's Manual, p. 10. Written in our own words; check the manual for your exact model.

Combined Timer ON and Timer OFF program

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Use both timers to set a start and stop time. Order of setting depends on whether the unit is on or off.

  1. If the unit is off: set TIMER ON, then TIMER OFF. It starts at ON time and stops at OFF time.
  2. If the unit is on: set TIMER OFF first, then TIMER ON. It stops at OFF time and starts again at ON time.

Applies to: All models

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 10. Written in our own words; check the manual for your exact model.

Enter and cancel special functions with SET

Mini-split · Vitocal Ind-O

Functions include Breeze Away, Active Clean, FRESH, SLEEP and FOLLOW ME. The same steps cancel a selected function.

  1. Press SET to enter the FUNCTION setting.
  2. Press SET, or TEMP up/down, to scroll to the desired function.
  3. When the symbol flashes, press OK to confirm.
  4. To cancel, repeat the same steps.

Applies to: Wireless remote

Source: Viessmann DLFSOAH Owner's Manual, p. 9. Written in our own words; check the manual for your exact model.

Fan speed is locked in AUTO and DRY

Mini-split · Vitocal IND-F

The remote sets fan speed automatically in AUTO and DRY modes, so manual fan speed cannot be selected there.

  1. Select COOL or HEAT if manual fan speed is needed.
  2. Use FAN or fan speed buttons in those modes.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 5. Written in our own words; check the manual for your exact model.

Louver direction and auto swing

Mini-split · Vitocal IND-F

Up-down louver positions are stored, but are cancelled by TURBO, MANUAL, or a power interruption.

  1. Press DIRECT repeatedly to step through up-down positions. Each press moves the louver 30 degrees.
  2. Use the downward or horizontal position for cooling, and the vertical position for heating.
  3. Press SWING to start or stop automatic swing.
  4. Always adjust with the remote, not by hand.
  5. If the louver was moved by hand out of its range, switch the unit off, then back on.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 9, p. 10. Written in our own words; check the manual for your exact model.

Set cooling and heating temperature compensation

Mini-split · Vitocal 100-S, DLCURA

Two compensation values are set the same way. The display shows Ch during the query.

  1. Press On/Off for 2 seconds to enter the compensation settings.
  2. Press OK to send the query code (display shows Ch).
  3. Use Up/Down to select the compensation value, then press OK.
  4. Press On/Off for 2 seconds to exit.

Applies to: DLCURA 18-60 indoor/outdoor units

Source: Viessmann DLCURA service manual, p. 24. Written in our own words; check the manual for your exact model.

Set cooling frequency threshold

Mini-split · Vitocal 100-S, DLCURA

Adjust the cooling frequency threshold. Must be done within 1 minute after power on.

  1. Within 1 minute of power on, press On/Off for 2 seconds to enter Cooling Frequency Threshold Settings.
  2. Use Up/Down to select the threshold, then press OK.
  3. Press On/Off for 2 seconds to exit.

Applies to: DLCURA 18-60 indoor/outdoor units

Source: Viessmann DLCURA service manual, p. 24. Written in our own words; check the manual for your exact model.

Set heating frequency threshold

Mini-split · Vitocal 100-S, DLCURA

Adjust the heating frequency threshold. Must be done within 1 minute after power on.

  1. Within 1 minute of power on, press On/Off for 2 seconds to enter Heating Frequency Threshold Settings.
  2. Use Up/Down to select the threshold, then press OK.
  3. Press On/Off for 2 seconds to exit.

Applies to: DLCURA 18-60 indoor/outdoor units

Source: Viessmann DLCURA service manual, p. 24. Written in our own words; check the manual for your exact model.

Set the room temperature set point

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Set point is adjusted in 1°F or 1°C steps. Page 9 gives the range as 62°F (17°C) to 86°F (30°C); page 8 gives a model-dependent range. In COOL the unit will not start if the set point is above room temperature; in HEAT it will not start if the set point is below room temperature.

  1. Press TEMP up or down to change the set point.
  2. Wait for the beep and confirm the new value on the display.
  3. If the unit does not start, check that the set point is on the correct side of room temperature for the mode.

Applies to: All models

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 8-9. Written in our own words; check the manual for your exact model.

SILENCE function

Mini-split · DLFSHC

Press SILENCE on the remote to start. The compressor runs below F2 and the indoor unit gives a faint breeze to reduce noise.

  1. Press SILENCE on the remote controller to turn the function on.

Applies to: Remote controller

Source: DLFSHC service manual, p. 12. Written in our own words; check the manual for your exact model.

Timer function options

Mini-split · Vitocal IND-F

24-hour timing range. Options: TIMER ON, TIMER OFF, TIMER ON/OFF and TIMER OFF/ON. Timer does not change the current operating mode, and the setting time is relative. The timer exits if the unit has a malfunction.

Applies to: Remote control timer

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 10. Written in our own words; check the manual for your exact model.

Timer OFF (stop time) setting

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Same stepping as Timer ON (30 min to 10 h, then 60 min to 24 h). The unit shuts off automatically at the set time.

  1. Press TIMER OFF to start the time sequence.
  2. Press again to step the time up.
  3. Set to 0.0 to cancel.

Applies to: All models

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 10. Written in our own words; check the manual for your exact model.

Timer ON (start time) setting

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Can be set with the unit on or off. Each press adds 30 minutes up to 10 h, then 60 minute steps up to 24 h. The TIMER light on the unit lights when set.

  1. Press TIMER ON to start the time sequence.
  2. Press again to step the time up.
  3. Set to 0.0 to cancel.

Applies to: All models

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 10. Written in our own words; check the manual for your exact model.

Timer ON and TIMER OFF

Mini-split · Vitocal IND-F

Each press adds time. TIMER ON and TIMER OFF can be used alone or together. Setting either to 0.0 cancels it.

  1. Press TIMER ON to set the auto-start time. Each press adds 30 minutes up to 10 h, then 60 minutes up to 24 h.
  2. Press TIMER OFF to set the auto-stop time, using the same increments.
  3. To cancel, set the timer back to 0.0.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 12. Written in our own words; check the manual for your exact model.

Turn off indoor display and buzzer

Mini-split · Vitocal IND-F

The LED button turns the indoor unit display and buzzer on or off for a quieter room.

  1. Press the LED button on the remote to toggle the indoor display and buzzer.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 5. Written in our own words; check the manual for your exact model.

DHW operating program ON or OFF

Water heater · Vitodens 100-W B1HE/B1KE

DHW ON: DHW is heated per the DHW temperature and time program. DHW OFF: no DHW heating, but tank frost protection stays active. Not valid for systems with a DHW tank thermostat (Aquastat-type).

  1. Call up the home screen.
  2. Select Turn on/off, then confirm with OK.
  3. Select DHW, then confirm twice with OK.
  4. Select ON or OFF, then confirm with OK.
  5. Acknowledge the information with OK.
  6. Press and hold the exit button for about 4 sec to leave the menu.

Applies to: DHW heating on/off

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 16-17. Written in our own words; check the manual for your exact model.

High temperature limit for high heating water supply

Water heater · Vitocell 100-V

If the heating water supply runs above 248°F (120°C), install an approved high limit that caps the tank DHW temperature at 180°F (82°C).

  1. Confirm the heating water supply temperature.
  2. If it can exceed 248°F (120°C), install an approved high limit.
  3. Set the high limit so the tank DHW temperature does not exceed 180°F (82°C).

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC Technical Data Manual, p. 18. Written in our own words; check the manual for your exact model.

Set the DHW target temperature (Standard level)

Water heater · Vitodens 100-W B1HE/B1KE

Not adjustable on systems with a DHW tank thermostat (Aquastat-type); the boiler maximum then applies. Do not set DHW below 122°F (50°C) for hygiene reasons. Hot water can cause serious injury.

  1. Call up the home screen.
  2. Select DHW, then confirm with OK.
  3. Select Temperature level, then confirm.
  4. Select Standard, then confirm.
  5. Set the target value and confirm with OK.
  6. Acknowledge the information with OK.
  7. Press and hold the exit button for about 4 sec to leave the menu.

Applies to: DHW temperature setting

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Tempering valve for scald protection

Water heater · Vitocell 100-V

A tempering valve is required when the DHW storage temperature exceeds 140°F (60°C) to protect against scalding. Follow local plumbing codes.

  1. Install a tempering valve on the DHW outlet if storage temperature will exceed 140°F (60°C).
  2. Check local plumbing code for additional requirements.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC Technical Data Manual, p. 18. Written in our own words; check the manual for your exact model.

Commissioning

Start-up and set-up steps that are easy to miss.

24V interface compatibility

Air handler · DLFSDAH / DLFLDAH

The 24V interface works with all sizes except 58. From serial V191410001, size 58 ships with the compatible control board.

  1. On size 58, check the serial number before ordering the 24V interface kit.
  2. On size 58 units before V191410001, confirm the control board is compatible before connecting a 24V interface.

Applies to: Size 58 and all other sizes

Source: Vitocal IND-D technical data manual, p. 4. Written in our own words; check the manual for your exact model.

Choose the control method

Air handler · Vitocal IND-A

Scenario 1 uses the wired controller KSACN1001AAA (non-polarity, has an infrared receiver that works with the remote). The included wireless remote gives the same functions and can be used with the wired controller. Both need SW1-1 in the OFF position (default). Scenario 2 uses a third-party heat pump thermostat through the built-in 24V interface, which needs SW1-1 in the ON position.

  1. For wired or wireless controller control, set SW1-1 to OFF (default).
  2. For third-party 24V heat pump thermostat control, set SW1-1 to ON.
  3. Connect the wired controller KSACN1001AAA if used; it is non-polarity.

Applies to: DLFSAB / DLFLAB

Source: Vitocal IND-A DLFSAB/DLFLAB service manual, p. 10. Written in our own words; check the manual for your exact model.

Condensate lift pump location by size

Air handler · DLFSDAH / DLFLDAH

Sizes 09 to 18 ship with an external condensate lift pump. Sizes 24 to 58 have the lift pump built in.

  1. For 09 to 18, install the shipped external lift pump.
  2. For 24 to 58, use the built-in lift pump and the 1 in drain connection.

Applies to: All indoor sizes

Source: Vitocal IND-D technical data manual, p. 4. Written in our own words; check the manual for your exact model.

Remove J7 short connector for on/off remote function

Air handler · DLFSDAH, DLFLDAH

If the on/off remote control function is used, remove the short connector on J7 first.

  1. Remove the short connector on J7 on the indoor mainboard.
  2. Connect the external on/off switch to CN23.

Applies to: Indoor unit mainboard with on/off remote

Source: Vitocal IND-D technical data manual, p. 24. Written in our own words; check the manual for your exact model.

Set the network address for central control

Air handler · Vitocal IND-A

Use the micro-switch S1 and dial switch S2 to set the unit address when a central controller is used. Address range is 00 to 63.

  1. Set the address with S1 and S2 together; the range is 00 to 63.
  2. Use the dial positions 0 to F on S2 and the micro-switch on S1 to reach the address.
  3. Address groups: 0 to 15, 16 to 31, 32 to 47, 48 to 63.
  4. Check the factory setting in the figure before changing it; the figure values are not readable in this extract.

Applies to: Vitocal IND-A DLFUAA indoor units with central controller

Source: Vitocal IND-A DLFUAA service manual, p. 7. Written in our own words; check the manual for your exact model.

120 VAC supply and overcurrent protection

Boiler · Vitotronic 100

Install the power supply per local authority requirements, or per national codes if none apply. A disconnect switch outside the boiler room is recommended. Protection must be a maximum of 15 A (fuse or breaker) on the 120 VAC supply.

  1. Install a disconnect switch on the 120 VAC supply outside the boiler room.
  2. Fit maximum 15 A overcurrent protection (fuse or circuit breaker) on the 120 VAC supply.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 6. Written in our own words; check the manual for your exact model.

Accessory power supply

Boiler · Vitodens 200-W B2HA

Accessory power can be taken directly from the control and is switched by the system on/off switch. The Vitotronic 200-H HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control need their own 120 VAC supply from a wall receptacle.

  1. Connect accessory power at the control if the accessory is switched by the system on/off switch.
  2. Provide a separate 120 VAC supply from a wall receptacle for the HK1B mixing valve control, mixing valve kit and Solartrol.
  3. Install the accessory's own instructions for any remaining steps.

Applies to: Vitodens 200-W B2HA 45, 60 with accessories

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 45. Written in our own words; check the manual for your exact model.

Achievable combustion efficiency

Boiler · Vitorond 200 VD2

Efficiency depends on the burner fitted.

  1. With a high-performance gas burner, combustion efficiency can reach up to 85%.
  2. With a #2 oil burner, efficiency can reach up to 88%.

Applies to: Weishaupt or Riello burners

Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 14. Written in our own words; check the manual for your exact model.

Activate the filling function after commissioning

Boiler · Vitodens 100-W B1HE/B1KE

Filling function ends automatically after 20 minutes or when OK is pressed.

  1. Press the two buttons shown on the control panel together with OK for about 4 seconds, then release.
  2. Select Basic settings and press OK.
  3. Select Commissioning assistant and press OK.
  4. Use Next until Filling appears, then press OK.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W, B1HE/B1KE Combi Installation/Service instructions, p. 43. Written in our own words; check the manual for your exact model.

Activate the purging function after commissioning

Boiler · Vitodens 100-W B1HE/B1KE

Purging function ends automatically after 20 minutes or when OK is pressed. An automatic air vent valve must be installed on site.

  1. Press the two buttons shown on the control panel together with OK for about 4 seconds, then release.
  2. Select Basic settings and press OK.
  3. Select Commissioning assistant and press OK.
  4. Use Next until Purging appears, then press OK.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W, B1HE/B1KE Combi Installation/Service instructions, p. 44. Written in our own words; check the manual for your exact model.

Add external disconnect and fuel shut-off

Boiler · Vitorond 200 VD2

Viessmann recommends extra isolation outside the mechanical room or enclosed installation area.

  1. Install an additional electrical disconnect switch outside the mechanical room if possible.
  2. Install a fuel shut-off valve outside the mechanical room if possible.

Applies to: Vitorond 200 VD2

Source: Vitorond 200 VD2 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Adjust the adjustable high limit to 100 °C / 212 °F

Boiler · Vitotronic 100 GC1

Factory setting is 95 °C / 203 °F. Note the coding address 06 setting after adjusting.

  1. Disconnect power to the control and burner.
  2. Using a suitable screwdriver, lever out and remove the selector knob R behind the hinged cover.
  3. Using pointed pliers, break off the cams marked in the figure from the stop dial.
  4. Fit the selector knob R so the marking is in the centre of the selected range (75 to 100 °C / 167 to 212 °F).
  5. Check and note the coding address 06 setting.

Applies to: Vitotronic 100 GC1 adjustable high limit

Source: Vitotronic 100, GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

Adjust the differential pressure bypass valve

Boiler · Vitotron 100 VLN2

The bypass valve keeps a minimum flow through the boiler when zone valves close and reduces noise. It is set by finding the tipping point and then backing off one turn.

  1. Turn the bypass valve clockwise until it stops.
  2. Turn on all heating zones and let them run a couple of minutes.
  3. Slowly turn the valve counterclockwise until a temperature rise is felt on the outlet side. This is the tipping point.
  4. Turn the valve one further full turn.
  5. Set the thermostats to their normal temperatures.
  6. Piping can get hot quickly when the valve opens, so open it slowly.

Applies to: Vitotron 100 VLN2 hydronic piping

Source: Vitotron 100 VLN2 installation and service instructions, p. 9. Written in our own words; check the manual for your exact model.

Adjust the fixed high limit to 99 °C / 210 °F

Boiler · Vitotronic 100 GC1

Used when the safety equipment and applicable codes call for it. Adjustment is permanent.

  1. Disconnect power to the control and burner.
  2. Unclip the fuse box and swing it upwards.
  3. Turn the slotted screw on the rear of the fixed high limit until the slot points to 99 °C / 210 °F.
  4. Refit the fuse box.
  5. If set to 99 °C / 210 °F, keep the adjustable high limit at 75 °C / 167 °F or below.

Applies to: Vitorond 200 VD2/VD2A, Vitocrossal 300 CT3, Vitocrossal 200 CM2 with Vitotronic 100 GC1

Source: Vitotronic 100, GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.

Adjusting the barometric draft regulator

Boiler · Vitorond 100

Set the barometric draft regulator so the draft readings are correct, and confirm it moves freely.

  1. Adjust the barometric draft regulator so the over-fire draft is 0.00 to +0.01 in w.c.
  2. With this setting, the breeching draft should be approximately -0.02 in w.c.
  3. Confirm the barometric draft regulator moves freely while the burner runs.

Applies to: Vitorond 100 VR1 22 to 33, 91 to 140 with barometric draft regulator

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Air removal from the system

Boiler · Vitodens 200-W

Remove air through air vents in the system supply. Avoid restrictive piping where air could get trapped so the boiler can be fully purged.

  1. Install air vents in the system supply.
  2. Check that supply and return lines have no restrictive piping that can trap air.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 29. Written in our own words; check the manual for your exact model.

Allocate heating circuits to a remote control

Boiler · Vitocrossal 300

Heating circuit allocation must be set when commissioning a Vitotrol 200A or Vitotrol 300A. The Vitotrol 200A serves one heating circuit; the Vitotrol 300A serves up to three.

  1. Allocate the heating circuit to the remote control during commissioning.
  2. If the allocation is cancelled later, reset coding address A0 for that heating circuit to 0.

Applies to: Vitotrol 200A and Vitotrol 300A

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 53. Written in our own words; check the manual for your exact model.

Allocate heating circuits to Vitotrol 200A / 300A remote control

Boiler · Vitodens 200-W B2HA

The heating circuit allocation must be set during commissioning. The Vitotrol 200A serves one heating circuit; the Vitotrol 300A serves up to three. Up to two remote controls can be connected. The manual's column layout for the allocation table is unclear in this extraction, so confirm the mapping on the boiler.

  1. During commissioning, allocate the heating circuit to the Vitotrol 200A (one circuit) or Vitotrol 300A (up to three circuits).
  2. If the allocation is later cancelled, reset coding address A0 for that heating circuit to 0.

Applies to: Vitotrol 200A / 300A

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 85. Written in our own words; check the manual for your exact model.

Allocating heating circuits to a Vitotrol remote control

Boiler · Vitodens 200-W

Heating circuit allocation must be set when commissioning a Vitotrol 200A or 300A. One heating circuit can go to the 200A, up to three to the 300A, and up to two remote controls can be connected. The extract does not clearly map each Vitotrol column to its circuit, so check the full table in the manual.

  1. Configure heating circuit allocation at commissioning.
  2. If an allocation is later cancelled, set coding address A0 for that heating circuit back to 0.

Applies to: Vitotrol 200A and 300A remote controls

Source: Vitodens 200-W B2HB service manual, p. 90. Written in our own words; check the manual for your exact model.

Alternative DHW connection with low-loss header

Boiler · Vitodens 200-W B2HA

The alternative DHW piping applies to system layouts 2, 5, 6 and 8. The boiler control pump logic must be programmed in the Service Instructions. With a low-loss header, the DHW connections can be made downstream of the header.

  1. Program the boiler control pump logic in the Service Instructions.
  2. Set the applicable system coding at coding level 2 in the Service Instructions.

Applies to: System layouts 2, 5, 6 and 8

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 42. Written in our own words; check the manual for your exact model.

Alternative DHW tank connection

Boiler · Vitodens 200-W B2HB

Alternative piping for the DHW tank only, used with system layouts 2, 5, 6 and 8. The boiler control pump logic must be programmed in the Service Instructions. With a low-loss header, the DHW connections can be made downstream of the header.

  1. Program the boiler control pump logic in the Service Instructions.
  2. If a low-loss header is used, the DHW connections can be made downstream of it.
  3. Set the system coding at coding level 2 as described in the Service Instructions.
  4. Refer to the Service Instructions for the coding values that apply to this layout.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 (system layouts 2, 5, 6, 8)

Source: Vitodens 200-W B2HB installation instructions, p. 43. Written in our own words; check the manual for your exact model.

Altitude derating

Boiler · Vitocrossal 200 CM2

Derate the input capacity by 3% per 1000 ft up to 4,999 ft. From 5,000 to 10,000 ft with the electronic altitude adjustment made, derate by an additional 0.6% per 1000 ft, for a total derate of 18%.

  1. Up to 4,999 ft: derate input 3% per 1000 ft.
  2. 5,000 to 10,000 ft: make the electronic altitude adjustment, then derate an additional 0.6% per 1000 ft (18% total).
  3. Input capacity after electronic altitude adjustment is the value to check.

Applies to: Vitocrossal 200 CM2 186 to 311

Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 60. Written in our own words; check the manual for your exact model.

Ambient and mechanical room limits

Boiler · Vitodens 200-W B2HB

Keep the boiler room within the listed temperature range and free of contaminants. Marine locations need room-air vent systems.

  1. Keep ambient temperature above 32°F (0°C) and no higher than 104°F (40°C).
  2. Do not install where combustion air contains halogenated hydrocarbons, paint solvents, cleaning fluids or heavy dust.
  3. Avoid constant high humidity (for example frequent laundry drying) and never close existing ventilation openings.
  4. In damp, salty coastal areas, do not use direct vent (outdoor air) systems; use room-air-dependent venting.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 9, p. 12. Written in our own words; check the manual for your exact model.

Antifreeze in heating system

Boiler · Vitodens 100-W, B1HE, B1KE

Use only glycol made for hot water heating. Antifreeze may need a backflow preventer and can affect other components.

  1. Use no automotive silicate-based antifreeze.
  2. Check the system frequently after filling with antifreeze.
  3. Tell the owner the system is filled with glycol.
  4. Give the owner a material safety data sheet (MSDS) for the antifreeze used.

Applies to: Systems filled with glycol mix

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 27. Written in our own words; check the manual for your exact model.

Antifreeze in the heating system

Boiler · Vitorond 100

Antifreeze may be used where freezing can occur. Use only antifreeze made for hot water heating systems.

  1. Use a 40% antifreeze content for freeze-up protection to -10°F (-23°C).
  2. Do not use automotive silicate-based antifreeze.
  3. Check the total system often when it is filled with antifreeze.
  4. Leave a copy of the Material Safety Data Sheet on site.
  5. Check whether a backflow preventer is needed in the automatic water feed.

Applies to: Hydronic heating system

Source: Vitorond 100 installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.

Application 3: DHW timer and HC1 settings

Boiler · Vitocrossal 300 CU3A

Set the DHW timer to match when domestic hot water can be made. The HC1 settings remain available if an outdoor-reset zone is also connected.

  1. If DHW can be produced at any time, set the timer to 0:00 to 24:00.
  2. If an outdoor-reset zone is connected, use the HC1 settings.
  3. If mixing valve extension kits are used, adjust the outdoor reset settings as required.

Applies to: Application 3 operational setup

Source: Vitocrossal 300 CU3A Application Guide, p. 29. Written in our own words; check the manual for your exact model.

Application 5 DHW timer setting

Boiler · Vitodens 222-F

If domestic hot water should be available at any time, the DHW timer must be opened up for the full day.

  1. Set the timer schedule as the customer needs.
  2. For DHW available at any time, program the timer to 0:00 to 24:00.

Applies to: Vitodens 222-F, B2TB, Application 5

Source: vitodens_222_application_guide.pdf, p. 49. Written in our own words; check the manual for your exact model.

Application 5 start-up wizard (zone circuit with fixed setpoint)

Boiler · Vitodens 222-F

Start-up wizard for Application 5: one high temperature zone (ZC1) plus a low temperature heating circuit with a 3-way mixing valve (HC2). Simultaneous space heating and DHW is allowed, so size the boiler for both loads.

  1. Select the number of zone circuits to match the thermostats wired to the DE connections, then press OK.
  2. Confirm the fixed setpoint mode for zone calls, then press OK.
  3. Enter the target water temperature the boiler should hold on a call for heat, then press OK.
  4. Arrow to the 157 output to assign the zone pump, then press OK.
  5. Check the zone circuit output summary against the number of zones chosen, then press OK.
  6. Press OK to finish start-up. The boiler is then ready for operation.

Applies to: Vitodens 222-F, B2TB, Application 5

Source: vitodens_222_application_guide.pdf, p. 48. Written in our own words; check the manual for your exact model.

Application 5: HC1 outdoor reset and mixing valve extension kits

Boiler · Vitocrossal CU3A

HC1 settings remain available if an outdoor reset zone is connected. If mixing valve extension kits are used, set the outdoor reset parameters to suit.

  1. If an outdoor reset zone is wired, check the HC1 settings.
  2. If mixing valve extension kits are fitted, review and adjust the outdoor reset settings.

Applies to: Application 5 with outdoor reset or mixing valve extension kits

Source: Vitocrossal 300, CU3A Application Guide, p. 41. Written in our own words; check the manual for your exact model.

Application 6 DHW timer setting

Boiler · Vitodens 222-F

Same DHW timer rule as Application 5: for DHW at any time, the timer must run the full day.

  1. Set the timer schedule as the customer needs.
  2. For DHW available at any time, program the timer to 0:00 to 24:00.

Applies to: Vitodens 222-F, B2TB, Application 6

Source: vitodens_222_application_guide.pdf, p. 53. Written in our own words; check the manual for your exact model.

Application 6 piping: no external check valves or primary/secondary loop

Boiler · Vitocrossal CU3A

External flow check valves are not needed when the circulators have them built in. Primary/secondary piping is not required because the CU3A is a high mass boiler. Application code CU3I 3HC/ZC3ZP.02 applies.

  1. Confirm the circulators have built-in flow check valves before leaving out external check valves.
  2. Do not add primary/secondary piping for the CU3A high mass boiler.

Applies to: Application 6, code CU3I 3HC/ZC3ZP.02

Source: Vitocrossal 300, CU3A Application Guide, p. 42. Written in our own words; check the manual for your exact model.

Application 6 start-up wizard (1 zone circuit, fixed setpoint, 157 pump output)

Boiler · Vitodens 222-F

Start-up wizard for Application 6 with two mixing heat circuits (HC2, HC3) plus one unmixed high temperature circuit (ZC1). The ZC1 call runs the P3 pump through the 28/20 plug. ZC1 can run on fixed setpoint or weather compensation. HC2 and HC3 follow the boiler heating curves.

  1. Select 1 zone circuit to match the ZC thermostat wired to the DE connections, then press OK.
  2. Confirm the fixed setpoint mode for zone calls, then press OK.
  3. Enter the target water temperature the boiler should hold on a call for heat, then press OK.
  4. Arrow to the 157 output to assign the pump, then press OK.
  5. Check the zone circuit output summary against the zones selected, then press OK.
  6. Press OK to finish start-up. The boiler is then ready for operation.

Applies to: Vitodens 222-F, B2TB, Application 6

Source: vitodens_222_application_guide.pdf, p. 52. Written in our own words; check the manual for your exact model.

Application 6: the mixing valves follow the boiler heating curves

Boiler · Vitocrossal CU3A

In this layout the HC2 and HC3 mixing valves run on heating curve settings stored in the boiler. The ZC1 circuit can be set to a fixed setpoint or to weather compensation. The ZC1 call switches the 28/20 output to pump P3.

  1. Set the heating curves for HC2 and HC3 in the boiler control.
  2. Choose fixed setpoint or weather compensated operation for ZC1 as the system requires.

Applies to: Application 6 with two mixing valves and a high temperature zone

Source: Vitocrossal 300, CU3A Application Guide, p. 44. Written in our own words; check the manual for your exact model.

Application 7: boiler target when several zones call for different temperatures

Boiler · Vitocrossal CU3A

When several zones request different temperatures at the same time, the boiler targets the highest requested temperature.

  1. Expect the boiler to run to the highest zone setpoint when more than one zone is calling.

Applies to: Application 7, code CU3I 3ZC9C.01

Source: Vitocrossal 300, CU3A Application Guide, p. 43. Written in our own words; check the manual for your exact model.

Application 7: jumper between the 40A plug and the 157 plug

Boiler · Vitocrossal CU3A

A jumper must be installed between the 40A plug and the 157 plug in this application.

  1. Install the jumper between the 40A plug and the 157 plug before starting up Application 7.

Applies to: Application 7, code CU3I 3ZC9C.01

Source: Vitocrossal 300, CU3A Application Guide, p. 43. Written in our own words; check the manual for your exact model.

Application 7: zone control wizard, ZC1 weather compensated with ZC2 and ZC3 fixed setpoint

Boiler · Vitocrossal 300 CU3A

Three heating circuits: ZC1 gets a call from a Multizone Control and runs weather compensated, ZC2 gets a call from a second Multizone Control (two zone valves, fixed setpoint), ZC3 comes from a snow melt control and runs fixed setpoint with a pump on the 157 output. ZC1 has no pump in this layout.

  1. Select the number of zone circuit connections to match the controls wired to the DE connections, then press OK.
  2. For ZC1, arrow down to the weather compensated function and press OK.
  3. Adjust slope and shift to set the heating curve. The screen shows the curve moving as you change them.
  4. Press OK to continue. These settings can be changed later.
  5. For ZC2, select fixed setpoint, press OK, and set the zone target temperature.
  6. For ZC3, select fixed setpoint, set the zone target temperature, and select the 157 pump output.

Applies to: Application 7, ZC1 weather compensated with ZC2 fixed setpoint

Source: Vitocrossal 300 CU3A application guide, p. 48. Written in our own words; check the manual for your exact model.

Assembling PP(s) and stainless vent pipe

Boiler · Vitocrossal 300 CA3B Dual Fuel

Keep the vent route short and direct with as few bends as possible. Pipe must slope back to the boiler so condensate drains from the flue to the boiler. Use only the vent maker's parts with PP(s) systems.

  1. Check that the gaskets are seated in the rigid pipe collars.
  2. Lubricate the pipe ends and collars with water, then slide the pieces together with a gentle twist.
  3. Slope the vent at least 2 to 3 degrees toward the boiler. For a 3 degree slope, use about 2 in. per 3.3 ft (50 mm per 1 m).
  4. Cut pipe square with a hacksaw or snips, file the edges smooth, and keep the pipe round.
  5. Deburr and clean the pipe after cutting.
  6. Follow the vent manufacturer's installation instructions alongside this manual.
  7. Keep elbows to a minimum, avoid back-to-back 90 degree elbows, and use 45 degree elbows where possible.
  8. Do not route the vent through or inside another vent or chimney, except a masonry flue used only by this boiler.

Applies to: Vitocrossal 300 CA3B Dual Fuel venting

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 49. Written in our own words; check the manual for your exact model.

Assign a heating circuit to the remote control (key method during operation)

Boiler · Vitotrol 200A

Changes the heating circuit assignment while the system is running.

  1. Press the two keys shown on the remote control together for about 4 seconds.
  2. Use the +/- keys to select heating circuit 1 (H 1), 2 (H 2) or 3 (H 3).
  3. Press OK to confirm. The operating state of the heating system is transferred.
  4. Wait for the display segments to finish rotating (this can take up to 5 minutes).

Applies to: Vitotrol 200A remote control

Source: Vitotrol 200A Installation, Operating and Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Assign a heating circuit to the remote control (power-up method)

Boiler · Vitotrol 200A

Used when the remote control is first connected to the boiler control unit. Up to 2 remote controls can be connected to one control unit.

  1. Switch on the power supply at the control unit. The remote control shows H 1.
  2. Use the +/- keys to select heating circuit 1 (H 1), heating circuit 2 (H 2) or heating circuit 3 (H 3).
  3. Press OK to confirm. The operating state of the heating system is transferred.
  4. Wait for the display segments to finish rotating (this can take up to 5 minutes).

Applies to: Vitotrol 200A remote control

Source: Vitotrol 200A Installation, Operating and Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Assign functions in the commissioning assistant

Boiler · Vitocrossal 200 CI2

Relay and input functions are chosen in the commissioning assistant by selecting the connected component.

  1. Open the commissioning assistant.
  2. Select the connected component for P1, P2, lH or the tank sensor.

Applies to: P1, P2, lH and tank sensor

Source: Vitocrossal 200 CI2 Installation Instructions, p. 26. Written in our own words; check the manual for your exact model.

Autobinding reset without a power cycle

Boiler · Versatronik 503, NR2/Analog Bridge

Use this when the LON participant number has to change without a power cycle, or when a tool binding must be cleared.

  1. Set the S1 dial to position 9.
  2. Wait 10 seconds.
  3. Press and hold the service button for 2 seconds.
  4. Wait 10 seconds.
  5. Set the dial to the desired boiler number.
  6. Wait about 10 seconds for the new address to take effect.

Applies to: Versatronik 503 rotary dial S1

Source: Versatronik 503 NR2/Analog Bridge installation and operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Automatic summer and winter time changeover

Boiler · Versatronik 200

The controller changes time automatically on the Sunday after the set start date, at 2:00 or 3:00 am. Only change the default if the rule changes.

  1. Set the earliest date for the change under the summer time start and end entries.
  2. Leave the default unless the date is changed by political decree.

Applies to: Controllers in Central European time zones

Source: Versatronik 200 installation and operating manual, p. 134. Written in our own words; check the manual for your exact model.

Avoid overheating the heat source with dynamic settings

Boiler · Versatronik 200

Stage-on and stage-off dynamic values that are too low or too high can overheat the heat source and trip the STB.

  1. Keep Stage-on dynamic and Stage-off dynamic within 20-500 K.
  2. Check the STB (safety thermal cutout) after changing these values.
  3. Do not set values too low or too high for the system load.

Applies to: Versatronik 200 modulating boilers

Source: Versatronik 200 installation and operating manual, p. 145. Written in our own words; check the manual for your exact model.

Balancing valve placement

Boiler · Vitorond 200 VD2

Valve position is needed for laminar flow through the boiler.

  1. Install any balancing valve 5 pipe diameters from fittings.
  2. Install any balancing valve 10 pipe diameters from circulation pumps.
  3. Have a certified balancing firm balance the system before boiler start-up.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 12. Written in our own words; check the manual for your exact model.

Balancing valve placement and balancing

Boiler · Vitorond 200 VD2A

Balancing valves must be placed with enough straight pipe for laminar flow. The balancing must be done by a certified balancing firm before boiler start-up.

  1. Install the balancing valve 5 pipe diameters from any fittings.
  2. Install the balancing valve 10 pipe diameters from circulation pumps.
  3. Have a certified balancing firm balance the system before start-up.
  4. Ask the consulting engineer to review the design if more balancing valves are needed.

Applies to: Vitorond 200 VD2A hydronic piping

Source: vitorond 200 VD2A technical data manual, p. 12. Written in our own words; check the manual for your exact model.

Barometric draft regulator type and location

Boiler · Vitorond 200 VD2

A barometric draft regulator is required in the chimney or vent for proper operation.

  1. For natural gas or propane, use a double-acting barometric draft regulator.
  2. For #2 fuel oil, use a single-acting barometric draft regulator.
  3. Install the regulator 5 to 7 ft. (1½ to 2 m) from the breeching outlet at the rear of the boiler.
  4. Size the regulator opening to match the chimney diameter, not the breeching outlet.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 15-16. Written in our own words; check the manual for your exact model.

Beckett GeniSys post purge

Boiler · Vitorond 100

The GeniSys control has post purge set at the factory.

  1. Factory default post purge is 30 seconds.
  2. Field adjustment is allowed. Follow the Beckett burner manual.

Applies to: Beckett NX burner with GeniSys control

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

Boiler circuit pump sizing for cascade systems

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

Each boiler circuit pump must move at least the total heating circuit volume flow. Recommended margin is 110%.

  1. Size each boiler circuit pump for at least the maximum total heating circuit volume flow.
  2. Apply the recommended 110% margin.

Applies to: Multi-boiler systems with boiler circuit pumps (system versions 4 to 5)

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Boiler coding card

Boiler · Vitotronic 300

Only the coding card supplied with the boiler may be used. It comes in the boiler accessory pack.

  1. Push the boiler coding card through the recess in the cover.
  2. Insert it in plug-in location X7.

Applies to: Vitotronic 300 KW3

Source: Vitotronic 300 installation instructions, p. 22. Written in our own words; check the manual for your exact model.

Boiler connection kit contents

Boiler · Vitorond 200 VD2A

The standard boiler connection kit includes a safety supply connection to the pressure relief valve, a low water cut-off, a temperature gauge and the boiler water supply connection. A single or dual aquastat is optional.

  1. Connect the safety supply to the pressure relief valve.
  2. Install the low water cut-off in its connection.
  3. Install the temperature gauge in its connection.

Applies to: Vitorond 200 VD2A boiler connection kit

Source: vitorond 200 VD2A technical data manual, p. 10. Written in our own words; check the manual for your exact model.

Boiler in heating/cooling application valve setup

Boiler · Vitodens 100-W WB1B

When the chilled medium is piped in parallel with the boiler, valves stop chilled water from entering the boiler. Flow control valves or automatic means are needed to prevent gravity circulation during cooling.

  1. Label the valves v1 and v2.
  2. Cooling season: close valve v1 and open valve v2.
  3. Heating season: close valve v2 and open valve v1.
  4. Check the chiller manufacturer's installation instructions for extra requirements.

Applies to: Vitodens 100-W WB1B with refrigeration system or chiller

Source: Vitodens 100-W, WB1B installation manual, p. 47. Written in our own words; check the manual for your exact model.

Boiler piping with a chiller (heating/cooling)

Boiler · Vitodens 200-W B2HB

When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler through valves so chilled medium cannot enter the boiler. Hot water coils in air handlers exposed to refrigerated air need flow control valves or another automatic means to stop gravity circulation during cooling.

  1. Pipe the chilled medium in parallel with the boiler using valves.
  2. Add flow control valves or an automatic means on hot water coils in air handlers exposed to refrigerated air.
  3. Use a spring-loaded flow check valve and a safety header with automatic air vent and pressure relief valve as shown.
  4. Check the chiller manufacturer's installation instructions for additional requirements.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 44. Written in our own words; check the manual for your exact model.

Boiler placement and levelling

Boiler · Vitorond 100

Place the boiler close to the chimney and protect the oil ignition components from water spray or splashing during operation and service.

  1. Locate the boiler as close to the chimney as possible.
  2. Set the boiler with a slight incline toward the rear using the levelling bolts.
  3. Protect oil ignition system components from water spraying or splashing.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 13. Written in our own words; check the manual for your exact model.

Boiler sensor installation

Boiler · Vitotronic 100

The boiler sensor goes into the boiler sensor well. Do not kink the surrounding capillaries.

  1. Insert the boiler sensor into the boiler sensor well without kinking the capillaries.
  2. Route the cable to the boiler control between the enclosure panels and insulation jacket.
  3. Connect the boiler sensor wires to connector X6 terminals 3.1 and 3.2.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 14. Written in our own words; check the manual for your exact model.

Boiler water temperature limit

Boiler · Vitorond 100 VR1

Factory high limit is 167 °F (75 °C) on Vitotronic controls. The adjustable high limit can be raised to increase supply temperature. For new systems, Viessmann recommends designing radiation and DHW for 158 °F (70 °C) supply to reduce piping losses.

Applies to: Vitotronic and high limit settings

Source: Vitorond 100, VR1 Technical Data, p. 10. Written in our own words; check the manual for your exact model.

Boiler water temperature limit and supply design

Boiler · Vitorond 200 VD2

The factory high limit is set at 167°F (75°C). Viessmann recommends designing for 158°F (70°C) to reduce piping losses.

  1. Leave the high limit at 167°F (75°C) unless the system needs more.
  2. Raise the adjustable high limit only if a higher supply temperature is required.
  3. Design radiation and domestic hot water for a 158°F (70°C) supply temperature where possible.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 16. Written in our own words; check the manual for your exact model.

Burner blast tube and insulation fit-up

Boiler · Vitorond 200, VD2A

Set the burner blast tube depth and seal the gap at the combustion chamber door.

  1. Make sure the burner blast tube projects at least 4.5 in. (110 mm) into the boiler from the front edge of the burner plate.
  2. After the burner is installed, fill the gap between the blast tube and the door insulation insert with the supplied insulating material.
  3. Seal the sight glass for pressure tightness.
  4. Connect the sight glass to the burner with the supplied clear plastic hose.

Applies to: Vitorond 200 VD2A burner installation

Source: Vitorond 200 VD2A installation manual, p. 32. Written in our own words; check the manual for your exact model.

Burner primary control 120VAC supply

Boiler · Vitorond 100

The Beckett GeniSys or Carlin 70200 primary control needs a constant 120VAC supply on its black wire, even when the burner is idle.

  1. Connect a constant 120VAC supply to the BLACK wire on the primary control.
  2. Disconnect power before servicing the control.

Applies to: Beckett GeniSys and Carlin 70200 primary controls

Source: Vitorond 100 installation and service instructions, p. 33. Written in our own words; check the manual for your exact model.

Burner selection and firing pressure

Boiler · Vitorond 200, VD2A

The burner must be ordered for a specific fuel or as a combination burner, and the boiler must run with positive pressure in the combustion chamber.

  1. Order the burner for the specific fuel, or as a combination burner naming the fuels.
  2. Use only an approved oil or gas burner type.
  3. Check the separate burner selection chart in the Technical Data Manual.
  4. Keep all components protected from water during operation and service.

Applies to: Vitorond 200 VD2A burners

Source: Vitorond 200 VD2A installation manual, p. 32. Written in our own words; check the manual for your exact model.

Burner sight glass and door insulation

Boiler · Vitorond 200 VD2

Seal the sight glass and avoid overtightening it. Fill the gap between the burner blast tube and the door insulation.

  1. Connect the sight glass to the burner with the clear plastic hose supplied.
  2. Seal the sight glass for pressure tightness.
  3. Do not overtighten the brass sight glass holder, as this can break the glass.
  4. After burner installation, fill the gap between the blast tube and the combustion chamber door insulation with the supplied insulating material.

Applies to: VD2-320 to VD2-1080

Source: Vitorond 200 VD2 installation manual, p. 33. Written in our own words; check the manual for your exact model.

BUS ID numbering for heating circuits

Boiler · Versatronik 200

Heating circuits are numbered in order starting at 01, and no number may be used twice. If you replace a controller, enter exactly the same heating circuit numbers as the old controller.

  1. Number heating circuits in sequence from 01.
  2. Do not assign the same circuit number twice.
  3. On a replacement controller, enter the same heating circuit numbers as the unit being replaced.

Applies to: Versatronik 200 System Control

Source: Versatronik 200 Installation and Operating Manual, p. 120. Written in our own words; check the manual for your exact model.

Bus termination and Time Master checks

Boiler · Versatronik 200

Only one bus termination resistor and only one Time Master may be used in the system. Incorrect settings can cause malfunctions.

  1. Confirm only one controller (HG or cascade controller) has BUS Termination set to On. Set it to Off if a CoCo is installed.
  2. Confirm only one controller has Time Master set to On.
  3. Check that heating circuit numbers (BUS ID) are unique; replacement controllers must match the old numbers.

Applies to: Versatronik 200 system with multiple controllers and bus

Source: Versatronik 200 installation and operating manual, p. 137. Written in our own words; check the manual for your exact model.

Bypass required on large water content systems

Boiler · Vitorond 100 VR1

Systems with more than 1 USG of water for every 13,000 Btu/h of boiler input (for example, older gravity systems with large free-standing radiators) need a supply-to-return bypass to prevent flue gas condensation in the heat exchanger and vent. Viessmann recommends a bypass on all cast iron boilers.

  1. Calculate system water volume against boiler input (1 USG per 13,000 Btu/h).
  2. If the system is above that ratio, install a bypass pipe from the supply pipe to the return pipe.
  3. Install the bypass on any system as a precaution if preferred.

Applies to: Vitorond 100 VR1 boilers on large water content systems

Source: Vitorond 100 VR1 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.

Cable routing at the control unit

Boiler · Vitodens 200-W B2HA

Cables must be routed as illustrated so the control unit can move freely. Cables near the control unit must not be secured to the control unit bracket. Cable temperature ratings must not be exceeded.

  1. Route all cables as shown in the illustration.
  2. Do not secure cables to the control unit bracket.
  3. Check that the cable temperature ratings are not exceeded when routing and securing cables on site.

Applies to: Vitodens 200-W B2HA 45, 60 control connections

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 45. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm and start-up paperwork

Boiler · Vitodens 200-W

Before the boiler is put into operation, confirm that at least one CO alarm is installed in the living space, following the alarm maker's instructions and local codes. The licensed heating contractor must complete the Maintenance Record at initial start-up.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 7. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm before operation

Boiler · Vitocrossal 200 CI2

Installation requirement for CO protection.

  1. Confirm at least one carbon monoxide alarm is installed in the living space before the appliance is put into operation.
  2. Install, maintain and replace alarms per the alarm manufacturer's instructions and local codes.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 operating instructions, p. 2, 6. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm check

Boiler · Vitodens 200-W B2HA

Confirm at least one carbon monoxide alarm is installed in the living space before the boiler is put into operation, following the alarm maker's instructions and local codes.

  1. Verify a CO alarm is installed in the residence or living space.
  2. Only then start the appliance.

Applies to: All B2HA models

Source: Vitodens 200-W B2HA installation manual, p. 6. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm required

Boiler · Vitorond 200 VD2A

The installer must confirm that at least one carbon monoxide alarm is installed in the living space or home, following the alarm maker's instructions and local codes, before the boiler is put into operation.

  1. Confirm a CO alarm is installed in the residential living space before start-up.
  2. Install the alarm per the manufacturer's instructions and local code.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Installation Instructions, p. 6. Written in our own words; check the manual for your exact model.

Carbon monoxide detectors and maintenance

Boiler · Vitotrol 200A

Follow local rules for installing carbon monoxide detectors. Follow the Viessmann maintenance schedule for the boiler. The heating contractor must show the owner the equipment, safety requirements and shutdown procedure, and advise annual professional service before each heating season.

  1. Install carbon monoxide detectors per local regulations.
  2. Follow the boiler maintenance schedule.
  3. Review the shutdown procedure and the need for annual service with the owner before the heating season.

Applies to: Vitotrol 200A with Viessmann boiler

Source: Vitotrol 200A installation, operating and service instructions, p. 2. Written in our own words; check the manual for your exact model.

Cascade control amp load and isolation relays

Boiler · Vitocrossal 300 CU3A

The cascade control can carry a maximum of 6 amps. Isolation relays may be needed when the current draw of field-supplied components is exceeded.

  1. Add up the current draw of field-supplied circulators and mixing valve motors.
  2. If the total exceeds 6 amps, fit isolation relays.

Applies to: Cascade control, Applications 9 and 10

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 56. Written in our own words; check the manual for your exact model.

Cascade heat generator scan and output entry

Boiler · Versatronik 200

After a restart or new configuration, the controller scans the bus for about one minute. Output values cannot be entered during this scan. A generator that reports its output is entered automatically. A generator that reports no output is entered as 15 kW and can be changed by hand. Identical boilers only need one release each.

  1. Wait for the SCAN display to finish (about 1 minute).
  2. Select the boiler and stage with the Prog button.
  3. Enter or adjust the HS output value; use --- for not available and 0 for available but deactivated.
  4. Check the entered output matches the actual boiler.

Applies to: Versatronik 200 cascade, output boiler stage list

Source: Versatronik 200 installation and operating manual, p. 109. Written in our own words; check the manual for your exact model.

Cascade setup for maximum burner count

Boiler · Versatronik 200

To keep as many burners running as possible, set the next-boiler threshold to zero and the minimum modulation to the lowest stage value.

  1. Set Mod % next boiler on to 0.
  2. Set Modulation Min to the minimum modulation degree of the heat generator stages.
  3. Check that the boiler on-delay in the burner control matches the controller setting.

Applies to: Versatronik 200 multi-boiler cascade

Source: Versatronik 200 installation and operating manual, p. 144. Written in our own words; check the manual for your exact model.

Cascade wiring layout for 4 boilers

Boiler · Vitocrossal 300 CU3A

The Application 10 diagram shows boilers #1 to #4, each with power and a LON cable connection to the cascade control. Circulators P1.1 to P1.4 are shown with power connections.

  1. Connect power to each boiler and to circulators P1.1 to P1.4.
  2. Connect a LON cable from each boiler to the cascade control.
  3. Use the diagram in the manual for the full wiring layout. Only the labels are legible in the extracted text.

Applies to: Application 10, 4-boiler cascade

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 59. Written in our own words; check the manual for your exact model.

Central heating only without DHW heating

Boiler · Vitotronic 300-K MW1B, Vitotronic 100 GC1B

There is no program for central heating without DHW. To get central heating only, the DHW heating is kept at a low setpoint. DHW is not heated unnecessarily, while DHW tank frost protection stays active.

  1. Select the heating program Heating and DHW.
  2. Set the DHW temperature to 50° F (10° C).

Applies to: Vitotronic 300-K MW1B and Vitotronic 100 GC1B

Source: Viessmann Vitotronic 100 GC1B / 300-K MW1B operating instructions, p. 40. Written in our own words; check the manual for your exact model.

Change mixing valve rotation direction

Boiler · Vitotronic 200-H

The rotation direction of the mixing valve is set with coding address CA (see page 49). Modular-Divicon systems need the rotation reversed. The source table of factory default direction per piping layout is not legible in this extract.

  1. Change the rotation direction with coding address CA (see page 49 of the manual).
  2. For systems with Modular-Divicon, reverse the rotation direction.
  3. If the mixing valve insert must be converted, follow the mixing valve installation instructions.
  4. Check the result with the relay test (outputs 7 and 9).

Applies to: Systems with mixing valve actuator

Source: Vitotronic 200-H installation and service instructions, p. 18-19. Written in our own words; check the manual for your exact model.

Check and set expansion tank precharge

Boiler · Vitotron 100 VLN2

The expansion tank is precharged to 12 psi at the factory. Its Schrader valve is reached from the bottom of the boiler.

  1. Access the Schrader valve from the bottom of the boiler.
  2. Connect a pressure gauge to read the tank pressure.
  3. Use a pump to add air if the precharge is low.
  4. Match the precharge to the system pressure requirement if needed.

Applies to: Vitotron 100 VLN2 expansion tank

Source: Vitotron 100 VLN2 installation and service instructions, p. 8-9. Written in our own words; check the manual for your exact model.

Check before enabling central heating

Boiler · Vitotronic 300-K, Vitotronic 200

Before relying on central heating, confirm the heating circuit, room temperature, heating program and time program are set. Heating circuit selection only applies when the system has more than one circuit.

  1. Select the heating circuit to change, if the system has several.
  2. Set the required standard room temperature.
  3. Set the heating program to the required option.
  4. Set the time program for central heating.
  5. Allow time for the rooms to reach the set temperature when planning time phases.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 16. Written in our own words; check the manual for your exact model.

Check burner cycling before leaving site

Boiler · Vitorond 100, VR1

Confirm the burner switches on and off correctly on a real call for heat before leaving the job. Failure to do this can cause a boiler runaway with risk of damage, injury or death.

  1. Call for heat at the thermostat and confirm the burner fires.
  2. Let the setpoint be reached and confirm the burner shuts off.

Applies to: Hydrostat 3250-Plus and other burner controls

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 28. Written in our own words; check the manual for your exact model.

Check burner motor rotation at commissioning

Boiler · Vitotronic 300

Three-phase burner motors can run backwards if the phases are wired wrong. Correct it at the burner terminals, not in the control.

  1. Check motor rotation against the arrow on the burner.
  2. If the rotation is wrong, disconnect power.
  3. Reverse wires BK1 and BK2 on the burner terminals.

Applies to: 3 PH 208, 460 or 575 V burners on VD2/VD2A/CT3 controls

Source: Vitotronic 300 GW2 installation and service instructions, p. 54. Written in our own words; check the manual for your exact model.

Check burner motor rotation at commissioning (3-phase)

Boiler · Vitotronic 100

On 3-phase burners, the motor must turn in the direction marked on the burner. If it turns the wrong way, the wires must be swapped. Power must be off before any change.

  1. During commissioning, check the burner motor rotation.
  2. If the motor turns opposite to the direction marked on the burner, disconnect the power supply.
  3. Reverse wires BK1 and BK2 on the burner terminals.
  4. Restore power and recheck rotation.

Applies to: 3-phase burner motor supply (208, 460 or 575 V)

Source: Vitotronic 100 GC1 installation and service instructions, p. 81. Written in our own words; check the manual for your exact model.

Check coding addresses C7 and C9 for underfloor heating with heat exchanger

Boiler · Vitotronic 200-H

In System Example 2 (underfloor heating circuit with heat exchanger), the coding addresses 00:2 to 00:10 are set automatically with a DHW tank. Also observe coding addresses C7 and C9 in the group "Heating circuit...".

  1. Check coding addresses C7 and C9 in the group "Heating circuit...".

Applies to: Vitotronic 200-H HK1B, underfloor heating with heat exchanger

Source: Vitotronic 200-H HK1B installation and service manual, p. 13. Written in our own words; check the manual for your exact model.

Check combustion air leakage in the coaxial vent

Boiler · Vitodens 200-W B2HB

Simple leak test on the coaxial air intake gap during start-up.

  1. Measure CO2 in the combustion air in the coaxial gap of the air intake pipe using the port on the vent adaptor.
  2. Pass if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
  3. If the readings fail, check the venting system thoroughly.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.

Check connections and perform combustion analysis

Boiler · Vitodens 200-W B2HA

Check all primary and secondary connections for leaks. Take a CO measurement before and after work on gas appliances.

  1. Check heating system and domestic hot water connections for leaks.
  2. Correct leaks at fittings, pumps and valves.
  3. Take a CO measurement before and after work (see page 31).
  4. Record combustion values in the sequence given in the maintenance record on page 105.

Applies to: Commissioning checks

Source: Vitodens 200-W B2HA service instructions, p. 23. Written in our own words; check the manual for your exact model.

Check heating circuit allocation label

Boiler · Vitotronic 300-K MW1S

Before changing any adjustments, confirm the heating circuit allocation label is attached to the matching field on the programming unit. Press the correct heating circuit button before making changes.

  1. Check that the heating circuit allocation label is on the correct field of the programming unit.
  2. Press the matching heating circuit button before adjusting anything.

Applies to: Vitotronic 300-K, MW1S

Source: Viessmann Vitotronic 100/300-K installation and service manual, p. 72. Written in our own words; check the manual for your exact model.

Check heating circuit assignment stickers

Boiler · Vitotronic 300

Confirm the heating circuit stickers are in place before any setting. Press the matching circuit button before each adjustment.

  1. Check that the assignment stickers are on the correct positions on the control unit.
  2. Press the matching heating circuit button before starting each setting.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 64. Written in our own words; check the manual for your exact model.

Check heating circuit sticker assignment

Boiler · Vitotronic 300 GW2

Confirm the heating circuit assignment stickers are on the correct spots on the control unit before settings are changed.

  1. Check that the assignment stickers for the heating circuits are placed in the right locations on the control unit.
  2. Press the matching circuit button before starting each setting.

Applies to: Vitotronic 300 GW2

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 64. Written in our own words; check the manual for your exact model.

Check heating water connections for leaks

Boiler · Vitocrossal 300 CA3B

Check all heating water connections for leaks, including the connections for control equipment and the minimum pressure monitor (low-water indicator). Only open heating water connections when the boiler is unpressurized. Working on pressure-loaded parts is dangerous. Under-pressure can damage the boiler, so empty it only with open ventilation using a suction pump.

  1. Confirm the boiler is unpressurized before opening any heating water connection.
  2. If emptying the boiler, open the ventilation and use a suction pump. Do not create a vacuum in the boiler.
  3. Check the heating water connections and the low-water indicator connections for leakage.
  4. After about 500 hours of initial run, check all heating water side connections for leaks again.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

Check LWCO function after installation

Boiler · Vitotronic 300

Test the low water cut-off function once the installation is finished.

  1. Complete the LWCO wiring and remove the jumper on the Power Pump Module board.
  2. Check that the LWCO device stops the burner when it should.

Applies to: Low water cut-off device, Vitotronic 300

Source: Vitotronic 300 installation instructions, p. 11. Written in our own words; check the manual for your exact model.

Check rating plate for CombiPLUS compatibility

Boiler · Vitodens 100-W WB1B

Not every boiler works with the CombiPLUS kit. Confirm the rating plate states compatibility before fitting it.

  1. Read the boiler rating plate on WB1B-26 or WB1B-35.
  2. Confirm it lists CombiPLUS compatibility before installing the kit.

Applies to: Vitodens 100-W WB1B with CombiPLUS

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 8. Written in our own words; check the manual for your exact model.

Check the boiler rating plate for CombiPLUS compatibility

Boiler · Vitodens 100-W WB1B

Before fitting the CombiPLUS kit, confirm the boiler rating plate on WB1B-26 or WB1B-35 states it is compatible with the kit.

  1. Read the boiler rating plate.
  2. Confirm it states CombiPLUS compatibility before installing the kit.

Applies to: WB1B-26, WB1B-35 with CombiPLUS kit

Source: Vitodens 100-W WB1B installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Check the design examples on site

Boiler · Vitotronic 100 GC1, Vitotronic 300-K MW1S

The application examples are recommendations only and must be checked on site for completeness and function. A low water cut-off must be installed where local codes require it. Proper installation and function in the field is the responsibility of the heating contractor.

  1. Field verify piping and all components against the chosen system version.
  2. Install a low water cut-off where local codes require it.

Applies to: Heating system designs

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Check the heating circuit allocation label

Boiler · Vitotronic 300-K MW1S

Confirm the heating circuit allocation label is in place before making any changes.

  1. Check that the heating circuit allocation label is affixed to the matching field of the programming unit.
  2. Press the matching button before making any adjustments.

Applies to: Vitotronic 300-K MW1S programming unit

Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 72. Written in our own words; check the manual for your exact model.

Check the power supply protection before connecting

Boiler · Vitotronic 300

The Power Pump Module supply must have overcurrent protection rated at most 15 A, and the ground must be connected.

  1. Confirm the main supply to the Power Pump Module has overcurrent protection of 15 A or less.
  2. Make sure L, N and G are not swapped.
  3. Connect the ground. The equipment must be grounded.

Applies to: Power supply to Power Pump Module, Vitotronic 300

Source: Vitotronic 300 installation instructions, p. 10. Written in our own words; check the manual for your exact model.

Check three-phase burner motor rotation

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3

Caution: a motor running backwards is a known risk on three-phase burners. Check rotation at commissioning and correct it at the burner terminals, never on the control.

  1. Power up the burner and observe motor rotation.
  2. If rotation does not match the burner direction, disconnect all power first.
  3. Reverse the BK1 and BK2 wires on the burner terminals.

Applies to: Three-phase burners, VD2/VD2A/CT3

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 65. Written in our own words; check the manual for your exact model.

Chimney sizing and insulation

Boiler · Vitorond 200 VD2

Relatively cool flue gases can cause corrosive condensation in an oversized or poorly insulated chimney.

  1. Design the chimney for the actual boiler model and its input; do not size it from the flue outlet.
  2. If a calculated diameter falls between two sizes, select the larger one.
  3. Insulate the chimney connection between the boiler vent collar and the chimney.
  4. Use a chimney that is gas tight when the Category III option is used.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 15-16. Written in our own words; check the manual for your exact model.

Choose boiler control method by command state

Boiler · Versatronik 515 / 515D

Boilers can be driven by a modulation percentage (Boiler On) or by a temperature set point (Auto mode). Pick the command state for each boiler.

  1. Set command state to 1 to run the boiler on the command value percentage.
  2. Set command state to -1 (0xFF) to run the boiler on its set point.
  3. Set command state to 0 to turn the boiler off.

Applies to: Boiler 1-16 command state points AO301-316

Source: Versatronik 515 and 515D BACIP Type B gateway manual, p. 16. Written in our own words; check the manual for your exact model.

Clearance to combustible construction for hot water piping

Boiler · Vitorond 100

Keep 2 in of clearance around non-insulated hot water pipes to combustible construction. With adequate pipe insulation the clearance can be reduced to 0 in.

Applies to: All VR1 models

Source: Vitorond 100 installation and service manual, p. 43. Written in our own words; check the manual for your exact model.

Clearances to combustibles and top clearance

Boiler · Vitodens 100-W B1HE/B1KE

The boiler is listed for zero clearance to combustibles when vented with listed AL-29-4C special venting or UL/ULC-listed CPVC gas vent. The top clearance is 12 in. (30 cm). Vent pipe clearances are in the Vitodens Venting System instructions.

  1. Keep 12 in. (30 cm) above the boiler.
  2. Use only the listed venting materials to get zero clearance to combustibles.

Applies to: All Vitodens 100-W B1HE/B1KE models

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 9. Written in our own words; check the manual for your exact model.

Clearances to hot water piping

Boiler · Vitodens 200-W B2HB

Keep a minimum 2 in. (51 mm) circumferential clearance from non-insulated hot water pipes to combustible construction. With suitable pipe insulation, the clearance may be reduced to 0 in. per local gas codes. Pumps in the piping examples are field supplied.

  1. Keep at least 2 in. (51 mm) around non-insulated hot water pipes from combustible construction.
  2. If pipes are insulated to appropriate thickness, the clearance may be reduced to 0 in. per local gas codes.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words; check the manual for your exact model.

Closed-end connectors on red, orange and blue wires

Boiler · Vitorond 100

The red, orange and blue wires have factory closed-end connectors. Red is live at 120VAC at all times.

  1. Do not remove or cut the closed-end connectors on the red, orange or blue wires unless it is necessary.
  2. Disconnect power before working on the red wire.

Applies to: Vitotronic burner wiring harness

Source: Vitorond 100 installation and service instructions, p. 36. Written in our own words; check the manual for your exact model.

CO2 check before and after gas work

Boiler · Vitocrossal 300 CA3B

Measure CO2 before and after any work on gas appliances to protect health and confirm correct condition.

  1. Measure CO2 before starting work.
  2. Measure CO2 again after the work is finished.
  3. Verify burner adjustment with the boiler at operating temperature.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 11, p. 15. Written in our own words; check the manual for your exact model.

Coding addresses auto-set for DHW and extra mixing circuits

Boiler · Vitotronic 200-H

With a DHW tank, and with extra mixing valve circuits on the HK3S, coding addresses 00:2 to 00:10 are set automatically.

Applies to: Vitotronic 200-H HK3S (and HK1S for DHW tank systems)

Source: Vitotronic 200-H installation and service instructions, p. 4. Written in our own words; check the manual for your exact model.

Coding addresses set automatically when a DHW tank is used

Boiler · Vitotronic 200-H

In systems with a DHW tank, coding addresses 00:2 to 00:10 are set automatically by the control unit.

Applies to: Vitotronic 200-H HK1B, systems with a DHW tank

Source: Vitotronic 200-H HK1B installation and service manual, p. 10. Written in our own words; check the manual for your exact model.

Cold fill pressure and boiler filling

Boiler · Vitocrossal 200 CI2

Cold water fill pressure must match the expansion tank pressure. Do not let the cold fill pressure go above 18-20 psig. Fill only with suitable water, because poor water quality can damage the boiler.

  1. Set cold water fill pressure equal to the expansion tank pressure.
  2. Keep cold fill pressure at or below 18-20 psig.
  3. Fill the boiler and bleed all air from it.
  4. Check every boiler opening and pipe connection for leaks before fitting insulation.
  5. Check that no leaks exist on connections that will be covered by insulation.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 40. Written in our own words; check the manual for your exact model.

Combustion air cover and room air operation

Boiler · Vitodens 100-W, B1HE, B1KE

The combustion air cover is not fitted at the factory on the concentric vent adaptor but ships with the boiler. Leaving it off can cause unintended room air dependent operation.

  1. Check the chosen venting configuration.
  2. Install the combustion air cover if the configuration requires it.
  3. For room air dependent operation, provide combustion and ventilation air per the single pipe venting section of the venting instructions.

Applies to: Concentric vent installations

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 30. Written in our own words; check the manual for your exact model.

Combustion chamber insert and door bolts

Boiler · Vitorond 100

The boiler has a stainless steel combustion chamber insert. The door bolts must be tight before the burner is installed.

  1. Check that the combustion chamber door bolts are tight.
  2. Install the burner only after the door bolts are tightened.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

Combustion test basis

Boiler · Vitorond 200, VD2A

Combustion efficiency and flue temperature figures assume a set CO2 level for each fuel, so set the burner to match the reference when comparing results.

  1. For fuel oil #2, reference CO2 is 13.0%.
  2. For natural gas, reference CO2 is 10%.
  3. Measure flue gas temperature with combustion air at 68 °F (20 °C) and boiler water at 176 °F (80 °C).

Applies to: Vitorond 200 VD2A, oil and gas combustion checks

Source: Vitorond 200 VD2A Technical Data Manual, p. 8. Written in our own words; check the manual for your exact model.

Commissioning and service test value record

Boiler · Vitocrossal 300 CA3B Dual Fuel

Blank record sheet for combustion and gas readings, kept separately for Section 1, 2 and 3 on natural gas and LPG. Fields are static pressure, running supply pressure, CO2 and O2 (actual and set) at upper and lower rated output, CO (actual and set), flue gas temperature (gross), ionization current at upper and lower output, and draught.

  1. Record static pressure for each section, NG and LPG.
  2. Record running supply pressure for each section, NG and LPG.
  3. Measure CO2 at the upper rated heating output, then the lower rated output. Enter actual and set values.
  4. Measure O2 at the upper rated heating output, then the lower rated output. Enter actual and set values.
  5. Record CO (ppm) actual and set.
  6. Record gross flue gas temperature actual and set.
  7. Record ionization current in µA at the upper and lower rated heating outputs.
  8. Record draught actual and set (hPa / in. w.c.).
  9. Record results in the Maintenance Record at each service visit.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 158. Written in our own words; check the manual for your exact model.

Commissioning hand-over checklist

Boiler · Vitocrossal 200 CM2

Initial start-up must be done by a qualified heating contractor, and the Maintenance Record must be completed.

  1. Verify field-supplied controls: low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents and thermostats.
  2. Explain the operating sequence and the need for combustion air to the owner.
  3. Demonstrate emergency shut-down, including what to do and what not to do.
  4. Tell the owner that annual professional service is required before the heating season.
  5. Leave all literature at the site and tell the owner where it is kept.

Applies to: All Vitocrossal 200 CM2 units

Source: Vitocrossal 200 CM2 service instructions, p. 2, 6 and 7. Written in our own words; check the manual for your exact model.

Common supply temperature sensor location

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The mounting point depends on the system layout.

  1. For a single boiler, or multi-boiler with external cascade control, mount the common supply sensor on the supply piping near the boiler.
  2. For multi-boiler systems using integrated cascade, mount it on the supply piping common to all boilers.
  3. See the system layouts on page 45 of the manual.

Applies to: Single and multi-boiler systems

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 20. Written in our own words; check the manual for your exact model.

Common venting and side wall coaxial venting

Boiler · Vitodens 200-W B2HB

Models 45, 57, 160 and 199 can only be common vented with other Vitodens 200-W boilers of the same size and series. Do not exceed the maximum equivalent vent length in the Venting System instructions. A side wall coaxial vent must include the Viessmann protective screen.

  1. Confirm the other boilers on the common vent are Vitodens 200-W of the same size and series.
  2. Check the total equivalent vent length against the Venting System instructions.
  3. Fit the Viessmann protective screen on any side wall coaxial vent.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 61. Written in our own words; check the manual for your exact model.

Complete the setup wizard first

Boiler · Vitocrossal 300 CU3A

The setup wizard for the boilers and the cascade control must be completed before any other configuration.

  1. Run the setup wizard on each boiler.
  2. Run the setup wizard on the cascade control.
  3. Start the additional configurations only after both wizards are complete.

Applies to: Multi-boiler cascade systems

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 57. Written in our own words; check the manual for your exact model.

Condensate pump and discharge location

Boiler · Vitodens 200-W

If the condensate outlet is lower than the drain, install a pump approved for condensing boilers with an overflow switch. The drain must end in an open or vented drain as close to the boiler as possible to prevent siphoning. Vent the tubing to atmosphere before a neutralization unit.

  1. Install a condensing-approved pump with an overflow switch if the outlet is below the drain.
  2. Terminate the drain into an open or vented drain close to the boiler.
  3. Vent the discharge tubing to atmosphere before the neutralization unit, if used.
  4. Vent the pipe between the siphon trap and the neutralization unit.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 28. Written in our own words; check the manual for your exact model.

Conditions that prohibit burner start

Boiler · Vitorond 100

Do not attempt to start the burner in these conditions.

  1. Do not start the burner unless the combustion chamber door is secured in place.
  2. Do not start the burner if excess oil has built up, the unit is full of vapor, or the combustion chamber is very hot.
  3. Do not fire the boiler without water.
  4. Do not use gasoline, crankcase draining or any oil containing gasoline.

Applies to: Oil burner start-up

Source: Vitorond 100, VR1 installation and service instructions, p. 47. Written in our own words; check the manual for your exact model.

Configure BACnet IP device settings and activate

Boiler · Versatronik 515

Set the BACnet device settings for the site network. Device ID must be unique on the whole BACnet internetwork. Changes do not take effect until the configuration is activated.

  1. Open the BACnet Device Settings screen.
  2. Enter a Device ID that is unique on the entire BACnet internetwork.
  3. Press SAVE on every screen where you change a setting.
  4. Select Activate Configuration and confirm the save. The gateway stores the settings and reboots automatically.
  5. Keep a record of every change made, because the gateway only shows configuration pages.
  6. Once the IP address is set, the gateway can join the network. Make sure no other device uses the same IP address.

Applies to: Versatronik 515 NR2/BACIP and 515D NR2/BACIP gateways

Source: Versatronik 515 BACnet IP Type B manual, p. 15. Written in our own words; check the manual for your exact model.

Confirm burner cycling before leaving site

Boiler · Vitorond 100

Check that the burner cycles on and off with a proper call for heat before leaving. Failure can cause a boiler runaway, which can lead to property damage, injury or death.

  1. Raise and lower the thermostat demand and confirm the burner starts and stops.
  2. Confirm the field-supplied high limit is set correctly before handover.

Applies to: All Vitorond 100 VR1 installations

Source: Vitorond 100 VR1 installation and service manual, p. 31. Written in our own words; check the manual for your exact model.

Confirm gas type before start-up

Boiler · Vitodens 200-W B2HA

The boiler is factory set for natural gas. Check the rating plate fuel type matches the installation and record it in the maintenance record on page 105.

  1. Compare the fuel type on the rating plate with the gas supplied.
  2. Record the fuel type in the maintenance record on page 105.

Applies to: Gas type verification

Source: Vitodens 200-W B2HA service instructions, p. 18. Written in our own words; check the manual for your exact model.

Confirm multi-boiler wiring before power-up

Boiler · Vitotronic 100

Disconnect power before wiring combustion air devices and external contacts. Use the adaptor and interface manuals for detailed installation.

  1. Disconnect power to control and burners before any wiring on these pages.
  2. Read the adaptor or common interface manual before installing the hardware.

Applies to: Combustion air devices and external controls

Source: Viessmann Vitotronic 100 GC1 installation manual, pp. 66-72. Written in our own words; check the manual for your exact model.

Connect boiler control to LON system

Boiler · Vitodens 200-W B2HB

Set LON participant numbers and functions using coding level 2 and the LON table. Data transfer can take several minutes.

  1. Install the LON communication module (accessory) per its installation instructions.
  2. Set participant numbers: boiler control 1 (code 77:1), Vitotronic 200-H HK1B 10 (code 77:10), next unit 11 (set code 77:11).
  3. Make only one Vitotronic the fault manager (code 79:1); other units use code 79:0.
  4. Set time and outside temperature sharing codes per the LON table (7B:1, 81:3, 97:2, 97:1).
  5. Set LON participant fault monitoring to code 9C:20 on the units listed.
  6. Do not allocate the same participant number twice in one LON system.

Applies to: Single boiler with Vitotronic 200-H, HK1B mixing valve control and Vitocom LON module

Source: Vitodens 200-W B2HB service instructions, p. 41. Written in our own words; check the manual for your exact model.

Connect boiler to ViGuide Web

Boiler · Vitocrossal 200 CI2

Remote connection needs a Partner Account, and the system operator's email must be known. The connection ends if the system is not confirmed within 30 days.

  1. Turn on Internet > Accesspoint > On in settings (see the access label on the programming unit).
  2. Log in to the ViGuide app with a Partner Account and select Connect system.
  3. Select the boiler and follow the app steps.
  4. Confirm the connection in ViGuide Web within 30 days using the email sent to the system operator.

Applies to: Vitocrossal 200 CI2 with ViGuide

Source: Vitocrossal 200 CI2 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

Connect the control unit to WiFi for app access

Boiler · Vitodens 100-W B1HE/B1KE

Sets up remote access through the app. The WiFi credentials are on a label on the unit.

  1. Call up the home screen.
  2. Press and hold OK for about 4 sec until information is shown.
  3. Follow the instructions in the app.
  4. Confirm with OK at the end.
  5. Acknowledge the information with OK.
  6. Press and hold the exit button for about 4 sec to leave the menu.

Applies to: WiFi and app connection

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 22. Written in our own words; check the manual for your exact model.

Connect the gateway to the boiler control

Boiler · Versatronik 511 / 511D

The supplied 3 ft (91 cm) CAT-5 cable joins the boiler control to the gateway. The control must have its LON communication card installed. Check the control's own manual for card location.

  1. Confirm the LON communication card is installed in the boiler control.
  2. Plug one RJ45 end of the supplied CAT-5 cable into the control.
  3. Plug the other RJ45 end into the RJ45 socket inside the gateway.
  4. Wire the BMS LON 2-wire bus to terminals A and B.
  5. Connect the 120VAC plug-in power cord (120VAC unit).

Applies to: Versatronik 511 with Vitotronic 100 GC1/GC1B, 300 GW2 or 300 GW5B

Source: Versatronik 511 & 511D LON Type B manual, p. 8. Written in our own words; check the manual for your exact model.

Connecting several remote controls

Boiler · Vitotrol 200

With more than one remote control, use the KM-BUS Expansion Module (accessory, Part No. 7133 393) or a field-supplied junction box. If only remote controls are on the bus, plug each one into the KM-BUS Expansion Module. If other KM-BUS participants are present, wire everything through a junction box. Total cable length must not exceed 50 m (164 ft).

  1. Use the KM-BUS Expansion Module (Part No. 7133 393) or a field-supplied junction box.
  2. If only remote controls are connected, plug each one into the KM-BUS Expansion Module.
  3. If other KM-BUS participants are connected, wire all devices through the junction box.
  4. Keep total cable length at or below 50 m (164 ft).

Applies to: Multiple Vitotrol remote controls on one control unit

Source: Vitotrol 200 installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Connecting the control to the gateway

Boiler · Versatronik 585, Versatronik 585D

The supplied 3 ft (91 cm) CAT-5 cable links the boiler control LON card to the gateway RJ45 socket. The BACnet IP RJ45 connection goes into the gateway for the building network. The LON card must be installed in the control first, following the boiler control manual.

  1. Confirm the LON communication card is installed in the boiler control.
  2. Plug one end of the supplied CAT-5 cable into the control RJ45.
  3. Plug the other end into the RJ45 socket inside the gateway.
  4. Plug the BACnet IP RJ45 communication cable into the gateway.

Applies to: Vitotronic 300 GW5B, GW6B and 300-K MW2C controls

Source: Versatronik 585 and 585D BACnet IP gateway manual, pp. 7-8. Written in our own words; check the manual for your exact model.

Connecting the gateway to the boiler control

Boiler · Versatronik 502 & 502D

The boiler control needs its LON communication card fitted. The gateway connects to the control with a supplied CAT-5 cable, with an RJ45 plug at each end. For full control-side setup, refer to the manual for the specific boiler control.

  1. Confirm the LON communication card is installed in the boiler control.
  2. Plug one RJ45 end of the supplied 3 ft (91 cm) CAT-5 cable into the control.
  3. Plug the other RJ45 end into the RJ45 socket inside the gateway.
  4. For 120VAC units, plug in the supplied power cord.

Applies to: Versatronik 502 and 502D with Vitotronic 100/GC1, 300/GW2, 300-K and similar controls

Source: Versatronik 502 NR2 Modbus manual, p. 8. Written in our own words; check the manual for your exact model.

Connection points on the DIN-rail gateway

Boiler · Versatronik 511 / 511D

The 511D has four labelled connection points: the control RJ45 port, the paralleled BUS connection, the LON terminals A and B, and the 24VAC power input.

  1. Connect the control RJ45 port to the boiler control.
  2. Use the paralleled BUS connection where needed.
  3. Connect the LON field wiring to terminals A and B.
  4. Connect 24VAC power.

Applies to: Versatronik 511D NR2/LON

Source: Versatronik 511 & 511D LON Type B manual, p. 6. Written in our own words; check the manual for your exact model.

Control connections and cable routing

Boiler · Vitodens 200-W B2HB

Cabling is needed for the outdoor sensor, Vitotronic 200-H HK1B, the mixing valve kit, remote operating mode switching, remote disable, alarm output, wall-mount base and circulating pump. Only one accessory or switch contact can be connected to a plug contact at a time.

  1. Route the cables as illustrated so the control unit can move freely.
  2. Do not secure connecting cables to the control unit bracket.
  3. Keep cable runs within the maximum permitted cable temperatures.
  4. Connect accessory power at the control; it switches with the system on/off switch.
  5. Supply the Vitotronic 200-H HK1B, mixing valve kit and Solartrol from a separate 120 VAC wall receptacle.
  6. Insert the programming unit into the control unit support, or use a wall mounting base (accessory) near the boiler.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 46. Written in our own words; check the manual for your exact model.

Control installation checklist

Boiler · Versatronik

Order of work for installing the Versatronik 200 control, from unboxing through coding and testing.

  1. Review the box contents.
  2. Mount the control on a solid surface using field-supplied hardware.
  3. Wire and connect the outdoor temperature sensor.
  4. Wire and connect the LLH/common supply temperature sensor.
  5. Wire and connect the DHW temperature sensor.
  6. Wire the boiler as required by the system (demand and communication connections, including the CoCo OT device).
  7. Wire the 120 VAC pumps (DHW, mixing valve heating circuit and multifunction).
  8. Wire the mixing valve (multifunction).
  9. Wire Lago remotes if used (accessory).
  10. Wire the input demand/signal as the system requires.
  11. Code and test the system.

Applies to: Versatronik 200 System Control

Source: Versatronik 200 installation and operating manual, p. 7. Written in our own words; check the manual for your exact model.

Control requirement to prevent flue gas condensation

Boiler · Vitorond 200 VD2A

The boiler must be run through the Vitotronic Therm-Control logic to prevent flue gas condensation at all local return water temperatures. Other control options need approval from a Viessmann technical representative.

  1. Confirm the Vitotronic control with Therm-Control logic is installed.
  2. Confirm the Therm-Control sensor is in place on the boiler return casting.
  3. Contact Viessmann before using any other control option.

Applies to: Vitorond 200 VD2A with Vitotronic control

Source: vitorond 200 VD2A technical data manual, p. 10. Written in our own words; check the manual for your exact model.

Convert from natural gas to liquid propane

Boiler · Vitodens 200-W B2HB

Field conversion of the gas valve and coding to liquid propane. Apply the supplied conversion labels when finished.

  1. Set adjusting screw A at the gas valve to "2" using a 2.5 mm hex key.
  2. Switch ON/OFF switch 8 to ON. Slide the black control cover out to reach it.
  3. Enter coding level 2 and open "General".
  4. Set coding address 11 to 9.
  5. Set coding address 82 to 1 for liquid propane.
  6. Return to coding address 11 and set any value except 9.
  7. Exit coding level 2 and open the gas shut-off valve.
  8. Apply the supplied fuel conversion labels.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 19. Written in our own words; check the manual for your exact model.

Customer handover

Boiler · Vitodens 200-W B2HA

The installer must give the operating instructions to the system user and show them how to operate the system.

  1. Hand over the operating instructions.
  2. Show the system user how to operate the system.

Applies to: All Vitodens 200-W B2HA installations

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 installation instructions, p. 58. Written in our own words; check the manual for your exact model.

DHW circulating pump direction

Boiler · Vitodens 200-W B2HA

In the piping layouts, the DHW circulating pump must pump into the boiler, not away from it. This applies to every layout shown.

  1. Pipe the DHW circulating pump so it pumps into the Vitodens boiler, as shown in the layout for the system.
  2. Check the pump label letter against the legend for the chosen layout.

Applies to: Vitodens 200-W B2HA 45, 60 DHW circulation piping

Source: Vitodens 200-W B2HA 45, 60 installation manual, pp. 33, 36-39. Written in our own words; check the manual for your exact model.

DHW piping and tank requirements

Boiler · Vitodens 200-W B2HB

DHW supply and return piping between the boiler and the Viessmann DHW tank must be at least 1¼ in. For non-Viessmann tanks, calculate the coil pressure drop against the pump residual head. Undersized DHW piping can cause short-cycling and poor DHW supply.

  1. Run DHW supply and return piping at least 1¼ in. between boiler and tank connections.
  2. For a non-Viessmann tank, calculate the tank coil pressure drop against the field pump residual head.
  3. Verify the Viessmann DHW tank sensor operates correctly with a non-Viessmann tank, per the tank manufacturer.
  4. Install a temperature tempering valve in the DHW supply line (strongly recommended).

Applies to: Vitodens 200-W B2HB with DHW tank

Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words; check the manual for your exact model.

DHW piping size

Boiler · Vitodens 200-W

DHW supply and return piping between the boiler and the tank connections must be at least 1 1/4 in. pipe. Smaller piping can cause boiler short-cycling and poor DHW supply.

  1. Use at least 1 1/4 in. pipe for DHW supply and return to the tank.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 32. Written in our own words; check the manual for your exact model.

DHW piping size and flow for tank applications

Boiler · Vitocrossal 300

DHW supply and return piping must be sized so the field pump has enough head to push water through the tank coil and the boiler heat exchanger. Undersized piping can cause short-cycling and poor DHW supply.

  1. Use at least 1¼ in. pipe between the boiler DHW connections and the Viessmann DHW tank connections.
  2. With a non-Viessmann tank, calculate the tank coil pressure drop against the field pump's residual head.
  3. Confirm enough flow reaches the boiler heat exchanger.

Applies to: Vitocrossal 300 CU3A with DHW storage tank

Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 43. Written in our own words; check the manual for your exact model.

DHW piping size and flow with non-Viessmann tanks

Boiler · Vitodens 200-W B2HA

DHW supply and return piping between the boiler and the tank must be at least 1¼ in. so the field pump's residual head is used well. A non-Viessmann tank needs a coil pressure drop check against the pump head. Undersizing can cause short-cycling and poor DHW supply.

  1. Install DHW supply and return piping of at least 1¼ in. between boiler DHW connections and the Viessmann tank connections.
  2. For a non-Viessmann tank, calculate the tank coil pressure drop against the boiler pump residual head.
  3. Confirm enough water flow reaches the boiler heat exchanger before commissioning.

Applies to: Vitodens 200-W B2HA 45, 60 DHW installations

Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 32. Written in our own words; check the manual for your exact model.

DHW piping size between boiler and tank

Boiler · Vitodens 200-W

Piping between boiler DHW connections and the Viessmann DHW tank connections must be at least 1¼ in. This lets the field pump's residual head overcome the DHW coil and still feed the boiler heat exchanger. Undersized piping can cause short-cycling and weak DHW supply.

  1. Run DHW supply and return piping at a minimum of 1¼ in. between the boiler and the tank.
  2. Confirm pump residual head covers the tank coil and boiler heat exchanger flow.

Applies to: DHW tank piping

Source: Vitodens 200-W B2HA installation manual, p. 32. Written in our own words; check the manual for your exact model.

DHW pump connection

Boiler · Vitotronic 100

The KW10B can run a DHW pump when OT or DHW set point function is on. The pump is a 120 VAC, 3 A full load pump on output 21 at the LGN terminals. Pump operation follows the DIP and dial switch settings.

  1. Connect the 120 VAC DHW pump (max 3 A) to the LGN terminals of output 21.
  2. Set DIP and dial switches for the required DHW pump operation.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 15. Written in our own words; check the manual for your exact model.

DHW sensor installation

Boiler · Vitotronic 100

Install the DHW sensor in the tank well as the tank manufacturer instructs. DHW function must be enabled in the start-up section.

  1. Install the DHW sensor in the tank well following the tank maker instructions.
  2. Connect the DHW sensor wires to connector X6 terminals 5.1 and 5.2.
  3. Enable DHW function as described in the start-up section.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 15. Written in our own words; check the manual for your exact model.

DHW sensor on a non-Viessmann tank

Boiler · Vitocrossal 300 CU3A

With a non-Viessmann tank, the installer must check the sensor works correctly with the tank maker. A temperature tempering valve is strongly recommended in the DHW supply line.

  1. Confirm sensor operation with the original tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A installation manual, p. 29. Written in our own words; check the manual for your exact model.

DHW tank piping and non-Viessmann tanks

Boiler · Vitodens 200-W B2HB

DHW supply and return piping between the boiler and a Viessmann DHW tank must be at least 1 1/4 in. For non-Viessmann tanks, calculate the DHW coil pressure drop against the field supplied pump residual head to confirm enough flow reaches the boiler heat exchanger. Insufficient flow can cause short cycling and poor DHW supply. If a tank other than a Viessmann Vitocell 100 or 300 is used, verify the Viessmann DHW sensor operation with the tank manufacturer. A temperature tempering valve in the DHW supply line is strongly recommended.

  1. Use at least 1 1/4 in. piping between the boiler DHW connections and the Viessmann tank.
  2. For non-Viessmann tanks, calculate the coil pressure drop against pump residual head.
  3. Verify DHW sensor operation with the original tank manufacturer.
  4. Install a temperature tempering valve in the DHW supply line.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words; check the manual for your exact model.

DHW tank piping and pump check

Boiler · Vitodens 200-W B2HB

Undersized DHW piping or a pump with too little head can cause short-cycling and poor DHW supply. Non-Viessmann tanks need a coil pressure drop check against pump head.

  1. Size DHW supply and return piping to the minimum pipe size for the model.
  2. On non-Viessmann tanks, calculate DHW coil pressure drop against the field pump's residual head.
  3. Confirm the tank sensor with the tank maker if the tank is not Viessmann Vitocell 100 or 300.
  4. Install a temperature tempering valve in the DHW supply line.

Applies to: DHW tank installations

Source: Vitodens 200-W, B2HB technical data manual, p. 33. Written in our own words; check the manual for your exact model.

DHW timer for continuous availability

Boiler · Vitodens 222-F

If DHW production should be possible at any time, the timer schedule must cover the full day.

  1. Set the DHW timer schedule as desired.
  2. For DHW available at any time, program the timer to 0:00 to 24:00.

Applies to: Applications 3 and 4

Source: Viessmann Vitodens 222-F B2TB application guide, p. 41, 45. Written in our own words; check the manual for your exact model.

Direct vent gasket selection

Boiler · Vitodens 100-W, B1HE, B1KE

Direct vent combustion air gaskets can be swapped. One is sized for 3 in. (89 mm) OD CPVC/PVC/ABS pipe, the other for 3 in. (80 mm) OD PP(s) pipe.

  1. Match the gasket to the combustion air pipe material.
  2. Use the 89 mm gasket for CPVC/PVC/ABS.
  3. Use the 80 mm gasket for PP(s).

Applies to: Direct vent installations

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 30. Written in our own words; check the manual for your exact model.

Do not use Teflon tape or compression fittings on oil lines

Boiler · Vitorond 100, VR1

Teflon tape can cause oil valves to fail. Compression fittings are not allowed on the oil piping. Use non-hardening pipe joint compound on all threads.

Applies to: Oil piping at the burner and fuel unit

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 25. Written in our own words; check the manual for your exact model.

Domestic hot water limit when the system uses a DHW tank

Boiler · Vitotronic 100 GC1

If the system is run with a domestic hot water tank, the maximum permissible DHW temperature must not be exceeded. Install a suitable safety device if needed.

  1. Check the maximum permissible domestic hot water temperature.
  2. Install a suitable safety device if the limit could be exceeded.

Applies to: Vitotronic 100 GC1 with domestic hot water tank

Source: Vitotronic 100, GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

Domestic hot water tank sensor and tempering valve

Boiler · Vitodens 200-W B2HA

For a Vitocell 100 or 300 tank, mount the DHW temperature sensor in its well per the tank instructions. For any other tank, the installer must check sensor operation with the tank maker. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. Locate the DHW sensor well on the Vitocell tank and install the sensor per the tank instructions.
  2. For a non-Viessmann tank, confirm sensor operation with the tank manufacturer.
  3. Install a temperature tempering valve in the DHW supply line.
  4. Apply thread sealant to the DHW connections.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 21. Written in our own words; check the manual for your exact model.

Drip pocket clearance with ducted combustion air kit

Boiler · Vitocrossal 200 CI2

Clearance needed between boiler and drip pocket on large models.

  1. Install the drip pocket according to CAN/CSA B149.1 or NFPA 54.
  2. On CI2 1500 and 2000 with a ducted combustion air filter kit, leave at least 16 in. (400 mm) between the boiler and the drip pocket.

Applies to: Vitocrossal 200 CI2 1500 and 2000

Source: Vitocrossal 200 CI2 installation manual, p. 20. Written in our own words; check the manual for your exact model.

Electrical installation code

Boiler · Vitodens 200-W

Electrical work must meet the current National Electrical Code in the USA or the Canadian Electrical Code in Canada, plus state, provincial and local rules.

  1. Confirm the code edition and local amendments before wiring.
  2. Wire field connections per the wiring diagram and component legend.

Applies to: B2HA 112, 150, 399, 530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 96. Written in our own words; check the manual for your exact model.

Electrical supply and wiring to the boiler control

Boiler · Vitodens 100-W B1HE/B1KE

The boiler control is powered at 120 VAC, single phase, 60 Hz, rated 12 A. Install a disconnect and power service switch as local code requires. Outdoor sensor wiring must stay away from line voltage.

  1. Confirm supply is 120 VAC, 1 phase, 60 Hz, 12 A before connecting.
  2. Install a disconnect and service switch per local code.
  3. Route outdoor sensor cable away from 120 VAC or higher wiring.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Electrostatic discharge precaution

Boiler · Vitodens 200-W B2HA

Electronic modules can be damaged by electrostatic discharge.

  1. Before working on electronic modules, touch a grounded object such as a heating or water pipe to discharge static.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 24. Written in our own words; check the manual for your exact model.

Emergency mode in a cascade

Boiler · Vitocrossal 200 CI2

Emergency mode starts when lag boilers lose communication with the lead boiler. The boilers then run at a user-set temperature until communication returns.

  1. Set the emergency mode temperature in the commissioning assistant or ViGuide app.
  2. Restore communication between lead and lag boilers to exit emergency mode.

Applies to: Viessmann cascade systems

Source: Vitocrossal 200 CI2 Service Instructions, p. 15. Written in our own words; check the manual for your exact model.

Emissions test circuit jumpers

Boiler · Vitotronic 300-K MW1S

Both jumpers must be removed before the emissions test circuit is connected.

  1. Remove both jumpers before connecting the emissions test circuit.

Applies to: Vitotronic 300-K MW1S with emissions test switch S1

Source: Vitotronic 100/300-K installation and service instructions, p. 60. Written in our own words; check the manual for your exact model.

Establish a WiFi connection

Boiler · Vitocrossal 200 CI2

WiFi must be switched on first. Hidden networks can be added by entering the network name (SSID) and password. An error message appears if the connection fails. The connection exists only if the WiFi itself is connected to the internet.

  1. Make sure WiFi is switched on.
  2. Open Settings, then 'Internet', then 'Network selection'.
  3. Select the WiFi network from the list. For a hidden network, enter the SSID and password.
  4. Confirm.
  5. If the network is protected, enter the password (maximum 40 characters) and confirm.
  6. Confirm the internet use prompt.

Applies to: WiFi connection

Source: Vitocrossal 200 CI2 operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Expansion tank and boiler pump placement in a multi-circuit system

Boiler · Vitodens 200-W B2HA

In the example layout with DHW storage, a low-loss header and mixing-valve circuits, the expansion tank has a specific location and the boiler-side pumps must pump into the boiler.

  1. Locate the expansion tank as shown in the system layout.
  2. Pipe pumps C and K so they pump into the boiler, as illustrated.
  3. Confirm the boiler pump and mixing-valve pump functions are set by coding address 53 where the pump output is used.

Applies to: Vitodens 200-W B2HA 45, 60 with DHW tank and low-loss header

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 40. Written in our own words; check the manual for your exact model.

Expansion tank precharge

Boiler · Vitorond 100

If the precharged nitrogen pressure in the expansion tank is less than the static system pressure, the membrane must be inflated.

  1. Inflate the membrane to slightly above the system static pressure.
  2. Size the expansion tank correctly. An undersized tank lets fresh water enter through the fill valve and causes premature section failure, which is not covered by warranty.

Applies to: Expansion tank

Source: Vitorond 100 installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.

Factory calibration and high altitude operation

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

The burner is factory calibrated, so no field gas adjustment is expected. For high altitude sites up to 10,000 ft (3,000 m), set the electronic elevation in the boiler software; no input derate is needed.

  1. Confirm the gas type (natural gas or LPG) matches the boiler rating.
  2. At altitude above sea level, set the electronic elevation in the boiler software.
  3. Check that the gas supply pressure is within the min and max values in the specification table.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 2, 5. Written in our own words; check the manual for your exact model.

Factory date, time and daylight saving

Boiler · Vitotronic 300

Date and time are preset at the factory in CET. Daylight saving changeover happens automatically.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 operating instructions, p. 4. Written in our own words; check the manual for your exact model.

Factory default settings and commissioning

Boiler · Vitocrossal 300 CA3B Dual Fuel

The Vitotronic 300 GW6C ships with factory defaults. The boiler can be started with these, but commissioning should be completed with the Commissioning Assistant or System Configuration in the service menu. Defaults include standard room temperature 68°F (20°C), DHW setpoint 122°F (50°C), frost protection, automatic daylight saving time, and saved settings after power loss.

  1. Complete commissioning with the Commissioning Assistant or System Configuration in the service menu.
  2. Have the heating contractor set the date and time and match the control to local conditions.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Factory setup and parts ordering

Boiler · Vitodens 200-W B2HA

Units ship factory tested and calibrated for natural gas. Gas valve adjustment is normally not needed at startup. Always give the 16-digit boiler serial number (bar code label) or the 12-digit ASME/NB serial number when ordering parts, because some parts are not reverse compatible with earlier versions.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 9. Written in our own words; check the manual for your exact model.

Factory-calibrated gas valve

Boiler · Vitodens 200-W B2HA

The B2HA boiler is factory tested and calibrated. Gas valve adjustments are typically not needed at field start-up.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.

Factory-preset behaviour after commissioning

Boiler · Vitocrossal 200 CI2

The boiler is preset at the factory and is ready for use after commissioning. Frost protection for the boiler and DHW tank is on. Wintertime and summertime changeover is automatic. Date and time are set by the contractor and can be changed. All settings are kept during a power failure. Commissioning and local matching are done by the contractor.

  1. Confirm date and time after commissioning if the site requires it.
  2. Check that frost protection is active on the boiler and DHW tank.
  3. Leave settings as set by the contractor unless the user requests a change.

Applies to: Vitocrossal 200 CI2 after commissioning

Source: Vitocrossal 200 CI2 operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Fault message on first start-up of multi boiler system

Boiler · Vitotronic 300

In a multi boiler application with a Vitocrossal 200 CM2 boiler, a fault message appears at first start-up. It means the boiler controller commissioning is not finished yet.

  1. Acknowledge the fault message.
  2. Complete the commissioning process.

Applies to: Multi boiler systems with Vitocrossal 200 CM2 boilers

Source: Vitotronic 300, GW6B installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

Feedback contact D: remove jumper

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The feedback contact for on-site safety equipment or indoor air damper is wired to terminal D.

  1. Remove the jumper between 25 L and 26 L before connecting feedback contact D (the factory setting has the jumper fitted).

Applies to: Feedback contact D on the boiler control

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 23. Written in our own words; check the manual for your exact model.

Field conversion from natural gas to LP gas

Boiler · Vitocrossal 300 CU3A

Boiler ships set for natural gas. Field conversion to LP gas uses the conversion label kit.

  1. Use the NG to LPG conversion label kit, which includes instructions and labels.
  2. Follow the kit instructions to convert the boiler to LP gas.
  3. Convert back to natural gas with the same process if required.

Applies to: Vitocrossal 300 CU3A natural gas and LP gas

Source: Vitocrossal 300 CU3A technical data manual, p. 16 and 18. Written in our own words; check the manual for your exact model.

Field pump sizing for underfloor layouts

Boiler · Vitodens 200-W B2HA

Sizing of the field-supplied pump is critical in layouts with a mixing valve and system separation. An undersized pump can cause short-cycling or improper boiler operation. Viessmann strongly recommends a low-loss header and a boiler pump here.

  1. Check the boiler supply head pressure drop on page 28.
  2. Size the field-supplied pump against that drop.
  3. Use a low-loss header and a boiler pump in the underfloor system layout.

Applies to: Vitodens 200-W B2HA 45, 60 underfloor heating systems

Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 35. Written in our own words; check the manual for your exact model.

Field-verify piping and install a low water cut-off where required

Boiler · Vitodens 200-W B2HB

The piping examples are simplified concepts. The installer must field-verify all piping and components, and a low water cut-off (LWCO) is required where local codes call for one.

  1. Field-verify all piping and componentry against the drawing.
  2. Install a low water cut-off where local codes require it.
  3. Confirm proper installation and function, which is the heating contractor's responsibility.

Applies to: Vitodens 200-W B2HB system piping

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 43. Written in our own words; check the manual for your exact model.

Fill the condensate siphon before start-up

Boiler · Vitodens 100-W WB1B

Flue gases can come out of the condensate drain at first start-up if the siphon is dry.

  1. Pour at least 10 fl oz (0.3 L) of water into the boiler condensate adaptor before start-up.

Applies to: Initial start-up

Source: Vitodens 100-W WB1B installation manual, p. 21. Written in our own words; check the manual for your exact model.

Fill the condensate trap before commissioning

Boiler · Vitodens 100-W B1HE/B1KE

The trap must hold water before start-up. Flue gas can escape from the condensate drain during commissioning.

  1. Pour at least 10 oz (0.3 L) of water into the flue gas connection.
  2. If there is a freeze risk, fill the trap only just before commissioning.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W, B1HE/B1KE Installation/Service, p. 21. Written in our own words; check the manual for your exact model.

Fill the flue gas siphon before start-up

Boiler · Vitocrossal 300 CU3A

An unfilled siphon can let flue gas escape into the room.

  1. Undo fitting A on the siphon B and remove the siphon.
  2. Fill the siphon with water.
  3. Refit the siphon.

Applies to: Start-up

Source: Vitocrossal 300 CU3A service instructions, p. 11. Written in our own words; check the manual for your exact model.

Fill the heating system

Boiler · Vitodens 200-W B2HB

Fill the system through the boiler fill connection with the filling function.

  1. Flush the whole heating system before filling. Use potable water only.
  2. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
  3. Open system isolation valves at C and D if installed.
  4. Check the expansion tank pre-charge. If it is below system static pressure, raise it to just above system pressure.
  5. Connect a hose to the boiler fill tap and fill at boiler fill BF while draining air from boiler drain BD.
  6. Activate the filling function from the service menu and end it with OK.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

Fill the siphon trap before commissioning

Boiler · Vitodens 100-W B1HE/B1KE

Only commission the boiler once the siphon trap is full of water.

  1. Check that the siphon trap has been filled with water.
  2. Only then continue with commissioning.

Applies to: Condensate siphon trap

Source: Viessmann Vitodens 100-W B1HE/B1KE Combi Installation and Service Instructions, p. 40. Written in our own words; check the manual for your exact model.

Filling and purging programs (20 min auto-stop)

Boiler · Vitodens 200-W B2HE

Purging cycles the pump 30 s on/off and toggles the diverter valve for 20 min with the burner off. Filling parks the diverter valve in the middle and runs the pump; both stop by themselves after 20 min.

  1. Service menu > Service functions > Filling or Purging
  2. Program ends automatically after 20 min; exit Service to stop earlier

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Function description p.82. Written in our own words; check the manual for your exact model.

Filling the condensate siphon

Boiler · Vitocrossal 200 CM2

Fill the siphon before start-up so flue gas cannot escape through the drain.

  1. Undo siphon cup A and fill it with water.
  2. Check that condensate drains freely.
  3. Refit siphon cup A.

Applies to: Vitocrossal 200 CM2 186 to 311 boilers

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 9. Written in our own words; check the manual for your exact model.

Fire at the appliance

Boiler · Vitocrossal 300 CU3A

If fire comes from the boiler, act at once.

  1. Call the fire department immediately.
  2. Shut down the boiler and close the fuel shut-off valves.
  3. Only fight the fire if qualified, using a tested class ABC extinguisher.

Applies to: All models

Source: Vitocrossal 300 CU3A installation instructions, p. 9. Written in our own words; check the manual for your exact model.

First start-up codings on the control unit

Boiler · Vitocrossal 300 CA3B Dual Fuel

The control unit is preset, but several codings must be set on site. Language, date and time, temperature units, system layout and elevation can be changed at start-up.

  1. Switch on the main switch and all network switches on the control units.
  2. Switch on the control unit. Start-up begins automatically.
  3. Set language, date and time, temperature units, system layout and elevation as needed.
  4. Confirm each entry. When asked 'Do you want to make further changes', answer as required.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 32. Written in our own words; check the manual for your exact model.

First start-up of the control unit

Boiler · Vitocrossal 300 CA3B Dual Fuel

The control unit comes pre-set, but several codings still need to be set on site. Switch on the main switch and all network switches first, then the control unit switch. Start-up runs by itself. Language, date and time, temperature units, system layout and elevation can be changed at this point. Confirm each one, then answer the prompt asking whether further changes are needed.

  1. Switch on the main switch and all network switches on the control units.
  2. Switch on the control unit. Start-up begins automatically.
  3. Set language, date and time, temperature units, system layout and elevation as required.
  4. Confirm each entry, then answer 'Do you want to make further changes'.

Applies to: Vitocrossal 300 CA3B Dual Fuel boilers, control unit start-up

Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

First start-up settings

Boiler · Vitocrossal 300 CA3B Dual Fuel

The control unit comes pre-set, but several codings must be set individually before the system runs.

  1. Turn on the main switch and all network switches on the control units.
  2. Switch on the control unit. Start-up begins automatically.
  3. Set language, date and time, temperature units, system layout and elevation as required.
  4. Confirm with OK. When asked whether you want to make further changes, answer as needed.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 32. Written in our own words; check the manual for your exact model.

Flow ratio for radiator plus underfloor circuits

Boiler · Vitodens 200-W B2HA

When a radiator circuit and an underfloor circuit with a 3-way mixing valve share the boiler, the radiator circuit's water flow must be at least 30% greater than the underfloor circuit's. The total of both circuits must stay below the boiler's maximum water flow.

  1. Confirm the radiator circuit flow is at least 30% greater than the underfloor circuit flow.
  2. Confirm the combined flow is below the boiler maximum on page 29.

Applies to: Vitodens 200-W B2HA 45, 60 layout 4

Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 36. Written in our own words; check the manual for your exact model.

Flue gas damper coding (0a) during commissioning

Boiler · Vitotronic 300 GW6B

The flue gas damper coding is set to 0a:1 (with damper) in all applications by default.

  1. If the boiler has no flue gas damper, set coding 0a to 0a:0 during commissioning.
  2. If coding 0a is not set in the commissioning assistant, the burner checks for a damper and its function can only be adjusted at the burner control.

Applies to: All applications, Vitotronic 300 GW6B

Source: Vitotronic 300 GW6B installation and service manual, p. 48. Written in our own words; check the manual for your exact model.

Flue gas damper coding during commissioning

Boiler · Vitotronic 300

Flue gas damper coding address 0a defaults to 0a:1 (damper fitted) in all applications. If no flue gas damper is used, set it to 0a:0. If it is not changed at the control unit during commissioning, the burner checks for a damper itself and the damper function can then only be set at the burner control.

  1. Check whether a flue gas damper is fitted.
  2. If none is fitted, set coding address 0a to 0a:0 during commissioning or on Coding level 1.

Applies to: All Vitotronic 300 GW6B applications

Source: Vitotronic 300, GW6B installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

Flue gas test point

Boiler · Vitorond 200, VD2

Create a flue gas test point on the vent pipe for combustion testing. The printed hole size is partly unreadable; 10 mm is the value shown.

  1. Drill a 10 mm hole on the side of the vent pipe.
  2. Place the hole about two to three times the vent pipe diameter away from the boiler flue gas collar.
  3. Seal and insulate the vent pipe after drilling.

Applies to: Vitorond 200 VD2 flue test point

Source: Vitorond 200 VD2 installation manual, p. 24. Written in our own words; check the manual for your exact model.

Flue length calculation examples

Boiler · Vitocrossal 200 CI2

Worked examples for the entered Flue System Length.

  1. CI2 399 with burner filter: 75 ft + 0 ft + 33 ft = 108 ft (33 m) entered.
  2. CI2 750 with no intake accessory: 150 ft (46 m) entered.
  3. CI2 1500 with direct vent inline filter: 75 ft + 60 ft + 98 ft = 233 ft (71 m) entered.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 service instructions, p. 19. Written in our own words; check the manual for your exact model.

Flush and pressure-check the heating water side

Boiler · Vitodens 200-W B2HA

Flush the heating system thoroughly, especially before connecting to an existing system. Maximum operating pressure is 4 bar (60 psig) and test pressure is 6 bar (90 psig). Pressures above these values are not covered by warranty.

  1. Flush the heating system thoroughly before connecting the boiler.
  2. Connect the boiler supply and return to the heating system.
  3. Keep operating pressure at or below 4 bar (60 psig).
  4. Keep test pressure at or below 6 bar (90 psig).

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 20. Written in our own words; check the manual for your exact model.

Flush existing piping before connecting a retrofit boiler

Boiler · Vitocrossal 300 CA3B Dual Fuel

On retrofits, a previously used heating system must be flushed to remove sludge and debris. Failure to flush can restrict flow or cause deposits and boiler failure, which is not covered by warranty.

  1. Flush the piping with city pressure water at 50 to 60 psi before connecting the boiler.
  2. Install magnetic filtration; Viessmann recommends it.

Applies to: Retrofit installations

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Flush existing system before connecting boiler

Boiler · Vitocrossal 200 CI2

When the boiler is piped into an existing system, flush the heating system first to remove dirt and sludge. Sludge settles in the boiler and can cause hot spots, noise and water-side corrosion. Damage from these impurities voids the warranty. Water treatment should be considered where mineral content or hardness is high.

  1. Flush the existing heating system completely before connecting the boiler.
  2. Consider water treatment in areas with high mineral content or hardness.
  3. Refer to the Service Instructions for water quality guidelines.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 40. Written in our own words; check the manual for your exact model.

Flush piping on retrofit installs before connecting the boiler

Boiler · Vitocrossal 300 CA3B Dual Fuel

Existing piping must be flushed before the boiler is connected. Skipping this can cause restricted flow and deposits that lead to boiler failure, and that failure is not covered under warranty.

  1. Flush the existing piping with city pressure water at 50-60 psi to remove sludge and contaminants.
  2. Install magnetic filtration if possible (recommended).
  3. Flush the whole heating system piping again if it is connected to a boiler in a retrofit.

Applies to: Retrofit applications on CA3B Dual Fuel boilers

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 8, 15. Written in our own words; check the manual for your exact model.

Flush retrofit piping before connecting the boiler

Boiler · Vitocrossal 200 CI2

On retrofit jobs, old piping can carry sludge that restricts flow and damages the boiler. Damage from this is not covered under warranty.

  1. Before connecting the boiler, flush previously used piping with city pressure water at 50-60 psi.
  2. Consider installing magnetic filtration; Viessmann recommends it.

Applies to: Retrofit installations of Vitocrossal 200 CI2

Source: Viessmann Vitocrossal 200 CI2 Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.

Frost protection with the standby program

Boiler · Vitocrossal 300 CA3B

With frost protection monitoring, select Standby mode on every heating circuit. Central heating and DHW heating stop, but frost protection for the boiler and DHW tank stays active. Outdoor temperatures below 37°F (3°C) need frost protection measures for the system.

  1. For every heating circuit, select the Standby mode operating program.
  2. If outdoor temperatures below 37°F (3°C) are expected, take frost protection measures or call the heating contractor.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Fuel conversion to liquid propane

Boiler · Vitodens 222-F

The boiler ships set for natural gas. Converting to liquid propane does not need a conversion kit, but the fuel type must be changed in the start-up procedure.

  1. Use the Convert Fuel Type to Liquid Propane Gas procedure (see p. 18 of the manual).

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB service instructions, p. 8. Written in our own words; check the manual for your exact model.

Gas and CO2 measurement before and after gas work

Boiler · Vitocrossal 200 CI2

A CO2 measurement is required before and after working on gas appliances.

  1. Take a CO2 reading before starting work on the gas system.
  2. Take a CO2 reading again after the work is finished.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 service instructions, p. 24. Written in our own words; check the manual for your exact model.

Gas connection components before the boiler

Boiler · Vitodens 200-W B2HA

Install a ground joint union, a capped drip leg and a manual equipment shutoff valve ahead of the boiler gas connection. Valves must be listed by a nationally recognized testing agency. Tag the shutoff valves and show the operator where they are.

  1. Fit the ground joint union, capped drip leg and manual shutoff valve as shown in the manual.
  2. Use only listed valves.
  3. Make the boiler gas connection (1 in. NPT).
  4. Put a tag on each shutoff valve and brief the owner on them.
  5. Consider an external safety solenoid valve for LPG where the boiler is below grade.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 19. Written in our own words; check the manual for your exact model.

Gas leak test and gas work safety

Boiler · Vitodens 200-W B2HA

Test for leaks with soap and water. Keep open flames out of the room. Never purge gas into the combustion chamber.

  1. Make sure there is no open flame in the room.
  2. Never use matches, candles or flames to check for leaks.
  3. Apply soap and water solution to joints and check for bubbles.
  4. After any gas work, run a gas leak test.

Applies to: Gas line work

Source: Vitodens 200-W B2HA service instructions, p. 20 and p. 24. Written in our own words; check the manual for your exact model.

Gas leak test and purge

Boiler · Vitodens 200-W B2HA

Use an approved liquid leak-detection spray. Keep it off electrical parts, wires and connectors, and away from the gas valve regulator and regulator vent opening. Never check for leaks with an open flame.

  1. Spray approved leak solution on all joints and fittings.
  2. Keep spray off electrical components, wires and connectors.
  3. Keep spray away from the regulator and the regulator vent opening.
  4. Fix any leaks found and retest.
  5. Purge air from the gas line before lighting.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 20. Written in our own words; check the manual for your exact model.

Gas piping pressure test isolation

Boiler · Vitodens 200-W B2HA

At test pressures of 1/2 psig (14 in. w.c.) or less, the boiler can stay connected but must be isolated by its manual shutoff valve. At higher test pressures, the boiler and its shutoff valve must be disconnected from the piping. Overpressure to the boiler gas regulator or gas valve voids the warranty.

  1. At 1/2 psig (14 in. w.c.) or less, close the boiler's manual shutoff valve to isolate it.
  2. Above 1/2 psig (14 in. w.c.), disconnect the boiler and its shutoff valve from the gas piping.
  3. Never expose the gas regulator or gas valve to extreme test pressure.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 20. Written in our own words; check the manual for your exact model.

Gas supply piping recommendations

Boiler · Vitocrossal 200 CI2

Gas train layout and regulator requirements for the boiler supply.

  1. Install one gas pressure regulator per boiler.
  2. Use a regulator with an outlet size equal to the boiler fuel connection; use a concentric reducing coupling if the pipe diameter changes.
  3. Install a ground joint union, capped drip leg and manual shutoff valve before the boiler connection; valves must be listed by a nationally recognized testing agency.
  4. Install a gas filter if the gas pipe may contain dirt.
  5. Design piping so it does not interfere with serviceable components.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 installation manual, pp. 19-20. Written in our own words; check the manual for your exact model.

Gas supply pressure limit and fuel type

Boiler · Vitodens 222-F

Maximum gas supply pressure is 14 in w.c. The boiler is factory set for natural gas. Switching to liquid propane needs no conversion kit. The factory gas valve is set and normally needs no field adjustment.

Applies to: Vitodens 222-F B2TB, natural gas and liquid propane

Source: Viessmann Vitodens 222-F B2TB installation manual, p. 8 and p. 14. Written in our own words; check the manual for your exact model.

Gas supply sizing and pressure drop

Boiler · Vitodens 200-W B2HA

Gas piping must be sized from pipe length, fittings, gas type and the total input of all gas appliances in the building. There must be no noticeable pressure drop when any appliance (or combination) lights or runs. Maximum gas supply pressure is 14 in. w.c. Design the layout so piping does not block serviceable components.

  1. Size the gas line using CAN/CSA B149.1 and .2, or NFPA 54 / ANSI Z223.1, plus local codes.
  2. Confirm the line can carry the total input of all appliances in the building.
  3. Check that no pressure drop is seen when appliances light or run.
  4. Do not exceed 14 in. w.c. gas supply pressure.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 19. Written in our own words; check the manual for your exact model.

Gas type and gas valve setup

Boiler · Vitocrossal 300 CU3A

Boiler is factory set for natural gas. Converting to liquid propane needs no kit. Gas valve is factory calibrated and usually needs no field adjustment.

  1. Confirm the fuel is natural gas or liquid propane as installed.
  2. Do not adjust the gas valve at field start-up unless required.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A service instructions, p. 8. Written in our own words; check the manual for your exact model.

Gas type and natural gas to LPG conversion

Boiler · Vitocrossal 300 CU3A

Lambda Pro adjusts automatically to gas type and quality, so no fuel conversion kit is needed for normal gas type changes. For a field conversion from natural gas to liquid propane, use the NG>LPG label kit included in the boiler literature set.

  1. Confirm gas type on site before startup.
  2. For a field conversion to LPG, use the NG>LPG kit and follow its included instructions and labels.
  3. Boiler is factory set for natural gas.

Applies to: Vitocrossal 300 CU3A, natural gas and liquid propane

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Technical Data Manual, p. 2 and p. 16. Written in our own words; check the manual for your exact model.

Gas type and propane conversion

Boiler · Vitodens 100-W WB1B

Boiler ships factory set for natural gas. A propane conversion kit comes with each boiler. Factory gas valve settings are tested, so field gas valve adjustment is normally not needed at start-up.

  1. Confirm the boiler is set for the gas type being supplied before start-up.
  2. If the site uses propane, install the included propane conversion kit.

Applies to: Vitodens 100-W WB1B

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 8. Written in our own words; check the manual for your exact model.

Gas type changes do not need a conversion kit

Boiler · Vitodens 200-W B2HB

Lambda Pro combustion control adjusts automatically to the gas type and quality, so no fuel conversion kit is needed. The unit is delivered preset for natural gas.

  1. Confirm supply gas is within the minimum and maximum pressure ratings for the gas type.
  2. Do not install a conversion kit for LPG operation.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB technical data manual, p. 2-3. Written in our own words; check the manual for your exact model.

Gas valve and fuel conversion

Boiler · Vitodens 222-F

The boiler ships set for natural gas. Converting to liquid propane needs no conversion kit. The boiler is factory-tested and calibrated, so gas valve adjustment is not normally needed at field start-up.

  1. Confirm the boiler is set for the fuel being used.
  2. Do not adjust the gas valve at field start-up unless testing shows it is needed.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Gas valve and ignition protection

Boiler · Vitodens 200-W B2HB

Gas valve is factory set. Protect the ignition components from water during operation and service.

  1. Do not expect to need gas valve adjustment at field start-up; the boiler is factory-tested and calibrated.
  2. Install the boiler so the gas ignition components are protected from spraying or splashing water.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 8, p. 10. Written in our own words; check the manual for your exact model.

Gas valve factory setting

Boiler · Vitocrossal 300 CU3A

The boiler is factory tested and calibrated, so gas valve adjustments are usually not needed at field start-up.

  1. Do not adjust the gas valve at field start-up unless the instructions require it.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Gas valve factory setting and model selection

Boiler · Vitodens 200-W B2HB

The boilers are factory tested and calibrated, so gas valve adjustment is usually not needed at field start-up. Boiler size must come from an accurate building heat loss calculation and must suit the connected radiation.

  1. Confirm the boiler size against a heat loss calculation of the building.
  2. Confirm the connected radiation suits the selected boiler.
  3. Do not adjust the gas valve at start-up unless it is required.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Gas valve is factory set

Boiler · Vitodens 200-W B2HA

The boiler is factory tested and calibrated. Gas valve adjustment is normally not needed at field start-up.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Gateway mounting options

Boiler · Versatronik 505 & 505D

The gateway can be part of a control panel or a stand-alone device. It translates between the listed boiler controls and BACnet IP DDC systems.

Applies to: Versatronik 505 and 505D

Source: Versatronik 505 & 505D BACnet IP gateway manual, p. 3. Written in our own words; check the manual for your exact model.

Hand over documentation and operator instruction

Boiler · Vitocrossal 300 CA3B Dual Fuel

The system manufacturer must instruct the system operator on operation and maintenance and hand over the documents.

  1. Complete the customer information file and split it into the operator segment and the heating contractor segment.
  2. Give the operator segment to the system operator and keep the contractor segment on file.
  3. Assemble all parts lists, operating and service instructions into one file and give it to the system operator.
  4. Include instruction on maintenance work and any installed accessories, such as remote controls.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 17. Written in our own words; check the manual for your exact model.

Hand over the system to the owner

Boiler · Vitodens 200-W B2HA

The installer must make the system operator or owner familiar with the system before leaving.

  1. Explain the proper operating sequence of the system.
  2. Explain the equipment.
  3. Demonstrate an emergency shut-down, and explain what to do and what not to do.
  4. Explain that proper maintenance is required for safe operation.
  5. Explain the need for professional service every year before the heating season begins.
  6. Leave the documentation in a readily accessible place near the boiler.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 2 and p. 7. Written in our own words; check the manual for your exact model.

Hand over the system to the user

Boiler · Vitodens 200-W

After installation, the installer should give the operating instructions to the system user and show them how to run the system.

  1. Give the operating instructions to the system user.
  2. Instruct the user on operating the system.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB installation manual, p. 57. Written in our own words; check the manual for your exact model.

Hand over to the system user

Boiler · Vitodens 200-W B2HB

The installer must give the operating instructions to the system user and show them how to operate the system. Labels on the boiler surfaces must be kept and read. Contact Viessmann for any replacement labels.

  1. Give the operating instructions to the system user.
  2. Instruct the user in operating the system.
  3. Do not remove any safety labels or stickers on the boiler; order replacements from Viessmann if needed.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 59. Written in our own words; check the manual for your exact model.

Handover and annual service

Boiler · Vitotrol 300A

Once installation is complete, the contractor must review the system with the owner. Documentation should be kept near the boiler.

  1. Explain all equipment, safety requirements and the shutdown procedure to the owner.
  2. Explain the need for professional service every year before the heating season.
  3. Leave the product documentation near the boiler for service personnel.

Applies to: Vitotrol 300A installations

Source: Vitotrol 300A operating instructions, p. 2. Written in our own words; check the manual for your exact model.

Handover and start-up checks

Boiler · Vitocrossal 300 CA3B Dual Fuel

Initial start-up must be done by a qualified heating contractor, who also completes the maintenance record. The contractor must confirm the field-supplied controls work before handover.

  1. Check the field-supplied low water cut-offs, staging controls, pumps, motorized valves, air vents and thermostats.
  2. Brief the owner on system operation, the combustion air need, emergency shutdown, and that maintenance is required.
  3. Complete the Maintenance Record on page 158.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Handover to owner

Boiler · Vitocrossal 300 CA3B

The heating contractor must review the system with the owner after installation.

  1. Review all equipment, safety precautions, and shutdown procedure with the owner.
  2. Explain the need for professional service every year before the heating season begins.
  3. Store the literature (installation, service and operating instructions) near the boiler.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 operating instructions, p. 2, p. 8. Written in our own words; check the manual for your exact model.

Handover to the system operator

Boiler · Vitocrossal 300 CA3B Dual Fuel

The installer must show the operator how the system works, how to start and shut it down, and the need for annual professional service before the heating season.

  1. Explain normal operating sequence and the need for combustion air.
  2. Demonstrate emergency shutdown and what not to do.
  3. Explain that proper maintenance is required for safe operation.
  4. Complete the Maintenance Record (page 158 of the manual).

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 2, 8. Written in our own words; check the manual for your exact model.

Handover to the system user

Boiler · Vitodens 200-W B2HA

Before leaving the site, the installer should hand over the operating instructions and show the user how to run the system.

  1. Give the operating instructions to the system user.
  2. Instruct the user in operating the system.
  3. Follow the safety instructions on all labels attached to the boiler and do not remove them. Contact Viessmann for replacement labels.

Applies to: Models 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 56. Written in our own words; check the manual for your exact model.

Hanging the boiler on the bracket

Boiler · Vitodens 100-W B1HE/B1KE

Protective caps on connections stay on until the boiler is about to be fitted. The wooden blocks on the bottom rails must be removed after mounting.

  1. Hang the boiler on the wall bracket.
  2. Confirm all four mounting tabs have locked into the boiler.
  3. Remove the plastic shipping caps from the connections.
  4. Remove the wooden blocks from the bottom rails.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 15. Written in our own words; check the manual for your exact model.

Heat demand inputs must be dry contacts

Boiler · Vitodens 222-F

Heat demand from an air handler or an infloor control must be a potential-free dry contact. Do not apply line voltage to these inputs.

  1. Use a potential-free contact for air handler heat demand.
  2. Use a potential-free contact for the radiant circuit from a thermostat, zone valve or multi-zone controller.

Applies to: Application 4 (VD2T 2HC2T2ZP.01)

Source: Viessmann Vitodens 222-F B2TB application guide, p. 39. Written in our own words; check the manual for your exact model.

Heating circuit assignment

Boiler · Vitotronic 200

On systems with two heating circuits, select the circuit before making settings, because settings apply to the selected circuit.

  1. Confirm labels show Heating circuit 1 without mixing valve and Heating circuit 2 with mixing valve.
  2. Press the circuit button for the circuit to set. The corresponding button lights.

Applies to: Two-circuit Vitotronic 200 KW2 systems

Source: Vitotronic 200 Si service instructions, p. 17. Written in our own words; check the manual for your exact model.

Heating circuit controls not on LON bus

Boiler · Vitotronic 100 GC1

When downstream heating circuit controls are not connected to the boiler control unit via LON, the temperature sensor and plug wiring must match the coding.

  1. Wire temperature sensor T1 or T2 to plug aJA or aJB as shown in the circuit diagram.
  2. Set the matching coding (4A: 1 or 4b: 1 is set automatically when the sensor is connected).
  3. If sensor T1 closes the downstream mixing valves, set 4C: 2 and use plug sÖ (A1).

Applies to: Circuit diagrams 3, 4 and 5

Source: Vitotronic 100 GC1 installation and service instructions, p. 9. Written in our own words; check the manual for your exact model.

Heating circuit numbering (BUS ID 1/2)

Boiler · Versatronik 200

Heating circuits are numbered in sequence starting at 01. Never give two circuits the same number. When replacing a controller, enter the exact same heating circuit numbers as the old one. Sensor type (1 kOhm or 5 kOhm) is chosen during programming and system selection.

  1. Number heating circuits in sequence starting at 01.
  2. Check that no heating circuit number is used twice on the bus.
  3. On a replacement controller, enter the same heating circuit numbers as the unit it replaces.
  4. Set the sensor type (1 kOhm or 5 kOhm) to match the system selection made during programming.

Applies to: Versatronik 200 system control, start-up settings

Source: Versatronik 200 installation and operating manual, p. 120. Written in our own words; check the manual for your exact model.

Heating system layout and mixing valves

Boiler · Vitodens 222-F

Recommended maximum boiler supply temperature is 158°F (70°C) for heating and DHW to limit distribution losses. Avoid mixing valves on the heating circuit where possible because condensing boilers need low return temperatures. If a mixing valve is needed (multi-zone or underfloor), use only 3-way mixing valves. Never use 4-way mixing valves with condensing boilers. Underfloor systems and large-volume loops must connect through a 3-way mixing valve.

  1. Set max boiler supply temperature to 158°F (70°C) where possible.
  2. Avoid mixing valves on the heating circuit when possible.
  3. Use 3-way mixing valves only.
  4. Do not use 4-way mixing valves.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 17. Written in our own words; check the manual for your exact model.

Heating system type sets the curve

Boiler · Vitodens 200-W B2HB

Match the heating curve slope to the emitter type: low temperature for radiant floor, medium for cast iron or staple-up radiant, high for fintube or fan coils. The room set-point and outdoor temperature drive the curve.

  1. Identify the heat emitter type in the building.
  2. Set the slope and shift to match the building's required supply temperature.
  3. Check room temperature after the system has settled.

Applies to: Heating curve adjustment

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 24. Written in our own words; check the manual for your exact model.

High altitude de-rate

Boiler · Vitodens 200-W B2HB

At high altitude installation at 10,000 ft the input of models B2HB 45, 57, 160 and 199 is de-rated by 21 percent.

  1. Apply the 21 percent input de-rate when the boiler is installed at 10,000 ft altitude.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 at 10,000 ft

Source: Vitodens 200-W B2HB installation manual, p. 61. Written in our own words; check the manual for your exact model.

High altitude operation

Boiler · Vitodens 200-W B2HB

The boiler can run at high altitude up to 10,000 ft (3,000 m) with a simple electronic adjustment. At 10,000 ft the input for B2HB 19 to 199 is derated by 21%.

  1. Set the high altitude adjustment electronically for the install site elevation.
  2. Account for the 21% input derate at 10,000 ft when checking input rate.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB technical data manual, p. 2, 5. Written in our own words; check the manual for your exact model.

High gas supply pressure

Boiler · Vitodens 200-W

Maximum gas supply pressure is 14 in. w.c. for both natural gas and LPG. If the supply can go above this, a separate gas pressure regulator must go upstream of the heating system.

  1. Measure the incoming gas supply pressure.
  2. If it can exceed 14 in. w.c., install a separate gas pressure regulator upstream of the boiler.
  3. Confirm the minimum pressure is 4 in. w.c. for natural gas or 10 in. w.c. for LPG.

Applies to: B2HA 112, 150, 399, 530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 103. Written in our own words; check the manual for your exact model.

High limit and air purge notes

Boiler · Vitorond 100

The Hydrostat high limit maximum setting is 240 F (110 C). A flow switch is not required on this boiler. Air must be bled from the system supply air vents, so avoid restrictive piping where air could be trapped.

  1. Set the high limit no higher than 240 F (110 C).
  2. Do not install a flow switch on this boiler.
  3. Bleed air at the system supply air vents.
  4. Avoid restrictive piping that can trap air.

Applies to: Vitorond 100 VR1 with Hydrostat 3250-Plus

Source: Vitorond 100 VR1 installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Hydraulic separation of boiler and system

Boiler · Vitodens 222-F

Closely spaced tees or a low-loss header separate the boiler and system flows so they do not affect each other.

  1. Install closely spaced tees or a low-loss header between boiler and system loops.
  2. Size the boiler circulator and flow per the sizing section (pages 13-15, not included here).

Applies to: Applications 3, 4 and 5

Source: Viessmann Vitodens 222-F B2TB application guide, p. 38, 42. Written in our own words; check the manual for your exact model.

Hydraulically separate boiler and system flow

Boiler · Vitodens 222-F

Separating the boiler loop from the system loop keeps their flows from affecting each other, since system flow may fall outside the boiler's recommended range. A low loss header with a sensor improves control and efficiency.

  1. Use closely spaced tees or a low loss header between the boiler and system loops.
  2. Install a low loss header sensor if a header is used, for better control and efficiency.
  3. Check boiler flow sizing against the pressure drop chart referenced in the manual.

Applies to: Applications 1 to 3

Source: Vitodens 222-F B2TB application guide, p. 32. Written in our own words; check the manual for your exact model.

Hydrostatic pressure test before connecting the boiler

Boiler · Vitorond 200

Leak test and hydrostatically pressure test the boiler before it is connected to piping or power. Hold between 127 psig (875 kPa) and 130 psig (896 kPa) maximum. Stay with the boiler during the test.

  1. Pipe up to the isolation valves and close them.
  2. Install temporary caps on the nipples for the pressure relief valve and expansion tank.
  3. Connect a hose to the boiler drain valve and fill slowly until the gauge reads 130 psig (896 kPa) max.
  4. Hold pressure for 30 minutes and do not leave the boiler unattended.
  5. Check all push nipples and pipe connections with a flashlight for leaks. Place paper under the cast iron block to catch minor drips from the bottom push nipples.
  6. After 30 minutes, open the drain valve slowly to release pressure.
  7. Remove the caps and install the pressure relief valve and expansion tank immediately.

Applies to: Vitorond 200 VD2A boiler

Source: Vitorond 200, VD2A Series Installation, p. 24. Written in our own words; check the manual for your exact model.

Hydrostatic test pressure limits

Boiler · Vitorond 200 VD2A

Minimum test pressure is 127 psig (875 kPa). Maximum is 130 psig (896 kPa), which is also 1½ times the maximum operating pressure. Do not exceed 130 psig.

  1. Set the test between 127 and 130 psig and hold for 30 minutes.

Applies to: All VD2A models

Source: Vitorond 200, VD2A Series Installation, pp. 21, 24. Written in our own words; check the manual for your exact model.

Hygiene and DHW temperature advice

Boiler · Vitodens 100-W, B1HE, B1KE

Keep DHW above 122 F (50 C) for hygiene. Larger systems or low-exchange systems should stay above 140 F (60 C). Warn the owner about the risk of hot outlets.

  1. Explain the DHW temperature settings and the scald risk at draw-off points to the system user.

Applies to: DHW systems

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 61. Written in our own words; check the manual for your exact model.

Ignition and reset after air in gas line

Boiler · Vitocrossal 300 CA3B Dual Fuel

The boiler uses direct spark ignition and starts after a safety time. On first start the gas line may contain air and the unit can show a fault.

  1. If a fault appears at initial start-up, wait about 5 seconds.
  2. Press the reset button R on the burner to reset.
  3. The ignition sequence repeats automatically.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 15. Written in our own words; check the manual for your exact model.

Ignition, gas leak test and CO measurement at startup

Boiler · Vitodens 200-W B2HA

Gas leak checks and CO readings are required around any gas work. Startup faults from air in the gas line are common, especially with LPG.

  1. Take a CO measurement before and after working on the gas appliance (see page 27).
  2. Check for gas leaks with soap and water only. Do not use matches, candles or flame, and do not purge gas into the combustion chamber.
  3. Make sure there is no open flame in the room.
  4. If a fault shows during first startup because of air in the gas supply, wait about 5 seconds and press the R reset button. Ignition repeats.
  5. Record the combustion values in the order given in the Maintenance Record on page 96.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 17. Written in our own words; check the manual for your exact model.

Initial control unit start-up and settings

Boiler · Vitocrossal 300 CA3B

The control unit comes pre-set, but several codings must be set on site. The cascade (lead boiler) control unit runs the system and boiler section 1, and the other units run as lag boilers.

  1. Switch on the main switch and all network switches on the control units.
  2. Switch on the control unit. Start-up runs automatically.
  3. Set the language, date and time, temperature units, system layout and elevation as needed.
  4. Confirm. The prompt 'Do you want to make further changes' appears.

Applies to: CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 32. Written in our own words; check the manual for your exact model.

Initial power-up of the control units

Boiler · Vitocrossal 300 CA3B Dual Fuel

The control units come pre-set, but several codings must still be set on site. Switch on the main switch and all network switches first, then the control unit switch. Start-up runs automatically. Check the language, date and time, temperature units, system layout and elevation, then confirm with OK.

  1. Switch on the main switch and all network switches on the control units.
  2. Switch on the control unit; start-up begins automatically.
  3. Check language, date and time, temperature units, system layout and elevation.
  4. Confirm with OK, then answer the prompt 'Do you want to make further changes'.
  5. Check all addresses in coding level 1 and adjust as required.
  6. Check the listed coding addresses in coding level 2 and adjust.

Applies to: CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 32-33. Written in our own words; check the manual for your exact model.

Initial start-up and factory calibration

Boiler · Vitodens 200-W B2HA

Initial start-up must be done by a qualified heating contractor, who must also complete the Maintenance Record. The boiler is factory tested and calibrated, so gas valve adjustments are normally not needed at field start-up.

  1. Complete initial start-up as a qualified heating contractor.
  2. Fill in the Maintenance Record in the Service Instructions.
  3. Do not adjust the gas valve unless the situation requires it.

Applies to: All B2HA models

Source: Vitodens 200-W B2HA installation manual, p. 6, p. 8. Written in our own words; check the manual for your exact model.

Initial start-up and handover

Boiler · Vitodens 200-W, B2HA

Initial start-up must be done by a qualified heating contractor. Complete the Maintenance Record, and show the owner the system operation, the emergency shutdown, and the need for yearly professional service.

  1. Perform initial start-up as a qualified heating contractor.
  2. Complete the Maintenance Record.
  3. Explain normal operation and emergency shutdown to the owner, including what to do and what not to do.
  4. Tell the owner that yearly professional maintenance is required.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 7. Written in our own words; check the manual for your exact model.

Initial start-up and maintenance record

Boiler · Vitocrossal 200 CI2

Initial start-up must be done by a qualified heating contractor, who also completes the maintenance record.

  1. Complete the Maintenance Record at initial start-up.
  2. Find the Maintenance Record on page 95 of the manual.
  3. Verify the field supplied controls, such as low water cut-offs, pumps, motorized valves, air vents and thermostats.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Initial start-up and matching done by heating contractor

Boiler · Vitotronic 200-H

The first start-up and adjustment of the control to the local system and building must be carried out by the licensed heating contractor.

Applies to: Vitotronic 200-H HK1M

Source: Vitotronic 200-H operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Initial start-up requirements

Boiler · Vitodens 222-F

Initial start-up must be done by a qualified heating contractor. The Maintenance Record in the service instructions must be completed. Turn off main power and close the main gas valve before service work.

  1. Deactivate main power to the equipment, heating system and external controls.
  2. Close the main gas supply valve.
  3. Complete the Maintenance Record after start-up.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB service instructions, p. 6. Written in our own words; check the manual for your exact model.

Install a carbon monoxide alarm

Boiler · Vitocrossal 300 CU3A

Install at least one carbon monoxide alarm in the residential living space before the boiler is put into operation.

  1. Install at least one CO alarm in the living space.
  2. Follow the alarm maker's instructions and local codes.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 6. Written in our own words; check the manual for your exact model.

Install CO alarm before startup

Boiler · Vitodens 200-W, B2HA

Confirm a carbon monoxide alarm is installed in the living space following the alarm maker's instructions and local codes before the boiler is put into operation.

  1. Check that a CO alarm is installed in the living space.
  2. Confirm it was installed per the manufacturer's instructions and local code before firing the boiler.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 7. Written in our own words; check the manual for your exact model.

Install pressure relief valve and discharge piping

Boiler · Vitodens 200-W B2HB

Fit the factory pressure relief valve and drain valve with pipe sealant. The discharge pipe must go to a floor drain, not outdoors, and must not have a shutoff valve.

  1. Remove the pressure relief valve, drain valve and fittings from the box.
  2. Apply pipe sealant to both ends of the fittings and install the tees.
  3. Install the pressure relief valve and the isolation valve, then tighten them.
  4. Pipe the discharge to a floor drain, ending about 6 in. (150 mm) above the drain.
  5. Use an unthreaded pipe end, and make sure there is no shutoff valve in the discharge line.
  6. Do not install an isolation valve between the boiler and the pressure relief valve.
  7. Position the discharge so it cannot scald people.

Applies to: Vitodens 200-W B2HB 19, 26, 35, 68, 94, 125

Source: Vitodens 200-W B2HB installation manual, p. 29. Written in our own words; check the manual for your exact model.

Install the pressure relief valve and discharge pipe

Boiler · Vitodens 200-W

Use the factory supplied approved pressure relief valve. Do not put an isolation valve between the boiler and the relief valve. The discharge pipe must be unthreaded, not reduced, and free of shutoff valves, and must run to a floor drain. Never pipe the discharge outdoors.

  1. Install the factory supplied pressure relief valve.
  2. Do not install an isolation valve between the boiler and the relief valve.
  3. Run the discharge pipe, unthreaded, to a floor drain and end it about 6 in. (150 mm) above the drain.
  4. Keep the discharge pipe diameter at least 3/4 in. and do not reduce it.
  5. Place the discharge so it does not scald people nearby.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 29. Written in our own words; check the manual for your exact model.

Installation codes to follow

Boiler · Vitorond 200 VD2A

Install gas boilers to CAN/CSA-B149.1 or B149.2 in Canada, or NFPA 54 / ANSI Z223.1 in the U.S. Install oil boilers to CSA B-139 in Canada or NFPA 31 in the U.S. Wire to CSA C22.1 Part 1 in Canada or NFPA 70 (NEC) in the U.S. Use the latest editions and local codes where they apply.

  1. Identify the fuel and country, then follow the matching gas, oil and electrical code.
  2. Use the latest code editions and local amendments.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Installation Instructions, p. 6. Written in our own words; check the manual for your exact model.

Installation requirements for side-wall horizontal venting in Massachusetts

Boiler · Vitodens 100-W WB1B

For side-wall horizontally vented gas equipment in Massachusetts dwellings where the vent termination is under 7 feet above grade, a hard-wired CO detector with battery backup is required on the installation floor, and a battery-operated or hard-wired CO detector on each additional level. A metal or plastic sign reading 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' must be mounted at least 8 feet above grade in line with the vent terminal. The detectors must meet NFPA 720 and ANSI/UL 2034 with IAS certification.

  1. Confirm a hard-wired CO detector with battery backup is on the installation floor.
  2. Confirm battery-operated or hard-wired CO detectors are on each additional level.
  3. If the requirement cannot be met at completion, install a battery-operated CO detector and comply within 30 days.
  4. Mount the required sign at least 8 feet above grade, in line with the vent terminal.

Applies to: Side-wall horizontally vented gas equipment, Commonwealth of Massachusetts

Source: Vitodens 100-W WB1B installation and service instructions, p. 6. Written in our own words; check the manual for your exact model.

Installing insulation and jacket panels

Boiler · Vitorond 100

Insulation blankets and panels are fitted around the cast iron block. Fit the Vitotronic cable and panels in the order shown in the manual.

  1. Wrap the insulation blanket around the cast iron block with the cutout facing front, and secure it with the spring clips.
  2. If installing a Vitotronic control, run the plug-in connector cable down behind the front panel and out the bottom.
  3. Install support brackets and the left side panel, line up the bottom tab with the casting leg notch, and bend the tab down.
  4. Install the rear insulation blanket with the black side facing out, then install the rear panel.
  5. Install the right side panel on the brackets, with its top over the rear panel, and bend down the bottom tab.
  6. Before installing the top panels, follow the Vitotronic sections if a control is fitted.
  7. Slide the top front panel locking notches into the side panel holes, then install the top rear panel.
  8. Secure the top rear panel with sheet metal screws and mount the front panel with screws.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 13-15. Written in our own words; check the manual for your exact model.

Installing the safety devices (pressure relief and drain valve)

Boiler · Vitodens 200-W B2HB

Use the factory supplied approved pressure relief valve. Relief valve and fittings are 3/4 in. NPT minimum. Do not install an isolation valve between the boiler and the relief valve, and do not install a shutoff valve or reduce the diameter in the discharge pipe. The discharge pipe must not be threaded at the end, must run close to a floor drain and end about 6 in. (150 mm) above it, and must never be piped outdoors. Orient the discharge to prevent scalding. Piping to a precharged expansion tank is field supplied.

  1. Remove the loosely pre-assembled combination pressure relief and drain valve assembly.
  2. Apply pipe sealant to both ends of fittings B, D, F and H, and install them onto tees A and E.
  3. Install the pressure relief valve G and the isolation valve C on the tees, and tighten.
  4. Run the discharge pipe to a floor drain, ending about 6 in. (150 mm) above the drain, with no threads on the end.
  5. Confirm there is no shutoff valve in the discharge pipe and the pipe is not reduced in size.
  6. Confirm the relief valve and discharge pipe are at least 3/4 in.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 29. Written in our own words; check the manual for your exact model.

Instruct the system owner

Boiler · Vitorond 200 VD2

Explain system operation sequence, start-up and shutdown, and the need for combustion air. Demonstrate an emergency shutdown and what to avoid. Explain that proper maintenance is required for safe operation.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200 VD2 Service Instructions, p. 6. Written in our own words; check the manual for your exact model.

Instructing the system user

Boiler · Vitodens 100-W, B1HE, B1KE

The installer must give the operator the operating instructions for the system and all accessories, such as remote controls, and explain required maintenance.

  1. Hand over operating instructions for the system and any accessories.
  2. Train the operator on system operation and maintenance requirements.

Applies to: System handover

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 61. Written in our own words; check the manual for your exact model.

Isolation and drain valves for service

Boiler · Vitocrossal 200 CI2

Install boiler isolation valves on the system supply and return, with drain valves above them. This allows boiler or system maintenance without draining the whole system. The boiler suits only closed hot water heating systems with pumps.

  1. Install isolation valves on the system supply and return.
  2. Install drain valves above the isolation valves.
  3. Use the boiler only on closed hot water systems that use pumps.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 40. Written in our own words; check the manual for your exact model.

Jumper between the 40A plug and 157 plug

Boiler · Vitodens 222-F

Application 5 requires a jumper between the 40A plug and the 157 plug.

  1. Install the jumper between the 40A plug and the 157 plug before starting up Application 5.

Applies to: Application 5 (VD2T 2HC2T2ZP.02)

Source: Viessmann Vitodens 222-F B2TB application guide, p. 43. Written in our own words; check the manual for your exact model.

Jumper pin must be removed for on-demand DHW via CombiPLUS

Boiler · Vitodens 100-W WB1B

If the X8 jumper pin is left in place, the boiler will not provide on-demand hot water through the CombiPLUS. If the jumper is removed but the CombiPLUS is not programmed, DHW falls back to the built-in resistors in the power pump module.

  1. Remove the X8 jumper pin.
  2. Program the boiler for CombiPLUS use (see programming, p. 35).

Applies to: Vitodens 100-W WB1B with CombiPLUS

Source: Vitodens 100-W WB1B installation and service instructions, p. 31. Written in our own words; check the manual for your exact model.

Keep sensor and remote wiring away from line voltage

Boiler · Vitotronic 300

Sensor and remote control wiring can pick up electromagnetic interference. Keep it away from 120/240 VAC conductors and use shielded or twisted pair where crossings cannot be avoided.

  1. Route low voltage sensor wiring away from 120/240 VAC conductors.
  2. If crossing cannot be avoided, use stranded twisted pair or shielded wire.
  3. Ground only one end of the shielding.

Applies to: Sensor and remote control wiring

Source: Vitotronic 300 technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Keep sensor cables and capillaries clear of the heat exchanger

Boiler · Vitorond 100, VR1

Do not kink capillaries, or sensors will not read correctly. Route all cables and capillaries between the nylon-backed insulation and the metal panels, never directly on the cast iron heat exchanger.

Applies to: Sensor cables and capillaries on Vitotronic control

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 31. Written in our own words; check the manual for your exact model.

Lago FB remote heating circuit control (accessory)

Boiler · Versatronik 200

Lago FB remote controls mixing valve circuit 1 and/or 2 over CAN bus. It mounts on a wall sub-base with a wiring strip. It has a room temperature trim of ±5 K and an integrated room sensor. Two Lago remotes can be wired in parallel.

  1. Secure the sub-base to the wall with field-supplied hardware.
  2. Connect the sub-base with 4-conductor cable: H to terminal 1, L to terminal 2, — to terminal 3, + to terminal 4.
  3. For a second Lago, parallel the terminal connections.

Applies to: Lago FB remote with Versatronik 200

Source: Versatronik 200 installation and operating manual, p. 55. Written in our own words; check the manual for your exact model.

Language and display at first start

Boiler · Vitocrossal 300 CU3A

The display starts in German at commissioning and must be changed to the required language.

  1. Select the language option on the first wizard screen.
  2. Choose the required language.
  3. Press OK to accept.

Applies to: Start-up wizard

Source: Vitocrossal 300 CU3A service instructions, p. 13. Written in our own words; check the manual for your exact model.

Lead boiler activation contact must stay closed

Boiler · Vitotronic 300

On multi-boiler systems the boiler activation contact is essential and the lead boiler contact must be constantly closed.

  1. Verify the lead boiler activation contact is closed during operation.

Applies to: Multi-boiler systems

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

Lead boiler activation contact on multi-boiler systems

Boiler · Vitotronic 100

The boiler activation contact is essential on multi-boiler systems and must not be left open on the lead boiler.

  1. Verify the contact on the lead boiler is constantly closed before startup.

Applies to: Multi-boiler systems

Source: Viessmann Vitotronic 100 GC1 installation manual, p. 65. Written in our own words; check the manual for your exact model.

Leak test the gas supply before start-up

Boiler · Vitodens 100-W, WB1B

The gas supply piping must be leak tested before the boiler goes into operation. Check all gas joints and valves under normal operating pressure with an approved leak detection liquid, never with an open flame.

  1. Leak test all gas joints under normal operating pressure with approved leak detection liquid.
  2. Confirm the gas valves do not leak.
  3. Do not use an open flame to check for leaks.

Applies to: Vitodens 100-W WB1B

Source: Vitodens 100-W WB1B installation and service instructions, p. 72. Written in our own words; check the manual for your exact model.

Leave the rotary address dial at 0

Boiler · Versatronik 515, Versatronik 515D

The rotary dial sets LON addressing. Leave it at the factory default of 0 unless several gateways are on the same system, where a unique setting is needed to avoid duplicate LON addresses.

  1. Check that the rotary dial is at 0.
  2. Change the dial only on systems with multiple 515 gateways, and give each gateway a unique setting.

Applies to: Versatronik 515 and 515D gateways

Source: Versatronik 515 BACnet IP Type B manual, p. 7. Written in our own words; check the manual for your exact model.

Level the boiler for condensate drainage

Boiler · Vitodens 200-W B2HA

The boiler must sit level both vertically and horizontally or condensate will not drain properly.

  1. Use the levelling screws to level the boiler front to back and side to side.
  2. Check the level again after the connections are made.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 17. Written in our own words; check the manual for your exact model.

Licensed installer and annual service

Boiler · Vitocontrol-S

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor. The contractor must train the owner on the system, shutdown procedure and the need for annual professional service before the heating season.

  1. Confirm the installer is a licensed professional heating contractor.
  2. Check that the owner has been shown the shutdown procedure.
  3. Arrange annual professional service before each heating season.

Applies to: Boiler and control system

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 4, p. 5. Written in our own words; check the manual for your exact model.

Locate disconnect and gas shut-off outside the mechanical room

Boiler · Vitocrossal 300 CA3B Dual Fuel

Viessmann recommends a separate electrical disconnect and, where possible, a fuel shut-off valve installed outside the mechanical room or enclosed installation area.

  1. Install an extra electrical disconnect outside the mechanical room.
  2. Install a fuel shut-off valve outside the room if possible.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 3. Written in our own words; check the manual for your exact model.

LON bus wiring length and participant limits

Boiler · Vitotronic 200, Vitotronic 300-K

Up to 99 participants can share the LON bus. Maximum line length is 3000 ft (900 m) with LON plugs, or 3000 ft (900 m) when using LON junction boxes with a 23 ft (7 m) LON cable. A terminator is required at the end of the bus.

  1. Connect the control unit or Vitocom as the start of the bus.
  2. Use on-site cable with LON plugs, or LON cable with junction boxes, as shown in the manual.
  3. Fit a terminator at the far end of the line.
  4. Keep the total line length within 3000 ft (900 m).

Applies to: Vitotronic 300-K and Vitotronic 200-H on LON system

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 24. Written in our own words; check the manual for your exact model.

LON communication setup notes

Boiler · Vitotronic 300-K, Vitotronic 200-H

The LON communication module is an accessory and must be plugged in. Data transfer over LON can take several minutes. In one LON system no participant number may be used twice.

  1. Fit the LON communication module (see parts list).
  2. In code 1, set the LON participant number at coding address 77.
  3. Allow several minutes for LON data transfer before judging the system.
  4. Make sure each participant number is unique on the LON.

Applies to: Vitotronic 300-K and 200-H

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 29. Written in our own words; check the manual for your exact model.

LON setup notes

Boiler · Vitodens 200-W

Data transfer over LON can take several minutes.

  1. Install the LON communication module (accessory) per its installation instructions.
  2. Set participant numbers and functions via coding level 2.
  3. Assign unique participant numbers.
  4. Program only one Vitotronic as fault manager.

Applies to: Vitodens 200-W B2HA 112–530

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 43. Written in our own words; check the manual for your exact model.

Low water cut-off

Boiler · Vitodens 222-F

A low water cut-off may be required by local codes.

  1. Check local codes for a low water cut-off requirement.
  2. Do not install an isolation valve between the boiler and the low water cut-off.

Applies to: Vitodens 222-F, B2TB

Source: Vitodens 222-F, B2TB installation instructions, p. 29. Written in our own words; check the manual for your exact model.

Low water cut-off (LWCO) device connection

Boiler · Vitotronic 200

A 3-conductor cable runs from the low water cut-off to the Power Pump Module. The LWCO contact closes when water is present. The jumper on the Power Pump Module board must be removed when an LWCO is installed.

  1. Run a 3-conductor cable between the LWCO device and the Power Pump Module.
  2. Remove the jumper between terminals L/P1 and P2 on the Power Pump Module board.
  3. Wire the LWCO as shown in the manual drawing.
  4. After installation, check that the LWCO function works.

Applies to: Vitotronic 200 KW2 with low water cut-off

Source: Vitotronic 200 Service Instructions, p. 62. Written in our own words; check the manual for your exact model.

Low water cut-off and isolation valves

Boiler · Vitocrossal 300 CU3A

Low water cut-off requirements for the boiler.

  1. Install an approved low water cut-off if local codes require one, and always if the boiler is installed above the radiation level.
  2. Do not install an isolation valve between the boiler and the low water cut-off.
  3. Let the heating contractor supply the low water cut-off device.

Applies to: Vitocrossal 300 CU3A installation

Source: Vitocrossal 300 CU3A technical data manual, p. 30. Written in our own words; check the manual for your exact model.

Low water cut-off device

Boiler · Vitodens 200-W B2HA

A low water cut-off may be required by local code.

  1. If required, install an approved low water cut-off per its manufacturer instructions.
  2. Do not install an isolation valve between the boiler and the low water cut-off.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 30. Written in our own words; check the manual for your exact model.

Low water cut-off device in every system layout

Boiler · Vitotronic 300

All five application examples show a low water cut-off device wired into the boiler system. Include it in any layout you build.

Applies to: Vitotronic 300 KW3, all application examples

Source: Vitotronic 300 installation instructions, p. 4. Written in our own words; check the manual for your exact model.

Low water cut-off placement

Boiler · Vitodens 200-W B2HA

A low water cut-off (LWCO) is required wherever local codes call for one. Piping and components must be verified in the field, and proper function is the responsibility of the heating contractor.

  1. Check local codes for LWCO requirements.
  2. Install the LWCO where required.
  3. Verify all piping and components in the field against the simplified layout drawings.

Applies to: Vitodens 200-W B2HA 45, 60 system piping

Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 32. Written in our own words; check the manual for your exact model.

Low water cut-off requirement

Boiler · Vitorond 200 VD2A

A low water cut-off is required if the boiler sits above radiation level. Viessmann recommends one in all installations.

  1. Install an approved low water cut-off in the supply header, by the mechanical contractor where local code requires it.

Applies to: Supply header

Source: Vitorond 200, VD2A Series Installation, p. 24. Written in our own words; check the manual for your exact model.

Low-loss header and pump sizing

Boiler · Vitodens 200-W B2HB

A low-loss header is strongly recommended when system flow may exceed boiler max flow or when flow is unknown. Field pump sizing is critical in underfloor systems.

  1. Check the system flow rate against the boiler maximum water flow rate table.
  2. Fit a low-loss header if flow may exceed the boiler maximum or flow is unknown.
  3. Size the field-supplied pump against the boiler supply head pressure drop to avoid short-cycling.
  4. Install a low water cut-off where local codes require it.

Applies to: Multi-circuit and high-flow systems

Source: Vitodens 200-W, B2HB technical data manual, p. 33. Written in our own words; check the manual for your exact model.

Low-loss header flow relationships

Boiler · Vitocrossal 300 CU3A

Relationships between boiler and system circuit flows when a low-loss header is used.

  1. Confirm primary (boiler) flow is less than secondary (heating circuit) flow.
  2. Confirm secondary flow equals primary flow plus bypass flow.
  3. Confirm heat supplied by boiler equals heat consumed by system.
  4. Confirm boiler return temperature T2 equals system return temperature T4.
  5. Confirm boiler supply temperature T1 is higher than system supply temperature T3.

Applies to: Vitocrossal 300 CU3A with low-loss header

Source: Vitocrossal 300 CU3A technical data manual, p. 17. Written in our own words; check the manual for your exact model.

Low-loss header installation

Boiler · Vitocrossal 300 CU3A

Use the low-loss header as a hydraulic break and for air and debris removal, especially when system head and flow rates are unknown.

  1. Install the header with the Viessmann temperature sensor at the TS connection, typically at the top of the header.
  2. Use only a Viessmann temperature sensor (accessory). Do not use another manufacturer's sensor.
  3. Check the maximum system flow rate for the header type against the table in this manual.
  4. Mount the header in the system as shown in the low-loss header design drawing.

Applies to: Vitocrossal 300 CU3A with low-loss header

Source: Vitocrossal 300 CU3A technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Low-loss header piping and air/debris removal

Boiler · Vitodens 100-W WB1B

In a low-loss header layout, system mixed supply temperature (T3) must be calculated per the manual formula. Temperatures T1 must be above 176°F (80°C) for the header design to work as shown. The header also removes air and debris from the heating system, so use the air bleed and drain valve connections.

  1. Connect boiler supply and return to the header boiler ports.
  2. Connect the system supply and return to the header system ports.
  3. Use the air bleed and drain valve to purge air and debris from the header.

Applies to: Low-loss header installations

Source: Viessmann Vitodens 100-W WB1B installation and service manual, p. 49. Written in our own words; check the manual for your exact model.

Low-loss header sensor connection

Boiler · Vitocrossal 300 CU3A

Where a low-loss header is used, connect the Viessmann temperature sensor at the TS connection, normally at the top of the header. This keeps boiler return temperatures low. Do not use another manufacturer's sensor.

  1. Install the Viessmann temperature sensor (accessory) at the TS connection on the low-loss header.
  2. Do not substitute a sensor from another manufacturer.

Applies to: Vitocrossal 300 CU3A with low-loss header

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Technical Data Manual, p. 16. Written in our own words; check the manual for your exact model.

Marine and damp environments

Boiler · Vitocrossal 300 CU3A

Boiler casing and fan housing corrode quickly in salty, damp areas.

  1. Do not use direct vent (outdoor combustion air) in damp or salty marine locations.
  2. Use a room air dependent vent system in those locations.

Applies to: Coastal or salt-air installations

Source: Vitocrossal 300 CU3A installation instructions, p. 9. Written in our own words; check the manual for your exact model.

Mechanical room ambient limits

Boiler · Vitocrossal 300 CU3A

Boiler room must stay in the allowed temperature range and free of combustion air contaminants.

  1. Keep ambient temperature above 32°F (0°C) and below 104°F (40°C).
  2. Keep combustion air free of halogenated hydrocarbons and excessive dust.
  3. Avoid continuously high humidity.
  4. Never close existing ventilation openings.

Applies to: All models

Source: Vitocrossal 300 CU3A installation instructions, p. 9. Written in our own words; check the manual for your exact model.

Mechanical room and combustion air requirements

Boiler · Vitodens 222-F

Mechanical room must stay between 32 °F (0 °C) and 104 °F (40 °C), be free of chemical and dust contamination, and keep humidity moderate. Never close existing ventilation openings.

  1. Check the room is heated, indoors, near a floor drain, and near an outside wall where possible.
  2. Keep halogenated hydrocarbons and excessive dust away from combustion air.
  3. In marine or salt-air areas, use a room-air-dependent vent system rather than direct vent.

Applies to: Vitodens 222-F B2TB

Source: Viessmann Vitodens 222-F B2TB installation manual, p. 9. Written in our own words; check the manual for your exact model.

Mechanical room location and air requirements

Boiler · Vitorond 100

Install the boiler where fresh combustion air can reach it. The room must not be under negative pressure, and the boiler must not sit where chemicals, aggressive vapours or high dust or humidity are present.

  1. Install the boiler near an outside wall so fresh air can be ducted directly to the boiler area.
  2. Do not use exhaust, attic or dryer fans in the boiler room.
  3. Do not install the boiler in a room with refrigeration equipment or where chemicals are stored.
  4. Keep the boiler on a floor that can carry its filled weight, and do not block combustion air circulation.
  5. Place a concrete foundation under the boiler if the floor may flood, is not level, or the boiler is in a residential garage.
  6. In a garage, raise the burner at least 18 in. (457 mm) above the floor.
  7. Check local authority requirements for combustion air.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 9. Written in our own words; check the manual for your exact model.

Mechanical room maximum temperature

Boiler · Vitorond 200 VD2A

The mechanical room where the boiler is located must not exceed 104°F (40°C). Viessmann also recommends an extra electrical disconnect and a fuel shut-off valve outside the mechanical room, where possible.

  1. Check the mechanical room temperature stays at or below 104°F (40°C).
  2. Install an extra electrical disconnect and fuel shut-off outside the room if possible.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Installation Instructions, p. 6. Written in our own words; check the manual for your exact model.

Mixing valve circuits need the actuator kit and supply sensor

Boiler · Vitotronic 300

Each heating circuit with a mixing valve needs a mixing valve actuator accessory kit. The kit includes the mixing valve motor and the supply temperature sensor, which connect to the control.

  1. Order one actuator kit per mixing valve circuit.
  2. Use the 7133 392 kit on older valves or the 7837 524 kit on newer valves.
  3. Connect the supply temperature sensor from the kit to the control.

Applies to: Vitotronic 300 KW3 with one or more mixing valve circuits

Source: Vitotronic 300 installation instructions, p. 5-8. Written in our own words; check the manual for your exact model.

Mixing valve control options

Boiler · Vitodens 200-W B2HA

The built-in 3-way mixing valve for low-temperature circuits is controlled by an accessory kit for a heating circuit with mixing valve. Alternatively, a Vitotronic 200-H HK1B mixing valve control with LON communication module can be used instead of the kit and Vitocontrol.

  1. Fit the accessory kit for a heating circuit with mixing valve to control the 3-way mixing valve.
  2. Or use Vitotronic 200-H HK1B with the LON communication module instead of the kit and Vitocontrol.
  3. For complex multi-circuit designs, contact the local Viessmann sales representative.

Applies to: Vitodens 200-W B2HA 45, 60 mixing valve circuits

Source: Vitodens 200-W B2HA 45, 60 installation manual, pp. 36-40. Written in our own words; check the manual for your exact model.

Mixing valve type selection

Boiler · Vitotronic 300

Condensing boilers have low return water temperatures, so only 3-way mixing valves are allowed on them. Non-condensing boilers can use a 4-way valve.

  1. On condensing boilers, install only 3-way mixing valves.
  2. On non-condensing boilers such as Vitogas 100, Vitorond 200 and Vitola 200, a 4-way mixing valve may be used.
  3. Order the circulation pump with flow check valve for DHW tank control separately.

Applies to: Mixing valve circuits

Source: Vitotronic 300 technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Mixing valves and underfloor heating

Boiler · Vitocrossal 300 CU3A

Rules for mixing valves and underfloor tubing.

  1. Avoid mixing valves in heating circuits where possible, because condensing needs low return temperatures.
  2. If a mixing valve is required, use only 3-way mixing valves. Do not use 4-way mixing valves.
  3. Connect underfloor systems with large water volumes through a 3-way mixing valve.
  4. Separate underfloor systems that use tubing without an oxygen diffusion barrier from the boiler with a heat exchanger.

Applies to: Vitocrossal 300 CU3A heating circuit design

Source: Vitocrossal 300 CU3A technical data manual, p. 31. Written in our own words; check the manual for your exact model.

Mixing valves on condensing systems

Boiler · Vitodens 100-W, B1HE, B1KE

Condensing operation needs low return temperatures, so avoid mixing valves in the heating circuit where possible.

  1. Avoid mixing valves in the heating circuit where possible.
  2. If a mixing valve is needed (multi-circuit or underfloor), use only 3-way mixing valves.
  3. Do not use 4-way mixing valves with condensing boilers.

Applies to: Hydronic system layout

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 26. Written in our own words; check the manual for your exact model.

Modbus RS-485 wiring

Boiler · Versatronik 502 & 502D

Use COM 1 terminals A and B for Modbus. A is the non-inverting (+) line and B is the inverting (-) line. Naming can differ between manufacturers, so check the DDC system. The gateway has no termination resistor, so handle termination at the network. Two 4.7 kOhm pull-up/pull-down bias resistors are on the lines.

  1. Connect the DDC network to COM 1 terminals A and B on the gateway.
  2. Confirm A is (+) and B is (-) against the DDC system labelling.
  3. Add termination at the network end, because the gateway does not provide it.
  4. Confirm the Modbus device address is set on the rotary dial.

Applies to: Versatronik 502 and 502D MODBUS gateway

Source: Versatronik 502 NR2 Modbus manual, p. 8. Written in our own words; check the manual for your exact model.

Modbus RS-485 wiring and termination

Boiler · Versatronik 502, Versatronik 502D

Use COM 1 terminals A and B. Terminal naming differs between manufacturers, so A is the non-inverting (+) line and B is the inverting (-) line. The gateway has no termination resistor, only two weak 4.7 kOhm pull up/down bias resistors on the lines. Add termination at the network ends as the Modbus network requires.

  1. Connect the field Modbus wiring to COM 1 terminals A and B.
  2. Match A to the (+) non-inverting side and B to the (-) inverting side of the DDC network.
  3. Do not rely on the gateway for line termination; provide it on the network if needed.

Applies to: Versatronik 502 and 502D gateway, all listed controls

Source: Versatronik 502 MODBUS manual, p. 8. Written in our own words; check the manual for your exact model.

Mounting the 120VAC gateway

Boiler · Versatronik 585, Versatronik 585D

Mount the 120VAC gateway near the boiler control. Loosen the two screws on the base to remove the cover, fix the base to the wall, and remove a knockout for the strain relief or box connector. Reinstall the cover after all 120VAC and low-voltage wiring is done and checked.

  1. Remove the cover by loosening the two screws on each side of the base.
  2. Fasten the base to the wall with field-supplied fasteners.
  3. Remove one knockout and fit the strain relief or box connector.
  4. Remove the other knockouts only as needed for connections.
  5. Complete and verify all 120VAC and low-voltage wiring, then refit the cover.

Applies to: Versatronik 585 (120VAC)

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 4. Written in our own words; check the manual for your exact model.

Mounting the 24VAC DIN rail gateway

Boiler · Versatronik 585D

The 585D mounts on a DIN rail inside an enclosure near the boiler controls. It needs a field-supplied 24VAC power connection.

  1. Mount the 585D gateway on a DIN rail inside an enclosure close to the boiler controls.
  2. Make all connections, including the field-supplied 24VAC power supply.
  3. Check the connection overview: BACnet IP RJ45, control BACnet RJ45, paralleled BUS connection, and 24VAC power.

Applies to: Versatronik 585D (24VAC)

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 5. Written in our own words; check the manual for your exact model.

Multi boiler fault message at first start-up

Boiler · Vitotronic 300 GW6B

A fault message appears on first start-up of a CM2 boiler in a multiple boiler application because the boiler controller commissioning is not finished.

  1. Acknowledge the fault message.
  2. Complete the commissioning process.

Applies to: Vitocrossal 200 CM2 in multi boiler systems

Source: Vitotronic 300 GW6B installation and service manual, p. 48. Written in our own words; check the manual for your exact model.

Multi-boiler and zone control capability

Boiler · Vitocrossal 300 CU3A

Up to 8 boilers can be installed in multi-boiler configuration up to 1592 MBH (464 kW). The Vitotronic control provides 3 zone circuit inputs for third party thermostats, SIM controls, multizone controllers, and on/off devices. Setup uses a start-up wizard.

  1. Use the start-up wizard to enter the relevant system information.
  2. Set each zone circuit to a set temperature or an outdoor reset curve as needed.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 Technical Data Manual, p. 2. Written in our own words; check the manual for your exact model.

Multi-boiler systems without Vitotronic 333

Boiler · Vitotronic 100, GC1

Cascade and DHW tank control must be activated by a building automation system.

  1. Confirm building automation activates cascade staging and DHW tank control before commissioning.

Applies to: Circuit Diagrams 5, 6, 7 and 8 multi-boiler systems

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Never adjust the burner by eye

Boiler · Vitorond 100

Burner settings must be measured, not judged visually.

  1. Set the burner using combustion measurements from calibrated equipment only.

Applies to: Oil burner adjustment

Source: Vitorond 100, VR1 installation and service instructions, p. 45. Written in our own words; check the manual for your exact model.

Never check gas leaks with an open flame

Boiler · Vitodens 200-W B2HA

Use only approved leak detection solution for gas leak checks.

  1. Check gas connections with an approved liquid spray solution, not an open flame.

Applies to: Vitodens 200-W B2HA gas connections

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation Instructions, p. 20. Written in our own words; check the manual for your exact model.

No flow switch required

Boiler · Vitocrossal 300 CU3A

This boiler does not use a flow switch. It is only suitable for fully pumped hot water heating systems.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 18. Written in our own words; check the manual for your exact model.

No isolation valve between boiler and safety header

Boiler · Vitorond 200 VD2A

Do not install an isolation valve between the boiler and the safety header or between the relief valve and the boiler. The relief discharge must be routed so it cannot scald people.

  1. Pipe the relief discharge so it cannot scald attendants.
  2. Keep the relief discharge pipe as short and straight as possible, with an elbow close to the valve outlet.

Applies to: Safety piping

Source: Vitorond 200, VD2A Series Installation, pp. 22-23. Written in our own words; check the manual for your exact model.

Non-Viessmann DHW tank

Boiler · Vitodens 200-W B2HA

If the DHW storage tank is not a Viessmann Vitocell 100 or 300, the DHW tank temperature sensor must be checked with the tank manufacturer. A temperature tempering valve is strongly recommended in the DHW supply line.

  1. Verify the DHW tank temperature sensor operation with the tank's original manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

Applies to: Non-Viessmann DHW storage tanks

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 41. Written in our own words; check the manual for your exact model.

Non-Viessmann DHW tank checks

Boiler · Vitodens 200-W

With a DHW tank that is not a Viessmann Vitocell 100 or 300, the installer must confirm the Viessmann DHW tank sensor works correctly with the tank maker. The coil pressure drop must also be calculated against the field pump's residual head to make sure enough flow reaches the boiler heat exchanger.

  1. Verify the Viessmann DHW tank temperature sensor operation with the original tank manufacturer.
  2. Calculate DHW coil pressure drop and compare it with the field pump's residual head.
  3. Confirm the boiler heat exchanger still gets sufficient flow.

Applies to: Non-Viessmann DHW storage tanks

Source: Vitodens 200-W B2HA installation manual, p. 32. Written in our own words; check the manual for your exact model.

Non-Viessmann DHW tank sensor check

Boiler · Vitodens 200-W B2HB

With a DHW tank other than a Viessmann Vitocell 100 or 300, the Viessmann DHW tank sensor must be checked against the tank maker's data. A temperature tempering valve is strongly recommended in the DHW supply line.

  1. Confirm with the tank manufacturer that the Viessmann DHW tank sensor operates correctly on that tank.
  2. Install a temperature tempering valve in the DHW supply line.

Applies to: Non-Viessmann DHW storage tanks

Source: Vitodens 200-W B2HB installation instructions, p. 32. Written in our own words; check the manual for your exact model.

Only a licensed heating contractor may install and service

Boiler · Vitorond 200 VD2

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor experienced with hot water boilers. There are no user-serviceable parts on the boiler, burner or control.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200 VD2 Service Instructions, p. 6. Written in our own words; check the manual for your exact model.

Outdoor sensor and DHW limits

Boiler · Versatronik

The controller works with or without an outdoor sensor. Without a sensor, outdoor reset is not possible and some settings are unavailable. When a sensor is wired in, the controller recognises it automatically. Domestic hot water through the controller only works if the boiler supports a DHW function over OpenTherm.

  1. Wire the outdoor sensor to terminals 5 and 6 if outdoor reset is wanted.
  2. Confirm the boiler supports DHW over OpenTherm before expecting hot water production from the controller.

Applies to: Versatronik COMO OT with OpenTherm boiler

Source: Versatronik COMO OT manual, p. 14. Written in our own words; check the manual for your exact model.

Outdoor sensor and DHW sensor installation notes

Boiler · Vitodens 100-W B1HE/B1KE

The outdoor sensor is field wired and must sit on the north or northwest wall, 2 to 2.5 m above ground. The DHW tank sensor is an immersion sensor with about 12 ft cable and is supplied ready to plug in. All pipe connections are field supplied.

  1. Mount outdoor sensor on north or northwest wall, 80 to 100 in. above ground.
  2. Keep sensor cable clear of line voltage.
  3. Plug in DHW tank sensor and field-pipe the tank connections.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE technical data manual, p. 18. Written in our own words; check the manual for your exact model.

Outdoor sensor mounting location

Boiler · Vitotronic 300

The outdoor sensor must be on a specific side of the building at a set height, with its cable kept away from line voltage.

  1. Mount the outdoor sensor on the north or northwest side of the building.
  2. Mount it 6.6 to 8.2 ft (2 to 2.5 m) above ground.
  3. On multi-storey buildings, mount it on the upper half of the second floor.
  4. Do not lay the sensor cable near 120/240 V wiring.

Applies to: Outdoor temperature sensor

Source: Vitotronic 300 technical data manual, p. 4. Written in our own words; check the manual for your exact model.

Outdoor temperature sensor placement and wiring

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Mount the outdoor sensor on a north or north-west wall, 6 to 8 ft (2 to 2.5 m) above ground. In multi-storey buildings use the upper half of the second floor.

  1. Keep the sensor away from windows, doors and vent outlets, and away from balconies or gutters above it.
  2. Do not paint over the sensor.
  3. Wire it with 2-conductor cable, 18 AWG, to a maximum length of 115 ft (35 m).

Applies to: All Vitocrossal 300 CA3B Dual Fuel models

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 20. Written in our own words; check the manual for your exact model.

Owner briefing after installation

Boiler · Vitorond 200 VD2A

The installer must make the system operator or owner familiar with system operation, start-up, shut-down and emergency shut-down, and explain the need for combustion air and regular maintenance.

  1. Explain the proper system operation sequence.
  2. Explain the equipment and the need for combustion air.
  3. Demonstrate an emergency shut-down and state what to do and what not to do.
  4. Explain that proper maintenance is needed for safe operation.
  5. Tell the owner where the literature is kept on site.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Service Instructions, p. 6. Written in our own words; check the manual for your exact model.

Owner handover and initial start-up duties

Boiler · Vitocrossal 300 CA3B Dual Fuel

The installer must show the owner how the system works, how it is switched on and off, and how to shut it down in an emergency. Initial start-up must be done by a qualified heating contractor, who also completes the maintenance record.

  1. Explain the operating sequence and the need for combustion air.
  2. Demonstrate emergency shutdown and state what to do and what not to do.
  3. Explain that regular maintenance is required for safe operation.
  4. Complete the maintenance record (page 158 of the manual).

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Owner handover and initial start-up requirements

Boiler · Vitodens 200-W

The installer must walk the owner through system operation, the equipment, and a manual emergency shutdown. Initial start-up must be done by a qualified heating contractor, and the Maintenance Record must be filled in. The boiler has no user-serviceable parts. Leave the literature on site.

  1. Show the owner the proper operating sequence and explain the equipment.
  2. Demonstrate emergency shutdown, including what to do and what not to do.
  3. Tell the owner that regular maintenance is required for safe operation.
  4. Complete the Maintenance Record after initial start-up.
  5. Leave all literature at the site and tell the owner where it is kept.

Applies to: Vitodens 200-W B2HB 19 to 125

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 service instructions, p. 7. Written in our own words; check the manual for your exact model.

Oxygen diffusion barrier in underfloor tubing

Boiler · Vitodens 222-F

Boiler warranty does not cover leaks from corrosion caused by underfloor plastic tubing without an oxygen diffusion barrier. Non-barrier tubing must be separated from the boiler with a heat exchanger. Use barrier tubing where possible.

  1. Use underfloor plastic tubing with an oxygen diffusion barrier.
  2. If non-barrier tubing is used, separate it from the boiler with a heat exchanger.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 17. Written in our own words; check the manual for your exact model.

Piping and pump sizing are the installer's responsibility

Boiler · Vitodens 200-W B2HB

The layout drawings are conceptual only. The heating contractor must verify all piping, components and pump sizing in the field. Undersized pumps or small DHW piping can cause short-cycling and poor DHW supply.

  1. Verify all piping and components in the field before using any layout drawing.
  2. Use at least 1¼ in. pipe for DHW supply and return between the boiler and the Viessmann DHW tank.
  3. For non-Viessmann DHW tanks, calculate the coil pressure drop against the field pump's residual head.
  4. Check boiler heat exchanger flow against the pressure drop table on page 30.
  5. Install a low water cut-off where local codes require it.

Applies to: All system layouts

Source: Vitodens 200-W B2HB installation instructions, p. 32. Written in our own words; check the manual for your exact model.

Piping and system requirements

Boiler · Vitocrossal 300 CU3A

Rules for the hydronic and gas piping.

  1. Use only fully pumped hot water systems.
  2. Never install 4-way mixing valves, overflow valves or flow/return bypass devices.
  3. Never connect a heating return to the safety return.
  4. Keep gas ignition components protected from water spray and splashing.
  5. Ensure gas line is large enough so no pressure drop occurs when any appliance lights or runs.
  6. Do not install the boiler where the piping interferes with serviceable parts.

Applies to: All models

Source: Vitocrossal 300 CU3A installation instructions, p. 11, 10, 15. Written in our own words; check the manual for your exact model.

Post-installation checklist

Boiler · Vitotronic 300

Check these items before start-up and correct any faults.

  1. Confirm limit capillaries and sensors are fully inserted in the sensor wells.
  2. Confirm all electrical connections are correct and secure.
  3. Confirm the boiler coding card is inserted.
  4. Confirm fuse F2 is plugged in.
  5. Confirm the outdoor sensor is mounted correctly and cabled to the sensor and connector.
  6. Confirm the fixed and adjustable high limits are set as required.
  7. Label the programming unit fields according to heating circuit allocation.
  8. File the installation, operating and service instructions in the service binder.

Applies to: Vitotronic 300 KW3

Source: Vitotronic 300 installation instructions, p. 24. Written in our own words; check the manual for your exact model.

Post-installation checklist for the Vitotronic 300

Boiler · Vitotronic 300

Before leaving the job, confirm the wiring, sensors and boiler coding card are right and that the control is set up for the heating circuits present.

  1. Check that the limit capillaries and sensors are fully seated in their wells.
  2. Check that all electrical connections are made correctly and every connector is fully plugged in.
  3. Confirm the boiler coding card is inserted.
  4. Confirm fuse F2 is plugged in.
  5. Confirm the outdoor temperature sensor is mounted correctly and its cable is properly connected at the sensor and at the connector.
  6. Set the fixed high limit and the adjustable high limit correctly, if required.
  7. Label the programming unit fields to match the heating circuit allocation.
  8. Carry out start-up and adjustments using the Service Instructions.

Applies to: Vitotronic 300 KW3

Source: Vitotronic 300 installation instructions, p. 24. Written in our own words; check the manual for your exact model.

Power supply and grounding for the Versatronik 503

Boiler · Versatronik 503

The module ships with a 6 ft (2 m) power cord with a plug. Electrical work must follow local code and the listed standards. Bond the appliance and pipework to the building's equipotential bonding, and do not swap L and N.

  1. Protect the power cable with a maximum 15 A breaker.
  2. Connect the power supply and provide grounding, including an RCD circuit where required.
  3. Make sure the building grounding and equipotential bonding are connected to the appliance and pipework.
  4. Keep L and N correctly matched; never swap them.
  5. Check phase equality against the control unit supply and confirm the phase sequence.
  6. If extra wire is run, keep it away from 120/240 VAC conductors. Use stranded twisted-pair shielded wire where that cannot be avoided, and ground only one end of the shield.

Applies to: Versatronik 503 power connection

Source: Versatronik 503 NR2/Analog Bridge installation and operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Power supply and input wiring

Boiler · Versatronik 300

The control has a 120VAC, 10A rating and comes with a power cord. Finish all low-voltage and output wiring before plugging it in. Do not run the power outlet through a switch or a low water cut-off. A heavy pump may need its own dedicated 120VAC circuit.

  1. Complete low-voltage and output wiring first.
  2. Plug the control into a standard 120VAC outlet.
  3. Do not put a switch or low water cut-off in the power supply to the outlet.
  4. If the pump load is heavy, feed the control from a dedicated 120VAC source.

Applies to: Versatronik 300 power input

Source: Versatronik 300 Cascade Control manual, p. 25. Written in our own words; check the manual for your exact model.

Power supply and overcurrent protection

Boiler · Versatronik 10.WB1

The 120 VAC supply needs a disconnect switch located outside the boiler room and maximum 15 A overcurrent protection (fuse or breaker). Wiring must follow CSA C22.1 Part 1 or NEC ANSI/NFPA 70 and local codes.

  1. Install a disconnect switch for the 120 VAC supply outside the boiler room.
  2. Protect the 120 VAC supply with a fuse or breaker rated 15 A maximum.
  3. Wire according to CSA C22.1 Part 1 or NEC ANSI/NFPA 70 and local code.

Applies to: Versatronik 10.WB1 power supply

Source: Versatronik 10.WB1 installation and operating manual, p. 4. Written in our own words; check the manual for your exact model.

Power supply for the external accessories box

Boiler · Vitodens 200-W B2HA

The external accessories connection box needs a 120 VAC, 12 A supply. Wiring diagram is referenced on page 44, which is not in this extract.

  1. Provide a 120 VAC, 12 A supply to the external accessories connection box.
  2. Check the wiring against the wiring diagram on page 44.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 18. Written in our own words; check the manual for your exact model.

PP(s) vent system requirements

Boiler · Vitocrossal 300 CA3B Dual Fuel

PP(s) is rated for a maximum of 230 F (110 C). Do not mix components from different vent makers. Flexible vent or air intake pipe reduces the allowed equivalent length by 25 percent. Vent that passes outside the building must be in an enclosed, insulated and waterproof chase.

  1. Use only ULC S636 / UL-1738 listed PP(s) components.
  2. Do not mix pipe, fittings or joining methods from different vent manufacturers.
  3. Check the equivalent length against the two-pipe limits on p. 58 or the single-pipe limits on p. 63.
  4. Reduce the maximum equivalent length by 25 percent when flexible pipe is used.
  5. Install a side wall vent with a protective screen.

Applies to: PP(s) venting

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 53. Written in our own words; check the manual for your exact model.

Pressure relief valve discharge and isolation rules

Boiler · Vitodens 222-F

Keep the relief discharge safe and never isolate the relief valve from the boiler.

  1. Do not install an isolation valve between the boiler and the pressure relief valve.
  2. Orient the discharge pipe so it cannot scald people.
  3. Pipe the discharge close to a floor drain.
  4. Never pipe the relief discharge to the outdoors.

Applies to: Vitodens 222-F, B2TB

Source: Vitodens 222-F, B2TB installation instructions, p. 29. Written in our own words; check the manual for your exact model.

Pressure relief valve installation and discharge piping

Boiler · Vitocrossal 200 CI2

The pressure relief valve mounts on the top of the boiler or on the boiler safety supply. Nothing that can shut off or block flow may be between the boiler and the relief valve or on its discharge side. The discharge pipe keeps the same size as the outlet, runs horizontally over the side of the boiler and then down to about 1 ft (300 mm) above the floor, as close to a floor drain as possible. Do not pipe the discharge outdoors or to any place where it can freeze.

  1. Mount the relief valve on the top of the boiler or the boiler safety supply.
  2. Do not install any valve or obstruction between the boiler and the relief valve.
  3. Keep the discharge pipe the same size as the relief valve outlet.
  4. Run the discharge horizontally over the side of the boiler, then vertically down to about 1 ft (300 mm) above the floor.
  5. Route the discharge close to a floor drain and not outdoors or where freezing can occur.
  6. Secure the discharge piping with hangers or brackets.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 40. Written in our own words; check the manual for your exact model.

Primary waterside flow and low-loss header

Boiler · Vitodens 200-W B2HB

The boiler is for closed-loop, forced-circulation hot water systems only. Size pipe with the standard friction loss method and stay within the boiler flow limits. Viessmann strongly recommends a low-loss header (LLH) and prefers it over closely spaced tees. If system flow is unknown or outside the boiler limits, use an LLH.

  1. Size the primary piping with the standard friction loss method.
  2. Confirm system flow is within the boiler minimum and maximum limits.
  3. Install a low-loss header if flow is above the maximum, below the minimum, or unknown.
  4. Connect the low-loss temperature sensor (80/60) for single-boiler applications.

Applies to: Vitodens 200-W B2HB 19, 26, 35, 68, 94, 125

Source: Vitodens 200-W B2HB installation manual, p. 30-31. Written in our own words; check the manual for your exact model.

Pump selection and low-loss header logic

Boiler · Vitodens 222-F

Pump selection must be based on accurate system flow and pressure drop calculations, including DHW sizing. The boiler has a factory-set integrated boiler/system pump, and its flow must be selected based on Ut. With a low-loss header connected, the boiler's built-in LLH logic manages Ut through sensor communication with the header.

  1. Calculate system flow and pressure drop, including DHW sizing.
  2. Confirm system flow is within boiler max and min flow limits.
  3. Install a low-loss header if flow exceeds max, falls below min, or is unknown.
  4. Connect the Viessmann low-loss temperature sensor for single-boiler use.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 14. Written in our own words; check the manual for your exact model.

Pump selection for field-supplied pumps

Boiler · Vitodens 100-W B1HE/B1KE

The boiler is only for closed-loop, forced-circulation hot water systems. Size field pumps on pressure drop from accurate system flow and head calculations, including DHW sizing.

  1. Calculate system flow and pressure drop, including DHW load.
  2. Size pipe with the standard friction loss method.
  3. Keep flow within the boiler's maximum and minimum limits.

Applies to: Heating circuit pumps

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 10. Written in our own words; check the manual for your exact model.

Pump sizing for underfloor layouts

Boiler · Vitocrossal 300 CU3A

In system layouts with mixing valves, the field-supplied pump size controls proper boiler operation.

  1. Size the field-supplied pump using the boiler supply head pressure drop given on page 8 of the manual.
  2. Do not undersize the pump, which can cause short cycling or poor boiler operation.
  3. Check the pressure drop of the plate heat exchanger on the secondary side is not greater than the pressure drop of the 3-way mixing valve.

Applies to: Vitocrossal 300 CU3A system layouts 2, 3 and 4

Source: Vitocrossal 300 CU3A technical data manual, p. 21, 22 and 23. Written in our own words; check the manual for your exact model.

Pump wiring with motor contactors or starters

Boiler · Vitotronic 100 GC1

Single-phase and three-phase pumps must be connected through field-supplied motor contactors or motor starters.

  1. Install field-supplied motor contactors or motor starters for single-phase and three-phase pumps.

Applies to: Vitotronic 100 GC1 pump connections

Source: Vitotronic 100, GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 33. Written in our own words; check the manual for your exact model.

Purge LPG supply

Boiler · Vitodens 222-F

Purge the LPG tank and gas supply line during commissioning or replacement.

  1. Purge the LPG tank and gas supply line twice during commissioning or replacement.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 19. Written in our own words; check the manual for your exact model.

Recall the commissioning assistant later

Boiler · Vitocrossal 200 CI2

The commissioning assistant can be restarted at any time if commissioning must be finished later.

  1. Tap the menu button.
  2. Select Service.
  3. Enter password viservice and confirm.
  4. Select Commissioning and confirm.

Applies to: Vitocrossal 200 CI2, all sizes

Source: Vitocrossal 200 CI2 service instructions, p. 16. Written in our own words; check the manual for your exact model.

Record slab curing heat-up data for the report

Boiler · Vitotronic 200-H

The contractor report for slab curing needs the heat-up data.

  1. Record the heat-up supply temperatures for each step.
  2. Record the actual maximum supply temperature reached.
  3. Record the operating condition and outdoor temperature at handover.
  4. Follow the slab supplier's instructions and DIN 4725-2 or local rules.

Applies to: Slab curing function (coding address F1)

Source: Vitotronic 200-H installation and service manual, p. 64. Written in our own words; check the manual for your exact model.

Record technical data at initial start-up

Boiler · Vitorond 200, VD2A

Values and calibrations in the Technical Data section must be recorded during the first start-up.

  1. Record the values and calibrations from the Technical Data section (page 38) at initial start-up.
  2. Explain the sequence of operation, combustion air needs, emergency shut-down, and the need for annual maintenance to the owner.

Applies to: Vitorond 200 VD2A boilers

Source: Vitorond 200 VD2A installation manual, p. 36. Written in our own words; check the manual for your exact model.

Red wire on Riello and Carlin burners

Boiler · Vitorond 100

The red wire is not used in this application.

  1. Use wire nuts to cap both ends of the red wire: inside the high limit control and at the Riello burner sub-base.

Applies to: Riello and Carlin burner wiring

Source: Vitorond 100 installation and service instructions, p. 32. Written in our own words; check the manual for your exact model.

Replacing the control printed circuit board

Boiler · Vitocontrol-S VD2/CT3/CM2

Before the board is swapped, the coding must be saved, because the new board needs its coding restored.

  1. Record all coding and adjustments made at the control unit.
  2. Replace the printed circuit board.
  3. Set coding 8A: 176.
  4. Set coding address 92 to 92: 160.

Applies to: Line voltage and low voltage motherboards

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 135. Written in our own words; check the manual for your exact model.

Replacing the electronics board

Boiler · Vitotronic 100

The electronics board holds the microprocessor and software. Codings must be saved before swapping the board.

  1. Write down all codings and settings on the control unit.
  2. Replace the electronics board.
  3. Set coding 8A: 176.
  4. Set coding address 92 (not in the overview) to 92: 160.

Applies to: Vitotronic 100 GC1 electronics board, Part 7828 193

Source: Vitotronic 100 GC1 installation and service instructions, p. 110. Written in our own words; check the manual for your exact model.

Required codes for installation

Boiler · Vitorond 200 VD2

Follow local codes first. Where none apply, use the codes listed in the manual for gas, oil, electrical and controls.

  1. For gas in Canada use CAN/CSA-B149.1 or .2; in the US use NFPA/ANSI Z223.1 (National Fuel Gas Code).
  2. For oil in Canada use CSA B-139; in the US use NFPA 31.
  3. For wiring in Canada use CSA C22.1 Part 1; in the US use NFPA 70 (NEC).
  4. Comply with ANSI/ASME CSD-1 where the authority having jurisdiction requires it.
  5. Use the latest editions of all codes.

Applies to: Installation

Source: Vitorond 200 VD2 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Required system type and expansion tank

Boiler · Vitocrossal 300 CA3B Dual Fuel

The boiler is only approved for closed loop hot water heating systems. The system needs a pre-charged membrane expansion tank.

  1. Install the boiler only in a closed loop hot water heating system.
  2. Make sure the system has a pre-charged membrane expansion tank.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 3. Written in our own words; check the manual for your exact model.

Resetting coding to factory condition

Boiler · Vitocrossal 300 CA3B Dual Fuel

Returning the coding to the factory condition also clears the LON participant number, so it must be set again.

  1. Note the current LON participant number before changing the coding.
  2. Set coding 77 back to the number needed for each boiler section (1, 2, 3 for sections 1 to 3).
  3. Check the other coding addresses against the factory column.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 80. Written in our own words; check the manual for your exact model.

Restart the start-up wizard after a setup error

Boiler · Vitodens 222-F

Use this after a setup error or after adding system components. Record existing settings first, because some may reset during the wizard.

  1. Press OK and menu together for about 4 seconds.
  2. Select Service Functions.
  3. Select Set-up Wizard.
  4. Select Yes.
  5. Press OK to restart the start-up wizard.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 14. Written in our own words; check the manual for your exact model.

Restarting after extended shut-down

Boiler · Vitorond 200, VD2A

Recondition the system before restarting after a long outage.

  1. Check cold fill pressure and make sure the system is properly vented.
  2. Set the automatic feed valve to the desired fill pressure.
  3. For oil burners, do not reset the burner flame safeguard control more than two times.
  4. If you smell gas, do not touch electrical switches or open flames, open windows, close gas valves, and call the gas supplier from another phone.

Applies to: Vitorond 200 VD2A boilers

Source: Vitorond 200 VD2A installation manual, p. 36. Written in our own words; check the manual for your exact model.

Return connection loading on Vitocrossal 300

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

The lower return connection must receive at least 15% of the boiler's rated output.

  1. Connect at least 15% of the rated output to the lower return connection.

Applies to: Vitocrossal 300 with two return connections (system versions 6 and 7)

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 21. Written in our own words; check the manual for your exact model.

Return water sensor for underfloor heating

Boiler · Vitotronic 300

In underfloor heating systems, the return water temperature sensor is used so the control can measure both supply and return water temperature.

  1. Install the return water temperature sensor on underfloor heating circuits.
  2. Confirm the control reads both supply and return temperature.

Applies to: Vitotronic 300 KW3 with underfloor heating

Source: Vitotronic 300 installation instructions, p. 5-8 (footnote 3). Written in our own words; check the manual for your exact model.

Return water temperature and flow limits with Vitotronic

Boiler · Vitorond 200 VD2A

With Vitotronic controls there is no minimum boiler return water temperature and no minimum heating water flow rate. A shunt pump or low temperature protection package is not needed.

Applies to: Vitorond 200 VD2A with Vitotronic control

Source: vitorond 200 VD2A technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Room sensor placement for RS function remote controls

Boiler · Vitotronic 300

Remote controls with room sensing must be placed where they read a representative room temperature. Remote controls without room sensing (WS function) can go anywhere in the building.

  1. Install the RS remote control on an inside wall of the main living area.
  2. Place it across from radiators, not on shelves, in niches, near doors, or near heat sources such as direct sunlight, fireplaces or TV.
  3. Use a separate room temperature sensor if the remote cannot be placed in a suitable spot.

Applies to: Vitotrol 200, Vitotrol 300, room temperature sensor

Source: Vitotronic 300 technical data manual, p. 5, p. 6. Written in our own words; check the manual for your exact model.

Room temperature sensor placement

Boiler · Vitocrossal 300 CU3A

Mount the room temperature sensor or remote control in the main living room on an internal wall opposite radiators. Keep it away from shelf units, recesses, doors, and heat sources such as direct sunlight, fireplaces, or TV sets.

  1. Select an internal wall in the main living room opposite radiators.
  2. Keep the sensor out of shelving, recesses, door areas, and direct heat sources.

Applies to: Room temperature sensor, Vitotrol 200A and 300A

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Technical Data Manual, p. 13-15. Written in our own words; check the manual for your exact model.

Room thermostat heat anticipator

Boiler · Vitorond 100

Set the heat anticipator in the room thermostat to match the power requirement of the connected equipment.

  1. Install the thermostat on an inside wall away from drafts, pipes, lighting, sun and fireplaces.
  2. Set the heat anticipator to the value given in the boiler wiring diagram for standard equipment.

Applies to: Room thermostat wiring

Source: Vitorond 100 installation and service instructions, p. 33. Written in our own words; check the manual for your exact model.

Room thermostat installation and heat anticipator

Boiler · Vitorond 100, VR1

Mount the thermostat on an inside wall away from drafts, hot or cold pipes, lights, TV, sun and fireplaces. If the thermostat has a heat anticipator, set it to match the load the boiler wiring diagram gives.

Applies to: Room thermostat wiring

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

Rotary dial address

Boiler · Versatronik 511 / 511D

The rotary dial sets LON addressing when several gateways are used. Leave it at the factory default of 0 unless a multi-gateway system needs a different setting to avoid duplicate LON addresses.

  1. Leave the rotary dial at 0 for a single gateway.
  2. Set unique dial values only on systems with multiple 511 gateways.

Applies to: Versatronik 511 and 511D

Source: Versatronik 511 & 511D LON Type B manual, p. 7. Written in our own words; check the manual for your exact model.

Route and secure field connecting cables

Boiler · Vitodens 200-W B2HB

Keep connecting cables away from hot components, since contact will damage them. Do not exceed the maximum permissible cable temperature. A larger cable (up to 9/16 in.) needs the existing cable grommet removed. Secure the power cable with the grommet seated in the lower orange casing section.

  1. Touch a grounded metal object such as a pipe before handling the electronic modules.
  2. Remove the existing cable grommet if using a larger cable, up to 9/16 in.
  3. Route all connecting cables to their areas (low voltage, 120 V, communication module, DHW sensor plugs).
  4. Secure the cables to the control base using the existing strain reliefs.

Applies to: Vitodens 200-W B2HB 19, 26, 35, 68, 94, 125

Source: Vitodens 200-W B2HB installation manual, p. 24. Written in our own words; check the manual for your exact model.

Route LON and low-voltage wiring away from mains

Boiler · Versatronik 511 / 511D

Electromagnetic interference can couple onto long wire runs. Keep LON wiring away from 120/240VAC conductors. If that is not possible, use stranded twisted-pair shielded wire and ground only one end of the shield.

  1. Keep LON wires clear of 120/240VAC conductors.
  2. If they must run close, use stranded twisted-pair shielded cable.
  3. Ground only one end of the shield.

Applies to: Versatronik 511 and 511D LON wiring

Source: Versatronik 511 & 511D LON Type B manual, p. 5; p. 6. Written in our own words; check the manual for your exact model.

Route wiring away from high voltage

Boiler · Versatronik 515, Versatronik 515D

Extended wiring can pick up electromagnetic interference. Keep it away from 120/240VAC conductors. If that is not possible, use stranded twisted-pair shielded wire and ground only one end of the shield.

  1. Keep low-voltage wiring clear of 120/240VAC conductors.
  2. If proximity cannot be avoided, use stranded twisted-pair shielded wire.
  3. Ground only one end of the shield.

Applies to: Versatronik 515 and 515D gateways

Source: Versatronik 515 BACnet IP Type B manual, p. 5. Written in our own words; check the manual for your exact model.

Save and activate gateway configuration

Boiler · Versatronik 585

Changes are not used until the configuration is activated. The gateway reboots after you save.

  1. Press SAVE on every configuration screen where you made changes.
  2. Go to the Activate Configuration screen and confirm.
  3. When asked, choose SAVE to store the new settings. The gateway then reboots automatically.
  4. Write down every change you make. The configuration pages can be reached at 192.168.88.89 and at the address you selected.

Applies to: Versatronik 585 VI/BACIP

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 14. Written in our own words; check the manual for your exact model.

Select heating circuit before adjusting

Boiler · Vitotronic 300-K

Heating circuit settings apply to the circuit selected on the control, so the correct circuit must be chosen first.

  1. Select the corresponding heating circuit before making any adjustment.

Applies to: Vitotronic 300-K heating circuits

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 29. Written in our own words; check the manual for your exact model.

Select the boiler sequence

Boiler · Vitotronic 300-K MW1S

Set the lead boiler and the boiler sequence in a cascade system.

  1. In coding 2, if required, set coding addresses 39 (permanent lead boiler) and 3A (permanent last boiler).
  2. Press the two buttons shown together for about two seconds.
  3. Select the boiler sequence with the arrow buttons. Pressing both buttons together exits without saving.
  4. Press OK to save the sequence.
  5. In coding 2, set coding addresses 38, 41, 42, 43 and 44 as described in the function description.

Applies to: Vitotronic 300-K MW1S cascade

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 81. Written in our own words; check the manual for your exact model.

Selecting the boiler sequence

Boiler · Vitocontrol-S VD2/CT3

Sets the boiler sequence on the Vitocontrol-S. Lead and last boiler are set in coding 2.

  1. If required, set coding 2 addresses 39 (permanent lead boiler) and 3A (permanent last boiler).
  2. Press the two buttons shown together for about 2 seconds.
  3. Select the boiler sequence with the up or down button. Press both buttons together to exit without saving.
  4. Press the button shown. The adjustment is transferred.
  5. In coding 2, set addresses 38, 41, 42, 43 and 44 (see function description from page 168).

Applies to: Vitocontrol-S VD2/CT3

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 99. Written in our own words; check the manual for your exact model.

Sensor capillaries and cable routing

Boiler · Vitorond 100

Sensor capillaries must not be kinked, or the sensors will not work properly. Cables and capillaries must not sit directly on the cast iron heat exchanger.

  1. Keep sensor capillaries straight and unkinked.
  2. Route all cables and capillaries between the nylon-backed insulation and the metal enclosure panels.
  3. Coil any excess cabling and tuck it between the side panel and the insulation.
  4. Tighten the strain reliefs.

Applies to: Vitotronic control installation

Source: Vitorond 100 installation and service instructions, p. 34. Written in our own words; check the manual for your exact model.

Sensor setup at power-up

Boiler · Versatronik 200

The start-up level for setting the installed sensors shows once after power-on and can be called again by briefly switching the supply off.

  1. Switch the supply voltage off briefly to show the sensor setup level again.
  2. Confirm the installed sensor types before running the system.

Applies to: Versatronik 200 controller

Source: Versatronik 200 installation and operating manual, p. 163. Written in our own words; check the manual for your exact model.

Sensor type selection (1 kOhm or 5 kOhm)

Boiler · Versatronik 200

Sensors are set to 1 kOhm or 5 kOhm depending on the programming and system selection.

  1. Select the sensor type that matches the programming and system selection.

Applies to: Versatronik 200 System Control

Source: Versatronik 200 Installation and Operating Manual, p. 120. Written in our own words; check the manual for your exact model.

Service access clearance

Boiler · Vitorond 100

Leave enough room in front of the boiler for cleaning and service. The recommended minimum clearance values are shown in a drawing that does not come through in the text.

  1. Keep at least the minimum service access for cleaning and service.
  2. In an alcove, keep 24 in. (610 mm) free for burner service.
  3. Check the drawing for the recommended minimum service clearances.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 12. Written in our own words; check the manual for your exact model.

Service clearances

Boiler · Vitodens 200-W B2HA

Zero-clearance to combustibles applies when the boiler is vented with a listed special venting system or CPVC/PP vent. Recommended service clearance is 12 in. (305 mm) on the side, mainly to view the rating plate and fit the PRV kit. Closet and alcove installation is approved. Keep gas ignition components protected from water spray or splashing.

  1. Check the venting system instructions before setting clearances.
  2. Leave 12 in. (305 mm) on the side for rating plate access and the PRV kit.
  3. If the PRV is turned 90° forward with an extension, the side clearance can be reduced; the exact reduced value is not legible in this copy.
  4. Protect gas ignition components from water during operation and service.

Applies to: Vitodens 200-W B2HA 45, 60 clearances

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 10. Written in our own words; check the manual for your exact model.

Set a static IP address for LAN

Boiler · Vitocrossal 200 CI2

The LAN must be connected to the internet for internet access to work.

  1. Open Settings, then 'LAN'.
  2. Select 'Network type'.
  3. Select 'STATIC'.
  4. Confirm.
  5. Enter the IP address, subnet mask, standard gateway, primary DNS server and secondary DNS server.
  6. Confirm.

Applies to: LAN connection

Source: Vitocrossal 200 CI2 operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Set a static IP address for WiFi

Boiler · Vitocrossal 200 CI2

Only needed when the WiFi router does not assign addresses automatically. The router must be set so that addresses are not automatically assigned.

  1. Open Settings, then 'Internet', then 'WiFi'.
  2. Select the network from the available list.
  3. Select network type 'STATIC'.
  4. Confirm.
  5. Enter the IP address, subnet mask, standard gateway, primary DNS server and secondary DNS server.
  6. Confirm.

Applies to: WiFi connection

Source: Vitocrossal 200 CI2 operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Set a unique BACnet Device ID and IP address

Boiler · Versatronik 585

Each device needs a unique BACnet Device ID on the whole network. Do not give the gateway an IP address that is already in use.

  1. Open the BACnet Device Settings screen.
  2. Enter a Device ID that is not used anywhere else on the BACnet network.
  3. Set the gateway IP address to a free address on your network.
  4. Press SAVE and then activate the configuration.

Applies to: Versatronik 585 VI/BACIP

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 14. Written in our own words; check the manual for your exact model.

Set BACnet device ID and IP before joining the network

Boiler · Versatronik 300 Cascade Control

Applies only to unit 704092 with BACnet/IP. The BACnet Device ID must be unique across the entire BACnet internetwork. Changes do not take effect until Activate Configuration is confirmed.

  1. Connect the Ethernet cable to the BACnet port closest to the middle of the control.
  2. Connect the computer directly to the BACnet port with no other devices attached.
  3. Set the computer to DHCP, or set its IP to 192.168.88.90 with mask 255.255.255.0.
  4. Cycle power on the Versatronik 300.
  5. Browse to http://192.168.88.89/admin and log in.
  6. Change the default password in the Change Password screen if required.
  7. Set the BACnet device settings, pressing SAVE on each screen.
  8. Confirm Activate Configuration and save to reboot.
  9. Write down any changes made, since they are required later.

Applies to: Versatronik 300 unit 704092 with BACnet/IP

Source: Versatronik 300 Cascade Control V1.4 manual, p. 19-21. Written in our own words; check the manual for your exact model.

Set DHW temperature range before adjusting

Boiler · Vitotronic 200

The DHW setpoint is 50 to 140 F / 10 to 60 C by default. Coding 56:1 extends it to 50 to 203 F / 10 to 95 C. Observe the maximum DHW temperature and adjust the high limit before raising the range.

  1. Check the maximum allowed domestic hot water temperature.
  2. Set coding 56:1 only if a higher range is needed.
  3. Adjust the adjustable high limit to match.

Applies to: DHW temperature setpoint, coding 56

Source: Vitotronic 200 KW2 service instructions, p. 53, p. 55. Written in our own words; check the manual for your exact model.

Set high altitude operation

Boiler · Vitodens 200-W B2HB

Altitude setting uses coding address 93 in coding level 2, General.

  1. Set coding address 11 to 9 to unlock coding 93.
  2. Set 93:0 for altitudes up to 5,000 ft (1,500 m).
  3. Set 93:6 for altitudes from 5,000 ft to 10,000 ft (1,500 m to 3,000 m).
  4. After setting 93, set coding address 11 to 0.
  5. Do not set or use 93:1 to 93:5.
  6. The high altitude program turns off automatically after 20 minutes.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 19. Written in our own words; check the manual for your exact model.

Set high limit to match safety equipment

Boiler · Vitotronic 300

Settings for fixed high limit and other values depend on the safety equipment installed per applicable codes.

  1. Confirm installed safety equipment before setting the fixed and adjustable high limits.
  2. Use the table values for the boiler type.

Applies to: All external control setups

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 40, 42, 44. Written in our own words; check the manual for your exact model.

Set the boiler sequence

Boiler · Vitotronic 300-K

The control offers several boiler sequences, depending on the coding and internal calculations. Changing the sequence helps the boilers run evenly. The legend shows the start order (A) and the permanently assigned boiler numbers (B). The example shows boilers started in the order 4, 3, 2, 1, 8.

  1. From the home screen, select 'Boiler sequence'.
  2. Select 'New boiler sequence' and choose the required sequence.

Applies to: Vitotronic 300-K, MW2C

Source: Vitotronic 300-K, MW2C operating instructions, p. 21. Written in our own words; check the manual for your exact model.

Set the display language

Boiler · Versatronik COMO OT

The language prompt appears only the first time the cover is opened after power-up. It appears again if the unit is removed from its base.

  1. Open the flap; the display shows ENGLISH.
  2. Press E to change the mode, then use Plus/Minus to choose the language.
  3. Press Save to store it and move to USER SETTING.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 32. Written in our own words; check the manual for your exact model.

Set the rotary dial on the 2-wire BUS communication module

Boiler · Vitotronic 200-H

The control connects to the Viessmann 2-wire BUS through a plug-in communication module. Its rotary dial sets the system version and must be unique on the bus. Position 4 is the default when a mixing valve actuator kit is used on a wall-mounted boiler, so do not duplicate it when adding a second Vitotronic 200-H.

  1. Plug the 2-wire BUS communication module into the control unit (accessory, see parts list).
  2. Set the rotary dial on the module to a system version between 4 and C.
  3. Make sure no other control unit on the bus uses the same rotary dial position.
  4. On a wall-mounted boiler with one mixing valve actuator kit, the default position is 4; when adding another Vitotronic 200-H, pick a position other than 4.
  5. If a boiler control unit for wall-mounted boilers or a Dekamatik system is connected, adjust the differential temperature at that control unit.

Applies to: Vitotronic 200-H with 2-wire BUS communication module

Source: Vitotronic 200-H installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Set the time and weekday

Boiler · Versatronik COMO OT

Time and day are set in the Time-Day level. Time changes in steps of 15 minutes, starting from :00, :15, :30 or :45.

  1. Open the cover so USER shows, then press Plus twice to reach TIME-DAY.
  2. Press Prog to show TIME and E, then use Plus/Minus to set the time. Hold the key to scroll faster.
  3. Press Prog to show DAY and E, then use Plus/Minus to set the weekday.
  4. Press Prog to save and return to TIME-DAY.
  5. Close the cover.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT manual, p. 24. Written in our own words; check the manual for your exact model.

Set time and date (300-K only)

Boiler · Vitotronic 200 and 300-K

Time and date are factory set. After the system has been shut down for a long time, check and reset them.

  1. Open the extended menu.
  2. Select "Settings", then "Time/Date".
  3. Set the time and date.

Applies to: Vitotronic 300-K

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 27. Written in our own words; check the manual for your exact model.

Set up Vitotronic 200 for coding in cascade mode

Boiler · Vitotronic 200

Put the boiler in cascade mode before coding a Vitotronic 200. The button names are missing from the text, so use the boiler's control keys as shown on the display.

  1. Press the menu key and OK together for about 4 seconds.
  2. Scroll to 'service' and select it with OK.
  3. Scroll to 'service functions' and select it with OK.
  4. Scroll to 'multi-boiler system' and select it with OK.
  5. When finished, press the exit key to leave.

Applies to: Vitotronic 200 on a multi-boiler (cascade) system

Source: Vitotronic 200 and 300-K installation and service instructions, p. 44. Written in our own words; check the manual for your exact model.

Set Vitodens WB2B coding 00 to 00

Boiler · Versatronik 300 Cascade Control

Coding 00 cannot be set to 0 directly. The Vitodens boiler pump keeps running unless this is done correctly.

  1. Temporarily change coding 01 to 2 (multi-boiler). Listen for the click.
  2. Change coding 01 back to 1.
  3. Set address 34 to 23.
  4. Confirm coding 00 now reads 00.

Applies to: Vitodens 200 WB2B with Vitotronic 100 HC1

Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 15. Written in our own words; check the manual for your exact model.

Setting the altitude parameter

Boiler · Vitodens 200-W B2HB

The factory default is set for altitudes up to 5,000 ft (1,500 m). For other altitudes, change the altitude using coding address 93 in coding level 2 (General).

  1. Enter coding level 2 (General).
  2. Set coding address 93 to the site altitude.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 25. Written in our own words; check the manual for your exact model.

Setting the DIP switch for a separate room temperature sensor

Boiler · Vitotronic 200-H

When a separate room temperature sensor is connected, the matching DIP switch on the remote control PCB must be turned on. The switch differs between the two remotes.

  1. On Vitotrol 200, set DIP switch S6.3 to ON.
  2. On Vitotrol 300, set DIP switch S3.3 to ON.

Applies to: Vitotrol 200 and Vitotrol 300 remote controls

Source: Vitotronic 200-H installation and service instructions, p. 44 and p. 46. Written in our own words; check the manual for your exact model.

Setting values during start-up

Boiler · Versatronik 200

Each start-up screen shows the current value. Change it with the rotary knob, then confirm. Values follow the system selection; the Standard setting applies to the function screens.

  1. Open the start-up screen for the item (for example Boiler 1 type or Tank type).
  2. Turn the rotary knob to select the value that matches the system.
  3. Press OK to save, or Back to leave without changing it.
  4. Work through the screens in order so no value is skipped.

Applies to: Versatronik 200 start-up screens

Source: Versatronik 200 installation and operating manual, p. 104. Written in our own words; check the manual for your exact model.

Shunt pump sizing for return temperature raising

Boiler · Vitotronic 300 GW2

The shunt pump must be sized so that the bypassed water is about 30% of the boiler's total flow rate.

  1. Size the shunt pump so bypassed flow is approx. 30% of total boiler flow.
  2. Confirm the sensor T2 switches the shunt pump on when return temperature falls below the minimum.

Applies to: System type 2, single-boiler with shunt pump and return valve (modulating boiler)

Source: Vitotronic 300 GW2 installation and service instructions, p. 11. Written in our own words; check the manual for your exact model.

Side wall coaxial vent and common venting

Boiler · Vitodens 222-F

Do not common-vent this boiler with another appliance. A side wall coaxial vent must use the Viessmann protective screen and must not exceed the maximum equivalent length.

  1. Check the equivalent vent length against the Venting System Installation Instructions.
  2. Confirm the Viessmann protective screen is fitted to the side wall coaxial vent.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 108. Written in our own words; check the manual for your exact model.

Side wall coaxial vent installation requirements

Boiler · Vitodens 200-W

Do not exceed the maximum equivalent vent length in the Vitodens 200-W B2HB Venting System Installation Instructions. A Viessmann protective screen must be fitted on side wall coaxial vent installations.

  1. Check the equivalent length against the venting Installation Instructions before finalizing the run.
  2. Fit the Viessmann protective screen on the side wall coaxial vent.

Applies to: B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service, p. 100. Written in our own words; check the manual for your exact model.

Side wall vent termination

Boiler · Vitocrossal 300 CA3B Dual Fuel

Side wall vents use a termination elbow with screen. Exhaust and air intake piping outside must be UV resistant PP(s) when PP(s) is used. Snow level and grade heights apply.

  1. Fit a protective screen on the termination.
  2. Keep the exhaust terminal at least 12 in (305 mm) above grade or the expected snow level.
  3. Keep the intake terminal at least 12 in (305 mm) above grade or expected snow level.
  4. Use UV resistant polypropylene for exposed exhaust and intake piping on PP(s) systems.
  5. Caulk gaps around the vent and seal any penetrations.

Applies to: Side wall venting

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 55-56. Written in our own words; check the manual for your exact model.

Simplified coaxial vent leak test

Boiler · Vitodens 200-W B2HA

Check the air intake coaxial gap for leaks during start-up by measuring the combustion air. The vent is acceptable if CO2 is 0.2% or lower, or O2 is 20.6% or higher. If the readings are worse, check the venting system thoroughly.

  1. Use the two measurement ports on the vent pipe adaptor (one for air intake, one for flue gas).
  2. Measure CO2 in the combustion air in the coaxial gap of the air intake pipe.
  3. If CO2 is above 0.2% or O2 is below 20.6%, check the whole venting system for leaks.

Applies to: Vitodens 200-W B2HA, all sizes

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.

Simplified leak test on coaxial flue (annular gap)

Boiler · Vitodens 100-W B1HE/B1KE

Recommended during start-up for sealed-combustion coaxial vent only. Measure CO2 in the combustion air in the annular gap of the air intake pipe. Venting is considered tight if CO2 is 0.2% or lower, or O2 is 20.6% or higher. If readings are worse, check the venting system thoroughly. Not applicable to single-wall venting.

  1. Measure CO2 (or O2) in the air intake annular gap using the test port on the vent adaptor.
  2. Accept if CO2 is 0.2% or lower, or O2 is 20.6% or higher.
  3. If not, inspect the full venting system.
  4. Re-seal the test port with its plug after the test, otherwise room air is drawn in.

Applies to: Coaxial sealed-combustion venting

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 49. Written in our own words; check the manual for your exact model.

Slab curing function profiles

Boiler · Vitotronic 300-K MW1S

The slab curing function has four supply-temperature profiles over 30 days, selected with coding F1 (values 1 to 4). Profile curves are graphs only; no numeric table is printed.

  1. Set coding F1 to the profile needed (1, 2, 3 or 4). Coding is covered on the previous page (167).
  2. Check the supply temperature against the profile curve for the day of curing.
  3. Use the back-of-manual conversion chart if the temperature is needed in °F.

Applies to: Vitotronic 300-K MW1S slab curing function

Source: Vitotronic 300-K MW1S installation and service manual, p. 168. Written in our own words; check the manual for your exact model.

Solar multifunction conflict

Boiler · Versatronik 200

If an MF solar function (07, 08, 09, 23, 27, 28 or 29) is active, no other external solar controller may be connected to the system.

  1. Before enabling an MF solar function, confirm no external solar controller is connected.
  2. Set F15 to 5 where the storage 3 switch-over functions (08, 09) are used.

Applies to: Versatronik 200 controller, solar MF functions

Source: Versatronik 200 installation and operating manual, p. 110. Written in our own words; check the manual for your exact model.

Spring-loaded flow check valves during system fill

Boiler · Vitorond 200, VD2A

Flow check valves must be open to fill and purge the system and closed again once it is purged.

  1. Open the spring-loaded flow check valves before filling the heating system.
  2. After the system is full and purged of air, close the flow check valves to restore flow-check operation.

Applies to: Vitorond 200 VD2A hydronic installations

Source: Vitorond 200 VD2A installation manual, p. 34. Written in our own words; check the manual for your exact model.

Stainless vent and vacuum relief damper

Boiler · Vitocrossal 300 CA3B Dual Fuel

Stainless vent must be UL/ULC listed for Category IV. Where a sealed vertical vent is used, a vacuum relief damper may be needed for the rare case of a sudden burner interruption at full firing, such as a power failure.

  1. Check the single-wall vent parts were ordered and supplied correctly before installation.
  2. Fit a starter stainless adaptor at the boiler vent connection if needed. It is supplied by others.
  3. Check whether a vacuum relief damper is required for sealed vertical venting and install it per its own instructions.
  4. Seal gaps between the vent or air intake pipe and the wall with approved sealant or caulk.

Applies to: Stainless steel venting

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 52. Written in our own words; check the manual for your exact model.

Standard equipment and wall mounting

Boiler · Vitodens 100-W B1HE/B1KE

The boiler ships fully piped and pre-wired with a 30 psig relief valve, air vent, pressure gauge, two fill/drain valves, mounting bracket and hardware, and the outdoor sensor. B1KE adds a DHW relief valve and B1HE adds a DHW tank sensor. Mounting screws are supplied for wood studs (2x4), metal studs and brick or concrete walls.

  1. Select the mounting screws that suit the wall type.
  2. Mount the bracket and boiler using supplied hardware.
  3. Connect all pipes at the bottom of the boiler.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE technical data manual, p. 19. Written in our own words; check the manual for your exact model.

Start-up must be done by a licensed heating contractor

Boiler · Vitodens 200-W

Initial start-up and any adjustment, service or maintenance must be done by a licensed professional heating contractor. Complete the Maintenance Record in the service instructions.

  1. Complete the Maintenance Record at initial start-up.
  2. Show the system operator the system operation, shutdown and emergency shutdown.

Applies to: All Vitodens 200-W B2HB models

Source: Vitodens 200-W B2HB Service Instructions, p. 7. Written in our own words; check the manual for your exact model.

Start-up of Weishaupt burner boilers

Boiler · Vitorond 200 VD2A

Vitorond 200 VD2A boilers with Weishaupt burners require start-up by Viessmann. Ask Viessmann for the start-up prerequisites.

  1. Arrange boiler and burner start-up through Viessmann.
  2. Ask Viessmann for the required start-up prerequisites before scheduling.

Applies to: Vitorond 200 VD2A boilers with Weishaupt burners

Source: Vitorond 200 VD2A technical data manual, p. 25. Written in our own words; check the manual for your exact model.

Start-up precautions

Boiler · Vitorond 100

Several conditions must be met before the burner is started.

  1. Keep the fresh air intake of the boiler room open.
  2. Confirm the chimney and all flue pipes are connected, sealed and unobstructed.
  3. Do not start the burner unless the combustion chamber door is secured.
  4. Do not attempt to start the burner with excess oil accumulated, when the unit is full of vapor, or when the chamber is very hot.
  5. Do not fire the boiler without water.
  6. Do not use gasoline, crankcase drainings or oil containing gasoline.
  7. Do not leave tools inside the combustion chamber.

Applies to: Vitorond 100 oil-fired boiler

Source: Vitorond 100 installation and service instructions, p. 39-40. Written in our own words; check the manual for your exact model.

Start-up programming sequence

Boiler · Versatronik 200

Applies to the start-up of the cascade system examples shown on these pages.

  1. Finish all wiring checks and make sure every connection is made before powering the control on.
  2. Power the control on. The start-up screen appears on the display.
  3. Press the button next to OK to enter the start-up sequence.
  4. Enter the values with the rotary dial and function keys.
  5. Use the programming table for the chosen system example. The variables shown depend on the system selection.

Applies to: System Examples 02, 03 and 04

Source: Versatronik 200 installation and operating manual, p. 26, 29, 32. Written in our own words; check the manual for your exact model.

Start-up sequence

Boiler · Versatronik 200

Complete all wiring checks before applying power. The start-up screen appears when the control is powered on.

  1. Complete all necessary connections before powering the control ON.
  2. Once the initial wiring checks are complete, power the control ON.
  3. When the start-up screen appears, press the button next to OK to enter the start-up sequence.
  4. Enter the required values using the rotary dial and function keys.
  5. Use the start-up programming table for the required values.

Applies to: Versatronik 200 System Control

Source: Versatronik 200 installation and operating manual, p. 23. Written in our own words; check the manual for your exact model.

Start-up sequence on the Versatronik 200 control

Boiler · Versatronik 200

The start-up screen is entered from the OK prompt. The values shown depend on the system selection, so use the table that matches the installed system example.

  1. Finish all initial wiring checks before powering the control on.
  2. Power the control on. The start-up screen appears.
  3. Press the button next to OK to enter the start-up sequence.
  4. Enter the required values with the rotary dial and the function keys.
  5. Check each value against the programming table for the system example.

Applies to: System examples 07, 08 and 09

Source: Versatronik 200 installation and operating manual, p. 41. Written in our own words; check the manual for your exact model.

Start-up with lime-risk water

Boiler · Vitocrossal 300 CA3B

If the system is not filled with fully softened water, reduce the risk of scale build-up during start-up.

  1. Start the system step by step with high heating water flow, beginning at the lowest boiler output.
  2. In multiple-boiler systems, start all boilers at the same time.
  3. Treat the first fill (and any later top-up or repair fill) before start-up where water treatment is required.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 13. Written in our own words; check the manual for your exact model.

Suitable system type

Boiler · Vitocrossal 300 CU3A

This boiler is only suitable for fully pumped hot water heating systems.

  1. Confirm the system is fully pumped before installing.
  2. Do not use this boiler on gravity or non-pumped hot water systems.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 Technical Data Manual, p. 8. Written in our own words; check the manual for your exact model.

Supply check valve for common boiler return

Boiler · Vitotronic 300

A supply check valve is required only when the piping connects to one common boiler return.

  1. Install a supply check valve if the system piping ties into one common boiler return.

Applies to: Vitotronic 300 KW3 with mixing valve circuits

Source: Vitotronic 300 installation instructions, p. 5-8 (footnote 1). Written in our own words; check the manual for your exact model.

Supply/return bypass for large water content systems

Boiler · Vitorond 100

Systems with volume above about 1 US gal per 13,000 Btu/h of boiler input (for example older gravity systems with large free-standing radiators) need a bypass from supply to return to prevent flue gas condensation in the heat exchanger and vent. Viessmann strongly recommends a bypass on all cast iron boilers.

  1. Check the system water volume against the boiler input.
  2. If the system is large, install a bypass pipe from the supply pipe to the return pipe.
  3. Install a bypass on any system as a preventive measure, as Viessmann recommends for all cast iron boilers.

Applies to: Vitorond 100 boilers on large water content systems

Source: Viessmann Vitorond 100 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.

System Example 05 system overview (cascade, modulating boilers)

Boiler · Versatronik 200

Cascade controller layout for modulating boilers with no domestic hot water and no space heating control.

  1. Communicate with OpenTherm-enabled boilers 1 through 8 over the CAN bus.
  2. Boiler set point comes from the heating system manager. Each boiler modulates its burners to reach it.
  3. Use outdoor reset with an outdoor sensor and a common supply sensor.
  4. Use a low loss header or hydraulic separator.
  5. No DHW production and no DHW recirculation pump.
  6. No space heating control.
  7. Each boiler pump is driven from the boiler pump output; see the boiler manual.

Applies to: Versatronik 200, System Example 05

Source: Versatronik 200 installation and operating manual, p. 33. Written in our own words; check the manual for your exact model.

System Example 06 system overview (cascade, modulating boilers with DHW)

Boiler · Versatronik 200

Cascade controller layout for modulating boilers that also produces domestic hot water.

  1. Communicate with OpenTherm-enabled boilers 1 through 8 over the CAN bus.
  2. Boiler set point comes from the heating system manager. Each boiler modulates its burners to reach it.
  3. Use outdoor reset with an outdoor sensor and a common supply sensor.
  4. Use a low loss header or hydraulic separator.
  5. DHW production is enabled, with DHW recirculation pump operation.
  6. No space heating control.
  7. Each boiler pump is driven from the boiler pump output; see the boiler manual.

Applies to: Versatronik 200, System Example 06

Source: Versatronik 200 installation and operating manual, p. 36. Written in our own words; check the manual for your exact model.

System Example 07 system overview (cascade, modulating boilers)

Boiler · Versatronik 200

Cascade controller layout for modulating boilers with no domestic hot water and no space heating control. The common supply pump is run from the heating system manager.

  1. Communicate with OpenTherm-enabled boilers 1 through 8 over the CAN bus.
  2. Boiler set point comes from the heating system manager. Each boiler modulates its burners to reach it.
  3. Use outdoor reset with an outdoor sensor and a common supply sensor.
  4. Use a low loss header or hydraulic separator.
  5. No DHW production and no DHW recirculation pump.
  6. No space heating control.
  7. The common supply pump is controlled and connected to the heating system manager.

Applies to: Versatronik 200, System Example 07

Source: Versatronik 200 installation and operating manual, p. 39. Written in our own words; check the manual for your exact model.

System Example 11: boiler set by 0-10 V signal

Boiler · Versatronik 200

Boiler flow temperature is set by a 0-10 V signal from a heating system manager. The controller uses outdoor reset. Primary side LLH/hydraulic separator pump runs on multifunction relay 3. DHW is taken from the secondary side supply/return header and the DHW recirc pump runs on multifunction relay 4. Heating circuits 1 and 2 run through mixing valves. Lago remotes for both mixing valves are optional.

  1. Wire the 0-10 V boiler control and set the system selection to 03 (see example 11 settings).
  2. Connect outdoor, DHW and supply sensors as listed in the example 11 wiring table.
  3. Set multifunction relays 3 and 4 for the LLH pump and DHW recirc pump.

Applies to: System Example 11 (0-10 V controller)

Source: Versatronik 200 installation and operating manual, p. 48. Written in our own words; check the manual for your exact model.

System Example 12: two single-stage boilers, lead/lag

Boiler · Versatronik 200

Two single-stage boilers, each with its own boiler pump, run in lead/lag operation. The controller uses outdoor reset. DHW is taken from the supply/return header. Heating circuits 1 and 2 run through mixing valves. No DHW recirculation.

  1. Wire the burner call and boiler pump outputs as in the example 12 wiring table.
  2. Set system selection to 05 and boiler 1 type to 04 (see example 12 settings).

Applies to: System Example 12 (two single-stage boilers switching)

Source: Versatronik 200 installation and operating manual, p. 52. Written in our own words; check the manual for your exact model.

System layout 10: multiple boilers (up to eight) with a low-loss header

Boiler · Vitodens 200-W B2HB

Piping example for up to eight Vitodens 200-W B2HB boilers with mixing valve circuits and a low-loss header. This is a conceptual drawing only. Piping and components must be verified in the field, and the heating contractor is responsible for proper installation and function. WARNING: If a DHW tank other than a Viessmann Vitocell 100 or 300 is used, verify operation of the Viessmann DHW tank sensor with the tank maker. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. Use the applicable multiple Vitodens technical documentation for the design.
  2. Install a low water cut-off where local codes require it.
  3. Verify the DHW tank temperature sensor with the original tank manufacturer if the tank is not a Vitocell 100 or 300.
  4. Install a temperature tempering valve in the DHW supply line.
  5. Contact the local Viessmann sales representative for further help.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 42. Written in our own words; check the manual for your exact model.

System layout 8: DHW tank, low-loss header and three zone circuits

Boiler · Vitodens 200-W B2HB

Layout for Vitodens 200-W B2HA/B2HB with a DHW storage tank, a low-loss header and three zone circuits. A low-loss header is strongly recommended and is sold as an accessory.

  1. Wire the boiler pump to output 20 and the DHW pump to output 21.
  2. Wire zone circuit 1 to output 157 on the boiler.
  3. Wire zone circuits 2 and 3 to outputs A1 and A2 on the AM1 extension module (accessory).
  4. Connect the thermostats for zone circuits 1, 2 and 3 as dry contacts.
  5. Connect the outdoor sensor, DHW sensor and supply temperature sensor as shown in the layout.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 40. Written in our own words; check the manual for your exact model.

System layout 9: multiple mixing valve circuits with one direct circuit

Boiler · Vitodens 200-W B2HB

Layout with a DHW storage tank, low-loss header, several heating circuits with mixing valves and one heating circuit without a mixing valve. Design work for this layout goes through the local Viessmann sales representative.

  1. Install the expansion tank in the location shown in the drawing.
  2. Pipe pumps C and K so they pump into the boiler, as illustrated.
  3. Use the Vitotronic 200-H HK1B with LON communication module instead of the accessory kit and Vitocontrol if the design calls for it.
  4. Set the function of heating circuit pump 28/20 through coding address 53.
  5. Contact the local Viessmann sales representative for design help and details on the layout.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 41. Written in our own words; check the manual for your exact model.

System separation for underfloor heating

Boiler · Vitocrossal 300 CU3A

Underfloor systems with non-oxygen diffusion barrier tubing need system separation.

  1. Install system separation (plate heat exchanger or equivalent) between boiler and underfloor circuit.
  2. Use corrosion-resistant materials for all components on the secondary side of the heat exchanger.

Applies to: Vitocrossal 300 CU3A underfloor heating

Source: Vitocrossal 300 CU3A technical data manual, p. 21 and 22. Written in our own words; check the manual for your exact model.

System separation with plate heat exchanger

Boiler · Vitodens 200-W B2HA

Underfloor systems using non-oxygen diffusion barrier tubing need system separation. Components on the secondary side must be corrosion resistant. The plate heat exchanger's secondary pressure drop must be less than or equal to the mixing valve's pressure drop.

  1. Fit a plate heat exchanger where non-oxygen diffusion barrier tubing is used.
  2. Use corrosion-resistant materials for all components on the secondary side.
  3. Size the plate heat exchanger so its secondary pressure drop is at or below the 3-way mixing valve's pressure drop.

Applies to: Vitodens 200-W B2HA 45, 60 system separation layouts

Source: Vitodens 200-W B2HA 45, 60 installation manual, pp. 35, 39. Written in our own words; check the manual for your exact model.

Take CO2 readings before and after gas work

Boiler · Vitodens 200-W B2HB

Combustion analysis must be taken before and after work on gas appliances. Record values in the order listed in the Maintenance Record.

  1. Measure CO2 before starting work.
  2. Measure CO2 again after work is complete.
  3. Record the values on page 101 in the stated sequence.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 22. Written in our own words; check the manual for your exact model.

Tank sensor or aquastat connection (B1HE)

Boiler · Vitodens 100-W

On the B1HE, connect the tank temperature sensor to terminals 3 and 4. A temperature switch (aquastat) can be used instead.

  1. Connect the tank temperature sensor to terminals 3 and 4 on the wiring panel.
  2. Alternatively connect a temperature switch (aquastat) to the same terminals.

Applies to: Vitodens 100-W B1HE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 26. Written in our own words; check the manual for your exact model.

Tools and literature to have on site

Boiler · Vitocrossal 200 CM2

Service tools and literature referenced in the manual.

  1. Bring flathead and Phillips screwdrivers, pipe wrenches, open-ended wrenches, hex keys, pipe sealant and a flashlight.
  2. Bring approved leak detection fluid for natural gas and propane.
  3. Bring a plastic hand brush, cleaning brush, vacuum and clean rags.
  4. Bring a flue gas analyzer, multimeter, gas pressure gauge, CO meter, stack thermometer and efficiency calculator.
  5. Have the installation, service and operating instructions, plus the burner and boiler control literature.

Applies to: All Vitocrossal 200 CM2 units

Source: Vitocrossal 200 CM2 service instructions, p. 3. Written in our own words; check the manual for your exact model.

Torque boiler door screws

Boiler · Vitocrossal 200 CM2

Tighten the boiler door screws evenly to the specified torque.

  1. Tighten the boiler door screws evenly across the door to about 13 lb.ft (18 Nm).

Applies to: Vitocrossal 200 CM2 186 to 311

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 20. Written in our own words; check the manual for your exact model.

Underfloor heating mixing circuit must be M1 with supply and return sensors

Boiler · Vitotronic 200-H

If the underfloor heating is controlled with supply and return temperature sensors (optimised control), the underfloor heating mixing valve circuit must be M1. Coding addresses C7 and C9 must also be checked for this optimised control.

  1. Connect the underfloor heating mixing valve circuit to M1.
  2. Check coding addresses C7 and C9 for optimised underfloor heating control.

Applies to: Vitotronic 200-H system version 2 (underfloor heating)

Source: Vitotronic 200-H installation and service instructions, p. 5. Written in our own words; check the manual for your exact model.

Underfloor heating overheat protection

Boiler · Vitodens 200-W B2HB

For underfloor heating, an extra immersion or strap-on aquastat must be installed in the low temperature underfloor loop, downstream of the mixing valve, to shut off the pump and/or boiler. High water temperatures can damage concrete slabs.

  1. Install an immersion or strap-on aquastat in the low temperature underfloor loop, downstream of the mixing valve.
  2. Wire the aquastat to de-energize the pump and/or boiler on high temperature.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words; check the manual for your exact model.

Underfloor heating restrictions

Boiler · Vitotronic 300

Underfloor heating responds slowly, so room sensing and direct remote control are restricted on that circuit.

  1. Do not let the RS function influence an underfloor heating circuit.
  2. Do not control the underfloor circuit with a remote control that has a room temperature sensor.
  3. Install an accessory kit for operation of the underfloor circuit with a mixing valve.
  4. Install a temperature control with high limit in the flow of the radiant floor application.

Applies to: Underfloor heating circuits

Source: Vitotronic 300 technical data manual, p. 2, p. 5. Written in our own words; check the manual for your exact model.

Underfloor loop overheat protection

Boiler · Vitodens 200-W B2HA

Underfloor heating needs an extra immersion or strap-on aquastat in the low temperature loop, downstream of the mixing valve. High water temperatures can damage concrete slabs.

  1. Install an immersion or strap-on aquastat in the low temperature underfloor loop, downstream of the mixing valve.
  2. Set it so it de-energizes the pump and/or boiler on overheating.

Applies to: Vitodens 200-W B2HA 45, 60 underfloor heating systems

Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 32. Written in our own words; check the manual for your exact model.

Underfloor tubing without oxygen barrier

Boiler · Vitodens 100-W, B1HE, B1KE

Plastic underfloor tubing without an oxygen diffusion barrier lets oxygen into the system. Leaks from the resulting corrosion are not covered by warranty.

  1. Use underfloor tubing with an oxygen diffusion barrier where possible.
  2. If non-barrier tubing is used, separate that circuit from the boiler with a heat exchanger.

Applies to: Underfloor heating systems

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 26-27. Written in our own words; check the manual for your exact model.

Unpacking and moving the boiler without carrying handles

Boiler · Vitorond 100

Boiler casting and jacketry ship separately in crates. Lift only by the casting, never by panels, and avoid dropping or bumping the boiler.

  1. Do not lift or position the boiler alone.
  2. Remove the top and sides of the crate, then lift the front panel up and out.
  3. Place a wooden block about 12 in. from the rear of the skid.
  4. Insert two 1 in. Schedule 40 pipes through the openings in the casting legs and center them on the rear block.
  5. Lift the boiler clear of the skid and remove the skid.
  6. Lower the boiler until the pipes rest on the front block.
  7. Remove the rear block by tilting forward by the casting, and the front block by tilting backward by the casting.
  8. Remove the pipes and reinstall the front panel once the boiler is in place.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 11. Written in our own words; check the manual for your exact model.

Update LON participant list

Boiler · Vitodens 222-F

Only possible when all participants are connected and the control unit is set as fault manager (code 79:1).

  1. Confirm all LON participants are connected.
  2. Confirm the control unit is set as fault manager (code 79:1).
  3. Delete the existing list using Delete list? in the menu.
  4. Rebuild the participant list.

Applies to: Vitotronic fault manager on LON system

Source: Vitodens 222-F B2TB service instructions, p. 45. Written in our own words; check the manual for your exact model.

Update LON participant list (Vitotronic 300-K cascade)

Boiler · Versatronik 501 LON

Run this after all communication connections are made. The Vitotronic 300-K must be the error manager (its default), and each gateway needs a unique LON participant number.

  1. Confirm the Vitotronic 300-K is coded as the error manager (default). See the 300-K manual at address 79:01.
  2. Set a unique LON participant number on each gateway with its rotary dial. Check for duplicates.
  3. Press OK and the Menu button together to open the Service menu, then press OK.
  4. Arrow down to Service Functions and press OK.
  5. In Service Functions, make sure Participant Check is highlighted. Arrow up or down to highlight it if needed, then press OK.
  6. Arrow down to Delete List? and press OK.
  7. Wait for all devices to report back. Re-entering Participant Check too early shows No Participant, so wait and then enter Participant Check again.

Applies to: Vitotronic 300-K cascade control with Versatronik 501 gateways

Source: Versatronik 501 and 501D LON gateway manual, p. 16. Written in our own words; check the manual for your exact model.

Update LON participant list for Vitocontrol-S cascade control

Boiler · Versatronik 505, Versatronik 505D

Run this after all communication connections are made. Vitocontrol-S must be the error manager (default), and every gateway needs a unique LON participant number.

  1. Confirm Vitocontrol-S is coded as error manager (default). Refer to the Vitocontrol-S manual, address 79:01.
  2. Set the rotary dial LON participant number on each Versatronik 505 gateway and make sure no two numbers match.
  3. Press OK and the Menu button together to open the Service menu, then press OK.
  4. Arrow down to Service Functions and press OK.
  5. On the Service Functions screen, make sure Subscriber Check is highlighted. Arrow up or down to highlight it if needed, then press OK.
  6. Arrow down to Delete List? and press OK.
  7. Wait for the participant list to update with the boiler controls and other Versatronik LON devices.
  8. If the screen shows No Subscriber, wait some time and run Subscriber Check again. Devices can take time to report back.

Applies to: Vitocontrol-S cascade control with Versatronik 505 gateways

Source: Versatronik 505 NR2/BACIP manual, p. 16. Written in our own words; check the manual for your exact model.

Use a low-loss header

Boiler · Vitodens 200-W

The boiler is for closed loop, forced circulation hot water systems only. Viessmann strongly recommends a low-loss header if system flow is above the boiler maximum, below the minimum, or unknown. The built-in logic of the boiler works with the low-loss header to keep the required temperature rise. Closely spaced tees are an alternative but are less preferred.

  1. Size the piping using the standard friction loss method.
  2. Compare system flow to the boiler maximum and minimum flow limits.
  3. Install a low-loss header if flow is out of range or unknown.
  4. Connect the low-loss header so it can communicate with the boiler.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 30. Written in our own words; check the manual for your exact model.

Use a low-loss header for system flow

Boiler · Vitodens 200-W B2HA

Viessmann recommends a low-loss header when system flow is above the boiler maximum, below the minimum, or unknown.

  1. Connect a low-loss header so the built-in low-loss header logic keeps the required flow across the system.
  2. If a primary/secondary tee arrangement is used instead, know that the low-loss header is the preferred method.
  3. Check the Technical Data manual for low-loss header sizing.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 30. Written in our own words; check the manual for your exact model.

Use only in fully pumped hot water systems

Boiler · Vitocrossal 300 CU3A

The Vitocrossal 300 CU3A is only suitable for fully pumped hot water heating systems. No flow switch is needed on this boiler.

  1. Confirm the system is fully pumped before connecting the boiler.
  2. Size flow using the water flow table for the chosen temperature rise.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A application guide, p. 12. Written in our own words; check the manual for your exact model.

Use variable speed pump for zone flow

Boiler · Vitodens 222-F

A variable speed circulator for P3 adjusts flow as zone valves open and close. A single speed pump needs a pressure differential bypass to avoid over-pumping a single circuit.

  1. Select a variable speed circulator for P3 when possible.
  2. If a single speed pump is used, install a pressure differential bypass in the system.

Applies to: Application 2 pump selection

Source: Vitodens 222-F B2TB application guide, p. 36. Written in our own words; check the manual for your exact model.

Venting and common vent limits

Boiler · Vitodens 200-W B2HA

Only common vent with other Vitodens 200-W boilers of the same size. Side wall coaxial vent installs must include the Viessmann protective screen. Do not exceed the maximum equivalent length in the Venting System instructions. The coaxial vent transition adds about 65 mm (about 2.5 in.) to the overall dimension.

  1. Confirm the other boilers on the common vent are Vitodens 200-W of the same size.
  2. Fit the Viessmann protective screen on side wall coaxial vents.
  3. Check the equivalent vent length against the Venting System instructions.

Applies to: Flue and combustion air venting

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 installation instructions, p. 61. Written in our own words; check the manual for your exact model.

Venting codes and chimney requirements

Boiler · Vitorond 100

Install the vent system to all applicable local and national codes, and make sure any side wall vent meets the manufacturer's requirements.

  1. Follow local codes; in Canada use CSA B139-00, in the U.S. use NFPA 31.
  2. Build masonry or concrete chimneys to the provincial or state building code, or to CSA A405 (Canada) or NFPA 211 (U.S.). Metal chimneys must also meet Chapter 4 of NFPA 211.
  3. In Canada, use factory built chimneys that conform to CAN/ULC-S629 (1202°F / 650°C), CAN/ULC-S604 Type A, or CAN/ULC-S609 Type L.
  4. In Canada, install factory built chimneys per the manufacturer's certified instructions.
  5. In Canada, provide a clean-out with a tight-fitting removable cap so no air can enter when it is in place.
  6. In the U.S., factory built chimneys must meet NFPA requirements and be listed, installed and used per their listings and manufacturer instructions.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

Venting route and piping support

Boiler · Vitodens 200-W B2HA

The vent can be single-wall or coaxial. Route it through the side wall or roof by the shortest practical path, rising at least 3 degrees. The piping must be supported on its own and must not rest on or hang from the boiler.

  1. Run the venting system by the shortest route, rising at a minimum of 3 degrees.
  2. Support all piping with a proper hanger method so no load goes onto the boiler.
  3. Use only a moderate amount of pipe dope.
  4. If using single-wall venting that relies on room air, remove the outer gasket on the vent adaptor.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 18. Written in our own words; check the manual for your exact model.

Verify a carbon monoxide alarm is installed

Boiler · Vitodens 222-F

Before start-up, confirm at least one CO alarm is installed in the living space, following the alarm maker's instructions and local codes.

  1. Check that a CO alarm is installed in the residential living space.
  2. Install it per the alarm manufacturer's instructions and local codes if missing.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB installation instructions, p. 6. Written in our own words; check the manual for your exact model.

Verify CO alarm before start-up

Boiler · Vitotronic 100

Installer must confirm at least one carbon monoxide alarm is installed in the living space, per the alarm maker's instructions and local codes, before the appliance is put into operation.

  1. Confirm a CO alarm is installed in the residence per the alarm maker's instructions and local code.
  2. Only then start the appliance.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 5. Written in our own words; check the manual for your exact model.

Verify combustion after startup

Boiler · Vitorond 100

Check combustion results of the oil burner after startup. If adjustment is needed, confirm the results with a calibrated flue gas analyzer.

  1. Start the burner and check combustion with a calibrated flue gas analyzer.
  2. Adjust the burner only if results are out of range, then recheck.

Applies to: Oil-fired VR1 boilers with factory-mounted burners

Source: Vitorond 100 VR1 installation and service manual, p. 26. Written in our own words; check the manual for your exact model.

Verify DHW sensor and add a tempering valve with a non-Viessmann tank

Boiler · Vitodens 200-W B2HB

If the DHW tank is not a Viessmann Vitocell 100 or 300, the sensor operation must be verified with the tank maker. A temperature tempering valve is strongly recommended in the DHW supply.

  1. Confirm the DHW tank sensor works correctly with the tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

Applies to: Vitodens 200-W B2HB DHW storage installations

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 43. Written in our own words; check the manual for your exact model.

Verify DHW tank sensor with non-Viessmann tanks

Boiler · Vitocrossal 300 CU3A

If a DHW storage tank other than a Viessmann Vitocell 100 or 300 is used, the installer must confirm the Viessmann DHW tank temperature sensor works correctly with the tank manufacturer. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. Check with the original tank manufacturer that the Viessmann DHW sensor works with the tank.
  2. Install a temperature tempering valve in the DHW supply line.

Applies to: Multi-boiler and single-boiler DHW tank layouts

Source: Vitocrossal 300 CU3A Installation Instructions, p. 50. Written in our own words; check the manual for your exact model.

Verify field-supplied controls

Boiler · Vitocrossal 300 CA3B Dual Fuel

The heating contractor must confirm that all field-supplied controls and components work correctly before handover.

  1. Check low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents and thermostats.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Verify field-supplied controls before start-up

Boiler · Vitorond 100 VR1

The heating contractor must confirm that field-supplied controls and components work correctly. Thermostats, pumps, zone valves and other controls are not supplied by Viessmann.

  1. Check low water cut-offs (if used).
  2. Check flow switches (if used), staging controls, pumps, motorized valves, air vents and thermostats.
  3. Confirm all of these work before leaving the boiler running.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100 VR1 installation and service manual, p. 5. Written in our own words; check the manual for your exact model.

Verify field-supplied safety controls

Boiler · Vitotronic 100

The contractor must check that field-supplied controls are complete and working. These include low water cut-offs, flow switches if used, staging controls, pumps, motorized valves, air vents and thermostats.

  1. Check low water cut-offs.
  2. Check flow switches if used.
  3. Check staging controls, pumps, motorized valves, air vents and thermostats.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 5. Written in our own words; check the manual for your exact model.

Verify gas input by clocking the meter

Boiler · Vitodens 200-W B2HA

Verify burner input by timing the gas meter with all other gas appliances off. Input is correct when it matches the nameplate input. A boiler underfired by up to 5% is acceptable. Never overfire.

  1. Get the correct heating value of the gas from the gas utility before timing.
  2. Turn off all other gas appliances served by the meter.
  3. Time how long the boiler takes to use 10 ft3 of gas, in seconds.
  4. Calculate Btu/h as 3600 x 10 divided by the seconds, multiplied by the heating value.
  5. Example: 68 s with 1000 Btu/ft3 gives 530000 Btu/h for the 530 model.

Applies to: Vitodens 200-W B2HA

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 30. Written in our own words; check the manual for your exact model.

Verify mixing valve stroke direction

Boiler · Vitocrossal 300 CU3A

The stroke direction of the mixing valve motors must be checked with an actuator test.

  1. Run an actuator test on each mixing valve motor.
  2. Confirm the valve strokes in the correct direction.
  3. Refer to the Installation and Service Manual of the Cascade Control for the test procedure.

Applies to: Application 9 mixing valves

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 56. Written in our own words; check the manual for your exact model.

Verify the system diagrams on site

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

The connection diagrams are only recommendations. Check them for completeness and function at the installation site. Single-phase and three-phase pumps must be wired through field-supplied motor contactors or motor starters.

  1. Verify the wiring against the site, and confirm completeness and function.
  2. Use field-supplied motor contactors or motor starters for single-phase and three-phase pumps.

Applies to: System versions 7 to 10

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 24-31. Written in our own words; check the manual for your exact model.

Water connections and minimum system pressure

Boiler · Vitodens 222-F

Boiler can be used in any fully pumped hot water heating system. Minimum system pressure is 14 psig.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 16. Written in our own words; check the manual for your exact model.

Water quality for fill water

Boiler · Vitocrossal 300 CU3A

Use potable water and flush the system first. Soften water harder than 8.77 grains or 150 ppm TDS. Heating inhibitors or antifreeze may be added by hand.

  1. Flush the entire heating system before filling.
  2. Use only potable quality water.
  3. Soften water above 8.77 grains / 150 ppm TDS.
  4. Add suitable inhibitor or antifreeze manually if needed.

Applies to: Heating system fill water

Source: Vitocrossal 300 CU3A service instructions, p. 10. Written in our own words; check the manual for your exact model.

Water quality for filling the heating system

Boiler · Vitocrossal 300 CU3A

Unsuitable fill water causes deposits and corrosion that can damage the equipment.

  1. Flush the entire heating system before filling.
  2. Use only water of potable quality.
  3. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
  4. Add inhibitors or antifreeze suitable for heating systems manually if needed.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 20. Written in our own words; check the manual for your exact model.

Water quality, antifreeze and corrosion protection

Boiler · Vitodens 222-F

Corrosion is not typical in correctly installed and operated sealed systems. Use only corrosion inhibitors approved for boilers with single-wall DHW heat exchangers when required by plastic pipe makers. Treat fill water in areas of high mineral content or hardness. If antifreeze is used, maximum content is 50% for this boiler, use only hot water heating antifreeze, and never automotive silicate antifreeze. Check the system often when filled with antifreeze. Tell the owner the system contains glycol and provide the antifreeze MSDS. Antifreeze may require a backflow preventer and can affect expansion tanks and other components.

  1. Verify inhibitor or antifreeze is approved for hot water heating boilers.
  2. Keep antifreeze at or below 50%.
  3. Check glycol concentration regularly.
  4. Give the owner the MSDS and tell them the system is glycol-filled.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 16. Written in our own words; check the manual for your exact model.

Water treatment and freeze protection

Boiler · Vitotron 100 VLN2

Treated water extends heating element life and reduces sediment. Only certain glycol may be used.

  1. Fill the boiler and system with soft or distilled water where possible.
  2. Use only propylene glycol freeze protection that is non-toxic and corrosion resistant.
  3. Keep propylene glycol at no more than 50% by volume.
  4. Never add methanol or ethylene glycol (automotive antifreeze).

Applies to: Vitotron 100 VLN2 hydronic system

Source: Vitotron 100 VLN2 installation and service instructions, p. 9. Written in our own words; check the manual for your exact model.

Waterside design: low-loss header preferred

Boiler · Vitodens 200-W B2HB

Viessmann prefers a low-loss header over closely spaced tees. The boiler's built-in low-loss header logic works with the header through sensor communication. Primary/secondary piping with closely spaced tees is an alternative if needed.

  1. Size the low-loss header from the system flow tables on pages 11 to 13.
  2. Connect the low-loss header sensor as required by the header sizing table.
  3. Confirm the boiler flow stays within the maximum flow rate for the model.

Applies to: Vitodens 200-W B2HB 19 to 199

Source: Vitodens 200-W B2HB technical data manual, p. 9. Written in our own words; check the manual for your exact model.

Waterside flow and low-loss header

Boiler · Vitodens 200-W B2HB

The boiler is for closed loop, forced circulation hot water systems only. Size pipe using the standard friction loss method and stay within the boiler minimum and maximum flow rates. Max flow is 14.3 GPM (3,250 L/h). If system flow exceeds the max, falls below the min, or is unknown, a low-loss header is strongly recommended. Primary-secondary piping with closely spaced tees is an alternative, but a low-loss header is preferred. The built-in low-loss header logic in the boiler maintains the required temperature rise through communication with the header. The temperature rise text in the manual is partly garbled.

  1. Size the piping using the standard friction loss method.
  2. Confirm the system flow is within the boiler limits (min to 14.3 GPM).
  3. If flow is above max, below min, or unknown, install a low-loss header.
  4. Refer to the Technical Data manual for low-loss header information.
  5. Check pressure drop from the primary circuit chart when sizing the circulator.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 30. Written in our own words; check the manual for your exact model.

Weishaupt boiler/burner start-up must be done by Viessmann

Boiler · Vitorond 200 VD2

Vitorond 200 VD2 boilers with Weishaupt burners must be started up by Viessmann. Ask Viessmann for the start-up prerequisites.

  1. Contact Viessmann to arrange the boiler/burner start-up.
  2. Ask for the start-up prerequisites before the visit.

Applies to: Vitorond 200 VD2 boilers with Weishaupt burners

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data, p. 17. Written in our own words; check the manual for your exact model.

When to use a low-loss header

Boiler · Vitodens 100-W WB1B

A low-loss header is recommended when the water flow is below 1.7 GPM (400 L/h) or above 6.2 GPM (1400 L/h). It is strongly preferred over closely spaced tees.

  1. Check the system flow rate against the 1.7 GPM and 6.2 GPM limits.
  2. If flow is out of range, fit a low-loss header, using the accessory size that matches the flow.

Applies to: Vitodens 100-W WB1B 26 and 35 in all system layouts

Source: Vitodens 100-W, WB1B installation manual, p. 40. Written in our own words; check the manual for your exact model.

WiFi router and network requirements

Boiler · Vitodens 100-W

The router and network must meet these requirements before commissioning.

  1. Protect the WiFi router with a WPA2 password.
  2. Keep the router firmware updated.
  3. Do not use unencrypted connections between the boiler and the router.
  4. Use a flat rate internet connection with no time or data limit.
  5. Use dynamic IP addressing (DHCP, factory setting); have an IT expert check or set this up.
  6. Enable ports 80, 123, 443 and 8883 for direct outward connections; have an IT expert check or set this up.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 29. Written in our own words; check the manual for your exact model.

Wire size and wire type for field wiring

Boiler · Vitorond 100, VR1

Supply wiring to the boiler and other control wiring must be 14 ga. or heavier. If the factory wire must be replaced, use 105°C wire or equivalent.

Applies to: All field wiring on the boiler

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

Wiring a mixing valve controller

Boiler · Vitodens 222-F

Multiple 145 communication accessories are connected by daisy chain, running cable device to device. Set the S1 switch to assign the mixing valve to the heating circuit. Wiring terminals are shown on page 18 of the manual.

  1. Daisy-chain multiple 145 communication accessories device to device.
  2. Set switch S1 to assign the mixing valve heating circuit.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 18. Written in our own words; check the manual for your exact model.

Zero-clearance venting and service clearances

Boiler · Vitodens 200-W B2HB

The boiler is listed for zero clearance to combustibles with approved venting. Leave 12 in. (305 mm) at the side where practical for rating plate access and the PRV kit.

  1. Vent with single-wall special venting (AL-29-4C) or UL/ULC-listed CPVC/PPs gas vent material to use zero clearance to combustibles.
  2. Leave 12 in. (305 mm) side clearance where practical to view the rating plate and fit the PRV kit.
  3. If the PRV is turned 90° facing forward using an extension, the side clearance can be reduced; the reduced figure is not legible in this copy, so check the manual's clearance table.
  4. Closet and alcove installation is approved with the clearances listed in Table 1; confirm them against the full table before installing.
  5. See the Vitodens 200-W B2HB Venting System Installation Instructions for venting details.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 10. Written in our own words; check the manual for your exact model.

Zone circuit pump connections

Boiler · Vitodens 200-W B2HB

Up to 2 zone circuit pumps can connect directly to the boiler. Extra pumps need the AM1 extension module (accessory). Pump outputs are assigned in the start-up wizard.

  1. Connect up to 2 zone circuit pumps to the boiler.
  2. For more pumps, install the AM1 extension module and connect the pumps there per its installation instructions.
  3. Assign pump outputs in the start-up wizard.
  4. See the boiler service instructions for start-up.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 53. Written in our own words; check the manual for your exact model.

Zone circuit pump limits and assignment

Boiler · Vitodens 200-W B2HB

Pump outputs are assigned during the start-up wizard. Only two zone circuit pumps connect directly to the boiler; more require an AM1 extension module.

  1. Assign the pump outputs using the start-up wizard.
  2. Connect no more than 2 zone circuit pumps directly to the boiler.
  3. For additional pumps, use an AM1 extension module and follow its installation instructions.
  4. Refer to the boiler service instructions for start-up.

Applies to: Models 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 54. Written in our own words; check the manual for your exact model.

Automatic software update

General · Vitoconnect OPTO2

Available updates download automatically. During an update the LED is green for up to 5 minutes, then the Vitoconnect restarts. Commissioning also updates the software automatically once the unit is connected to the internet.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Configure the remote control

General · Vitotrol

Power on the control unit first. The heating system state transfers and a running bar shows. Choose the language, then choose which heating circuits and room sensor to control. Save, confirm, and answer Yes. The transfer can take several minutes. Configuration is done when the bar disappears. If it does not, check the heating circuit allocation.

  1. Switch on power to the control unit and wait for the running bar.
  2. Select the language and confirm with OK.
  3. Select the heating circuits and the room temperature sensor (if installed) to control.
  4. Select 'Save with OK', confirm with OK, select 'Yes', then confirm with OK.
  5. Wait for the running bar to disappear. If it stays, check the heating circuit allocation.

Applies to: Vitotrol 300A

Source: Vitotrol 300A installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Connect the Modbus version through the RJ45 adapter

General · Versatronik 521 OT/LON, Versatronik 521D OT/LON

The Modbus version uses a supplied RJ45 adapter. Field wiring goes to terminal X1.

  1. Use the supplied adapter and RJ45 cable to connect the gateway to the adapter.
  2. Connect the field wiring to terminal X1 for Modbus communication.

Applies to: Modbus version with RJ45 adapter

Source: Versatronik 521 & 521D OT/LON technical information, p. 9. Written in our own words; check the manual for your exact model.

Connection limits

General · Vitotrol

One Vitotrol 300A can operate up to 3 heating circuits. A maximum of two Vitotrol 300A units can be connected to one Vitotronic.

Applies to: Vitotrol 300A with Vitotronic control unit

Source: Vitotrol 300A installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Device ID and IP address must be unique

General · Versatronik 525

The BACnet Device ID must be unique across the entire BACnet internetwork. Do not assign a duplicate IP address when joining the gateway to the network.

  1. Assign a unique Device ID before joining the BACnet network.
  2. Check that the chosen IP address is not already in use.
  3. Once on the network, confirm any computer can open the configuration screens.

Applies to: Versatronik 525 OT/BACIP

Source: Versatronik 525 OT/BACIP manual, p. 10. Written in our own words; check the manual for your exact model.

Device ID must be unique

General · Versatronik 535 Solar

The BACnet Device ID must be unique across the whole BACnet internetwork.

  1. Check the Device ID against the rest of the BACnet network before activating the configuration.

Applies to: Versatronik 535 Solar gateway, BACnet IP

Source: Versatronik 535 Solar BACnet IP manual, p. 13. Written in our own words; check the manual for your exact model.

DIN rail 24VAC gateway installation

General · Versatronik 522

The 522D mounts on a DIN rail inside an enclosure close to the boiler controls and needs a field-supplied 24VAC supply.

  1. Mount the Versatronik 522D on a DIN rail inside an enclosure near the boiler controls.
  2. Make all required connections, including the field-supplied 24VAC power.
  3. Check that the OT terminals A and B are wired to the boiler.

Applies to: Versatronik 522D OT/Modbus, P/N 704077 (DIN rail, 24VAC)

Source: Versatronik 522 and 522D OT Modbus gateway manual, p. 6. Written in our own words; check the manual for your exact model.

First-time configuration of the remote control

General · Vitotrol 300A

After power-up the remote control reads the heating system state and walks through a language and circuit setup. The configuration is complete when the running bar disappears. If it does not, check the heating circuit allocation.

  1. Switch on power at the control unit. A running bar shows in the display.
  2. Select the language and confirm with OK.
  3. Select the heating circuits and room temperature sensor (if installed) to control.
  4. Select "Save with OK" and confirm with OK.
  5. Select "Yes" and confirm with OK.
  6. Wait for the running bar to disappear. This can take several minutes.
  7. If the bar does not clear, check the heating circuit allocation.

Applies to: Vitotrol 300A

Source: Vitotrol 300A installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Initial start-up and owner handover

General · Vitocell 100-E

Initial start-up must be done by a qualified heating contractor, who also completes the Maintenance Record. Before handover, explain the system operation sequence, the need for combustion air, how to do an emergency shutdown, and that proper maintenance is required.

  1. Complete initial start-up as a qualified heating contractor.
  2. Complete the Maintenance Record (see p. 16).
  3. Show the owner how to operate and shut down the system and what to do in an emergency.
  4. Tell the owner that annual professional service is needed before the heating season.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation manual, p. 3, p. 5. Written in our own words; check the manual for your exact model.

Keep the maintenance record up to date

General · Vitocell 100-E

The maintenance record on this page is a blank log for startup and each later service visit.

  1. Enter the startup date and the name of the technician at startup.
  2. Enter the date and technician name at each later maintenance or service visit.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation, service and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Leave the rotary dial at 0 for RESOL controls

General · Versatronik 531 Solar/LON

The rotary dial sets the address when several gateways share a system. With RESOL controls it does not need changing, so leave it at the factory default of 0.

  1. Check that the rotary dial on the gateway is set to 0.
  2. Change it only if the system uses several gateways and needs a unique address.

Applies to: Versatronik 531 Solar/LON with RESOL controls

Source: Versatronik 531 Solar LON manual, p. 7. Written in our own words; check the manual for your exact model.

Reset coding after changing a heating circuit allocation

General · Vitotrol 300A

If a heating circuit assignment is changed later, the matching coding address on the Vitotronic must be cleared. The control unit manual has the full coding details.

  1. Change the heating circuit allocation on the remote control.
  2. On the Vitotronic, find the coding address or parameter for that heating circuit.
  3. Set that coding address or parameter to 0.
  4. Check the control unit installation and service instructions for the coding details.

Applies to: Vitotrol 300A with Vitotronic control

Source: Vitotrol 300A installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Reset coding after changing heating circuit allocation

General · Vitotrol

If a heating circuit allocation is changed later, reset the coding address or parameter for that heating circuit on the Vitotronic control unit to 0. Refer to the control unit installation and service instructions for the address.

  1. Change the heating circuit allocation on the Vitotrol 300A.
  2. On the Vitotronic, set the coding address or parameter for that heating circuit to 0.
  3. Check the setting against the control unit manual.

Applies to: Vitotrol 300A with Vitotronic control unit

Source: Vitotrol 300A installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Set the RJ45 LON adapter jumpers for a free bus

General · Versatronik 521 OT/LON, Versatronik 521D OT/LON

The RJ45 LON adapter must be jumpered to match the system. This setting makes the adapter act as the termination resistor on a free bus topology.

  1. Set jumpers JP1 and JP2 to ON.
  2. Set jumper JP3 to ON.
  3. Connect the field wiring to terminal X1 for LON communication.
  4. Use the supplied RJ45 cable between the gateway and the adapter.
  5. Refer to the adapter manual for more detail.

Applies to: LON version with RJ45 LON adapter

Source: Versatronik 521 & 521D OT/LON technical information, p. 9. Written in our own words; check the manual for your exact model.

Set up Wi-Fi after replacing the router

General · Vitoconnect

Reconnects the Vitoconnect to a new Wi-Fi router through its access point.

  1. Activate access point mode (see page 14).
  2. Connect the smartphone to the VITOCONNECT-<xxxx> Wi-Fi.
  3. Enter the WPA2 password from the supplied sticker.
  4. Open http://vitoconnect.gateway or http://169.254.11.1 in the browser.
  5. Select "Select router" and follow the instructions.
  6. Wait for access point mode to deactivate after 5 minutes, or deactivate it manually.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Tank position and transport

General · Vitocell 100-E

Incorrect centring can damage the appliance. Two people are needed to transport and position the tank.

  1. Centre the Vitocell 100-E correctly on the Vitocell 100-V.
  2. Use two people when transporting and positioning the tank.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation, service and operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Vent the system at the tank's highest point

General · Vitocell 100-E

Air should be vented at the highest point of the system at the tank's system supply port, and drain taken at the lowest return port.

  1. Vent air at the system supply connection marked as highest point/ventilation (J).
  2. Drain the tank at the return to the primary generator marked as lowest point/drain (G).

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 Technical Data Manual, p. 4. Written in our own words; check the manual for your exact model.

Wall-mount 120VAC gateway installation

General · Versatronik 522

Mount the gateway near the boiler control, then complete all 120VAC and low-voltage wiring before closing the unit.

  1. Mount the gateway close to the boiler control.
  2. Remove the cover by loosening the two screws on either side of the base.
  3. Fasten the base to the wall with field-supplied fasteners.
  4. Remove one knockout and fit the strain relief or box connector. Remove any other knockouts needed for further connections.
  5. Make and verify all 120VAC and low-voltage connections.
  6. Refit the cover.

Applies to: Versatronik 522 OT/Modbus, P/N 704054 (wall mount, 120VAC)

Source: Versatronik 522 and 522D OT Modbus gateway manual, p. 5. Written in our own words; check the manual for your exact model.

Wire the 24VAC OT connection to the boiler

General · Versatronik 521 OT/LON

The gateway takes its power from a field-supplied 24VAC source. The OpenTherm link to the boiler goes to terminals A and B. The LON RJ45 port is the BMS connection.

  1. Connect the field-supplied 24VAC supply to the power terminals.
  2. Wire the OpenTherm 2-wire link to terminals A and B.
  3. Connect the BMS network to the LON RJ45 port.

Applies to: 24VAC version

Source: Versatronik 521 & 521D OT/LON technical information, p. 8. Written in our own words; check the manual for your exact model.

Wiring near high voltage and EMI

General · Versatronik 522

Keep low-voltage gateway wiring away from high-voltage conductors to limit electromagnetic interference.

  1. Do not run wires beside or near 120/240 VAC conductors.
  2. If the wire must run close to high voltage, use stranded, twisted-pair or shielded wire.
  3. Ground only one end of the shield.

Applies to: Versatronik 522 and 522D OT/Modbus gateway

Source: Versatronik 522 and 522D OT Modbus gateway manual, p. 5. Written in our own words; check the manual for your exact model.

Activate frost protection before filling the secondary circuit

Heat pump · Vitocal 100-WA

Frost protection only works when the heat pump is electrically connected, so power must be on first.

  1. Thermally insulate all hydronic lines.
  2. Connect the heat pump electrically and switch on the power supply.
  3. Only then fill the secondary (hydronic) circuit.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, p. 5. Written in our own words; check the manual for your exact model.

Antifreeze and water treatment at fill

Heat pump · Vitocal 100-AW

Treat the fill water where minerals or hardness are known to be a problem, and add antifreeze only where freezing can occur.

  1. Check hardness and pH of the fill and top-up water before filling.
  2. If hardness is high or pH is out of range after operation, take corrective treatment.
  3. Keep antifreeze at or below 50% glycol and check the system often when it is filled with antifreeze.
  4. Check that a backflow preventer is in the automatic water feed when a glycol mix is used.
  5. Tell the system operator the system contains glycol and provide the antifreeze Safety Data Sheet (SDS).

Applies to: Vitocal 100-AW hydronic system

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 110. Written in our own words; check the manual for your exact model.

Buried refrigerant line limits and tubing check

Heat pump · Vitocal 100-S

Limits for buried line runs and checks before charging the system.

  1. Do not bury more than 36 in (914 mm) of refrigerant line.
  2. If any line is buried, give it a minimum 6 in (152 mm) vertical rise to the outdoor service valves.
  3. Check that factory tubing has not shifted in shipping.
  4. Check that tubes do not rub each other or sheet metal.
  5. Check that the wire ties on the feeder tubes are secure and tight.

Applies to: DLCSRB outdoor units, all sizes

Source: DLCSRB Service Manual, p. 2, 16-17. Written in our own words; check the manual for your exact model.

Buried refrigerant pipe limits

Heat pump · Vitocal 100-S

Do not bury more than 36 in of refrigerant pipe. If any section is buried, the pipe must rise at least 6 in to the outdoor unit valve connections. Too much buried pipe lets refrigerant migrate and can cause slugging at start-up.

Applies to: DLCURA field piping

Source: DLCURA installation instructions, p. 9. Written in our own words; check the manual for your exact model.

Check factory tubing before final connection

Heat pump · Vitocal 100-S, DLCLRC

Factory tubing can shift in shipping and rub. Check it before finishing the install.

  1. Check that factory tubing on both indoor and outdoor units has not shifted.
  2. Make sure no tubes rub against each other or sheet metal.
  3. Check that wire ties on the feeder tubes are secure and tight.

Applies to: DLCLRC indoor and outdoor units

Source: Vitocal 100-S DLCLRC service instructions, p. 9. Written in our own words; check the manual for your exact model.

Check water connections for leaks

Heat pump · Vitocal 100-WA

Escaping ground loop water or DHW can cause electric shock risk, so check all water side connections.

  1. Fit new gaskets or seals on every connection that was opened or loosened.
  2. During commissioning and after any maintenance, check all water side connections for leaks.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 13. Written in our own words; check the manual for your exact model.

Closed loop flow and loop temperature

Heat pump · Vitocal 100-WA

Closed loops need a minimum of 3 GPM/ton (11.5 LPM/3.5 kW), based on a loop designed for 32 to 90°F (0 to 32°C). Use higher flow if design temperatures fall outside that range. The loop pump depends on the project loop design; residential systems typically use one pump per unit.

  1. Confirm loop design temperature is within 32-90°F.
  2. Size the loop pump for at least 3 GPM/ton.
  3. Increase flow if loop temperatures fall outside the range.

Applies to: Closed loop systems

Source: Vitocal 100-WA technical data manual, p. 14. Written in our own words; check the manual for your exact model.

Closed loop purging and pump mounting

Heat pump · Vitocal 100-WA

Air trapped in the pump will burn it out quickly. Purging needs a minimum velocity in every branch. With several heat pumps on one loop, only one auto purge kit is used.

  1. Mount the ground loop pump vertically so air cannot be trapped in it.
  2. Achieve at least 2 ft/s in every branch of the ground loop while purging.
  3. Use the purge ports for anti-freeze charging.
  4. With two or more heat pumps on one loop, install only one auto purge kit, ideally on the highest unit.
  5. Install check valves and a Y-strainer on each unit.
  6. Keep the auto purge tank ½ to ¾ full at all times.

Applies to: Closed loop systems

Source: Vitocal 100-WA installation, service and operating instructions, p. 40-41. Written in our own words; check the manual for your exact model.

Communication bus cable between indoor and outdoor units

Heat pump · Vitocal 100-AW AM2V

The indoor and outdoor modules communicate over a bus. Use the specified cable type.

  1. Use two-wire twisted pair, shielded 22 AWG cable between the indoor and outdoor unit.

Applies to: Indoor and outdoor unit wiring

Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 16. Written in our own words; check the manual for your exact model.

Condensate drain connections

Heat pump · D5CSRA

Install the drains according to local sanitation codes.

  1. Route the drain lines per local sanitation codes.

Applies to: All D5CSRA systems

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

Connecting to the control board with PuTTY

Heat pump · Vitocal 100-WA

A Windows computer or Android phone/tablet with PuTTY and a USB link is used to view and adjust the control board system run parameters, zone parameters and basic system program.

  1. Install PuTTY on the computer or device.
  2. Open PuTTY and note the COM port the controller uses; check Device Manager under Ports (COM & LPT).
  3. If several COM ports are in use, unplug the controller to see which port disappears, then plug it back in.
  4. Connect the USB cable between the computer and the control board and make sure the controller is powered.
  5. Select Connection Type Serial, enter the COM number and set the speed (baud rate) to 250000.
  6. Click Default Settings under Saved Sessions and press Save so these settings load by default.
  7. Press Open on the Configuration page to start communicating with the controller.

Applies to: Vitocal 100-WA control board

Source: Vitocal 100-WA installation, service and operating manual, p. 82-83. Written in our own words; check the manual for your exact model.

DHW desuperheater piping requirements

Heat pump · Vitocal 100-WA

Use isolation valves and two drain valves so the pump can be serviced without draining the tank. Use a horizontal swing check valve to stop the tank overheating. Copper must match the unit fittings; if 1 in. (25 mm) copper is used, reduce it as close to the tank as possible. Use metal fittings within 12 in. (300 mm) of the desuperheater tee. With a Marathon plastic tank use mechanical fittings at the tank only, and never use plastic fittings between the tank and the unit. Follow the tank installation instructions.

  1. Install isolation valves and two drain valves (tank draining and purging).
  2. Install a horizontal swing check valve.
  3. Use metal fittings within 12 in. (300 mm) of the desuperheater tee.
  4. Reduce 1 in. copper to match the unit as close to the tank as possible.
  5. Upsize long pipe runs if pressure drop is too high.

Applies to: DHW tank with desuperheater

Source: Vitocal 100-WA technical data manual, p. 10. Written in our own words; check the manual for your exact model.

DHW piping sizing to the indoor unit

Heat pump · Vitocal 100-AW

DHW piping must not restrict flow, so the internal pump has enough head to push water through the heat exchanger.

  1. Make the DHW supply and return piping between the indoor unit DHW connections and the DHW tank at least the same size as the indoor unit outlets.
  2. With a non-Viessmann tank, calculate the tank coil pressure drop against the indoor unit pump residual head to confirm adequate flow.
  3. Be aware that undersized DHW piping can cause inadequate DHW supply.

Applies to: Indoor unit DHW connections

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 31. Written in our own words; check the manual for your exact model.

DHW tank and DHW piping requirements

Heat pump · Vitocal 100-AW AM2V

A non-Viessmann DHW tank requires the installer to verify the tank temperature sensor with the tank maker. A tempering valve is strongly recommended in the DHW supply line. DHW piping must be at least the size of the Vitocal DHW connections so the integral pump has enough residual head.

  1. For a non-Viessmann tank, verify the DHW tank temperature sensor operation with the tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.
  3. Size DHW supply and return piping to at least the Vitocal DHW outlet size.
  4. For non-Viessmann tanks, calculate the tank coil pressure drop against the integral pump residual head.

Applies to: Vitocal 100-AW AM2V domestic hot water

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 46. Written in our own words; check the manual for your exact model.

Duct design and install notes

Heat pump · Vitocal 100-WA

Design ducts per ACCA Manual D or local code and keep them inside conditioned space. Attic duct should be low profile, laid on the joists and covered with 6-8 in. (150-200 mm) of insulation. Line the first 6 ft of supply and return with acoustic insulation and use flex duct for the first 6 ft from the grille. Do not undersize the return. Make turns smooth. Do not let screws or drilling reach the air coil.

  1. Design per ACCA Manual D or local code.
  2. Keep ducts inside conditioned space where possible.
  3. Insulate attic ducts with 6-8 in. (150-200 mm) of insulation.
  4. Line the first 6 ft of supply and return with acoustic insulation.
  5. Size the return to avoid pulsation and poor performance.
  6. Keep screws and drilling clear of the air coil.

Applies to: Ducted installs

Source: Vitocal 100-WA technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Factory refrigerant charge and line length

Heat pump · Vitocal 100-S, DLCURA

The factory charge in the outdoor unit covers up to 25 ft (8 m) of line length.

  1. For refrigerant lines longer than 25 ft (8 m), add refrigerant up to the allowable length.

Applies to: Outdoor unit sizes 18K to 60K

Source: DLCURA installation instructions, p. 16. Written in our own words; check the manual for your exact model.

Filter drier replacement rule

Heat pump · Vitocal 100-S

Replace the filter drier any time the refrigeration system is exposed to air. Use only factory liquid-line driers rated below 600 psig. Do not install a suction-line drier in the liquid line.

Applies to: DLCURA heat pump models

Source: DLCURA installation instructions, p. 13. Written in our own words; check the manual for your exact model.

First power-up language and outdoor unit type

Heat pump · Vitocal 100-AW

At first power-up the indoor unit asks for the operating language and the connected outdoor unit model. Choose the model that matches the outdoor unit: 020028, 034043 or 051078.

  1. Scroll with the navigation dial to the language and press the dial to select it.
  2. Scroll to the connected outdoor unit type and press the dial to accept it.

Applies to: Vitocal 100-AW AM2V indoor unit first start-up

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 51. Written in our own words; check the manual for your exact model.

Flush the heating system before connecting

Heat pump · Vitocal 100-WA

Flush the heating system thoroughly, especially when adding the heat pump to an existing system.

  1. Flush the whole system before making the heat pump connections.
  2. Use isolation valves so system components can be isolated.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Freeze protection and power failure precautions

Heat pump · Vitocal 100-AW AM2V

Do not switch the unit off when outdoor air is below freezing, because leaving it powered protects the outdoor unit condenser. If power failure is a risk, isolate the heat pump heating circuit from the hydronic module with an additional exchanger and fill that circuit with antifreeze.

  1. Keep the outdoor unit powered when outdoor air is below freezing.
  2. Where power failure is a risk, add an additional exchanger to isolate the heat pump circuit.
  3. Fill the heat pump heating circuit with antifreeze in that case.

Applies to: Vitocal 100-AW AM2V outdoor unit

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 46. Written in our own words; check the manual for your exact model.

Freeze protection tab

Heat pump · Vitocal 100-WA

The ANTIFREEZE tab sets the freeze set point. Breaking it off is permanent and is only allowed on closed loops that have adequate antifreeze.

  1. On closed loops with adequate antifreeze, break off the ANTIFREEZE tab with needle nose pliers if a 20°F (-7°C) set point is wanted.
  2. On open loops, leave the tab in place to keep the 38°F (3°C) set point.
  3. Do not remove the tab on open loops or on closed loops with minimal freeze protection, as this voids the warranty.

Applies to: Liquid to refrigerant heat exchanger

Source: Vitocal 100-WA installation, service and operating instructions, p. 45. Written in our own words; check the manual for your exact model.

Ground loop and DHW connection points

Heat pump · Vitocal 100-WA

Port legend for the water and air connections on the unit. A and B are the ground loop return and supply. C is the condensate line. D is return air and G is supply air. E is the DHW supply to the tank and F is the DHW tank return to the desuperheater. H is an optional field-supplied double O-ring flow center.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, p. 16. Written in our own words; check the manual for your exact model.

Heating water piping practice and pressure limit

Heat pump · Vitocal 100-AW

Support all piping with hangers and never let the indoor unit carry the pipe weight. Use two wrenches on fittings so the connector is not twisted. The maximum allowable working pressure is 30 psig (2 bar); exceeding it or the listed temperatures damages the unit and voids the warranty.

  1. Flush the heating system thoroughly, especially before connecting to an existing system.
  2. Install isolation valves so system components can be isolated.
  3. Use approved pipe sealant or Teflon tape on the fittings.
  4. Hold the connector with one wrench and tighten the fitting with a second wrench.
  5. If no DHW tank is connected, cap the DHW tank supply connection.
  6. Keep 2 in. (50 mm) from uninsulated hot water pipes to combustible parts, unless the pipe has suitable insulation.
  7. Install a temperature gauge (field supplied) in the supply piping near the heat pump.

Applies to: Indoor unit heating water and DHW connections

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 16. Written in our own words; check the manual for your exact model.

Hydronic installation requirements

Heat pump · Vitocal 100-AW AM2V

The hydronic side must follow applicable standards and be sized for adequate flow. Flexible piping is needed to limit vibration. Heating medium piping must be insulated. A solids separator at the unit inlet is required for warranty.

  1. Size the piping between outdoor and indoor units for adequate flow (see technical data table).
  2. Connect the heat pump to the system with flexible piping.
  3. Insulate all heating medium pipes and connections.
  4. Install a solids separator at the unit inlet.
  5. Keep the minimum heating medium pressure at 8 PSI (0.5 bar).
  6. Pipe so the indoor unit can run the heating circuit without the outdoor unit.

Applies to: Vitocal 100-AW AM2V hydronic system

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 46. Written in our own words; check the manual for your exact model.

Indoor to outdoor connection polarity

Heat pump · Vitocal 100-S, DLCLRC

The indoor to outdoor connections are polarity sensitive and a wrong connection will generate a fault code. Do not use thermostat wire for any link between indoor and outdoor units. Use a 2-core shielded wire for the communication link. Use the connection diagram exactly as drawn.

  1. Connect the power and communication wires between outdoor and indoor units as shown in the connection diagram.
  2. Use shielded 2-core communication wire, not thermostat wire.
  3. Check polarity before power-up.

Applies to: DLCLRC sizes 36K-58K

Source: Viessmann DLCLRC service manual, p. 5 of 60. Written in our own words; check the manual for your exact model.

Indoor to outdoor unit connection polarity

Heat pump · DLFSHCH, Vitocal IND-H

Do not run thermostat wire between the indoor and outdoor units. The connections are polarity sensitive, and a wrong connection will cause a fault code. All indoor-outdoor connections must match figures 1 and 2 of the manual.

  1. Do not use thermostat wire between the units.
  2. Wire the indoor and outdoor units exactly as shown in the 115 V or 208/230 V connection diagram.
  3. Confirm polarity on every communication connection before power-up.

Applies to: DLFSHCH indoor and outdoor unit wiring

Source: Vitocal IND-H DLFSHC service manual, p. 4. Written in our own words; check the manual for your exact model.

Indoor unit location

Heat pump · Vitocal 100-AW

Place the indoor unit in a heated indoor space near a floor drain and close to an outside wall, so it connects easily to the outdoor unit. The wall must carry the unit's weight.

  1. Pick a heated indoor location near a floor drain.
  2. Use an outside wall where possible to shorten the link to the outdoor unit.
  3. Confirm the wall can hold 100 lb (45 kg).

Applies to: Vitocal 100-AW AM2V indoor unit

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Initial start-up and maintenance record

Heat pump · Vitocal 100-WA

Initial start-up must be done by a qualified licensed contractor.

  1. Complete the start-up by a qualified licensed contractor.
  2. Complete the Maintenance Record properly.
  3. Make sure the system operator is shown how the system works, how to start and shut it down, and that annual professional service is needed.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Install condensate drain fittings before mounting

Heat pump · Vitocal 100-AW AM2V

Drain fittings go into the base pan first. Relief opening count depends on the model.

  1. Locate the drain relief openings in the base pan.
  2. Install the supplied condensate drain connectors before setting the unit.
  3. Expect two relief openings on AM2V 020028 and 051078, and three on AM2V 034043.

Applies to: All AM2V outdoor units

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 38. Written in our own words; check the manual for your exact model.

Intended use and installation limits

Heat pump · Vitocal 100-AW AM2V

The unit is only for sealed, unvented hydronic systems and is designed for space heating, space cooling and DHW heating. Mount the indoor unit so components are protected from water spray or splashing during operation and service.

  1. Confirm the system is a sealed unvented hydronic system before installing.
  2. Protect the indoor unit from water spray and splashing.

Applies to: Whole system

Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 18. Written in our own words; check the manual for your exact model.

Keep 25% propylene glycol in closed loops

Heat pump · Vitocal 100-WA

Closed loops must always carry at least 25% propylene glycol in the unit and ground loop. Damage from low antifreeze is not covered by the warranty.

  1. Confirm the glycol concentration in the unit and ground loop is at least 25% propylene glycol.
  2. Re-check glycol level after purging and before start-up.

Applies to: Closed loop systems

Source: Vitocal 100-WA installation, service and operating instructions, p. 40. Written in our own words; check the manual for your exact model.

Keep the system dry and clean during install

Heat pump · Vitocal 100-S

Keep air, dust, moisture and foreign material out of the refrigerant circuit. Contamination can reduce capacity and raise high-side pressure.

  1. Do not install the connecting pipe until both indoor and outdoor units are mounted.
  2. Ventilate the area right away if refrigerant leaks during installation.
  3. Check for leaks after the work is finished.

Applies to: DLCURA refrigerant circuit

Source: DLCURA installation instructions, p. 12. Written in our own words; check the manual for your exact model.

Limit buried refrigerant pipe length

Heat pump · Vitocal 100-S

Do not bury more than 36 in. (914 mm) of refrigerant pipe. Any buried section needs a 6 in. (152 mm) vertical rise to the outdoor unit valve connections. Over-length buried pipe can let refrigerant migrate during shutdown and cause liquid slugging that may damage the compressor at start-up.

  1. Keep buried refrigerant pipe to 36 in. (914 mm) maximum.
  2. Provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections on any buried section.

Applies to: Refrigerant piping runs

Source: Viessmann DLCURA installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Long line applications

Heat pump · D5CSRA

Line sizing does not change for long lines, but refrigerant must be added. The maximum total line length is 213 ft (65 m).

  1. Keep the same line size as a standard install.
  2. Add refrigerant per the long line table for the unit size and line length.
  3. Do not exceed 213 ft (65 m) total line length.

Applies to: All D5CSRA systems

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

Mechanical room location requirements

Heat pump · Vitocal 100-WA

Install the unit in a heated indoor area near a floor drain. Where possible, place it near an outside wall to make the ground loop connection easier. The room must not drop below 60 °F (15 °C).

  1. Place the unit in a heated indoor area near a floor drain.
  2. Place it near an outside wall if possible.
  3. Confirm the room stays at or above 60 °F (15 °C).

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 3. Written in our own words; check the manual for your exact model.

Mount outdoor unit on a stand

Heat pump · Vitocal 100-AW AM2V

Use a field-supplied stand whose mounting spacing matches the outdoor unit feet. Make sure the condensate drains freely. The stand or wall bracket must be rated for the unit weight, and the manufacturer's assembly instructions must be followed.

  1. Assemble and secure the stand, matching its spacing to the outdoor unit mounting feet.
  2. Secure the outdoor unit to the stand.
  3. Confirm the condensate drains freely (see condensate drain fittings section, p. 38).

Applies to: Vitocal 100-AW AM2V outdoor unit

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 40. Written in our own words; check the manual for your exact model.

Nitrogen flow when brazing fan coil piping

Heat pump · D5CSRA

When the outdoor unit is matched with a multi-family or residential fan coil and the fan coil side piping must be brazed, nitrogen must flow through the system while brazing the line set. A filter drier is not recommended with these condensing units.

  1. Flow nitrogen through the system while brazing the line set.
  2. Do not install a filter drier with these condensing units.

Applies to: D5CSRA matched with multi-family or residential fan coils

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

No PVC or CPVC in ground loop connections

Heat pump · Vitocal 100-WA

PVC or CPVC may only be used for condensate lines. Using it on ground loop connections is not allowed.

  1. Use approved piping for all ground loop connections.
  2. Use PVC or CPVC only for condensate lines.

Applies to: Ground loop connections

Source: Vitocal 100-WA installation, service and operating instructions, p. 40. Written in our own words; check the manual for your exact model.

Non-Viessmann DHW tank requirements

Heat pump · Vitocal 100-AW

Using a DHW tank that is not a Viessmann Vitocell tank changes what the installer must verify.

  1. Verify the Viessmann DHW tank temperature sensor works correctly with the original tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line. Viessmann strongly recommends this.
  3. Use only tank and heat pump combinations that appear in the Viessmann price list.

Applies to: Indoor unit with DHW storage tank

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 31. Written in our own words; check the manual for your exact model.

On/off remote control function: remove J7 short connector

Heat pump · DLFLDAH

The short connector on J7 must be removed before the on/off remote function is used.

  1. Remove the short connector on J7 on the indoor control board.
  2. Connect the on/off remote control to CN23.

Applies to: Indoor unit control board, on/off remote control function

Source: Vitocal IND-D technical data manual, p. 24. Written in our own words; check the manual for your exact model.

Open loop water source requirements

Heat pump · Vitocal 100-WA

Only a well or retention pond with enough capacity and good water quality is acceptable. Pond or lake water must not be pumped directly through the units.

  1. Install an 18-20 mesh strainer in an easy-to-reach location.
  2. Provide isolation valves so the strainer can be cleaned.
  3. Replace an undersized well strainer with a larger 18-20 mesh unit if debris restricts it quickly.
  4. Route discharge water to a well, creek, pond or other use without restriction.
  5. Do not connect discharge directly to a sprinkler.
  6. Make sure discharge tubing cannot freeze.
  7. Water flow is controlled by a modulating water valve or an ON/OFF two position valve.

Applies to: Open loop systems

Source: Vitocal 100-WA installation, service and operating instructions, p. 42. Written in our own words; check the manual for your exact model.

Open loop water valve options

Heat pump · Vitocal 100-WA

The unit works with an ON/OFF two-position water valve or with a proportional modulating water valve driven by a 2-10 VDC signal. Water flow is controlled by the modulating valve when used.

  1. Select ON/OFF two-position valve or 2-10 VDC modulating valve.
  2. Wire the valve per the unit wiring diagram.
  3. Confirm the valve sets water flow at 2-3 GPM/ton.

Applies to: Open loop systems

Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Outdoor temperature limits for operation

Heat pump · Vitocal 100-AW

The heat pump only runs efficiently within a set outdoor air range. Outside that range it switches off periodically and the controller shows a notice. Auxiliary electric heat then covers the load.

  1. Confirm outdoor air is between -13°F and 113°F (-25°C and +43°C) during operation.
  2. If the unit cycles off at the temperature limits, check the controller notice before troubleshooting further.
  3. Confirm the auxiliary electric heater is enabled so the building load is still met outside the limits.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Outdoor unit location and mounting

Heat pump · D5CSRA

The outdoor unit must sit level in all directions. Keep the minimum clearance from Fig. 5 open so air can move freely. Do not restrict the air inlets or outlets. Pick a spot that is out of strong winds and can carry the unit's weight. Do not install in locations with special environmental conditions unless the manufacturer approves it.

  1. Level the outdoor unit in all planes.
  2. Keep the Fig. 5 minimum clearances clear for airflow.
  3. Do not block the air inlets or outlets.
  4. Choose a location out of strong wind that can hold the unit's weight.

Applies to: All D5CSRA outdoor units

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

Pipe cutting and flaring quality

Heat pump · Vitocal 100-S

Poor pipe preparation reduces efficiency and causes leaks. Cut at 90 degrees without deforming the pipe, then remove all burrs and flare with the factory flare nut in the correct orientation.

  1. Measure the distance between units and cut the pipe slightly longer.
  2. Remove burrs with a reamer or deburring tool, holding the pipe pointing down.
  3. Seal the pipe ends with PVC tape until flaring.
  4. Place the factory flare nut before flaring, because it cannot be changed after flaring.
  5. Inspect the flare for cracks and even shape before connecting.

Applies to: DLCURA copper line set

Source: DLCURA installation instructions, p. 12. Written in our own words; check the manual for your exact model.

Piping pressure drop must stay within residual head

Heat pump · Vitocal 100-AW

The indoor unit internal pump has a limited residual head. Extra pressure drop in the piping to the buffer tank and indirect DHW coil reduces flow and system performance.

  1. Size the piping between indoor unit, outdoor unit, buffer tank and DHW coil so total pressure drop stays within the indoor unit residual head.
  2. Check that the indoor unit flow stays within its minimum and maximum flow range for the model.

Applies to: Vitocal 100-AW AM2V indoor unit

Source: Vitocal 100-AW AM2V technical data manual, p. 4. Written in our own words; check the manual for your exact model.

Piping support and isolation

Heat pump · Vitocal 100-WA

Support all piping with hangers. Do not let the piping hang from the Vitocal or its components. Fit isolation valves so system components can be isolated.

  1. Hang all piping from hangers.
  2. Do not use the Vitocal or its components as a pipe support.
  3. Install isolation valves on system components.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 6. Written in our own words; check the manual for your exact model.

Power and communication wiring between indoor and outdoor units

Heat pump · DLFSHCH, Vitocal IND-H

Use stranded copper wire rated 600 V, sized per NEC/CEC and local code using the MCA and MOCP values in the electrical data. Power and communication run together from the outdoor unit to the indoor unit. The main line voltage goes on terminals 1 and 2, the communication wire on terminal 3, and green ground on the ground terminal. Keep every connection tight. No wire may touch refrigerant tubing, the compressor or moving parts. If there is high EMF interference, a 14/2 stranded shielded wire can replace the 2 and 3 conductors, with the shield grounded at the outdoor unit only.

  1. Size wires and disconnect per NEC/CEC, local code and the MCA/MOCP values.
  2. Use stranded copper, 600 V rated wire only.
  3. Connect L1 to terminal 1, N or L2 to terminal 2, communication to terminal 3, green to ground.
  4. Check the 115 V or 208/230 V connection diagram before landing wires.
  5. Tighten all connections and keep wires clear of tubing, compressor and moving parts.
  6. If EMF interference is present, use shielded 14/2 for conductors 2 and 3 and ground the shield at the outdoor unit only.

Applies to: DLFSHCH indoor and outdoor unit wiring

Source: Vitocal IND-H DLFSHC service manual, p. 3. Written in our own words; check the manual for your exact model.

Pre-start-up checklist

Heat pump · Vitocal 100-WA

Confirm these items before energising the unit.

  1. Confirm the loop is purged and filled, with propylene glycol mixed correctly for closed loops.
  2. Confirm well pressure and open valves for open loops, and that water flow stops when the system is off.
  3. Purge all air from hot water loop lines and open all valves. Do not run a dry pump.
  4. Confirm supply and return grilles and return filter are installed and unrestricted.
  5. Secure all air chamber service panels.
  6. Confirm supply voltage matches the nameplate and fuses, breakers and wire sizes are correct.
  7. Complete low voltage wiring, including thermostat and field safeties.
  8. Confirm the unit is level and the condensate drain is open and pitched.
  9. Confirm access panels allow service to the front and sides.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 49. Written in our own words; check the manual for your exact model.

Pressure and temperature limits and plumbing code

Heat pump · Vitocal 100-WA

Exposing the heat pump to pressures or temperatures above the listed values will damage it and void the warranty. All plumbing must meet or exceed local, state and national plumbing codes.

  1. Check system pressures and temperatures against the listed limits before startup.
  2. Confirm the plumbing meets local, state and national code.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 6. Written in our own words; check the manual for your exact model.

Purge the domestic hot water (DHW) lines

Heat pump · Vitocal 100-WA

Air left in the unit and the lines between the DHW tank and the unit will cavitate and damage the pump. Purging the building plumbing alone does not clear the unit.

  1. Close boiler drain valves and the isolation valves.
  2. Open the cold supply to the DHW tank.
  3. Open a hot tap and bleed air from the tank, or lift the tank relief valve lever.
  4. Purge the air remaining in the unit and the lines to the hot water tank.
  5. Confirm all air is removed from the DHW lines before running the unit for hot water.

Applies to: Domestic hot water circuit

Source: Vitocal 100-WA installation, service and operating instructions, p. 44. Written in our own words; check the manual for your exact model.

Refrigerant line insulation and buried pipe limits

Heat pump · DLFSHCH, Vitocal IND-H

Insulate the two refrigerant lines separately. Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any section is buried, it must rise at least 6 in. (152 mm) to the outdoor unit valve connections. Too much buried pipe lets refrigerant migrate to the cold section during shutdown, which can cause slugging and compressor damage at start-up.

  1. Insulate each refrigerant line separately.
  2. Keep total buried refrigerant pipe to 36 in. (914 mm) or less.
  3. If pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.

Applies to: DLFSHCH refrigerant piping

Source: Vitocal IND-H DLFSHC service manual, p. 2 and p. 7. Written in our own words; check the manual for your exact model.

Refrigerant line orientation and insulation

Heat pump · DLFSDAH and DLFLDAH

Refrigerant lines on these units can exit from the side of the unit. Both refrigerant lines must be insulated.

  1. Orient the refrigerant lines toward the side of the unit where the piping run requires.
  2. Insulate both refrigerant lines.

Applies to: DLFSDAH and DLFLDAH indoor ducted fan coils

Source: Viessmann Vitocal IND-D DLFSDAH & DLFLDAH technical data manual, p. 32. Written in our own words; check the manual for your exact model.

Refrigerant line set installation

Heat pump · D5CSRA

Outdoor units ship with a full charge of R-454B. Charges, line sizing and capacities are based on 25 ft (7.6 m) runs; longer runs need a charge adjustment from the long line table. The outdoor unit uses an electronic expansion valve to control refrigerant flow to the indoor fan coil.

  1. Do not bury the lines deeper than 36 in (914 mm).
  2. Give the lines at least a 6 in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
  3. Insulate both lines with at least 1/2 in (12.7 mm) insulation; closed-cell is recommended for long lines.
  4. Isolate the tubing from the building structure so vibration and noise do not transfer.
  5. For runs over 25 ft, add refrigerant per the long line table.

Applies to: All D5CSRA systems

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

Remove air from the system and avoid air traps

Heat pump · Vitocal 100-AW AM2V

Air must be removed through air vents in the system supply. Supply and return lines must not contain restrictive piping where air can be trapped, so the heat pump can be fully purged.

  1. Install air vents in the system supply.
  2. Route supply and return lines without restrictive pipe sections where air can collect.
  3. Purge the heat pump of all air.

Applies to: Vitocal 100-AW AM2V hydronic side

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 41. Written in our own words; check the manual for your exact model.

Remove ground loop caps before connecting

Heat pump · Vitocal 100-WA

Ground loop connections ship with caps fitted. The caps must be removed before the loop is connected.

  1. Remove the caps from the ground loop connections.
  2. Connect supply and return to the ground loop.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 6. Written in our own words; check the manual for your exact model.

Route connection pipe to prevent rain entering indoor unit

Heat pump · Vitocal 100-S

If the outdoor unit is higher than the indoor unit, make a downward arc in the connection pipe before it enters the wall so rain drips off before reaching the indoor unit.

  1. Form a downward arc in the connection pipe before it enters the wall.
  2. Confirm rain drips off the pipe before the wall penetration.

Applies to: Outdoor unit mounted above indoor unit

Source: Viessmann DLCURA installation instructions, p. 4. Written in our own words; check the manual for your exact model.

Safe leak testing and lockout before service

Heat pump · Vitocal 100-S, DLCSRB

Never use air or oxygen-containing gases for leak testing or running the compressor. Shut off and lock out the main disconnect before installing or servicing; there may be more than one disconnect.

  1. Lock out and tag every disconnect switch before working on the system.
  2. Use only nitrogen or other non-oxygen gases for leak testing.
  3. Never use air or oxygen-containing gases to pressurize or run refrigerant compressors.

Applies to: DLCSRB outdoor units, sizes 06 to 36

Source: DLCSRB Service Manual, p. 1. Written in our own words; check the manual for your exact model.

Sizing and air distribution compatibility

Heat pump · Vitocal 100-WA

Select the heat pump model from an accurate heat loss or gain calculation for the building. Confirm the model is compatible with the connected air distribution system.

  1. Complete a heat loss or gain calculation for the building.
  2. Confirm the model is compatible with the air distribution system.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Sound and vibration isolation

Heat pump · Vitocal 100-WA

Heat pumps, pumps, blowers and fans make noise and vibration. Use flexible ducting or duct connectors to separate the equipment from the building. Place a shock-absorbing pad under the unit on hard floors such as concrete, which also reduces moisture damage.

  1. Use flexible ducting or duct connectors.
  2. Place a shock-absorbing pad under the heat pump on hard surfaces.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Stand-alone DHW tank: sensor and tempering valve

Heat pump · Vitocal 100-AW

A stand-alone DHW tank needs the DHW sensor supplied with the heat pump plus field-supplied fittings. For a non-Viessmann tank, confirm with the tank maker that the Viessmann DHW sensor works with it. A temperature tempering valve in the DHW supply line is strongly recommended.

  1. Mount the DHW sensor in the sensor well following the tank instructions (Vitocell tanks).
  2. For a non-Viessmann tank, verify sensor operation with the tank manufacturer.
  3. Install a temperature tempering valve in the DHW supply line.

Applies to: Indoor unit DHW storage tank connection

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 19. Written in our own words; check the manual for your exact model.

System example 1: direct and mixing heating circuits with buffer tank

Heat pump · Vitocal 100-AW AM2V

Example layout with one direct-connected heating circuit, one mixing-valve heating circuit, a system buffer tank and a DHW storage tank. Components are labelled A to V in the manual legend, including outdoor sensor, room sensor, DHW sensor, heating circuit pumps, mixing valve and a wye strainer.

  1. Follow the legend to match each component letter to its function before piping.
  2. Place the system separation required for underfloor tubing without oxygen diffusion barrier, and use corrosion-resistant materials on the secondary side of the heat exchanger.

Applies to: Vitocal 100-AW AM2V indoor and outdoor units with buffer and DHW tank

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 32. Written in our own words; check the manual for your exact model.

System example 2: direct and mixing circuits with fan coil

Heat pump · Vitocal 100-AW AM2V

Same layout as example 1 with a fan coil added as component W. Uses the same buffer tank, DHW storage tank and component legend.

  1. Use the legend to identify the fan coil (W) and its connection to the buffer tank circuit.
  2. Apply the same system separation requirement for underfloor tubing and corrosion-resistant secondary-side materials.

Applies to: Vitocal 100-AW AM2V with fan coil

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 33. Written in our own words; check the manual for your exact model.

Tighten water connections with two wrenches

Heat pump · Vitocal 100-WA

Hold the heat pump connector with one wrench so the pipe cannot twist, and tighten the fitting with the second. Without support, the internal piping can be damaged.

  1. Hold the heat pump connector with one wrench.
  2. Tighten the fitting or pipe with the second wrench.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 6. Written in our own words; check the manual for your exact model.

Underfloor heating separation

Heat pump · Vitocal 100-AW AM2V

Underfloor heating that uses non-oxygen diffusion barrier tubing must be separated from the system. All components on the secondary side of the heat exchanger must be corrosion-resistant.

  1. Separate underfloor heating that uses non-oxygen diffusion barrier tubing.
  2. Use corrosion-resistant materials for all secondary-side components.

Applies to: Vitocal 100-AW AM2V system piping

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 47. Written in our own words; check the manual for your exact model.

Unit selection sizing

Heat pump · D5CSRA

Pick equipment that matches or slightly exceeds the expected peak load. This gives better humidity control, fewer cycles and less part-load running. In spaces with high sensible loads, size on the unit sensible load instead of the total load, and adjust for the room wet-bulb temperature so the unit is not undersized.

  1. Size on peak load, rounding slightly up.
  2. For high sensible-load rooms, size on sensible load.
  3. Adjust for the expected room wet-bulb temperature.

Applies to: All D5CSRA systems

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

Buried refrigerant line limits

Mini-split · Vitocal 100-S

Do not bury more than 36 in (914 mm) of refrigerant pipe. If any section is buried, the pipe must rise at least 6 in (152 mm) to the outdoor unit valve connections. Longer buried runs let refrigerant migrate to the cold section during shutdown and can cause slugging and compressor damage at start-up.

Applies to: DLCURA refrigerant lines

Source: Viessmann DLCURA Service Manual, p. 1. Written in our own words; check the manual for your exact model.

Buried refrigerant pipe limits

Mini-split · Vitocal IND-C

Burying refrigerant pipe deeper or longer than allowed can let refrigerant migrate into the cold buried section during shutdown, causing slugging and possible compressor damage at start-up.

  1. Do not bury more than 36 in. (914 mm) of refrigerant pipe.
  2. If any pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.

Applies to: Refrigerant piping routed underground

Source: DLFSCBH and DLFLCBH installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Check refrigerant charge when the line run is longer than standard

Mini-split · D5CSRA

Each size has a factory charge and a standard piping length of 24.6 ft (7.5 m). Longer runs need extra refrigerant, and total piping is limited by size, up to 213.25 ft (65 m) on the 36K.

  1. Confirm the total line length is within the limit for the size.
  2. For each foot of line beyond 24.6 ft (7.5 m), add refrigerant at the rate shown for the size: 0.16 oz/ft (15 g/m) for 9K to 18K, or 0.32 oz/ft (30 g/m) for 24K to 36K.
  3. Check the height difference between indoor and outdoor units against the size limit.

Applies to: D5CSRA outdoor units

Source: D5CSRA product data, p. 8. Written in our own words; check the manual for your exact model.

Customer handover items

Mini-split · Vitocal IND-F

Walk the customer through the owner's functions with the owner's manual, then leave both manuals with them.

  1. Show how to switch on and off, select COOL, HEAT and other modes, set temperature and timer, and use the display panel.
  2. Show how to remove and clean the air filter.
  3. Show how to set the air deflection louver.
  4. Explain care and maintenance.
  5. Leave the owner's manual and installation instructions with the customer.

Applies to: All sizes

Source: DLFSFA and DLFLFA installation instructions, p. 13. Written in our own words; check the manual for your exact model.

Deep vacuum target before charging

Mini-split · Vitocal IND-O

Deep vacuum to 500 microns is the preferred method for removing air and water from the tubing and indoor coil.

  1. Use a vacuum gauge that reads accurately at 500 microns.
  2. Break vacuums only with dry nitrogen.

Applies to: Refrigerant tubing and indoor coil

Source: DLFSOAH Service Manual, p. 6. Written in our own words; check the manual for your exact model.

Field wiring rules

Mini-split · Vitocal 100-S

Field wiring must be finished by a qualified electrician. Ground the unit per local code and install a current leakage protection device.

  1. Connect power only to terminals L1 or L2. Power on any other terminal damages the control board.
  2. Keep control wiring in a separate conduit from power wiring, at least 12 in (300 mm) apart. Metallic conduit or shielded cable is recommended.
  3. Match wire colours and terminal numbers to the indoor unit.
  4. Tighten all connections firmly. Loose wiring can overheat terminals.
  5. Keep wires clear of refrigerant tubing, the compressor and moving parts.
  6. Provide a disconnect within sight of and readily accessible from the unit.

Applies to: DLCURA field wiring

Source: Viessmann DLCURA Service Manual, p. 3-4. Written in our own words; check the manual for your exact model.

Final checks before handover

Mini-split · Vitocal IND-C

Check the indoor and outdoor unit functions and the drain before handing the system over to the customer.

  1. Confirm all remote control buttons work.
  2. Confirm the display panel lights work.
  3. Confirm the air deflection louver moves.
  4. Confirm the drain works.
  5. Check for unusual noise or vibration at the outdoor unit.
  6. Explain operation, filter cleaning, louver setting and maintenance to the customer, and leave the owner's manual and this manual with them.

Applies to: DLFSCBH / DLFLCBH, sizes 24-48

Source: DLFSCBH and DLFLCBH installation instructions, p. 15. Written in our own words; check the manual for your exact model.

Final tubing check and do not use compressor for vacuum

Mini-split · DLFSHC

Make sure factory tubing has not shifted in shipping and is not rubbing on other tubes or sheet metal. Check the wire ties on the feeder tubes. Never use the system compressor as a vacuum pump.

  1. Check indoor and outdoor factory tubing for shift from shipping.
  2. Check that tubes do not touch each other or sheet metal.
  3. Check that the wire ties on the feeder tubes are secure and tight.
  4. Do not run the compressor to pull vacuum.

Applies to: Refrigerant tubing, all DLFSHC sizes

Source: DLFSHC service manual, p. 9. Written in our own words; check the manual for your exact model.

Fit compressor crankcase heater clamps

Mini-split · D5CSRA

The crankcase heater is standard on all sizes. Its clamps must be placed around the compressor oil sump.

  1. Confirm the crankcase heater is fitted on the compressor.
  2. Place the heater clamps around the compressor oil sump.

Applies to: D5CSRA outdoor units

Source: D5CSRA product data, p. 3. Written in our own words; check the manual for your exact model.

Humidity sensor is inactive on some system types

Mini-split · Vitocal IND-F

The humidity setting is not active when the floor console is matched with a multi-zone outdoor unit or a wired controller is used.

  1. Check the system type before relying on the remote humidity setting.
  2. Use a wired controller or multi-zone match only with the understanding that the humidity sensor is disabled.

Applies to: DRY mode humidity control

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 5. Written in our own words; check the manual for your exact model.

Indoor to outdoor wiring requirements

Mini-split · Vitocal IND-C

Power and communication run as four conductors. Polarity matters, and BX cable is not recommended.

  1. Size wire per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
  2. Use 14/3 stranded wire with ground, 600 V rated, between outdoor and indoor units.
  3. Two conductors carry line voltage, one is communication (S), and one is ground.
  4. Keep the wiring polarity correct between the indoor and outdoor units.
  5. In high EMF areas with communication problems, use 14/2 stranded shielded wire for L2 and S, and land the shield to ground at the outdoor unit only.
  6. Make every connection tight and keep wires clear of refrigerant tubing, the compressor and moving parts.
  7. Provide a disconnect within sight of and readily accessible from the air conditioner.

Applies to: DLFSCBH and DLFLCBH 24K, 36K, 48K

Source: Viessmann Vitocal IND-C ductless technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Indoor unit power supply

Mini-split · Vitocal IND-C

The indoor fan motor runs on 208-230 V. Power is supplied from the outdoor unit, so no separate supply is needed at the indoor unit.

Applies to: DLFSCBH and DLFLCBH, sizes 24K, 36K, 48K

Source: Vitocal IND-C technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Insulate both refrigerant lines separately

Mini-split · DLFSHC

Both refrigerant lines must be insulated on their own. Use the outdoor unit installation instructions for other allowed piping lengths and refrigerant details.

  1. Insulate the liquid line and the suction line separately.
  2. Check the outdoor unit installation instructions for allowed piping lengths and refrigerant data.

Applies to: Refrigerant line install, all DLFSHC sizes

Source: DLFSHC service manual, p. 8. Written in our own words; check the manual for your exact model.

Keep wall clearance and snow height for the outdoor unit

Mini-split · D5CSRA

Use the wall-height clearance table before mounting. The unit cannot be installed where the wall behind it is taller than the unit. Mount the outdoor unit at least 2 in (50 mm) above the deepest expected snow.

  1. Measure the wall height behind the unit and compare it with the unit height.
  2. Keep at least 9.8 in (25 cm) to the wall when the wall is half the unit height or less.
  3. Keep at least 11.8 in (30 cm) when the wall is between half the unit height and the full unit height.
  4. Raise the unit at least 2 in (50 mm) above the expected snow depth.

Applies to: D5CSRA outdoor units

Source: D5CSRA product data, p. 6. Written in our own words; check the manual for your exact model.

Leak testing and lockout

Mini-split · Vitocal IND-C

Never use air or gas containing oxygen for leak testing or for running refrigerant compressors. Mixtures can explode. Before any installation or service, the main disconnect must be off and locked out and tagged.

  1. Use dry nitrogen or other non-oxygen gas for leak testing.
  2. Turn off the main electrical disconnect, lock it out and tag it before working.
  3. Check for more than one disconnect switch.

Applies to: All installation and service work

Source: DLFSCBH and DLFLCBH installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Outdoor unit mounting, leveling and clearance

Mini-split · Vitocal 100-S

Mount the outdoor unit level in all planes, in a spot that can carry its weight, is convenient to install, and is not exposed to strong wind. Keep the minimum clearances from the manual's clearance figure so air can flow freely and service access is kept.

  1. Check the unit is level in all planes before final connection.
  2. Confirm the mounting spot can bear the weight of the outdoor unit.
  3. Keep the minimum clearance shown on the clearance figure (Fig. 6, page 14) for airflow and service.
  4. Make sure air inlets and outlets are not restricted.
  5. Do not install in areas with special environmental conditions without contacting the sales representative.

Applies to: Outdoor unit, 36K-58K

Source: Viessmann DLCLRC technical data manual, p. 30. Written in our own words; check the manual for your exact model.

Outdoor unit power supply

Mini-split · Vitocal 100-S

The DLCURA outdoor unit runs on single-phase 60 Hz power at 208/230 V for the listed sizes. It has one point of electrical connection. Wiring must follow the NEC and local codes. High-voltage and low-voltage terminal blocks are provided.

  1. Confirm the supply is 208/230 V, single-phase, 60 Hz before connecting.
  2. Make one single point power connection to the unit.
  3. Run high-voltage and low-voltage wiring per NEC and local code, using the separate terminal blocks.

Applies to: DLCURA outdoor units, 1.5T to 5T

Source: Vitocal 100-S DLCURA technical data manual, p. 96. Written in our own words; check the manual for your exact model.

Panel installation sequence

Mini-split · Vitocal IND-C

Install the panel only after piping and wiring work is complete.

  1. Finish refrigerant piping and wiring first.
  2. Install the panel afterwards.

Applies to: Cassette indoor unit

Source: DLFSCBH and DLFLCBH installation instructions, p. 7. Written in our own words; check the manual for your exact model.

Power and communication wiring layout

Mini-split · Vitocal 100-S

Main power goes to the outdoor unit only. The indoor unit receives power through the 3-wire link from the outdoor unit. Indoor unit does not need its own disconnect on that link, but a 3-pole disconnect can be added for extra protection.

  1. Feed the main power to the outdoor unit.
  2. Run the 3-wire power link from outdoor to indoor unit.
  3. Run the separate shielded communication wire from outdoor to indoor unit.
  4. Provide a separate supply for any auxiliary electric heater.

Applies to: 36K-58K ductless systems

Source: Viessmann DLCLRC technical data manual, p. 31. Written in our own words; check the manual for your exact model.

Power off before dip switch changes

Mini-split · Vitocal 100-S

Dip switch settings are only read at power-up, so switch power off before changing any of them.

  1. Turn power OFF at the outdoor unit.
  2. Set the dip switches (S1 on the outdoor unit, S4 on the indoor unit).
  3. Restore power.

Applies to: DLCURA outdoor and compatible indoor units

Source: DLCURA technical data manual, p. 83. Written in our own words; check the manual for your exact model.

Refrigerant line connection options

Mini-split · Vitocal IND-C

Refrigerant lines can be oriented to connect from the left, right or back of the unit. Both refrigerant lines must be insulated.

  1. Choose the connection side (left, right or back) for the refrigerant lines.
  2. Insulate both refrigerant lines.

Applies to: DLFSCBH and DLFLCBH

Source: Vitocal IND-C technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Refrigerant line length and insulation

Mini-split · Vitocal IND-C

The minimum refrigerant line length between indoor and outdoor units is 10 ft (3 m). Both refrigerant lines must be insulated separately.

  1. Keep the line run at least 10 ft (3 m).
  2. Insulate the gas and liquid lines separately.

Applies to: Indoor to outdoor refrigerant piping

Source: DLFSCBH and DLFLCBH installation instructions, p. 4. Written in our own words; check the manual for your exact model.

Refrigerant line rules, standard and long line

Mini-split · Vitocal 100-S

The outdoor unit ships with a full R410A charge. Line sizing and capacities are based on 25 ft (7.6 m) runs. Long-line runs keep the same line size but need extra charge.

  1. Check the line set is insulated on both lines with at least 1/2 in (12.7 mm) closed-cell insulation.
  2. Do not bury lines deeper than 36 in (914 mm). Provide at least a 6 in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
  3. Do not bury the lines otherwise; isolate the tubing from the building structure so vibration and noise do not transfer.
  4. For long-line applications, keep the same line size and add refrigerant per the Additional Charge requirement in Table 3, page 5.

Applies to: 36K-58K ductless systems

Source: Viessmann DLCLRC technical data manual, p. 30. Written in our own words; check the manual for your exact model.

Relocate the IR receiver when using a wireless remote

Mini-split · Vitocal IND-F

The factory IR receiver sits inside the control box. It must be moved within line of sight of the remote location. An authorized technician should do this.

  1. Use the 6 ft cable supplied with the kit.
  2. Route the IR receiver to a location in line of sight of where the remote will be used.
  3. Have an authorized technician carry out the work.

Applies to: Wireless remote control installations

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 7. Written in our own words; check the manual for your exact model.

Seal base pan holes only when the condensate must be redirected

Mini-split · D5CSRA

The base pan has several holes for draining during defrost. Rubber plugs are sold separately if the holes must be sealed and the condensate routed elsewhere.

  1. Leave the base pan holes open for normal defrost drainage.
  2. If the condensate must be redirected, fit the rubber plugs listed for the model, using the quantity per unit from the accessory table.

Applies to: D5CSRA outdoor units

Source: D5CSRA product data, p. 3. Written in our own words; check the manual for your exact model.

Troubleshooting order and LED use

Mini-split · Vitocal IND-C

Check the indoor unit diagnostic code first; it gives the most information. The outdoor board has only two LEDs (red and green) and shows a limited set of errors. The manual points to the Service Manual for more detail.

  1. Read the indoor unit lamp pattern and match it to the Table 9 code list.
  2. If the code is not on the indoor display, read the outdoor board red and green LED pattern.
  3. Refer to the Service Manual for detailed diagnosis.

Applies to: DLFSCBH / DLFLCBH, sizes 24-48

Source: DLFSCBH and DLFLCBH installation instructions, p. 16. Written in our own words; check the manual for your exact model.

Wire termination and routing

Mini-split · Vitocal IND-C

Connections must be tight, and no wire may touch refrigerant tubing, the compressor or moving parts. The disconnect must be within sight and readily accessible from the unit.

  1. Tighten every wire connection firmly.
  2. Keep wires clear of refrigerant tubing, compressor and moving parts.
  3. Route the cable through the hole in the conduit panel.
  4. Locate the disconnect within sight of the air conditioner.

Applies to: Indoor and outdoor wiring

Source: DLFSCBH and DLFLCBH installation instructions, p. 5. Written in our own words; check the manual for your exact model.

Additional high limit in multi-tank installations

Water heater · Vitocell 100-V

In a multi-tank system, fit an extra high limit device in the common DHW supply header. Wire it in series with the operating control of the tank battery. Set it about 9°F (5°C) above the operating high limit.

  1. Install an additional high limit in the common DHW supply header.
  2. Wire it in series with the operating control of the tank battery.
  3. Set it approximately 9°F (5°C) higher than the operating high limit.

Applies to: Vitocell 100-V CVWC multi-tank installations

Source: Vitocell 100-V CVWC Technical Data Manual, p. 18. Written in our own words; check the manual for your exact model.

Initial startup and owner handover

Water heater · Vitocell 100-V

A qualified heating contractor must perform the initial startup and complete the Maintenance Record (page 30). Explain normal operation, shutdown and emergency shutdown to the owner, and leave the literature at the site.

  1. Perform initial startup as a qualified heating contractor.
  2. Complete the Maintenance Record (manual page 30).
  3. Show the owner the system operation, shutdown and emergency shutdown steps.
  4. Leave all literature at the installation site and tell the owner where it is kept.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC installation manual, p. 5. Written in our own words; check the manual for your exact model.

Sensor well and clamp use

Water heater · Vitocell 100-V

Use the stainless steel sensor well so the sensing bulb is large enough and well protected. Clamp the capillary bulb against the well with the spring clip for proper contact and heat transfer. Use the sensor clamps for control sensors for maximum operating safety.

  1. Fit the control sensor into the stainless steel well.
  2. Secure the capillary bulb against the well with the spring clip.
  3. Confirm the bulb makes good contact before closing up.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC Technical Data Manual, p. 18. Written in our own words; check the manual for your exact model.

Verify field-supplied controls before startup

Water heater · Vitocell 100-V

The installing contractor must check that field-supplied electrical controls work. These include low-water cut-offs, flow switches if used, staging controls, pumps, motorized valves, air vents, thermostats and temperature controls.

  1. Test low-water cut-offs, flow switches (if used), staging controls, pumps and motorized valves.
  2. Check air vents, thermostats and temperature controls.
  3. Confirm the main power and external controls are de-energized before service work.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC installation manual, p. 4. Written in our own words; check the manual for your exact model.

Other

Everything else worth knowing at the appliance.

ALARM contact (CN33) for external alarm

Air handler · Vitocal IND-A

Dry normally open output that closes when the unit has a fault, which triggers the external alarm or annunciator. The unit supplies no voltage, so the alarm system must provide power. Rated 250 VAC, 10 A maximum.

  1. Wire the alarm interface or annunciator to CN33 with its own power source.
  2. Keep the load within 250 VAC and 10 A.

Applies to: Main board CN33 ALARM terminal

Source: DLFSAB and DLFLAB Service Manual, p. 3. Written in our own words; check the manual for your exact model.

Built-in control functions (guide spec)

Air handler · DLFSDAH, DLFLDAH

Indoor ducted units include automatic restart after power failure at the prior operating conditions, a 24-hour timer for auto start/stop, return air temperature sensing, indoor coil freeze protection, high temperature protection in heat pump mode, dehumidification mode, fan-only operation, user-selectable fan speed or automatic fan, and automatic heating-to-cooling changeover with deadband. Error messages appear on the unit.

Applies to: Indoor ducted units, DLFSDA and DLFLDA

Source: Vitocal IND-D technical data manual, p. 25. Written in our own words; check the manual for your exact model.

Built-in indoor unit control functions

Air handler · Vitocal IND-D, DLFSDAH and DLFLDAH

The indoor unit has automatic restart after power loss, a 24-hour timer for auto start/stop, return-air temperature sensing, indoor coil freeze protection, and wireless infrared remote control. In heat pump mode it also has indoor coil high-temperature protection and a deadband to prevent rapid heating/cooling changeover. Dehumidification and fan-only modes are included. Diagnostics show error messages on the unit.

Applies to: Indoor ducted fan coil units

Source: Vitocal IND-D technical data manual, p. 32. Written in our own words; check the manual for your exact model.

Check capacitors are discharged before troubleshooting

Air handler · Vitocal IND-A

Capacitors keep charge after power is off. Measure the voltage between P and N on the back of the outdoor main PCB. A reading below 36 V means the capacitors are fully discharged. Use anti-static gloves or a wrist strap when handling boards.

  1. Turn off all power and disconnect wires.
  2. Measure the voltage between P and N on the outdoor main PCB with a multimeter.
  3. Continue only if the reading is below 36 V.
  4. Wear anti-static gloves or a wrist strap when touching the indoor or outdoor PCBs.

Applies to: Indoor and outdoor PCB service

Source: Vitocal IND-A DLFSAB/DLFLAB service manual, p. 14. Written in our own words; check the manual for your exact model.

Electric auxiliary heater power

Air handler · Vitocal IND-A

The electric auxiliary heater needs its own power supply.

  1. Do not power the electric heater from the outdoor unit.
  2. Follow the EHKMB installation manual for the heater.
  3. Paste the auxiliary heat wiring diagram supplied with the accessories in its designated spot after installing the heat modules.

Applies to: DLFUAA with EHKMB auxiliary heat

Source: DLFUAA service manual, p. 8. Written in our own words; check the manual for your exact model.

Field water level float switch (CN5)

Air handler · Vitocal IND-A

Input for a field-supplied float switch. Jumper J1 must be removed to enable it. Closed contacts mean normal. Open contacts mean overflow, which sends a signal to the system to shut the unit off.

  1. Remove jumper J1.
  2. Connect the field-supplied float switch to CN5.
  3. Confirm the contacts are closed during normal operation.

Applies to: Main board CN5 WATER LEVEL switch input

Source: DLFSAB and DLFLAB Service Manual, p. 4. Written in our own words; check the manual for your exact model.

Network address for central controller

Air handler · Vitocal IND-A

Micro-switch S1 and dial switch S2 set the network address when a central controller is used. The address range is 00 to 63. The factory setting figure is not legible in this copy, so check the address on the unit before changing it.

  1. Set the address with S1 and S2 in the 00 to 63 range.
  2. Record the address and confirm the central controller communicates with the unit.

Applies to: Micro-switch S1 and dial S2 network address

Source: DLFSAB and DLFLAB Service Manual, p. 6. Written in our own words; check the manual for your exact model.

Power feed and auxiliary heater circuit

Air handler · Vitocal IND-A

Outdoor unit supplies main power to the indoor unit, so turning off the outdoor unit also removes indoor power. No indoor-side disconnect is needed on the link wiring; a 3-pole disconnect may be added for extra protection. The electric auxiliary heater needs its own branch circuit with a field-supplied disconnect within sight of and readily accessible from the unit. Do not connect it to the indoor unit breaker.

  1. Isolate the outdoor unit power when the indoor unit must be de-energised.
  2. Use a separate branch circuit with a disconnect for the auxiliary heater, within sight of the unit.
  3. Do not connect the auxiliary heater to the indoor unit circuit breaker.

Applies to: DLFSAB / DLFLAB with electric auxiliary heater

Source: Vitocal IND-A DLFSAB/DLFLAB service manual, p. 9. Written in our own words; check the manual for your exact model.

Quick maintenance by error code: parts to check

Air handler · Vitocal IND-A

Tables 8 to 11 list parts linked to each error code. The column alignment in the extracted text is not reliable, so use the printed page for part-to-code matching. Parts named in the tables: indoor PCB, outdoor PCB, indoor fan motor, outdoor fan motor, T1, T2, T2A, T2B, T3, T4 and TP sensors, pressure sensor, reactor, compressor, IPM module board, additional refrigerant, water-level switch, water pump, low pressure protector, high pressure protector, high pressure valve assembly, data adapter board, electric control box.

  1. Find the error code in the tables on pages 14 to 16.
  2. Check the listed parts for that code on the printed table.
  3. For some models the outdoor PCB cannot be removed alone. Replace the outdoor electric control box as a whole.

Applies to: DLFUAA indoor and outdoor units

Source: DLFUAA service manual, p. 14-16. Written in our own words; check the manual for your exact model.

Reading the model number

Air handler · Vitocal IND-A

DLF is the indoor unit, S&L is the model, and K means 208/230-1-60 voltage. The fan coil type letter A is the air handler and H is heat pump. The number after the type gives nominal capacity: 18 is 1 1/2 ton, 24 is 2 ton, 30 is 2 1/2 ton, 36 is 3 ton, 48 is 4 ton and 60 is 5 ton. Series and sequence are shown after that, along with week and year of manufacture and serial number.

Applies to: DLFSAB and DLFLAB air handler units, sizes 18 to 60

Source: DLFSAB and DLFLAB Service Manual, p. 2. Written in our own words; check the manual for your exact model.

Remote ON-OFF switch (CN2 and JR1)

Air handler · Vitocal IND-A

Remove jumper JR1 to enable remote ON-OFF control on CN2. An open switch turns the unit off. A closed switch turns it on, and the unit responds within 2 seconds. With the switch on, the remote or wired controller operates the unit normally. With the switch off, the unit ignores controller commands and displays the CP code on the board.

  1. Remove jumper JR1 on the 24V interface board.
  2. Wire the remote switch to CN2.
  3. Close the switch to allow operation, then test the response within 2 seconds.

Applies to: 24V interface board CN2 and JR1

Source: DLFSAB and DLFLAB Service Manual, p. 5. Written in our own words; check the manual for your exact model.

UV LED output (CN43) 24 VAC

Air handler · Vitocal IND-A

Provides 24 VAC through a relay that closes while the fan runs. It can power a compatible UV LED light or a pilot relay with a 24 VAC coil to control other equipment.

  1. Connect a compatible UV LED or a 24 VAC pilot relay coil to CN43.
  2. Confirm the load is compatible with 24 VAC output.

Applies to: Main board CN43 UV LED terminal

Source: DLFSAB and DLFLAB Service Manual, p. 4. Written in our own words; check the manual for your exact model.

Wait before servicing the PCB

Air handler · Vitocal IND-A

Capacitors keep a charge after power is off.

  1. Turn off all power and disconnect wires before working on the unit.
  2. Wear anti-static gloves or a wrist strap when checking the indoor or outdoor PCB.
  3. Wait five minutes after power is off before servicing the PCB, so the capacitors can discharge.

Applies to: DLFUAA indoor and outdoor PCBs

Source: DLFUAA service manual, p. 13. Written in our own words; check the manual for your exact model.

WORK contact (CN23) for blower status

Air handler · Vitocal IND-A

Dry normally open output that follows the indoor blower. It is closed while the blower runs and open when it is off. The unit supplies no voltage here, so the external system must provide the power. Rated 250 VAC, 10 A maximum. If you need a 24 V signal, the G and C thermostat terminals can be used instead.

  1. Wire the external load to CN23 with its own power source.
  2. Keep the load within 250 VAC and 10 A.

Applies to: Main board CN23 WORK terminal

Source: DLFSAB and DLFLAB Service Manual, p. 3. Written in our own words; check the manual for your exact model.

30% LTP package strap-on sensor

Boiler · Vitotronic 100 GC1

The 30% LTP package uses a strap-on sensor (1-17B) on the VD2/VD2A control.

Applies to: VD2/VD2A with 30% LTP package

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 50. Written in our own words; check the manual for your exact model.

aBJ programmable output function

Boiler · Vitocrossal 300 CU3A

The aBJ output is a programmable function output. It can be coded for only one function: alarm output, DHW recirculation pump, field pump or zone circuit pump. Maximum output is 2 FLA.

  1. Select one function for the aBJ output using the coding in the Service Instructions.
  2. Keep the load within 2 FLA.
  3. See the wiring diagram on page 57 for connection to the control base.

Applies to: Vitocrossal 300 CU3A 26 to 199, extension module EA1

Source: Vitocrossal 300 CU3A 26 to 199 Installation Instructions, p. 37. Written in our own words; check the manual for your exact model.

Access the control unit and connection area

Boiler · Vitodens 200-W

Opening the control unit requires removing the junction box cover and the external accessory connection box, then folding down the control unit.

  1. Remove both screws from the junction box cover and set them aside.
  2. Loosen both retaining screws (do not remove), pull the accessory connection box forward until the screws clear the guides, and swing it down.
  3. Tilt the bottom of the cover forward, lift it past the locating pins and remove it.
  4. Close the programming unit cover, release the hinged hooks on both sides of the control unit, and fold it down.
  5. Release the locking tabs and remove the control unit cover.
  6. Touch a grounded object (such as a heating or water pipe) before working to discharge static from electronic modules.

Applies to: Vitodens 200-W B2HB control unit

Source: Vitodens 200-W B2HB installation manual, p. 22-24. Written in our own words; check the manual for your exact model.

Accessing the control unit and wiring

Boiler · Vitodens 200-W B2HB

Access the control unit through the external accessory connection box. Power requires a 120 VAC / 12 A supply.

  1. Remove both screws from the junction box cover and set them aside.
  2. Loosen both retaining screws (do not remove them).
  3. Pull the external accessory connection box forward until the screws clear the rail guides.
  4. Swing the connection box down.
  5. Tilt the bottom of the cover forward, lift it off the locating pins and set it aside.
  6. Close both sides of the programming unit cover.
  7. Release the hinged hooks on both sides of the control unit.
  8. Lift the control unit cover and fold the control unit down.
  9. Release the locking tabs and remove the cover.
  10. Route all connecting cables to their areas and secure them to the control base at the existing strain reliefs.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 22-24. Written in our own words; check the manual for your exact model.

Accessory kit and closing the control cover

Boiler · Vitodens 222-F, B2TB

The mixing valve controller kit can be used as an alternative to a Vitotronic control, but the manual states it works only with wall-mounted boilers and a weather-responsive control, which conflicts with this floor-mounted model. Coding and connection details are in the Service Instructions.

  1. Install the control cover onto the control board.
  2. Flip the control console back into position.
  3. Secure the locking tabs as shown.
  4. Refer to the Service Instructions for coding and control connection.
  5. Refer to the accessory kit Installation Instructions for kit installation.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB Installation Instructions, p. 53. Written in our own words; check the manual for your exact model.

Accessory power supply and disconnect requirements

Boiler · Vitodens 222-F, B2TB

Accessory power outputs at the control are switched by the system on/off switch. The Vitotronic 200-H, HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control need their own 120 VAC supply from a wall receptacle. Install a disconnect switch that isolates all live conductors from the mains, and a GFCI receptacle is also recommended.

  1. Connect accessories that need 120 VAC from their own wall receptacle.
  2. Install a disconnect that isolates all live conductors.
  3. Use a GFCI receptacle as an additional measure.
  4. Only one accessory or switch contact per plug connection at a time.

Applies to: Vitodens 222-F, B2TB (19, 35, 68, 125)

Source: Vitodens 222-F, B2TB installation instructions, p. 43-44. Written in our own words; check the manual for your exact model.

Accessory power supply at the control

Boiler · Vitocrossal 300 CU3A

Accessory power can be taken from the control. It switches on and off with the system on/off switch. The Vitotronic 200-H, the HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control each need their own 120 VAC supply from a wall receptacle.

  1. Connect accessory power at the control so it follows the system on/off switch.
  2. Run a separate 120 VAC wall supply to the Vitotronic 200-H, HK1B, mixing valve kit and Solartrol control.

Applies to: Vitocrossal 300 CU3A boiler accessories

Source: Vitocrossal 300 CU3A installation instructions, p. 56. Written in our own words; check the manual for your exact model.

Acknowledge all pending messages

Boiler · Vitodens 100-W B1HE/B1KE

Clears the acknowledge state of all pending messages.

  1. Call up the home screen.
  2. Open the menu and select Active messages, then tap OK.
  3. Select Acknowledge, then tap OK.
  4. Tap OK to acknowledge the information.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Acknowledge and review active faults

Boiler · Vitocrossal 300

A fault flashes the red fault indicator A and shows 2 and Fault on the display. Acknowledging moves the message to the standard menu and switches off any connected fault output. An unresolved fault comes back the next day and restarts the fault output.

  1. Follow the instructions on the display to acknowledge the fault.
  2. To review active faults later, select Fault in the standard menu.

Applies to: Active fault messages

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 85. Written in our own words; check the manual for your exact model.

Adjust display contrast

Boiler · Vitotronic 200

Changes the display contrast.

  1. Press the two buttons together to darken the display.
  2. Press the two buttons together for the other direction to brighten the display.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 service instructions, p. 24. Written in our own words; check the manual for your exact model.

Adjusting room temperature with an external thermostat

Boiler · Vitodens 100-W, WB1B

With an external room thermostat, set the room temperature on that device. If the room cannot reach the target in cold weather, raise the boiler water temperature with the tr dial. Thermostatic radiator valves in the control room must be fully open.

  1. Set the desired room temperature on the external room thermostat.
  2. Open any thermostatic radiator valves in the room where the control is installed.
  3. If the room stays too cool, increase the boiler water temperature with the tr dial.

Applies to: Vitodens 100-W WB1B

Source: Vitodens 100-W WB1B installation and service instructions, p. 73. Written in our own words; check the manual for your exact model.

Adjusting the adjustable high limit to 100 °C / 212 °F

Boiler · Vitotronic 100, GC1

Changes the adjustable high limit from the factory 95 °C / 203 °F. Limit the DHW temperature when the system feeds a DHW tank.

  1. Disconnect power to the control and burner.
  2. Using a suitable screwdriver, lever out and remove selector knob R behind the hinged cover.
  3. With pointed pliers, break off the cams shaded in the figure from the stop dial.
  4. Refit selector knob R so the marking sits in the centre of the selected range.
  5. Note the coding address 06 setting.

Applies to: Vitotronic 100 GC1 adjustable high limit

Source: Vitotronic 100 GC1 installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

Adjusting the fixed high limit to 99 °C / 210 °F (VD2 only)

Boiler · Vitotronic 100, GC1

Applies to Vitorond 200 VD2 where the factory fixed high limit is 110 °C / 230 °F. Not required for CT3 or CM2.

  1. Disconnect power to the control and burner.
  2. Unclip the fuse box and swing it upwards.
  3. Turn the slotted screw on the rear of the fixed high limit until the slot points to 99 °C / 210 °F.
  4. Refit the fuse box.

Applies to: Vitorond 200 VD2

Source: Vitotronic 100 GC1 installation and service instructions, p. 47. Written in our own words; check the manual for your exact model.

Air pressure switch LDW1 (fan) function

Boiler · Vitocrossal 300 CA3B Dual Fuel

LDW1 is checked during all fan start-up phases and tested during modulation. It causes a fault shutdown if the cold-state checkup fails after about 5 minutes, if pre-aeration pressure is out of range for about 5 minutes, or if the switch fails or pressure is out of range in normal operation. Shown as F F5 or F F7, released with reset button R.

  1. Check the fan and the LDW1 switch and hose if F F5 or F F7 appears.
  2. Press reset button R to release the shutdown once the cause is cleared.

Applies to: LDW1 air pressure switch (fan)

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 62. Written in our own words; check the manual for your exact model.

Air pressure switch LDW2 (combustion chamber) function

Boiler · Vitocrossal 300 CA3B Dual Fuel

LDW2 is checked in every operating phase except safety and stabilization times. It shuts the burner down if chamber pressure is out of range after two attempts during pre-aeration, normal operation or post-purge. The fault is shown as F Fb and is released with the reset button R.

  1. Check chamber pressure if F Fb appears.
  2. Press reset button R to release the shutdown once the cause is cleared.

Applies to: LDW2 air pressure switch (combustion chamber, non-adjustable)

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 62. Written in our own words; check the manual for your exact model.

Air vent and drain tubing

Boiler · Vitotron 100 VLN2

The air vent sits on top of the heat exchanger and removes air from the boiler.

  1. Confirm the plastic drain tubing from the air vent is still in place.
  2. Confirm the tubing exits the boiler in the lower right corner.
  3. Purge air from the whole system and its components.

Applies to: Vitotron 100 VLN2 heat exchanger

Source: Vitotron 100 VLN2 installation and service instructions, p. 8-9. Written in our own words; check the manual for your exact model.

Air venting between trap and neutralization unit

Boiler · Vitodens 100-W B1HE/B1KE

Pipe ventilation must be provided between the siphon trap and the neutralization unit.

  1. Vent the piping between the siphon trap and the neutralization unit, where one is fitted.

Applies to: Condensate neutralization

Source: Vitodens 100-W, B1HE/B1KE Installation/Service, p. 20. Written in our own words; check the manual for your exact model.

Alcove top clearance depends on the control

Boiler · Vitorond 100 VR1

Alcove top clearance is 6 in (150 mm) in the standard listing. With Vitotronic control the top clearance is 24 in.

Applies to: Alcove installs

Source: Vitorond 100 VR1 technical data manual, p. 6. Written in our own words; check the manual for your exact model.

Alternative DHW connection piping layout

Boiler · Vitodens 222-F, B2TB

Reference piping layout for connecting the domestic hot water (DHW) system to the boiler. Key parts: boiler heat exchanger, DHW heat exchanger, boiler pump, DHW circulating pump, diverting valve, expansion tank, flow check valve, water softener if fitted, and temperature and pressure relief valve outlet. Check the legend letters against the drawing on site.

Applies to: Vitodens 222-F, B2TB (19, 35, 68, 125)

Source: Vitodens 222-F, B2TB installation instructions, p. 40. Written in our own words; check the manual for your exact model.

Alternative DHW connection with diverting valve

Boiler · Vitodens 222-F

Alternative piping where the boiler heats a separate DHW heat exchanger through a diverting valve, instead of the integrated tank. Includes an optional DHW recirculation loop.

  1. Pipe the boiler supply and return to the diverting valve and the boiler heat exchanger as shown.
  2. Connect the DHW heat exchanger and the DHW storage tank.
  3. Install a water softener on the DCW inlet where water hardness requires it.
  4. If a DHW recirculation pump is used, install a flow check valve in the recirculation line.
  5. Fit the temperature and pressure relief valve outlet and pressure relief valve outlet to drains.

Applies to: Vitodens 222-F B2TB, external DHW storage with diverting valve

Source: Vitodens 222-F, B2TB installation instructions, p. 40. Written in our own words; check the manual for your exact model.

Altitude derate for input capacity

Boiler · Vitocrossal 300 CA3B Dual Fuel

Input must be derated for elevation. Up to 4,999 ft, derate 3% per 1,000 ft. From 5,000 to 10,000 ft, with the electronic altitude adjustment made, derate an extra 0.6% per 1,000 ft, for a total derate of 18%.

  1. Check the installation altitude.
  2. Up to 4,999 ft, derate input 3% per 1,000 ft.
  3. From 5,000 to 10,000 ft, make the electronic altitude adjustment, then derate an additional 0.6% per 1,000 ft (18% total).

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service, p. 153. Written in our own words; check the manual for your exact model.

Altitude operation without input derate

Boiler · Vitocrossal 200 CI2

The Lambda PrO2 combustion system adjusts the burner to oxygen level at each input rate. Combined with the electronic elevation setting in the boiler software, the boiler runs up to 10,000 ft (3,000 m) without input derate.

  1. Set the elevation in the boiler software for the install altitude.
  2. Confirm combustion values with the combustion test at commissioning.

Applies to: Vitocrossal 200 CI2, all sizes

Source: Vitocrossal 200 CI2 service instructions, p. 99. Written in our own words; check the manual for your exact model.

AM1 pump connections A1 and A2

Boiler · Vitodens 200-W

Up to two circulation pumps can be connected to outputs A1 and A2: heating circuit pump without mixing valve or zone pump, DHW tank heating pump, or DHW recirculation pump.

  1. Assign the pump function to each output with the codes on the boiler control unit.
  2. Follow the AM1 module installation instructions.

Applies to: AM1 extension module

Source: Vitodens 200-W B2HA service instructions, p. 89. Written in our own words; check the manual for your exact model.

Annual inspection and service

Boiler · Vitodens 100-W B1HE/B1KE

The boiler, burner and controls must be checked at least once a year by the original installer or a competent heating contractor. Defects must be corrected right away.

  1. Schedule a service inspection once a year, ideally before the heating season.
  2. Follow the Viessmann maintenance schedule and the cleaning and maintenance steps in the installation instructions.
  3. Correct any defects found immediately.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Viessmann Vitodens 100-W B1HE/B1KE operating instructions, p. 2, p. 5, p. 6. Written in our own words; check the manual for your exact model.

Annual magnetic filter cleaning

Boiler · Vitotron 100 VLN2

The magnetic filter protects the flow sensor inside the boiler. Clean it at least once a year, because residue left in the filter can contaminate the boiler.

  1. Remove the pre-installed magnetic filter.
  2. Clean the filter.
  3. Reinstall the filter and check system pressure.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 18. Written in our own words; check the manual for your exact model.

Annual service and owner handover

Boiler · Vitorond 200 VD2

Once installation is complete, the contractor must train the owner and state that annual professional service is needed before each heating season.

  1. Walk the owner through the equipment, safety requirements and shutdown procedure.
  2. Tell the owner professional service is needed every year before the heating season.
  3. Follow the Viessmann maintenance schedule in the Service Instructions manual.

Applies to: Vitorond 200 VD2

Source: Vitorond 200 VD2 installation instructions, p. 2. Written in our own words; check the manual for your exact model.

Annual service requirement

Boiler · Vitocrossal 300 CU3A

The boiler, burner and controls must be checked at least once a year by the original installer or a competent heating contractor. Defects must be corrected immediately.

  1. Schedule a yearly inspection by a qualified heating contractor before the heating season.
  2. Correct any defects found right away.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 2, p. 7. Written in our own words; check the manual for your exact model.

Antifreeze and water quality

Boiler · Vitorond 100 VR1

Treat feed water where minerals or hardness are high. Antifreeze may be used where freezing can occur, but only glycol made for hot water heating systems.

  1. Do not use automotive silicate-based antifreeze.
  2. A 40% antifreeze content gives freeze protection to -10 °F (-23 °C).
  3. Follow the antifreeze manufacturer's specifications.
  4. Check the system frequently when filled with antifreeze.
  5. Provide the system owner an MSDS for the antifreeze and advise that the system contains glycol.
  6. Check whether antifreeze may need a backflow preventer, and check diaphragm tanks and radiation for compatibility.

Applies to: System water treatment

Source: Vitorond 100, VR1 Technical Data, p. 11. Written in our own words; check the manual for your exact model.

Antifreeze and water treatment

Boiler · Vitorond 200, VD2A

Use only antifreeze made for hot water heating systems and follow the antifreeze maker's specifications.

  1. Consider water treatment where feed water has high mineral content or hardness.
  2. Use 40% antifreeze content to protect to -10°F (-23°C).
  3. Do not use automotive silicate-based antifreeze.
  4. Check the whole system often when it is filled with antifreeze, and check for a backflow preventer in the auto fill line.

Applies to: Vitorond 200 VD2A hydronic systems

Source: Vitorond 200 VD2A installation manual, p. 34. Written in our own words; check the manual for your exact model.

Appendix B relay state references

Boiler · Versatronik 505 NR2/BACIP, Versatronik 505D NR2/BACIP

Relay state values are listed in Appendix B, which is outside these pages.

Applies to: AI6, AI12, AI18, AI24, AI26

Source: Versatronik 505 and 505D BACnet IP manual, p. 21. Written in our own words; check the manual for your exact model.

Applicable boiler controls

Boiler · Versatronik 511 / 511D

The gateway works with these Viessmann controls: Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2, Vitotronic 300 GW5B, Vitotronic 200 HO1 and Vitodens 200 B2HA. The Type B gateway is for multi-LON boiler controls that do not talk to a Vitocontrol Cascade control.

Applies to: Versatronik 511 and 511D Type B gateways

Source: Versatronik 511 & 511D LON Type B manual, p. 1; p. 3. Written in our own words; check the manual for your exact model.

Applicable codes for installation

Boiler · Vitocrossal 300 CA3B Dual Fuel

Installation must follow local codes first. Where no local code applies, the listed national codes are used.

  1. Canada gas: CAN/CSA-B149.1 or .2.
  2. USA gas: National Fuel Gas Code ANSI Z223.1.
  3. Canada electrical: CSA C22.1 Part 1 and/or local codes.
  4. USA electrical: National Electrical Code ANSI/NFPA 70.
  5. Controls and safety devices: ANSI/ASME CSD-1 where the authority having jurisdiction requires it.

Applies to: All installations

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Application 10 application code

Boiler · Vitocrossal 300 CU3A

Application 10 is identified by the application code 4CU3I 2HC2ZP.01 printed on the drawing.

Applies to: Vitocrossal CU3A Application 10

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 58. Written in our own words; check the manual for your exact model.

Application 1: hydraulic separation with low loss header or closely spaced tees

Boiler · Vitodens 222-F

Separates the boiler loop from the system loop so their flows do not affect each other. The boiler circulator P1 is built in. A low loss header sensor can be added for better control and efficiency.

  1. Install a low loss header or closely spaced tees on the system loop.
  2. Confirm the boiler flow is within its recommended range (see sizing and flow pages referenced in the manual).
  3. Connect the outdoor sensor and the low loss header sensor if used.
  4. Connect the thermostat, or use a Vitotrol 200-A or 300-A in place of a standard thermostat.
  5. Set the application code VD2T 1HC1T1ZP.01 as shown in the manual.

Applies to: Vitodens 222-F Application 1

Source: Vitodens 222-F application guide, p. 26, p. 27, p. 28. Written in our own words; check the manual for your exact model.

Application 5 system overview

Boiler · Vitodens 222-F

Low temperature heating circuit with a 3-way mixing valve (HC2), plus a high temperature zone (ZC1). The ZC1 call starts the 28/20 plug pump for the high temperature zone. HC2 mixing follows the heating curve set in the boiler control.

  1. Wire the ZC1 thermostat to the DE connections and the pump to the 28/20 output.
  2. Leave the HC2 mixing valve on the boiler heating curve settings.

Applies to: Vitodens 222-F, B2TB, Application 5

Source: vitodens_222_application_guide.pdf, p. 48. Written in our own words; check the manual for your exact model.

Application 6 wiring and thermostat notes

Boiler · Vitodens 222-F

Thermostats may be replaced by Vitotrol room controls to give a communicating room control. Only one control can be selected per heat circuit, either a thermostat or a Vitotrol. The P1 boiler circulator is built into the boiler. External flow check valves are not needed where they are built into the circulators.

  1. Pick one control per heat circuit: a thermostat or a Vitotrol.
  2. Do not add external check valves where the circulators already have them.
  3. Use the sizing and flow pages referenced in the manual for pump and flow sizing.

Applies to: Vitodens 222-F, B2TB, Application 6

Source: vitodens_222_application_guide.pdf, p. 50-51. Written in our own words; check the manual for your exact model.

Application 8 design notes

Boiler · Vitocrossal 300 CU3A

Design notes for the Application 8 layout.

  1. Note that the air handler circulator is not controlled by the boiler, so higher than design water temperatures can reach the air handler during DHW calls.
  2. CU3A is a high mass boiler, so primary/secondary piping is not required.
  3. The low loss header can be replaced with closely spaced tees (see Application 9).
  4. Cascade control max load is 6 amps. Use isolation relays if multiple circulators and mixing valve motors are used.
  5. P5 is controlled internally by the air handler.
  6. Verify mixing valve motor stroke direction with an actuator test (see Cascade Control Installation & Service Manual).

Applies to: Application 8 (2CU3I 3HC/ZC3ZP.01)

Source: Vitocrossal 300 CU3A application guide, p. 50-52. Written in our own words; check the manual for your exact model.

Application 8 operating concept

Boiler · Vitocrossal 300 CU3A

Low temperature heat circuit with motorized mixing valve, hot water forced air fan coil, indirect DHW, and a two-boiler cascade with low loss header. The cascade control targets the highest system temperature. The mixing valve sets supply temperature for the low temperature circuit regardless of the temperature for the other circuits. Allows turndown, boiler redundancy, higher input, and simultaneous heating and DHW.

Applies to: Application 8

Source: Vitocrossal 300 CU3A application guide, p. 49. Written in our own words; check the manual for your exact model.

Application 9 application code

Boiler · Vitocrossal 300 CU3A

Application 9 is identified by the application code 2CU3I 4HC4ZP.01 printed on the drawing.

Applies to: Vitocrossal CU3A Application 9

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 56. Written in our own words; check the manual for your exact model.

Application 9 design notes

Boiler · Vitocrossal 300 CU3A

Design notes for the Application 9 layout with three heating circuits and a heat exchanger.

  1. External flow check valves are not needed if the circulators already have them built in.
  2. HC3 is separated from the system by a heat exchanger. An automatic fluid feeder may be desired.
  3. Based on recommended piping practice, install a pressure relief valve on the secondary side of the heat exchanger.
  4. Cascade control max load is 6 amps. Use isolation relays if multiple circulators and mixing valve motors are used.
  5. Verify mixing valve motor stroke direction with an actuator test (see Cascade Control Installation and Service Manual).

Applies to: Application 9 (2CU3I 4HC4ZP.01)

Source: Vitocrossal 300 CU3A application guide, p. 50-52. Written in our own words; check the manual for your exact model.

Application code 2CU3I 3HC/ZC3ZP.01

Boiler · Vitocrossal 300 CU3A

Application code for Application 8, the two-boiler cascade with mixing valve, air handler, and indirect DHW.

Applies to: Application 8

Source: Vitocrossal 300 CU3A application guide, p. 50-52. Written in our own words; check the manual for your exact model.

Application code 2CU3I 4HC4ZP.01

Boiler · Vitocrossal 300 CU3A

Application code for Application 9, the layout with four heating circuits and a heat exchanger.

Applies to: Application 9

Source: Vitocrossal 300 CU3A application guide, p. 50-52. Written in our own words; check the manual for your exact model.

Application index for Vitodens 222-F B2TB

Boiler · Vitodens 222-F

Application codes listed in the guide and the pages where each is shown.

  1. Application 1: VD2T 1HC1T1ZP.01, page 26.
  2. Application 2: VD2T 1HC1T4ZV.01, page 30.
  3. Application 3: VD2T 1HC1T4ZP.01, page 34.
  4. Application 4: VD2T 2ZC2T2ZP.01, page 38.
  5. Application 5: VD2T 2ZC/HC2T2ZP.02, page 42.
  6. Application 6: VD2T 3HC3T3ZP.01, page 46.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F application guide, p. 11. Written in our own words; check the manual for your exact model.

Approved boilers for KW10B

Boiler · Vitotronic 100

This control is only approved for use with the Vitola 200, Vitorond 100, Vitogas 050, RS Series, or Vitogas 100 hot water heating boilers. Applies to serial no. V00101 and later.

Applies to: Vitotronic 100 KW10B, serial no. V00101 and up

Source: Vitotronic 100 KW10B installation manual, p. 7. Written in our own words; check the manual for your exact model.

Balanced flue and combustion air inlet setup

Boiler · Vitodens 222-F

A factory vent adaptor C comes installed. Run the vent single-wall or coaxial through the side wall or roof on the shortest route, rising at least 3 degrees. Support the piping so it does not rest on the boiler.

  1. Remove the outer gasket from vent adaptor C if using a single-wall, room-air-dependent system.
  2. For B2TB combustion air, remove inlet seal A, tear out the center section, and reinstall the rubber seal in the air inlet opening.
  3. Seal or shield building surfaces exposed to flue products (e.g. aluminum sheeting) before attaching the vent termination.
  4. Install the vent termination on the leeward side of the building where possible.
  5. Connect the balanced flue per the Venting System Installation Instructions.

Applies to: Vitodens 222-F B2TB

Source: Viessmann Vitodens 222-F B2TB installation manual, p. 13 and p. 15. Written in our own words; check the manual for your exact model.

Barometric draft regulator type and size

Boiler · Vitorond 200 VD2A

Choose the regulator type by fuel. The regulator opening must match the chimney it serves, not the boiler breeching.

  1. On natural gas or propane, use a double-acting barometric draft regulator.
  2. On No. 2 fuel oil, use a single-acting barometric draft regulator.
  3. Size the regulator opening to the chimney diameter the vent is designed for.
  4. Do not size the regulator to the boiler breeching outlet unless the chimney is the same diameter.

Applies to: Vitorond 200 VD2A oil and gas boilers

Source: Vitorond 200 VD2A technical data manual, p. 24. Written in our own words; check the manual for your exact model.

Basic display shows boiler sequence

Boiler · Vitocontrol-S

The default screen shows the boiler sequence and boiler temperature. It returns to this screen after each setting is entered.

  1. Confirm the basic display after a setting is entered.
  2. If the screen does not change, wait for it to time out to the boiler sequence view.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Basic display shows supply temperature

Boiler · Vitotronic 200-H

In the basic display the window shows the supply temperature in degrees C. A participant check message appears when no other control units are connected, or when several interconnected control units are installed.

Applies to: Vitotronic 200-H HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Basic display shows the boiler sequence

Boiler · Vitocontrol-S

In normal operation the Vitocontrol-S display shows the boiler sequence. It returns to that view after every setting you make.

  1. After you finish a setting, wait for the display to return to the boiler sequence view.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Before servicing: power and gas isolation

Boiler · Vitocrossal 300 CA3B Dual Fuel

Isolate all power and the gas supply before any service work to prevent accidental start-up.

  1. Turn off main power to the boiler, heating system and all external controls.
  2. Close the main gas supply valve.
  3. Keep precautions in place so power is not restored during work.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Blocked vent safety switch (Canada)

Boiler · Vitorond 100

Canadian installations include a blocked vent safety switch in the vent connection. Install it per the instructions in the manual.

  1. Locate the blocked vent safety switch shown in the venting connection drawing.
  2. Install it according to the manual instructions before commissioning.

Applies to: Vitorond 100 VR1 boilers sold in Canada

Source: Vitorond 100 VR1 installation and service instructions, p. 18. Written in our own words; check the manual for your exact model.

Board and module reference in wiring summary

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

Reference list of the component IDs used in the connection and wiring diagrams: A2 low voltage motherboard, A3 line voltage motherboard, A6 programming unit, A7 Optolink PCB and override switch, A8 supplementary PCB, A9 boiler coding card, A10 LON communication module, A11 power supply PCB, A12 boiler control unit.

Applies to: Vitotronic 100 GC1 wiring

Source: Vitocontrol-S, VD2/CT3/CM2 Installation and Service Instructions, p. 184. Written in our own words; check the manual for your exact model.

Boiler 3 data points readable via Versatronik 503 on a Vitogate 300

Boiler · Versatronik 503

The Vitogate 300 does not recognise the Versatronik 503 and cannot talk to the target boiler directly. It can still read some boiler 3 values through the cascade control, for example on a GW6B lead control.

  1. Read AI:1085 - 1.1 for boiler 3 output value.
  2. Read AI:1050 - 1.1 for boiler 3 water temperature.
  3. Read AI:1059 - 1.1 for boiler 3 set water temperature.
  4. Read MI:1033 - 1.1 for boiler 3 fault.
  5. Read MI:1013 - 1.1 for boiler 3 operating mode.

Applies to: Vitogate 300 with GW6B lead control

Source: Versatronik 503 NR2/Analog Bridge installation and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Boiler cleaning interval

Boiler · Vitotronic 300-K, Vitotronic 100

Boiler contamination raises flue gas temperature and energy losses.

  1. Clean all boilers annually

Applies to: Vitotronic 300-K MW1B / Vitotronic 100 GC1B

Source: Vitotronic 300-K MW1B / Vitotronic 100 GC1B operating instructions, p. 36. Written in our own words; check the manual for your exact model.

Boiler control and harness mounting

Boiler · Vitorond 200

The control housing and burner harness bracket mount to the side panel. Capillaries and the boiler sensor must stay away from heat sources such as the vent, chimney and supply or return piping.

  1. Drill the four mounting holes on the side panel as shown (mirror the drawing for left-side mount) and punch the 7/8 in. (22 mm) opening.
  2. Install the control harness bracket with the supplied 8-32 self-tapping screws.
  3. Install the burner harness bracket with two supplied screws.
  4. Remove the two plugs on the back of the control housing and mount it on the side panel with two screws.
  5. Run capillaries and the boiler temperature sensor through the side opening and insert the sensor into the sensor well as far as possible.
  6. Install the top panels and the name plate.
  7. In Canada, install the oil door safety switch per its separate instructions.
  8. Follow the boiler control installation instructions for electrical connections.

Applies to: Vitorond 200 VD2A boiler

Source: Vitorond 200, VD2A Series Installation, p. 27-28. Written in our own words; check the manual for your exact model.

Boiler controls the gateway supports

Boiler · Versatronik 505 & 505D

The gateway is listed for the Vitocontrol-S, Vitotronic 300-K, 100, 300 (GW2, GW5B), 200 and Vitodens 200 B2HA controls. Each control has its own communication setup and connection detail.

Applies to: Versatronik 505 and 505D

Source: Versatronik 505 & 505D BACnet IP gateway manual, p. 1. Written in our own words; check the manual for your exact model.

Boiler exposed to water

Boiler · Vitocrossal 200 CM2

Do not run the boiler if any part was under or exposed to water.

  1. Do not use the boiler.
  2. Call a qualified heating contractor to inspect the boiler.
  3. Have the control system and any gas control that were exposed to water replaced.

Applies to: All CM2 models

Source: Vitocrossal 200 CM2 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Boiler has been under water

Boiler · Vitocrossal 300 CU3A

A boiler that has been flooded must not be used. The control system and any gas control that was under water must be replaced.

  1. Do not use the boiler.
  2. Call a qualified heating contractor to inspect the boiler.
  3. Have any control system part and any gas control that was under water replaced.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Boiler isolation valve must be power open, spring return

Boiler · Vitocrossal 200 CI2

Boiler isolation valves must be power open with spring return. Viessmann sells them as accessories.

  1. Select a power open, spring return isolation valve.
  2. Match the valve size to the boiler model.

Applies to: Boiler isolation valves

Source: Vitocrossal 200 CI2 installation instructions, p. 33. Written in our own words; check the manual for your exact model.

Boiler location and flue gas system

Boiler · Vitodens 222-F

The boiler is a direct vent appliance and can be installed for sealed combustion regardless of room size or ventilation. It can go in living areas, unventilated utility rooms, cupboards, closets, alcoves with no combustible clearance, and attics with a direct outlet for the flue. Use the Viessmann PPS concentric flue system for sealed combustion or side wall venting, certified with the boiler. Vertical venting is possible with AL29-4C single-wall room-air-dependent venting (UL listed Category IV). See the Venting System Installation Instructions for details.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 16. Written in our own words; check the manual for your exact model.

Boiler location restrictions

Boiler · Vitocrossal 200 CM2

Do not install the boiler where halogenated hydrocarbons can reach the combustion air, such as in barber shops, beauty salons, print shops, chemical cleaners or laboratories. Boiler efficiency depends on return water temperature and load.

  1. Check the installation room for halogenated hydrocarbons before installing.
  2. Keep the boiler room frost-free and properly ventilated.

Applies to: Vitocrossal 200 CM2 186 to 620

Source: Vitocrossal 200 CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Boiler number shown in multi-boiler systems

Boiler · Vitotronic 200

In a multi-boiler system each Vitotronic 200 shows its boiler number on the standard display, next to the boiler water temperature.

Applies to: Vitotronic 200 (type H01B) in multi-boiler systems

Source: Vitotronic 200 and 300-K operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Boiler pump may run continuously after reset

Boiler · Vitodens 200-W B2HA

After a reset of the Vitodens 200 B2HA, coding address 30:0 can change to 30:3, which makes the boiler pump run continuously.

  1. Verify that coding address 30:0 is set.
  2. Adjust to 30:0 if necessary (see page 54).

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 service instructions, p. 79. Written in our own words; check the manual for your exact model.

Boiler pump runs continuously after switching to multi-boiler operation

Boiler · Vitodens 200-W B2HA

In multi-boiler operation, coding address 30:0 can change to 30:3 on its own, which makes the boiler pump run continuously.

  1. Verify that coding address 30:0 is set on each boiler.
  2. Set 30:0 if necessary (see page 59).

Applies to: Vitodens 200 B2HA in multi-boiler systems

Source: Vitodens 200-W B2HA service instructions, p. 84. Written in our own words; check the manual for your exact model.

Boiler pump runs continuously in multi-boiler setup

Boiler · Vitodens 200-W B2HA

When switched from single boiler to multi-boiler operation, coding address 30:0 may reset to 30:3, making the boiler pump run continuously.

  1. Verify coding address 30:0 on each boiler.
  2. Adjust to 30:0 if necessary (see page 54).

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 78. Written in our own words; check the manual for your exact model.

Boiler reporting 0 degrees is skipped

Boiler · Versatronik 581 / 581D

A boiler that reports 0 degrees boiler water temperature has all its other points skipped. This speeds up the refresh of the points for boilers that are present, because the gateway does not poll a boiler that is not there.

Applies to: Default 8-boiler GW6B configuration

Source: Versatronik 581 LON gateway manual, p. 13. Written in our own words; check the manual for your exact model.

Boiler room location and air quality

Boiler · Vitocrossal 200 CM2

Halogenated hydrocarbons or aggressive chemicals in the combustion air can corrode the heat exchanger.

  1. Do not install the boiler where halogenated hydrocarbons are present in the combustion air, such as barber shops, beauty salons, printing shops or chemical cleaners.
  2. Keep chemicals such as bleach, hair spray, methyl chloride, carbon tetrachloride or perchloroethylene out of the boiler room.
  3. Keep the boiler room free of high dust or humidity levels.

Applies to: All CM2 models

Source: Vitocrossal 200 CM2 operating instructions, p. 6, 8. Written in our own words; check the manual for your exact model.

Boiler room location and combustion air restrictions

Boiler · Vitocrossal 300 CA3B Dual Fuel

Do not install the boiler where halogenated hydrocarbons are in the combustion air, such as in barber shops, beauty salons, print shops, chemical cleaners or laboratories. The boiler room must be frost-free and well ventilated.

  1. Check that the combustion air is free of halogenated hydrocarbons.
  2. Keep the boiler room frost-free and ventilated.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Boiler room location and flue gas temperatures

Boiler · Vitocrossal 300 CA3B

Do not install the boiler where halogenated hydrocarbons are present in the combustion air. Flue gas temperature varies with boiler water temperature.

  1. Keep the boiler room free of frost and properly ventilated.
  2. Avoid locations such as barber shops, beauty salons, print shops, chemical cleaners and laboratories.
  3. Flue gas temperature may range from 77°F (25°C) to 257°F (125°C) depending on boiler water temperature.

Applies to: Vitocrossal 300 CA3B, all sizes 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 10. Written in our own words; check the manual for your exact model.

Boiler section count and lead/lag layout

Boiler · Vitocrossal 300 CA3B Dual Fuel

Models 2.5, 3.0, 3.5 and 4.0 have two boiler sections. Models 5.0 and 6.0 have three. In a single boiler, section A is the lead (section 1), B is lag 1 (section 2), and C is lag 2 on the 5.0 and 6.0 (section 3). In multi-boiler systems the first boiler's controls show all sections. A minimum of 4 and a maximum of 8 boiler sections are allowed.

  1. Confirm the number of boiler sections for the model.
  2. In a multi-boiler system, set up the lag control on the 2nd, 3rd or 4th boiler.

Applies to: Vitocrossal 300 CA3B Dual Fuel, 2.5 to 6.0 and multi-boiler systems

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Boiler section status symbols

Boiler · Vitocrossal 300 CA3B Dual Fuel

The flame symbol shows the heat output of each boiler section. A solid white circle means the section is enabled and running, a solid grey circle means it is available but not called, and a crisscrossed circle means it is unavailable. The number under the circle shows current output.

  1. Flame with one line long: 1 to 33% output.
  2. Flame with half length: 34 to 66% output.
  3. Flame at full length: 66 to 100% output (67 to 100% on the service display).
  4. Solid white circle: enabled and operating.
  5. Solid grey circle: available, not called.
  6. Crisscrossed circle: unavailable.

Applies to: Vitocrossal 300 CA3B Dual Fuel programming unit and service display

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 15-16. Written in our own words; check the manual for your exact model.

Boiler sequence icons in the standard menu

Boiler · Vitotronic 300-K

Solid white: boiler enabled by the cascade and operating. Solid grey: available but not enabled. Solid black and crossed out: not available for heat production.

Applies to: Vitotronic 300-K (type MW2B) cascade

Source: Vitotronic 200 and 300-K operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Boiler serial number for parts orders

Boiler · Vitodens 200-W B2HA

Parts orders need the 16-digit boiler serial number from the bar code label, or the 12-digit ASME/NB serial. Both are under the front enclosure panel. Some parts are not reverse compatible with earlier B2HA versions.

  1. Remove the front enclosure panel to read the serial number.
  2. Quote the serial number on every parts order.

Applies to: Vitodens 200-W B2HA 45, 60 parts ordering

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.

Boiler timeout after five minutes with no data

Boiler · Versatronik 581 / 581D

If a boiler sends no data for five minutes, the gateway treats it as offline and reports zero for all its points. The gateway skips that boiler until it reports a non-zero boiler water temperature. This applies to LON communication between boilers only, not KMK.

Applies to: LON cascade communication

Source: Versatronik 581 LON gateway manual, p. 13. Written in our own words; check the manual for your exact model.

Boiler water temperature is set by the Vitocontrol-S

Boiler · Vitocontrol-S

In a multi-boiler system the Vitocontrol-S sets the boiler water temperature for every boiler control unit. This cannot be changed on the Vitotronic 100, GC1.

  1. Make the boiler water temperature change on the Vitocontrol-S, not on the Vitotronic 100.

Applies to: Vitocontrol-S with Vitotronic 100 GC1 boilers

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 15. Written in our own words; check the manual for your exact model.

Breech draft check

Boiler · Vitorond 100 VR1

Required flue draft is -0.02 in w.c. Draft at the breech is typically between -0.02 and -0.08 in w.c. Use a sized chimney that meets local and national codes wherever possible.

Applies to: All VR1 sizes

Source: Vitorond 100 VR1 technical data manual, p. 4, 7. Written in our own words; check the manual for your exact model.

Brief scan of temperatures, software and connected parts

Boiler · Vitodens 200-W B2HA

Shows temperatures, software versions and connected components on a 9-line by 6-field display.

  1. Open the service level.
  2. Select Diagnosis, then Brief scan.
  3. Press OK. The display shows 9 lines with 6 fields each.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.

Built-in battery disposal

Boiler · Vitotronic 200-H

The control unit has a built-in non-toxic battery. A competent person should remove it. Dispose of depleted batteries at a proper collection point.

  1. Have a competent person remove the battery.
  2. Dispose of the battery at an appropriate collection point.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Built-in frost protection thresholds

Boiler · Vitodens 100-W B1HE/B1KE

Frost protection is always active. The burner fires when boiler water reaches 41°F (5°C) and shuts off again once water reaches at least 59°F (15°C), but no more than 68°F (20°C).

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Burner connection

Boiler · Vitotronic 100

The RAST-5 plug goes to the control PCB and the 7-pole plug goes to the burner or wall vent system counter plug. Do not connect the 41-plug from the boiler control directly to the burner when installing a wall vent system.

  1. Connect the RAST-5 plug to the main control circuit board.
  2. Connect the 7-pole plug to the burner counter plug, or to the wall vent system counter plug if one is installed.
  3. Do not connect the 41-plug directly to the burner when a wall vent system is used.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 13. Written in our own words; check the manual for your exact model.

Burner control display layout and exit

Boiler · Vitocrossal 200 CM2

The four-digit display has a status display and a service display, plus LEDs for heat demand, flame, maintenance and fault. Standard mode scrolls through the operating states. In a fault state the status display shows the current condition after pressing reset.

  1. Press and hold the reset button for more than 2 seconds to exit any display or menu.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 42. Written in our own words; check the manual for your exact model.

Burner control terminals T6, T7, T8

Boiler · Vitotronic 100

Terminals T6, T7 and T8 carry the control signal for a two-stage burner or a modulating burner. Two-point control gives two-stage operation; three-point control gives modulating direction. Control to burner and burner to control signal directions are both marked on the terminal diagram.

  1. Confirm burner type (two-stage or modulating) before wiring T6, T7 and T8.
  2. Use the 2-stage/modulating burner extension as described in its installation instructions.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 13. Written in our own words; check the manual for your exact model.

Burner control unit component key

Boiler · Vitocrossal 300 CA3B Dual Fuel

Key components on the burner control unit connection diagram that are used when troubleshooting burner fault codes.

  1. Gas pressure switch at first valve seat: check when F6 or E1/E2 is shown.
  2. Gas valves V1 and V2: check connecting cable and replace if the fault points to the gas valve.
  3. Inlet fan pressure switch (APS1) and overfire pressure switch (APS2): check when F5 or F7 is shown.
  4. Fan motor with PWM control: check when F9, Fa or varying fan speed is shown.
  5. Ignition unit and flame sensor: check when F4 is shown.
  6. Burner damper servomotor: check when F3 poor start-up is shown.
  7. Vitotronic control unit: check the KM BUS connection when F0 is shown.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 131. Written in our own words; check the manual for your exact model.

Burner control unit display and buttons

Boiler · Vitocrossal 300 CA3B Dual Fuel

Each burner control unit has an integrated display with a status display (A), a service display (B), reset button (C/R), LEDs (D: heat demand, flame, maintenance, fault), a selection button (F) and cursor buttons (E/G). In normal mode the status display shows the current operating condition, and after reset it shows the fault condition. Faults are shown with fault codes.

  1. Read the status display for the current operating condition.
  2. After a fault, press reset R to see the fault condition.
  3. Hold reset R for 0.5 to 10 seconds to exit the current display.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 20. Written in our own words; check the manual for your exact model.

Burner fault codes are in the burner section

Boiler · Vitocrossal 300 CA3B Dual Fuel

Burner faults show on the control unit display, but the burner fault code list is not on these pages. Use the burner section of the manual, which starts on page 53.

  1. Refer to the burner section starting on page 53 for burner fault codes.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 128. Written in our own words; check the manual for your exact model.

Burner fault codes are serviced in the burner section

Boiler · Vitocrossal 300 CA3B Dual Fuel

Burner fault codes are shown on the control unit display. Service the burner using the burner section of the manual.

  1. Read the burner fault code on the control unit display.
  2. Refer to the burner section starting on page 53 to service the burner.

Applies to: Burner fault codes F0 to Fd

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 128. Written in our own words; check the manual for your exact model.

Burner head material temperature rating

Boiler · Vitorond 200 VD2

The combustion burner head material must be rated for at least 932°F (500°C).

  1. Check that the burner head material is rated for at least 932°F (500°C).

Applies to: All VD2 models 320 to 1080

Source: Vitorond 200 VD2 technical data manual, p. 7. Written in our own words; check the manual for your exact model.

Burner installation and fuel selection

Boiler · Vitorond 200

Only approved oil or gas burners may be used. Order the burner for a specific fuel or as a combination burner. The combustion chamber must run under positive pressure. Keep all burner components protected from water.

  1. Confirm the burner is ordered for the correct fuel: #2 fuel oil or natural gas or LP.
  2. Make sure the blast tube protrudes at least 4.5 in. (110 mm) into the boiler from the front edge of the burner plate.
  3. Fill the gap between the blast tube and the insulation insert on the combustion chamber door with the supplied insulating material.
  4. Seal the sight glass for pressure tightness.
  5. Connect the sight glass to the burner with the supplied clear plastic hose.
  6. Protect the boiler and burner from dripping, spraying and rain during operation and service.

Applies to: Vitorond 200 VD2A boiler

Source: Vitorond 200, VD2A Series Installation, p. 32. Written in our own words; check the manual for your exact model.

Burner modulation percentage is approximate

Boiler · Versatronik 501

The nvoBStatus value gives modulation in percent for boilers 1 to 4 (one byte each). It is only a control approximation and does not show the true burner position. Check the burner manufacturer documentation for actual position.

Applies to: Versatronik 501 gateway modulation status

Source: Versatronik 501 NR2/LON communication manual, p. 20. Written in our own words; check the manual for your exact model.

Burner mounting and door insulation

Boiler · Vitorond 200 VD2

The burner must be fitted to the burner plate. Direct mounting to the boiler door is not allowed. Viessmann supplies a pre-drilled end burner plate that matches the supplied burner dimensions. For blast tube diameters of 7 to 11 in. (180 to 280 mm) the door refractory can be cut to size. The blast tube must extend past the thermal insulation on the boiler door.

  1. Fit the burner to the pre-drilled burner plate, not to the boiler door.
  2. For blast tubes 7 to 11 in. (180 to 280 mm), cut the door refractory to the required size.
  3. Make sure the blast tube protrudes past the door insulation.

Applies to: All VD2 models 320 to 1080

Source: Vitorond 200 VD2 technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Burner mounting on the burner plate

Boiler · Vitorond 200 VD2A

The burner must be mounted to the burner plate, not directly to the boiler door. The blast tube must protrude through the door insulation.

  1. Mount the burner to the supplied pre-drilled end burner plate.
  2. For blast tubes over 6 in (150 mm), cut the door refractory insulation to size.
  3. Confirm the blast tube protrudes from the door insulation.

Applies to: Vitorond 200 VD2A burner installation

Source: vitorond 200 VD2A technical data manual, p. 9. Written in our own words; check the manual for your exact model.

Burner terminal reference

Boiler · Vitotronic 300

Terminal codes on the burner connection: L1 is line via safety high limit, PE is ground, N is neutral, T1 and T2 are the control circuit, S3 is the burner fault input, and B4 is the operating hours counter input.

Applies to: Vitotronic 300 KW3

Source: Vitotronic 300 installation instructions, p. 17. Written in our own words; check the manual for your exact model.

Burner wiring: follow the burner maker's drawing

Boiler · Vitotronic 100 GC1, Vitotronic 300-K MW1S

The burner connection drawing in the manual is generic. Use the burner manufacturer's Viessmann control drawings for the real wiring, and mark the terminal numbers on the drawing for future reference.

  1. Get the burner manufacturer's connection drawing for Viessmann controls.
  2. Mark the terminal numbers or markings on the drawing.
  3. Keep the burner power supply in mind, since it is not shown on the generic drawing.

Applies to: Any burner connected to the Vitotronic

Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 48. Written in our own words; check the manual for your exact model.

Cable routing near the boiler

Boiler · Vitotronic 300 GW6B

Keep control and sensor wiring away from heat.

  1. Route cables through the boiler front panel into the control wiring chamber.
  2. Never let cables touch hot metal components.
  3. Secure the cables to the top rail with cable ties and route through the cable retainers.

Applies to: Control unit wiring

Source: Vitotronic 300 GW6B installation and service manual, p. 26. Written in our own words; check the manual for your exact model.

Cable strain relief at the control unit

Boiler · Vitotronic 100 GC1

Cables run from the connection enclosure into the control unit and need strain relief.

  1. Run the cables from the connection enclosure into the control unit.
  2. For cables with moulded strain relief, connect the cable and the strain relief clamp.
  3. Otherwise, fasten the cable to the cable lead with a cable tie.

Applies to: Vitotronic 100 GC1 installation

Source: Vitotronic 100, GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 37. Written in our own words; check the manual for your exact model.

Call up acknowledged fault messages

Boiler · Vitocrossal 200 CI2

Lists earlier fault messages that were acknowledged but may still be relevant. They appear in time order.

  1. Open the main menu.
  2. Tap "Message lists".
  3. Review the fault list in chronological order.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 58. Written in our own words; check the manual for your exact model.

Call up active fault messages

Boiler · Vitocrossal 200 CI2

When a fault is present the display shows the fault message. If a central fault facility is connected it is also started.

  1. Tap the fault button in the footer to show the fault messages.
  2. Read the fault code and look it up in the fault table.
  3. Tap to hide the fault messages when finished.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 58. Written in our own words; check the manual for your exact model.

Call up fault history

Boiler · Vitodens 200-W B2HA

The last 10 faults, including resolved ones, are stored and sorted by date.

  1. Enter the service level (OK and the second key for about 4 seconds).
  2. Select Fault history.
  3. Select Display? and review the fault codes.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 70. Written in our own words; check the manual for your exact model.

Call up help messages

Boiler · Vitocrossal 200 CI2

Help messages explain the displays and functions.

  1. Tap the help icon to show help messages.
  2. Tap the back icon to return to the previous screen.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Calling up and acknowledging fault messages

Boiler · Vitotronic 300-K

Fault messages appear in red. Acknowledging stops the signal device. Faults that cannot be fixed now return the next day and the alarm is switched back on.

  1. Tap the fault symbol in the footer. The fault list appears.
  2. Tap a fault to see its information and self-help tips.
  3. Note the fault code and cause. Example code shown: f0 Combustion controller.
  4. Tap Close, then notify the heating contractor.

Applies to: Heating system

Source: Vitotronic 300-K MW2C operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Calling up and confirming service messages

Boiler · Vitotronic 300-K

Service messages appear in orange. If a service cannot be done yet, the message returns the following Monday until the heating contractor resets the interval.

  1. Tap Confirm. The footer shows the service symbol.
  2. Tap the service symbol in the footer to show the list.
  3. Notify the local heating contractor.

Applies to: Heating system

Source: Vitotronic 300-K MW2C operating instructions, p. 25. Written in our own words; check the manual for your exact model.

CAN bus subscriber numbers and electronics modules

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

When troubleshooting, note the subscriber number shown with the fault and check that component. Modules: A = BCU burner control unit, B = HMU heat management unit with wiring panel, C = HMI programming unit with WiFi module.

  1. Subscriber 1: HMU heat management unit.
  2. Subscriber 50: BCU burner control unit.
  3. Subscriber 58: communication module (TCU 200).
  4. Subscriber 59: HMI programming unit.
  5. Subscriber 60: fan unit.
  6. To find the module, check the rotary switch S1 on the module if needed.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 69, 71. Written in our own words; check the manual for your exact model.

Capability expansions available with Vitotronic 200 and 300

Boiler · Switching Module-V

Supported functions: remote burner disable, external heat demand, external heat demand (2nd stage with two-stage burners), remote switching of operating mode to continuous reduced operation and back, short-term DHW recirculation pump operation, external fault input, and connection of a compiled fault indicator.

Applies to: Switching Module-V

Source: Switching Module-V installation instructions, p. 1. Written in our own words; check the manual for your exact model.

Capillary handling warning (CM2)

Boiler · Vitotronic 100 GC1

Damaged capillaries cause control malfunction.

  1. Do not bend or kink the capillaries.

Applies to: CM2 control installation

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm before start-up

Boiler · Vitocrossal 300 CU3A

The installer must confirm that at least one carbon monoxide alarm is installed in the living space before the appliance is put into operation. Alarms must be installed, maintained and replaced per the alarm maker's instructions and local codes.

  1. Confirm at least one CO alarm is installed in the living space before commissioning.
  2. Follow the alarm manufacturer's instructions and local codes for installation and replacement.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm before startup

Boiler · Vitocrossal 200 CI2

A carbon monoxide alarm must be in place in any residential living space before the appliance is started.

  1. Install at least one carbon monoxide alarm in the residential living space or home.
  2. Follow the alarm maker's instructions and local codes.
  3. Confirm the alarm is installed before putting the boiler into operation.

Applies to: Vitocrossal 200 CI2 installations in residential buildings

Source: Viessmann Vitocrossal 200 CI2 Installation Instructions, p. 5. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm requirement

Boiler · Vitocrossal 300 CA3B

Carbon monoxide can be produced by incomplete combustion. The installer must confirm an alarm is in place before start-up.

  1. Confirm at least one carbon monoxide alarm is installed in the living space before the boiler is put into operation.
  2. Install, maintain and replace alarms per the alarm maker's instructions and local codes.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Carbon monoxide and venting

Boiler · Vitotronic 200, Vitotronic 300-K

Improper installation, adjustment, service or maintenance can let flue gas, which contains carbon monoxide, enter the living space. Never run the boiler without an installed venting system. Carbon monoxide detectors should be installed and maintained in line with local rules.

  1. Check that the venting system is installed and connected before operating the boiler.
  2. Check that vents and chimneys are not blocked or partly blocked.
  3. Check for moisture, water or rust on flue pipes, joints, dampers and side wall terminals.
  4. Confirm that carbon monoxide detectors are installed as local regulations require.
  5. Follow the installation instructions for mechanical room and venting requirements.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 2, 5, 6. Written in our own words; check the manual for your exact model.

Carbon monoxide detector and gas vent signage (Massachusetts)

Boiler · Vitodens 200-W B2HA

Applies to side-wall horizontally vented gas equipment in residential buildings where the vent terminal is less than 7 ft above finished grade.

  1. Confirm a hard-wired CO detector with alarm and battery backup is installed on the floor level where the boiler is located.
  2. Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level served.
  3. If the boiler is in a crawl space or attic, the hard-wired detector may be on the next adjacent floor level.
  4. If the requirement cannot be met at completion, the owner has 30 days. A battery-operated CO detector with alarm must be installed in the meantime.
  5. Use CO detectors that meet NFPA 720, are ANSI/UL 2034 listed and IAS certified.
  6. Mount a metal or plastic sign on the building exterior at least 8 ft above grade, directly in line with the vent terminal. Lettering must be at least 1/2 in. and must state the gas vent is directly below and to keep the area clear of obstructions.
  7. Note that the state or local gas inspector will not approve the installation without the detectors and sign.

Applies to: Vitodens 200-W B2HA 19, 28, 35 on Massachusetts installations

Source: Vitodens 200-W B2HA service instructions, p. 8. Written in our own words; check the manual for your exact model.

Carbon monoxide detector and signage for low side-wall vents (Massachusetts)

Boiler · Vitodens 200-W B2HB

For side-wall horizontally vented gas equipment in dwellings where the vent termination is under 7 ft above grade, Massachusetts rules apply. Hard-wired CO detectors with battery backup go on the floor level of the install and battery or hard-wired detectors on each additional level. A sign is required 8 ft above grade in line with the vent.

  1. Install a hard-wired CO detector with battery backup on the floor level where the gas equipment is installed.
  2. Install a battery or hard-wired CO detector with alarm on each additional level served.
  3. Mount the metal or plastic sign at least 8 ft above grade, directly in line with the vent terminal, reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS, with letters at least 1/2 inch.

Applies to: Side-wall horizontally vented installs in Massachusetts

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 7. Written in our own words; check the manual for your exact model.

Carbon monoxide detector and signage requirements (Massachusetts)

Boiler · Vitodens 200-W

For side-wall horizontally vented installations in Massachusetts, a hard-wired CO detector with battery backup must be on the floor level where the gas equipment is installed, and detectors must be on each additional level. Signage is also required. Exemptions apply to certain equipment and to units in a separate structure.

  1. Confirm a hard-wired CO detector with alarm and battery backup is installed on the equipment's floor level.
  2. Confirm a battery or hard-wired CO detector is installed on each additional level.
  3. Confirm the required metal or plastic sign is mounted at least 8 ft above grade in line with the vent terminal.

Applies to: Side-wall horizontally vented installations in Massachusetts

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Carbon monoxide detector and signage rules for Massachusetts side-wall venting

Boiler · Vitocrossal 300 CA3B Dual Fuel

For side-wall horizontal venting where the exhaust termination is under 7 ft above grade, Massachusetts rules require hard-wired CO detectors with battery backup on each level and a warning sign at the vent. The sign must be at least 8 ft above grade, in line with the vent.

  1. Install a hard-wired CO detector with alarm and battery backup on the floor level where the gas equipment is located.
  2. Install a battery-operated or hard-wired CO detector on each additional level served.
  3. Mount a metal or plastic sign reading "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS" at least 8 ft above grade, in line with the vent.

Applies to: Massachusetts side-wall horizontal venting with exhaust under 7 ft

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 5. Written in our own words; check the manual for your exact model.

Carbon monoxide detector requirement (Massachusetts)

Boiler · Vitodens 200-W B2HA

For side-wall horizontally vented gas equipment with the vent termination under 7 ft above grade, Massachusetts rules require CO detectors with alarm and battery backup on the floor where the appliance is installed, plus detectors on each additional level. A metal or plastic sign reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS must be mounted at least 8 ft above grade in line with the vent terminal. If the detector cannot be installed at completion, a battery detector is required for 30 days.

Applies to: Installations in the Commonwealth of Massachusetts

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 8. Written in our own words; check the manual for your exact model.

Carbon monoxide detectors

Boiler · Vitocrossal 300 CA3B

The U.S. Consumer Product Safety Commission recommends CO detectors in buildings with gas-burning equipment. Installers must follow local rules.

  1. Install carbon monoxide detectors that meet a recognized standard (e.g. ANSI/UL 2034, CSA 6.19-01) where local rules require them.
  2. Maintain the detectors.
  3. Make sure the installation and service of the boiler are done properly to avoid carbon monoxide formation.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 operating instructions, p. 2, p. 6. Written in our own words; check the manual for your exact model.

Carbon monoxide detectors and venting

Boiler · Vitodens 200-W B2HB

Improper installation, adjustment, service or maintenance can let flue gas into living space. The boiler must never run without an installed venting system.

  1. Never run the boiler without the venting system connected.
  2. Follow local rules for installing carbon monoxide detectors.
  3. In Massachusetts, sidewall-vented gas equipment with the vent less than 7 ft above grade needs hard-wired CO detectors with battery backup on the floor where the gas equipment is installed, and a warning sign 8 ft above grade in line with the vent terminal. The sign must read "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, pp. 2, 7. Written in our own words; check the manual for your exact model.

Carbon monoxide detectors in Massachusetts

Boiler · Vitodens 200-W

For side-wall horizontally vented gas equipment in Massachusetts where the vent termination is less than 7 feet above grade, a hard-wired CO detector with alarm and battery backup is required on the floor level of the equipment, plus detectors on each additional level. A warning sign must be placed on the exterior 8 feet above grade in line with the vent.

  1. Confirm hard-wired CO detectors with battery backup are installed on the equipment floor level.
  2. Confirm battery or hard-wired CO detectors are installed on each additional level.
  3. Confirm the exterior sign reads "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS" at 8 feet above grade.

Applies to: Side-wall horizontally vented installations in Massachusetts

Source: Vitodens 200-W B2HB Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Cascade addressing for GW6B and MW2C controls

Boiler · Versatronik 585

Cascade controls must use fixed LON addresses so the gateway can find every boiler.

  1. On Vitotronic 300 GW6B used as master cascade control, set the control to LON address 1 at coding address 77 for the master or lead boiler.
  2. Set the following boilers to LON addresses 2 to 8.
  3. For Vitotronic 300-K MW2C (Vitodens B2HA), set AO2 Cascade Config to 1 so the cascade is at address 9.
  4. Set the MW2C to LON address 77 with a value of 9, so the boilers run from LON address 1 to 8.
  5. If boiler communication uses KMK instead of LON, set AO3 Comm Config to 1.

Applies to: Vitotronic 300 GW6B cascade, Vitotronic 300-K MW2C (Vitodens 200, B2HA)

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 15. Written in our own words; check the manual for your exact model.

Cascade adjustment strategies

Boiler · Versatronik 300

Pure modulation staging: raise Stage On (up to about 10C/18F or 15C/27F) so boilers are not forced on by temperature. Set Maximum Burner Mod to the point where the next boiler should start; each boiler then comes on at that value. To stage off sooner, set Minimum Burner Mod above the 30% default. Temperature dependent: keep Stage On at factory default or lower it so boilers are brought on faster. Each boiler still modulates to its own set point.

Applies to: Versatronik 300 cascade control

Source: Versatronik 300 Cascade Control manual, p. 36. Written in our own words; check the manual for your exact model.

Cascade control unit roles

Boiler · Vitocrossal 300 CA3B Dual Fuel

Control unit A runs as the system and lead boiler section 1 control, with the cascade role shown as 'Lead boiler + cascade'. Control units B and C run as lag boiler section controls. Unit C applies to 5.0 and 6.0 models only.

  1. Identify the control units: A = system and lead boiler section 1, B = boiler section 2, C = boiler section 3 (5.0 and 6.0 only).
  2. Use the fuel selector switch D as needed for the fuel in use.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 32. Written in our own words; check the manual for your exact model.

Cascade default display

Boiler · Vitocrossal 200 CI2

Cascade displays show all cascade participants, the current supply temperature and target supply temperature. The lead boiler is marked with a star. Each participant's status and burner run hours can be viewed. Emissions test mode can be run only on a lag appliance. Dynamic control strategy is described elsewhere in the manual.

  1. Check the star to confirm which boiler is the lead appliance.
  2. Open a participant to see its status and burner run hours.
  3. Use the all-on function only to switch on standby-deactivated displays of cascade participants.
  4. Run emissions test mode only on a lag appliance.

Applies to: Vitocrossal 200 CI2 cascade systems

Source: Vitocrossal 200 CI2 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Category I vent installation practices

Boiler · Vitorond 200

Category I venting is for natural gas or LP and must use approved vent material. The boiler must not connect to any mechanical draft system under positive pressure. Keep the vent run short with few elbows and avoid long horizontal runs. Correct any downdraft or condensation problems.

  1. Locate the boiler as close to the chimney as possible and use the shortest vent path with minimal elbows.
  2. Rearrange existing water piping if needed to shorten the vent connection.
  3. Support horizontal runs to prevent sagging and check the rise per the venting dimensions.
  4. Drill a 1/2 in. (13 mm) test opening on the side of the vent pipe about three vent diameters from the flue collar for combustion analysis.
  5. Where the boiler vents into a masonry or unlined chimney, install an approved stainless steel liner.
  6. Observe local codes for any vent into a chimney or breeching shared with a direct-fired gas water heater.

Applies to: Vitorond 200 VD2A boiler, Category I

Source: Vitorond 200, VD2A Series Installation, p. 30. Written in our own words; check the manual for your exact model.

Category III positive pressure venting

Boiler · Vitorond 200

The Vitorond 200 is a Category III positive pressure non-condensing boiler and must be vented individually. The vent must be gas tight and use a suitable stainless steel system listed for Category III.

  1. Use an AL29-4C special stainless steel venting system listed for Category III for single-wall vertical venting.
  2. Connect the flue outlet with the shortest run, a slight upward slope to the stack, and no sharp bends. Flue outlet outside diameter is 8 in. (200 mm).
  3. Drill a 10 mm test hole in the side of the vent pipe about two to three vent diameters from the flue collar.
  4. Seal and insulate the vent pipe.
  5. Follow the Viessmann positive pressure venting system instructions for details.

Applies to: Vitorond 200 boiler, Category III

Source: Vitorond 200, VD2A Series Installation, p. 31. Written in our own words; check the manual for your exact model.

Central control of heating circuits (coding 7a)

Boiler · Vitocrossal 300 CA3B Dual Fuel

Coding 7a in the General group sets central control to one heating circuit. Its operating and holiday program then applies to all other heating circuits.

  1. When the central operating and holiday program is enabled, 'Central control' is shown on the other heating circuits.
  2. Any holiday programs previously set on those circuits are deleted.
  3. Party and economy modes are not available on all control units.

Applies to: Multiple heating circuits

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 40. Written in our own words; check the manual for your exact model.

Central heating without DHW heating

Boiler · Vitotronic 300-K

No program exists for central heating alone. Hot water is normally also required in winter.

  1. Select the heating program Heating and DHW
  2. Set the DHW temperature to 50 F (10 C) so DHW is not heated unnecessarily, while DHW tank frost protection is kept

Applies to: Vitotronic 300-K MW1B

Source: Vitotronic 300-K MW1B / Vitotronic 100 GC1B operating instructions, p. 40. Written in our own words; check the manual for your exact model.

Centralized operation display

Boiler · Vitotronic 200-H

If centralized operation is coded on a boiler and heating circuit or cascade control, the heating and holiday program settings are accepted from the central unit.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Change or delete a time phase

Boiler · Vitocrossal 200 CI2

Edit the start point of an existing time phase, or remove a phase from one day.

  1. Select the heating circuit and the day.
  2. Select the time phase with the arrow.
  3. To change the start, set the new time and the temperature level, then confirm.
  4. To delete, use the X and confirm.
  5. Exit the time program.

Applies to: Time programs

Source: Vitocrossal 200 CI2 Operating Instructions, p. 19. Written in our own words; check the manual for your exact model.

Change the central heating time program

Boiler · Vitocontrol-S, VD2/CT3/CM2

Set the on and off times for up to four central heating phases, either the same for all days or separately for each weekday.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the time program button until 'Central heating time program' shows in the display.
  4. Choose '1-7' for the same phases every day, or a weekday (Mo, Tu, etc.) for individual days, then confirm.
  5. Set the phase 1 ON time, then confirm, then set the phase 1 OFF time, then confirm.
  6. Repeat for phases 2 to 4. Skip a phase by pressing the skip button.
  7. Close the hinged cover. After the finishing time of phase 4 is confirmed, the display shows the boiler sequence.

Applies to: Central heating time program

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Check active messages by type

Boiler · Vitodens 100-W B1HE/B1KE

Lists are shown by type: Burner faults, Faults, Warnings, Maintenance, Status and Information. Only types with current messages are listed.

  1. Call up the home screen and open the menu.
  2. Select Active messages, then tap OK.
  3. Select the required message type, then tap OK.
  4. Select the required message, then tap OK.
  5. Read the message details.
  6. Hold the exit button for about 4 seconds to leave the menu.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Check and acknowledge service messages

Boiler · Vitocrossal 200 CI2

Service messages are listed in yellow. If the service cannot be done yet, the message appears again the following Monday. When the contractor's service interval is exceeded, a 'Service' message appears automatically. The contractor's contact details show if available.

  1. Tap the navigation area.
  2. If fault messages are present, open 'Faults', then 'Service messages'.
  3. Tap a message to see details and self-help tips.
  4. Write down the service message number and notify your contractor.
  5. Acknowledge the service if needed.

Applies to: Service messages menu

Source: Vitocrossal 200 CI2 operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Check and replace refractory ring and DHW tank burner

Boiler · Vitodens 200-W B2HA

Inspect the burner refractory ring and the DHW tank burner assembly for damage and replace if needed. Use a calibrated torque wrench for the fasteners.

  1. Remove the electrode block and ionization electrode.
  2. Release the three retaining clips on the refractory ring and remove the ring.
  3. Remove the four Torx screws, then the DHW tank burner assembly and its assembly gasket.
  4. Fit the new DHW tank burner assembly and new gasket. Tighten to 3.3 lb.ft (4.5 Nm).
  5. Refit the refractory ring and secure with the retaining clips.
  6. Refit the electrode block and ionization electrode. Tighten to 3 lb.ft (4 Nm).

Applies to: Vitodens 200-W B2HA

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 25. Written in our own words; check the manual for your exact model.

Check communication with the boiler

Boiler · Versatronik COMO OT

When the communication symbol shows on the display, data exchange with the boiler is working. If it is not shown next to the clock, the boiler data cable is faulty or disconnected.

  1. Look for the communication symbol next to the clock.
  2. If it is absent, check the data cable to the boiler.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 31 and p. 32. Written in our own words; check the manual for your exact model.

Check controls and wiring before troubleshooting

Boiler · Vitotronic 100

Before troubleshooting any fault, confirm the system controls work and the wiring is sound.

  1. Check that all controls operate properly, such as thermostats and the low water cut-off.
  2. Check that all wire connections are tight and secure.

Applies to: Vitotronic 100 KW10B boiler systems

Source: Vitotronic 100, KW10B Operating and User's Information manual, p. 8. Written in our own words; check the manual for your exact model.

Check estimated energy consumption

Boiler · Vitodens 100-W B1HE/B1KE

The value is calculated and may differ from actual consumption. It is not suitable for billing.

  1. Call up the home screen.
  2. Select Energy metering, then confirm with OK.
  3. Select Consumption, then confirm with OK.
  4. Select the current month or last month, then confirm with OK.
  5. Read off the value.
  6. Press and hold the exit button for about 4 sec to leave the menu.

Applies to: Energy metering

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Check heating circuit allocation

Boiler · Vitotronic 200-H

Confirm the heating circuit allocation label is on the matching array of the programming unit before making changes.

  1. Check that the heating circuit allocation label is affixed to the correct array on the programming unit.
  2. Select the corresponding heating circuit before adjusting any settings.

Applies to: Vitotronic 200-H programming unit

Source: Vitotronic 200-H installation and service instructions, p. 13. Written in our own words; check the manual for your exact model.

Check heating zone status on a lead or lag boiler

Boiler · Vitocrossal 200 CI2

Shows the status of heating zones from a cascade lead or lag boiler.

  1. Select the device status of the lead or lag boiler.
  2. On the lead boiler, tap the symbol in the middle of the screen.
  3. Read the heating zone status.

Applies to: Cascade systems

Source: Vitocrossal 200 CI2 Operating Instructions, p. 22. Written in our own words; check the manual for your exact model.

Check operating data and burner runtime

Boiler · Vitocrossal 200 CI2

Reads current output, hours run, burner runtime, burner starts and other data.

  1. Open the main menu and select Information.
  2. Select the data group.
  3. Retrieve the data.

Applies to: Vitocrossal 200 CI2 boiler

Source: Vitocrossal 200 CI2 Operating Instructions, p. 17. Written in our own words; check the manual for your exact model.

Check system information

Boiler · Vitocrossal 200 CI2

Shows current system data such as temperatures. Groups: General, Burner, DHW, Heating circuit 1 to 4, Heating zones 1 to 4, Contractor contact details, Internet, Open source licence, Cascade and Cascade boilers. Named heating circuits and zones show their assigned names.

  1. Open Information.
  2. Select the required group.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Check system information (temperatures and pump data)

Boiler · Vitodens 100-W B1HE/B1KE

Shows current system data such as temperatures, including temperature controller and heating circuit pump information. Detailed groups are in the menu overview.

  1. Call up the home screen.
  2. Select Information, then confirm with OK.
  3. Select the required group, then confirm with OK.
  4. Select the required information.
  5. Press and hold the exit button for about 4 sec to leave the menu.

Applies to: System information

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 23. Written in our own words; check the manual for your exact model.

Checking live values under the Information menu

Boiler · Vitocrossal 300 CU3A, Vitotronic 200 KW6B

The Information menu lets you scan live readings and status. Under General it lists outside temperature, boiler temperature, flue gas temperature, sensor 9, burner status, operating hours and per-stage hours run, fuel consumption, feed pump, and the compiled fault message. Under Solar, DHW and each heating circuit it lists temperatures, pump and valve status, time programs and operating status. Which scans appear depends on the equipment fitted, so some may be missing.

  1. Open the extended menu and select Information.
  2. Pick the group you need: General, DHW, Solar, or the heating circuit.
  3. Scroll the list and read the value or status shown.

Applies to: Vitocrossal 300 CU3A boilers with Vitotronic 200 KW6B control

Source: Vitocrossal 300 CU3A 26 to 199 Operating Instructions, p. 41. Written in our own words; check the manual for your exact model.

Chemicals not to store near boiler

Boiler · Vitocrossal 200 CI2

Chemicals in the air can form poisonous and corrosive combustion by-products. Keep these away from the boiler and boiler room.

  1. Do not store chlorine products, bleach, cleaning solvents, detergents, acids, hair spray, spray cans, paint thinners, paint, water softener salt, perchloroethylene, or carbon tetrachloride near the boiler.

Applies to: Boiler room storage

Source: Vitocrossal 200 CI2 Installation Instructions, p. 55. Written in our own words; check the manual for your exact model.

Chilled water and cooling season valve changeover

Boiler · Vitocrossal 200 CI2

With a refrigeration system, pipe the chilled medium in parallel with the boiler and fit valves so chilled water cannot enter the boiler. Flow control valves or other automatic means must stop gravity circulation of boiler water during cooling. The boiler circulating pump must run from its own on/off switch, not from the boiler control. Valves V1 and V2 are changed over by season, and metal tags should label them.

  1. Pipe the chilled medium in parallel with the boiler.
  2. Install valves so chilled water cannot enter the boiler.
  3. Install flow control valves or equivalent to prevent gravity circulation during cooling.
  4. Power the circulating pump from a separate on/off switch, not the boiler control.
  5. Cooling season: close valve V1 and open valve V2.
  6. Heating season: close valve V2 and open valve V1.
  7. Attach metal tags to label valves V1 and V2.

Applies to: Vitocrossal 200 CI2 with chilled water or refrigeration system

Source: Vitocrossal 200 CI2 Installation Instructions, p. 46. Written in our own words; check the manual for your exact model.

Chimney and draft regulator requirements

Boiler · Vitorond 200

The boiler is not approved for side wall venting. The chimney must be designed for the relatively cool flue gases. Vent collar diameter does not set chimney size. Insulate the connection length between the vent collar and chimney. If a calculated diameter falls between two sizes, use the larger one.

  1. Do not vent through a side wall. Vent all products of combustion to the outdoors.
  2. Insulate the chimney connection between the vent collar and the chimney.
  3. Install a barometric draft regulator in the chimney or vent 5 to 7 ft. (1.5 to 2 m) from the breeching outlet at the rear of the boiler.
  4. Do not stand on the top panel when installing or insulating overhead piping or venting.

Applies to: Vitorond 200 VD2A boiler

Source: Vitorond 200, VD2A Series Installation, p. 29. Written in our own words; check the manual for your exact model.

Chimney sizing and intermediate venting

Boiler · Vitorond 100 VR1

Chimney must be sized for the flue gas temperatures this boiler produces. Oversized, poorly insulated chimneys let gases cool and condense. If the calculated diameter falls between two sizes, use the larger.

  1. Keep the intermediate vent section the same diameter as the boiler vent collar.
  2. Keep the path between boiler and chimney as short as possible, with no more than two elbows.
  3. Avoid two level 90° elbows in a row.
  4. Seal the intermediate section pressure tight at the boiler collar and chimney connection, including any combustion test ports.
  5. Install a barometric damper.

Applies to: Chimney venting

Source: Vitorond 100, VR1 Technical Data, p. 10. Written in our own words; check the manual for your exact model.

Choose an operating program when heat or hot water is not needed

Boiler · Vitocrossal 300

Operating programs reduce energy use when full heating is not required.

  1. For summer with hot water only, select "Only DHW".
  2. If the home needs no heat and no hot water for longer periods, select "Standby mode".
  3. For a short absence, select "Economy mode" to reduce room temperature.
  4. For a longer absence, select the "Holiday program", which lowers room temperature and turns off DHW heating.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Circuit diagrams are recommendations only

Boiler · Vitotronic 100, GC1

The circuit diagrams are recommendations. The customer or heating contractor must confirm the design is complete and fully functional.

  1. Check the hydraulic and electrical design is complete and functional before final commissioning.

Applies to: All circuit diagrams 5 to 9

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Circulation pump exercise function

Boiler · Vitocrossal 300 CU3A

Circulation pumps run for 10 seconds every 24 hours to stop them seizing. This runs in all operating programs and during warm weather shutdown.

Applies to: Circulation pumps

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Circulation pump wiring

Boiler · Vitotronic 300

Use only Viessmann pre-wired plug-in pumps on the Power Pump Module. If pre-wired pumps are used, do not also connect a pump to the hard-wired terminals of the same circuit.

  1. Insert the supplied strain relief through the Power Pump Module knockout and fasten with the nut.
  2. Connect the Rast-5 connector to the matching plug-in terminal on the Power Pump Module.
  3. For hard-wired 120 VAC pumps, connect to the terminal strip of the Power Pump Module.

Applies to: Vitotronic 300 KW3 with circulation pumps

Source: Vitotronic 300 installation instructions, p. 16. Written in our own words; check the manual for your exact model.

Circulator type with zone valves

Boiler · Vitocrossal 300 CU3A

Single-speed circulators need a pressure differential bypass so flow does not rise when one zone valve opens. Variable-speed circulators adjust automatically as zones open and close.

  1. With a single-speed circulator, install a pressure differential bypass.
  2. With a variable-speed circulator, no bypass is needed for flow adjustment.

Applies to: Vitocrossal CU3A zoned systems

Source: Vitocrossal 300 CU3A application guide, p. 26. Written in our own words; check the manual for your exact model.

Clean condensate trap

Boiler · Vitodens 200-W B2HA

Clean the condensate trap during regular maintenance. Blocked drainage makes condensate build up in the boiler and causes a burner shut-down with a fault message.

  1. Remove the rubber cap below the condensate trap.
  2. Unscrew the threaded cap. It may need to be pried off.
  3. Clean out debris from the trap.
  4. Refit the threaded cap and rubber cap.
  5. Undo the union nut and pull the trap down off the boiler.
  6. Fill the trap with water.
  7. Reassemble in reverse order.

Applies to: Vitodens 200-W B2HA

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 27. Written in our own words; check the manual for your exact model.

Cleaning the control

Boiler · Vitotronic 300-K, Vitotronic 100

Equipment can be cleaned with a commercially available non-scouring domestic cleaner.

  1. Clean the front of the programming unit with a microfibre cloth

Applies to: Vitotronic 300-K MW1B / Vitotronic 100 GC1B

Source: Vitotronic 300-K MW1B / Vitotronic 100 GC1B operating instructions, p. 36. Written in our own words; check the manual for your exact model.

Cleaning the devices

Boiler · Vitotronic 200-H

All devices can be cleaned with a commercially available domestic cleaning agent. Use a non-scouring product.

  1. Clean with a domestic non-scouring cleaning agent only.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H Operating Instructions, p. 17. Written in our own words; check the manual for your exact model.

Cleaning the equipment

Boiler · Vitocontrol-S VD2/CT3/CM2

Clean the outside of the equipment with suitable cleaning agents.

  1. Use domestic cleaning agents available on the market.
  2. Do not use abrasive cleaning agents.

Applies to: Vitocontrol-S VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 35. Written in our own words; check the manual for your exact model.

Cleaning the remote control

Boiler · Vitotrol 300A

The unit can be cleaned with a commercially available household cleaner that is not scouring.

  1. Use a non-scouring domestic cleaning agent.

Applies to: Vitotrol 300A

Source: Vitotrol 300A Remote Control Operating Instructions, p. 25. Written in our own words; check the manual for your exact model.

Clear maintenance display

Boiler · Vitocrossal 300 CA3B Dual Fuel

The maintenance message is confirmed from the home screen. If several faults are active, a list of service messages appears in yellow.

  1. Tap Confirm on the maintenance display.
  2. If several fault messages exist, tap Service messages to view the yellow list.

Applies to: Maintenance and service messages

Source: Vitocrossal 300 CA3B Dual Fuel Service Instructions, p. 119. Written in our own words; check the manual for your exact model.

Clear the maintenance display

Boiler · Vitocrossal 300 CA3B

When the service limit is reached, Service and a symbol appear on the display. Several fault messages can be listed under Service messages.

  1. Tap Confirm on the maintenance display.
  2. If several messages are active, tap Service messages to view the list.
  3. Carry out the maintenance and reset the service interval.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 120. Written in our own words; check the manual for your exact model.

Clearance from hot water pipes to combustible construction

Boiler · Vitodens 200-W B2HB

Keep at least 2 in. (51 mm) clearance around non-insulated hot water pipes to combustible construction. Insulated pipes may be reduced to 0 in. if the insulation thickness and value are sufficient, per local gas codes.

  1. Keep a minimum 2 in. (51 mm) clearance around non-insulated hot water pipes.
  2. If the pipe is insulated to the required thickness and value, check local gas codes before reducing clearance to 0 in.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words; check the manual for your exact model.

Clearance from uninsulated hot water pipes

Boiler · Vitodens 100-W B1HE/B1KE

Uninsulated hot water pipes need clearance from combustible materials. Insulation of adequate thickness removes the need for it.

  1. Keep at least 2 in. (50 mm) from uninsulated hot water pipes to combustible components.
  2. Follow local gas regulations for insulated pipes.

Applies to: Heating and DHW piping

Source: Vitodens 100-W, B1HE/B1KE Installation/Service, p. 19. Written in our own words; check the manual for your exact model.

Clearance from uninsulated hot water piping

Boiler · Vitodens 200-W

Keep at least 2 in. (51 mm) all around uninsulated hot water pipes to combustible construction. With suitable pipe insulation the clearance can drop to 0 in., but check local gas code first.

  1. Measure clearance around each uninsulated hot water pipe to combustible material.
  2. If pipes are insulated, confirm insulation thickness and value are adequate, then check local gas code before reducing clearance.

Applies to: Piping layout near combustible construction

Source: Vitodens 200-W B2HA installation manual, p. 32. Written in our own words; check the manual for your exact model.

Clearances to combustibles

Boiler · Vitorond 100 VR1

Clearance from non-insulated hot water pipes to combustible construction is 2 in minimum. Insulated pipes with adequate insulation may be reduced to 0 in.

Applies to: Piping clearances

Source: Vitorond 100, VR1 Technical Data, p. 11. Written in our own words; check the manual for your exact model.

Closing the control unit cover

Boiler · Vitodens 200-W B2HB

Final steps to close the boiler control unit.

  1. Install the cover onto the control board.
  2. Flip the control board back into position.
  3. Secure the locking tabs as shown.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 56. Written in our own words; check the manual for your exact model.

Closing the external accessory connection box

Boiler · Vitodens 200-W B2HB

Closing and securing the external accessory connection box cover and retaining screw.

  1. Tilt the top of the external accessory connection box cover forward.
  2. Drop the cover down over the locating pins and set it in place.
  3. Swing the external accessory connection box up.
  4. Push the box in until the holding screw is in place.
  5. Tighten the external accessory connection box retaining screw.
  6. Install the external accessory connection box cover screws.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 57-58. Written in our own words; check the manual for your exact model.

CO and gas tightness checks

Boiler · Vitodens 222-F

Incorrect burner adjustment can cause dangerous CO build-up. Gas leaks at the test nipple are an explosion risk.

  1. Carry out a CO test before and after any work on the gas appliance.
  2. Check gas tightness at test nipple A using a soap and water solution.
  3. Never use a flame or match to check for leaks.
  4. Never purge a gas line into the combustion chamber.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 19. Written in our own words; check the manual for your exact model.

CO2 measurement required around gas work

Boiler · Vitocrossal 200 CI2

A CO2 measurement must be taken before and after working on gas appliances to check the combustion condition.

  1. Measure CO2 before working on the gas appliance.
  2. Measure CO2 again after the work is done.
  3. Refer to page 25 for the measurement procedure.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 service instructions, p. 24. Written in our own words; check the manual for your exact model.

Code references for combustion air and venting

Boiler · Vitorond 100 VR1

Canada: CSA B139-00 (oil installations) and CAN/CSA-A405 for chimney construction. US: NFPA 31 (oil burning equipment) and NFPA 211 (chimneys, vents). Always use the latest editions.

Applies to: VR1 22 to 33, 91 to 140

Source: Vitorond 100 installation and service manual, p. 10, 14. Written in our own words; check the manual for your exact model.

Codes and wiring requirements

Boiler · Vitorond 100

Installation must follow local codes. Where none apply, use CAN/CSA-B139.00 for oil installations in Canada. Electrical wiring follows CSA C22.1 Part 1 or local codes, and NEC ANSI/NFPA 70 in the U.S. Controls must also meet ANSI/ASME CSD-1 where the authority having jurisdiction requires it.

Applies to: Vitorond 100 installation

Source: Viessmann Vitorond 100 installation and service manual, p. 5. Written in our own words; check the manual for your exact model.

Coding 2 address map

Boiler · Vitotronic 300-K MW1S

Coding 2 addresses are grouped by function. Scrolling starts with system circuit A1, then mixing valve circuits M2 and M3, then the general and multi-boiler ranges.

  1. System circuit A1: addresses A0 to F2.
  2. Mixing valve circuit M2: addresses A0 to F2.
  3. Mixing valve circuit M3: addresses A0 to F2.
  4. DHW: addresses 54 to 75.
  5. General: addresses 76 to 9F and 40.
  6. General: addresses 4A to 4F.
  7. Multi-boiler control unit: addresses 41 to 49 and 35 to 3F.

Applies to: Vitotronic 300-K, MW1S

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 151. Written in our own words; check the manual for your exact model.

Coding 8F changes apply on exit

Boiler · Vitodens 200-W B2HA

Lockout (8F) only takes effect after you leave the service menu. Emissions test mode can be enabled when 8F is set to 1 or 2.

  1. Set coding 8F to the required lockout value.
  2. Exit the service menu.
  3. Confirm the lockout is active on the next menu access.

Applies to: Vitodens 200-W B2HA 80-100

Source: Vitodens 200-W B2HA service instructions, p. 44. Written in our own words; check the manual for your exact model.

Coding changes take effect when the service menu is exited

Boiler · Vitocrossal 300 CU3A

Some coding values, including 8F menu access, only become active after you leave the service menu.

  1. Make the coding change in the service menu.
  2. Exit the service menu to activate the change.
  3. Confirm the new setting works as expected.

Applies to: Vitocrossal 300 CU3A coding

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.

Combustion air and carbon monoxide precautions

Boiler · Vitocrossal 200 CM2

The boiler needs fresh air for safe combustion. Installation and CO detector rules must be followed.

  1. Confirm adequate combustion and ventilation air according to the Mechanical room section of the installation instructions.
  2. Keep chemicals that produce poisonous combustion by-products out of the boiler room.
  3. Follow local regulations for carbon monoxide detector installation.
  4. Follow the Viessmann maintenance schedule.

Applies to: All Vitocrossal 200 CM2 units

Source: Vitocrossal 200 CM2 service instructions, p. 2. Written in our own words; check the manual for your exact model.

Combustion air and installation location

Boiler · Vitorond 100 VR1

The boiler needs clean combustion air. Corrosive chemicals and contaminated air can damage it.

  1. Do not install the boiler where chlorine, bromine, fluorine or other corrosive chemicals are stored, such as refrigerants, bleach, paint, thinner, hair spray, solvents or water softener salt.
  2. Avoid areas with excessive dust, high humidity or frost risk.
  3. Provide adequate ventilation and fresh combustion air.
  4. For oil-fired installs, follow CAN/CSA-B139 (Canada) or NFPA 31 (USA) and local codes.
  5. Size round combustion air ducts from outside using the methods in those codes.

Applies to: Installation location and combustion air

Source: Vitorond 100, VR1 Technical Data, p. 10. Written in our own words; check the manual for your exact model.

Combustion air and ventilation openings

Boiler · Vitocrossal 300 CA3B

Incomplete combustion and poisonous gases result if fresh air intakes in the mechanical room are closed.

  1. Confirm combustion air openings and ventilation air openings in the mechanical room are open.
  2. Never close or obstruct these openings.
  3. Keep the boiler room clear of combustible materials, gasoline and flammable vapors or liquids.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 operating instructions, p. 6, p. 7. Written in our own words; check the manual for your exact model.

Combustion air blower power and protection

Boiler · Vitocontrol-S VD2/CT3/CM2

Provide a disconnect and overcurrent protection for the 120 VAC blower supply as local codes require.

Applies to: Combustion air blower power supply

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 54. Written in our own words; check the manual for your exact model.

Combustion air supply for the boiler room

Boiler · Vitotronic 100

Tightly insulated homes can starve the boiler of combustion air, so the boiler room needs a fresh air supply.

  1. Provide a properly sized fresh combustion air supply to the boiler room.
  2. In tightly insulated homes, add a duct or opening for outside air.
  3. Follow applicable codes and instructions.

Applies to: All fuel burning appliances including the hot water heating boiler

Source: Vitotronic 100, KW10B Operating and User's Information manual, p. 10. Written in our own words; check the manual for your exact model.

Combustion and ventilation air

Boiler · Vitocrossal 300

The boiler needs fresh combustion and ventilation air. Do not run it where the air is contaminated by dust, lint or chemicals, such as construction sites, garages, laundry rooms or near pools. Contaminated air can damage the boiler and cause property damage or injury.

  1. Confirm provisions for combustion and ventilation air exist in the mechanical room.
  2. Check the combustion air is free of dust, lint and chemicals before start-up.
  3. Keep chemicals that can contaminate the air out of the boiler room.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 service instructions, p. 2. Written in our own words; check the manual for your exact model.

Combustion chamber door and side clearance

Boiler · Vitorond 200 VD2

The door can swing left or right to reduce side clearance.

  1. The combustion chamber door hinges on the left from the factory.
  2. Rebuild the door hinge hardware to change to a right-hand hinge.
  3. Keep at least 20 in. (500 mm) side clearance for side-mounted Vitotronic controls.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 11. Written in our own words; check the manual for your exact model.

Comfort adjustments for occupants

Boiler · Vitocrossal 200 CI2

Set the preferred room temperature and adjust time programs so the preferred temperature is reached when occupied. In weather-compensated operation, heating curves can be adjusted for year-round comfort. Extended heating gives a higher room temperature short term. One-off DHW heating gives extra hot water for a short time. Remote control units, if installed, can also adjust some settings.

  1. Set the preferred room temperature on the heating circuit display.
  2. Adjust heating curves only in weather-compensated operation.
  3. Use Extended heating for a short-term higher room temperature.
  4. Use one-off DHW heating for a short-term higher DHW temperature.

Applies to: Vitocrossal 200 CI2 weather-compensated and constant operation

Source: Vitocrossal 200 CI2 operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Common venting limitation

Boiler · Vitodens 200-W

The Vitodens 200-W can only be common vented with other Vitodens 200-W boilers of the same size and series. Refer to the Common Venting Manual for details.

  1. Confirm that all boilers on the common vent are the same size and series before connecting.

Applies to: B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service, p. 100. Written in our own words; check the manual for your exact model.

Compiled fault indicator alarm connection

Boiler · Vitotronic 300

A visual and/or audible alarm can be wired to the Power Pump Module. Alarm rating is 120 VAC, 60 Hz, 3 FLA.

  1. Connect the alarm wires to the matching terminals on the Power Pump Module (L, G, N).

Applies to: Vitotronic 300 KW3

Source: Vitotronic 300 installation instructions, p. 18. Written in our own words; check the manual for your exact model.

Condensate and venting notes

Boiler · Vitocrossal 200 CM2

Condensate pH is about 3 to 4 (the venting section gives 3 to 5.5). Flue gas temperatures can range from 77°F (25°C) to 257°F (125°C) depending on boiler water temperature. Condensate can drain to a floor drain. If local rules require neutralizing, a correctly sized neutralization tank is needed. Treated condensate should reach pH 6.5 to 9 before disposal. The vent system must be designed by the chimney or venting manufacturer.

  1. Confirm local requirements for neutralizing condensate before disposal.
  2. Use a neutralization tank sized by Viessmann if neutralizing is required.
  3. Confirm treated condensate is pH 6.5 to 9 before disposal to waste water.

Applies to: Vitocrossal 200 CM2 186 to 620

Source: Vitocrossal 200 CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Condensate disposal

Boiler · Vitocrossal 200 CM2

Condensate is acidic and may need neutralizing before drain disposal.

  1. Dispose of condensate into a floor drain, collecting chimney condensate with it if desired.
  2. If local rules require neutralizing, use a correctly sized neutralization tank from Viessmann.
  3. Confirm treated condensate reads pH 6.5 to 9 before disposal into the waste water system.

Applies to: All CM2 models

Source: Vitocrossal 200 CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Condensate drain back in vent

Boiler · Vitocrossal 200 CI2

Condensate from the vent can drain back to the boiler.

  1. Plan the base of the vent so condensate can drain back to the boiler.
  2. A base tee may be replaced with an elbow where shown in the venting options.

Applies to: Two-pipe and single-pipe vent layouts

Source: Vitocrossal 200 CI2 Installation manual, p. 59, 61, 62, 63, 64. Written in our own words; check the manual for your exact model.

Condensate drain installation rules

Boiler · Vitodens 200-W

Vent the drain between the condensate trap and the neutralization unit where one is fitted. Do not connect drains from other appliances such as a water softener backwash into the Vitodens condensate drain.

  1. Confirm the drain is open or vented to a field drainage system.
  2. Make sure the drain pipe between the trap and the neutralizer is vented.
  3. Do not tie in other appliance drains.

Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

Condensate pH and disposal

Boiler · Vitocrossal 300 CA3B

Condensate from this condensing boiler is acidic. Local rules may require neutralising it before drain disposal. Neutralised condensate should reach a pH of about 6.5 to 9.

  1. Check local building requirements before disposing of condensate.
  2. If neutralising is required, use a correctly sized neutralisation tank from Viessmann.
  3. Dispose of condensate into a floor drain or wastewater system only after neutralising where required.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Connect control unit to LON system

Boiler · Vitotronic 200-H

If used, the LON system cable plugs into the LON connection on module A2. Data transfer over LON can take several minutes.

  1. Plug the LON system cable into the LON connection on module A2.
  2. Allow several minutes for data transfer before judging the connection.

Applies to: Vitotronic 200-H with LON system

Source: Vitotronic 200-H installation and service instructions, p. 13. Written in our own words; check the manual for your exact model.

Connect external dry contacts safely

Boiler · Vitodens 200-W B2HA

External contacts on DE1 to DE3 must be floating. Keep the required spacing from live parts.

  1. Use floating (dry) contacts only.
  2. Keep 8.0 mm air and creep path, or 2.0 mm insulation thickness, from live parts (safety category II).
  3. Only assign one function to each connection.

Applies to: Digital inputs DE1 to DE3

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 83. Written in our own words; check the manual for your exact model.

Connect the DHW tank temperature sensor

Boiler · Vitodens 200-W

The DHW sensor plugs into the quick connect plugs from the boiler control board (connector X9). Install the sensor in the tank as described in the storage tank instructions.

  1. Attach the DHW sensor to the quick connect plugs from the control board (X9).
  2. Install the sensor in the DHW tank per the Vitocell instructions.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 25. Written in our own words; check the manual for your exact model.

Connecting a 24 VAC thermostat

Boiler · Vitodens 222-F, B2TB

A potential-free (dry) T-T contact from a switching relay connects to the EA1 module in the boiler junction box. With the contact closed, burner operation depends on load and heats the supply water to the value set in coding address 9b. Live contacts cause short circuits or phase failure, so the external connection must be potential-free. With only a thermostat controlling room temperature, the standard and reduced room set points can be set to 37 ºF (3 ºC) to reduce cycling.

  1. Connect the normally open dry contact of the switching relay (T-T) to terminal DE1, DE2 or DE3 of the EA1 module in the boiler electrical junction box.
  2. Connect the switching relay to the thermostat and power supply per the manufacturer's instructions.
  3. Set coding addresses 3A, 3B or 3C in the General group to 2.
  4. Set coding address 9b in the General group to the required supply water limit.
  5. If the thermostat is the only room control, set the standard and reduced room set points to 37 ºF (3 ºC).

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB Installation Instructions, p. 50. Written in our own words; check the manual for your exact model.

Connecting the DHW tank temperature sensor

Boiler · Vitodens 200-W B2HB

The DHW sensor plugs into the quick connect plugs on the boiler control board. The sensor itself is installed per the Vitocell instructions supplied with the DHW tank. System coding information is in the Service Instructions.

  1. Attach the DHW sensor to the quick connect plugs from the boiler control board (X9 connector).
  2. Install the DHW tank temperature sensor as described in the Vitocell Installation Instructions.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 25. Written in our own words; check the manual for your exact model.

Connecting the low-loss header sensor

Boiler · Vitodens 200-W B2HB

The low-loss header sensor plugs into the X3 connector on the boiler control board. The X3 plug must be removed first to reach the terminals.

  1. Remove the control unit cover.
  2. Remove the X3 plug from the control board.
  3. Connect the low-loss header sensor to terminals X3.4 and X3.5.
  4. Reinstall the X3 plug and control cover.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 48. Written in our own words; check the manual for your exact model.

Connection overview

Boiler · Versatronik 200

Terminal blocks are grouped by function: sensor low voltage (1 to 13), 0-10 VDC input, CAN BUS (H, L, -, +), 120 VAC power in (N, L), 120 VAC pump outputs (24, 25, 26, 36, 37), ground strip, dry-contact burner demands (29, 30, 32, 33), and mixing valve terminals (27, C, 28 and 34, C, 35) with a coding card.

  1. Identify the terminal group before wiring.
  2. Use the coding card for the mixing valve connections.
  3. Keep sensor wiring away from 120/240 VAC conductors.

Applies to: Versatronik 200 control

Source: Versatronik 200 installation manual, p. 9. Written in our own words; check the manual for your exact model.

Constant and weather-compensated heating operation

Boiler · Vitodens 100-W B1HE/B1KE

In constant operation the boiler holds a fixed supply temperature regardless of outside temperature. In weather-compensated operation the supply temperature follows the outside temperature, so more heat is supplied as it gets colder. The outside temperature is read by a sensor mounted outside the building. The contractor selects the mode at commissioning.

  1. Check with the contractor which operating mode was set at commissioning.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE Operating Instructions, p. 35. Written in our own words; check the manual for your exact model.

Contaminated combustion air

Boiler · Vitocrossal 300 CU3A

Do not run the boiler where combustion air is contaminated by dust, lint or chemicals. Such air damages the boiler and can cause serious harm.

  1. Check that the boiler room air is free of dust, lint and chemicals.
  2. Keep the boiler away from construction sites, garages, workshops, laundry areas, pools and manufacturing areas.
  3. Have the boiler inspected and serviced at least once a year.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 2. Written in our own words; check the manual for your exact model.

Control applicability

Boiler · Vitotronic 100 GC1, Vitotronic 300-K MW1S

Both control units are only for integration and installation on Viessmann boilers and for control panel mounting. The Vitotronic 100 GC1 has no LON module fitted as standard; its LON module is supplied with the control panel. The Vitotronic 300-K MW1S has an integral LON module.

Applies to: Vitotronic 100 GC1 and Vitotronic 300-K MW1S

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 7. Written in our own words; check the manual for your exact model.

Control board fuse ratings

Boiler · Vitotronic 200

Fuse F1 on the rear of the control is T6.3 A (heating system on/off switch circuit). Fuse F2 on the mother board is T4 A (adjustable high limit circuit).

  1. Replace F1 only with a T6.3 A fuse.
  2. Replace F2 only with a T4 A fuse.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 Service Instructions, p. 60 and p. 63. Written in our own words; check the manual for your exact model.

Control is not a temperature limit safety device

Boiler · Versatronik 10.WB1

This control does not replace a temperature limit. Where required, install a separate mechanical or electrical safety device.

  1. Check whether local rules require a separate limit device on the system.
  2. Install that device separately if it is required.

Applies to: Versatronik 10.WB1 with Viessmann Vitodens 100-W WB1A and WB1B

Source: Versatronik 10.WB1 installation and operating manual, p. 4. Written in our own words; check the manual for your exact model.

Control keys and menu access

Boiler · Vitotronic 200

The back key cancels a started setting or goes back one menu step. The cursor keys scroll the menu and change values. OK confirms a selection or saves a setting. The ? key has no function. Tapping the menu key opens settings and scanning, which includes Information, Further adjustments, Emissions test mode and Heating program.

  1. Tap the menu key to enter settings and scanning.
  2. Use the cursor keys to move through the menu and change values.
  3. Press OK to save, or the back key to cancel.

Applies to: Vitotronic 200 HO1B user interface

Source: Vitotronic 200 operating instructions 5838 962-03, p. 7. Written in our own words; check the manual for your exact model.

Control layout (Vitocontrol-S)

Boiler · Vitocontrol-S

The Vitocontrol-S has heating circuit buttons, heating program buttons, a normal and reduced room temperature selector, party and energy saving buttons, a holiday program, time programs for central heating, DHW and DHW circulation, DHW temperature selector, heating curve shift and slope, a time/date setting, and a boiler sequence display. It also has green and red status lights and fuse F1.

  1. Use the status lights to confirm the operating state and any fault.
  2. Check the boiler sequence display for the current boiler state.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Control options and side-mounted control in North America

Boiler · Vitorond 200 VD2

The boiler is designed for Vitotronic or Dekamatik digital boiler and heating system control. In North America only the side-mounted control option is offered, so use the side-mounted control dimensions when planning clearances.

  1. Confirm the control type (Vitotronic or Dekamatik) before commissioning.
  2. For North American installs, plan the room for the side-mounted control dimensions.

Applies to: All VD2 models 320 to 1080

Source: Vitorond 200 VD2 technical data manual, p. 2 and p. 8. Written in our own words; check the manual for your exact model.

Control panel and display indicators

Boiler · Vitodens 100-W WB1B

The LCD shows boiler water temperature in °F or a fault code. Other indicators: heating pump output on when the room thermostat is closed; DHW pump output on when DHW call is closed; burner firing rate; burner in operation; fault; service mode; comfort function started or stopped. Selector dials set DHW temperature and boiler water temperature. An ON/OFF switch and gas shut-off valve are also on the panel. The pressure gauge is on the control panel.

  1. Lift the flap and pull the control unit cover down to reach the boiler controls.

Applies to: Vitodens 100-W WB1B control panel

Source: Viessmann Vitodens 100-W WB1B installation and service manual, p. 53. Written in our own words; check the manual for your exact model.

Control panel elements

Boiler · Vitotronic 200

Lettered controls on the panel include heating circuit selection, reduced, standard and DHW temperature, standby, DHW only, heating and DHW, economy and party modes, information, basic settings, acknowledgment, value adjustment, time programs, holiday program, time/date, and heating curve level and slope.

Applies to: Vitotronic 200 control panel

Source: Vitotronic 200 KW2 service instructions, p. 16. Written in our own words; check the manual for your exact model.

Control PCB and display overview

Boiler · Vitocrossal 300 CA3B Dual Fuel

Board list and display indicators on the extension PCB for heating circuits 2 and 3.

  1. V1 red fault display: indicates a fault.
  2. V2 green operating mode display: indicates operating mode.
  3. S3 emissions test switch is on the extension PCB.
  4. A9 coding card and A7 Optolink PCB / emissions test switch are on the control board set.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 134-135. Written in our own words; check the manual for your exact model.

Control unit display symbols

Boiler · Vitodens 200-W B2HB

Symbols shown on the display depending on system version and operating state.

  1. HC1 (2, 3): heating circuit selected in the standard menu.
  2. Frost protection monitoring active.
  3. Central heating with standard temperature.
  4. Central heating with reduced temperature.
  5. Party mode and Economy mode enabled.
  6. Solar circuit pump running (with solar thermal system).
  7. Burner in operation.
  8. Service message and Fault message indicators.

Applies to: Vitodens 200-W B2HB control unit

Source: Vitodens 200-W B2HB service instructions, pp. 32-33. Written in our own words; check the manual for your exact model.

Control unit features and external connections

Boiler · Vitodens 100-W B1HE/B1KE

The integrated control has an LCD display, push-button setting of boiler water temperature, adjustable high limit, burner fault display and reset, a pressure gauge, a fuse, and integrated WiFi. It can take a room thermostat or external control, an external heat demand, a DHW temperature sensor, a Viessmann outdoor sensor (field wired), and instantaneous DHW control on B1KE.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Control unit layout (Vitotronic 100, GC1)

Boiler · Vitocontrol-S

The Vitotronic 100, GC1 has a manual override, value selector buttons, information and confirmation buttons, a factory settings button, a display window, an adjustable high limit, a manual reset fixed high limit, a power on/off switch, fuses F1 and F2, and green and red status indicators. The green light shows operating status and the red light shows a fault.

  1. Use the green indicator to confirm operating status.
  2. If the red fault indicator is on, look up the fault in the troubleshooting section of the manual.

Applies to: Vitotronic 100, GC1 on each boiler

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Control unit modules and programming unit functions

Boiler · Vitotronic 300-K MW1S

Component overview from the parts list. Module A1 is the power supply, A2 the cascade electronics, A3 the power module, and the front panel has heating circuit selector keys.

  1. Power supply module A1: fuse F1, see the fuse data on p. 120.
  2. Cascade electronics module A2: microprocessor with software; replace per the PCB procedure.
  3. Power module A3 and extension module: fit as listed in the parts list.
  4. Programming unit (in the control panel front door) sets heating program, set values, switching times, heating curve (slope and shift), date, time and economy/party mode.
  5. Displays temperatures, operating conditions and faults.

Applies to: Vitotronic 300-K MW1S control panel

Source: Vitotronic 300-K MW1S installation and service instructions, p. 119. Written in our own words; check the manual for your exact model.

Control wiring safety and replacement rules

Boiler · Vitodens 200-W B2HB

Disconnect power before servicing the boiler. Label every wire before disconnecting it, since wiring errors can cause dangerous operation. Any original supplied wire that must be replaced needs an exact equivalent. Verify correct operation after any control service. Each connection point accepts only one function or accessory.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any original wire only with an exact equivalent.
  4. Assign only one function or accessory to each connection.
  5. Verify correct operation after servicing the controls.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125 control wiring

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 45. Written in our own words; check the manual for your exact model.

Controls and display elements

Boiler · Vitotronic 200-H

Overview of the control keys and display symbols on the user interface: heating circuit selection keys, time programs, DHW and room temperature, heating curve slope and level, time/date, operating modes (standby, DHW only, heating and DHW), energy saving and party mode, and the adjust, confirm and information keys. A rotary selector sets the standard room temperature and a flap covers the controls.

  1. Select the heating circuit with its selection key before making adjustments.
  2. Use the adjust key to change values and the confirm key to save them.

Applies to: Vitotronic 200-H user interface

Source: Vitotronic 200-H installation and service instructions, p. 12. Written in our own words; check the manual for your exact model.

Controls and indicators on the Vitotronic 100 GC1

Boiler · Vitotronic 100

Front panel items: override switch; boiler water temperature and domestic hot water temperature selectors (no function on multi-boiler systems); value selection buttons; information and confirmation buttons; basic setting; display window; heating program selector buttons (no function on multi-boiler systems); adjustable high limit; fixed high limit reset button; control on/off switch; fuses F1 and F2; TUV button; green operating status indicator; red fault indicator.

Applies to: Vitotronic 100 GC1 boiler control

Source: Vitotronic 100 GC1 installation and service instructions, p. 85. Written in our own words; check the manual for your exact model.

Convert fault codes from decimal to hex

Boiler · Versatronik 581

The gateway sends fault codes as decimal numbers in a SNVT_count variable. Viessmann displays them in hex, so convert before comparing with the code tables.

  1. Read the fault value from the gateway as a decimal number.
  2. Convert it to hexadecimal.
  3. Look up the hex value in the fault code tables (appendix A).

Applies to: Versatronik 581 gateway fault reporting to BMS

Source: Versatronik 581 and 581D LON gateway manual, p. 20. Written in our own words; check the manual for your exact model.

Convert gateway fault values from decimal to hex

Boiler · Versatronik 585

The gateway reports fault codes as decimal numbers. Convert them to hex to match the Viessmann code shown on the control. Some BMS software can do this with a mask or enum conversion object.

  1. Read the decimal fault value from the gateway.
  2. Convert it to hexadecimal.
  3. Match it to the hex code in the fault code table.

Applies to: Tridium/Niagara BMS integration with Versatronik 585

Source: Versatronik 585 BACnetIP manual, p. 23. Written in our own words; check the manual for your exact model.

Copy a time program to other days

Boiler · Vitocrossal 200 CI2

Copies one day's time program to other selected days.

  1. Select the heating circuit and the source day.
  2. Select the target days.
  3. Confirm and exit.

Applies to: Time programs

Source: Vitocrossal 200 CI2 Operating Instructions, p. 19. Written in our own words; check the manual for your exact model.

Corrosion protection for heating water

Boiler · Vitocrossal 300 CA3B

Oxygen in the heating water causes corrosion. Keep the system sealed and at positive pressure, and keep the pH in range.

  1. Keep the sealed system above atmospheric pressure at all points, including the pump suction side.
  2. Check the expansion vessel precharge at least during the annual service.
  3. Use a corrosion-resistant separation (heat exchanger) where gas-permeable plastic pipe is used, such as in underfloor heating.
  4. Where oxygen ingress is a risk, consider a sodium sulphite oxygen binder at 5 to 10 ppm.
  5. Keep the heating water pH between 8.2 and 9.5.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 14. Written in our own words; check the manual for your exact model.

Damaged cables or lines

Boiler · Vitocrossal 300 CA3B

Damaged connecting cables or lines on the boiler or on externally installed accessories must be replaced with the correct parts.

  1. Replace damaged cables or lines with Viessmann cables or lines only.
  2. Have a qualified contractor make the replacement.

Applies to: Boiler and external accessory cables

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 41. Written in our own words; check the manual for your exact model.

Dangerous conditions and emergency shutdown

Boiler · Vitocrossal 300 CA3B

Use this sequence when the boiler or its power is in an unsafe condition.

  1. Deactivate main power immediately.
  2. Close the gas supply valve.
  3. If there is no gas smell, switch off the power at the separate fuse or disconnect switch.
  4. Use suitable extinguishers if there is a fire.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Dangerous conditions: emergency shutdown

Boiler · Vitocrossal 300 CU3A

If a dangerous condition exists, cut power and gas to the boiler before doing anything else.

  1. Deactivate the main power immediately.
  2. Close the gas supply valve.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Default pre-configuration of gateway

Boiler · Versatronik 585

The gateway is set at the factory for eight Vitotronic 300 GW6B boilers and three heating zones.

  1. If you do not have eight GW6B boilers or three zones, change the configuration to match your system.
  2. Apply changes using the activate configuration steps.

Applies to: Versatronik 585 VI/BACIP

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 15. Written in our own words; check the manual for your exact model.

Demonstration (trade fair) mode

Boiler · Vitodens 100-W B1HE/B1KE

If the contractor has set the boiler to demonstration mode, for example at an exhibition, the boiler does not provide central heating, domestic hot water or frost protection.

  1. Check the main menu for the trade fair mode message.
  2. Have the contractor return the boiler to normal operation before relying on heat or hot water.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE Operating Instructions, p. 33. Written in our own words; check the manual for your exact model.

DHW 4th phase heating (auxiliary function)

Boiler · Vitocrossal 300 CA3B

This heats the DHW tank to a second, higher DHW temperature during time phase 4. The heating contractor has to enable it by setting the second temperature.

  1. Have the heating contractor enable the second DHW set temperature.
  2. Set the start and stop times for time phase 4.
  3. Make sure start and stop times are also set for the 2nd and 3rd time phases.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

DHW anti-Legionella boost function

Boiler · Vitodens 200-W B2HB

The boost heats the DHW tank to a second setpoint during the fourth time phase. It can act as an anti-Legionella function if DHW is not heated to 140°F (60°C) during the regular schedule. It is enabled by selecting a switching period for the fourth time phase. The boost differential is in coding level 2, address 59. The boost setpoint is in coding address 58.

  1. Select a switching period for the fourth time phase to enable the boost.
  2. Adjust the boost differential at coding level 2, address 59 if needed.
  3. Adjust the boost setpoint at coding address 58 if needed.

Applies to: Vitodens 200-W B2HB DHW tank

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 33. Written in our own words; check the manual for your exact model.

DHW booster heating

Boiler · Vitodens 222-F

The booster heating function runs when a switching period is set for the fourth time phase. The boost temperature is set in coding address 58.

  1. Set the boost temperature in coding address 58.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 35. Written in our own words; check the manual for your exact model.

DHW call for heat from a tank aquastat

Boiler · Vitodens 100-W B1HE/B1KE

With a tank temperature switch (aquastat), the boiler target is the maximum permissible value for that boiler.

  1. No demand from the aquastat means no frost protection.
  2. Demand from the aquastat calls for the target value. There is no time program for DHW, no scald protection and no increased DHW hygiene in this case.
  3. Maximum DHW heating duration and minimum wait before the next DHW heating still apply. Check the system configuration parameter DHW.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 92. Written in our own words; check the manual for your exact model.

DHW circulation pump operation

Boiler · Vitotronic 200 and 300-K

With automatic mode, the DHW circulation pump runs alongside the DHW heating time program. Up to 4 individual time phases per day can be set instead, the same every day or different per day. The current program can be checked under Information, DHW. Only run the pump when DHW is actually drawn.

  1. Keep automatic mode for the pump, or set up to 4 individual time phases per day.
  2. To check the program, open Information and select the DHW group.

Applies to: Heating systems with DHW circulation pump

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

DHW circulation pump time program

Boiler · Vitotronic 300-K, Vitotronic 200

The circulation pump runs in parallel with the DHW heating program in automatic mode. Individual phases can be set instead. Only use circulation when DHW is actually drawn.

  1. Leave the pump in automatic mode to follow the DHW heating time program.
  2. For individual times, open the extended menu and select DHW.
  3. Select DHW circ time prog, then Individual.
  4. Select part of the week or a day, then the time phase.
  5. Set start and end times and press the exit key.
  6. Check the current program under Information, DHW group.

Applies to: Vitotronic 300-K, systems with DHW circulation pump

Source: Vitotronic 200 and 300-K Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

DHW fourth phase heating (auxiliary function)

Boiler · Vitotronic 300-K

This function heats the DHW tank to a second, higher DHW temperature. The heating contractor must enable it by setting a second DHW temperature. It runs during time phase 4. The 2nd and 3rd time phases must have a start and stop time set.

  1. Have the heating contractor set a second DHW temperature.
  2. Set the start and stop time for time phase 4.

Applies to: DHW tank

Source: Vitotronic 300-K MW2C operating instructions, p. 19. Written in our own words; check the manual for your exact model.

DHW fourth time phase (second DHW temperature)

Boiler · Vitotronic 300-K

The heating contractor can enable a second, higher DHW setpoint. It runs during time phase 4. The 2nd and 3rd time phases need both a start and a stop time.

  1. Have the heating contractor set the second DHW temperature value.
  2. Set the start and stop times for time phase 4 in the DHW time program.
  3. Make sure start and stop times are set for time phases 2 and 3.

Applies to: Vitotronic 300-K, MW2C

Source: Vitotronic 300-K, MW2C operating instructions, p. 19. Written in our own words; check the manual for your exact model.

DHW frost protection

Boiler · Vitotronic 200

If domestic hot water temperature drops below 50 F / 10 C, the tank is heated to 68 F / 20 C.

Applies to: DHW tank

Source: Vitotronic 200 KW2 service instructions, p. 53. Written in our own words; check the manual for your exact model.

DHW hygiene function (B1HE only)

Boiler · Vitodens 100-W, B1HE, B1KE

Heats DHW to a higher target temperature for one hour. Activate it through the operating instructions.

  1. Activate the hygiene function as described in the operating instructions.

Applies to: B1HE

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 61. Written in our own words; check the manual for your exact model.

DHW hygiene function settings

Boiler · Vitocrossal 200 CI2

The hygiene function heats the DHW to a higher target for 1 hour. If the final temperature is not reached, the DHW heating can be aborted after the set time. Set the abort time to 60 minutes while hygiene runs (factory is 240 minutes).

  1. Configure the hygiene function via the HMI or ViGuide Web Pro (parameters 874.0 to 876.0).
  2. For the hygiene run, set parameter 1087.0 to 60 min so heating aborts early if the final temperature is missed.

Applies to: Vitocrossal 200 CI2 DHW tank heating

Source: Vitocrossal 200 CI2 service instructions, p. 90. Written in our own words; check the manual for your exact model.

DHW priority and heating circuit pump behaviour

Boiler · Vitocontrol-S VD2/CT3/CM2

With DHW priority (coding A2: 2), the set supply temperature drops to 0 °C (32 °F) while the DHW tank heats, the mixing valve closes and heating circuit pumps stop. Without priority, the heating circuit keeps its set value.

  1. Check coding A2 to confirm whether DHW priority is set.
  2. If the heating circuit must keep running during DHW heating, do not select priority control.

Applies to: Heating circuits with DHW tank

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 131. Written in our own words; check the manual for your exact model.

DHW recirculation line insulation

Boiler · Vitodens 200-W B2HB

Recirculation lines lose a lot of heat if poorly insulated. Viessmann recommends effective insulation on DHW recirculation lines that are 23 ft (7 m) or longer.

  1. Insulate DHW recirculation lines that are 23 ft (7 m) or longer.
  2. Check the recirculation pump and line layout against the Vitocell tank layout on this page.

Applies to: Vitodens 200-W B2HB with DHW recirculation

Source: Vitodens 200-W B2HB technical data manual, p. 15. Written in our own words; check the manual for your exact model.

DHW recirculation pump brief operation

Boiler · Vitodens 200-W B2HA

The DHW recirculation pump starts briefly when a pushbutton closes the contact at DE1, DE2 or DE3. The runtime is set at coding address 3D.

  1. Assign the input to brief recirculation operation (DE1, DE2 or DE3).
  2. Set the runtime at coding address 3D in the General group.

Applies to: DHW recirculation pump on EA1 input

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 84. Written in our own words; check the manual for your exact model.

DHW recirculation pump brief operation via EA1 input

Boiler · Vitocrossal 300 CA3B Dual Fuel

A pushbutton on DE1, DE2 or DE3 can start the DHW recirculation pump outside its time program. Run time is set by coding 3d in the General group. Output aBJ can signal a central fault or reduced mode (reduces heating circuit pump speed); its function is set by coding 5c in the General group.

  1. Wire a pushbutton to DE1, DE2 or DE3 and set the matching input function code.
  2. Set run time at coding 3d (General group).
  3. Set output aBJ function at coding 5c (General group).

Applies to: DHW recirculation pump, output aBJ

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 34. Written in our own words; check the manual for your exact model.

DHW recirculation pump use

Boiler · Vitocrossal 300

Run the DHW recirculation pump only when hot water is regularly drawn off, using a time program.

  1. Set the DHW recirculation pump time program to match regular draw-off periods.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A operating instructions, p. 10. Written in our own words; check the manual for your exact model.

DHW safety valve check

Boiler · Vitocrossal 300 CA3B

The DHW tank safety valve must be checked every six months by venting it. The valve seat can become contaminated, and water may drip during heat-up. The outlet must stay open to atmosphere.

  1. Vent the DHW tank safety valve every six months, following the valve manufacturer's instructions.
  2. Do not close off the valve outlet.

Applies to: DHW tank safety valve

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 41. Written in our own words; check the manual for your exact model.

DHW supply and return piping size

Boiler · Vitodens 200-W

Pipe between the boiler DHW connections and the Viessmann DHW tank must be at least 1¼ in. This lets the field pump's residual head overcome the DHW coil resistance and still feed the boiler heat exchanger. With a non-Viessmann tank, also calculate the coil pressure drop against the pump's residual head. Undersized piping can cause short-cycling and poor DHW supply.

  1. Use at least 1¼ in. pipe between boiler DHW connections and the DHW tank.
  2. With a non-Viessmann tank, calculate coil pressure drop versus the field pump's residual head.
  3. Confirm enough flow reaches the boiler heat exchanger.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 32. Written in our own words; check the manual for your exact model.

DHW tank and safety valve maintenance

Boiler · Vitocrossal 300 CA3B

DHW tank must be cleaned no later than 2 years after commissioning and as needed after that. The DHW tank safety valve must be checked every six months.

  1. Have a qualified heating contractor clean the inside of the DHW tank and DHW connections.
  2. Check the DHW tank safety valve every six months by venting it.
  3. Make sure the valve outlet is open to the atmosphere and not closed off.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B operating instructions, p. 41. Written in our own words; check the manual for your exact model.

DHW tank maintenance

Boiler · Vitocrossal 300 CA3B

The DHW tank must be cleaned and serviced no later than 2 years after commissioning and as needed after that. Only a qualified heating contractor should clean inside the tank and DHW connections.

  1. Clean and service the DHW tank within 2 years of commissioning, then as needed.
  2. Refill any water treatment equipment in the cold supply in good time, following its manufacturer's instructions.

Applies to: Vitocrossal 300 CA3B DHW tank

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 41. Written in our own words; check the manual for your exact model.

DHW tank sensor and tempering valve with non-Viessmann tanks

Boiler · Vitocrossal 200 CI2

If a DHW tank other than the Viessmann Vitocell 300 is used, confirm the Viessmann DHW tank temperature sensor works correctly with the tank manufacturer. A temperature tempering valve is strongly recommended in the DHW supply line. For DHW tank applications, calculate the coil pressure drop against the field-supplied DHW pump residual head to make sure enough water flows through the boiler heat exchanger. Insufficient flow can cause short-cycling and poor DHW supply.

  1. Verify the Viessmann DHW sensor with the tank manufacturer if the tank is not a Vitocell 300.
  2. Install a temperature tempering valve in the DHW supply line.
  3. Calculate tank coil pressure drop against the DHW pump residual head.
  4. Confirm enough flow reaches the boiler heat exchanger.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 41. Written in our own words; check the manual for your exact model.

DHW tank sensor check and tempering valve

Boiler · Vitodens 200-W B2HA

A non-Viessmann DHW tank requires the Viessmann DHW tank sensor to be verified with the tank manufacturer. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. For a non-Viessmann tank, verify the Viessmann DHW tank temperature sensor operation with the tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

Applies to: Vitodens 200-W B2HA 45, 60 with DHW storage tank

Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 32. Written in our own words; check the manual for your exact model.

DHW tank with temperature switch (Aquastat)

Boiler · Vitodens 100-W B1HE/B1KE

Some DHW menu items (On/Off, time program, hygiene program, recirculation pump, temperatures and scald protection) do not apply to systems that use a DHW tank with a temperature switch such as an Aquastat.

  1. Confirm whether the system has a DHW tank with an Aquastat before looking for these DHW menu items.

Applies to: Vitodens 100-W B1HE/B1KE with Aquastat DHW tank

Source: Vitodens 100-W B1HE/B1KE Operating Instructions, p. 32-33. Written in our own words; check the manual for your exact model.

DHW temperature shows 'Without function'

Boiler · Vitotronic 200-H

When DHW is supplied by a central DHW tank, the control cannot set the DHW temperature and shows 'Without function'.

Applies to: Vitotronic 200-H with central DHW tank

Source: Vitotronic 200-H operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Diagnosis display items and brief scan lines

Boiler · Vitodens 200-W B2HB

Diagnosis shows outdoor temperature adjustment and actual, boiler setpoint and actual, DHW setpoint and actual, supply setpoint and actual, common supply setpoint and actual, boiler coding card, and brief scan pages 1 to 8. Slope A1 and shift A1 apply to a heating circuit with mixing valve; Slope M2 and shift M2 apply to a second mixing valve circuit. Low-loss header values apply to a low-loss header. Brief scan lines cover system type, software versions, KM BUS participants, burner control unit type and version, flow rate sensor state, and LON addresses and software.

  1. Press D in the outdoor temperature display to reset adjusted outdoor temperature to actual.

Applies to: Vitodens 200-W B2HB diagnosis

Source: Vitodens 200-W B2HB service instructions, p. 72. Written in our own words; check the manual for your exact model.

Diagnosis scan values

Boiler · Vitodens 200-W

Diagnosis scan shows slope A1 and shift A1, slope M2 and shift M2, outdoor temperature adjustment and actual, boiler setpoint and actual, DHW setpoint and actual, supply temperature setpoint and actual, common supply setpoint and actual, boiler coding card, and brief scans 1 to 8. The manual's explanation column for these lines is jumbled in this text, so match each item to the manual page before relying on it.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA service instructions, p. 73. Written in our own words; check the manual for your exact model.

Differential pressure bypass valve

Boiler · Vitotron 100 VLN2

The built-in bypass valve keeps a minimum flow through the boiler and reduces noise when zone valves are used.

  1. Do not remove or block the bypass valve when setting up the system.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 3. Written in our own words; check the manual for your exact model.

Digital room controller overrides heating program

Boiler · Versatronik 200

If a digital room controller with a heating program input is connected, its own heating program replaces the matching program on this controller.

Applies to: Systems with a digital room controller

Source: Versatronik 200 installation and operating manual, p. 130. Written in our own words; check the manual for your exact model.

Digital time switch and control functions

Boiler · Vitodens 200-W, B2HB

The digital time switch has a 7-day program, automatic daylight savings change, up to four switching periods per day, a 10 minute minimum switching interval and 14 day power backup. Zone circuits support up to three zones using setpoint or outdoor reset.

  1. Set daily switching times for heating, DHW and the DHW recirculation pump as needed.
  2. Use the start-up wizard to set up zone circuits.
  3. Choose setpoint or outdoor reset operation for each zone circuit.

Applies to: Vitotronic 200 HO1B

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 23. Written in our own words; check the manual for your exact model.

Direct vent exhaust pressure and sealing

Boiler · Vitorond 100 VR1

Direct vent exhaust runs under positive pressure from the burner, so every joint must be airtight.

  1. Tighten all vent connection and observation port screws.
  2. Use high temperature silicone sealant where needed.
  3. Do not alter vent components except cutting the flex pipe to length.

Applies to: Direct vent systems

Source: Vitorond 100, VR1 Technical Data, p. 10. Written in our own words; check the manual for your exact model.

Direct vent is limited to some sizes

Boiler · Vitorond 100 VR1

Direct vent is only offered for VR1 22, 27, 33, 91, 105 and 140. Direct vent burners are not available for the larger sizes. Follow the separate direct vent installation supplement for those installs.

Applies to: VR1 22, 27, 33, 91, 105, 140

Source: Vitorond 100 VR1 technical data manual, p. 7. Written in our own words; check the manual for your exact model.

Direct vent operation in contaminated-air rooms

Boiler · Vitocrossal 200 CI2

Where halogenated hydrocarbons from sprays, paints, solvents or cleaning agents are expected in the room air, the boiler must run in direct vent (sealed combustion) operation only.

  1. Check the room for halogenated hydrocarbon sources before installation.
  2. If contamination is expected, set up the boiler for direct vent (sealed combustion) operation only.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 installation instructions, p. 9. Written in our own words; check the manual for your exact model.

Discharge static before touching electronics

Boiler · Vitodens 222-F, B2TB

Electronic modules can be damaged by electrostatic discharge.

  1. Touch a grounded object, such as a heating or water pipe, before working on the control modules.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB installation instructions, p. 19. Written in our own words; check the manual for your exact model.

Discoloured heat exchanger is normal

Boiler · Vitocrossal 300 CA3B

Discolouration of the stainless steel heat exchanger surface is a normal result of combustion. It does not affect function or service life, so do not treat it as a fault.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 74. Written in our own words; check the manual for your exact model.

Disconnect power and label wires before servicing

Boiler · Vitodens 200-W

Power must be off before any boiler service. Wiring errors can cause dangerous operation, so verify correct operation after servicing. Replace any original wire only with an exact equivalent.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any damaged original wire only with an exact equivalent.
  4. Assign only one function or accessory to each connection.
  5. Verify correct operation after any control service.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 47. Written in our own words; check the manual for your exact model.

Disconnect power before any wiring

Boiler · Vitotronic 300

Every connection on these pages starts with isolating the power to the burner and the control.

  1. Disconnect power to the burner and boiler control before making any connection.
  2. Confirm the power is off before removing plugs or jumpers.

Applies to: All Vitotronic 300 GW2 wiring

Source: Vitotronic 300 GW2 installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

Disconnect power before any wiring work

Boiler · Versatronik 10.WB1

Before any work, disconnect the boiler and the Versatronik from the 120 VAC supply. Check all wiring before applying power. The boiler pump output to the Versatronik must not be live. Skipping this can cause early failure of the pump module.

  1. Disconnect the boiler and Versatronik from 120 VAC power.
  2. Check all wiring connections.
  3. Apply power only after the check, then test operation.

Applies to: All Versatronik 10.WB1 wiring

Source: Versatronik 10.WB1 installation and operating manual, p. 16. Written in our own words; check the manual for your exact model.

Disconnect power before servicing

Boiler · Vitocrossal 300 CA3B

Power inside the boiler junction box must be disconnected before any service work on the boiler.

  1. Disconnect power inside the boiler junction box before servicing the boiler.

Applies to: Vitocrossal 300 CA3B boiler

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 131. Written in our own words; check the manual for your exact model.

Disconnect power before servicing the boiler

Boiler · Vitocrossal 300 CA3B Dual Fuel

Power inside the boiler junction box must be disconnected before any service work on the boiler.

  1. Disconnect power inside the boiler junction box before servicing the boiler.

Applies to: Boiler junction box and all service work

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 131. Written in our own words; check the manual for your exact model.

Display backlight behavior

Boiler · Vitotrol 300

The display light comes on when any button is pressed, provided the supplied batteries are installed. It turns off about 30 seconds after the last operation.

Applies to: Vitotrol 300 remote control

Source: Vitotrol 300 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Display backlighting

Boiler · Vitocrossal 300 CA3B

Sets the brightness of the screen and the screen saver.

  1. From the home screen, select Settings.
  2. Select Screen.
  3. Select Brightness screen saver or Brightness control.
  4. Set the required value.
  5. Confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Display gas consumption

Boiler · Vitocrossal 200 CI2

Shows gas consumption under the General information group.

  1. Open Information.
  2. Confirm with OK.
  3. Select 'General'.
  4. Confirm with OK.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Display symbols

Boiler · Vitodens 200-W

Symbols appear depending on system version and operating state.

  1. 9 = standby with frost protection monitoring.
  2. w = DHW only.
  3. wz = heating and DHW.
  4. e = frost protection monitoring.
  5. s = central heating at standard temperature.
  6. m = central heating at reduced temperature.
  7. Party mode, Economy mode, solar circuit pump running and burner in operation each have their own symbol.
  8. Service message and fault message symbols show on the display.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB service instructions, p. 32. Written in our own words; check the manual for your exact model.

Display symbols and messages

Boiler · Vitodens 200-W

Symbols show only when the system version and operating state call for them. They cover heating program, circuit state, pumps, solar, burner status, party and economy modes, and service or fault messages.

  1. Heating program symbols: standby with frost protection monitoring, DHW only, heating and DHW.
  2. Circuit symbols: frost protection monitoring, central heating with standard temperature, central heating with reduced temperature.
  3. Burner in operation: the burner symbol is shown.
  4. Zone circuit display: shows zone pump output, outdoor temperature (weather compensated only), set zone temperature, and burner modulation rate in %.
  5. Service message and fault message are shown in the display header.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 33. Written in our own words; check the manual for your exact model.

Display symbols for heating programs and operating states

Boiler · Vitodens 200-W B2HB

Heating program symbols: 9 means standby with frost protection monitoring, w means DHW only, wz means heating and DHW. Operating symbols: e means frost protection monitoring is active, s means central heating at standard temperature, m means central heating at reduced temperature. Other symbols show party mode, economy mode, solar circuit pump running, burner in operation, a service message, or a fault message. Not all symbols show on every system; they depend on system version and operating state.

Applies to: Vitodens 200-W B2HB control unit display

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

Display symbols on the control unit

Boiler · Vitocrossal 300

Symbols do not always show; they depend on the system version and operating state. Heating program symbols: standby with frost protection, DHW only, heating and DHW, frost protection monitoring, central heating at standard or reduced temperature. Other symbols: party mode, economy mode, solar circuit pump running, burner in operation, service message, fault message. HC1/HC2/HC3 show the heating circuit and ZC1/ZC2/ZC3 show the zone circuit selected in the standard menu.

Applies to: Vitotronic control unit display

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 48. Written in our own words; check the manual for your exact model.

Display symbols on the programming unit

Boiler · Vitodens 222-F

Symbols appear depending on system version and operating state. Heating program symbols: 9 standby with frost protection, w DHW only, wz heating and DHW. Other symbols: e frost protection monitoring, s central heating at standard temperature, m central heating at reduced temperature. Party mode and economy mode have their own symbols, as do service and fault messages. Zone circuit (ZC 1-3) and heating circuit (HC1-3) symbols show which circuit is selected in the standard menu.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 33. Written in our own words; check the manual for your exact model.

Display symbols on the Vitocontrol-S

Boiler · Vitocontrol-S

Symbols show heating and DHW status. They appear only when the system type and operating state call for them.

  1. Read the symbols: e = risk of freezing; s = central heating at normal room temperature; m = central heating at reduced room temperature; w = DHW heating, DHW pump on; p = heating circuit pump on; U = fault message; V = mixing valve open; v = mixing valve closed.
  2. If a U fault symbol shows, check the fault and correction tables in the manual for the cause.

Applies to: Vitocontrol-S, VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Display symbols reference

Boiler · Vitodens 200-W B2HA

Symbols appear depending on system version and operating state. Heating circuit labels show HC1, HC2 or HC3.

  1. Heating program symbols: standby with frost protection monitoring; DHW only; heating and DHW.
  2. Frost protection monitoring shown with a separate symbol.
  3. Central heating with standard temperature and central heating with reduced temperature each have a symbol.
  4. Party mode and economy mode each have a symbol.
  5. Solar circuit pump running and burner in operation each have a symbol.
  6. Service message and fault message each have a symbol.

Applies to: Programming unit display

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 29. Written in our own words; check the manual for your exact model.

Display symbols that appear only when needed

Boiler · Vitotronic 200-H

Some symbols are not shown all the time. They appear according to system type and operating status: risk of freezing, normal or reduced room temperature heating, DHW heating with DHW pump on, heating circuit pump on, and mixing valve open or closed.

Applies to: Vitotronic 200-H HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Display symbols to check during service

Boiler · Vitotronic 200-H

Flashing symbols mean a value can be changed. The U symbol shows a fault. The r symbol shows space heating is active, rp shows the heating circuit pump is running, and s and m show normal or reduced room temperature. Some symbols only appear depending on system version and operating state.

Applies to: Vitotronic 200-H HK1M

Source: Vitotronic 200-H operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Displaying active and acknowledged faults

Boiler · Vitocrossal 300 CA3B Dual Fuel

An active fault makes the red fault display flash and show the symbol with Fault. If several faults are present, a list appears and the faults are shown in red in time order.

  1. Look at the red fault display on the control unit.
  2. If several faults are active, open the Faults list to see them in time order.
  3. Use the fault code tables to find the cause and the measures.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 121. Written in our own words; check the manual for your exact model.

Disposal of the control unit battery

Boiler · Vitocontrol-S VD2/CT3/CM2

The control unit contains a built-in non-toxic battery.

  1. Have a competent person remove the battery.
  2. Dispose of the spent battery at an appropriate collection point.

Applies to: Vitocontrol-S VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 35. Written in our own words; check the manual for your exact model.

Do not adjust Multi-boiler system menu item

Boiler · Vitodens 200-W B2HB

Changing the Multi-boiler system item turns a weather-compensated control unit into a constant temperature control unit. Do not adjust it.

  1. Leave the Multi-boiler system menu item unchanged.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB service manual, p. 71. Written in our own words; check the manual for your exact model.

Do not adjust the multi-boiler system menu item

Boiler · Vitodens 222-F

The multi-boiler system item turns a weather-compensated control unit into a constant temperature control unit.

  1. Leave the 'Multi-boiler system' menu item unchanged unless the system design calls for it.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F B2TB service instructions, p. 69. Written in our own words; check the manual for your exact model.

Do not adjust the valve seat gas pressure switch GDW2

Boiler · Vitocrossal 200 CM2

GDW2 is factory set to 10 mbar (4 in. w.c.) and must be left alone. Its activation causes E1 or E2 faults on the burner control.

Applies to: GDW2 valve seat gas pressure monitoring switch

Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 26. Written in our own words; check the manual for your exact model.

Do not bend or kink capillaries

Boiler · Vitocontrol-S CM2

Warning: damaged capillaries cause control malfunction.

  1. Do not bend or kink the capillaries when routing them to the sensor well.

Applies to: Vitocontrol-S CM2 capillary sensors

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 70. Written in our own words; check the manual for your exact model.

Do not change Multi-boiler system menu item

Boiler · Vitodens 200-W

The 'Multi-boiler system' item turns a weather-compensated control unit into a constant temperature control unit. Do not adjust it during normal service.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 73. Written in our own words; check the manual for your exact model.

Do not change the Multi-boiler system menu item

Boiler · Vitodens 200-W

Changing this item turns a weather-compensated control unit into a constant temperature control unit. Leave it alone unless that is the intent.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA service instructions, p. 72. Written in our own words; check the manual for your exact model.

Do not connect the boiler 41-plug directly to the burner when venting is installed

Boiler · Vitotronic 200

If a venting system is installed, the 41-plug from the boiler control must not go straight to the burner.

  1. Connect the 7-pole plug to the wall vent system counter plug.
  2. See the technical instructions of the vent system.

Applies to: Vitotronic 200 KW2 with venting system

Source: Vitotronic 200 KW2 service instructions, p. 83. Written in our own words; check the manual for your exact model.

Do not mix vent systems

Boiler · Vitocrossal 200 CI2

Mixing pipe, fittings or joining methods from different vent manufacturers is not permitted.

  1. Use one vent manufacturer's pipe, fittings and joining method throughout.
  2. Follow the manufacturer's sidewall termination kit instructions.

Applies to: All vent materials

Source: Vitocrossal 200 CI2 Installation manual, p. 56. Written in our own words; check the manual for your exact model.

Do not operate a boiler that has been under water

Boiler · Vitotronic 300-K

A boiler that was submerged must not be used. The control system and any gas control that was under water must be replaced.

  1. Do not use the boiler.
  2. Call a qualified heating contractor to inspect the boiler.
  3. Replace any control system part and gas control that was under water.

Applies to: Vitotronic 300-K MW2C boiler system

Source: Vitotronic 300-K MW2C operating instructions, p. 5. Written in our own words; check the manual for your exact model.

Do not reroute the Switching Module-V terminals

Boiler · Vitotronic 200

The terminal assignment on the Switching Module-V is fixed and must not be changed.

  1. Keep the Switching Module-V wiring to the printed terminal assignment.

Applies to: Vitotronic 200 KW2 with Switching Module-V

Source: Vitotronic 200 KW2 service instructions, p. 80. Written in our own words; check the manual for your exact model.

Do not run the boiler in contaminated combustion air

Boiler · Vitodens 200-W B2HA

Dust, lint or chemical vapours damage the boiler and can cause carbon monoxide and property damage. Chemicals stored in the boiler room also produce poisonous by-products.

  1. Check the area for dust, lint or chemicals before start-up. These are common in construction sites, garages, workshops, dry cleaning or laundry areas, near pools and in manufacturing facilities.
  2. Do not operate the boiler if combustion air is contaminated. Relocate or correct the source first.
  3. Have the boiler inspected and serviced by a qualified heating contractor at least once a year.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 2. Written in our own words; check the manual for your exact model.

Do not run the control without the junction box lid

Boiler · Vitodens 100-W

The junction box lid separates mains and extra low voltage and seals the control enclosure off from the air box. It must be fitted when replacing the control unit or closing the enclosure.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 30. Written in our own words; check the manual for your exact model.

Do not run without the front cover

Boiler · Vitodens 200-W

Never operate the boiler with the front cover removed.

  1. Put the front cover back on before the boiler is run.

Applies to: All Vitodens 200-W B2HB models

Source: Vitodens 200-W B2HB Service Instructions, p. 2. Written in our own words; check the manual for your exact model.

Do not share the condensate drain

Boiler · Vitocrossal 300 CU3A

Other appliance drains must not feed the boiler condensate line.

  1. Do not connect the drain from any other appliance, such as a water softener backwash, to the condensate drain pipe.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 23. Written in our own words; check the manual for your exact model.

Do not use a damaged gas control or boiler that was under water

Boiler · Vitodens 200-W B2HA

If any part was under water, do not run the appliance. Have a qualified service technician inspect it and replace the water-damaged control system and gas control parts. Never use tools on the gas control knob.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 60. Written in our own words; check the manual for your exact model.

Domestic hot water tank connection point

Boiler · Vitotronic 300-K

If a DHW tank is part of the system, connect it at the Vitotronic 300-K, not at the boiler control.

Applies to: Vitotronic 300-K cascade systems with DHW tank

Source: Vitotronic 200 and 300-K installation and service instructions, p. 9. Written in our own words; check the manual for your exact model.

Domestic hot water temperature limit warning

Boiler · Vitotronic 100 GC1

Check the DHW tank temperature cannot exceed its maximum permitted value when the control runs with a DHW tank. Add a suitable safety device if the tank cannot guarantee this.

Applies to: Systems with DHW tank connected to the control

Source: Vitotronic 100 GC1 installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

Domestic hot water temperature warning

Boiler · Vitotronic 100 GC1

If the system is used with a domestic hot water tank, make sure the maximum allowed DHW temperature is not exceeded. Install a suitable safety device if needed.

Applies to: Systems with domestic hot water tank

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 32. Written in our own words; check the manual for your exact model.

Domestic hot water temperature with high limit

Boiler · Vitotronic 300

If the system is operated with a domestic hot water tank, do not exceed the maximum permissible DHW temperature. Install a suitable safety device if needed.

  1. Check that the maximum permissible DHW temperature is not exceeded.
  2. Install a suitable safety device if needed.

Applies to: Systems with a DHW tank and adjustable high limit

Source: Vitotronic 300 GW2 installation and service instructions, p. 24. Written in our own words; check the manual for your exact model.

Domestic hot water via indirect cylinder

Boiler · Vitocrossal 200 CM2

The boiler can supply domestic hot water through an indirect-fired storage tank. Connections and a correctly sized circulating pump are needed. The DHW control circuit is built into the Vitotronic control.

  1. Make the appropriate boiler connections to the storage tank.
  2. Fit a circulating pump of the correct size.
  3. Set up the DHW circuit in the Vitotronic control.

Applies to: Vitocrossal 200 CM2 with indirect-fired storage tank

Source: Vitocrossal 200 CM2 operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Draining the boiler at the end of heating season

Boiler · Vitotron 100 VLN2

Do not drain water from the boiler after the heating season.

  1. Leave the water in the boiler at the end of the heating season.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 3. Written in our own words; check the manual for your exact model.

EA1 extension terminal layout

Boiler · Vitocrossal 300 CA3B Dual Fuel

The EA1 extension has three digital inputs (DE1, DE2, DE3), a 0-10 V analog input, a mains connection, a power supply for extra accessories, a floating switching output (aBJ) and a KM-BUS connection.

Applies to: EA1 extension

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 32. Written in our own words; check the manual for your exact model.

EA1 internal extension terminals

Boiler · Vitodens 200-W

Extension EA1 has three digital inputs (DE1 to DE3), a 0-10 V input, power supply terminals and output aBJ (central fault message, feed pump or DHW recirculation pump, potential-free).

  1. Refer to the main wiring diagram on page 95 before wiring field contacts.
  2. Assign the function of each input and of output aBJ with the coding codes listed on the following pages.

Applies to: Internal extension EA1

Source: Vitodens 200-W B2HA service instructions, p. 90. Written in our own words; check the manual for your exact model.

Economy mode (energy saving)

Boiler · Vitotronic 300-K, Vitotronic 200

Lowers room temperature in standard heating mode, for example when the building is empty for a few hours.

  1. Open the extended menu and select Heating.
  2. Select the heating circuit if needed.
  3. Select Economy mode and set it as required.
  4. To end early, set Economy mode to OFF.
  5. It also ends automatically when the time program switches to reduced heating mode.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 20. Written in our own words; check the manual for your exact model.

Electrical code compliance

Boiler · Vitocrossal 300 CU3A

Electrical installation must follow the current NEC (ANSI/NFPA 70) and any state or local codes in the USA. In Canada, follow the CEC (CSA C22.1 Part 1) and any provincial or local codes.

  1. Follow NEC / ANSI/NFPA 70 and local code in the USA.
  2. Follow CEC CSA C22.1 Part 1 and local code in Canada.

Applies to: Vitocrossal 300 CU3A electrical installation

Source: Vitocrossal 300 CU3A installation instructions, p. 58. Written in our own words; check the manual for your exact model.

Electrical code requirements

Boiler · Vitocrossal 300 CU3A

Wiring must follow the current national electrical code and local rules. In the US that is the NEC, and in Canada the CEC.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A installation manual, p. 31. Written in our own words; check the manual for your exact model.

Electrical connection overview: wiring points on the boiler

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The connection overview lists where field wiring lands on the CA3B Dual Fuel boiler.

  1. Route sensor and low-voltage wiring in the lower cable tray.
  2. Route power supply wiring in the upper cable tray.
  3. Connect supply temperature sensors for heating circuits M2/M3, external LON participants (Vitotronic 200-H), pumps and mixing valve, the internal disconnect switch with lockout provision, the EA1 extension and the fuel selector switch.
  4. On 5.0 and 6.0 models, the Section 3 control is also wired in.

Applies to: CA3B Dual Fuel, all models

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 18-19. Written in our own words; check the manual for your exact model.

Electrical installation requirements

Boiler · Vitodens 100-W

The control must be grounded. L, N and G must not be interchanged. Installation must follow the NEC/ANSI/NFPA 70 in the USA or the CEC/CSA C22.1 Part 1 in Canada, plus local rules.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 28. Written in our own words; check the manual for your exact model.

Electrical safety before servicing

Boiler · Versatronik

The control has more than one live circuit. The control is not a safety device, and there are no user-serviceable parts inside.

  1. Turn off power to the control and to the damper/blower before servicing.
  2. Check the wiring diagram in the manual, because more than one circuit is live.
  3. Keep static electricity under control when working inside the control, since static-sensitive components can be damaged by improper handling.

Applies to: Versatronik 200 System Control

Source: Versatronik 200 installation and operating manual, p. 3-4. Written in our own words; check the manual for your exact model.

Electrical service precautions

Boiler · Vitocrossal 300 CU3A

Safety notes for wiring and service work.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them when servicing controls.
  3. Replace any original wire only with an exact equivalent.
  4. Verify proper operation after servicing.

Applies to: Vitocrossal 300 CU3A service

Source: Vitocrossal 300 CU3A technical data manual, p. 28. Written in our own words; check the manual for your exact model.

Electrical servicing precautions

Boiler · Vitodens 200-W B2HB

WARNING: Disconnect power before servicing the boiler. Electrical installations must follow the NEC (ANSI/NFPA 70) and state or local codes in the U.S.A., or the CEC (CSA C22.1 Part 1) and provincial or local codes in Canada. Wiring errors can cause improper and dangerous operation.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any original wire only with an exact equivalent.
  4. Assign only one function or accessory to each connection.
  5. Verify proper operation after servicing.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 47. Written in our own words; check the manual for your exact model.

Electrical supply and condensate drain location

Boiler · Vitodens 222-F

The external accessories connection box needs a 120 VAC wall receptacle supply. The condensate drain is on the boiler side. See the wiring diagram on page 41 for connections.

  1. Run 120 VAC to the external accessories connection box.
  2. Connect the condensate drain on the side of the boiler.

Applies to: Vitodens 222-F B2TB

Source: Viessmann Vitodens 222-F B2TB installation manual, p. 12 and p. 13. Written in our own words; check the manual for your exact model.

Electrical use of zone circulators

Boiler · Vitocrossal 300 CU3A

Zoning with several circulators adds electrical consumption. Check for more efficient options during design.

Applies to: Vitocrossal CU3A zoned systems

Source: Vitocrossal 300 CU3A application guide, p. 30. Written in our own words; check the manual for your exact model.

Electrical work code requirements

Boiler · Vitodens 200-W B2HB

All field wiring must follow the latest National Electrical Code (US) or Canadian Electrical Code (Canada) plus any state, province or local rules.

Applies to: All Vitodens 200-W B2HB models

Source: Vitodens 200-W B2HB technical data manual, p. 48. Written in our own words; check the manual for your exact model.

Emergency and dangerous-condition shutdown

Boiler · Versatronik 503, NR2/Analog Bridge

If a dangerous condition exists, shut the system down at once.

  1. Turn off main power immediately.
  2. Close the gas supply valve.
  3. In an emergency, switch off the external power supply to the panel at its separate fuse or power supply.

Applies to: Versatronik 503 NR2/Analog Bridge

Source: Viessmann NR2/Analog Bridge installation manual, p. 2. Written in our own words; check the manual for your exact model.

Enable separate room temperature sensor on remote control

Boiler · Vitotronic 300-K MW1S

When a separate room temperature sensor is connected to the remote control, its DIP switch must be turned on.

  1. Open the top casing of the remote control to reach the printed circuit board DIP switches.
  2. For Vitotrol 200, set DIP switch S6.3 to ON.
  3. For Vitotrol 300, set DIP switch S30.3 to ON.

Applies to: Vitotrol 200 and Vitotrol 300

Source: Viessmann Vitotronic 300-K MW1S installation and service instructions, p. 131. Written in our own words; check the manual for your exact model.

Energy metering correction factor and calorific value

Boiler · Vitodens 100-W B1HE/B1KE

Used to set the arithmetic consumption calculation. The numeric values are not printed on these pages.

  1. Select Energy metering, then Consumption, then Settings.
  2. Select Correction factor or Calorific value, then confirm with OK.
  3. Enter the values and acknowledge with OK.

Applies to: Energy metering

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 22. Written in our own words; check the manual for your exact model.

Energy saving recommendations

Boiler · Vitotrol 300A

Reduce room and DHW temperatures and use the right program to save energy.

  1. Do not set the room temperature above 68 °F (20 °C); each degree of reduction saves up to 6% on heating costs.
  2. Do not set the DHW temperature too high.
  3. Enable the DHW recirculation pump only when DHW is drawn off.
  4. Use economy mode for short absences and the holiday program for longer absences.
  5. In summer, use the Only DHW program if rooms do not need heat.
  6. Use Standby mode if neither rooms nor DHW are needed for an extended period.

Applies to: Vitotrol 300A users

Source: Vitotrol 300A operating instructions, p. 4. Written in our own words; check the manual for your exact model.

Energy saving settings

Boiler · Vitocrossal 200 CI2

Lower the DHW temperature at night or during absences and limit DHW recirculation to the hours of use. Keep standard room temperature at or below 68°F (20°C). Use the reduced room or supply temperature at night and during absences. Set unused heating circuits to Standby mode, and use the holiday program when away, which lowers the room temperature and turns off DHW heating.

  1. Adjust the DHW time program and DHW recirculation time program to match hot water use.
  2. Set the room set temperature to 68°F (20°C) or less.
  3. Set Standby mode on heating circuits not needed (for example central heating in summer).
  4. Select the holiday program before going away.

Applies to: Vitocrossal 200 CI2 central heating and DHW

Source: Vitocrossal 200 CI2 operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Energy saving settings for the standard room temperature

Boiler · Vitocrossal 300 CA3B

Each degree of room temperature reduction saves up to 6% on heating. The standard room temperature should not exceed 68°F (20°C).

  1. Keep the standard room temperature at or below 68°F (20°C).
  2. Use the time program to heat to standard temperature during the day and reduced temperature at night.
  3. Use Economy mode for short absences.

Applies to: Vitocrossal 300 CA3B, all sizes 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 13. Written in our own words; check the manual for your exact model.

Energy saving tips for DHW and heating

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Lowering the DHW temperature at night or during absences saves energy. Each degree of room temperature reduction saves up to 6% on heating bills. In weather-compensated operation, keep the standard room temperature at or below 68°F (20°C).

  1. Lower the DHW time program or temperature for nights and absences.
  2. Use DHW recirculation only during the times hot water is regularly used.
  3. In weather-compensated operation, keep the Standard temperature level at or below 68°F (20°C).
  4. Use a reduced room or supply temperature at night and during absences.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Energy saving tips for the heating system

Boiler · Vitotrol 300

Practical habits that reduce heating energy use. Heating contractor maintenance and insulation also matter.

  1. Ventilate properly and do not overheat.
  2. Aim for a room temperature of 20 ºC (68 ºF). Each degree saves up to 6 % of heating cost.
  3. Use reduced room temperature at set times.
  4. Keep radiators and thermostatic valves unobstructed and adjust valves properly.
  5. Adjust the DHW tank temperature at the control unit.
  6. Use hot water in a controlled way. A shower typically uses less energy than a bath.
  7. Have the heating system maintained regularly by the heating contractor.
  8. Check insulation of heating system and DHW piping, outside walls, roof, windows and between heated and unheated rooms.

Applies to: Heating systems controlled with Vitotrol 300

Source: Vitotrol 300 operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Enter contractor contact details

Boiler · Vitocrossal 200 CI2

Contact details entered here can be called up later in the Information menu.

  1. Open Information.
  2. Select 'Contractor contact details'.
  3. Select the entry field.
  4. Enter the contractor's details in each box.
  5. Confirm.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Example single-boiler layout with three-way mixing valve

Boiler · Vitotronic 100 GC1

Circuit diagram 1 shows a single Vitorond 200 VD2A boiler with Therm-Control and a three-way mixing valve. The diagram includes a heating circuit with mixing valve, a DHW tank with primary and circulation pumps, a burner with stage 2 or modulating output, and a 120 VAC supply that needs a main isolator. External connections are covered in the Vitotronic 300 GW2 control manual.

  1. Install the main isolator per local regulations before connecting the power supply.
  2. Use the Vitotronic 300 GW2 control manual for external connections.

Applies to: Single-boiler system with Therm-Control and three-way mixing valve, Vitorond 200 VD2A

Source: Vitotronic 100 GC1 installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Example: boiler set-point boost after switching to normal room temperature (FA:20, Fb:30)

Boiler · Vitotronic 200-H

When operation changes from reduced to normal room temperature, the boiler set-point is raised by a percentage for a set time. Example: boiler set-point from the heating curve is 50°C / 122°F; with FA 20% it becomes 60°C / 146°F and is held for 60 minutes (Fb 30 steps at 2 minutes each).

  1. Confirm FA (raise %) and Fb (duration) values in Coding 2.
  2. Note the boiler set-point from the heating curve at the time of the switch.
  3. Verify the raised set-point holds for the coded duration before it returns to the curve.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 50. Written in our own words; check the manual for your exact model.

Example: outdoor temperature raises the reduced room set-point (F8:-5, F9:-14)

Boiler · Vitotronic 200-H

With an outdoor sensor, the reduced room set-point rises as outdoor temperature falls. Example: reduced room set-point 3°C / 37°F, normal room set-point 20°C / 68°F. The raise starts below -5°C / 23°F (F8) and reaches normal room temperature at -14°C / 7°F (F9).

  1. Check that F8 is -5 and F9 is -14 (factory defaults).
  2. Confirm the reduced set-point (3°C / 37°F) and normal set-point (20°C / 68°F) are as expected.
  3. Watch the room set-point climb along the heating curve between the two outdoor limits.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H installation and service instructions, p. 50. Written in our own words; check the manual for your exact model.

Exhaust vent pipe material

Boiler · Vitocrossal 300 CA3B Dual Fuel

Only ULC S-636 / UL 1738 listed vent material may be used for the exhaust vent pipe.

  1. Check the vent pipe label for ULC S-636 / UL 1738 before installing the exhaust.

Applies to: Exhaust vent pipe

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 57. Written in our own words; check the manual for your exact model.

Expert level menu groups

Boiler · Versatronik 200

The expert level menu is organised into these groups: Configuration, Heat source, Cascade, Tank, Slab curing, 0-10 I/O, DHW, Heating circuit 1, Heating circuit 2, Solar / MF, and Cooling operation. Subgroups include bus ID, boiler type, sequencing, hysteresis, voltage curves, DHW pump function, mixing valve timing, and solar protection parameters. Parameter values are not printed on these pages.

  1. Open Main Menu, then Expert level.
  2. Select the group that matches the component to set.
  3. Refer to the parameter table in the manual for the correct values.

Applies to: Versatronik 200 System Control expert level

Source: Versatronik 200 manual, p. 71. Written in our own words; check the manual for your exact model.

Expert menu branches (menu map)

Boiler · Versatronik 200

The Expert level menu is split into branches for heat source, cascade, buffer tank, 0-10/slab curing/DHW, two heating circuits, solar/MF and Expert Level IM. The menu map pages show only the branch headings. The individual settings are in diagram form and cannot be read from the text.

  1. Open the Main Menu, then go to the Expert level.
  2. Choose the branch that matches the equipment: Heat Source, Cascade, Buffer Tank, 0-10/Slab Curing/DHW, Heating Circuit 1, Heating Circuit 2, Solar/MF or Expert Level IM.
  3. Check the full menu diagram in the manual for the exact settings in each branch.

Applies to: Versatronik 200 Expert menu

Source: Versatronik 200 installation and operating manual, p. 88-95. Written in our own words; check the manual for your exact model.

Extended and standard menu layout

Boiler · Vitotronic 300-K

The extended menu holds Information, Fault, Solar energy, Test mode, Boiler sequence, Economy and Party modes, plus the heating and DHW program groups. The standard menu holds Settings, Time/Date, Language, Contrast, Brightness, Temperature unit, Name for heating circuit and Holiday program.

  1. Use the menu overview on p. 40 to find each function before adjusting it.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 40. Written in our own words; check the manual for your exact model.

Extended menu structure

Boiler · Vitocrossal 300 CU3A

Top-level groups of the extended menu are Heating, DHW, Information, Settings, Test mode and Solar energy. Settings include time and date, language, contrast, brightness, temperature unit and heating circuit names. Heating covers room temperature and operating program settings, time programs, holiday program, heating curve and zone circuits. DHW covers DHW temperature and time programs.

  1. Use the overview to find the menu group you need.
  2. Check the Heating, DHW and Settings groups for the setting to change.

Applies to: Vitocrossal 300 CU3A with Vitotronic 200 KW6B

Source: Vitocrossal 300 CU3A operating instructions, p. 40. Written in our own words; check the manual for your exact model.

External 0-10 V DC signal connection

Boiler · Vitodens 222-F, B2TB

The external 0-10 V DC signal connects to the plug labelled 0-10VDC in the external connection accessory box. The manual refers to a chart for maximum boiler water temperature versus signal, but that chart is not on the pages supplied.

  1. Connect the external 0-10 VDC signal to plug 0-10VDC in the external connection accessory box.
  2. Make sure the polarity is correct.
  3. Use the manufacturer's chart for the maximum boiler water temperature and required signal.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB Installation Instructions, p. 49. Written in our own words; check the manual for your exact model.

External accessory connection box wiring

Boiler · Vitodens 200-W B2HB

The external accessory connection box takes a 0-10V input for accessories such as a Vitotrol remote or a mixing valve, and the pump. Power is 120/1/60, 12 A full load amperage, supplied through a disconnect and protection. Wiring must follow the NEC/ANSI NFPA 70 in the USA and the CEC CSA C22.1 Part 1 in Canada, plus local codes. See the wiring diagram on p. 47 for connection to the control base.

  1. Provide power supply at 120/1/60 with a disconnect and overcurrent protection, rated for 12 A full load.
  2. Connect the 0-10V input for accessories as required.
  3. Connect the pump.
  4. Follow NEC or CEC and local electrical codes.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 27. Written in our own words; check the manual for your exact model.

External contacts must be potential-free

Boiler · Vitotronic 300

Live contacts on the aVD, aBÖ and similar inputs cause short circuits or phase failure.

  1. Confirm each external contact is dry (potential-free) before connecting.
  2. Use normally closed contacts for safety chains at plug aBÖ.

Applies to: Vitotronic 300 GW6B

Source: Vitotronic 300, GW6B installation and service instructions, p. 37, 40. Written in our own words; check the manual for your exact model.

External potential-free contacts on 24 VAC thermostat terminals

Boiler · Vitotronic 100

Room thermostats or other potential-free contacts, such as a zone valve end switch, connect to the 24 VAC thermostat terminals. Contacts must have adequate insulation clearance to live parts and must be certified for this application.

  1. Confirm the contact has sufficient insulation clearance to live parts.
  2. Confirm the contact is certified for this application before connecting it to the thermostat terminals.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 6. Written in our own words; check the manual for your exact model.

External safety and disable connections

Boiler · Vitotronic 100 GC1

Jumpers on the line voltage motherboard must be removed before external safety equipment or an external disable is wired in.

  1. Remove the jumper at terminal a before connecting external safety equipment.
  2. Remove the jumper at terminal b before connecting an external disable.
  3. Connect the external burner activation at terminal c as needed.

Applies to: Vitotronic 100 GC1 line voltage motherboard

Source: Vitotronic 300-K MW1S installation and service manual, p. 171. Written in our own words; check the manual for your exact model.

Factory default time programs

Boiler · Vitotronic 200-H

Factory default: heating at normal room temperature from about 6:00 to 22:00, domestic hot water from about 5:30 to 22:00 if a DHW tank is fitted, and reduced room temperature with frost protection at 3 C (37 F) from 22:00 to 6:00. Date and time are preset and change for winter and summer time automatically.

Applies to: Vitotronic 200-H HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 4. Written in our own words; check the manual for your exact model.

Fault code variables on the gateway

Boiler · Versatronik 501

Boiler 1 to 4 and zone/cascade fault code points carry the Appendix A fault code. Relay state points carry the Appendix B state.

Applies to: Versatronik 501 gateway fault variables

Source: Versatronik 501 NR2/LON communication manual, p. 20. Written in our own words; check the manual for your exact model.

Fault codes are shown in hexadecimal

Boiler · Versatronik 300 Cascade Control

The control shows fault codes in hex to save screen space. The base format shown on a BMS depends on the BMS software. The manual gives Niagara AX examples: a mask on a numeric bit-and object shows the hex value, and a numeric-to-enum conversion maps the codes to text.

  1. Check the hex code in the fault table (column 1) against the display.
  2. Use the decimal column when the BMS shows base 10.

Applies to: Versatronik 300 cascade control

Source: Versatronik 300 Cascade Control manual, p. 43. Written in our own words; check the manual for your exact model.

Fault display format

Boiler · Vitotronic 200

A fault on the display shows plain text or a fault code, a fault number from 1 to 10, and a fault symbol. Faults shown in plain text include burner, fixed high limit, safety circuit, outdoor sensor, supply sensor, DHW tank sensor, return sensor, room sensor and flue gas sensor. The fixed high limit, safety circuit and flue gas sensor only show with the fault indication module accessory.

Applies to: Vitotronic 200 KW2

Source: Vitotronic 200 Service Instructions, p. 35. Written in our own words; check the manual for your exact model.

Fault indication module

Boiler · Vitotronic 200

Faults show on the display and trigger the central fault output on the Switching Module-V accessory.

Applies to: Fault indication and Switching Module-V

Source: Vitotronic 200 service instructions, p. 65. Written in our own words; check the manual for your exact model.

Fault memory

Boiler · Vitocrossal 200 CI2

The 10 most recent faults are saved. The newest code is shown first, followed by earlier codes. If the burner restarts repeatedly on a non-lockout fault without a code, the fault memory may show the cause.

  1. Open the fault memory to read the last 10 faults.
  2. Check the newest code first, then the earlier codes.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 76. Written in our own words; check the manual for your exact model.

Fault messages: acknowledge and recall

Boiler · Vitodens 200-W, Vitotronic 200, Vitocrossal 300

A fault flashes the fault symbol and shows "Fault", and the red fault indicator flashes. Acknowledging stops the flashing but the fault message returns the next day if the fault is not fixed. Signalling equipment such as a buzzer is switched off on acknowledgement.

  1. Note the fault code and give it to the heating contractor.
  2. Acknowledge the fault with OK.
  3. To recall an acknowledged fault, tap OK for about 4 seconds, or use the extended menu and select "Fault".
  4. If there are several faults, scroll through them with the arrow keys.
  5. For the meaning of fault codes, refer to the Vitodens 200-W and Vitocrossal 300 CU3A Service Instructions.

Applies to: Vitodens 200-W and Vitocrossal 300 CU3A

Source: Viessmann Vitotronic 200 Operating Instructions, p. 15. Written in our own words; check the manual for your exact model.

Fault reporting in GW6B lead and lag system

Boiler · Versatronik 585

The lead boiler shows its own faults. The gateway does not pass lag boiler faults to the BMS as lead faults, but it reports each boiler fault on its own boiler fault point.

  1. If the physical control shows a fault but the gateway does not report it, check the fault point for the boiler that has the fault.
  2. Boiler 1 fault point shows only faults from the lead boiler (boiler 1).

Applies to: Vitotronic 300 GW6B cascade

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 15. Written in our own words; check the manual for your exact model.

Fault search and acknowledging a fault (Vitocontrol-S)

Boiler · Vitocontrol-S VD2/CT3/CM2

The programming unit shows the fault in plain language and as a fault code. Acknowledging stops the lamp flashing only for that fault and the fault message comes back at 7:00 the next day if it is still present.

  1. Open the hinged cover on the programming unit.
  2. Press the fault search button. The error source appears in plain language and as a fault code.
  3. Press the next key until the display shows 'Acknowledge? Yes'.
  4. Use the arrow keys to choose Yes or No.
  5. Press confirm. The display returns to the boiler temperature.
  6. Close the hinged cover on the programming unit.
  7. To view an acknowledged fault again, press the fault key for about 2 seconds. Use the arrow keys to scroll if two or more faults exist.

Applies to: Vitocontrol-S VD2/CT3/CM2

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 33. Written in our own words; check the manual for your exact model.

Fault system behavior definitions

Boiler · Vitodens 200-W

The fault tables use three behavior terms: control mode, burner in fault mode, and burner blocked.

  1. Control mode: boiler and burner stay fully operational. The fault code must still be verified and reset.
  2. Burner in fault mode: boiler control needs a manual reset (reset button R) before the burner can run again.
  3. Burner blocked: the burner resumes operation once the fault cause is corrected.
  4. Some codes stay on factory default settings (control mode with factory default) until the part is fixed.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB service instructions, p. 75-80. Written in our own words; check the manual for your exact model.

Field cabling and routing requirements

Boiler · Vitodens 200-W B2HB

Cables required in the field include the outdoor sensor, mixing valve control, mixing valve kit, remote operating mode switching, remote disable, alarm output, wall-mount base and circulating pump. Route cables as illustrated so the control unit can move freely. Do not secure cables to the control unit bracket. Keep cable temperatures within their rated limits.

  1. Run cables as shown in the installation illustration so the control unit moves freely.
  2. Do not clamp cables to the control unit bracket.
  3. Check that cable temperature ratings are not exceeded where cables are routed and secured.
  4. Only one accessory or switch contact may be connected to a plug contact at a time.
  5. Read the accessory's own installation instructions for other required steps.

Applies to: Vitodens 200-W B2HB field wiring

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 47. Written in our own words; check the manual for your exact model.

Field cabling needed for accessories

Boiler · Vitocrossal 300 CU3A

These accessories need field cabling to the boiler control. Only one accessory or one switch contact can be connected to a plug contact at a time.

  1. Cable the outdoor temperature sensor.
  2. Cable the Vitotronic 200-H and HK1B mixing valve control.
  3. Cable the accessory kit for a heating circuit with mixing valve.
  4. Cable remote switching of operating mode.
  5. Cable remote disable.
  6. Cable the alarm output.
  7. Cable the wall-mount base.
  8. Cable the circulating pump.
  9. Cable the zone circuit thermostats.

Applies to: Vitocrossal 300 CU3A boiler accessories

Source: Vitocrossal 300 CU3A installation instructions, p. 56. Written in our own words; check the manual for your exact model.

Field contact requirements for digital inputs

Boiler · Vitodens 200-W

External contacts must be floating (dry). Observe safety category II: 8.0 mm air and creep path, or 2.0 mm insulation thickness to live parts.

  1. Use floating contacts only on DE1 to DE3.
  2. Keep the required clearances to live parts when wiring.
  3. For brief DHW recirculation pump operation, use a pushbutton contact on DE1, DE2 or DE3 and set the runtime with coding address 3D.

Applies to: Extension EA1 digital inputs

Source: Vitodens 200-W B2HA service instructions, p. 91. Written in our own words; check the manual for your exact model.

Field modifications void CSA certification

Boiler · Versatronik 503, NR2/Analog Bridge

Changing this control panel in the field cancels the factory CSA certification. If you modify it, an electrical safety field inspection is required under local codes. Viessmann is not responsible for damage from field modifications.

Applies to: Versatronik 503 NR2/Analog Bridge

Source: Viessmann NR2/Analog Bridge installation manual, p. 4. Written in our own words; check the manual for your exact model.

Field wiring to digital inputs and low-voltage outputs

Boiler · Vitotronic 200-H

Keep the separation required for external contacts and the 0-10 V input.

  1. For external contacts, observe safety category II: 8.0 mm air gap and creep path, or 2.0 mm insulation thickness against live parts.
  2. Ensure DC separation between the LV output and the earth conductor of the on-site voltage source when using the 0-10 V input.

Applies to: EA1 extension module and external connections

Source: Vitotronic 200-H HK1B installation and service instructions, p. 77. Written in our own words; check the manual for your exact model.

Field-supplied controls and OpenTherm

Boiler · Vitodens 100-W, WB1B

Field-supplied operating controls connect to the terminal strip for accessories. Follow the installation instructions of those controls. OpenTherm is a point-to-point link between the boiler and a room controller that sends a heat demand (water temperature request). The Viessmann Input Module accepts a 0-10 VDC modulating signal from a boiler reset controller and sends it to the Vitodens 100 over OpenTherm.

  1. Wire the field outdoor temperature sensor and OpenTherm connections to the terminal strip as shown in the manual.
  2. Follow the field controls' installation instructions.

Applies to: Terminal strip for accessories, OpenTherm, outdoor sensor

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 84. Written in our own words; check the manual for your exact model.

Find active faults and service messages

Boiler · Vitodens 100-W B1HE/B1KE

Active messages appear in the main menu when a fault, warning or service message is present. Faults and warnings are sorted into their own entries, and the message history is kept under Information.

  1. Open the main menu from the home screen.
  2. Select Active messages or Faults and Warnings.
  3. Tap Acknowledge to clear a fault or service message that is listed.
  4. Check Information > Message history for earlier messages.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE Operating Instructions, p. 33-34. Written in our own words; check the manual for your exact model.

Find the serial number before ordering parts

Boiler · Vitodens 222-F

Parts orders need the 16-digit boiler serial number from the bar code label, or the 12-digit ASME/NB serial. Serial 7542250 applies to B2TB 19 and 68; serial 7542251 applies to B2TB 35 and 125. Some parts are not reverse compatible with earlier versions, so always quote the serial.

  1. Remove the front enclosure panel to reach the serial number location.
  2. Note the 16-digit bar code serial or the 12-digit ASME/NB serial.
  3. Quote the serial when ordering replacement parts.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 8. Written in our own words; check the manual for your exact model.

Finding and acknowledging faults on the 300-K

Boiler · Vitotronic 300-K MW1S

Fault numbers are shown as a consecutive number (1 to 10) with a code. The red fault lamp flashes for all faults.

  1. Press the fault button to show the fault.
  2. Scroll through further fault codes with the arrow buttons.
  3. Acknowledge a fault with the acknowledge button. The message hides but the red lamp keeps flashing.
  4. To view acknowledged faults, press and hold the button for about 3 seconds, then select with the arrow buttons.
  5. An unacknowledged fault returns the following morning if it is not cleared.

Applies to: Vitotronic 300-K MW1S

Source: Vitotronic 100 GC1 / 300-K MW1S service instructions, p. 99-100. Written in our own words; check the manual for your exact model.

Finding the serial number for parts orders

Boiler · Vitodens 222-F

Parts orders need either the 16-digit serial on the bar code label or the 12-digit ASME/NB serial. Both are under the boiler front enclosure panel.

  1. Remove the front enclosure panels (see the front panel removal guide).
  2. Read the 16-digit bar code serial or the 12-digit ASME/NB serial.
  3. Give the boiler serial number when ordering replacement parts.

Applies to: All B2TB 19, 35, 68, 125 models

Source: Viessmann Vitodens 222-F B2TB installation manual, p. 8. Written in our own words; check the manual for your exact model.

Fire in the boiler room

Boiler · Vitodens 200-W B2HA

If fire is seen coming from the appliance, call the fire department first. Do not fight the fire unless trained to do so.

  1. Shut down the boiler.
  2. Close the fuel shut-off valves.
  3. Use a tested class ABC fire extinguisher only if qualified.

Applies to: Vitodens 200-W B2HA 112, 150, 399, 530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 10. Written in our own words; check the manual for your exact model.

Fire response

Boiler · Vitocrossal 300 CU3A

If the appliance is on fire, call the fire department. Only attempt to extinguish if qualified.

  1. Call the fire department immediately.
  2. Shut down the boiler.
  3. Close fuel shutoff valves.
  4. Use a tested class ABC fire extinguisher only if qualified.

Applies to: Boiler room fire

Source: Vitocrossal 300 CU3A service instructions, p. 9. Written in our own words; check the manual for your exact model.

Fitting the front panel

Boiler · Vitocrossal 300 CU3A

Refit the front panel by locating it on the pegs and securing it at the top.

  1. Place the front cover onto the locating pegs.
  2. Push the top of the panel in place.
  3. Secure the panel with the retaining screw.

Applies to: Vitocrossal 300 CU3A front panel

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 103. Written in our own words; check the manual for your exact model.

Fixed high limit location for underfloor heating

Boiler · Vitotronic 300

An adjustable high limit is required for underfloor heating. The fixed high limit goes in the heating supply pipe after the mixing valve and the heating circuit pump.

  1. Install the fixed high limit in the heating supply pipe downstream of the mixing valve and the heating circuit pump.
  2. Follow the limit thermostat installation instructions.

Applies to: Vitotronic 300 with underfloor heating

Source: Vitotronic 300 installation instructions, p. 16. Written in our own words; check the manual for your exact model.

Fixed high limit warning

Boiler · Vitotronic 100 GC1

If the fixed high limit is set to 99 °C / 210 °F, keep the adjustable high limit at or below 75 °C / 167 °F.

Applies to: Vitotronic 100 GC1

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 31. Written in our own words; check the manual for your exact model.

Flashing and storm collar selection

Boiler · Vitocrossal 200 CI2

Flashings and storm collars are field supplied and must suit the vent type.

  1. Use flashings and storm collars rated for Type B vent materials or better.
  2. Follow the installation instructions from the special venting manufacturer.

Applies to: Roof and wall vent penetrations

Source: Vitocrossal 200 CI2 Installation manual, p. 57. Written in our own words; check the manual for your exact model.

Flashing data in display means settings can be changed

Boiler · Vitotronic 200-H

When a value flashes in the display window, the control is waiting for a new setting to be entered.

  1. Use the setting buttons to enter the new value while it flashes.
  2. Confirm the entry with the confirmation button.

Applies to: Vitotronic 200-H HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Flashing data in the display means input is open

Boiler · Vitotronic 200-H

Data flashing in the display window means the value can be changed now.

  1. Use the up/down buttons to set the value.
  2. Press the confirm button to store it; the value stops flashing.

Applies to: HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Flashing data means it can be changed

Boiler · Vitocontrol-S

When the value in the display flashes, a new setting can be entered. Use the value selector to change it and confirm with the confirmation button.

  1. Wait for the value to flash in the display.
  2. Use the value selector to set the new value.
  3. Press the confirmation button to save it.

Applies to: Vitocontrol-S and Vitotronic 100, GC1

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 6, p. 8. Written in our own words; check the manual for your exact model.

Flashing data means the value can be changed

Boiler · Vitotronic 300

Flashing data in the display window means a new setting can be entered.

  1. Use the setting buttons to change the flashing value.
  2. Confirm to store it.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Flow check valve and underfloor heating notes

Boiler · Vitotronic 200

A flow check valve is only needed when the piping connects to one common boiler return. For underfloor heating, the control measures supply and return water temperature, so the return water sensor is used.

Applies to: System layouts in Application Examples 2 and 3

Source: Vitotronic 200 KW2 service instructions, p. 9 and p. 12. Written in our own words; check the manual for your exact model.

Flow check valve on the supply side

Boiler · Vitorond 200 VD2A

Install a spring-loaded flow check valve just downstream of the circulation pump. It stops unintended flow to space heating during DHW priority or summer operation.

  1. Install the spring-loaded check valve immediately after the circulation pump on the heating circuit supply.

Applies to: Heating circuit supply

Source: Vitorond 200, VD2A Series Installation, p. 22. Written in our own words; check the manual for your exact model.

Flue connection and venting practice

Boiler · Vitocrossal 200 CI2

Keep the flue run to the boiler as short as possible with a slight rise of 2-3 degrees and no sharp bends. Support all venting components so connections carry no load or torque. The boiler flue collar is not designed to carry the weight of the vent, so the vent must be anchored per the venting manufacturer. A flue gas adaptor may be needed (supplied by the venting manufacturer) for stainless steel venting. Insert the adaptor fully into the flue outlet, and seat the vent fully into the flue gas collector. Check every joint for leaks with a certified leak detector. Escaping flue gas can cause fatal carbon monoxide poisoning. Refer to the common venting instructions for the Vitocrossal 200 CI2 when venting is shared. A motorized flue gas damper is available for common vented systems.

  1. Run the flue outlet to the flue pipe on the shortest route with a slight rise of 2-3 degrees.
  2. Avoid sharp bends in the flue run.
  3. Support all venting components so connections carry no load or torque.
  4. Anchor the vent with a system approved by the venting manufacturer.
  5. Fit a flue gas adaptor from the venting manufacturer if needed for stainless steel venting, fully inserted in the flue outlet.
  6. Seat the venting fully into the flue gas collector.
  7. Check all vent and coupling connections for leaks with a certified leak detector.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 47-48. Written in our own words; check the manual for your exact model.

Flue gas temperature and efficiency

Boiler · Vitodens 222-F

Flue gas runs only about 5 to 15°C (9 to 27°F) above boiler return temperature. Efficiency depends on system return temperature and load.

  1. Keep system return temperatures low to get the best efficiency.
  2. Check the waterside flow information on page 8 before sizing piping.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F application guide, p. 12. Written in our own words; check the manual for your exact model.

Flue gas temperature and protection

Boiler · Vitodens 222-F

Flue pipes are rated for a maximum flue gas temperature of 230°F (110°C). No flue gas temperature protection is required because the maximum is not exceeded in any operating or malfunction condition.

Applies to: Vitodens 222-F, B2TB 68 and 125

Source: Vitodens 222-F B2TB application guide, p. 16. Written in our own words; check the manual for your exact model.

Flue gas temperature rating

Boiler · Vitodens 100-W, B1HE, B1KE

Coaxial PPS flue pipes are rated up to 230°F (110°C) max flue gas temperature. Flue gas temperature protection is built in.

  1. Confirm the flue pipe material is rated for the expected flue gas temperature.
  2. Refer to the Vitodens venting installation instructions for full venting detail.

Applies to: Coaxial PPS flue installations

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 26. Written in our own words; check the manual for your exact model.

Flue products and nearby building materials

Boiler · Vitodens 100-W

Flue products vented close to unprotected surfaces can stain or damage some building materials. Shield exposed surfaces with corrosion-resistant material such as aluminum sheeting before fitting the vent termination. Install the vent termination on the leeward side of the building.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 26. Written in our own words; check the manual for your exact model.

Follow the Viessmann maintenance schedule

Boiler · Vitorond 200 VD2

Service the boiler according to the maintenance schedule in these service instructions. Annual professional service is needed before each heating season.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200 VD2 Service Instructions, p. 2. Written in our own words; check the manual for your exact model.

Free up DIN rail space for accessory adaptors (CM2)

Boiler · Vitotronic 100, GC1

Remove the four spare DIN terminals to make room for accessory adaptors.

  1. Pull up on the bottom front of the DIN rail clamp and set it aside.
  2. With a flat-head screwdriver, remove spare terminals 23, 24, 25 and 26 one at a time. Turn the screwdriver clockwise between rail and terminal base.
  3. Discard the removed terminals.
  4. Refit the DIN rail clamp: hook the latch over the top of the rail, then push the front down.

Applies to: CM2

Source: Vitotronic 100, GC1 installation manual, p. 58. Written in our own words; check the manual for your exact model.

Free-standing frame mounting

Boiler · Vitodens 200-W B2HA

A boiler stand can be used for free-standing single-boiler installs. Anchor the stand securely to the floor; the manual recommends Hilti KB-TZ 3/8 x 4 concrete anchors or equivalent.

  1. Position the stand in the mechanical room.
  2. Anchor the stand to the floor with concrete expansion anchors (Hilti KB-TZ or equivalent).
  3. Confirm the stand is secure before mounting the boiler.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA installation instructions, p. 16. Written in our own words; check the manual for your exact model.

Freeze protection for unattended homes

Boiler · Vitocrossal 300 CA3B

The boiler is not designed to protect water pipes from freezing. A shutdown during cold weather can cause pipe bursts and mold.

  1. Shut off the building water supply, drain the pipes and add potable-water antifreeze to drain traps and toilet tanks, or
  2. have someone check the building often in cold weather and call a service agency if needed, or
  3. install a reliable remote temperature sensor that alerts someone to freezing conditions.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Freeze protection is not guaranteed

Boiler · Vitotronic 200, Vitotronic 300-K

The boiler is not designed to prevent water pipes from freezing. If the boiler stays off during cold weather, pipes can freeze and burst. The boiler may shut down when frozen pipe conditions occur.

  1. If the home will be empty in cold weather, shut off the water supply and drain the pipes.
  2. Add potable-water antifreeze to drain traps and toilet tanks where appropriate.
  3. Alternatively, have someone check the building often or install a remote temperature sensor that alerts someone to freezing conditions.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 7. Written in our own words; check the manual for your exact model.

Freeze protection when the system is drained

Boiler · Vitocrossal 200 CM2

If the system is exposed to freezing and not protected with antifreeze, the system including the boiler must be drained.

  1. Close the valve before the automatic feed valve, if installed.
  2. Leave all other valves, air vents and drain valves open while draining.

Applies to: Vitocrossal 200 CM2 186 to 620

Source: Vitocrossal 200 CM2 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Freeze protection when the system is not in use

Boiler · Vitocrossal 300 CA3B Dual Fuel

If the system is exposed to freezing temperatures and has no antifreeze, drain the system including the boiler.

  1. Close the valve before the automatic feed valve (if installed).
  2. Keep all other valves, air vents and drain valves open while draining.
  3. Drain the boiler and the system water.

Applies to: Heating system with Vitocrossal 300 boiler

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 42. Written in our own words; check the manual for your exact model.

Freeze-up protection

Boiler · Vitotronic 200-H

When outdoor temperature drops below +1 °C / 34 °F the control holds a supply temperature of 10 °C / 50 °F. The frost limit can be changed with coding A3.

Applies to: Heating circuit control

Source: Vitotronic 200-H HK1M installation and service instructions, p. 32. Written in our own words; check the manual for your exact model.

Freezing protection when the home is left unattended

Boiler · Vitocrossal 200 CM2

The boiler is not designed to protect water pipes from freezing and may shut down in cold weather.

  1. Shut off the water supply, drain the water pipes and add potable-water antifreeze to drain traps and toilet tanks, opening faucets where appropriate.
  2. Or have someone check the building often in cold weather.
  3. Or install a reliable remote temperature sensor that alerts someone to freezing conditions.

Applies to: All CM2 models

Source: Vitocrossal 200 CM2 operating instructions, p. 5. Written in our own words; check the manual for your exact model.

Fresh air and contaminated combustion air

Boiler · Vitodens 200-W B2HA

The boiler needs adequate combustion and ventilation air. Do not operate it where combustion air is contaminated by dust, lint or chemicals, such as construction sites, garages, laundries or near pools.

  1. Confirm the boiler room has adequate combustion and ventilation air.
  2. Check the boiler room for chemicals and dust before start-up.
  3. Have the boiler inspected and serviced at least once a year.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 2. Written in our own words; check the manual for your exact model.

Front cover and connections

Boiler · Vitodens 200-W B2HB

Operate the boiler only with the front cover in place. Use approved sealant or PTFE tape on field fittings.

  1. Never run the boiler with the front cover off.
  2. Use approved pipe sealant or teflon tape on the installation fittings.
  3. Make the heating water and gas connections in the field, and the power supply per the electrical connections section.
  4. Keep the maximum ambient temperature at or below 104°F (40°C) when making connections.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 2, p. 11, p. 12. Written in our own words; check the manual for your exact model.

Front cover and service access

Boiler · Vitodens 222-F

There are no user-serviceable parts on the boiler, burner or control. The boiler must never run with the front cover removed.

  1. Keep the front cover in place during operation.
  2. Leave service to a licensed professional heating contractor.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB service instructions, p. 2 and p. 6. Written in our own words; check the manual for your exact model.

Front cover must stay on during operation

Boiler · Vitodens 200-W B2HB

Running the boiler without the front cover in place is a hazard.

  1. Keep the front cover in place whenever the boiler is operating.
  2. Reinstall the front enclosure panel after service.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 2. Written in our own words; check the manual for your exact model.

Front panel controls and indicators

Boiler · Vitotronic 300 GW2

Front panel items used during start-up: override switch, heating circuit selection, display window, normal room temperature, heating programs, adjustable high limit, fixed high limit reset button, control on/off switch, fuses, TÜV TEST button, energy saving mode, party mode, programming unit cover, green operating status indicator and red fault indicator.

  1. Use the heating circuit selection button before making any setting for that circuit.
  2. Watch the green operating status indicator for normal operation and the red fault indicator for a fault.

Applies to: Vitotronic 300 GW2

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 64. Written in our own words; check the manual for your exact model.

Front panel indicators and controls

Boiler · Vitodens 200-W

The front panel has a red fault indicator, a green ON indicator, a reset button, the ON/OFF switch and a pressure gauge.

  1. Red fault indicator: lit when a fault is active.
  2. Green ON indicator: lit when the boiler is switched on and ready.
  3. Reset button: use to reset the boiler after a fault.
  4. ON/OFF switch: behind the black control cover, slide the cover out to reach it.
  5. Pressure gauge: read the heating system pressure here.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 32. Written in our own words; check the manual for your exact model.

Front panel refit

Boiler · Vitodens 100-W, B1HE, B1KE

The front panel is refitted by following the closing and panel instructions on page 30.

  1. See page 30 to refit the front panel.

Applies to: Vitodens 100-W

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 58. Written in our own words; check the manual for your exact model.

Front panel ribbon cable routing

Boiler · Vitotronic 300-K

When refitting the front part of the control, the ribbon cable must pass through the cable retaining tab so it does not pull on the connector.

  1. Route the ribbon cable through the retainer tab.
  2. Fit the front part of the control unit.
  3. Open the control only as described in the manual when access is needed.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

Front-panel and diagnostic indicators

Boiler · Vitotronic 100

The control has an integrated diagnostic system with power, burner call and fault indicators, front panel AHL and FHL lights, and a flash-based sensor diagnostic LED on the KW10B. The manual does not list the flash patterns on these pages.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B technical data manual, p. 3. Written in our own words; check the manual for your exact model.

Frost protection and prolonged shutdown

Boiler · Vitocrossal 300 CA3B Dual Fuel

Standby mode keeps frost protection active for the boiler and DHW tank. Circulation pumps may seize if left unpowered for long periods, so reset date and time after a prolonged shutdown.

  1. For each heating circuit, select the Standby mode operating program to keep frost protection active.
  2. If outdoor temperatures below 37°F (3°C) are expected, take frost protection measures for the heating system.
  3. After a prolonged shutdown, reset the date and time (see page 30).

Applies to: Vitotronic 300 GW6C

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 19. Written in our own words; check the manual for your exact model.

Frost protection for the supply temperature

Boiler · Vitotronic 300

Below +1°C / 34°F outdoors, the control holds the supply temperature at 15 to 22°C / 59 to 72°F (two-point control). The outdoor threshold can be changed via coding address A3.

  1. Check the outdoor sensor and frost threshold setting A3 if the supply is not held in the 15 to 22°C range.

Applies to: Heating circuits

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 88. Written in our own words; check the manual for your exact model.

Frost protection is lost when the control is powered off

Boiler · Vitotronic 200-H

Turning the control off with the ON/OFF switch or isolating power removes frost protection for the system. Settings are kept.

  1. Before switching off for a long period, check whether the system must stay frost protected.

Applies to: Vitotronic 200-H HK1M

Source: Vitotronic 200-H operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Frozen pipe protection

Boiler · Vitodens 200-W, Vitocrossal 300 CU3A

The boiler is not designed to protect water pipes from freezing and may shut down in cold weather. If the home is left unattended in freezing weather, the water supply should be shut off and pipes drained, or a remote temperature sensor installed.

  1. If the home will be unoccupied in freezing weather, shut off the water supply and drain pipes.
  2. Add antifreeze to drain traps and toilet tanks where appropriate.
  3. Or install a remote temperature sensor that alerts someone to freezing conditions.

Applies to: Vitodens 200-W and Vitocrossal 300 CU3A

Source: Vitotronic 200 operating instructions 5838 962-03, p. 6. Written in our own words; check the manual for your exact model.

Frozen pipe risk during extended shutdown

Boiler · Vitocrossal 300 CU3A

The boiler is not designed to stop water pipes from freezing. If the building will be left unattended in cold weather, the water supply and pipes must be protected, or someone must check the building.

  1. Shut off the building water supply and drain the water pipes, adding potable water antifreeze to drain traps and toilet tanks.
  2. Or have someone check the building often during cold weather.
  3. Or install a reliable remote temperature sensor that alerts someone to freezing conditions.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Frozen pipe risk when boiler is off

Boiler · Vitotronic 300-K

The boiler is not designed to prevent water pipes from freezing. If it stays off in cold weather, pipes can freeze and burst.

  1. If the building will be unattended in cold weather, shut off the water supply and drain the pipes, adding potable-water antifreeze to drain traps and toilet tanks.
  2. Or have someone check the building often, or install a remote temperature sensor that alerts on freezing conditions.

Applies to: Vitotronic 300-K MW2C boiler system

Source: Vitotronic 300-K MW2C operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Fuel conversion from natural gas to LPG

Boiler · Vitocrossal 200 CI2

Conversion is done with the kit. Follow the installation instructions supplied with the conversion kit.

  1. Follow the conversion kit installation instructions.
  2. Update the fuel labelling from NG to LPG.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 service instructions, p. 16. Written in our own words; check the manual for your exact model.

Fuel type

Boiler · Vitodens 200-W B2HA

Models B2HA 80 to 100, 285 to 352 are set up for natural gas. Conversion to liquid propane is covered in the service instructions.

  1. Use the Service Instructions for any conversion to liquid propane.

Applies to: All B2HA models

Source: Vitodens 200-W B2HA installation manual, p. 8. Written in our own words; check the manual for your exact model.

Fuel type and conversion

Boiler · Vitodens 200-W B2HB

Models B2HB 19, 26, 35, 68, 94 and 125 are supplied for natural gas. Conversion to liquid propane gas is covered in the service instructions. The boiler is factory tested and calibrated, so gas valve adjustment is normally not needed at field start-up.

  1. Confirm the boiler is set up for natural gas before commissioning.
  2. For LPG, follow the conversion procedure in the service instructions.

Applies to: All B2HB models

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Fuel type and factory calibration

Boiler · Vitodens 200-W B2HB

Models are for natural gas. Conversion to liquid propane needs the service instructions. The boiler is factory tested and calibrated, so gas valve adjustments are normally not needed at field start-up. Rated input is 12 to 125 MBH (3.5 to 37 kW).

  1. Confirm the fuel is natural gas before starting.
  2. For LPG, follow the conversion steps in the Service Instructions.
  3. Do not adjust the gas valve at start-up unless the situation requires it.

Applies to: Vitodens 200-W B2HB, all models

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.

Fuel type and LPG conversion

Boiler · Vitocrossal 300 CU3A

The boiler ships set for natural gas. Converting to liquid propane needs no conversion kit, but the Service Instructions must be followed.

  1. Confirm the boiler is set for natural gas as shipped.
  2. For conversion to liquid propane gas, refer to the Service Instructions.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Fuel valve and debris precautions

Boiler · Vitorond 100

Protect the boiler during idle periods and during service.

  1. Keep the manual fuel supply valve shut off if the burner is idle for an extended period.
  2. Never burn garbage or paper in the unit, and keep combustible material away from it.
  3. Do not leave tools inside the combustion chamber.
  4. Do not tamper with the unit or controls.

Applies to: Vitorond 100 VR1

Source: Vitorond 100, VR1 installation and service instructions, p. 45, p. 46, p. 47. Written in our own words; check the manual for your exact model.

Gas control knob handling

Boiler · Vitocrossal 300 CU3A

Only use the hand to push in or turn the gas control knob. Never use tools. If the knob will not move by hand, do not force or repair it; call a qualified service technician.

  1. Operate the gas control knob by hand only.
  2. If the knob will not move, call a qualified service technician.

Applies to: Vitocrossal 300 CU3A gas control

Source: Vitocrossal 300 CU3A installation instructions, p. 59. Written in our own words; check the manual for your exact model.

Gas fuel and conversion

Boiler · Vitodens 200-W B2HA

Models B2HA 45 and 60 are for natural gas only. Conversion to liquid propane is covered in the service instructions, not in the installation instructions.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.

Gas odor and water-damaged appliance

Boiler · Vitodens 200-W

Safety actions printed in the lighting instructions for gas smell and flood damage.

  1. Do not light any appliance if gas is smelled.
  2. Do not touch any electric switch or use a phone in the building.
  3. Leave the building and call the gas supplier from a safe location, following their instructions. If the supplier cannot be reached, call the fire department.
  4. Never use tools on the gas control knob. Use only hand force.
  5. Do not use the appliance if any part has been under water. Have a qualified service technician inspect it and replace the control system parts and gas control that were submerged.

Applies to: Vitodens 200-W B2HA

Source: Vitodens 200-W B2HA service instructions, p. 106. Written in our own words; check the manual for your exact model.

Gas odour: what to do

Boiler · Vitodens 200-W B2HA

Do not light anything, do not touch electric switches, and do not use a phone in the building. Call the gas supplier from outside the building. If the supplier cannot be reached, call the fire department. Do not use the appliance if any part has been under water; a qualified technician must inspect it and replace the control system and gas control parts that were wetted.

  1. Do not light any appliance or touch electric switches.
  2. Leave the building and call the gas supplier from a neighbour's phone.
  3. If the supplier cannot be reached, call the fire department.
  4. If any part was under water, have a qualified technician replace the affected control and gas control parts before use.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 98. Written in our own words; check the manual for your exact model.

Gas shut-off during overheating or gas valve failure

Boiler · Vitotronic 300-K

If the boiler overheats or the gas supply does not shut off, the pump power must stay on. Shut off the gas at a point outside the appliance.

  1. Do not disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location external to the appliance.

Applies to: Multi boiler system with Vitotronic 300-K cascade control

Source: Vitotronic 300-K MW2C operating instructions, p. 5. Written in our own words; check the manual for your exact model.

Gas smell or flue gas smell response

Boiler · Vitocrossal 300 CA3B Dual Fuel

If gas or flue gas is smelled, the room is a danger zone. Act quickly and safely.

  1. Do not smoke, create sparks or flames, or operate light or electrical switches.
  2. Close the gas shut-off valve.
  3. Open windows and doors.
  4. Move everyone out of the danger zone.
  5. From outside the building, notify the gas or electricity utility.
  6. From a safe place outside the building, shut off the electricity to the building.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 9. Written in our own words; check the manual for your exact model.

Gas type and conversion

Boiler · Vitodens 100-W WB1B

The boiler is factory set for natural gas. A propane conversion kit is included with each boiler. Boilers are factory tested and calibrated, so gas valve adjustment is usually not needed at field start-up.

  1. Confirm the boiler is set for the gas type supplied.
  2. Use the included propane conversion kit only if the gas supply is propane.

Applies to: WB1B-26, WB1B-35

Source: Vitodens 100-W WB1B installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Gas type and high altitude

Boiler · Vitocrossal 300 CU3A

Lambda Pro combustion management adjusts automatically to gas type and quality, so no fuel conversion kit is required. High altitude operation up to 10,000 ft (3,000 m) uses a simple electronic adjustment.

  1. Check the gas supply pressure is within 4 to 14 in. w.c. for natural gas and 10 to 14 in. w.c. for LP.
  2. At 10,000 ft, allow for the 18 percent input de-rate.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 Technical Data Manual, p. 2, p. 4. Written in our own words; check the manual for your exact model.

Gas valve leakage code F E1 / F E2 - replace valve

Boiler · Vitocrossal 300 CA3B Dual Fuel

Both leakage codes call for replacing the combination gas valve.

  1. Check for gas leaks at the gauge connections before and after valve work.
  2. Replace the combination gas valve when F E1 or F E2 appears.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 74. Written in our own words; check the manual for your exact model.

Gas valve work and leak detection

Boiler · Vitocrossal 300 CA3B

Check gas fittings for tightness after any gas valve work. Leak detection spray can cause faulty operation.

  1. Check all gas fittings for tightness after reassembly.
  2. Keep leak detection spray away from electrical contacts.

Applies to: CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 60. Written in our own words; check the manual for your exact model.

Gateway board LEDs and service button

Boiler · Versatronik 585

The gateway board has a power LED, a service LED and a service button. Use the LEDs to confirm power and service state.

  1. Check the power LED for supply voltage.
  2. Check the service LED when troubleshooting the gateway.
  3. Use the service button as described in the full manual.

Applies to: Versatronik 585 VI/BACIP gateway

Source: Versatronik 585 BACnetIP manual, p. 24. Written in our own words; check the manual for your exact model.

Gateway connection points (24VAC DIN rail unit)

Boiler · Versatronik 501, Versatronik 501D

The DIN rail unit has four connection points: the RJ45 control connection, the paralleled BUS connection, the LON terminals A and B, and the 24VAC power input.

  1. Connect the RJ45 cable to the control.
  2. Use the paralleled BUS connection where more than one gateway is used.
  3. Wire the LON network to terminals A and B.
  4. Connect 24VAC power.

Applies to: Versatronik 501D DIN rail unit

Source: Versatronik 501 & 501D LON gateway manual, p. 6. Written in our own words; check the manual for your exact model.

Gateway purpose

Boiler · Versatronik 511 / 511D

The gateway translates between the boiler control and a LON-capable DDC/BMS system. It can sit inside a control panel or stand alone.

Applies to: Versatronik 511 and 511D

Source: Versatronik 511 & 511D LON Type B manual, p. 3. Written in our own words; check the manual for your exact model.

Gateway status light meaning

Boiler · Versatronik 515

The gateway status light shows communication status.

  1. Light flashing: communication is active.
  2. Light solid or off: no communication. Check the wiring and the boiler control connection.

Applies to: Versatronik 515 NR2/BACIP and 515D NR2/BACIP gateways

Source: Versatronik 515 BACnet IP Type B manual, p. 16. Written in our own words; check the manual for your exact model.

Getting the short help guide

Boiler · Vitotrol 300A

The help key shows a short guide on the controls and heating circuit selection.

  1. From the standard display, press the ? key.
  2. From anywhere in the menu, press the back key until the standard display shows, then press ?.

Applies to: Vitotrol 300A

Source: Vitotrol 300A operating instructions, p. 5. Written in our own words; check the manual for your exact model.

Hand over operating and service documents to the owner

Boiler · Vitocrossal 200 CI2

The system manufacturer must give the operator the operating instructions and train them on the system. Include any accessories such as remote controls. Hand over the operator section and keep the heating contractor section. Installation instructions are not required after installation.

  1. Complete the customer information and separate the operator section from the heating contractor section.
  2. Hand over the operator section for safekeeping.
  3. Keep the heating contractor section.
  4. File all parts lists, operating and service instructions in folders and hand them to the operator.
  5. Explain the required maintenance to the operator.

Applies to: Vitocrossal 200 CI2 boilers

Source: Vitocrossal 200 CI2 Service Instructions, p. 36. Written in our own words; check the manual for your exact model.

Handle fiberglass wool and ceramic fiber safely

Boiler · Vitorond 200 VD2

Airborne fibers from fiberglass wool and ceramic fiber parts are a possible cancer hazard and cause irritation. Use proper protection when handling these materials. If eyes are irritated, flush with lukewarm water for at least 15 minutes.

  1. Avoid breathing dust and avoid contact with skin and eyes.
  2. Wear a NIOSH approved dust/mist respirator.
  3. Wear long-sleeved loose clothing, gloves and eye protection.
  4. Wash work clothes separately and rinse the washer well.
  5. Move the person to a dust-free area if breathing irritation develops.
  6. Wash skin with soap and water if irritated. Do not rub or scratch.

Applies to: Fiberglass wool and ceramic fiber parts such as the combustion chamber door insulation

Source: Vitorond 200 VD2 Service Instructions, p. 3. Written in our own words; check the manual for your exact model.

Handle the board as static sensitive

Boiler · Versatronik 515, Versatronik 515D

Static can damage components inside the control. Take steps to prevent static build-up before working inside the unit.

  1. Use static precautions before handling or working inside the control.

Applies to: Versatronik 515 and 515D gateways

Source: Versatronik 515 BACnet IP Type B manual, p. 2. Written in our own words; check the manual for your exact model.

Handle the control board with ESD precautions

Boiler · Versatronik 505 & 505D

Static-sensitive components can be damaged by poor handling or work inside the control. Take all reasonable steps to prevent static build-up.

  1. Use static-control precautions before working inside the control.

Applies to: Versatronik 505 and 505D

Source: Versatronik 505 & 505D BACnet IP gateway manual, p. 2. Written in our own words; check the manual for your exact model.

Handle the control boards with static precautions

Boiler · Versatronik 501, Versatronik 501D

Static can damage the components inside the control. Take all reasonable steps to prevent static build-up during handling or work.

  1. Use static precautions before handling or working inside the control.

Applies to: Versatronik 501 and 501D gateways

Source: Versatronik 501 & 501D LON gateway manual, p. 2. Written in our own words; check the manual for your exact model.

Handle the electronics with static precautions

Boiler · Versatronik 581 / 581D

Static can damage the components inside the control.

  1. Take measures to remove static build-up before touching the internal circuitry.
  2. Handle components carefully to avoid damage.

Applies to: Versatronik 581 and 581D

Source: Versatronik 581 LON gateway manual, p. 2. Written in our own words; check the manual for your exact model.

Handling fiberglass and ceramic fiber insulation

Boiler · Vitorond 100

Insulation and combustion chamber materials can be a cancer hazard when inhaled.

  1. Read the fiberglass and ceramic fiber warning on p. 3 before handling insulation.
  2. Use a NIOSH approved dust/mist respirator and long-sleeved clothing, gloves and eye protection.
  3. Avoid sawing, blowing, tear-out or spraying that creates airborne fibers without added protection.
  4. Wash work clothes separately and rinse the washer thoroughly.

Applies to: Insulation and combustion chamber door refractory

Source: Vitorond 100, VR1 installation and service instructions, p. 45, p. 46. Written in our own words; check the manual for your exact model.

Handling fiberglass and ceramic fiber materials

Boiler · Vitocrossal 300 CU3A

Breathing fiberglass wool or ceramic fiber dust can cause cancer risk and irritation to the lungs, skin and eyes.

  1. Wear a NIOSH approved dust/mist respirator, long sleeves, gloves and eye protection.
  2. Wash work clothes separately and rinse the washer well.
  3. Flush eyes with water if dust gets in them; wash skin with soap and warm water.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Handling fiberglass wool and ceramic fiber insulation

Boiler · Vitorond 200 VD2A

Fiberglass wool and ceramic fiber materials in the boiler (for example the combustion chamber door insulation) can cause respiratory, skin and eye irritation and are a possible cancer hazard when airborne. Use the protection below when handling or cutting them.

  1. Wear a NIOSH-approved dust/mist respirator.
  2. Wear long-sleeved loose clothing, gloves and eye protection.
  3. Avoid breathing dust and avoid contact with skin and eyes.
  4. Wash work clothes separately and rinse the washer thoroughly.
  5. Expect airborne fibers from sawing, blowing, tear-out or spraying; use extra protection.
  6. Eyes: flush with lukewarm water for at least 15 minutes, holding the eyelids open.
  7. Skin: remove soiled clothing, wash with soap and water, and do not rub or scratch.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Service Instructions, p. 3. Written in our own words; check the manual for your exact model.

Handling fiberglass wool and ceramic fiber materials

Boiler · Vitocrossal 300 CA3B

Fiberglass and ceramic fiber parts can cause cancer, and skin, eye and breathing irritation. Protect yourself when you work near them.

  1. Wear a NIOSH approved dust/mist respirator.
  2. Wear long-sleeved loose clothing, gloves and eye protection.
  3. Avoid breathing dust and avoid contact with skin and eyes.
  4. Wash work clothes separately from other clothing and rinse the washer well.
  5. Expect extra protection needs when sawing, blowing, tearing out or spraying.
  6. If eyes are irritated, flush with lukewarm water for at least 15 minutes. Do not rub them.
  7. If skin is irritated, remove soiled clothing and wash with soap and cold water.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 3. Written in our own words; check the manual for your exact model.

Handover to the owner

Boiler · Vitocrossal 300 CA3B Dual Fuel

The installer must review the equipment, safety requirements and shutdown procedure with the operator or owner. Annual professional service is required before each heating season.

  1. Review the equipment, safety precautions and shutdown procedure with the owner.
  2. Explain that annual professional service is needed before the heating season starts.
  3. Leave all literature at the site and tell the owner where it is kept.

Applies to: Final commissioning and handover

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 2, 6. Written in our own words; check the manual for your exact model.

Handover to the system owner

Boiler · Vitodens 222-F

Before leaving, the installer must show the system operator how the equipment works, how to shut it down in an emergency, and that annual professional service is needed before each heating season.

  1. Explain the system operation sequence to the owner.
  2. Demonstrate emergency shut-down and state what to do and what not to do.
  3. Tell the owner annual professional service is required before the heating season starts.
  4. Leave all literature near the boiler and complete the Maintenance Record.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB installation instructions, p. 6. Written in our own words; check the manual for your exact model.

Heat DHW once outside the time program

Boiler · Vitocrossal 300 CA3B

Forces a one-time DHW heat cycle. The operating program must be set to Heating and DHW or DHW only for at least one heating circuit. Turn comfort mode on and then straight off so central heating does not run at standard room temperature.

  1. Confirm that Heating and DHW or DHW only is set for at least one heating circuit.
  2. Enable comfort mode for that circuit.
  3. Immediately disable comfort mode.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Heat DHW once without rooms time program

Boiler · Vitotronic 300-K, Vitotronic 200

Used when DHW is needed once but the rooms should stay unheated. Sets the DHW temperature to 50°F (10°C) and disables party mode afterwards.

  1. Make sure Heating and DHW or Only DHW is set for at least one heating circuit.
  2. Open the extended menu and select Heating.
  3. Select Heating program, then Heating and DHW.
  4. Go back until the menu for DHW is shown.
  5. Select DHW, then Set DHW temperature.
  6. Set it to 50°F (10°C).
  7. Afterwards, set Party mode to OFF to prevent central heating at standard room temperature.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 23, p. 24. Written in our own words; check the manual for your exact model.

Heat DHW once, outside the time program

Boiler · Vitotronic 300-K

Comfort mode must be turned on and then off again straight away. This heats the DHW once without starting central heating at standard room temperature. The operating program Heating and DHW or DHW only must be set for at least one heating circuit.

  1. Turn on Comfort mode (see manual p. 26).
  2. Turn Comfort mode off again straight away.

Applies to: DHW tank

Source: Vitotronic 300-K MW2C operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Heat slope adaptation (ON/OFF)

Boiler · Versatronik COMO OT

Automatic heat slope adjustment is active only with the outdoor sensor connected. It runs only below 8°C outdoor and with the room below 18°C. If the room does not reach the target within 4 hours, the adaptation is cancelled and the warning indicator flashes. It then repeats the next day.

  1. Connect the outdoor sensor to terminals 5 and 6.
  2. Turn the adaptation on.
  3. Allow the system to run through the adaptation.
  4. If the warning indicator flashes, let the next day's adaptation run.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 28. Written in our own words; check the manual for your exact model.

Heating circuit and display symbols

Boiler · Vitocrossal 300 CU3A

HC1, HC2 or HC3 appear in the header only when the system has two or three heating circuits; single-circuit systems show no HC name. Other symbols appear depending on system version and operating state.

  1. Select HC1, HC2 or HC3 in the standard menu to choose which circuit displays.
  2. Use ZC1, ZC2 or ZC3 to display a zone circuit selected in the standard menu.
  3. Symbols include frost protection, central heating standard or reduced temperature, party and economy mode, solar pump running, burner on, service message and fault message.

Applies to: Vitocrossal 300 CU3A with Vitotronic control

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 47-48. Written in our own words; check the manual for your exact model.

Heating circuit and mixer terms

Boiler · Vitotrol 300A

Short definitions of heating circuit terms used in this manual.

  1. Heating circuit: sealed loop between the boiler and the radiators, with water circulated by the heating circuit pump.
  2. Mixer: mixes boiler water with cooled return water so the flow temperature matches demand. The control unit adjusts the flow temperature through the mixer.

Applies to: Vitotrol 300A

Source: Vitotrol 300A Remote Control Operating Instructions, p. 27. Written in our own words; check the manual for your exact model.

Heating circuit extension (heating circuits 2 and 3) legend

Boiler · Vitotronic 200, Vitotronic 300-K

The accessory extension for heating circuits 2 and 3 uses supply temperature sensors, heating circuit pumps, mixing valve motors and relays K1 to K6.

Applies to: Heating circuit extension accessory

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 91. Written in our own words; check the manual for your exact model.

Heating circuit labelling

Boiler · Vitotronic 300-K

With one heating circuit without a mixing valve and one or two heating circuits with mixing valves, the non-mixed circuit is called 'Heating circuit 1'. Mixed circuits are 'Heating circuit 2' or 'Heating circuit 3'. If a custom name was entered, that name appears together with HC1, HC2 or HC3.

Applies to: Vitotronic 300-K heating circuits

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 36. Written in our own words; check the manual for your exact model.

Heating circuit names

Boiler · Vitocrossal 300 CU3A

Heating circuits default to Heating circuit 1, 2 and 3. Names are changed in the Operating Instructions.

  1. Refer to the Operating Instructions to enter names for heating circuits.

Applies to: Heating circuit naming

Source: Vitocrossal 300 CU3A service instructions, p. 16. Written in our own words; check the manual for your exact model.

Heating circuit pump

Boiler · Vitodens 200-W B2HA

The heating circuit pump circulates the heating water in the heating circuit.

Applies to: Vitodens 200-W B2HA

Source: Vitotronic 200 Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Heating circuit pump OFF setting can freeze pipes

Boiler · Vitotronic 300 GW6B

A pump switch-off threshold set below 34°F (1°C) can let pipes outside the heated envelope freeze. Consider standby periods such as holidays.

  1. Check the outdoor temperature threshold in coding a3 before leaving the system in standby.
  2. Do not set a3 below 1°C unless the piping is protected.

Applies to: Vitotronic 300 GW6B heating circuit pump

Source: Vitotronic 300 GW6B installation and service manual, p. 111. Written in our own words; check the manual for your exact model.

Heating circuit pump runs periodically in standby

Boiler · Vitotronic 200-H

In standby or when the control is off, the heating circuit pump starts for a short time every 24 hours to prevent pump seizure.

Applies to: Vitotronic 200-H HK1M

Source: Vitotronic 200-H operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Heating circuit selection on HK3S

Boiler · Vitotronic 200-H

On the HK3S the heating circuit selection control chooses which circuit is displayed. The basic display can show a first key 1 or 2 or 1, 2 or 3 depending on how many heating circuits are connected.

Applies to: Vitotronic 200-H HK3S

Source: Vitotronic 200-H operating instructions, p. 7-8. Written in our own words; check the manual for your exact model.

Heating circuit selection on multi-circuit systems

Boiler · Vitotronic 200-H

With two or three heating circuits, the circuit to adjust must be selected before any adjustment or scan. Single-circuit systems skip this step.

  1. Press the circuit key (1, 2 or 3) for the heating circuit to adjust.
  2. Confirm the program keys that light up for that circuit.
  3. Make adjustments or scan only after selecting the circuit.
  4. If no adjustment is made, the key lights go off after a short time.

Applies to: HK3S (two or three heating circuits)

Source: Vitotronic 200-H operating instructions, p. 9. Written in our own words; check the manual for your exact model.

Heating circuit settings can be made on the control or remote

Boiler · Vitotronic 200-H

All heating circuit settings can be made on the control unit or the built-in programming unit. If a remote control is fitted, it can be used for the settings as well, following the remote control instructions.

Applies to: Vitotronic 200-H HK1S and HK3S

Source: Vitotronic 200-H operating instructions, p. 4. Written in our own words; check the manual for your exact model.

Heating circuits M2 and M3 need an extension module

Boiler · Vitotronic 200-H

The HK1B control unit can run up to 3 heating circuits, but only with the mixing valve extension module fitted. Heating circuits M2 and M3 need the heating circuit extension module, which is an optional accessory.

Applies to: Vitotronic 200-H, type HK1B

Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 7. Written in our own words; check the manual for your exact model.

Heating curve and heating circuit terms

Boiler · Vitotronic 300-K, Vitotronic 100

Heating curves show the link between outside temperature, room temperature set value and supply temperature. The lower the outside temperature, the higher the boiler water or heating circuit supply temperature.

Applies to: Vitotronic 300-K MW1B / Vitotronic 100 GC1B

Source: Vitotronic 300-K MW1B / Vitotronic 100 GC1B operating instructions, p. 40. Written in our own words; check the manual for your exact model.

Heating operating modes

Boiler · Vitocrossal 200 CI2

The boiler supplies heat at the set supply temperature. The contractor sets one of four operating modes at commissioning: weather-compensated, constant, or room temperature-dependent operation. Comfort, standard and reduced temperature levels are chosen by time program. In room temperature-dependent operation a separate room sensor is required, and the output does not follow outside temperature. Weather-compensated operation can run several heating circuits, and remote units can adjust settings. Constant operation holds a fixed supply temperature regardless of outside temperature.

Applies to: Heating operating mode setup

Source: Vitocrossal 200 CI2 Operating Instructions, p. 42. Written in our own words; check the manual for your exact model.

Heating program changed by external control

Boiler · Vitotronic 200-H

Shows Ext. control when an external control has switched the heating program set on the control unit.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Heating program options

Boiler · Vitotrol 300A

The heating program sets whether the rooms are heated, whether DHW is made, or whether the system is shut down with frost protection.

  1. Heating and DHW: rooms are heated and DHW is provided (winter mode).
  2. Only DHW: DHW is provided, no central heating (summer mode).
  3. Standby mode: frost protection for the boiler and DHW tank is on; no central heating and no DHW heating.
  4. There is no program for central heating alone. For central heating only, use Heating and DHW and set the DHW temperature to 50 F (10 C) so the tank is only kept from freezing (see p. 23).

Applies to: Vitotrol 300A

Source: Vitotrol 300A Remote Control Operating Instructions, p. 27. Written in our own words; check the manual for your exact model.

Heating program: Heating vs Standby

Boiler · Vitodens 200-W B2HA

The heating program decides whether the boiler supplies heat to the Vitotronic 300-K MW2C or sits in standby with frost protection active. Two programs exist: Heating (boiler available for heat production) and Standby mode (frost protection only).

Applies to: Vitotronic 200 heating program setting

Source: Vitotronic 200 Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Heating programs and what they do

Boiler · Vitotronic 300-K, Vitotronic 200

The heating program decides whether the system heats rooms and DHW, DHW only, or stays in standby with frost protection. Winter mode is 'Heating and DHW'. Summer mode is 'Only DHW', where the boiler still makes DHW but no central heating. 'Standby mode' turns off central heating and DHW but keeps frost protection active for the boiler and DHW tank. There is no heating-only program. For heating without DHW demand, select 'Heating and DHW' and set the DHW temperature to 10 °C (50 °F). DHW is then not heated needlessly, and the DHW tank stays frost protected.

  1. Select 'Heating and DHW' for winter operation with rooms and DHW.
  2. Select 'Only DHW' for summer operation.
  3. Select 'Standby mode' to shut down heating and DHW while keeping frost protection.
  4. For central heating only, select 'Heating and DHW' and set the DHW temperature to 10 °C (50 °F).

Applies to: Vitotronic 200 and 300-K heating program

Source: Vitotronic 200 and 300-K Operating Instructions, p. 43. Written in our own words; check the manual for your exact model.

Heating water quality requirements

Boiler · Vitocrossal 300 CU3A

Deposits and corrosion increase with poor fill water. Water harder than the limit must be softened.

  1. Flush the whole heating system before filling.
  2. Use potable quality water only.
  3. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
  4. Add heating system inhibitors or antifreeze only if they are suitable for heating systems and added manually.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

Heating/cooling changeover valves

Boiler · Vitorond 100 VR1

In a combined heating and cooling application, valves v1 and v2 switch the boiler loop between seasons.

  1. Cooling season: close v1 and open v2.
  2. Heating season: close v2 and open v1.
  3. Label the valves v1 and v2.

Applies to: Heating/cooling application with hydrostat

Source: Vitorond 100, VR1 Technical Data, p. 12. Written in our own words; check the manual for your exact model.

High altitude de-ration

Boiler · Vitodens 222-F

At 10,000 ft (3050 m) altitude, the input of all B2TB 19, 35, 68 and 125 models is de-rated by 21%.

  1. Account for the 21% input de-ration when checking input at high altitude.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F B2TB service instructions, p. 108. Written in our own words; check the manual for your exact model.

High altitude input de-rate

Boiler · Vitocrossal 300 CU3A

At 10,000 ft. altitude the input of the Vitocrossal 300 CU3A is reduced by 18%.

  1. Account for the 18% input reduction when checking input at high altitude.

Applies to: Vitocrossal 300 CU3A installed at high altitude

Source: Vitocrossal 300 CU3A application guide, p. 13. Written in our own words; check the manual for your exact model.

High altitude input de-ration

Boiler · Vitocrossal 300 CU3A

At 10,000 ft altitude the input for the Vitocrossal 300 CU3A is de-rated by 18 percent.

  1. Account for the 18 percent input de-ration when installing at 10,000 ft altitude.

Applies to: Vitocrossal 300 CU3A at high altitude

Source: Vitocrossal 300 CU3A Installation Instructions, p. 54. Written in our own words; check the manual for your exact model.

High limit setting can only be changed by coding card

Boiler · Vitocrossal 300 CA3B

The fixed high limit cut-out is preset at 210°F (99°C) and can only be changed by changing the coding card.

  1. Do not change the fixed high limit by other means.
  2. Refer to the control section of the installation instructions for the coding card procedure.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 10. Written in our own words; check the manual for your exact model.

Holiday function use

Boiler · Versatronik 200

Holiday mode stops heating for the set period. Stop it early with the program switch.

  1. Enter the first day of the holiday as the holiday start date, not the day of travel. Heating stops from this day.
  2. Enter the last day without heating as the holiday end date, not the day of return. The house should be warm and have hot water when you arrive.
  3. To end the holiday early, press the program switch.

Applies to: Heating and hot water holiday function

Source: Versatronik 200 installation and operating manual, p. 134. Written in our own words; check the manual for your exact model.

Hot water operation without burner (BoB)

Boiler · Versatronik 200

BoB is used for operation with solar energy, for example. The burner is only enabled when storage values drop below the set tolerance limit.

  1. Select BoB for hot water generation where solar or another source supplies the heat.
  2. Check that the tolerance limit is set so the burner starts only when needed.

Applies to: Versatronik 200 hot water generation

Source: Versatronik 200 Installation and Operating Manual, p. 154. Written in our own words; check the manual for your exact model.

Hot water pipe clearance to combustibles

Boiler · Vitodens 200-W

Keep at least 2 in. (51 mm) circumferential clearance from non-insulated hot water pipes to combustible construction. With adequately insulated pipe, the clearance can drop to 0 in. where local gas codes allow.

  1. Keep 2 in. (51 mm) around non-insulated hot water pipes from combustible construction.
  2. With suitable pipe insulation, 0 in. is allowed only if local gas codes permit.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 32. Written in our own words; check the manual for your exact model.

How heating curve adjustments change supply temperature

Boiler · Vitotronic 300-K

Changing the slope alters the gradient of the curve. Changing the shift moves the whole curve up or down in parallel. Changing the standard room temperature setpoint offsets the curve along the room temperature axis. The lower the outdoor temperature, the higher the boiler water or supply temperature.

Applies to: Heating curve settings

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 34. Written in our own words; check the manual for your exact model.

How the heating curve works

Boiler · Vitodens 200-W B2HA

The lower the outdoor temperature, the higher the boiler water or supply temperature. Room temperature follows boiler water temperature. A different room setpoint shifts the curve parallel. The boiler water is raised above the required supply temperature by a set differential (factory 14.4°F / 8 K, coding address 9F). The supply temperature cannot exceed the boiler water temperature. Heating curve slope suits system type: low temperature (radiant floor) 0.2 to 0.7; medium temperature (cast iron, panel radiant floor) 0.7 to 1.2; high temperature (fin tube, fan coils) 1.2 to 1.5.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 39. Written in our own words; check the manual for your exact model.

Hydraulic example scheme reference

Boiler · Vitocrossal 300 CU3A

Page 32 gives hydraulic scheme ID 4605300_1006_01 as a basic example only. It has no shut-off valves or safety equipment and does not replace local engineering.

  1. Add shut-off valves and safety equipment as required by local engineering.

Applies to: Vitocrossal 300 CU3A 26 to 199, example layout 1

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

Hydronic and electrical component index

Boiler · Vitodens 222-F

Components shown in the application drawings and the component index.

  1. Hydronic: ball valve, circulator with isolation flanges, low loss header, thermostatic mixing valve, radiant infloor manifold, motorized mixing valve, flow check valve, air eliminator, expansion tank, zone valve, hydronic air handler, plate and frame heat exchanger, purge assembly.
  2. Electrical: aquastat, secondary low water cut-off, outdoor temperature sensor, thermostat, temperature sensor, Vitotrol multi-zone control, 24V zone valve, 120 Volt circulator, 3-way mixing valve with actuator motor.

Applies to: Vitodens 222-F system piping and wiring

Source: Vitodens 222-F application guide, p. 9. Written in our own words; check the manual for your exact model.

Hydronic flow and pipe head estimate

Boiler · Vitocrossal 300 CU3A

Flow and heat rate formulas and a quick pipe resistance estimate for sizing a circuit pump.

  1. Flow (GPM) = BTUH / (500 x ΔT).
  2. Heat rate (BTUH) = GPM x 500 x ΔT.
  3. For pipe resistance, measure the longest run of pipe.
  4. Add 50% for fittings.
  5. Multiply by 0.04 to get a rough feet of head the pump must overcome for that circuit.

Applies to: Circulator and pipe sizing

Source: vitocrossal_300-cu3a_application_guide.pdf, p. 62. Written in our own words; check the manual for your exact model.

Hydrostat thermal targeting

Boiler · Vitorond 100 VR1

The Fuel Smart Hydrostat watches thermostat activity. It raises the boiler target temperature in cold weather and lowers it in mild weather to save fuel.

Applies to: VR1 22 to 33, 91 to 140

Source: Vitorond 100 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.

Hydrostat thermal targeting behavior

Boiler · Vitorond 100

Thermal Targeting analyzes thermostat activity and raises or lowers the boiler target temperature with heat demand. Colder outdoor conditions raise the target; milder conditions lower it to save fuel.

Applies to: Vitorond 100 with Fuel Smart HydroStat

Source: Viessmann Vitorond 100 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.

If you smell gas

Boiler · Vitocrossal 300 CU3A

Do not light any appliance and do not touch electrical switches or use a phone in the building. Call the gas supplier from a neighbour's phone and follow their instructions. If the gas supplier cannot be reached, call the fire department.

  1. Do not light any appliance.
  2. Do not touch electrical switches or use a phone in the building.
  3. Call the gas supplier from outside the building, from a neighbour's phone.
  4. If the gas supplier cannot be reached, call the fire department.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 1. Written in our own words; check the manual for your exact model.

Indirect DHW tank service interval

Boiler · Vitocrossal 300 CA3B

Indirect-fired domestic hot water storage tanks need regular service.

  1. Service indirect-fired DHW storage tanks within two years of installation at the latest.
  2. Continue regular service after that.

Applies to: Vitocrossal 300 CA3B with indirect DHW tank

Source: Vitocrossal 300 CA3B operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Indirect DHW tank: flow check valves

Boiler · Vitocrossal 200 CI2

When the boiler heats an indirect DHW tank, heating loops without a mixing valve need flow check valves on the pump discharge side to stop reverse flow.

  1. Install flow check valves on the discharge side of the pumps in loops without a mixing valve.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 40. Written in our own words; check the manual for your exact model.

Information scan list (lead control unit and boiler sections)

Boiler · Vitocrossal 300 CA3B

Scan list under Information. Some items only appear depending on equipment level. Items marked with an arrow can be opened for more detail.

  1. General: outdoor temp, boiler temperature, flue gas temperature, burner starts and hours, boiler sequence, sensors 9, 17A, 17B, outputs 20, 29, 52, feed pump, central fault message, participant no., time and date.
  2. Burner control: burner hours run, burner starts, max operational output, gas type, altitude, max boiler temperature, integral threshold controller, runtime optimization.
  3. Heating circuits 1 to 3: heating program, operating status, time program, room temperature targets, slope, shift, pump and mixing valve status, supply temperature, holiday program.
  4. Solar (if fitted): collector temp, solar energy, solar circuit pump status and hours, sensor 7 and 10, output 22.
  5. DHW: DHW time program, circulation time program, DHW temperature (top and bottom with two sensors), circulation pump, tank primary pump.

Applies to: Vitocrossal 300 CA3B, lead control unit and boiler section 2 or 3

Source: Vitocrossal 300 CA3B operating instructions, p. 34-36. Written in our own words; check the manual for your exact model.

Information shown per fault

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Each fault shows the date and time, the fault code, a description, and the subscriber number of the affected component.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 69. Written in our own words; check the manual for your exact model.

Initial checks before troubleshooting

Boiler · Vitotronic 100

Confirm the basics before working through the symptom guides.

  1. Confirm all controls operate properly (thermostats, low water cut-off, etc.).
  2. Confirm all wire connections are tight and secure.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation, start-up and service instructions, p. 27. Written in our own words; check the manual for your exact model.

Inlet damper must be fully open

Boiler · Vitocrossal 200 CM2

If the burner inlet damper does not open fully, it can cause malfunctions or show that the servomotor is set up wrong.

  1. After any damper, servomotor or linkage work, confirm the damper vents are fully open.
  2. Adjust the linkage if the vents are not fully open.

Applies to: CM2 246 and 311

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, pp. 37-38. Written in our own words; check the manual for your exact model.

Install carbon monoxide detectors

Boiler · Vitorond 200 VD2

Follow local regulations for installing carbon monoxide detectors in the building.

  1. Check local code for CO detector requirements before installation.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200 VD2 Service Instructions, p. 2. Written in our own words; check the manual for your exact model.

Installation and service qualifications

Boiler · Switching Module-V

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor qualified on hot water boilers. There are no user serviceable parts on the boiler, burner or control. Refer to the installation literature of other components.

  1. Make sure main power to the equipment, heating system and external controls is off.
  2. Close the main oil or gas supply valve.
  3. Take precautions so power cannot be switched on accidentally during service work.

Applies to: Switching Module-V

Source: Switching Module-V installation instructions, p. 1. Written in our own words; check the manual for your exact model.

Installation area ambient limits

Boiler · Vitotronic 300-K

Ambient temperature and air quality limits for the boiler room. Outside these limits, safe operation and the heating system are at risk.

  1. Keep ambient temperature above 32°F (0°C) and below 104°F (40°C).
  2. Keep halogenated hydrocarbons (paint solvents, cleaning fluids) and heavy dust out of the combustion and room air.
  3. Avoid continuously high humidity.
  4. Never close existing ventilation openings.
  5. Use only components tested with the heating system and install or replace them through a qualified heating contractor.

Applies to: Viessmann boiler installation areas

Source: Vitotronic 300-K MW2C operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Installation area and combustion air

Boiler · Vitotronic 200, Vitotronic 300-K

Ambient temperature must stay above 32 °F (0 °C) and below 104 °F (40 °C). Keep the air free of halogenated hydrocarbons and excessive dust. Combustion and boiler room air must be free of corrosive contaminants. Never close existing ventilation openings.

  1. Confirm the room temperature is between 32 °F (0 °C) and 104 °F (40 °C).
  2. Check for chemical sources such as paint solvents, cleaning fluids, chlorine products, refrigerant leaks or dry cleaning areas near the boiler.
  3. Check that ventilation openings are open and unobstructed.
  4. Use only replacement and spare parts that have been tested with the heating system.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 7. Written in our own words; check the manual for your exact model.

Installation area conditions

Boiler · Vitocrossal 300 CU3A

Ambient temperature must stay between 32°F (0°C) and 104°F (40°C). Keep the air free of halogenated hydrocarbons and excess dust, and do not close existing ventilation openings.

  1. Confirm ambient temperature is above 32°F (0°C) and below 104°F (40°C).
  2. Keep combustion and boiler room air free of chlorine bleaches, solvents, refrigerants, paint fumes and dust.
  3. Never close existing ventilation openings.
  4. Avoid continuously high humidity, such as frequent drying of laundry near the boiler.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Installation code references for oil boilers

Boiler · Vitorond 100 VR1

Installation must follow local codes. Where no local code applies, use the listed oil burning equipment standards.

  1. In Canada, install per CAN/CSA-B139.00 for oil installations.
  2. In the U.S., install per NFPA 31 (Standard for the Installation of Oil Burning Equipment).
  3. Use the latest editions of codes.
  4. Wire to CSA C22.1 Part 1 in Canada, or NEC ANSI/NFPA 70 in the U.S., and to ANSI/ASME CSD-1 where the authority having jurisdiction requires it.

Applies to: Vitorond 100 VR1 installation

Source: Vitorond 100 VR1 installation and service manual, p. 5. Written in our own words; check the manual for your exact model.

Installation codes referenced by the manual

Boiler · Vitorond 200 VD2

Install to local codes. Where none apply, the manual points to these codes.

  1. Gas: CAN/CSA-B149.1 or .2 in Canada; NFPA 54 (ANSI Z223.1) in the U.S.
  2. Oil: CSA B-139 in Canada; NFPA 31 in the U.S.
  3. Electrical: CSA C22.1 Part 1 in Canada; NFPA 70 (NEC) in the U.S.
  4. Controls and safety devices: ANSI/ASME CSD-1 where the authority having jurisdiction requires it.
  5. Use the latest editions of the codes.

Applies to: Vitorond 200 VD2

Source: Vitorond 200 VD2 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Installation environment and clearance precautions

Boiler · Vitorond 200 VD2A

Keep the boiler away from halogenated hydrocarbons, dust and high humidity, and protect it from frost. Provide good ventilation. Maintain clearance from uninsulated hot water pipes to combustibles.

  1. Check that the room is free of halogenated hydrocarbon vapors from sprays, paints, solvents or cleaning agents.
  2. Protect against frost and ensure good ventilation.
  3. Keep 1 in air clearance from uninsulated hot water pipes to combustible material.
  4. Install only where dusty or humid conditions are avoided, or where adequate air supply measures are in place.

Applies to: Vitorond 200 VD2A installation

Source: vitorond 200 VD2A technical data manual, p. 11. Written in our own words; check the manual for your exact model.

Installation of additional components

Boiler · Vitocrossal 300 CA3B

Components not tested with the boiler can affect its function and performance.

  1. Only use additional components that have been tested with the boiler.
  2. Note that warranty does not cover damage from untested components.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Installing the control unit front

Boiler · Vitotronic 100 GC1

Close the control unit front and connect the Optolink and programming unit.

  1. Position the front housing and clip the hinges onto the counter-parts on the main housing.
  2. Release the stay bar, open it and lock it at point A.
  3. Insert the flat cable from the Optolink into plug X20.
  4. Insert the programming unit plug into plug X10, routing it through the cable guides in the cover.
  5. Engage the stay bar in the front housing.
  6. Close the front housing and secure it with the supplied screws.
  7. Install the connection enclosure cover and support it with the supplied screw.

Applies to: Vitotronic 100 GC1

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 54. Written in our own words; check the manual for your exact model.

Installing the programming unit in a control panel

Boiler · Vitotronic 300-K MW1S

Mount the programming unit in the front door of the control panel and connect it to the cascade electronic module.

  1. Cut an opening of 305 x 129 mm in the front door of the control panel.
  2. If installing two programming units, keep 20 mm between them.
  3. Snap the frame into place.
  4. Insert the programming unit.
  5. Plug the connecting cable into the back of the programming unit and into the cascade electronic module (A2).

Applies to: Vitotronic 300-K MW1S in custom control panel

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 56. Written in our own words; check the manual for your exact model.

Insulation blanket and jacket installation

Boiler · Vitorond 200

Insulation and enclosure panels are fitted in sequence over the cast iron block. The temperature control sensor sits between the third and fourth sections from the back.

  1. Mount the four threaded extension bolts into the rear section and make sure they are straight.
  2. Install the rear insulation blanket and rear panels.
  3. Install the temp-control sensor between the third and fourth sections, counting from the back.
  4. Tie the sensor harness to the tie rods with plastic straps.
  5. Lay the insulation blanket over the block with the nylon backing outward and fold in excess about 3.5 in. (80 mm).
  6. Run the thermal sensor through the back cut-outs, mount the front brackets and tighten the blanket with the butterfly nuts and spring.
  7. Install side panels to front brackets and rear panels, then the front panel, and fasten the control panel with self-tapping screws.

Applies to: Vitorond 200 VD2A boiler

Source: Vitorond 200, VD2A Series Installation, p. 25-26. Written in our own words; check the manual for your exact model.

Integrated DHW tank relief and control

Boiler · Vitodens 222-F

The DHW tank and its components are built into the unit; the boiler control runs DHW operation.

  1. Note the DHW tank is protected by a temperature and pressure relief valve rated at 150 psi.
  2. Pipe the relief valve discharge outlet to the drain as the manual describes.
  3. DHW inlet and outlet fittings are NPT, size not legible in the extracted text.

Applies to: Vitodens 222-F, B2TB integrated DHW

Source: Vitodens 222-F, B2TB installation instructions, p. 31. Written in our own words; check the manual for your exact model.

Intended use

Boiler · Versatronik 300 Cascade Control

The control stages Viessmann LON-enabled boilers and boiler controls over a CAT5 LON communication connection.

Applies to: Versatronik 300 Cascade Control

Source: Versatronik 300 Cascade Control manual, p. 3. Written in our own words; check the manual for your exact model.

Intended use and system requirements

Boiler · Vitodens 100-W B1HE/B1KE

The boiler is intended for a fixed installation in a sealed, unvented heating system and for heating water of potable quality. Changes that seal the flue or air paths are not allowed.

  1. Confirm the system is sealed and unvented.
  2. Confirm the water is of potable water quality.
  3. Do not modify the flue gas or ventilation air paths.
  4. Do not use the boiler for commercial or industrial purposes other than heating the building or domestic hot water.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Viessmann Vitodens 100-W B1HE/B1KE operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Isolate boiler before service work

Boiler · Vitorond 200 VD2

Only a licensed professional heating contractor should service the boiler, burner or control. There are no user-serviceable parts.

  1. Turn off main power to the boiler, heating system and all external controls.
  2. Close the main gas or oil supply valve.
  3. Take steps to prevent power from being switched back on during service.

Applies to: Vitorond 200 VD2

Source: Vitorond 200 VD2 installation instructions, p. 1. Written in our own words; check the manual for your exact model.

Isolate power and fuel before any service work

Boiler · Vitorond 200 VD2

Only licensed heating contractors should service this boiler, burner or control. Before working, switch off the main power to the equipment, close the main fuel supply valve to the boiler, and take steps so power or fuel cannot be switched on by accident. Make sure the system can run safely before servicing any component.

  1. Switch off main power to the equipment being serviced.
  2. Close the main fuel supply valve to the boiler.
  3. Lock out or guard the power and fuel supplies against accidental restart.
  4. Confirm the heating system is safe to run before working on any component.
  5. Use only original Viessmann or Viessmann approved replacement parts.

Applies to: All VD2 models 320 to 1080

Source: Vitorond 200 VD2 technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Isolate power and fuel before work

Boiler · KM-BUS Expansion Module

Before installing or servicing, disconnect power to the boiler, heating system and external controls. Close the main gas or oil supply valve. Only a licensed heating contractor should do this work, and there are no user-serviceable parts.

  1. Switch off the main power to the equipment, the heating system and all external controls.
  2. Close the main oil or gas supply valve.
  3. Take steps to prevent power from being switched on accidentally during service.

Applies to: KM-BUS Expansion Module and the boiler it is connected to

Source: KM-BUS Expansion Module installation instructions, p. 1. Written in our own words; check the manual for your exact model.

Isolate power and gas before any service work

Boiler · Vitorond 200 VD2A

There are no user-serviceable parts on the boiler, burner or control. Service must be done by a licensed heating contractor, and power and gas must be shut off first.

  1. Switch off main power to the boiler, the heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take steps to prevent power from being switched back on during service work.
  4. Verify field-supplied controls (low water cut-offs, flow switches, staging controls, pumps, motorized valves, air vents, thermostats) are complete and working.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Service Instructions, p. 6. Written in our own words; check the manual for your exact model.

Isolate power and gas before service

Boiler · Vitotronic 100

Electrical shock hazard from live components. Power to the equipment, heating system and external controls must be off, and the main gas or oil valve closed, before any service work.

  1. Switch off the electric supply at the equipment, heating system and external controls.
  2. Close the main gas or oil supply valve.
  3. Take measures to prevent accidental re-energising during service.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 5. Written in our own words; check the manual for your exact model.

Isolate power and gas before service work

Boiler · Vitocrossal 300 CA3B Dual Fuel

Before any service work, make sure the boiler cannot be energized while you work on it.

  1. Turn off main power to the boiler, the heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take steps so power cannot be switched on accidentally during the work.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Isolate power and gas before servicing

Boiler · Vitocrossal 300 CA3B Dual Fuel

There are no user-serviceable parts on the boiler, burners or controls. Service must be done by a licensed professional heating contractor.

  1. Turn off the main power to the equipment, heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take steps to prevent power from being switched on accidentally during service.
  4. Verify field-supplied controls such as low water cut-offs, staging controls, pumps, motorized valves, air vents and thermostats.

Applies to: All service work on the boiler

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 6. Written in our own words; check the manual for your exact model.

Isolate power and gas before working on the control

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

Live electrical parts can cause shock. Gas supply must also be shut off before service work.

  1. Turn off the electric power supply before servicing.
  2. Close the main gas supply valve.
  3. Make sure power cannot be restored by accident while you work.
  4. Verify that field-supplied controls (low water cut-offs, flow switches, pumps, motorized valves, thermostats) are complete and working.

Applies to: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 service

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 6. Written in our own words; check the manual for your exact model.

Isolate power before servicing

Boiler · Versatronik 581 / 581D

More than one live circuit is present. Contact with live components can cause serious injury or death.

  1. Turn off power to the control and to the damper or blower before servicing.
  2. Check the wiring diagram in the manual before working inside the gateway.

Applies to: Versatronik 581 and 581D

Source: Versatronik 581 LON gateway manual, p. 3. Written in our own words; check the manual for your exact model.

Isolate the boiler before any work

Boiler · Vitocrossal 200 CM2

Remove gas and electrical supply before opening or servicing the boiler.

  1. Close the main gas supply valve and protect it against reopening.
  2. Isolate power at the separate fuse or main switch.
  3. Confirm the system is de-energized.
  4. Safeguard the system against reconnection.
  5. Deactivate power to the heating system and all external controls.

Applies to: All Vitocrossal 200 CM2 units

Source: Vitocrossal 200 CM2 service instructions, p. 7-8. Written in our own words; check the manual for your exact model.

Isolate the boiler before service work

Boiler · Vitocrossal 200 CI2

Make sure power and gas are off before any service work to avoid accidental activation.

  1. Deactivate main power to the boiler, the heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take precautions to prevent power from being switched on during the work.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Junction box fuse and terminal layout

Boiler · Vitotronic 300

The fuse in the junction box is 250 V AC, 6.3 A (F3). The top L/N terminals are pre-wired to the harness. The bottom L/N/G terminals feed external equipment such as pumps and mixing valves.

  1. Check fuse F3 is 250 V AC, 6.3 A if the outputs have no power.
  2. Use the top L/N terminals for the pre-wired harness.
  3. Use the bottom L/N/G terminals for external pumps and mixing valves.

Applies to: Vitotronic 300 GW6B junction box

Source: Vitotronic 300 GW6B Installation and Service Instructions, p. 23-24. Written in our own words; check the manual for your exact model.

Keep cables clear of the control bracket and within temperature rating

Boiler · Vitocrossal 300 CU3A

Cables near the control unit must not be fastened to the control unit bracket. Cable temperature ratings must not be exceeded when routing and securing site wiring.

  1. Do not secure any cable to the control unit bracket.
  2. Check that site-run cables stay within their maximum permitted temperature.

Applies to: Vitocrossal 300 CU3A control unit wiring

Source: Vitocrossal 300 CU3A installation instructions, p. 56. Written in our own words; check the manual for your exact model.

Keep chemicals away from the combustion air supply

Boiler · Vitorond 200 VD2

Corrosive chemicals in the combustion air can damage the boiler and burner.

  1. Do not install the boiler where chlorine, bromine, fluorine or other corrosive chemicals are stored.
  2. Keep out refrigerants, bleach, paint, paint thinner, hair spray, cleaning solvents and water softener salt.
  3. Do not install where there is heavy dust, high humidity or risk of frost.
  4. Provide adequate ventilation and fresh combustion air.
  5. Size combustion air ducts using the local code sizing methods.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data, p. 16. Written in our own words; check the manual for your exact model.

Keep combustion air clean

Boiler · Vitodens 200-W, B2HA

Do not run the boiler where combustion air is contaminated with dust, lint or chemicals, such as construction sites, garages, laundry rooms, pool areas or workshops. Contaminated air damages the boiler and can cause carbon monoxide. The boiler must have adequate combustion and ventilation air.

  1. Check the boiler room for dust, lint and chemicals before service.
  2. Verify combustion and ventilation air provisions meet local codes.

Applies to: Vitodens 200-W B2HA 112/150/399/530

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 2. Written in our own words; check the manual for your exact model.

Keep combustion air free of contaminants

Boiler · Vitodens 100-W B1HE/B1KE

Contaminated combustion air damages the boiler and can cause property damage or injury. Chemicals such as chlorine, halogenated solvents and dust are common causes.

  1. Check the installation area for contaminant sources such as pool chemicals, refrigerant leaks, cleaners, dust or new construction.
  2. Do not install the boiler in areas with chemical exposure.
  3. Do not close existing ventilation openings.
  4. Avoid continuous high humidity in the boiler room.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Viessmann Vitodens 100-W B1HE/B1KE operating instructions, p. 2, p. 7. Written in our own words; check the manual for your exact model.

Keep combustion and ventilation air clean

Boiler · Vitocrossal 200 CI2

Contaminated combustion air can damage the boiler and cause serious hazards.

  1. Do not store chemicals, garbage, gasoline, flammable vapours or liquids near the boiler, even temporarily.
  2. Do not close existing ventilation openings.
  3. Avoid continuously high humidity in the boiler room.
  4. Check that nothing blocks combustion and ventilation air flow.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 operating instructions, p. 6-7. Written in our own words; check the manual for your exact model.

Keep combustion and ventilation air open

Boiler · Vitocrossal 300 CA3B Dual Fuel

Closed or blocked fresh air openings in the mechanical room cause incomplete combustion and poisonous gases.

  1. Make sure combustion air openings and ventilation air openings in the mechanical room are open.
  2. Do not close or obstruct these openings.
  3. Keep the boiler and boiler room free of combustible materials, gasoline and flammable vapors.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 6 and p. 7. Written in our own words; check the manual for your exact model.

Keep gateway wiring away from 120/240 VAC conductors

Boiler · Versatronik 505 & 505D

Wires run near high-voltage conductors can pick up electromagnetic interference. Avoid this where possible. If it cannot be avoided, use stranded twisted-pair or shielded wire, and ground only one end of the shield.

  1. Route low-voltage wiring away from 120/240 VAC conductors.
  2. If close routing is unavoidable, use stranded twisted-pair or shielded cable.
  3. Ground only one end of the shield.

Applies to: Versatronik 505 and 505D

Source: Versatronik 505 & 505D BACnet IP gateway manual, p. 5. Written in our own words; check the manual for your exact model.

Keep leak spray away from electrical contacts

Boiler · Vitocrossal 200 CM2

Leak detection spray can cause a malfunction if it reaches electrical contacts.

  1. Keep leak detection spray off electric contacts when leak testing the gas valve.

Applies to: Gas valve

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, pp. 32-33. Written in our own words; check the manual for your exact model.

Keep LON and low-voltage wiring away from mains wiring

Boiler · Versatronik 501, Versatronik 501D

Long wire runs can pick up electromagnetic interference. Keep the LON wiring clear of 120/240 VAC conductors. If that cannot be done, use stranded twisted-pair shielded wire and ground only one end of the shield.

  1. Route LON wiring away from 120/240 VAC conductors.
  2. If the runs must be close, use stranded twisted-pair shielded wire.
  3. Ground only one end of the shield.

Applies to: All Versatronik 501 and 501D gateways

Source: Versatronik 501 & 501D LON gateway manual, p. 5. Written in our own words; check the manual for your exact model.

Keep LON wiring away from line voltage

Boiler · Versatronik 581 / 581D

Long wire runs can pick up electromagnetic interference.

  1. Do not run LON wires beside or near 120/240VAC conductors.
  2. If you cannot avoid them, use stranded, twisted-pair shielded wire.
  3. Ground only one end of the shield.

Applies to: LON field wiring

Source: Versatronik 581 LON gateway manual, p. 4. Written in our own words; check the manual for your exact model.

Keep safety labels in place

Boiler · Vitodens 200-W

Follow the safety instructions on boiler labels and stickers. Do not remove them. Contact Viessmann if a replacement label is needed.

  1. Check that all labels and stickers on the boiler surfaces are present and legible.
  2. Order replacement labels from Viessmann if any are missing or damaged.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB installation manual, p. 57. Written in our own words; check the manual for your exact model.

Keep standard room temperature at or below 68°F (20°C)

Boiler · Vitocrossal 300

Every degree of room temperature reduction saves up to 6% on heating bills. Use the time program to set reduced temperatures at night.

  1. Set the standard room temperature no higher than 68°F (20°C).
  2. Set a time program so the home is at standard temperature in the day and reduced temperature at night.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Keep the boiler and boiler room clear

Boiler · Vitocrossal 300 CA3B Dual Fuel

The boiler must be kept clear of combustibles and flammable material, and combustion and ventilation air must not be blocked. The boiler must be cleaned at least once a year by a qualified heating technician or service agency.

  1. Keep the boiler and boiler room free of gasoline, flammable vapors and liquids, and combustible materials.
  2. Do not block combustion or ventilation air.
  3. Have a qualified heating technician clean the boiler at least once a year.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service, p. 156. Written in our own words; check the manual for your exact model.

Keep the front cover on and check combustion air

Boiler · Vitodens 222-F

Do not run the boiler without the front cover. Do not run it where combustion air is contaminated by dust, lint or chemicals, which can damage the boiler and cause serious harm.

  1. Keep the front cover in place whenever the boiler runs.
  2. Check the boiler room for dust, lint and chemicals before start-up.
  3. Have the boiler inspected and serviced by a qualified contractor at least once a year.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB installation instructions, p. 2. Written in our own words; check the manual for your exact model.

Keep the installation and service documents with the boiler

Boiler · Vitotronic 300

The installation, operating and service instructions should go in the service document ring binder, which can be kept in an optional service box.

  1. File the installation, operating and service instructions in the service binder.
  2. Store the binder near the boiler where service personnel can reach it.

Applies to: Vitotronic 300 KW3

Source: Vitotronic 300 installation instructions, p. 24. Written in our own words; check the manual for your exact model.

Keep vent termination above snow level

Boiler · Vitocrossal 200 CI2

Vent termination must sit well above the expected snow level so snow cannot block it.

  1. Check local snow level with building authorities or the local weather office.
  2. Set the termination at least 12 in above that level.
  3. Make sure snow cannot block the termination.

Applies to: Sidewall and vertical vent terminations

Source: Vitocrossal 200 CI2 Installation manual, p. 56, 58. Written in our own words; check the manual for your exact model.

Label and check wiring during control service

Boiler · Vitodens 200-W B2HA

Wiring errors can make the boiler run improperly and dangerously. Replacement wires must match the original exactly.

  1. Label all wires before disconnecting them when servicing controls.
  2. Replace any original supplied wire only with an exact equivalent.
  3. Verify proper operation after servicing.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 88. Written in our own words; check the manual for your exact model.

Lag boiler faults are not sent to the BMS

Boiler · Versatronik 581 / 581D

The lead boiler reports when any lag boiler has a fault, but the gateway does not pass that to the BMS, so the lead does not appear faulted. The lag boiler's fault code is shown under its own boiler fault point. Boiler 1's fault point only shows faults from the lead boiler. If the physical control shows a fault that the gateway does not report, check the matching boiler fault point.

Applies to: GW6B cascade

Source: Versatronik 581 LON gateway manual, p. 13. Written in our own words; check the manual for your exact model.

Lag boiler section service display location

Boiler · Vitocrossal 300 CA3B

In a multi-boiler setup, service messages for lag sections B and C show on the lower panel and need the lower front panel and control cover opened. Service messages for section A on lag boilers use the top panel, depending on the fault.

  1. For section B or C service messages, open the lower front boiler panel and control cover.
  2. For section A on a second, third or fourth boiler, open the top front panel and control cover if the fault requires it.

Applies to: Vitocrossal 300 CA3B multi-boiler installations

Source: Vitocrossal 300 CA3B operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Lago FB display indicators

Boiler · Versatronik 200

Burner stages I and II, heating operation (D, with Z meaning pump on), DHW operation (!, with Z meaning pump on), mixing valve open/closed (y/z), BUS communication OK, room temperature and time (C/F), holiday days remaining (HO), outside temperature (AF, with outside sensor), boiler temperature (H), heating circuit supply temperature (D), DHW tank temperature (!), and fault (E001).

Applies to: Lago FB remote control

Source: Versatronik 200 installation and operating manual, p. 56. Written in our own words; check the manual for your exact model.

Lago FB display status indicators

Boiler · Versatronik 200

The Lago display shows status symbols for burner, heating, DHW, mixing valve, holiday mode, temperatures and faults. Use the value selector dial with the mode dial set to RUN to view current information.

Applies to: Lago FB remote with Versatronik 200

Source: Versatronik 200 installation and operating manual, p. 56. Written in our own words; check the manual for your exact model.

Lambda Pro automatic gas adjustment

Boiler · Vitodens 200-W B2HB

Lambda Pro adjusts combustion to the gas type and quality automatically, so no fuel conversion kit is needed for natural gas or LPG.

  1. Do not fit a fuel conversion kit for natural gas or liquid propane.
  2. Check combustion with CO2 or O2 readings and compare to the air factor table.

Applies to: Gas type changes on Vitodens 200-W B2HB

Source: Vitodens 200-W, B2HB technical data manual, p. 32. Written in our own words; check the manual for your exact model.

Lambda Pro combustion management and self-calibration

Boiler · Vitocrossal 300 CU3A

The control reads ionization current to set the air factor, then sets the gas valve to suit the gas quality. It self-calibrates after power failures and at burner start. Brief high CO can appear during calibration.

  1. Expect the automatic calibration to run for about 5 seconds shortly after burner start.
  2. Do not judge combustion readings during calibration. CO can briefly be higher than normal.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 29. Written in our own words; check the manual for your exact model.

Lead and lag section layout in single and multi-boiler setups

Boiler · Vitocrossal 300 CA3B

Single boiler sections are set up without opening any front panels. Section A is the lead, B is lag 1, and C is lag 2 on 5.0 and 6.0 models. Multi-boiler setups use the lag numbering in sequence.

  1. Single boiler: A is lead section 1, B is lag 1 (section 2), and C is lag 2 (section 3) on 5.0 and 6.0.
  2. Multi-boiler: all sections are controlled and displayed from the first boiler's lead control (section 1).
  3. Open the lower panel and control cover on the second, third or fourth boiler to set up lag control.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 14. Written in our own words; check the manual for your exact model.

Lead cascade dynamic control strategy (lead boiler only)

Boiler · Vitocrossal 200 CI2

Adjusts the dynamic control strategy and runtime optimization so each boiler in the cascade has the same runtime. Also sets which boiler starts first or last.

Applies to: Lead boiler in a cascade

Source: Vitocrossal 200 CI2 operating instructions, p. 30. Written in our own words; check the manual for your exact model.

Leak test after gas work

Boiler · Vitocrossal 200 CM2

Gas leakage can cause an explosion. Always leak test any gas line or gas valve connection you have disconnected.

  1. Leak test the reconnected gas line and valve connections before leaving the boiler.
  2. Use only approved leak detection fluid for natural gas and propane.

Applies to: Gas valve, burner tube, burner fan, burner door and electrode work

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, pp. 32-40. Written in our own words; check the manual for your exact model.

LED2 communication indicator

Boiler · Versatronik 502/502D

LED2 blinks each time a Modbus request is seen on the network. If it never blinks, the master is not reaching the gateway.

Applies to: Versatronik 502 / 502D gateway

Source: Versatronik 502 & 502D MODBUS manual, p. 18. Written in our own words; check the manual for your exact model.

Lifting the boiler

Boiler · Vitocrossal 300 CA3B Dual Fuel

Use lifting equipment rated for at least the boiler weight. Do not lift by the flue gas collector.

  1. Use certified lifting devices rated to at least the full boiler weight.
  2. Lift with lift-truck forks at the side locations (centre the forks on the / mark) or at the front location.
  3. Do not lift the boiler at the flue gas collector; damage can cause flue leakage.
  4. Lift the boiler by crane only while it is still in its packaging.

Applies to: CA3B Dual Fuel 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 10. Written in our own words; check the manual for your exact model.

Lightguide status light meaning

Boiler · Vitocrossal 200 CI2

A red illuminated strip (Lightguide) sits at the lower or upper edge of the control unit depending on boiler type. Its behaviour shows the system state. Slow pulsing means standby. Steady light means someone is operating the control unit, and each input is confirmed by a short flash. Fast flashing means a fault is present. The Lightguide can be switched off in the Settings menu.

  1. If the Lightguide pulses slowly, the display is in standby. No action is needed.
  2. If the Lightguide is steady, the control unit is in use.
  3. If the Lightguide flashes quickly, a fault is present. Check the message lists in the main menu for the fault.

Applies to: Vitocrossal 200 CI2 control unit

Source: Vitocrossal 200 CI2 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Lightguide status meanings

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

The red Lightguide strip on the control unit shows the system state. A slow pulse means standby. Constant light means the control unit is being operated, and each input gives a short flash. A quick flash means there is a fault in the system. No fault code is shown with this signal on these pages. The Lightguide can be switched off in the settings.

  1. If the Lightguide flashes quickly, check the active messages in the main menu for a fault.
  2. To turn the Lightguide off or on, use the Lightguide setting in the display menu.

Applies to: Vitodens 100-W B1HE and B1KE, control unit display

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Limit aquastat for underfloor heating

Boiler · Vitotronic 200

A field-supplied electromechanical limit aquastat protects underfloor heating and floor covering. It switches off the heating circuit pump when the preset temperature is exceeded.

  1. Set the aquastat within 59 to 203 ºF (15 to 95 ºC).
  2. Wire the aquastat to the heating circuit pump circuit as the diagram shows.

Applies to: Vitotronic 200 KW2 heating circuit with underfloor heating

Source: Vitotronic 200 service instructions, p. 75. Written in our own words; check the manual for your exact model.

Limit aquastat wiring jumper

Boiler · Vitotronic 200-H

A jumper is fitted across terminals L-L. It must be removed before the high limit aquastat is connected.

  1. Remove the jumper from terminals L-L.
  2. Connect the high limit aquastat (optional) to those terminals.

Applies to: Power/pump module, high limit aquastat connection

Source: Vitotronic 200-H installation and service instructions, p. 6 and p. 8. Written in our own words; check the manual for your exact model.

Literature to leave on site

Boiler · Vitorond 100

Keep the boiler literature at the installation site and tell the owner where it is stored. The set includes the Technical Data Manual, Installation Instructions, Service Instructions, Operating Instructions, instructions for other Viessmann products used, and Hydrostat 3250-Plus instructions.

Applies to: Vitorond 100 installation

Source: Viessmann Vitorond 100 installation and service manual, p. 5. Written in our own words; check the manual for your exact model.

Live circuits and service safety

Boiler · Versatronik 511 / 511D

More than one circuit is live. Shut off power to the control and the damper/blower before servicing, because contact with live parts can cause serious injury or death. Follow the wiring diagram in the manual.

  1. Turn off power to the control.
  2. Turn off power to the damper/blower.
  3. Confirm the circuits are dead before touching wiring.

Applies to: Versatronik 511 and 511D

Source: Versatronik 511 & 511D LON Type B manual, p. 3. Written in our own words; check the manual for your exact model.

Locate the cascade control programming unit and default display

Boiler · Vitotronic 300-K

All settings for the heating system are changed centrally at the Vitotronic 300-K. Each boiler has its own Vitotronic 200 control unit, which is limited in display and settings.

  1. If the screensaver is active, tap the display anywhere to start.
  2. To return to the default display from anywhere in the menu, tap the home button in the footer.
  3. The default display lists the boilers in boiler sequence order. The sequence can be changed on page 21.

Applies to: Multi boiler cascade system, Vitotronic 300-K MW2C

Source: Vitotronic 300-K MW2C operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Locating the serial number for parts orders

Boiler · Vitodens 200-W B2HB

Parts orders need either the 16-digit boiler serial number on the bar code label or the 12-digit ASME/NB serial number. Both are under the front enclosure panel. Remove the panel first.

  1. Remove the front enclosure panel (see page 15 of the manual).
  2. Read the 16-digit serial from the bar code label or the 12-digit ASME/NB serial.
  3. Give the serial when ordering parts, because some parts are not reverse compatible with earlier versions.

Applies to: Vitodens 200-W B2HB, all models

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.

LON communication module is pre-installed

Boiler · Vitocrossal 300 CU3A

The boiler comes with a LON communication module already fitted. Refer to the Service Instructions and the Vitotronic 200-H HK1B installation instructions for LON wiring.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A installation manual, p. 30. Written in our own words; check the manual for your exact model.

LON communication wiring

Boiler · Vitotronic 300

A LON module on the control unit allows data transfer between units. Interruption of communication is shown on the unit.

  1. Connect the control units with the LON connecting cable.
  2. Fit a terminal resistor on the first and last control unit only.
  3. Watch for the communication interruption indicator if data stops.

Applies to: Multiple control units on LON

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 96. Written in our own words; check the manual for your exact model.

Long shutdown (e.g. after heating season)

Boiler · Vitocrossal 300 CA3B Dual Fuel

Clean the boiler before a long shutdown to prevent corrosion. The heating system can stay filled and pressurized.

  1. Clean the combustion chamber, the flue gas collector and the vent pipe.
  2. Remove remaining condensate from the flue gas collector through the inspection opening.
  3. Leave the heating system filled and under pressure if desired.

Applies to: Vitocrossal 300 CA3B Dual Fuel boiler

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 42. Written in our own words; check the manual for your exact model.

Long shutdown cleaning

Boiler · Vitocrossal 200 CM2

After a long shutdown, such as after the heating season, the combustion chamber, flue gas collector and vent pipe should be cleaned to prevent corrosion. The system can stay filled and pressurized.

  1. Clean the combustion chamber, flue gas collector and vent pipe.
  2. Remove remaining condensate from the flue gas collector through the front inspection service opening.

Applies to: Vitocrossal 200 CM2 186 to 620

Source: Vitocrossal 200 CM2 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Long shutdown of boiler

Boiler · Vitocrossal 300 CA3B

After an extended shutdown, for example after the heating season, the boiler must be cleaned to prevent corrosion. The heating system can stay filled and pressurized.

  1. Properly clean the combustion chamber, flue gas collector and vent pipe.
  2. Remove remaining condensate from the flue gas collector through the inspection opening.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B operating instructions, p. 42. Written in our own words; check the manual for your exact model.

Long shutdown preparation

Boiler · Vitocrossal 300 CA3B

After a long shutdown, such as at the end of the heating season, clean the combustion chamber, flue gas collector and vent pipe to prevent corrosion. The system can stay filled and pressurized.

  1. Clean the combustion chamber, flue gas collector and vent pipe.
  2. Remove remaining condensate from the flue gas collector through the inspection opening.
  3. Leave the system filled and under pressure if desired.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 42. Written in our own words; check the manual for your exact model.

Low water cut-off (LWCO) installation

Boiler · Vitorond 200

A low water cut-off must be installed when the boiler sits above radiation level. It must be an approved type and is standard equipment. The mechanical contractor installs it where local codes require. Viessmann recommends an LWCO in all installations.

  1. Install supply and return headers with pressure gauge, temperature gauge, air vent, LWCO, boiler drain valve and bypass pump.
  2. Pipe up to the isolation valves and close them before testing.

Applies to: Vitorond 200 VD2A boiler

Source: Vitorond 200, VD2A Series Installation, p. 24. Written in our own words; check the manual for your exact model.

Low water cut-off and field-verified piping

Boiler · Vitodens 200-W

Piping examples are simplified conceptual drawings. Piping and required components must be verified in the field. A low water cut-off (LWCO) is required where local codes call for it. Proper installation and function are the heating contractor's responsibility.

  1. Field-verify all piping and components against the drawings.
  2. Install a low water cut-off where local codes require it.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 32. Written in our own words; check the manual for your exact model.

Low water cut-off and isolation valve

Boiler · Vitodens 200-W B2HB

A remote-mounted low water cut-off may be required by local code. Do not place an isolation valve between the boiler and the low water cut-off. Follow the cut-off maker's installation instructions and the wiring diagram referenced in the manual.

  1. Check local code to see whether a low water cut-off is required.
  2. Mount the low water cut-off remotely, following the manufacturer's instructions.
  3. Do not install an isolation valve between the boiler and the low water cut-off.
  4. Wire the low water cut-off as shown in the applicable wiring diagram.

Applies to: Vitodens 200-W B2HB with field-supplied remote low water cut-off

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 44. Written in our own words; check the manual for your exact model.

Low water cut-off installation

Boiler · Vitorond 100 VR1

A low water cut-off may be required by local codes. It must be installed whenever the boiler sits above the radiation level.

  1. Use an approved type low water cut-off supplied by the heating contractor.
  2. Do not install an isolation valve between the boiler and the low water cut-off.
  3. Hydrostat 3250-Plus includes a low water cut-off with electro well sensor. Do not disable it, since local codes may require it.
  4. The 3250-Plus can be set to automatic (default) or manual reset.

Applies to: Low water cut-off

Source: Vitorond 100, VR1 Technical Data, p. 11 and p. 12. Written in our own words; check the manual for your exact model.

Main component locations (legend)

Boiler · Vitotron 100 VLN2

Numbered components on the general view: 1 heating element power supply terminals, 2 control panel, 3 pump, 4 pressure relief valve, 5 pressure sensor, 6 magnetic filter, 7 manual reset high limit device, 8 heating element, 9 flow and outlet temperature sensor, 10 by-pass valve, 11 water inlet, 12 water outlet.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.

Main PCB LV connection legend

Boiler · Vitotronic 200, Vitotronic 300-K

Legend for the low-voltage main board. It covers the outside temperature sensor, the common supply sensor, the DHW tank sensors (1 and optional 2), the primary store sensor, the external hook-ups, the optional KM BUS participant and the LON cable between control units. The wiring drawing itself is not on these pages.

Applies to: Main PCB LV

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 88. Written in our own words; check the manual for your exact model.

Main power supply terminal wire colours

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The main power terminals are push-in type and accept only one conductor each.

  1. Connect the grey wire to Line (L).
  2. Connect the blue wire to Neutral (N).
  3. Connect the green/yellow wire to Ground (G).
  4. Press the orange button to open the terminal before inserting or releasing a wire.
  5. See page 31 of the manual for power supply connection details.

Applies to: Main power supply connection

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 22. Written in our own words; check the manual for your exact model.

Maintenance and energy saving

Boiler · Vitotronic 200-H

Regular maintenance keeps heating trouble-free and efficient. The manual recommends an inspection and maintenance contract. Energy saving measures include ventilating briefly with windows fully open and radiator valves closed, keeping room temperature near 20 °C (each degree lower saves up to 6%), closing roller shutters at dusk, not covering radiators or valves, and alternating normal and reduced room temperature.

  1. Arrange an inspection and maintenance contract with the heating contractor.
  2. Ventilate briefly with windows fully open and radiator valves closed.
  3. Keep room temperature near 20 °C.
  4. Close roller shutters at dusk.
  5. Do not cover radiators or thermostatic valves.
  6. Use normal and reduced room temperature settings on the control unit.

Applies to: Vitotronic 200-H, Model HK1M

Source: Vitotronic 200-H Operating Instructions, p. 17. Written in our own words; check the manual for your exact model.

Manual sequence for cascade stages

Boiler · Versatronik 200

In service mode the cascade boilers can be started one stage at a time. For a second stage on multi-stage units, preset an output above 50%. Entries reset automatically when service functions close.

  1. Open the Manual Sequence level (service code required).
  2. Select the heat generator with the F button.
  3. Select the output for that boiler.
  4. For a multi-stage unit, set the output above 50% to start the second stage.

Applies to: Cascades in Service operation mode

Source: Versatronik 200 installation and operating manual, p. 164. Written in our own words; check the manual for your exact model.

Manually adjust the mixing valve motor

Boiler · Vitotronic 300-K MW1S

Use this to move the valve by hand when the motor is out of service.

  1. Lift the motorized lever up.
  2. Unhook the mixing valve handle.
  3. Remove plug A from the motor.
  4. For 24 V actuators, follow the instructions supplied with the actuator.

Applies to: Mixing valve motor

Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 128. Written in our own words; check the manual for your exact model.

Marine or damp coastal installations

Boiler · Vitodens 200-W B2HA

Metal casing and fan housing corrode quickly in damp, salty air. Boilers in these areas must not use direct vent systems that draw outdoor air.

  1. Install room air dependent venting in marine environments.
  2. Keep indoor relative humidity low, for example avoid frequent laundry drying in the room.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 10. Written in our own words; check the manual for your exact model.

Marine or damp salty environment venting

Boiler · Vitodens 200-W B2HB

In damp, salty coastal areas chloride from sea spray can corrode the casing and fan housing. Boilers in these areas must use a room-air-dependent vent system, not a direct vent that draws outdoor air.

  1. Identify if the install is in a damp, salty coastal area.
  2. Use a room-air-dependent vent system, not a direct vent system.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 10. Written in our own words; check the manual for your exact model.

Marine or damp salty environments

Boiler · Vitodens 200-W B2HA

In coastal or marine areas, salt spray and humidity corrode the casing and fan housing. Do not use direct vent systems that pull outdoor air. Use a room air dependent vent system so the indoor air stays drier.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 10. Written in our own words; check the manual for your exact model.

Marine or salt-air installations

Boiler · Vitocrossal 300 CU3A

Direct vent air intake is not acceptable in damp, salty coastal areas. Use room air dependent venting.

  1. Do not use direct vent systems in marine environments.
  2. Install with a room air dependent vent system.

Applies to: Coastal installations

Source: Vitocrossal 300 CU3A service instructions, p. 9. Written in our own words; check the manual for your exact model.

Massachusetts CO detector and signage requirements

Boiler · Vitodens 200-W B2HB

For side-wall horizontally vented installs in Massachusetts where the vent terminal is under 7 ft above grade, a hard-wired CO detector with battery backup is required on the gas equipment floor and an alarm on each additional level. A metal or plastic sign reading 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' is required at least 8 ft above grade in line with the vent. Certain equipment is exempt.

  1. Confirm a hard-wired CO detector with battery backup is on the gas equipment floor.
  2. Confirm a CO detector with alarm is on each additional level served.
  3. Confirm the warning sign is posted at least 8 ft above grade, in line with the vent terminal.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Massachusetts CO detector and signage rules for sidewall vented installations

Boiler · Vitorond 100

For sidewall horizontally vented gas equipment in Massachusetts residential buildings where the vent termination is under 7 ft above grade, hard-wired CO detectors with alarm and battery backup are required on the floor level of the installation, with alarms on each additional level. Signage is required at the vent.

  1. Confirm a hard-wired CO detector with battery backup is on the installation floor level.
  2. Confirm CO detectors with alarms are on each additional level served.
  3. If the requirements cannot be met at completion, install a battery operated CO detector and allow 30 days to comply.
  4. Detectors must meet NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
  5. Mount a metal or plastic sign at least 8 ft above grade in line with the vent terminal reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.

Applies to: Sidewall horizontally vented fuel equipment in Massachusetts

Source: Viessmann Vitorond 100 installation and service manual, p. 4. Written in our own words; check the manual for your exact model.

Massachusetts side-wall vent CO detector requirements

Boiler · Vitodens 200-W B2HA

For side-wall horizontal venting where the vent end is under 7 ft above grade, a hard-wired CO detector with battery backup must be on the floor level of the installation, and CO detectors with alarms on each additional level. A warning sign must be placed 8 ft above grade in line with the vent.

  1. Confirm hard-wired CO detector with battery backup on the installation floor level.
  2. Confirm CO detectors with alarms on each additional level.
  3. Confirm the 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' sign is installed 8 ft above grade.

Applies to: Installations in the Commonwealth of Massachusetts

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 7. Written in our own words; check the manual for your exact model.

Massachusetts side-wall vent requirements

Boiler · Vitodens 200-W B2HB

For side-wall horizontally vented gas equipment in Massachusetts dwellings where the vent termination is under 7 ft above grade, a hard-wired CO detector with battery backup is required on the installation floor level and CO detectors on each additional level. A warning sign is also required 8 ft above grade in line with the vent. A 30-day allowance applies only if a battery CO detector is installed meanwhile. Detectors must meet NFPA 720 and ANSI/UL 2034.

Applies to: Installations in the Commonwealth of Massachusetts

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Maximum boiler-to-CombiPLUS distance

Boiler · Vitodens 100-W WB1B

The communication cable limits the distance between boiler and CombiPLUS to 36 in (915 mm), measured with field-supplied fittings and pipes.

Applies to: Vitodens 100-W WB1B with CombiPLUS

Source: Vitodens 100-W WB1B installation and service instructions, p. 27. Written in our own words; check the manual for your exact model.

Mechanical room conditions

Boiler · Vitocrossal 300 CA3B

Boiler room air quality and conditions affect heat exchanger life and warranty coverage.

  1. Do not install the boiler where chemicals, aggressive vapors (e.g. bleach, hair spray, perchloroethylene), halogenated hydrocarbons, high dust or high humidity are present.
  2. Keep the room frost-protected.
  3. Keep the ambient temperature at or below 95°F (35°C).
  4. Provide good ventilation and do not close or obstruct vents.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 operating instructions, p. 6, p. 7. Written in our own words; check the manual for your exact model.

Mechanical room disconnect and fuel shut-off

Boiler · Vitocrossal 200 CI2

Viessmann recommends extra safety shutoffs located outside the boiler room.

  1. Install an extra electrical disconnect switch outside the mechanical room or enclosed installation area.
  2. Install a fuel shut-off valve outside the mechanical room where possible.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 3. Written in our own words; check the manual for your exact model.

Mechanical room location and ambient limits

Boiler · Vitodens 200-W B2HB

Put the boiler in a heated indoor room near a floor drain and close to an outside wall. Room must stay between 32°F and 104°F (0°C and 40°C). Keep halogenated hydrocarbons and heavy dust out of the combustion air and never block existing vents. The wall must carry the full water weight of the boiler.

  1. Confirm the room is heated and stays between 32°F and 104°F (0°C and 40°C).
  2. Check the boiler sits near a floor drain and near an outside wall where the vent can run easily.
  3. Check the wall can carry the full water-filled boiler weight (see Technical Data, p. 99).
  4. Check for chemical or dust sources such as paint solvents, bleaches, refrigerant leaks, or salt before installing.
  5. Leave existing ventilation openings open.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 10. Written in our own words; check the manual for your exact model.

Mechanical room requirements

Boiler · Vitorond 200 VD2

The boiler room must be heated, indoors, and free of contaminated air. Keep fresh combustion air available.

  1. Locate the boiler in a heated indoor space near a floor drain and as close as practical to the chimney or vent.
  2. Place it near an outside wall where fresh air can be ducted directly to the boiler area when possible.
  3. Keep the room at or below 104°F (40°C).
  4. Do not install where chemicals are stored or in rooms with refrigeration equipment.
  5. Do not run exhaust fans unless fresh combustion air provisions are added, such as a fresh air fan.
  6. Install an electrical disconnect and a fuel shut-off valve outside the mechanical room if possible.

Applies to: Boiler room and combustion air

Source: Vitorond 200 VD2 installation instructions, p. 7-10. Written in our own words; check the manual for your exact model.

Minimum clearances to combustibles

Boiler · Vitodens 200-W B2HB

Vitodens 200-W B2HB is listed for zero clearance to combustibles when vented with listed single-wall special venting (AL-29-4C). This listing overrides the clearance printed on the venting label. The clearance row on the page is garbled: most positions read 0, and AL/CL (alcove/closet) is marked in one position. Confirm the exact per-side values from the clean table in the installation instructions before setting the boiler. Service clearance values are titled on this page but not printed in the text.

  1. Confirm the clearance table in the installation instructions before placing the boiler.
  2. Keep the vent pipe to the listed special venting system when using zero clearance.
  3. Leave the service clearances shown in the installation instructions for access.

Applies to: Vitodens 200-W B2HB 19 to 199

Source: Vitodens 200-W B2HB technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Minimum water pressure for operation

Boiler · Vitotron 100 VLN2

The boiler will not run below 7 psi water pressure.

  1. Check the system pressure is at least 7 psi before expecting the boiler to run.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 3. Written in our own words; check the manual for your exact model.

Mixing valve controller accessory kit

Boiler · Vitodens 200-W B2HB

The mixing valve controller kit works only with wall-mounted gas-fired hot water heating boilers and a weather-responsive control. It can replace a Vitotronic control.

  1. Check that the boiler is wall-mounted, gas-fired, hot water heating, and that a weather-responsive control is used.
  2. Connect the accessory kit to the heating circuit with mixing valve as shown in the manual.
  3. Set coding as described in the Vitodens 200-W B2HB service instructions.
  4. Follow the accessory kit installation instructions for installation.

Applies to: Models 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 56. Written in our own words; check the manual for your exact model.

Mixing valve extension kit sensor and components

Boiler · Vitotronic 200-H

The mixing valve kit includes a contact-type supply temperature sensor with a 19 ft (5.8 m) cable.

  1. Use the connecting plug for the heating circuit pump.
  2. Use the supply temperature sensor as a contact sensor for the supply temperature.

Applies to: Mixing valve extension kit

Source: Vitotronic 200-H HK1B installation and service instructions, p. 76. Written in our own words; check the manual for your exact model.

Mixing valve extension PCB for heating circuits 2 and 3: diagram legend

Boiler · Vitotronic 300

Legend for the wiring diagram of the extension PCB that serves heating circuits 2 and 3 with mixing valves. It covers the supply temperature sensors for M2/M3, the heating circuit pumps for M2/M3, the power supply, the mixing valve motors for M2/M3, relays K1 to K6 and the electrical interfaces.

Applies to: Vitotronic 300 GW6B extension PCB for heating circuits 2 and 3

Source: Vitotronic 300, GW6B installation and service instructions, p. 120. Written in our own words; check the manual for your exact model.

Mixing valve heating circuit

Boiler · Vitotronic 300-K

A mixing valve blends hot boiler water with cooler return water from the heating circuit. The heating circuit pump circulates the blended water. The control adjusts supply temperature through the mixer to suit outdoor conditions. The mixing valve assembly with extension kit is an accessory.

Applies to: Heating circuits with mixing valve

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 33. Written in our own words; check the manual for your exact model.

Mixing valve heating circuit and DHW recirculation pump

Boiler · Vitotronic 300-K

A mixing valve extension kit (accessory) lets the control run a heating circuit with a mixing valve. The mixer mixes hot boiler water with cooled return water to hold the supply temperature the control calls for. A DHW recirculation pump moves DHW around a loop between the tank and the draw-off points so hot water reaches the tap faster.

Applies to: Heating circuits with mixing valve; DHW recirculation

Source: Vitotronic 300-K, MW2C operating instructions, pp. 34-35. Written in our own words; check the manual for your exact model.

Mixing valve motor direction for installation examples

Boiler · Vitotronic 300-K MW1S

The factory motor direction is set for the default layout. Change the direction for the installation examples shown on this page. Abbreviations: HR heating return, HV heating supply, KR boiler return, KV boiler supply.

  1. Compare the installation layout with the example diagram.
  2. If the example requires it, reverse the mixing valve motor rotation (see the rotation procedure on page 128).
  3. Refer to the mixing valve installation instructions for insert conversion, if required.

Applies to: Mixing valve circuits

Source: Viessmann Vitotronic 300-K MW1S installation and service instructions, p. 129. Written in our own words; check the manual for your exact model.

Mixing valve motor wiring for installation examples

Boiler · Vitotronic 300 GW2

As delivered, the mixing valve motor is wired for the installation examples shown. Only change the motor connections when the installation example requires it. Legend: HR heating return, HV heating supply, KR boiler return, KV boiler supply, A marker notch.

  1. Leave the motor wiring as delivered if it matches the installation example.
  2. If a different installation example is used, change the electrical connections of the mixing valve motor as shown for that example.

Applies to: Mixing valve motor

Source: Vitotronic 300, Model GW2 installation and service instructions, p. 105. Written in our own words; check the manual for your exact model.

Modbus register access limits

Boiler · Versatronik 502/502D

The gateway treats holding and input registers as the same data. Holding register 1 is address 40001. Registers 1 to 23 are saved in EEPROM and survive a power cycle. Coil and input status are not used.

  1. Read no more than 40 registers in one request.
  2. Do not go past address 78, or the gateway returns an exception response.

Applies to: Versatronik 502 / 502D gateway

Source: Versatronik 502 & 502D MODBUS manual, p. 19. Written in our own words; check the manual for your exact model.

Mounting the 120VAC gateway (502)

Boiler · Versatronik 502 & 502D

The 120VAC unit mounts on a wall near the boiler control. The cover is held by two screws, one on each side of the base.

  1. Mount the gateway near the connected boiler control.
  2. Loosen the two screws on either side of the base and remove the cover.
  3. Fasten the base to the wall with field-supplied screws or fasteners.
  4. Remove a knockout and fit a strain relief or box connector. Remove other knockouts only as needed.
  5. After all 120VAC and low-voltage connections are complete and checked, refit the cover.

Applies to: Versatronik 502 NR2/MODBUS (120VAC)

Source: Versatronik 502 NR2 Modbus manual, p. 5. Written in our own words; check the manual for your exact model.

Mounting the 24VAC DIN rail gateway (502D)

Boiler · Versatronik 502 & 502D

The 24VAC unit mounts on a DIN rail inside an enclosure near the boiler controls.

  1. Mount the Versatronik 502D on a DIN rail inside an enclosure near the boiler controls.
  2. Make all connections, including the field-supplied 24VAC power connection.
  3. Check the connection overview on the unit: RJ45 control connection, paralleled BUS connection, Modbus A+ and B- connection, and 24VAC power connection.

Applies to: Versatronik 502D NR2/MODBUS (24VAC)

Source: Versatronik 502 NR2 Modbus manual, p. 6. Written in our own words; check the manual for your exact model.

Mounting the front part of the control unit (CM2 only)

Boiler · Vitotronic 100, GC1

CM2 boilers only. Refit the front housing of the control unit after wiring.

  1. Fit the front housing hinges into the counterparts on the main housing.
  2. Release the stay bar, open it up and lock it at point A.
  3. Plug the flat cable from the Optolink into socket X20.
  4. Plug the programming unit lead into socket X10 and route it through the cable guides in the cover.
  5. Engage the stay bar in the front housing.
  6. Close the front housing and secure it with the supplied screws.
  7. Fit the control cosmetic cover.

Applies to: Vitotronic 100 GC1 on CM2 boilers

Source: Vitotronic 100 GC1 installation and service instructions, p. 40. Written in our own words; check the manual for your exact model.

Multi-boiler display numbering

Boiler · Vitotronic 100 GC1B

In multi-boiler systems each Vitotronic 100 shows its boiler number on the standard display.

  1. Read the boiler number shown on the standard display to know which boiler's temperature is shown.

Applies to: Multi-boiler cascade

Source: Viessmann Vitotronic 100 GC1B / 300-K MW1B operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Multi-boiler system notes

Boiler · Vitocontrol-S

Some Vitotronic 100, GC1 functions do not work in a multi-boiler system. These include the boiler water temperature change, the domestic hot water temperature change and the heating program selector buttons, which are marked on the controls.

  1. In a multi-boiler system, make boiler water and DHW temperature changes through the Vitocontrol-S, not the individual boiler control.
  2. Note that heating program buttons on the Vitotronic do not function in a multi-boiler system.

Applies to: Multi-boiler systems

Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 2, p. 6. Written in our own words; check the manual for your exact model.

Naming heating circuits

Boiler · Vitocrossal 300 CA3B

Each heating circuit can be given its own name, such as Ground floor. The name then appears in the main menu.

  1. From the home screen, select Settings.
  2. Select Name for heating circuit.
  3. Select Heating circuit 1, 2 or 3.
  4. Enter the name using the keypad.
  5. Confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 29. Written in our own words; check the manual for your exact model.

Natural gas to LPG conversion reference

Boiler · Vitocrossal 300 CA3B

Conversion from NG to LPG is covered by the conversion kit instructions.

  1. Refer to the installation instructions supplied with the conversion kit.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 55. Written in our own words; check the manual for your exact model.

nciNR2Config is not user accessible

Boiler · Versatronik 581 / 581D

The nciNR2Config register cannot be changed by the user. The gateway is preconfigured for 8 Vitotronic 300 GW6B boilers and 3 zones.

Applies to: Versatronik 581 gateway firmware V1.1

Source: Versatronik 581 LON gateway manual, p. 13. Written in our own words; check the manual for your exact model.

Neutralizing unit in condensing system layouts

Boiler · Vitotronic 300 GW2

System types 3, 4 and 5 show a neutralizing unit in the boiler circuit. Include it in the installation as shown in the diagram.

  1. Locate the neutralizing unit in the layout shown for the system type.
  2. Confirm the installation matches the circuit diagram before commissioning.

Applies to: Vitocrossal 300 and Vitocrossal 200 condensing systems

Source: Vitotronic 300 GW2 installation and service instructions, p. 12, 14, 16. Written in our own words; check the manual for your exact model.

Never run boiler without venting

Boiler · Vitodens 200-W B2HA

The boiler must never run without an installed venting system. An improper vent can cause carbon monoxide poisoning. All combustion products must be vented outdoors.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 2. Written in our own words; check the manual for your exact model.

Never run the boiler without a complete venting system

Boiler · Vitorond 200 VD2

Improper venting can cause carbon monoxide poisoning. All combustion products must be vented safely outdoors. Check the Venting Information section for venting and chimney requirements.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200 VD2 Service Instructions, p. 2. Written in our own words; check the manual for your exact model.

Never run the boiler without a venting system

Boiler · Vitorond 200 VD2A

The boiler must never operate without an installed venting system. An improper vent can cause carbon monoxide poisoning. All products of combustion must be vented to the outdoors.

  1. Verify the venting system is installed and complete before firing the boiler.
  2. Confirm all combustion products exit to outdoors.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Installation Instructions, p. 2. Written in our own words; check the manual for your exact model.

Never run the boiler without venting

Boiler · Vitocrossal 200 CI2

Carbon monoxide from a missing or faulty vent can poison occupants.

  1. Do not operate the boiler unless the venting system is installed.
  2. Confirm all combustion products vent safely to the outdoors.
  3. Check the venting section of the manual for venting and chimney requirements.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 2. Written in our own words; check the manual for your exact model.

No batteries in the programming unit

Boiler · Vitotrol 200A

The remote control is powered by the control unit. Do not insert batteries into the programming unit.

Applies to: Vitotrol 200A

Source: Vitotrol 200A installation, operating and service instructions, p. 7. Written in our own words; check the manual for your exact model.

No frost protection when aBA is used as a safety switch-off

Boiler · Vitotronic 300

Switch-off through the aBA terminals stops the boiler and leaves the system without frost protection.

  1. Use the aBA terminals for safety switch-off only, for example through a high limit thermostat.
  2. Warn the owner that the heating system is not frost protected while the boiler is blocked.

Applies to: Vitotronic 300 GW6B

Source: Vitotronic 300, GW6B installation and service instructions, p. 38. Written in our own words; check the manual for your exact model.

No user serviceable parts

Boiler · Vitotronic 100

There are no user serviceable parts on the boiler, burner or control. Only a licensed professional heating contractor may install, adjust, service or maintain the equipment.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 5. Written in our own words; check the manual for your exact model.

No user-serviceable parts

Boiler · Vitocrossal 300 CA3B

The end user must not perform service work on the boiler, burners or controls.

  1. Only a qualified heating contractor should service the boiler, burners or control.
  2. Owner checks only as listed in the service schedule.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Non-Viessmann DHW tank and tempering valve

Boiler · Vitocrossal 300 CU3A

Requirements for a DHW tank that is not a Viessmann tank.

  1. If the DHW tank is not a Viessmann Vitocell 100 or 300, verify the DHW tank temperature sensor with the tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line, as Viessmann strongly recommends.

Applies to: Vitocrossal 300 CU3A DHW systems

Source: Vitocrossal 300 CU3A technical data manual, p. 26. Written in our own words; check the manual for your exact model.

Non-Viessmann DHW tank applications

Boiler · Vitodens 200-W B2HA

Non-Viessmann tanks need extra checks for sensor operation and coil flow.

  1. Verify the Viessmann DHW sensor works with the original tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.
  3. Size the DHW coil pressure drop against the field pump residual head to keep flow to the boiler heat exchanger.
  4. Keep DHW piping between boiler and tank connections at least 1¼ in.; undersized piping can cause short-cycling and poor DHW supply.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 32. Written in our own words; check the manual for your exact model.

Non-Viessmann DHW tank requirements

Boiler · Vitodens 200-W

If a DHW tank other than a Viessmann Vitocell 100 or 300 is used, the installer must confirm the Viessmann DHW tank sensor works correctly with the tank manufacturer. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. Verify the Viessmann DHW tank sensor with the original tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

Applies to: Vitodens 200-W B2HB with non-Viessmann DHW tanks

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 32. Written in our own words; check the manual for your exact model.

Not a safety control and no user-serviceable parts

Boiler · Versatronik COMO OT

The room controller is not a safety control. Only licensed or qualified heating contractors should install, adjust, service or maintain it. There are no user-serviceable parts inside.

Applies to: Versatronik COMO OT room controller

Source: Versatronik COMO OT installation and operating manual, p. 1 and p. 4. Written in our own words; check the manual for your exact model.

Nozzles that must be installed by the installer

Boiler · Vitorond 100 VR1

For VR1 27, 105 with Riello direct vent, the installed nozzle must be replaced with the nozzle packaged with the burner. The 0.60x60°W nozzle is installer-installed. For VR1 33, 140 the 0.85x60°W nozzle is factory installed.

Applies to: Riello direct vent burners

Source: Vitorond 100 VR1 technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Offline boiler timeout and zero values

Boiler · Versatronik 585

If a boiler sends no data for 10 minutes, the gateway treats it as offline and reports zero for all its points. This applies to LON communication only, not KMK.

  1. If a boiler reports 0 degrees for boiler water temperature, the gateway skips all other points for that boiler.
  2. Check that boiler is connected and powered if it reports zeros for all its points.

Applies to: Versatronik 585 VI/BACIP

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 15. Written in our own words; check the manual for your exact model.

Oil appliance draft requirement

Boiler · Vitorond 100 VR1

Oil-fired appliances must always connect to vents with enough draft for safe, proper operation.

Applies to: VR1 22 to 33, 91 to 140

Source: Vitorond 100 installation and service manual, p. 14. Written in our own words; check the manual for your exact model.

Oil burner start-up safety checks

Boiler · Vitorond 100

Warnings to follow before lighting the burner.

  1. Do not use gasoline, crankcase drainings or any oil containing gasoline.
  2. Do not start the burner unless the combustion chamber door is secured in place.
  3. Do not attempt to start the burner when excess oil has accumulated, the unit is full of vapor, or the combustion chamber is very hot.
  4. Do not fire the boiler without water.
  5. Do not leave tools inside the combustion chamber.
  6. Never burn garbage or paper in the unit.

Applies to: All VR1 models

Source: Vitorond 100 installation and service manual, p. 40, p. 48. Written in our own words; check the manual for your exact model.

Oil pump set-up for single-line or two-line fuel supply

Boiler · Vitorond 100

The burner ships set for single-line operation with no oil pump changes needed. For two-line systems, the bypass plug must be installed.

  1. Leave the oil pump as shipped for single-line systems.
  2. For a two-line system, install the bypass plug in the oil pump.

Applies to: Oil pump on the burner

Source: Vitorond 100 VR1 installation and service manual, p. 26 and p. 28. Written in our own words; check the manual for your exact model.

On-board Vitotronic 200 controls and tools

Boiler · Vitodens 200-W, B2HB

The HO1B control is built into the boiler. The standard unit has the ON/OFF switch, Optolink interface, operating and fault indicators, reset button and fuses. The programming unit has the display and keys and can be wall mounted with an accessory.

  1. Use the programming unit display and keys to set room temp, DHW temp, heating programs, time programs, economy and party modes, holiday program, heating curves, codes, actuator tests and test mode.
  2. Use the Optolink port for laptop access.
  3. Use the reset button on the standard unit for resets.
  4. Check fuses on the standard unit when troubleshooting power.

Applies to: Vitotronic 200 HO1B

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 22. Written in our own words; check the manual for your exact model.

One function per connection

Boiler · Vitodens 200-W B2HA

Each connection on the wiring diagram can carry only one function or accessory.

  1. Assign only one function or accessory to each connection.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 88. Written in our own words; check the manual for your exact model.

One-off DHW heating outside the time program

Boiler · Vitocontrol-S, VD2/CT3/CM2

Starts domestic water heating for a single period outside the programmed phases.

  1. Press the DHW button twice, 2 to 3 seconds apart.

Applies to: Domestic hot water

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Open the main menu from any screen

Boiler · Vitotronic 300-K

The main menu holds the boiler sequence, all cascade settings such as heating defaults and time programs, and the scanning functions.

  1. If the screensaver is active, tap the screen and then tap Menu.
  2. From any menu level, tap the menu button in the footer and then tap Menu.

Applies to: Vitotronic 300-K cascade control programming unit

Source: Vitotronic 300-K MW2C operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Open the Vitotronic 200 KW6B control

Boiler · Vitocrossal 300 CU3A

Access the control and power it up for start-up.

  1. Lift the programming unit to the upright position.
  2. Adjust the angle with the side push button if needed.
  3. Open the control cover.
  4. Switch the on/off switch to on.

Applies to: Vitotronic 200 KW6B

Source: Vitocrossal 300 CU3A service instructions, p. 12. Written in our own words; check the manual for your exact model.

Opening the control

Boiler · Vitotronic 100

The control cover is opened from the front and the top cover is unlocked with a screwdriver.

  1. Open the front cover.
  2. Carefully unlock the control top cover with a screwdriver.
  3. Flip the top cover open to reach the control PCB.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 9. Written in our own words; check the manual for your exact model.

Opening the control unit

Boiler · Vitotronic 100 GC1

Access the inside of the Vitotronic 100 control unit.

  1. Remove the cover of the connection enclosure.
  2. Unscrew the screws from the front housing.
  3. Swing up the front part of the control housing.
  4. Position the stay bar so it supports the front housing.

Applies to: Vitotronic 100 GC1

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 55. Written in our own words; check the manual for your exact model.

Opening the Vitotronic control unit

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

Procedure to open the control unit housing for service access.

  1. Remove the cover of the connection enclosure.
  2. Unscrew the screws from the front housing.
  3. Swing up the front part of the control housing.
  4. Position the stay bar so it supports the front housing.

Applies to: Vitotronic 100 and Vitocontrol-S control units

Source: Viessmann Vitotronic 100 / Vitocontrol-S installation and service instructions, p. 89. Written in our own words; check the manual for your exact model.

Operating modes for central heating

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

The contractor sets one of two modes during commissioning. In weather-compensated operation, supply water temperature follows outside temperature, so colder days get higher supply temperature. In constant operation, the boiler holds a fixed supply temperature regardless of outside temperature.

  1. Confirm with the contractor which mode the system uses before changing heating settings.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Operating modes set by the installer

Boiler · Vitodens 100-W B1HE/B1KE

The control unit runs in weather-compensated or constant operation. The heating contractor sets the mode during commissioning.

  1. Weather-compensated: supply water temperature follows outside temperature, so colder weather gives a higher supply temperature.
  2. Constant: the boiler holds a fixed supply water temperature regardless of outside temperature.
  3. Confirm the configured mode with the commissioning record before changing settings.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Viessmann Vitodens 100-W B1HE/B1KE operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Operating program choices

Boiler · Vitotronic 300-K

The operating program sets what the system heats. Options are central heating with DHW, DHW only with no central heating, or frost protection only for the boiler and DHW tank with no central heating and no DHW. There is no operating program for central heating without DHW, because central heating normally runs together with DHW in winter mode.

Applies to: Operating program setting

Source: Vitotronic 300-K, MW2C operating instructions, p. 33. Written in our own words; check the manual for your exact model.

Operating program options

Boiler · Vitocrossal 300 CA3B

The operating program defines whether the boiler heats the central heating and DHW, only DHW, or only provides frost protection. No program provides central heating without DHW.

  1. Select central heating and DHW for winter operation.
  2. Select DHW only for summer operation to keep DHW running with central heating off.
  3. Select frost protection only to keep the boiler and DHW tank protected with no heating or DHW.

Applies to: Vitotronic 300 GW6C control

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 42. Written in our own words; check the manual for your exact model.

Operating program selection

Boiler · Vitocrossal 300 CA3B Dual Fuel

Choose DHW only (central heating off, DHW still heated, summer use) or Heating and DHW.

  1. Go to Menu > Heating > required heating circuit > Operating program.
  2. Select DHW only or Heating and DHW.
  3. Press OK to confirm.
  4. In DHW only, frost protection for the boiler and DHW tank stays enabled. Standby mode also keeps frost protection active.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 24, 28. Written in our own words; check the manual for your exact model.

Operating program selection for summer and standby

Boiler · Vitocrossal 300 CA3B

Use DHW only mode in warm months, or standby mode when neither heat nor hot water is needed for long periods.

  1. Select the DHW only operating program to keep hot water on with central heating off.
  2. Select standby mode when heating and DHW are not needed for long periods.

Applies to: Vitocrossal 300 CA3B, all sizes 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 13. Written in our own words; check the manual for your exact model.

Operating programs for DHW and standby

Boiler · Vitocrossal 300 CA3B Dual Fuel

Summer mode uses the DHW only program, so the boiler heats domestic hot water but not the central heating. Standby mode is for long periods without heat or hot water needs. Holiday program lowers room temperature and turns off DHW.

  1. Select DHW only for summer hot water with no heating.
  2. Select Standby mode for long periods with no heating or hot water.
  3. Select the holiday program when away to reduce room temperature and turn off DHW.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 13, 44. Written in our own words; check the manual for your exact model.

Operating status: standard and reduced heating

Boiler · Vitotrol 300A

In the Heating and DHW program the operating status switches between standard and reduced heating mode.

  1. Standard heating mode: rooms are heated to the standard room temperature during the times set in the central heating time program.
  2. Reduced heating mode (setback): rooms are heated to the reduced room temperature when out or at night, during the times set in the central heating time program.

Applies to: Vitotrol 300A

Source: Vitotrol 300A Remote Control Operating Instructions, p. 27. Written in our own words; check the manual for your exact model.

Operating status: standard and reduced heating mode

Boiler · Vitotronic 300-K, Vitotronic 200

In the 'Heating and DHW' program, the control switches between standard heating mode (rooms at standard room temperature) and reduced heating mode (setback to reduced room temperature). The switch times come from the central heating time program. Standard mode is used when occupied, and reduced mode when away or at night.

  1. Set the standard room temperature for occupied periods.
  2. Set the reduced room temperature for away or night periods.
  3. Set the central heating time program to define when each mode runs.

Applies to: Vitotronic 200 and 300-K heating circuits

Source: Vitotronic 200 and 300-K Operating Instructions, p. 43. Written in our own words; check the manual for your exact model.

Order parts with the boiler serial number

Boiler · Vitodens 222-F

When ordering replacement parts, give the 16-digit boiler serial number from the barcode label, or the 12-digit ASME/NB serial. Both are under the front enclosure panel.

  1. Remove the front enclosure panel to reach the serial number labels.
  2. Record the 16-digit serial number or the 12-digit ASME/NB serial number before ordering parts.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Ordering parts: serial number

Boiler · Vitodens 200-W B2HB

Parts orders need the 16-digit serial number on the barcode label, or the 12-digit ASME/NB serial number. Both are behind the front enclosure panel. Some parts are not reverse compatible with earlier Vitodens 200-W B2HB versions.

  1. Remove the front enclosure panel to read the serial number.
  2. Give the 16-digit barcode serial or the 12-digit ASME/NB serial when ordering.
  3. Confirm the part works with the boiler serial before ordering.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Ordering parts: serial number needed

Boiler · Vitodens 200-W B2HA

Replacement parts must be ordered with the boiler serial number. Some parts are not reverse compatible with earlier B2HA versions. Use either the 16-digit serial on the barcode label or the 12-digit ASME/NB serial, found under the front enclosure panel. Serial numbers printed on the page: B2HA 112 and 399 are 7510835 and 7550393; B2HA 150 and 530 are 7510836 and 7550394.

  1. Remove the front enclosure panel to find the ASME/NB serial (see the front panel removal steps).
  2. Quote the 16-digit barcode serial or the 12-digit ASME/NB serial when ordering parts.

Applies to: Models 112, 150, 399, 530

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 9. Written in our own words; check the manual for your exact model.

Ordering replacement parts

Boiler · Vitocrossal 200 CI2

Have the model and serial number from the CSA rating plate ready before ordering. Order parts through a Viessmann distributor.

  1. Read the model and serial number from the CSA rating plate (plate A).
  2. Order replacement components from your Viessmann distributor.

Applies to: Vitocrossal 200 CI2 all sizes

Source: Vitocrossal 200 CI2 Service Instructions, p. 109. Written in our own words; check the manual for your exact model.

Ordering replacement parts for the control unit

Boiler · Vitotronic 300 GW2

Parts orders need the model and serial number from the rating plate. The serial number is a 16-digit bar-coded number on the front housing, below the flip-down cover.

  1. Read the model and serial number from the rating plate.
  2. Find the serial number on the front housing, below the flip-down cover.
  3. Order replacement components through a Viessmann distributor.

Applies to: Vitotronic 300 GW2 replacement parts

Source: Vitotronic 300 Installation and Service Instructions, p. 141. Written in our own words; check the manual for your exact model.

Ordering replacement parts needs the serial number

Boiler · Vitodens 200-W B2HB

Always give the 16-digit boiler serial number (bar code label) or the 12-digit ASME/NB serial number when ordering parts. Some parts are not reverse compatible with earlier B2HB versions.

  1. Find the serial number under the front enclosure panel.
  2. Quote the 16-digit or 12-digit serial number with the model when ordering.
  3. Check parts compatibility before fitting a part to an earlier B2HB unit.

Applies to: All Vitodens 200-W B2HB models

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Outdoor and DHW temperature sensor connections

Boiler · Vitodens 200-W B2HB

The outdoor temperature sensor and the DHW temperature sensor connect to the control base. For the connection to the external accessory connection box, see the wiring diagram on page 47.

  1. Connect the outdoor temperature sensor to the control base.
  2. Connect the DHW temperature sensor to the control base.
  3. Refer to the wiring diagram on p. 47 for the accessory connection box.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 26. Written in our own words; check the manual for your exact model.

Outdoor reset and energy management override restrictions

Boiler · Vitorond 100 VR1

The Hydrostat boiler control has an override intended for use with an external energy management system. It may only be used when one of the listed conditions is true.

  1. Use the override only if an external energy management system lowers boiler water temperature as heating load drops.
  2. Or use it only if the boiler is not used for space heating.
  3. Or use it only if the boiler is part of a modular or multiple boiler system with 300,000 BTU/h total input or more.
  4. Or use it only if the boiler has a tankless coil.

Applies to: Hydrostat control on Vitorond 100 VR1 boilers

Source: Vitorond 100 VR1 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.

Outdoor reset override restrictions

Boiler · Vitorond 100

The outdoor reset energy saving feature has an override meant mainly for an external energy management system. The override may only be used if one of the listed conditions is true.

  1. Use the override only if an external energy management system lowers boiler water temperature as heating load falls.
  2. Or use it only if the boiler is not used for any space heating.
  3. Or use it only if the boiler is part of a modular or multiple boiler system with total input of 300,000 Btu/h or more.
  4. Or use it only if the boiler is equipped with a tankless coil.

Applies to: Vitorond 100 with Hydrostat or outdoor reset module

Source: Viessmann Vitorond 100 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.

Outdoor reset override use limits

Boiler · Vitorond 100

The outdoor reset override is meant for an external energy management system. Use it only when one of the listed conditions applies.

  1. Use the override only if an external energy management system lowers boiler water temperature as the load drops.
  2. Or use it only if the boiler is not used for space heating.
  3. Or use it only if the boiler is part of a modular or multiple boiler system with 300,000 Btu/h total input or more.
  4. Or use it only if the boiler has a tankless coil.

Applies to: Vitorond 100 with Hydrostat outdoor reset

Source: Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Outdoor reset override: when it may be used

Boiler · Vitorond 100 VR1

The outdoor reset override is only for use when one of these is true: an external energy management system lowers boiler water temperature as load drops; the boiler is not used for space heating; the boiler is part of a modular or multiple boiler system of 300,000 BTU/h or more; or the boiler has a tankless coil.

Applies to: VR1 22 to 33, 91 to 140

Source: Vitorond 100 installation and service manual, p. 8. Written in our own words; check the manual for your exact model.

Outdoor reset pump behaviour at low outdoor temperature

Boiler · Vitotronic 100

With an outdoor sensor and internal outdoor reset or OpenTherm thermostat, the control starts calculating boiler water temperature at 37°F (3°C) outdoor and below. The boiler pump then runs continuously.

  1. Confirm the outdoor sensor is connected before testing outdoor reset.
  2. Expect the boiler pump to run continuously when outdoor temperature is 37°F (3°C) or below.

Applies to: Vitotronic 100 KW10B with outdoor sensor

Source: Vitotronic 100 KW10B installation manual, p. 11. Written in our own words; check the manual for your exact model.

Outdoor sensor wiring can pick up interference

Boiler · Vitocontrol-S VD2/CT3/CM2

Extending the outdoor sensor wire can expose it to electromagnetic interference. Keep the wire away from high voltage conductors and shield it correctly.

  1. Do not run sensor wires beside or near 120/240 VAC conductors.
  2. If that cannot be avoided, use stranded, twisted pair or shielded wire.
  3. Ground only one end of the shield.

Applies to: Outdoor temperature sensor wiring

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 78. Written in our own words; check the manual for your exact model.

Output aBJ function

Boiler · Vitodens 200-W B2HA

Output aBJ can run either the DHW recirculation pump or the fault message facility. The function is selected with coding address 36 in the General group.

  1. Select the output function with coding address 36 at the boiler control unit.

Applies to: Output aBJ on EA1

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 84. Written in our own words; check the manual for your exact model.

Overheating or gas supply fails to shut off

Boiler · Vitocrossal 200 CM2

Do not cut power to the pump in this case.

  1. Do not disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location outside the appliance.

Applies to: All CM2 models

Source: Vitocrossal 200 CM2 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Overheating or gas valve fails to close

Boiler · Vitocrossal 300 CA3B

If the boiler overheats or the gas supply does not shut off, the circulating pump must keep its power.

  1. Do not disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location outside the appliance.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Overheating or gas valve failure

Boiler · Vitotronic 200, Vitotronic 300-K

If the boiler overheats or the gas supply does not shut off, do not disconnect the electrical supply to the pump. Shut off the gas supply at a point outside the appliance instead.

  1. Do not switch off power to the circulating pump.
  2. Shut off the gas supply at a location outside the appliance.
  3. Close the main gas supply valve if there is a dangerous condition, and deactivate main power.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 5, 6. Written in our own words; check the manual for your exact model.

Overheating or gas will not shut off

Boiler · Vitocrossal 300 CU3A

If the boiler overheats or the gas supply does not shut off, do not cut power to the circulating pump. Shut off the gas at a point outside the appliance.

  1. Do not disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location outside the appliance.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Override switch positions

Boiler · Vitotronic 100

Up turns the boiler pump on, enables stage 1 and 2 calls for heat, and runs the boiler on the adjustable high limit. Down is normal operation.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B operating manual, p. 5. Written in our own words; check the manual for your exact model.

Owner checks and annual service

Boiler · Vitocrossal 200 CI2

Owner-level checks and the required service interval. The end user must not adjust or service boiler components.

  1. Check system (water) pressure on the gauge regularly.
  2. Look for water on the floor from the pressure relief valve discharge, pipes, joints, valves or air vents.
  3. Have the boiler, burner and controls checked at least once a year by a qualified heating contractor.
  4. Correct any defects immediately.
  5. Do not allow unsupervised children near the boiler.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 operating instructions, p. 2, 6. Written in our own words; check the manual for your exact model.

Owner checks between services

Boiler · Vitocrossal 300 CU3A

Items the owner should check regularly. Blocked venting is a carbon monoxide risk. Any blockage must be removed by a qualified heating contractor.

  1. Check that the vent or chimney is not blocked or partly blocked.
  2. Check the system water pressure on the pressure gauge.
  3. Check for water on the floor from the relief valve discharge or any pipe, joint, valve or air vent.
  4. Check flue pipes, joints, vent dampers and side wall terminals for moisture, water or rust.
  5. Make sure nothing blocks combustion and ventilation air and that no chemicals, gasoline or flammable materials are stored near the boiler.
  6. Keep unsupervised children away from the boiler.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Owner maintenance and service interval

Boiler · Vitocrossal 300 CA3B Dual Fuel

Only a qualified heating contractor should service the boiler, burners and controls. Soot build-up on the heat exchanger lowers efficiency and raises flue gas temperature. Indirect-fired DHW storage tanks must be serviced within two years of installation and regularly after that. The owner or dedicated staff should do the checks in the Service Schedule (p. 41).

  1. Have a qualified heating contractor service the system regularly.
  2. Service indirect-fired DHW tanks within two years of installation, then regularly.
  3. Owner checks the items listed in the Service Schedule on p. 41.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Oxygen diffusion barrier tubing

Boiler · Vitorond 100 VR1

Underfloor plastic tubing without an oxygen diffusion barrier causes corrosion. The warranty does not cover resulting leaks.

  1. Separate non-barrier underfloor tubing from the boiler with a heat exchanger.
  2. Use oxygen diffusion barrier tubing where possible.

Applies to: Underfloor heating loops

Source: Vitorond 100, VR1 Technical Data, p. 11. Written in our own words; check the manual for your exact model.

Parameter R62 after a flame loss

Boiler · Vitocrossal 200 CM2

After a fail of flame during operation the burner cannot modulate at partial load (20%) for one hour. During this time the minimum input for R62 is 50 to 60%. Standby before the hour is up does not clear the setting.

  1. To clear the one hour lockout early, press the reset button or switch the burner control off.

Applies to: Vitocrossal 200 CM2 burner control unit

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 44. Written in our own words; check the manual for your exact model.

Parameter settings reference

Boiler · Vitocrossal 200 CI2

Parameter settings for CAI, changeover contact and 0-10V are set in the Service Instructions or system configuration.

  1. Refer to the Service Instructions for parameter settings.

Applies to: Parameters 1706.0 and CAI feedback

Source: Vitocrossal 200 CI2 Installation Instructions, p. 25. Written in our own words; check the manual for your exact model.

Parameters shown with no function

Boiler · Vitocrossal 200 CI2

These parameters appear on the display but do nothing on this boiler. Do not expect a change from them.

Applies to: Vitocrossal 200 CI2 control unit

Source: Vitocrossal 200 CI2 Service Instructions, p. 54. Written in our own words; check the manual for your exact model.

Parts list for ordering

Boiler · Vitorond 100

Provide the boiler model and serial number from the rating plate when ordering. Order from your Viessmann distributor.

  1. Use the reference numbers below when identifying parts.

Applies to: Vitorond 100 VR1 replacement parts

Source: Vitorond 100, VR1 installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

Parts ordering information

Boiler · Vitodens 200-W B2HA

Parts must be ordered from the Viessmann distributor using the model number from the rating plate and the serial number.

  1. Get the model number from the rating plate.
  2. Get the serial number.
  3. Order the parts from your Viessmann distributor.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 90. Written in our own words; check the manual for your exact model.

Parts to keep on hand for service calls

Boiler · Vitorond 200 VD2

Stock these items for every service call. Full parts list is in the Parts List section.

  1. Carry O-rings for the mixing valve(s).
  2. Carry sealant rope for the combustion chamber door.
  3. Carry refractory for the combustion chamber door.
  4. Carry sealant rope for the clean-out opening cover.
  5. Carry glue for the sealant rope.

Applies to: All VD2 sizes 320 to 1080

Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Party mode (comfort function)

Boiler · Vitotronic 300-K, Vitotronic 200

Raises room temperature for several hours without changing the normal control settings. DHW is also reheated to its set temperature and the DHW circulation pump runs if installed.

  1. Open the extended menu and select Heating.
  2. Select the heating circuit if needed.
  3. Select Party mode.
  4. Set the room temperature for party mode.
  5. To end early, set Party mode to OFF.
  6. Party mode also ends automatically when the time program switches to standard heating mode.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 20. Written in our own words; check the manual for your exact model.

PC connection with ComfortSoft

Boiler · Versatronik 200

ComfortSoft parameterisation software sets and reads all system parameters on a PC, and can graph and log values at set intervals. CoCo PC is needed for SMS error messages and remote reading of controller data.

Applies to: Versatronik 200 System Control

Source: Versatronik 200 installation and operating manual, p. 62. Written in our own words; check the manual for your exact model.

Pipe clearance to combustible construction

Boiler · Vitodens 200-W B2HB

Non-insulated hot water pipes need a set clearance from combustible construction. Insulated pipes may use less clearance if the insulation is adequate.

  1. Keep at least 2 in. (51 mm) all around non-insulated hot water pipes from combustible construction.
  2. Insulated pipes may use 0 in. only if the insulation thickness and value are adequate.
  3. Confirm any reduced clearance against local gas codes.

Applies to: Hot water piping near combustible construction

Source: Vitodens 200-W B2HB installation instructions, p. 32. Written in our own words; check the manual for your exact model.

Piping for the high-mass CU3A

Boiler · Vitocrossal 300 CU3A

A high-mass boiler does not need primary/secondary piping.

Applies to: Vitocrossal CU3A, all applications

Source: Vitocrossal 300 CU3A application guide, p. 26. Written in our own words; check the manual for your exact model.

Piping layouts are conceptual only

Boiler · Vitocrossal 200 CI2

The schematics in this section are guidelines and do not show every system or safety device. Pumps shown are field supplied. Piping and components must be field verified. A low water cut-off (LWCO) is required where local codes call for it. The heating contractor is responsible for correct installation and function in the field.

  1. Verify all piping and components in the field.
  2. Install a low water cut-off where local codes require it.
  3. Confirm all pumps, which are field supplied, are sized and installed correctly.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 41. Written in our own words; check the manual for your exact model.

Plug-in terminals are live when replacing the coding card

Boiler · Vitocrossal 300 CA3B Dual Fuel

The plug-in terminals on the burner control unit stay live. Only swap the coding card after power to the burner control unit has been isolated.

  1. Isolate power to the burner control unit using the internal power disconnect inside the GW6C.
  2. Replace the coding card only after power is off.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel service instructions, p. 28. Written in our own words; check the manual for your exact model.

Potable water filter service

Boiler · Vitocrossal 300 CA3B

Filter service interval depends on filter type. Maintain high hygiene standards.

  1. On non-back-flushing filters, replace the filter element every six months and visually inspect every two months.
  2. On back-flushing filters, back flush every two months.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B operating instructions, p. 41. Written in our own words; check the manual for your exact model.

Power failure and saved data

Boiler · Vitotronic 300-K MW1B

Control settings survive a power outage.

  1. No action needed. All data is saved if there is a power failure.

Applies to: Vitotronic 300-K MW1B

Source: Viessmann Vitotronic 100 GC1B / 300-K MW1B operating instructions, p. 3. Written in our own words; check the manual for your exact model.

Power failure and seasonal changeover

Boiler · Vitotrol 300A

Settings are kept during a power failure, and the winter/summertime changeover happens automatically.

Applies to: Vitotrol 300A

Source: Vitotrol 300A operating instructions, p. 4. Written in our own words; check the manual for your exact model.

Power isolation before servicing

Boiler · Versatronik 502 & 502D

More than one live circuit can be present. Contact with live electrical parts can cause serious injury or death.

  1. Turn off the power supply to the control and to the damper/blower before servicing.
  2. Check the wiring diagram in the manual before working inside the unit.

Applies to: Versatronik 502 and 502D

Source: Versatronik 502 NR2 Modbus manual, p. 3. Written in our own words; check the manual for your exact model.

Power off before servicing

Boiler · Versatronik 585, Versatronik 585D

The unit has more than one live circuit. Turn off power to the control and to any damper or blower before servicing. Contact with live parts can cause serious injury or death. The gateway has no user-serviceable parts, and work must be done by a qualified heating contractor. Electrostatic discharge can damage the boards.

  1. Shut off power to the boiler control and any damper or blower.
  2. Check the wiring diagram in the manual before working on live circuits.
  3. Use static precautions when handling the control.

Applies to: Versatronik 585 and 585D

Source: Versatronik 585 and 585D BACnet IP gateway manual, pp. 2-3. Written in our own words; check the manual for your exact model.

Power off before servicing; no user-serviceable parts

Boiler · Versatronik 501, Versatronik 501D

The unit has more than one live circuit. Turn off power to the control and the damper/blower before servicing. The control has no user-serviceable parts, and work should be done by a qualified heating contractor.

  1. Switch off power to the control and the damper/blower before opening the unit.
  2. Check that all circuits are dead before working inside.

Applies to: Versatronik 501 and 501D gateways

Source: Versatronik 501 & 501D LON gateway manual, p. 3. Written in our own words; check the manual for your exact model.

Power Pump Module wiring and supply protection

Boiler · Vitotronic 200

Power supply must have overcurrent protection rated at most 15 A with a disconnect. The equipment must be grounded. Do not interchange the line, neutral and ground wires. Do not connect external equipment directly to the 120 VAC connectors; they are interface connections to the Power Pump Module only. Pump outputs are 120 VAC, 1 phase, 3 A max each; mixing valve motor is optional.

  1. Confirm the supply has max 15 A overcurrent protection and a disconnect.
  2. Ground the module.
  3. Check L, N and G are not swapped.
  4. Wire circulating pumps and the mixing valve motor to their marked terminals only.

Applies to: Vitotronic 200 KW2 with Power Pump Module

Source: Vitotronic 200 Service Instructions, p. 61. Written in our own words; check the manual for your exact model.

Power supply and pump interface connection

Boiler · Vitocrossal 300

Electrical work must meet the code in force where the boiler is installed. Ground the appliance and bond the pipework to the building's equipotential bonding.

  1. Connect the boiler power supply at the power/pump connection interface.
  2. Refer to the wiring diagram on page 57 for connection to the control base.
  3. Bond the appliance and pipework to the building equipotential bonding.
  4. Follow NEC/ANSI NFPA 70 and local codes in the U.S.A., or CEC CSA C22.1 Part 1 and local codes in Canada.

Applies to: Vitocrossal 300 CU3A boiler power supply

Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 41. Written in our own words; check the manual for your exact model.

Power supply connection

Boiler · Vitotronic 100

The control uses a 3-prong molded plug on a 120 VAC, 60 Hz supply. The receptacle must be dedicated to the heating system.

  1. Feed the power cord through the rear top panel wiring gate of the boiler.
  2. Slide the cable into the strain relief and tighten the set screw.
  3. Plug the cord into a receptacle reserved for the heating system only.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 12. Written in our own words; check the manual for your exact model.

Power supply connection checks

Boiler · Vitodens 200-W B2HA

The external accessories box needs 120 VAC from a 15 A fuse-protected receptacle. Line and neutral must not be swapped, and a neutral conductor is required.

  1. Confirm 120 VAC at connector 40 on the boiler control (see wiring diagram, page 86).
  2. Confirm the supply has a neutral conductor.
  3. Do not interchange L (line) and N (neutral).
  4. Wire in Canada to CSA C22.1 Part 1 and local codes; in the U.S. use NEC ANSI/NFPA 70 and ANSI/ASME CSD-1.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 15. Written in our own words; check the manual for your exact model.

Power supply for accessories and mixing controls

Boiler · Vitodens 200-W B2HB

Accessories can be powered directly from the control, and they switch with the system on/off switch. The Vitotronic 200-H HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control each need their own 120 VAC supply from a wall receptacle. The programming unit can also be used in a wall-mount base accessory near the boiler.

  1. Power accessories from the control, if they are rated for it, so they switch with the system on/off switch.
  2. Give the Vitotronic 200-H HK1B, mixing valve kit and Solartrol their own 120 VAC wall receptacle supply.
  3. Mount the programming unit in the optional wall base if it is needed near the boiler.

Applies to: Vitodens 200-W B2HB accessories

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 47. Written in our own words; check the manual for your exact model.

Power supply protection and disconnect

Boiler · Vitotronic 200-H

The 120 VAC supply needs overcurrent protection of no more than 15 A. Viessmann recommends a disconnect switch for this supply outside the boiler room. Follow local electrical code for any fuseable disconnect.

  1. Turn off power before servicing or wiring.
  2. Fit a maximum 15 A fuse or breaker on the 120 VAC supply.
  3. Recommended: place a disconnect switch on the 120 VAC supply outside the boiler room.
  4. Install the supply per local authority requirements, or CSA C22.1 Part 1 / NEC ANSI/NFPA 70 where no local code applies.

Applies to: Vitotronic 200-H control unit and power/pump module

Source: Vitotronic 200-H installation and service instructions, p. 5 and p. 8. Written in our own words; check the manual for your exact model.

Power supply to the control

Boiler · Vitotronic 100 GC1

The circuit diagrams show a 120 VAC, 60 Hz supply.

  1. Install the main isolator in accordance with local regulations.
  2. Use the supply connection as shown in the wiring diagram for the chosen system.

Applies to: All circuit diagrams

Source: Vitotronic 100 GC1 installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Power switch function

Boiler · Vitotronic 100

In the up position the control system is on. In the down position (0) the control system is off.

  1. Switch the power switch to 0 before opening the control or working on wiring.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 11. Written in our own words; check the manual for your exact model.

Power switch positions

Boiler · Vitotronic 100

Up (I) switches the control on. Down (0) switches the control off.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B operating manual, p. 5. Written in our own words; check the manual for your exact model.

Power-off and service rules

Boiler · Versatronik 503, NR2/Analog Bridge

Service and install work must be done by a licensed professional heating contractor. Fully isolate the electrical supply before servicing, since live components can cause shock or death. Add a disconnect switch on the 120 V supply outside the boiler room.

  1. Turn off the electric supply before any service work.
  2. Close the main gas supply valve.
  3. Lock or take other steps to stop accidental power-up during service.

Applies to: Versatronik 503 NR2/Analog Bridge

Source: Viessmann NR2/Analog Bridge installation manual, p. 4. Written in our own words; check the manual for your exact model.

Priority control during DHW tank heating

Boiler · Vitocrossal 200 CI2

With priority control on, the heating circuit target goes to 32°F (0°C) while the tank heats, the mixing valve closes and the circuit pump switches off. Without it, the circuit keeps its target. Priority is set per circuit with parameters 933.3, 934.3, 935.3 and 936.3.

Applies to: Heating circuits 1 to 4

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 88. Written in our own words; check the manual for your exact model.

Programming unit functions

Boiler · Vitotronic 200

Plug-in unit for setup and status viewing.

  1. Use it to set the heating program, setpoints, switching times, heating curve shift and slope, date, time, energy saving and party mode.
  2. Use it to read temperatures, operating status and faults.

Applies to: Programming unit

Source: Vitotronic 200 service instructions, p. 64. Written in our own words; check the manual for your exact model.

Programming unit placement

Boiler · Vitocrossal 300 CU3A

The programming unit is packed separately. It goes into the control unit support, or into an optional wall-mounting base near the boiler.

  1. Insert the programming unit into the control unit support.
  2. Or mount it in the optional wall-mounting base near the boiler.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A installation instructions, p. 56. Written in our own words; check the manual for your exact model.

Prolonged shutdown and clock reset

Boiler · Vitocrossal 300 CU3A

Circulation pumps can seize without power. After a prolonged or extended shutdown the date and time may need to be reset.

  1. Check the date and time after power is restored.
  2. Reset the date and time if needed (see the date and time section referenced in the manual).

Applies to: All operating programs

Source: Viessmann Vitocrossal 300 CU3A operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Protect building surfaces from flue products

Boiler · Vitocrossal 300 CU3A

Flue products can stain or damage nearby building materials in some climates. Shield exposed surfaces with corrosion-resistant material such as aluminum sheeting, attached and sealed to the building before the vent termination is installed. Vent termination on the leeward side of the building is strongly recommended.

  1. Shield or seal exposed building surfaces with corrosion-resistant material before installing the vent termination.
  2. Install the vent termination on the leeward side of the building.

Applies to: Vitocrossal 300 CU3A venting

Source: Vitocrossal 300 CU3A Installation Instructions, p. 53. Written in our own words; check the manual for your exact model.

Protect electronics and cable routing during install

Boiler · Vitodens 200-W B2HA

Keep connecting cables away from hot parts and discharge static before handling electronic modules.

  1. Route and secure cables so they stay below their maximum permissible temperature.
  2. Touch a grounded object, such as a heating or water pipe, before working on the electronic modules.
  3. Use the existing strain reliefs on the control base when securing cables.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 24. Written in our own words; check the manual for your exact model.

Protect electronics and cables during wiring

Boiler · Vitodens 200-W B2HB

Electronic modules can be damaged by electrostatic discharge. Cable temperature ratings must not be exceeded where cables run near hot components.

  1. Touch a grounded object, such as a heating or water pipe, before working to discharge static.
  2. Keep connecting cables away from hot components, which will damage them.
  3. Check that the cable temperature rating is not exceeded when routing and securing cables on site.
  4. Where larger cable is used, remove the existing cable grommet (up to 9/16 in.) and secure the cable with the grommet in the lower orange casing.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 24. Written in our own words; check the manual for your exact model.

Protect electronics from static discharge

Boiler · Vitocrossal 200 CM2

Electronic assemblies can be damaged by electrostatic discharge.

  1. Touch a grounded object, such as a heating or water pipe, before starting work on electronics.

Applies to: All Vitocrossal 200 CM2 units

Source: Vitocrossal 200 CM2 service instructions, p. 8. Written in our own words; check the manual for your exact model.

Protect internal components from static discharge

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

Static discharge can damage the internal electronics whenever the control is open.

  1. Discharge static from yourself before touching internal parts of an opened control.
  2. Avoid any static discharge to the internal components while the control is open.

Applies to: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 control unit

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 7. Written in our own words; check the manual for your exact model.

Protect piping against freezing when the building is unattended

Boiler · Vitodens 100-W B1HE/B1KE

The boiler is not designed to protect water pipes from freezing. If the boiler stays off in cold weather, pipes can freeze and burst.

  1. If the building will be empty in cold weather, shut off the water supply and drain the pipes.
  2. Add a potable-water antifreeze to drain traps and toilet tanks, and open faucets where appropriate.
  3. Alternatively, have someone check the building often or install a remote temperature sensor that alerts someone to freezing conditions.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Viessmann Vitodens 100-W B1HE/B1KE operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Protect the burner tube during service

Boiler · Vitodens 200-W

The burner tube is easily damaged and can cause improper operation.

  1. Do not lay the burner on its cylindrical tube.
  2. Do not touch the burner tube mesh.

Applies to: Vitodens 200-W B2HB 19 to 125

Source: Vitodens 200-W B2HB service instructions, p. 23. Written in our own words; check the manual for your exact model.

Protect the electronics from static discharge

Boiler · Vitotronic 300

Electronic assemblies can be damaged by static. Discharge yourself before work by touching a grounded object such as a heating or water pipe.

  1. Touch a grounded object such as a heating or water pipe before touching the PCB or assemblies.

Applies to: Vitotronic 300 GW6B control unit

Source: Vitotronic 300 GW6B Installation and Service Instructions, p. 21. Written in our own words; check the manual for your exact model.

Protect the gas ignition components from water

Boiler · Vitodens 100-W

Gas ignition system components must be protected from spray and splashing during boiler operation and service.

  1. Check that the gas ignition components are shielded from water before running the boiler.
  2. Keep them shielded during service work.

Applies to: All Vitodens 100-W boilers

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 8. Written in our own words; check the manual for your exact model.

Protect the heating system from high temperature

Boiler · Vitodens 100-W WB1B

Install the optional high limit safety control on heating circuit E when there are no automatic mixing valves or when DHW priority is not required.

  1. If the heating circuit has no automatic mixing valve, fit the optional high limit safety control on heating circuit E.
  2. Also fit it if DHW priority is not used.

Applies to: System layout 4 with high-temperature heating circuit

Source: Vitodens 100-W, WB1B installation manual, p. 43. Written in our own words; check the manual for your exact model.

Protect the top panel during piping and venting work

Boiler · Vitorond 100 VR1

Do not stand on the top panel of the boiler when installing piping or venting, or when insulating overhead pipes. Tell other trades.

Applies to: VR1 22 to 33, 91 to 140

Source: Vitorond 100 installation and service manual, p. 15. Written in our own words; check the manual for your exact model.

Provide proper combustion and ventilation air

Boiler · Vitorond 200 VD2

Installation must provide adequate combustion and ventilation air. Keep chemicals that can form harmful combustion by-products out of the boiler room. See the Mechanical Room section for the chemical list and air requirements.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200 VD2 Service Instructions, p. 2. Written in our own words; check the manual for your exact model.

Pump connection terminals in typical layout

Boiler · Vitotronic 100

In the typical one direct-connected heating circuit layout, the boiler/space heater pump connects to the pump connection (terminal 20, used with the listed boilers). The DHW pump connects to the DHW pump output (terminal 21). Boiler sensor, outdoor sensor and DHW sensor are also shown in this layout. Power is 120 VAC, 60 Hz.

Applies to: Vitotronic 100 KW10B typical layout (one direct-connected heating circuit without mixing valve)

Source: Vitotronic 100 KW10B installation manual, p. 8. Written in our own words; check the manual for your exact model.

Pump exercise function

Boiler · Vitocrossal 300 CA3B

Circulation pumps run for 10 seconds about once every 24 hours so they do not seize. This runs in all operating programs and during warm weather shutdown. Pumps can still seize during a long shutdown when they have no power, so the operator should reset the date and time after a prolonged shutdown.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Push-in DIN terminals in the junction box

Boiler · Vitotronic 300

The junction box uses push-in terminals. Press the orange button before inserting or removing a wire. Terminal wire size is 26 AWG minimum to 12 AWG maximum. Ferrules help stop stranded wires fraying.

  1. Press the orange push-in button before inserting or removing a wire.
  2. Use wire from 26 AWG to 12 AWG.
  3. Use a ferrule on stranded wire to prevent fraying.

Applies to: Vitotronic 300 GW6B junction box

Source: Vitotronic 300 GW6B Installation and Service Instructions, p. 24. Written in our own words; check the manual for your exact model.

Push-in terminal use for accessory wiring

Boiler · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The DIN rail accessory terminals are push-in type and must be opened before inserting or removing a wire.

  1. Push in the orange button next to the terminal before installing or removing a wire.
  2. Use solid, stranded or stranded with ferrule wire. A ferrule helps prevent stranded wire from fraying.
  3. Use the top L, N terminal for pre-wired harness connections and the bottom L, N, G terminals for external equipment such as pumps or mixing valves.

Applies to: Accessory connections on the DIN rail

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 21. Written in our own words; check the manual for your exact model.

Putting the control unit in maintenance position

Boiler · Vitodens 222-F

The control unit can be moved to a different position if it is needed for commissioning or servicing.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F B2TB service instructions, p. 81. Written in our own words; check the manual for your exact model.

Qualified contractor only

Boiler · Vitotronic 200, Vitotronic 300-K

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor. Owner or user must not service or adjust any part of the boiler, burner or control. The operator must have the boiler checked at least once a year, and defects must be fixed right away.

  1. Confirm the installer is a licensed heating contractor before any work.
  2. Leave all adjustments and repairs to the licensed contractor.
  3. Schedule an annual inspection before each heating season.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 2, 6. Written in our own words; check the manual for your exact model.

Quick heat-up and quick setback

Boiler · Vitotronic 200-H

Room set point changes of at least 2 K speed up heat-up or setback until the room reaches its new set point.

  1. For quick heat-up, raise the set room temperature by at least 2 K using party mode, a change from reduced to standard mode, or start optimisation (code B7).
  2. For quick setback, lower the set room temperature by at least 2 K using economy mode, a change from standard to reduced mode, or stop optimisation (code C1).
  3. Quick heat-up stops at the new set point; quick setback ends at the new set point.

Applies to: Vitotronic 200-H HK1B with remote control and room temperature hook-up

Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 41. Written in our own words; check the manual for your exact model.

Quick reference: Celsius to Fahrenheit conversion

Boiler · Vitotronic 200-H

The back page has a Celsius to Fahrenheit quick reference table running from -40 °C (-40 °F) to +110 °C (+230 °F). Sample pairs: -40 °C = -40 °F, -18 °C = 0 °F, 0 °C = +32 °F, +10 °C = +50 °F, +20 °C = +68 °F, +30 °C = +86 °F, +60 °C = +140 °F, +100 °C = +212 °F.

  1. Find the Celsius value in the left column and read the Fahrenheit value beside it.

Applies to: Vitotronic 200-H, HK1S and HK3S

Source: Vitotronic 200-H installation and service instructions, p. 76. Written in our own words; check the manual for your exact model.

Raise reduced room temperature based on outdoor temperature

Boiler · Vitodens 200-W B2HA

In reduced room temperature operation, the reduced setpoint can rise with outdoor temperature along the heating curve. It never goes above the standard room setpoint.

  1. Set the outdoor temperature at which raising starts in coding address F8.
  2. Set the outdoor temperature at which raising ends in coding address F9.
  3. Confirm the heating curve gives the expected room setpoint.

Applies to: Heating circuit control

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 85. Written in our own words; check the manual for your exact model.

Raising reduced room temperature by outdoor temperature

Boiler · Vitodens 200-W B2HB

During reduced room temperature operation the reduced setpoint can rise with outdoor temperature, following the heating curve, but never above the standard room setpoint.

  1. Set the outdoor temperature start limit for the raise at coding address F8.
  2. Set the outdoor temperature end limit for the raise at coding address F9.

Applies to: Heating circuit reduced mode

Source: Vitodens 200-W B2HB service instructions, p. 90. Written in our own words; check the manual for your exact model.

Reach the main menu

Boiler · Vitodens 100-W B1HE/B1KE

Start from the home screen. Every menu section (Heating, DHW, Faults, Information, Settings) is opened from the main menu. Some items only show on systems that have the matching feature, such as WiFi or a DHW recirculation pump.

  1. Tap the home screen to bring it up.
  2. Tap the menu button to open the main menu.
  3. Pick the section you need.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Read acknowledged fault messages

Boiler · Vitocrossal 300 CA3B Dual Fuel

When a fault occurs, the red fault display flashes and shows the symbol and Fault. A connected central fault message facility is also triggered.

  1. Open the Faults list from the control unit.
  2. Check the fault messages, which are shown in red in date order.
  3. For a fault explanation, see the fault messages section of the manual.

Applies to: Vitotronic control unit

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 121. Written in our own words; check the manual for your exact model.

Read boiler pressure and hot water temperature

Boiler · Vitodens 100-W WB1B

Water pressure is shown on an analog gauge. Hot water temperature is shown continuously during operation.

  1. Read water pressure on the analog gauge.
  2. Read hot water temperature on the display during operation.

Applies to: Operating readings

Source: Vitodens 100-W WB1B installation manual, p. 23. Written in our own words; check the manual for your exact model.

Read fault codes in BMS as hex text

Boiler · Versatronik 501

Fault codes come from the gateway as decimal SNVT count values, while Viessmann controls show them in hex. In Niagara AX, a numeric bit-and mask can display the hex value, and a numeric-to-enum conversion can map the full range of Viessmann codes to text. Bound labels on a webpage can then show the text.

Applies to: Niagara AX or similar BMS reading gateway fault codes

Source: Versatronik 501 NR2/LON communication manual, p. 24. Written in our own words; check the manual for your exact model.

Read gas consumption

Boiler · Vitocrossal 200 CI2

The boiler has an integral gas consumption meter. Readings are shown on the HMI and in ViGuide Web. DHW and heating circuit consumption are shown separately.

  1. Read current consumption, consumption for the past 7 days, current month, last month, current year and last year on the HMI or in ViGuide Web.
  2. Set the gas volume correction factor (parameter 1098.4) and the gross calorific value (parameter 1098.5) for accurate readings. Get these from the gas supplier or the gas bill.
  3. For lag boilers in ViGuide Web Pro, select the heat management unit (HMU) of the lag boiler.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 80. Written in our own words; check the manual for your exact model.

Read or enter the service address

Boiler · Vitocrossal 300 CA3B

Shows the heating contractor's details if they have been entered. If the field is empty, tap the white field to open the keypad and enter contact details.

  1. From the home screen, open Menu, then Information.
  2. Open Service address.
  3. If no details appear, tap the white field and enter them with the keypad.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Read system pressure from the pressure view

Boiler · Vitotron 100 VLN2

The pressure view shows the installation pressure in psi. Use it to check the pressure before and after any service work. Pressure adjustments are for the authorized service person only.

  1. Press the pressure view button on the panel.
  2. Read the psi value on the display.
  3. If pressure is below 7 psi, have the system pressure raised by the authorized service person.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Read the boiler section status icons

Boiler · Vitocrossal 300 CA3B Dual Fuel

The header shows each boiler section's status. The flame symbol shows the current heating output. The circle symbol shows whether the section is running, available or unavailable.

  1. Flame with short length (1 to 33%): low heating output.
  2. Flame with medium length (34 to 66%): mid heating output.
  3. Flame with full length (67 to 100%): high heating output.
  4. Solid white circle: section is enabled by the system and lead control unit and is operating.
  5. Solid grey circle: section is available but not currently called for by the system and lead control unit.
  6. Crisscrossed circle: section is not available to generate heat.

Applies to: Vitotronic 300 GW6C home screen

Source: Viessmann Vitocrossal 300 Dual Fuel operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Read the boiler status circles and output bars

Boiler · Vitotronic 300-K

The default display shows each boiler's state and its approximate heating output. The circle color and symbol show whether the boiler is enabled, idle or disabled.

  1. Blue circle: enabled by the cascade control and running.
  2. Gray circle: available to heat but not currently called by the cascade control.
  3. Circle with disable symbol: disabled for heat generation.
  4. A lead boiler symbol marks the lead boiler.
  5. Output bars show about 1-33%, 34-66% or 66-100% of heating output. The number under the circle shows the output in MBH or kW.

Applies to: Multi boiler cascade system, Vitotronic 300-K MW2C

Source: Vitotronic 300-K MW2C operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Read the boiler status symbols

Boiler · Vitotronic 300-K

The flame symbol shows approximate current heating output. The circle shows whether a boiler is enabled, available or disabled.

  1. Flame with a short length: 1 to 33% output.
  2. Flame with a medium length: 34 to 66% output.
  3. Flame with full length: 66 to 100% output.
  4. Solid white circle: boiler is enabled by the cascade control and is running.
  5. Solid grey circle: boiler is available but has not been called by the cascade control.
  6. Crossed-out circle: boiler is disabled for heat generation.
  7. Read the value under the circle as current output in MBH or kW, depending on the selected measuring units (p. 23).

Applies to: Vitotronic 300-K default display

Source: Vitotronic 300-K MW2C operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Read the default display

Boiler · Vitotronic 300-K

The default display lists the installed boilers in boiler sequence order. Header shows the common supply temperature (actual and setpoint). Each boiler line shows its number, its operating mode, and its output.

  1. Check the common supply temperature actual and setpoint in the header.
  2. Check each boiler number, which is listed in boiler sequence order.
  3. Check the boiler symbol and its output value.
  4. To change the boiler sequence, see the Setting the Boiler Sequence section (p. 21).

Applies to: Vitotronic 300-K default display

Source: Vitotronic 300-K MW2C operating instructions, p. 7-8. Written in our own words; check the manual for your exact model.

Read the fault history (Vitotronic 200)

Boiler · Vitotronic 200

The 10 most recent faults, including remedied ones, are saved and listed by date. The Vitotronic 200 menu path on this page is partly unreadable.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Fault history.
  3. Select Display?.
  4. Press the exit button to leave.

Applies to: Vitotronic 200

Source: Vitotronic 200 and 300-K Installation and Service, p. 71. Written in our own words; check the manual for your exact model.

Read the fault history (Vitotronic 300-K)

Boiler · Vitotronic 300-K

The 10 most recent faults, including resolved ones, are saved and listed by date.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Fault history.
  3. Select Display?.
  4. Press the exit button to leave.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service, p. 71. Written in our own words; check the manual for your exact model.

Read the fault memory (message history)

Boiler · Vitocrossal 200 CI2

The 10 most recent faults, including those already fixed, and maintenance messages are saved. They are sorted by date.

  1. Open the service menu and enter password "viservice".
  2. Select "Message history", then "Faults".
  3. To clear the list, use the delete button and confirm.

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 59. Written in our own words; check the manual for your exact model.

Read the gateway service LED

Boiler · Versatronik 585

The service LED shows the amount of data exchanged between the gateway and the boilers. It does not show BMS communication.

  1. In a single boiler system, the LED blinks slowly while boiler information is retrieved and speeds up when cascade information is retrieved.
  2. In a multi-boiler system, the LED blinks at a more even rate.

Applies to: Versatronik 585 VI/BACIP

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 15. Written in our own words; check the manual for your exact model.

Read the software number

Boiler · Versatronik 200

The software number with its index identifies the controller version and should be quoted when asking for support.

  1. Open the Software number display in the service area.
  2. Note the number with index (XXX.XX).

Applies to: Versatronik 200 controller

Source: Versatronik 200 installation and operating manual, p. 164. Written in our own words; check the manual for your exact model.

Reading and acknowledging fault messages

Boiler · Vitocrossal 300 CU3A

When a fault occurs, the fault symbol and red fault indicator flash and Fault appears. Note the cause and fault code before calling the heating contractor. Repeated acknowledgement in quick succession is dangerous; a repeating fault must be reported.

  1. Press OK to see the cause of the fault.
  2. Press the info button to see system performance and measures you can take first.
  3. Write down the cause and the fault code, for example Outside temp sens 18 and Fault A2.
  4. Acknowledge the fault by following the menu prompts. The message then moves to the menu.
  5. Do not acknowledge fault messages several times in quick succession.
  6. If a fault repeats, notify the heating contractor so the cause can be analysed.
  7. To view an acknowledged fault later, open the extended menu and choose Fault.

Applies to: Vitocrossal 300 CU3A with Vitotronic 200 KW6B

Source: Vitocrossal 300 CU3A operating instructions, p. 34. Written in our own words; check the manual for your exact model.

Reading and acknowledging service messages

Boiler · Vitocrossal 300 CU3A

When a service is due, the service symbol flashes and Service appears. If the service cannot be done yet, the message comes back the following Monday.

  1. Press OK to see the reason for the service.
  2. Press the info button to see details of the service that is due.
  3. To acknowledge, follow the menu prompts and contact the local heating contractor. The message then moves to the menu.
  4. To view an acknowledged service message later, open the extended menu and choose Service.

Applies to: Vitocrossal 300 CU3A with Vitotronic 200 KW6B

Source: Vitocrossal 300 CU3A operating instructions, p. 33. Written in our own words; check the manual for your exact model.

Reading and clearing service messages

Boiler · Vitotronic 300-K

The display shows a service message when the interval set by the heating contractor is reached. Service messages are shown in yellow.

  1. Tap Confirm on the service message. The footer then shows the service symbol.
  2. To view it later, tap the symbol in the footer to open the list.
  3. If several faults are active, tap Service messages to show them.
  4. Notify the heating contractor. If not done, the message returns the following Monday until the contractor resets the interval.

Applies to: Vitotronic 300-K MW2C

Source: Vitotronic 300-K MW2C operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Reading the boiler nomenclature chart (fuel, efficiency, type)

Boiler · Vitodens 200, Vitodens 222-F

The nomenclature chart maps letter codes to fuel type (gas or oil), efficiency class (low temperature, condensing, CHP), boiler type (wall-mounted or floor standing), and the DHW and heating options. The chart columns are not clear enough in the extracted text to read each letter with confidence, so use the printed chart on page 6 of the manual for the exact letter-to-option mapping.

  1. Open page 6 of the Vitodens 222-F B2TB Application Guide and locate the code chart.
  2. Match the fuel type letter (gas or oil) to the boiler's fuel.
  3. Match the efficiency letter (low temperature, condensing or CHP) to the boiler's efficiency class.
  4. Match the wall-mounted or floor-standing letter and the DHW and heating option letters to the model being installed.

Applies to: Vitodens 200 / 222-F nomenclature

Source: Vitodens 222-F B2TB Application Guide, p. 6. Written in our own words; check the manual for your exact model.

Reading the cascade overview symbols

Boiler · Vitotronic 300-K

The home screen shows each boiler with a flame and a circle. The flame length shows approximate heating output. The circle colour and marks show whether the boiler is running, available or disabled. The number under the circle is the current output in MBH or kW, depending on the selected units.

  1. Flame length: short for 1 to 33%, medium for 34 to 66%, full for 66 to 100%.
  2. Solid white circle: boiler is enabled by the cascade control and is operating.
  3. Solid grey circle: boiler is available but has not been called for.
  4. Crossed-out circle: boiler is disabled for heat generation.

Applies to: Cascade control home screen

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 8. Written in our own words; check the manual for your exact model.

Reading the fault history

Boiler · Vitodens 200-W B2HA

The 10 most recent faults, including resolved ones, are saved sorted by date. Some faults also show plain text.

  1. Press OK and the second button at the same time for about 4 seconds.
  2. Select Fault history.
  3. Select Display? and press OK to read the code.
  4. Look up the code in the fault code table (pages 71 to 72).

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 71. Written in our own words; check the manual for your exact model.

Reading the normal-mode display

Boiler · Versatronik

The display shows the time, set room temperature in °C, weekday (1 = Monday, 7 = Sunday), bus symbol, active heating program, burner and heating status, mode indicator, and current room temperature. If the bus symbol is missing, check the data cable to the boiler. Room temperature can drift about ±1°C (±2°F) from the set point, and it can deviate more during the change from reduced to heating operation.

  1. If the bus symbol does not show, check the data cable to the boiler.
  2. Do not treat a ±1°C (±2°F) difference from set point as a fault.

Applies to: Versatronik COMO OT display in normal mode

Source: Versatronik COMO OT manual, p. 15. Written in our own words; check the manual for your exact model.

Reading the Vitocrossal model nomenclature

Boiler · Vitocrossal 300

Segment code CU is the Vitocrossal boiler line. The first digit gives the series, so 3 means the 300 series. The domestic hot water code after the series digit shows the DHW capability: X means no DHW, I means indirect DHW, C means on-demand DHW, and T means stratified loading tank. The remaining letters and digits describe the efficiency and fuel type and are not fully legible on these pages, so check the technical data for the exact unit.

  1. Find the segment code (CU) to confirm the Vitocrossal line.
  2. Read the series digit: 3 = 300 series.
  3. Check the DHW code: X no DHW, I indirect DHW, C on-demand DHW, T stratified loading tank.
  4. Confirm the rest of the model code against the Technical Data Manual before ordering or specifying.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A application guide, p. 3. Written in our own words; check the manual for your exact model.

Reading the Vitodens boiler nomenclature

Boiler · Vitodens 200, Vitodens 222-F

The model code is built from segments. The boiler segment is shown first (VD = Vitodens). The next digit gives the series (1 = 100 series, 2 = 200 series). The domestic hot water capability follows (X = no DHW, I = indirect DHW, C = on-demand DHW, T = stratified loading tank). The page also shows the heating circuit and zone counts, the number of boilers and supply temperatures, and how the system is zoned (ZP = pumps, ZV = zone valves, TV = thermostatic radiator valves, C = combination).

  1. Read the boiler segment (VD = Vitodens) and the series digit (2 = 200 series).
  2. Read the domestic hot water letter (X, I, C or T) to confirm the DHW type.
  3. Read the circuit codes (HC = heating circuit, ZC = zone circuit, HC/ZC = combination) and the number of circuits.
  4. Read the zoning code (ZP, ZV, TV or C) to confirm how the system is zoned.
  5. Check the drawing version and the number of boilers and supply temperatures in the code against the job drawings.

Applies to: Vitodens 200 / 222-F nomenclature

Source: Vitodens 222-F B2TB Application Guide, p. 7. Written in our own words; check the manual for your exact model.

Record altered high limit settings

Boiler · Vitotronic 100

Note any changed high limit settings in the technical data table so the next technician can see them.

  1. Compare the current high limit settings with the factory defaults.
  2. Write any altered values in the altered settings column of the technical data table.

Applies to: KW10B

Source: Vitotronic 100 KW10B installation manual, p. 35. Written in our own words; check the manual for your exact model.

Record the serial number when ordering parts

Boiler · Vitodens 100-W WB1B

The boiler has a 16-digit bar code serial label and a 12-digit ASME/NB serial on a plate riveted to the heat exchanger. The two serials match, so either one is enough when ordering replacement parts.

  1. Locate the 16-digit bar code label on the boiler or the 12-digit ASME/NB plate on the heat exchanger.
  2. Give either serial number when ordering parts.

Applies to: WB1B-26, WB1B-35

Source: Vitodens 100-W WB1B installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Record water quality values

Boiler · Vitocrossal 200 CI2

Enter the amount of top-up water, total hardness and pH in the appendix table on page 94. The pH must be between 8.2 and 9.5. Water quality requirements are on page 95.

  1. Measure the top-up water amount, total hardness and pH.
  2. Enter the values in the table on page 94.
  3. Confirm pH is between 8.2 and 9.5.

Applies to: Vitocrossal 200 CI2 boilers

Source: Vitocrossal 200 CI2 Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

Reduced mode and boost examples

Boiler · Vitotronic 200-H

Example 1 (F8 −5, F9 −14): below −5 °C outdoor the reduced room set point rises with falling outdoor temperature, and below −14 °C it equals the standard room set point. Example 2 (FA 20, Fb 30): when switching from reduced to standard room temperature, the supply set point is raised by 20 % for 60 minutes.

Applies to: Vitotronic 200-H mixing valve circuit, coding addresses F8, F9, FA, Fb

Source: Vitotronic 200-H installation and service manual, p. 66. Written in our own words; check the manual for your exact model.

Reduced mode on underfloor heating

Boiler · Vitotronic 300-K

Underfloor heating responds very slowly to short temperature changes. Night setback or Economy mode during short absences saves little energy on this type of system.

Applies to: Underfloor heating systems

Source: Vitotronic 300-K, MW2C operating instructions, p. 33. Written in our own words; check the manual for your exact model.

Refitting the top and front panels

Boiler · Vitocrossal 300

Panels are refitted in reverse order of removal, using the parts removed earlier.

  1. Place the control cover on the control connection housing and slide it into place.
  2. Install the nuts removed earlier onto the threaded studs.
  3. Place the top jacket panel on the boiler and slide it into place.
  4. Fasten the top panel with the retaining screws removed earlier.
  5. Place the front cover onto the locating pegs.
  6. Push the top of the front panel into place.
  7. Secure the front panel with the retaining screw.

Applies to: Vitocrossal 300 CU3A boiler jacket

Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 42. Written in our own words; check the manual for your exact model.

Reinstalling the front enclosure panel

Boiler · Vitodens 200-W B2HB

Refit the front panel. Locking screws must be fitted before the boiler is operated. Never run the boiler without the front cover in place.

  1. Set the front enclosure panel on the guide rails and push it into place.
  2. Tighten the screws at the bottom.
  3. Insert the external accessories connection box cover in place.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 59. Written in our own words; check the manual for your exact model.

Remote burner disable: freeze-up protection warning

Boiler · Switching Module-V

While the external burner disable contact is closed, freeze-up protection of the heating system and boiler protection cannot be guaranteed.

Applies to: Switching Module-V

Source: Switching Module-V installation instructions, p. 6. Written in our own words; check the manual for your exact model.

Remote control only settings

Boiler · Vitotronic 200-H

Some settings can only be made on the remote control, not on the control unit. Example: normal room temperature on the ts selector knob.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Remove and reinstall burner assembly

Boiler · Vitodens 200-W B2HA

Burner removal and refit, including gasket replacement and a gas leak test after reassembly. Do not lay the burner on its cylindrical tube or touch the tube mesh, as this can damage it.

  1. Switch off the main power and the ON/OFF switch on the boiler control.
  2. Shut off the gas valve.
  3. Fold down the control unit and remove the cover.
  4. Disconnect the cables from the fan motor, gas valve, ionization electrode and ignition module.
  5. Release the gas supply pipe fitting. Note the gasket between gas valve and fitting.
  6. Loosen the six Torx T-30 screws and remove the burner.
  7. Check the burner gasket for damage. Generally replace it every 2 years.
  8. Refit the burner and tighten the screws in a diagonal pattern to 70 lb.in (8 Nm).
  9. Fit a new gasket on the gas line connection and tighten to 132 lb.in (15 Nm).
  10. Reconnect the electrical cables.
  11. Perform a gas leak test.

Applies to: Vitodens 200-W B2HA

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.

Remove the boiler front cover

Boiler · Vitocrossal 300 CU3A

Needed to reach the serial number label and the siphon.

  1. Remove the retaining screw and set it aside.
  2. Pull the top of the boiler cover away from the boiler.
  3. Lift the cover off and set it aside.

Applies to: Vitocrossal 300 CU3A

Source: Vitocrossal 300 CU3A service instructions, p. 11. Written in our own words; check the manual for your exact model.

Remove the front cover

Boiler · Vitodens 100-W B1HE/B1KE

The front cover is held by two retaining tabs at the top.

  1. Push up on the two retaining tabs with a screwdriver.
  2. Pull the bottom edge of the cover out.
  3. Lift the cover off.

Applies to: Vitodens 100-W service access

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 13. Written in our own words; check the manual for your exact model.

Removing the front panel

Boiler · Vitodens 100-W B1HE/B1KE

The front panel is held by a lock on its underside. Protective caps on the heating water and gas connections should stay on until just before installation.

  1. Unlock the front panel from the underside by pushing in with a screwdriver or similar tool.
  2. Swivel the front panel forward slightly.
  3. Lift the panel upward and away.
  4. Leave connection caps on until ready to connect.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 13. Written in our own words; check the manual for your exact model.

Replace an air pressure switch

Boiler · Vitocrossal 300 CA3B Dual Fuel

Remove the display unit and the hoses first. Observe torque values when reassembling.

  1. Undo the 2 mounting screws (1 Nm / 9 lb.in) and remove the display and programming unit from the burner control unit.
  2. Pull connector aCA (LDW1) and connector aCAA (LDW2) from the plug-in strip.
  3. Pull the compensation hose from the connector.
  4. Undo the screw(s) on the air pressure switch and remove the cover (1 Nm / 9 lb.in).
  5. Undo the base mounting screws and remove the base.
  6. Install the new switch in reverse order and set it to the same value as the old one.
  7. Attach the connection hose to the matching connector.

Applies to: LDW1 and LDW2 air pressure switches

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 63. Written in our own words; check the manual for your exact model.

Replace the boiler secondary temperature sensor (15A / 15B)

Boiler · Vitocrossal 300 CA3B Dual Fuel

The secondary sensor sits on each boiler section pressure vessel. Its plug is at the burner control unit for that section.

  1. Remove the spring clip from the sensor well and set it aside.
  2. Pull the boiler secondary temperature sensor out of the sensor well.
  3. Disconnect sensor cable plugs 15A / 15B.
  4. Connect the new sensor to plugs 15A / 15B and install it in the sensor well.
  5. Reinstall the spring clip.

Applies to: Boiler secondary temperature sensor 15A / 15B

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 59. Written in our own words; check the manual for your exact model.

Replace the boiler water temperature sensor (3A / 3B)

Boiler · Vitocrossal 300 CA3B Dual Fuel

Each boiler section has its own boiler water temperature sensor in a sensor well. Replace the sensor for the affected section.

  1. Remove the spring clip from the sensor well and set it aside.
  2. Pull the boiler water temperature sensor out of the sensor well.
  3. Disconnect sensor cable plugs 3A / 3B.
  4. Connect the new sensor to plugs 3A / 3B and install it in the sensor well.
  5. Reinstall the spring clip.

Applies to: Boiler water temperature sensors 3A (NTC 10k) and 3B (NTC 20k)

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 57. Written in our own words; check the manual for your exact model.

Replace the burner control unit

Boiler · Vitocrossal 300 CA3B Dual Fuel

Remove the display and programming unit and all cables before swapping the burner control unit. The coding card moves to the new unit.

  1. Disconnect the KM-BUS connector avG.
  2. Undo the 2 mounting screws on the display and programming unit (torque 1 Nm / 9 lb.in) and lift it off.
  3. Unplug the burner control unit connecting cable and remove the display unit.
  4. Unplug all connecting cables from the burner control unit.
  5. Pull the coding card from the burner control unit.
  6. Undo the 4 mounting screws and remove the burner control unit.
  7. Install the new unit in reverse order.

Applies to: Burner control unit

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 56. Written in our own words; check the manual for your exact model.

Replace the fan and Venturi assembly

Boiler · Vitocrossal 300 CA3B Dual Fuel

The Venturi pipe carries the gas valve. Fit the fan gasket in its correct position.

  1. Disconnect both fan connectors.
  2. Remove the 6 Venturi pipe nuts and remove the Venturi pipe with the gas valve attached. Tighten to 6 Nm (4.5 lb.ft) on reassembly.
  3. Undo the hex nuts on the 4 studs.
  4. Remove the fan and note how the gasket sits.
  5. Install the new fan in reverse order and fit the gasket in the correct position.

Applies to: Fan and Venturi pipe

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 64. Written in our own words; check the manual for your exact model.

Replace the gas valve

Boiler · Vitocrossal 300 CA3B Dual Fuel

Check the gas connections for tightness after reassembly. Leak detection spray must not contact electrical contacts. The gas valve mounts horizontally, rotated 90°. The orifice plate must be oriented with its chamfer facing the gas valve.

  1. Disconnect the electrical connectors from the gas valve and both gas pressure switches.
  2. Disconnect the pressure compensation line from the gas valve.
  3. Remove the gas inlet flange screws and remove the flange.
  4. Remove the nuts on the outlet flange and remove the gas valve.
  5. Fit new studs to the new gas valve outlet flange.
  6. Check the orientation of the gas valve and orifice plate.
  7. Replace the inlet and outlet gaskets.
  8. Secure the gas valve on the flange without stress and tighten the screws to 1.5 Nm (13 lb.in).
  9. Reconnect the valve and gas pressure switch connectors and the pressure compensation tubing.
  10. Do not swap the connecting cables of GDW1 and GDW2.
  11. Check the gas connections for tightness.

Applies to: Gas valve

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 61. Written in our own words; check the manual for your exact model.

Replace the ignition unit and ignition cables

Boiler · Vitocrossal 300 CA3B Dual Fuel

Ignition unit mounting screws are torqued to 1.5 Nm (13 lb.in).

  1. Unplug the connecting cable from the ignition unit.
  2. Pull the ignition cables from the ignition unit.
  3. Undo the ignition unit mounting screws and remove the unit.
  4. Install the new ignition unit in reverse order and torque the screws to 1.5 Nm (13 lb.in).
  5. For ignition cables, pull them from the unit and from the ignition electrodes, then fit the new cables in reverse order.

Applies to: Ignition unit and ignition cables

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 63. Written in our own words; check the manual for your exact model.

Replacement parts and electrical isolation before work

Boiler · Vitocrossal 300 CA3B

Only Viessmann recommended parts are allowed. Isolate power and gas before any service work.

  1. Use only original Viessmann recommended components when replacing defective parts.
  2. Turn off main power to the boiler, the heating system and all external controls.
  3. Close the main gas supply valve.
  4. Prevent accidental power-up during service work.
  5. Check the field supplied controls such as low water cut-offs, pumps, motorized valves, air vents and thermostats.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 7-8. Written in our own words; check the manual for your exact model.

Replacement parts for combustion chamber door

Boiler · Vitorond 100

Commonly needed items for combustion chamber door service.

  1. Use rope sealant for the combustion chamber door seal.
  2. Use refractory for the combustion chamber door.

Applies to: All VR1 models

Source: Vitorond 100 installation and service manual, p. 48. Written in our own words; check the manual for your exact model.

Replacing damaged cables or lines

Boiler · Vitocrossal 300 CA3B

Damaged connecting cables or lines on the appliance or on externally installed accessories must be replaced.

  1. Use only Viessmann cables or lines as replacements.
  2. Have a qualified contractor make the replacement.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B operating instructions, p. 41. Written in our own words; check the manual for your exact model.

Required test equipment

Boiler · Vitocrossal 300 CA3B Dual Fuel

Calibrated equipment is required for combustion and gas checks on this boiler.

  1. Use a flue gas analyzer to measure % CO2 or O2.
  2. Use a multimeter for 0-120 VAC, 0-25 A AC and 0-100 microamps DC.
  3. Use a gas pressure gauge covering 0 to 28 in. w.c. (a Magnehelic 0-10 psig gauge may also be used).
  4. Use a CO meter covering 0 to 400 ppm.
  5. Use a stack thermometer covering 0°F to 250°F.
  6. Have a leak detection fluid approved for natural gas and propane.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 7. Written in our own words; check the manual for your exact model.

Required test tools

Boiler · Vitodens 200-W B2HA

Calibrated equipment is needed for service work on this boiler.

  1. Use a multimeter for 0-230V AC, 0-12A AC and 0-100 mA DC.
  2. Use a flue gas analyzer to measure CO2 or O2.
  3. Use a manometer for gas pressure, 0 to 11 in. w.c. (accurate) and up to 28 in. w.c., or a Magnehelic manometer.
  4. Use a stack thermometer, 0 to 500°F (0 to 260°C).
  5. Use a CO meter, 0 to 400 ppm.
  6. Use a leak detection fluid approved for natural gas and LP, and pipe joint sealant.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 6. Written in our own words; check the manual for your exact model.

Required tools and supplies for service

Boiler · Vitorond 100

Equipment to have on hand for the service procedure.

  1. Calibrated flue gas analyzer.
  2. Hand brush, rags and vacuum cleaner.
  3. Rope sealant and refractory for the combustion chamber door, if replacement is needed.

Applies to: VR1 40 to 63, 161 to 245

Source: Vitorond 100 installation and service manual, p. 48. Written in our own words; check the manual for your exact model.

Required tools for service

Boiler · Vitorond 100

Use only calibrated equipment.

  1. Use a calibrated flue gas analyzer.
  2. Have a hand brush, rags and a vacuum cleaner ready.
  3. Keep rope sealant and refractory for the combustion chamber door on hand if replacement is needed.

Applies to: Vitorond 100 VR1 service

Source: Vitorond 100, VR1 installation and service instructions, p. 45. Written in our own words; check the manual for your exact model.

Resetting data counters

Boiler · Vitotrol 300A

Burner hours, fuel consumption (if set by the heating contractor) and solar yield or solar pump hours can be reset individually or together with All details.

  1. Open the extended menu.
  2. Select Information, then Reset data.
  3. Select the item, or All details, and reset.

Applies to: Vitotrol 300A remote control

Source: Vitotrol 300A operating instructions, p. 20. Written in our own words; check the manual for your exact model.

Respond to a fault display (Vitotronic 300-K)

Boiler · Vitotronic 300-K

A fault turns the red fault display on and it flashes. Fault appears on the display and flashes. Press OK to show the fault code. If a central fault message facility is connected, it starts. Some faults also show a short text.

  1. Press OK to show the fault code.
  2. Look up the code in the fault codes table.
  3. Follow the on-screen instructions to acknowledge the fault.
  4. Check the faulty component as listed in the fault code table.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Installation and Service, p. 71. Written in our own words; check the manual for your exact model.

Return to home screen and standby

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

The home screen is the start point for most navigation. The display backlight turns off after about 2 minutes without input.

  1. If the display is in standby, tap any button to wake it.
  2. From anywhere in the menu, tap Back repeatedly until the home screen appears.

Applies to: Vitodens 100-W B1HE and B1KE control unit

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Reverse mixing valve motor rotation

Boiler · Vitotronic 300-K MW1S

The motor rotation direction is set by how plug A is fitted. Reverse it when the installation example requires the opposite direction.

  1. Remove the motor cover.
  2. Remove plug A.
  3. Reinsert plug A turned 180°.
  4. Check that the mixing valve opens and closes correctly with the relay test.

Applies to: Mixing valve motor 7133 390

Source: Viessmann Vitotronic 300-K MW1S installation and service instructions, p. 128. Written in our own words; check the manual for your exact model.

Reverse the mixing valve motor rotation direction

Boiler · Vitotronic 300-K MW1S

To change the direction of rotation, the plug orientation is reversed.

  1. Remove the cover of the mixing valve motor.
  2. Remove the 3-pole plug A and reinsert it turned by 180°.

Applies to: Mixing valve motor

Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 128. Written in our own words; check the manual for your exact model.

Roof vent height and chimney routing

Boiler · Vitocrossal 200 CI2

Special vent with positive pressure has height and routing limits when passing through a roof.

  1. Extend the vent at least 18 in above the highest roof penetration point and any obstruction within 18 in horizontal distance.
  2. Do not route the special vent into, through or within another vent or existing chimney.
  3. Use a masonry chimney flue only if no other appliance vents into that flue.

Applies to: Special vent systems with positive vent pressure

Source: Vitocrossal 200 CI2 Installation manual, p. 58. Written in our own words; check the manual for your exact model.

Room air dependent versus direct vent combustion air

Boiler · Vitotronic 300-K

In room air dependent operation, combustion air comes from the room where the boiler is installed. In direct vent operation, combustion air is drawn from outside the building.

Applies to: Boiler combustion air supply

Source: Vitotronic 300-K, MW2C operating instructions, p. 34. Written in our own words; check the manual for your exact model.

Room air dependent vs direct vent combustion air

Boiler · Vitotronic 300-K

Room air dependent operation draws combustion air from the boiler room. Direct vent operation draws combustion air from outside the building.

Applies to: Boiler combustion air supply

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 34. Written in our own words; check the manual for your exact model.

Room air vs direct vent combustion air

Boiler · Vitodens 200-W B2HA

Room air dependent operation draws combustion air from the boiler room. Direct vent operation draws combustion air from outside the building.

Applies to: Vitodens 200-W B2HA venting configuration

Source: Vitotronic 200 Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Room feedback and system type

Boiler · Versatronik

Room temperature feedback can be turned on to improve comfort, and its influence factor changes how the boiler responds. On low-mass emitters like baseboard or panel radiators, and on high-mass radiant floors, feedback may not give the expected result because of how quickly each system responds.

Applies to: Versatronik COMO OT room feedback setting

Source: Versatronik COMO OT manual, p. 14. Written in our own words; check the manual for your exact model.

Room influence on supply temperature (worked example)

Boiler · Vitocrossal 200 CI2

The supply temperature rise from room temperature hook-up is: (target room temp - actual room temp) x (1 + slope) x room influence factor / 4. Example from the manual: target 20.0°C, actual 18.0°C, slope 1.4, factor 8 (factory) gives a rise of 9.6 K.

  1. Use the room influence factor parameter for the heating circuit: 933.7, 934.7, 935.7 or 936.7.

Applies to: Heating circuits with room temperature hook-up

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 86. Written in our own words; check the manual for your exact model.

Room temperature-dependent vs weather-compensated control

Boiler · Vitotronic 300-K

Room temperature-dependent mode controls supply temperature from a room sensor fitted in the room, independent of outdoor temperature. Weather-compensated mode controls supply temperature from an outdoor sensor fitted on the building exterior.

Applies to: Heating control modes

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 33. Written in our own words; check the manual for your exact model.

Rotary damper must be fully open

Boiler · Vitocrossal 300 CA3B Dual Fuel

An incompletely opened rotary damper can cause malfunctions or point to incorrect servomotor adjustment.

  1. Confirm the rotary damper is fully open with the burner off and during operation.
  2. If it is not, adjust it with the articulated rod and check the servomotor settings.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 64. Written in our own words; check the manual for your exact model.

Route and secure field wiring

Boiler · Vitodens 200-W

Keep connecting cables away from hot components and do not exceed their maximum temperature rating. Use the cable grommet for power cable entry and secure cables to the control base strain reliefs. Discharge static before touching electronics.

  1. Touch a grounded object such as a heating or water pipe before working on electronic modules.
  2. Remove the existing cable grommet when using larger cables.
  3. Plug the grommet into the lower casing section (black) and secure the cable.
  4. Route all connecting cables to their areas and secure them to the control base strain reliefs.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

Source: Vitodens 200-W B2HA installation instructions, p. 24. Written in our own words; check the manual for your exact model.

Route low-voltage and 120 V connecting cables

Boiler · Vitodens 200-W

Keep cables clear of hot components, since they will be damaged if touching them. Cables must stay within their rated temperature.

  1. Route low-voltage cables and 120 V cables to their connection areas.
  2. For larger cable sizes (up to 9/16 in.), remove the existing cable grommet and secure the cable with the grommet in the lower (orange) casing section.
  3. Secure all cables to the control base using the existing strain reliefs.
  4. Keep the power cable grommet in place for the 120 V connections.

Applies to: Vitodens 200-W B2HB wiring

Source: Vitodens 200-W B2HB installation manual, p. 24. Written in our own words; check the manual for your exact model.

Routine checks by the owner

Boiler · Vitodens 200-W, Vitocrossal 300 CU3A

Check that flue passages are not blocked, check the system water pressure on the gauge, look for water or rust on flue pipes and vent terminals, and keep combustion air openings clear of chemicals and flammable materials.

  1. Check the vent or chimney for blockage.
  2. Check the pressure gauge reads the correct system water pressure.
  3. Look for water on the floor, leaks at joints and valves, and rust on flue pipes.
  4. Make sure nothing blocks combustion and ventilation air.

Applies to: Vitodens 200-W and Vitocrossal 300 CU3A

Source: Vitotronic 200 operating instructions 5838 962-03, p. 5. Written in our own words; check the manual for your exact model.

Routine safety checks for the vent and system

Boiler · Vitodens 100-W B1HE/B1KE

Regular checks keep flue gases from leaking into the building and catch water leaks early.

  1. Check the vent or chimney for debris or blockage. Have any blockage removed by a qualified heating contractor.
  2. Check flue pipes, joints, vent dampers and side wall terminals for moisture, water or rust.
  3. Check the pressure gauge for correct system (water) pressure.
  4. Check for water on the floor from the pressure relief valve discharge or any pipe, joint, valve or air vent.
  5. Make sure nothing blocks combustion and ventilation air, and that no chemicals, gasoline or flammable materials are stored near the boiler.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Viessmann Vitodens 100-W B1HE/B1KE operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Routing and securing the connecting cables

Boiler · Vitodens 200-W B2HB

Cables must not touch hot components, as they will be damaged. Keep cable temperatures within the maximum permitted for the cable. Use the existing strain reliefs on the control base to secure the cables. For larger wire, remove the existing cable grommet and secure the cable with the grommet fitted in the lower (orange) casing section. The cable size figure in the manual is partly garbled and is not reproduced here.

  1. Discharge static by touching grounded piping before working on electronic modules.
  2. Remove the existing cable grommet if using larger wire.
  3. Route all connecting cables to their areas and secure them to the control base at the existing strain reliefs.
  4. Plug the DHW temperature sensor into the quick connect plugs on the cable harness.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB installation manual, p. 24. Written in our own words; check the manual for your exact model.

Routing connecting cables

Boiler · Vitodens 222-F, B2TB

Keep connecting cables away from hot components, since heat will damage them. Check that the cable temperature ratings are not exceeded where the cables are routed and secured on site. Low voltage, 120V and external accessory cables connect to the main PCB and the communication module.

  1. Route cables away from hot parts of the boiler.
  2. Check that the cable temperature limits are not exceeded.
  3. For larger cross-sections (up to 9/16 in. / 14 mm), remove the existing cable grommet.
  4. Secure the cable with the cable grommet fitted into the lower casing section (orange).

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB Installation Instructions, p. 48. Written in our own words; check the manual for your exact model.

Routing external cables near hot parts

Boiler · Vitocrossal 300 CU3A

Cables fail if they touch hot boiler components. Keep power and pump cables within their rated temperature limits.

  1. Route cables away from hot components.
  2. Check that the cable's maximum permitted temperature is not exceeded where it is secured on site.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A installation manual, p. 24. Written in our own words; check the manual for your exact model.

Sacrificial anode check

Boiler · Vitocell 100

For Vitocell 100 the sacrificial anode function should be checked annually. This can be done without interrupting system operation.

  1. Have the heating contractor check the ground current with an anode tester

Applies to: Vitocell 100

Source: Vitotronic 300-K MW1B / Vitotronic 100 GC1B operating instructions, p. 36. Written in our own words; check the manual for your exact model.

Safe operating requirements

Boiler · Vitodens 200-W B2HA

Never run the boiler without an installed venting system, and never run it with the front cover off. Do not run it in areas with contaminated combustion air.

  1. Confirm the venting system is installed before firing.
  2. Keep the front cover in place during operation.
  3. Check that combustion air is free of dust, lint and chemicals.

Applies to: All B2HA models

Source: Vitodens 200-W B2HA installation manual, p. 2. Written in our own words; check the manual for your exact model.

Safety before wiring the Versatronik 10.WB1

Boiler · Versatronik 10.WB1

Disconnect power before any work. The pump output from the Vitodens boiler to the Versatronik must not be live. Check all wiring before applying power, or the pump module may fail early. Static sensitive parts can be damaged by handling, so take static precautions.

  1. Disconnect the boiler and the Versatronik from 120VAC before any work.
  2. Check that the boiler pump output to the Versatronik is not live.
  3. Check all wiring connections before applying power.
  4. Use static precautions when working inside the control.

Applies to: Versatronik 10.WB1 with Vitodens 100-W WB1A and WB1B

Source: Versatronik 10.WB1 installation manual, p. 10, p. 16 (static caution from p. 3). Written in our own words; check the manual for your exact model.

Safety relief valve discharge piping

Boiler · Vitotron 100 VLN2

The 30 psi ASME relief valve must discharge through copper piping to a safe location near the floor.

  1. Install copper piping from the relief valve to within 6 in. of the floor or a floor drain.
  2. Do not install any barrier fitting or valve on the outlet of the safety valve.

Applies to: Vitotron 100 VLN2 relief valve

Source: Vitotron 100 VLN2 installation and service instructions, p. 3, 8. Written in our own words; check the manual for your exact model.

Safety rules during service

Boiler · Vitorond 100

Key warnings for anyone working on the boiler.

  1. Do not use gasoline, crankcase drainings or any oil containing gasoline.
  2. Never adjust the burner by eye.
  3. Do not start the burner unless the combustion chamber door is secured in place.
  4. Do not attempt to start the burner when excess oil has built up, the unit is full of vapor, or the chamber is very hot.
  5. Never fire the boiler without water.
  6. Do not tamper with the unit or controls.
  7. Keep the manual fuel supply valve shut off when the burner is down for a long time.
  8. Never burn garbage or paper in the unit or leave combustible material near it.
  9. Do not leave tools inside the combustion chamber.
  10. Read the fiberglass and ceramic fiber warning on page 3 before handling insulation, and use proper respirator and clothing.

Applies to: VR1 40 to 63, 161 to 245

Source: Vitorond 100 installation and service manual, p. 48 and p. 51. Written in our own words; check the manual for your exact model.

Safety valve (DHW tank) check

Boiler · Vitocrossal 300 CA3B Dual Fuel

The DHW tank safety valve can become contaminated at the seat. Water may drip from the outlet during heat-up, which is normal. The outlet must stay open to the atmosphere.

  1. Check the function of the safety valve every six months by venting it (see valve manufacturer's instructions).
  2. Do not close off the safety valve outlet.

Applies to: DHW tank safety valve

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 41. Written in our own words; check the manual for your exact model.

Safety valve and drinking water filter on DHW supply

Boiler · Vitotronic 300-K, Vitotronic 200

The safety valve is installed by the heating contractor in the cold water pipe. It opens automatically to prevent excess pressure in the DHW tank. A drinking water filter removes solids from the water and is installed in the cold water pipe upstream of the DHW tank or instantaneous water heater.

  1. Verify the safety valve is installed in the cold water pipe.
  2. Verify the drinking water filter is upstream of the DHW tank or instantaneous water heater.

Applies to: Viessmann DHW tank installations

Source: Vitotronic 200 and 300-K Operating Instructions, p. 45. Written in our own words; check the manual for your exact model.

Safety valve and drinking water filter on the cold water supply

Boiler · Vitotronic 300-K

The contractor installs the DHW safety valve in the cold water pipe. It opens automatically to limit excess pressure in the DHW tank. A drinking water filter, which removes solids, goes in the cold water pipe upstream of the DHW tank or instantaneous water heater.

  1. Install the safety valve in the cold water pipe.
  2. Install the drinking water filter in the cold water pipe upstream of the DHW tank or instantaneous heater.

Applies to: DHW tank cold water connection

Source: Vitotronic 300-K, MW2C operating instructions, p. 35. Written in our own words; check the manual for your exact model.

Safety valve on DHW tank

Boiler · Vitodens 200-W B2HA

The safety valve is installed by the heating contractor in the cold water pipe. It opens automatically to prevent excess pressure in the DHW tank.

Applies to: Vitodens 200-W B2HA domestic hot water tank

Source: Vitotronic 200 Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Scald protection on DHW piping

Boiler · Vitodens 100-W B1HE/B1KE

DHW from gas condensing combi boilers can exceed 140°F (60°C).

  1. Install scald protection on site in the DHW pipe.

Applies to: Vitodens 100-W B1HE/B1KE DHW outlet

Source: Vitodens 100-W, B1HE/B1KE Installation/Service, p. 19. Written in our own words; check the manual for your exact model.

Scald risk from raised DHW temperature

Boiler · Vitodens 100-W B1HE/B1KE

Raised DHW target temperatures increase the outlet temperature at draw-off points.

  1. Tell the system user about the scald risk from the higher outlet temperature at draw-off points.
  2. Provide on-site scald protection if needed.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 92. Written in our own words; check the manual for your exact model.

Scald warning for instantaneous DHW

Boiler · Vitodens 100-W B1KE

Hot water can cause serious injury. The B1KE with instantaneous DHW has a scalding label on the side of the boiler. Do not touch hot water.

  1. Warn occupants about hot water at the taps.
  2. Keep the scalding label on the boiler visible.

Applies to: Vitodens 100-W B1KE Combi series

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Scan current temperatures and operating data (Vitotronic 300-K)

Boiler · Vitotronic 200, Vitotronic 300-K

The 300-K groups its scan data into General, Heating circuit 1, 2 and 3, DHW, Solar and Reset data. Named heating circuits show their custom name in the scan list.

  1. Open the extended menu.
  2. Select "Information".
  3. Select the group you need.
  4. Select the required scan.

Applies to: Vitotronic 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Scan list for readings

Boiler · Vitotrol 300A

The scan list shows readings from the boiler and circuits. Not all scans are present on every system, depending on the equipment level.

  1. General: outdoor temperature, boiler temperature, common flow temperature, flue gas temperature, burner hours run (stage 1 and 2), time, date, subscriber number.
  2. Fuel consumption: oil boilers only.
  3. Solid fuel boilers only: idle state, control mode, burnout phase, ember retention, cleaning, buffer cylinder top and bottom.
  4. Heating circuits 1 to 3: heating program, operating status, time program, set and actual room temperature, circuit pump, flow and return temperature, holiday program.
  5. Solar: collector temperature, solar DHW, solar circuit pump and its speed, solar energy, heat suppression.
  6. DHW: DHW time programs HC 1 to 3, recirculation time programs, actual DHW temperature, DHW tank primary pump, DHW circulation pump.

Applies to: Vitotrol 300A

Source: Vitotrol 300A Remote Control Operating Instructions, p. 26. Written in our own words; check the manual for your exact model.

Scan points available under the Information menu

Boiler · Vitotronic 300-K

The Information menu lists scan points grouped by area: general boiler data, heating circuits 1 to 3, solar, and DHW. Which scans show depends on the installed equipment level, so some listed points will not appear on every system. Some points can be expanded for more detail. Groups include outdoor temperature, boiler sequence and temperatures, sensor and output readings, feed pump, central fault message, heating program and operating status, room and comfort targets, slope and shift, heating and mixer pumps, solar collector and pump data, DHW temperatures and DHW pump status.

Applies to: Vitotronic 300-K, type MW2C control, Information menu

Source: Vitotronic 300-K, MW2C operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Scan points under the Information menu (general and heating circuits)

Boiler · Vitotronic 300-K

The Information menu lets you scan live values. Which scans appear depends on the installed equipment level. Items marked with an icon in the manual have a detailed view. General scans include outdoor temperature, boiler sequence, boiler temperature, sensors 17 A/B and 9, outputs 20, 29 and 52, feed pump, central fault message, participant number, integral, external input EA1, 0-10 V external hook-up, time and date. Heating circuit 1, 2 and 3 scans include heating program, operating status, time program, room temperature and targets, set external room temperature, comfort and reduced targets, slope, shift, heating circuit pump, mixer, supply temperature and holiday program.

Applies to: Vitotronic 300-K MW2C, Information menu

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Scan points under the Information menu (solar and DHW)

Boiler · Vitotronic 300-K

Solar scans include solar energy history, collector temperature, solar DHW, solar circuit pump run hours and ON/OFF state or pump speed, solar energy, heating suppression of DHW, SM1 output 22 state and run hours, sensors 7 and 10, and heating suppression. DHW scans include DHW time program, DHW circulation time program, DHW temperature, or top and bottom DHW temperatures when two tank sensors are fitted, DHW circulation pump and tank primary pump.

Applies to: Vitotronic 300-K MW2C, Information menu, solar and DHW

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Scan solar energy yield

Boiler · Vitocrossal 300 CA3B

Only works with a SM1 solar control unit, or with a Vitosolic solar control unit. Yield is shown as a diagram. Tap a day of the week to show the figure as a number. The solar circuit pump run hours are in the extended Information menu under the Solar group.

  1. From the home screen, open Menu, then Solar energy.
  2. Tap the required day of the week for a numerical value.
  3. For solar circuit pump run hours, open Menu, Information, then the Solar group.

Applies to: Vitocrossal 300 CA3B with solar control unit SM1 or Vitosolic

Source: Vitocrossal 300 CA3B operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Scan the preset space heating time phases

Boiler · Vitotronic 200-H

Shows the factory time phases on the time slot graphic without changing them.

  1. Open the hinged cover on the programming unit.
  2. Press ur and the second button at the same time; the preset time phases appear on the time slot graphic.
  3. Close the hinged cover.

Applies to: Vitotronic 200-H space heating time program

Source: Vitotronic 200-H operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Scanned values list

Boiler · Vitotronic 300

The temperature scan lists the values below. Some only appear if the matching sensor or remote control is connected.

  1. Damped outdoor temperature (can be reset to current by pressing D).
  2. Current outdoor temperature.
  3. Output reduction %.
  4. Desired and current boiler temperature.
  5. Sensor 17A and 17B current values.
  6. Max. and current flue gas temperature (max. can be reset by pressing D).
  7. Desired and current DHW temperature, plus DHW 1 and DHW 2 if two sensors are fitted.
  8. Desired and current supply temperature.
  9. Desired and current room temperature.
  10. Boiler coding card and scans 1 to 7.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 73. Written in our own words; check the manual for your exact model.

Scanning boiler information and temperatures

Boiler · Vitocrossal 300 CA3B Dual Fuel

The main menu groups scan data such as General, Combustion controller, Heating circuits 1 to 3, DHW, Solar energy, Reset data, Opening source licenses and Service address. Available items depend on the equipment connected and the settings made. Items include outdoor, boiler and flue gas temperatures, burner starts and hours, boiler sequence, sensors, heating program, room temperatures, mixing valve, DHW temperatures and pump status.

  1. From the home screen, tap Menu.
  2. Tap Information.
  3. Select the group you need and read the value.
  4. For solar yield values, tap the respective day of the week to show a numerical value.

Applies to: Vitocrossal 300 CA3B Dual Fuel boiler, all listed heating circuits and DHW

Source: Vitocrossal 300 Dual Fuel Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Scanning heating system information

Boiler · Vitotronic 300-K

Live temperatures and operating states are grouped under the Information menu.

  1. From the home screen tap Menu.
  2. Tap Information.
  3. Select the group: General, Burner, Heating circuit 1, 2 or 3, DHW, Solar energy, Reset data or Service address.
  4. Heating circuit names show here if they have been set.

Applies to: Vitotronic 300-K MW2C

Source: Vitotronic 300-K MW2C operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Scanning information

Boiler · Vitocrossal 300 CA3B

Shows current temperatures and operating conditions. The menu groups depend on connected components and settings.

  1. From the home screen, open Information.
  2. Choose a group: General, Combustion controller, Heating circuit 1, 2 or 3, DHW, Solar energy, Reset data, Opening source licenses or Service contact.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Scanning information groups

Boiler · Vitotrol 300A

Current temperatures and operating conditions can be scanned. Groups are General, Heating circuit 1, 2 and 3, DHW, Solar and Reset data.

  1. Open the extended menu.
  2. Select Information.
  3. Select the category, then the required scan.
  4. To show a value on the standard display, press OK on items marked Adopt with OK.

Applies to: Vitotrol 300A remote control

Source: Vitotrol 300A operating instructions, p. 19. Written in our own words; check the manual for your exact model.

Scanning options available under Information

Boiler · Vitotronic 300-K

Subject to equipment fitted, not all scans are available. Some items have further detail. Groups are General, Heating circuit 1, 2 and 3, Solar, and DHW.

  1. General: outdoor temp, boiler sequence, boiler temperature, sensors 17 A and 17 B, common supply or demand temp, sensor 9, outputs 20, 29 and 52, feed pump, central fault message, participant number, integral, input ext. EA1, external hook-up 0 to 10 V, time, date.
  2. Heating circuits 1 to 3: heating program (slab curing, external hook-up, holiday, external program, comfort mode, economy mode, heating and DHW, DHW only, standby), operating status (standard heating, reduced, standby), time program, room temperature, room and reduced room targets, external room temp, comfort target, slope, shift, heating circuit pump, mixer, supply temperature, holiday program.
  3. Solar: solar energy history, collector temp, solar DHW, solar circuit pump hours and on/off, solar energy, solar pump speed, heating suppression DHW and heating, SM1 output 22 on/off and hours, sensors 7 and 10.
  4. DHW: DHW time program, DHW circulation time program, DHW temperature or top and bottom temperatures with two sensors, DHW circulation pump, tank primary pump.

Applies to: Vitotronic 300-K MW2C

Source: Vitotronic 300-K MW2C operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Scanning solar energy yield (SM1 with Vitosolic only)

Boiler · Vitotronic 300-K

Solar yield is shown as a diagram. Only applies with solar control unit SM1 and a Vitosolic.

  1. From the home screen tap Menu.
  2. Tap Solar energy.
  3. Tap a day of the week to show the values as numbers.
  4. For pump hours and other solar scans use the extended menu under Information, Solar group.

Applies to: Vitotronic 300-K with SM1 solar control and Vitosolic

Source: Vitotronic 300-K MW2C operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Scanning system information

Boiler · Vitocrossal 300 CA3B Dual Fuel

Current temperatures and operating conditions are shown in grouped menus, depending on the components connected.

  1. Go to Menu > Information.
  2. Select the group: General, Combustion controller, Heating circuit 1-3, DHW, Solar energy, Reset data, Opening source licenses or Service address.
  3. Solar yield requires a SM1 solar control unit with Vitosolic.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Scans 2 to 7 contents

Boiler · Vitotronic 300

Scans 2 to 7 show software versions, plug-in adaptors, extension kits, remote control modes, LON data and the equipment identification code. Scan 4 is not assigned. Scans 5 and 6 need the LON module.

  1. Scan 2: software versions of plug-in adaptor, programming unit, control unit and extension kits for M2 and M3.
  2. Scan 3: software versions and operating modes of remote controls for A1, M2 and M3.
  3. Scan 5: Viessmann participant number, node address and subnet/system number (LON).
  4. Scan 6: communication coprocessor and Neuron chip software, LON participant count, SNVT configuration (LON).
  5. Scan 7: equipment identification code.

Applies to: Vitotronic 300 GW2

Source: Vitotronic 300 GW2 installation and service instructions, p. 75-76. Written in our own words; check the manual for your exact model.

Screed drying program: behaviour after cancel

Boiler · Versatronik 200

Cancelling or ending the slab curing program returns the controller to the normal operating mode, so heating continues unless the mode is changed.

  1. Cancel or let the program finish.
  2. If no heating is required, set the operating mode to Standby/OFF manually.

Applies to: Versatronik 200 slab curing

Source: Versatronik 200 installation and operating manual, p. 148. Written in our own words; check the manual for your exact model.

Screen status symbols and DEMO mode

Boiler · Vitocrossal 200 CI2

Symbols show frost protection, holiday program, and central heating mode with reduced, standard or comfort temperature (weather-compensated or constant). If DEMO shows in the navigation area, there is no central heating, no DHW heating and no frost protection.

  1. If DEMO is shown, do not rely on heating, DHW or frost protection being active.
  2. Check the symbols to confirm the current temperature level and whether the holiday program is on.

Applies to: Vitocrossal 200 CI2 control unit

Source: Vitocrossal 200 CI2 operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Select automatic DHW time program

Boiler · Vitocontrol-S, VD2/CT3/CM2

In automatic mode, domestic hot water heating runs with the central heating time program but starts 30 minutes earlier. The DHW re-circulation pump runs with the DHW time program.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the time program button until 'DHW time program' shows.
  4. Select 'Automatic?' if it is not already shown.
  5. Confirm.

Applies to: Domestic hot water time program and DHW re-circulation pump

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Select boiler size from heat loss

Boiler · Vitodens 200-W B2HB

Pick the boiler model from an accurate building heat loss calculation and check that it suits the connected radiation.

  1. Run an accurate heat loss calculation for the building.
  2. Confirm the chosen model matches the connected radiation.

Applies to: All B2HB models

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Sensor and external connection sockets

Boiler · Vitotronic 200-H

The control has a sockets for the outdoor sensor, supply sensor and external controls. The return sensor is an accessory on the supply sensor socket for underfloor systems.

  1. Connect the outdoor temperature sensor (ATS) to socket X3.
  2. Connect the supply temperature sensor to socket X6. For underfloor systems with the optional return sensor, use X6 for the supply/return sensor.
  3. Connect external controls to socket X5 (aVD). See page 13 for details.

Applies to: Vitotronic 200-H control unit

Source: Vitotronic 200-H installation and service instructions, p. 6 and p. 7. Written in our own words; check the manual for your exact model.

Sensor notes for supply and room sensing

Boiler · Vitotronic 200, Vitotronic 300-K

The supply temperature sensor can be used as a contact sensor or an immersion sensor. The room temperature sensor connects at terminals 3 and 4 in the Vitotrol 300A.

Applies to: Supply temperature sensor, Vitotrol 300A room sensor

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 90. Written in our own words; check the manual for your exact model.

Sensor wiring near high voltage

Boiler · Vitotronic 300

Long sensor runs can pick up electromagnetic interference. Keep sensor wiring away from 120/240 VAC conductors. If that is not possible, use stranded, twisted pair or shielded wire and ground only one end of the shield.

  1. Route sensor wire away from 120/240 VAC conductors.
  2. If a crossing cannot be avoided, use stranded, twisted pair or shielded wire.
  3. Ground only one end of the shield.

Applies to: All Vitotronic 300 GW2 sensor and extension wiring

Source: Vitotronic 300 Installation and Service Instructions, p. 25. Written in our own words; check the manual for your exact model.

Sensors recognized automatically

Boiler · Vitotronic 200

The flue gas temperature sensor, return water temperature sensor and fault indication module are detected by the control and need no coding. Flue gas temperature is shown and used for limit monitoring.

Applies to: Application Examples 1, 2 and 3

Source: Vitotronic 200 KW2 service instructions, p. 8, p. 11 and p. 14. Written in our own words; check the manual for your exact model.

Separate 120 VAC supply for mixing valve control and accessories

Boiler · Vitodens 200-W

Accessory power can come directly from the control and is switched by the system on/off switch. The Vitotronic 200-H, HK1B, the mixing valve accessory kit and the Solartrol control need their own 120 VAC supply from a wall receptacle.

  1. Connect accessory power at the control if it is used.
  2. Provide a separate 120 VAC wall supply for the Vitotronic 200-H, HK1B, the mixing valve kit and the Solartrol.
  3. Remember the accessory power follows the system on/off switch.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 46. Written in our own words; check the manual for your exact model.

Serial number for parts orders

Boiler · Vitodens 200-W B2HB

Replacement parts orders need the boiler serial number. Some parts do not work on earlier Vitodens 200-W B2HB versions.

  1. Have the 16-digit serial (bar code label) or the 12-digit ASME/NB serial ready; both are under the front enclosure panel.
  2. Confirm the boiler serial before ordering, because some parts are not reverse compatible.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.

Service access limits for the end user

Boiler · Vitotronic 300-K

There are no user-serviceable parts on the boiler, burner or control. Adjustments and service are for a qualified heating contractor only.

  1. Do not perform service or adjustments on system components.
  2. Have the boiler, burners and controls checked at least once per year by the original installer or a competent heating contractor.
  3. Correct defects immediately.

Applies to: Viessmann boilers with Vitotronic 300-K

Source: Vitotronic 300-K MW2C operating instructions, p. 5. Written in our own words; check the manual for your exact model.

Service address

Boiler · Vitocrossal 300 CA3B

Shows the heating contractor's service contact details if they have been entered.

  1. From the home screen, open Information.
  2. Select Service contact.
  3. If no details are shown, tap the grey field to open the keypad, then enter the contact details.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Service address entry

Boiler · Vitotronic 300-K

Heating contractor details can be scanned. Each text box is limited to 45 characters. If no details are entered, the gray fields are blank.

  1. From the home screen, tap Information.
  2. Tap Service contact details.
  3. Tap a gray field to open the keyboard and enter details.

Applies to: Heating system

Source: Vitotronic 300-K MW2C operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Service and maintenance responsibility

Boiler · Vitocrossal 300 CA3B

There are no user-serviceable parts. Service must be done by a qualified heating contractor, and annual service is required.

  1. Do not let the end user perform service on boiler, burner or control components.
  2. Follow the Service Schedule in the manual (page 41).
  3. Indirect-fired DHW storage tanks must be serviced within two years of installation and regularly after that.
  4. Clean soot build-up from the heat exchanger, since it raises flue gas temperature and reduces efficiency.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 operating instructions, p. 2, p. 8. Written in our own words; check the manual for your exact model.

Service due indication

Boiler · Vitodens 200-W, Vitotronic 200, Vitocrossal 300

When service is due, a service symbol flashes on the display with the burner hours run (for example 05500 h). The heating contractor schedules the maintenance.

  1. Note the service indication and notify the heating contractor.

Applies to: Vitotronic 200

Source: Viessmann Vitotronic 200 Operating Instructions, p. 15. Written in our own words; check the manual for your exact model.

Service equipment needed

Boiler · Vitocrossal 200 CI2

Basic tools, cleaning supplies and calibrated test equipment for servicing the boiler.

  1. Bring screwdrivers, pipe wrenches, open-ended wrenches, hex keys and a flashlight.
  2. Bring pipe sealant and approved leak detection fluid for natural gas and propane.
  3. Bring a plastic hand brush, cleaning brush, vacuum and clean rags.
  4. Bring a calibrated flue gas analyzer for % CO2 or O2, a multimeter, a gas pressure gauge (0-28 in. w.c.) and a CO meter (0-400 ppm).
  5. Bring a stack thermometer (0 to 250°F) and a way to calculate efficiency.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 Service Instructions, p. 7. Written in our own words; check the manual for your exact model.

Service interval

Boiler · Vitotronic 300-K, Vitotronic 100

The heating system must be serviced by an authorised contractor at least every 2 years.

  1. Arrange an inspection and maintenance contract with the heating contractor

Applies to: Vitotronic 300-K MW1B / Vitotronic 100 GC1B

Source: Vitotronic 300-K MW1B / Vitotronic 100 GC1B operating instructions, p. 36. Written in our own words; check the manual for your exact model.

Service interval and annual cleaning

Boiler · Vitocrossal 300 CA3B

The boiler needs a qualified service at least every 2 years, and the manual calls for the boiler to be cleaned at least once a year. Dirty heat exchangers raise flue gas temperature and reduce efficiency.

  1. Book service with a qualified heating contractor at least every 2 years.
  2. Have the boiler cleaned at least once a year.
  3. Check the service schedule in the installation and service instructions.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 41. Written in our own words; check the manual for your exact model.

Service interval and boiler cleaning

Boiler · Vitodens 200-W B2HA

Have the heating system serviced by an authorized contractor at least every 2 years. Boilers should be cleaned annually, because contamination raises flue gas temperature and energy losses. Damaged connecting cables must be replaced with Viessmann cables only.

  1. Arrange an inspection and maintenance contract with the local heating contractor.
  2. Clean the boiler annually.
  3. Replace damaged connecting cables with Viessmann cables.

Applies to: Vitodens 200-W B2HA

Source: Vitotronic 200 Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Service interval reminders

Boiler · Vitocrossal 200 CM2

Regular service keeps efficiency up and flue temperatures down.

  1. Have the heating system cleaned and serviced on a regular basis by a qualified heating contractor.
  2. Service indirect-fired domestic hot water storage tanks within two years of installation and regularly after that.
  3. Keep the boiler and boiler room clean and free of combustible materials and flammable liquids.

Applies to: All CM2 models

Source: Vitocrossal 200 CM2 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Service LED shows communication activity, not BMS traffic

Boiler · Versatronik 581 / 581D

The gateway's service LED blinks with the data exchanged between the gateway and the boilers. It does not reflect communication with the BMS. A single boiler blinks slowly while reading boiler data and faster while reading cascade data. A multi-boiler system blinks at a more uniform rate.

Applies to: Versatronik 581 gateway, all supported boiler controls

Source: Versatronik 581 LON gateway manual, p. 13. Written in our own words; check the manual for your exact model.

Service lockout before working on the control

Boiler · Versatronik 10.WB1

The control has more than one live circuit. Power to the control and to the damper or blower must be off before any servicing. The control has no user-serviceable parts.

  1. Turn off power to the control.
  2. Turn off power to the damper or blower.
  3. Verify all circuits are de-energised before touching terminals.
  4. Leave repairs of the control to qualified service personnel.

Applies to: Versatronik 10.WB1 service

Source: Versatronik 10.WB1 installation and operating manual, p. 4. Written in our own words; check the manual for your exact model.

Service menu overview (single boiler)

Boiler · Vitocrossal 200 CI2

Top level menus: Diagnosis (General, Burner, Heating circuits 1 to 4, DHW, Communication module, Heating zones 1 to 4, Actuator test, System configuration, Message history); Service functions (Reset service, Filling, Air vent valve, System information, Connectivity information, Test Mode, Emissions Test Mode, High Limit Safety Cut-out Test); Change passwords; Commissioning; Appliances detected; Exit service; Access point on/off.

Applies to: Vitocrossal 200 CI2 service menu

Source: Vitocrossal 200 CI2 Service Instructions, p. 54. Written in our own words; check the manual for your exact model.

Service message if service is postponed

Boiler · Vitodens 100-W B1HE/B1KE

If the service cannot be done on the due date, the service message comes back the following Monday.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Service only by licensed heating contractor, power and fuel isolation

Boiler · Vitorond 100

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor. There are no user serviceable parts on the boiler, burner or control.

  1. Disconnect main power to the boiler, heating system and all external controls before working.
  2. Close the main fuel supply valve. The manual text says gas supply valve, but this is an oil-fired boiler.
  3. Take precautions to prevent accidental power activation during service work.
  4. Verify field supplied controls such as low water cut-offs, pumps, motorized valves, air vents and thermostats.

Applies to: Vitorond 100 oil-fired boiler

Source: Viessmann Vitorond 100 installation and service manual, p. 5. Written in our own words; check the manual for your exact model.

Service required code 0f

Boiler · Vitocrossal 300 CA3B Dual Fuel

Code 0f is shown only in the fault history. It means service is due.

  1. Service the boiler.
  2. After servicing, set code 24:0.

Applies to: Vitocrossal 300 CA3B Dual Fuel

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 122. Written in our own words; check the manual for your exact model.

Service restricted to qualified technicians

Boiler · Vitocrossal 300 CU3A

There are no user-serviceable parts on the boiler, burner or control. Adjustments, service and installation of replacement components must be done by a qualified or licensed heating contractor.

  1. Do not allow the end user to adjust or service boiler, burner or controls.
  2. Use only components tested with this heating system.

Applies to: Vitocrossal 300 CU3A, all models

Source: Vitocrossal 300 CU3A operating instructions, p. 2, p. 7, p. 8. Written in our own words; check the manual for your exact model.

Service restriction

Boiler · Vitorond 200, VD2A

Installation, adjustment, service and maintenance must be done by a licensed heating contractor. There are no user-serviceable parts on the boiler, burner or control.

  1. Turn off main power and close the main fuel supply valve before any service work.
  2. Use only original Viessmann or Viessmann-approved replacement parts.

Applies to: Vitorond 200 VD2A, all sizes

Source: Vitorond 200 VD2A Technical Data Manual, p. 2. Written in our own words; check the manual for your exact model.

Set a time program for a heating circuit

Boiler · Vitocrossal 200 CI2

Each time program allows up to 4 time phases per day. Outside the phases the system drops to the reduced level. DHW is not heated between phases, and DHW tank frost protection stays active. Allow time for the DHW tank to reach temperature before the phase starts.

  1. Select the heating circuit in the menu bar.
  2. Open the time program and select the day.
  3. Set Start and End for time phase 1 and choose the temperature level (Standard or Comfort).
  4. Add time phase 2 if needed, set Start and End, and choose the level.
  5. Confirm and exit the time program.

Applies to: Central heating and DHW time programs

Source: Vitocrossal 200 CI2 Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Set an individual DHW time program

Boiler · Vitocontrol-S, VD2/CT3/CM2

Use this instead of automatic mode when DHW timing must be set separately. The same steps apply to the DHW re-circulation pump.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the time program button until 'DHW time program' shows.
  4. Select 'Individual?' if it is not already shown.
  5. Confirm.
  6. Choose '1-7' for identical days, or a weekday for individual days, then confirm.
  7. Set DHW phase 1 ON time, confirm, set phase 1 OFF time, confirm.
  8. Repeat for DHW phases 2 to 4.
  9. Close the hinged cover.

Applies to: Domestic hot water time program and DHW re-circulation pump

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, pp. 18-19. Written in our own words; check the manual for your exact model.

Set the holiday departure and return dates

Boiler · Vitocontrol-S, VD2/CT3/CM2

Enter the dates for the holiday program. The return date defaults to the day after departure.

  1. Open the cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the holiday program button; the 'Holiday program' display appears.
  4. Press the confirm button; the departure date shows.
  5. Adjust with up or down until the departure date is correct.
  6. Confirm; the return date shows. Adjust with up or down until it is correct.
  7. Confirm; the display returns to the boiler temperature.
  8. To set the holiday reduced temperature (rw program only), press the temperature button, adjust, and confirm.
  9. Close the hinged cover.

Applies to: Holiday program

Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, p. 22. Written in our own words; check the manual for your exact model.

Shielding and separation of field wiring

Boiler · Versatronik 502 & 502D

When extending wire there is a risk of electromagnetic interference. Keep runs away from 120/240 VAC conductors.

  1. Route low-voltage communication wiring away from 120/240 VAC conductors.
  2. If the run must be near high-voltage wiring, use stranded twisted-pair shielded cable.
  3. Ground only one end of the shield.

Applies to: Versatronik 502 and 502D field wiring

Source: Versatronik 502 NR2 Modbus manual, p. 5. Written in our own words; check the manual for your exact model.

Show acknowledged faults

Boiler · Vitodens 200-W B2HA

Acknowledged faults are shown as a list in the standard menu.

  1. Select Fault in the standard menu.
  2. Review the list of current faults.

Applies to: Vitodens 200-W B2HA 45, 60

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 70. Written in our own words; check the manual for your exact model.

Show Viessmann fault codes as hex in a BMS

Boiler · Versatronik 515 / 515D

The gateway sends fault codes as decimal values. Use the BMS to convert them into hex or text for display.

  1. Use a numeric bit-and object with a mask to show the value in hexadecimal.
  2. Use a numeric-to-enum object with the full Viessmann code range to get the text.
  3. Bind a label on the webpage to the converted slot values.

Applies to: Niagara AX / KitControl based BMS

Source: Versatronik 515 and 515D BACIP Type B gateway manual, p. 19. Written in our own words; check the manual for your exact model.

Showing Viessmann fault codes in hex on the BMS

Boiler · Versatronik 511 / 511D

The gateway sends fault codes as decimal numbers. To read them as the hex codes shown on the boiler, mask the value in hex and map the decimal values to the code text in the BMS.

  1. Convert the decimal fault value to hex using a Numeric Bit And object with a mask input.
  2. Build an enum range in a Numeric To Enum object listing every Viessmann code.
  3. Point a bound label on the webpage at the matching slot values.

Applies to: Niagara AX or similar BMS with KitControl objects

Source: Versatronik 511 & 511D LON Type B manual, p. 17. Written in our own words; check the manual for your exact model.

Showing Viessmann fault codes in hex or as text on the BMS

Boiler · Versatronik 501 / 501D LON

The gateway sends fault codes as a decimal SNVT_count value, but Viessmann controls show them in hexadecimal. Decode them in the BMS software, for example in Niagara AX.

  1. Use a mask object (Numeric Bit And in KitControl Util) to show the code in hexadecimal.
  2. To show the fault text, use a Numeric To Enum conversion (KitControl Conversion) and enter the enum range for all Viessmann error codes.
  3. Point a Bound Label on the px webpage at the matching slot values to display the text.

Applies to: Versatronik 501 / 501D LON gateway fault display

Source: Versatronik 501 LON communication manual, p. 24. Written in our own words; check the manual for your exact model.

Shut down the boiler without frost protection

Boiler · Vitodens 100-W B1HE/B1KE

In this state, frost protection for the boiler and DHW tank is not active. Pumps and diverter valves may seize if left unpowered. Outside temperatures below 37°F (3°C) need frost protection measures.

  1. Turn off the ON/OFF switch.
  2. Close the gas shut-off valve and secure it against unauthorized reopening.
  3. Protect the system from frost if outside temperatures below 37°F (3°C) are expected. Contact the contractor if needed.
  4. After a long shutdown, reset the time and date.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Shutting off gas to the appliance

Boiler · Vitodens 200-W

Use this procedure to isolate the boiler from gas before service.

  1. Set the thermostat or control to its lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed.
  3. Close the main manual gas shut-off valve.

Applies to: Vitodens 200-W B2HA

Source: Vitodens 200-W B2HA service instructions, p. 106. Written in our own words; check the manual for your exact model.

Side wall vent protective screen

Boiler · Vitocrossal 300 CU3A

Side wall vent installations need the Viessmann protective screen.

  1. Install the Viessmann protective screen on any side wall vent installation.

Applies to: Vitocrossal 300 CU3A side wall venting

Source: Vitocrossal 300 CU3A technical data manual, p. 18. Written in our own words; check the manual for your exact model.

Side-wall coaxial vent installation rules

Boiler · Vitocrossal 300 CU3A

Do not exceed the maximum equivalent vent length in the Vitocrossal 300 CU3A venting system instructions. Do not common-vent the boiler with any other appliance. A Viessmann protective screen is required on side-wall coaxial vent installations.

  1. Check the equivalent vent length against the venting system instructions.
  2. Do not common-vent with any other appliance.
  3. Install the Viessmann protective screen on side-wall coaxial vents.

Applies to: Vitocrossal 300 CU3A side-wall coaxial venting

Source: Vitocrossal 300 CU3A Installation Instructions, p. 55. Written in our own words; check the manual for your exact model.

Size DHW supply and return piping correctly

Boiler · Vitodens 100-W B1HE/B1KE

DHW piping between the boiler and a Viessmann DHW tank must be at least 1-1/4 in nominal diameter. Undersized piping can cause short-cycling and poor DHW supply. Non-Viessmann tanks need coil pressure-drop calculations against pump head.

  1. Use at least 1-1/4 in nominal pipe between boiler DHW connections and the DHW tank connections.
  2. For non-Viessmann DHW tanks, calculate the tank coil pressure drop against the boiler pump head.
  3. Confirm enough water flow to the boiler heat exchanger.

Applies to: DHW storage tank piping

Source: Viessmann Vitodens 100-W B1HE/B1KE Combi Installation and Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

Slab curing display

Boiler · Vitotronic 200-H

If slab curing is coded, this display stays on until the function ends.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Slab curing function (mixing valve circuit only)

Boiler · Vitotronic 300

Slab curing runs for 30 days and can use one of four temperature curves selected via coding address F1. When the 30 days end, the mixing valve circuit returns to its normal preset parameters.

  1. Select the curve with coding F1 before activating slab curing.
  2. Confirm the mixing valve circuit pump is running and supply follows the selected curve.
  3. Note the date, as the function stops automatically after 30 days.

Applies to: Mixing valve heating circuit with underfloor heating

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 88. Written in our own words; check the manual for your exact model.

Smell of gas

Boiler · Vitocrossal 300 CA3B

Gas smell is an immediate hazard. Do not start the appliance and do not use switches or phones in the building.

  1. Do not try to light any appliance.
  2. Do not touch any electrical switches.
  3. Do not use any phone in the building.
  4. Call the gas supplier from a neighbor's phone and follow their instructions.
  5. If the gas supplier cannot be reached, call the fire department.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 1, p. 6. Written in our own words; check the manual for your exact model.

Solar energy yield

Boiler · Vitocrossal 300 CA3B

Only applies with a solar control unit type SM1 or a Vitosolic solar control unit. The yield is shown as a diagram. Tap a day of the week to see the figure as a number.

  1. From the home screen, open Solar energy.
  2. Tap the required day of the week to show the value as a number.

Applies to: Vitocrossal 300 CA3B with solar control unit SM1 or Vitosolic

Source: Vitocrossal 300 CA3B operating instructions, p. 31. Written in our own words; check the manual for your exact model.

Solar energy yield display

Boiler · Vitotronic 300-K

Only with solar control unit type SM1 and a Vitosolic solar control unit. The yield is shown as a diagram; tap a day to see numbers.

  1. From the home screen, tap Solar energy.
  2. Tap the required day of the week to show values in numerical form.

Applies to: Solar thermal systems with SM1 and Vitosolic

Source: Vitotronic 300-K MW2C operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Some settings can be changed at the Vitotrol 200 remote

Boiler · Vitotronic 200-H

If the system has a Vitotrol 200 remote control, a few adjustments can also be made there. The control unit itself is used for all settings.

Applies to: Vitotronic 200-H HK1M with Vitotrol 200

Source: Vitotronic 200-H operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Spring return dampers need no relay

Boiler · Vitotronic 100 GC1

Spring return combustion air dampers do not need the field-supplied relay.

Applies to: Spring return combustion air dampers

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 56. Written in our own words; check the manual for your exact model.

Standard and reduced heating mode

Boiler · Vitotronic 300-K

In the Heating and DHW program the operating status switches between standard and reduced heating mode. The change times are set in the time program.

  1. Set the times in the time program to control when standard and reduced heating mode switch

Applies to: Vitotronic 300-K MW1B

Source: Vitotronic 300-K MW1B / Vitotronic 100 GC1B operating instructions, p. 40. Written in our own words; check the manual for your exact model.

Standard and reduced heating operating status

Boiler · Vitotronic 300-K

In the Heating and DHW program, the operating status switches between standard heating mode and reduced heating mode. The switching times come from the time program. Standard mode heats to the standard room temperature during occupied periods. Reduced mode heats to the lower room temperature during absence or night setback.

Applies to: Heating and DHW operating program with time program

Source: Vitotronic 300-K, MW2C operating instructions, p. 33. Written in our own words; check the manual for your exact model.

Standard boiler equipment and separately ordered items

Boiler · Vitorond 100 VR1

The boiler shell includes insulation for VR1 22 to 33 and 91 to 140. Standard equipment includes a 30 psig pressure relief valve, a drain valve and installation fittings. Burners and controls are purchased separately. The boiler stand must be ordered separately.

Applies to: All VR1 sizes

Source: Vitorond 100 VR1 technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Standard display symbols

Boiler · Vitotrol 300A

Symbols appear depending on system version and operating state: frost protection monitoring, central heating with standard or reduced room temperature, party mode, economy mode, solar circuit pump running (with solar systems), current time, and 2 for service message.

Applies to: Vitotrol 300A standard display

Source: Vitotrol 300A operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Standard equipment cartons and loose parts

Boiler · Vitorond 200 VD2A

The boiler ships as cast iron sections on skids with several cartons: supply and return headers, insulation panels and cleaning brushes, the boiler control, and installation fittings with safety header. Turbulators and sealing materials are packed inside the combustion chamber.

  1. Check the cartons against the packing list before installation.
  2. Find the turbulators, bagged, inside the combustion chamber.
  3. If sections ship separately, find the push nipples, high temperature silicone and linseed oil graphite sealant inside the combustion chamber.

Applies to: Vitorond 200 VD2A delivery

Source: vitorond 200 VD2A technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Standard equipment in the box

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

Standard supply includes the wall-mount boiler and installation fittings, 30 psi pressure relief valve, pressure gauge, two fill/drain valves, mounting hardware, outdoor temperature sensor, and an LPG conversion labelling kit.

Applies to: Vitodens 100-W B1HE and B1KE

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, p. 3. Written in our own words; check the manual for your exact model.

Standard heating mode vs reduced heating mode

Boiler · Vitotronic 300-K

Standard heating mode heats rooms to the standard room temperature for periods when occupied. Reduced heating mode heats to the reduced room temperature for absences or nights. The time program sets when the status changes in the heating-and-DHW operating program.

Applies to: Heating program, time program

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 33. Written in our own words; check the manual for your exact model.

Standby mode

Boiler · Vitodens 100-W B1HE/B1KE

In standby the boiler is switched off. Only the frost protection of the boiler and the DHW tank is active. There is no central heating and no DHW heating.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE Operating Instructions, p. 35. Written in our own words; check the manual for your exact model.

Static and EMI precautions

Boiler · Versatronik 200

Static-sensitive components can be damaged by poor handling inside the control, so take anti-static measures. Sensor and extension wiring can pick up electromagnetic interference. Use stranded, twisted-pair shielded wire where high-voltage conductors cannot be avoided, and ground only one end of the shield.

  1. Discharge static before working inside the control.
  2. Use shielded twisted-pair wire if running near 120/240 VAC.
  3. Ground only one end of the shield.

Applies to: Versatronik 200 control and sensor wiring

Source: Versatronik 200 installation manual, p. 3 and p. 12. Written in our own words; check the manual for your exact model.

Static discharge when opening the control

Boiler · Vitotronic 200-H

Static discharge to the internal components must never occur when working on an opened control.

  1. Discharge static before touching internal components of the opened control.

Applies to: Vitotronic 200-H control unit

Source: Vitotronic 200-H installation and service instructions, p. 5. Written in our own words; check the manual for your exact model.

Static sensitive components

Boiler · Versatronik 511 / 511D

Static can damage the control boards. Take all measures to avoid static build-up before working inside the control.

Applies to: Versatronik 511 gateway and boiler controls

Source: Versatronik 511 and 511D LON Type B manual, p. 2. Written in our own words; check the manual for your exact model.

Static sensitive control board

Boiler · Vitotronic 100

The control is sensitive to static discharge. Static can damage internal components whenever the control is opened or handled.

  1. Follow electro-static discharge precautions before touching the control or its internal parts.
  2. Avoid static discharge to internal components when the control is open.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 5 and p. 6. Written in our own words; check the manual for your exact model.

Static-sensitive components

Boiler · Versatronik 10.WB1

Static discharge can damage components inside the control.

  1. Eliminate static build-up before handling or working inside the control.

Applies to: Versatronik 10.WB1 control board

Source: Versatronik 10.WB1 installation and operating manual, p. 3. Written in our own words; check the manual for your exact model.

Static-sensitive electronics

Boiler · Versatronik COMO OT

The control contains static-sensitive components that can be damaged by careless handling. Take anti-static precautions when working inside the control.

  1. Minimise static build-up before touching the inside of the control.

Applies to: Versatronik COMO OT room controller

Source: Versatronik COMO OT installation and operating manual, p. 3. Written in our own words; check the manual for your exact model.

Status light meaning on the gateway

Boiler · Versatronik 515 / 515D

The gateway status light shows communication state. Flashing means communication is on. Solid or off means there is no communication.

  1. If the light is solid or off, check the gateway power and the BACnet/LON and control cabling.

Applies to: Versatronik 515 gateway

Source: Versatronik 515 and 515D BACIP Type B gateway manual, p. 16. Written in our own words; check the manual for your exact model.

Subscriber check timing

Boiler · Versatronik 505 NR2/BACIP, Versatronik 505D NR2/BACIP

Re-entering the subscriber check too soon shows No Subscriber. Wait some time before trying again, because devices can take a while to report back.

  1. Wait, then re-enter the Subscriber Check.

Applies to: Vitocontrol-S cascade participant check

Source: Versatronik 505 and 505D BACnet IP manual, p. 16. Written in our own words; check the manual for your exact model.

Summary of system versions 1 to 10 and installation notes

Boiler · Vitotronic 100 GC1, Vitocontrol-S VD2/CT3/CM2

The manual lists ten heating system designs with boiler types such as Vitorond 200 and Vitocrossal 200/300. The drawings are simplified concepts only. Piping and components must be verified in the field, and a low water cut off (LWCO) must be fitted where local codes require it. The heating contractor is responsible for field installation and function.

  1. Pick the system version that matches the boiler type and piping layout.
  2. Verify the piping and all components in the field.
  3. Install a low water cut off where required by local codes.

Applies to: All system versions 1 to 10

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.

Summer mode (DHW only)

Boiler · Vitotronic 300-K

Summer mode uses the DHW only operating program. Central heating is off, and the boiler stays available for DHW heating.

Applies to: DHW only operating program

Source: Vitotronic 300-K, MW2C operating instructions, p. 35. Written in our own words; check the manual for your exact model.

Summer mode switch function

Boiler · Vitotronic 100

In the up (summer/winter) position the thermostat terminal can call for heat, DHW works and outdoor reset works if programmed. Outdoor reset follows the warm weather shut-down setting. In the down (summer/DHW) position the thermostat call for heat is disabled.

  1. Set the summer mode switch up for normal winter heating calls.
  2. Set the switch down to block room thermostat heat calls while keeping DHW.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B installation manual, p. 11. Written in our own words; check the manual for your exact model.

Summer mode switch positions

Boiler · Vitotronic 100

Up (summer/winter) lets the thermostat call for heat, DHW and outdoor reset. Down (summer/DHW) disables the thermostat heat call. With an outdoor sensor and internal outdoor reset or OpenTherm thermostat, the control starts calculating boiler water temperature at 37 °F (3 °C) outdoor and below, and the pump runs continuously.

Applies to: Vitotronic 100 KW10B

Source: Vitotronic 100 KW10B operating manual, p. 5. Written in our own words; check the manual for your exact model.

Summer mode: heating off, DHW on

Boiler · Vitocrossal 200 CI2

In warm months heating can be switched off while DHW heating continues. Central heating is off and only the DHW heating remains in operation.

  1. Select the DHW operating program set to On.
  2. Select Standby mode for the heating operation.
  3. Confirm that DHW heating still runs and central heating is off.

Applies to: Summer operation of the boiler

Source: Vitocrossal 200 CI2 Operating Instructions, p. 42-44. Written in our own words; check the manual for your exact model.

Summer stand-by and exercise timer

Boiler · Vitotron 100 VLN2

Keep power on during summer and leave the controller in stand-by between heating seasons. The exercise timer runs the pump for 15 minutes each day to prevent debris buildup.

  1. Do not shut off the 120VAC or 240VAC power supply between heating seasons.
  2. Leave the controller in stand-by (summer) mode.
  3. Confirm the pump exercise cycle runs about 15 minutes each day.

Applies to: Vitotron 100 VLN2

Source: Vitotron 100 installation and service instructions, p. 3. Written in our own words; check the manual for your exact model.

Support and brace the vent system

Boiler · Vitocrossal 200 CI2

The boiler is not designed to carry the weight of the vent system.

  1. Support the vent system with a suitable support system for its weight and design.
  2. Brace the installation to keep it stable.
  3. Secure PP(s) termination elbows as the manufacturer specifies.

Applies to: All vent installations

Source: Vitocrossal 200 CI2 Installation manual, p. 58, 60. Written in our own words; check the manual for your exact model.

Switch increased DHW hygiene off

Boiler · Vitocrossal 200 CI2

Stops the scheduled high-temperature DHW heating cycle.

  1. Open the DHW settings from the home screen.
  2. Select 'Hygiene function'.
  3. Deselect the highlighted day, or every day.
  4. Confirm.

Applies to: DHW tank without temperature switch

Source: Vitocrossal 200 CI2 operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Switch increased DHW hygiene on

Boiler · Vitocrossal 200 CI2

Heats the DHW tank above 140°F (60°C) once a week or for an hour every day, at the set start time. Not valid for systems with a DHW tank with a temperature switch (e.g. Aquastat).

  1. Open the DHW settings from the home screen.
  2. Select 'Hygiene function'.
  3. Set the starting time under 'Start'.
  4. Select the required day, or every day. The selection is highlighted.
  5. Confirm.

Applies to: DHW tank without temperature switch

Source: Vitocrossal 200 CI2 operating instructions, p. 24. Written in our own words; check the manual for your exact model.

Switch on the access point for communication module licences

Boiler · Vitocrossal 200 CI2

The access point lets a phone or PC reach the online legal information, such as open source licences. The WiFi credentials are on the label on the control unit.

  1. Open Settings, then 'Internet', then 'Access point'.
  2. Select 'ON' and confirm.
  3. Follow the instructions in the mobile app.
  4. Connect a phone or PC to the WiFi network 'Viessmann-<xxxx>' and enter the WiFi password.
  5. Open http://192.168.0.1 in a browser and follow the 'Open Source Components Licences' link.

Applies to: Communication module

Source: Vitocrossal 200 CI2 operating instructions, p. 32. Written in our own words; check the manual for your exact model.

Switch the display off for cleaning

Boiler · Vitocrossal 200 CI2

The display is deactivated for 30 seconds to prevent accidental operation. Clean it with a microfiber cloth.

  1. Open Settings.
  2. Select 'Clean screen'.
  3. Clean the display during the 30-second countdown.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 30. Written in our own words; check the manual for your exact model.

System example 08 overview

Boiler · Versatronik 200

Cascade control of up to eight OpenTherm boilers over CAN bus. The heating system manager sets the boiler set point and the boilers modulate to reach it. Includes outdoor reset, common supply sensor, low loss header or hydraulic separator, DHW production and DHW recirc pump. No space heating control in this example. The common supply pump is run from the heating system manager.

Applies to: System example 08

Source: Versatronik 200 installation and operating manual, p. 42. Written in our own words; check the manual for your exact model.

System example 09 overview

Boiler · Versatronik 200

Cascade control of OpenTherm boilers 1 to 8 with the boiler set point from the heating system manager. Includes outdoor reset, a dry contact demand for standby boiler and boiler pump, primary side LLH or hydraulic separator pump on multifunction 3, DHW production from the secondary side header, DHW recirc pump on multifunction 4, two heating circuits with mixing valves and optional remote controls for both mixing valves.

Applies to: System example 09

Source: Versatronik 200 installation and operating manual, p. 45. Written in our own words; check the manual for your exact model.

System example 11 overview (0-10 V controller)

Boiler · Versatronik 200

Boiler operation is set by a 0-10 VDC signal from the heating system manager, and that signal sets the boiler temperature set point. Includes outdoor reset, primary side LLH or hydraulic separator pump on multifunction 3, DHW production from the secondary side header, DHW recirc pump on multifunction 4, two heating circuits with mixing valves, and optional remote controls for both mixing valves.

Applies to: System example 11

Source: Versatronik 200 installation and operating manual, p. 48. Written in our own words; check the manual for your exact model.

System layout 1: direct heating circuit with integrated DHW

Boiler · Vitodens 222-F

Boiler feeds one radiator (high-temperature) circuit directly and makes domestic hot water in the integrated tank. Use this layout only when the heating circuit flow stays below the boiler's maximum water flow rate.

  1. Confirm the heating circuit flow is below the boiler maximum flow rate listed on page 30.
  2. If flow is above that limit or unknown, add a low-loss header (see system layout 2).
  3. Wire the boiler pump, DHW circulating pump and outdoor sensor as shown in the layout legend.

Applies to: Vitodens 222-F B2TB, integrated DHW, radiator circuit

Source: Vitodens 222-F, B2TB installation instructions, p. 32. Written in our own words; check the manual for your exact model.

System layout 2: low-loss header when heating flow is high

Boiler · Vitodens 222-F

Used when the heating circuit flow is greater than the boiler's maximum water flow rate. The low-loss header is a separate accessory and includes a Viessmann temperature sensor and a heating circuit pump.

  1. Install the low-loss header (accessory) between boiler and heating circuit.
  2. Fit the Viessmann temperature sensor to the low-loss header.
  3. Check the heating circuit pump and boiler pump are wired as shown in the legend.
  4. Keep the pressure relief valve outlet piped to a suitable drain.

Applies to: Vitodens 222-F B2TB, radiator circuit with high flow

Source: Vitodens 222-F, B2TB installation instructions, p. 33. Written in our own words; check the manual for your exact model.

System layout 3: underfloor heating with system separation

Boiler · Vitodens 222-F

Underfloor heating with a 3-way mixing valve and a plate heat exchanger for system separation. Required when the underfloor tubing is non-oxygen diffusion barrier type.

  1. Install a plate heat exchanger to separate the underfloor circuit from the boiler water when using non-oxygen diffusion barrier tubing.
  2. Make sure all components on the secondary side of the heat exchanger are corrosion-resistant.
  3. Install the accessory kit for the heating circuit with mixing valve and fit the mixing valve temperature sensor.
  4. Use a low-loss header if the system water flow rate is unknown.

Applies to: Vitodens 222-F B2TB, underfloor heating (low-temperature circuit)

Source: Vitodens 222-F, B2TB installation instructions, p. 34. Written in our own words; check the manual for your exact model.

System layout 4: radiator and underfloor circuits together

Boiler · Vitodens 222-F

Combines a direct radiator circuit with an underfloor circuit that uses a mixing valve. The radiator circuit flow must be at least 30% higher than the underfloor circuit flow.

  1. Verify the radiator circuit flow is at least 30% greater than the underfloor circuit flow.
  2. Verify the combined flow of both circuits is below the boiler maximum flow rate on page 30; otherwise use a low-loss header.
  3. Install the accessory kit for the mixing valve and the mixing valve temperature sensor.

Applies to: Vitodens 222-F B2TB, mixed radiator and underfloor circuits

Source: Vitodens 222-F, B2TB installation instructions, p. 35. Written in our own words; check the manual for your exact model.

System layout 8: three zone circuits with DHW

Boiler · Vitodens 222-F

Three zone circuits fed from a low-loss header, with zone circuit outputs on the AM1 extension module (accessory) and one zone circuit on the boiler's own output.

  1. Install the AM1 extension module (accessory) for zone circuits 2 and 3.
  2. Connect the thermostats for zone circuits 1, 2 and 3 to their outputs as shown in the legend.
  3. Use a low-loss header where the total flow exceeds the boiler maximum.
  4. For underfloor zones, install a 3-way mixing valve kit and use system separation with non-oxygen diffusion barrier tubing.

Applies to: Vitodens 222-F, three zone circuits

Source: Vitodens 222-F, B2TB installation instructions, p. 39. Written in our own words; check the manual for your exact model.

System layouts 5 to 7: combined circuits and low-loss header

Boiler · Vitodens 222-F

Layouts with two or more heating circuits, some with mixing valves, where total flow can exceed the boiler maximum. A low-loss header is strongly recommended in these layouts.

  1. Calculate the total flow of all heating circuits and compare with the boiler maximum on page 30.
  2. Install a low-loss header (accessory) if the total flow exceeds the boiler maximum.
  3. For layout 6, install a plate exchanger for system separation on the underfloor side.
  4. For layout 7, connect the Vitotronic 200-H HK1B controller for the extra circuit and the AM1 extension module as needed.

Applies to: Vitodens 222-F B2TB, multiple heating circuits

Source: Vitodens 222-F, B2TB installation instructions, pp. 36-38. Written in our own words; check the manual for your exact model.

Technical literature that must stay with the boiler

Boiler · Vitorond 200 VD2

Leave all literature at the site and tell the owner where it is kept. The set includes the technical data manual, installation instructions, service instructions, operating instructions, control manuals and any other Viessmann product instructions used.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200 VD2 Service Instructions, p. 6. Written in our own words; check the manual for your exact model.

Telephone switch to force heating mode

Boiler · Versatronik 200

A short between the remote control terminals switches the heating circuit to heating mode and activates DHW if fitted. When the short is removed, the controller goes back to its set program.

  1. Connect the switch to terminal 6 with GND at HC1, or to terminal 13 with GND at HC2.
  2. If a remote control is used, connect the switch at the operating module.

Applies to: Versatronik 200 heating circuits

Source: Versatronik 200 installation and operating manual, p. 62. Written in our own words; check the manual for your exact model.

Temperature tempering valve in DHW supply

Boiler · Vitodens 200-W

Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. Install a temperature tempering valve in the DHW supply line.

Applies to: DHW supply piping

Source: Vitodens 200-W B2HA installation manual, p. 32. Written in our own words; check the manual for your exact model.

Temperature units

Boiler · Vitocrossal 300 CA3B

Switches the display between metric and imperial units.

  1. From the home screen, select Settings.
  2. Select Temperature units.
  3. Select Metric or Imperial.
  4. Confirm.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 30. Written in our own words; check the manual for your exact model.

Terminal designations must not be changed

Boiler · Switching Module-V

Do not change the designation of the connections to the Switching Module-V terminals.

Applies to: Switching Module-V

Source: Switching Module-V installation instructions, p. 2. Written in our own words; check the manual for your exact model.

Terminology: set temperature and actual temperature

Boiler · Vitodens 200-W B2HA

Set temperature is the target value to be reached, for example the set boiler temperature. Actual temperature is the value at the time of the scan, for example the actual boiler temperature.

Applies to: Vitotronic 200 display values

Source: Vitotronic 200 Operating Instructions, p. 18. Written in our own words; check the manual for your exact model.

Test equipment needed

Boiler · Vitodens 222-F

Use calibrated equipment only.

  1. Use a multimeter for 0-230 V AC, 0-12 A AC and 0-100 mA DC.
  2. Use a flue gas analyzer that measures CO2 or O2.
  3. Use a manometer for gas pressure from 0 to 11 in. w.c., and up to 28 in. w.c. (a non-electric Magnehelic gauge can also be used).
  4. Use a stack thermometer rated 0 to 500 °F (0 to 260 °C).
  5. Use a CO meter rated 0 to 400 ppm.
  6. Use a Bacharach calculator or suitable tables to work out efficiency.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB service instructions, p. 6. Written in our own words; check the manual for your exact model.

Test equipment needed for service

Boiler · Vitocrossal 300 CA3B

Bring calibrated instruments only. The manual lists the following for combustion and gas checks.

  1. Bring a flue gas analyzer that measures % CO2 or O2.
  2. Bring a multimeter for 0-120 VAC, 0-25 A AC and 0-100 microamps DC.
  3. Bring a gas pressure gauge that reads 0 to 28 in. w.c. (a non-electric Magnehelic gauge at 0 to 10 psig also works).
  4. Bring a carbon monoxide meter that reads 0 to 400 ppm.
  5. Bring a stack thermometer that reads 0°F to 250°F (0°C to 121°C).
  6. Bring a 1/8 in. NPT male to 1/4 in. barb adaptor and tubing for pressure readings.
  7. Bring a leak detection fluid approved for natural gas and propane.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 7. Written in our own words; check the manual for your exact model.

Test equipment needed for start-up

Boiler · Vitodens 100-W WB1B

Use calibrated equipment only. Needed: multimeter (0-12A, 120V and resistance); flue gas analyzer for CO2 or O2; manometer for gas pressure 0 to 11 in. w.c. (accurate) and up to 28 in. w.c. (a Magnehelic may be used); stack thermometer 0 to 500°F (0 to 260°C); efficiency calculator or tables; CO meter 0 to 400 ppm. Also leak detection fluid approved for natural gas, pipe joint sealant, a garden hose for bleeding and pressure testing, plastic hand brush and rags.

Applies to: Vitodens 100-W WB1B start-up and service

Source: Viessmann Vitodens 100-W WB1B installation and service manual, p. 53. Written in our own words; check the manual for your exact model.

Therm-control (return temperature)

Boiler · Vitotronic 300

If the boiler return temperature drops below the set-point read by the therm-control sensor, heating circuit output is reduced. Mixing valves close until the therm-control sensor is satisfied.

  1. Check the therm-control sensor reading against the set-point when return temperature is low.
  2. Verify the mixing valves close when the sensor is satisfied.

Applies to: Heating circuits with therm-control

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 88. Written in our own words; check the manual for your exact model.

Thermostat location

Boiler · Vitorond 100

Mount the room thermostat on an inside wall away from drafts, hot or cold water pipes, lights, television, sun, or fireplaces.

  1. Pick an inside wall clear of drafts, pipes, lights and heat sources.
  2. Follow the thermostat instructions.

Applies to: Room thermostat installation

Source: Vitorond 100 VR1 installation and service manual, p. 29. Written in our own words; check the manual for your exact model.

Three-phase equipment needs additional power contactors

Boiler · Vitotronic 300

Three-phase pumps or equipment connected to the system must be switched through additional power contactors, not directly from the control unit.

  1. Connect any three-phase equipment through separate power contactors.
  2. Confirm the wiring against the circuit diagram supplied for the system.

Applies to: Vitotronic 300, Model GW2 system types

Source: Vitotronic 300 GW2 installation and service instructions, p. 7. Written in our own words; check the manual for your exact model.

Three-phase equipment wiring

Boiler · Vitotronic 100, GC1

Three-phase equipment must be connected through additional power contactors.

  1. Install additional power contactors for any three-phase equipment in the system.

Applies to: All circuit diagrams 5 to 9

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

Time master and DCF receiver behaviour

Boiler · Versatronik 200

Only one controller on the BUS can be the time master. When a time master or DCF radio receiver is in the system, the time is blanked on the other controllers. A DCF receiver keeps the time correct. Without DCF, the clock can drift by up to 2 minutes per month.

  1. Correct the time manually if it drifts, when no DCF receiver is connected.

Applies to: Multi-controller BUS systems

Source: Versatronik 200 installation and operating manual, p. 134. Written in our own words; check the manual for your exact model.

Time program setup method

Boiler · Vitotronic 300-K

Each time program day can have up to 4 time phases, each with its own start and end. Outside the time phases, the system uses reduced temperature.

  1. From the home screen, select the heating circuit, then time program heating.
  2. Select the day, then set the start and end points for each time phase.
  3. Use add to create more phases, then confirm.
  4. To copy a day's program, select the day, use copy, pick the target days and confirm.
  5. To change or delete a phase, select the day, select the phase and edit or delete it, then confirm.

Applies to: Central heating, DHW heating and DHW recirculation pump

Source: Vitotronic 300-K MW2C operating instructions, p. 11-12. Written in our own words; check the manual for your exact model.

Tools and test equipment for service

Boiler · Vitorond 200 VD2

Use calibrated test equipment only. Keep the original Viessmann parts; incorrect parts can cause unsafe operation and void the warranty.

  1. Have flathead and Phillips screwdrivers, pipe wrenches, open-ended wrenches, Allen keys and a flashlight.
  2. Have pipe sealant and approved leak detection fluid for natural gas and propane.
  3. Bring the supplied cleaning brush, a hand brush, a vacuum cleaner and rags.
  4. Bring a flue gas analyzer to measure CO2 or O2, a multimeter (0-120 VAC, 0-12 AAC, 0-20 microamp DC), a smoke test gun, and a CO meter (0-400 ppm).
  5. Bring oil pump pressure and vacuum gauges if servicing an oil burner.
  6. Bring a gas pressure gauge (0-7 in. w.c., and up to 28 in. w.c.) or a non-electric Magnehelic gauge.
  7. Bring an efficiency calculator or tables, and a stack thermometer (0-500 F / 0-260 C).
  8. Bring a 1/8 in. NPT male to 1/4 in. barb adaptor and tubing for pressure readings.

Applies to: All VD2 sizes 320 to 1080

Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Tools needed for service and analysis

Boiler · Vitodens 200-W B2HA

Use only calibrated test equipment. The list covers the electrical, combustion, gas pressure and cleaning tools needed for start-up and service.

  1. Use a multimeter for 0 to 230 V AC, 0 to 12 A AC and 0 to 100 mA DC.
  2. Use a flue gas analyzer that reads % CO2 or O2.
  3. Use a manometer for gas pressure from 0 to 11 in. w.c. (accurate) and up to 28 in. w.c. A non-electric Magnehelic manometer may also be used.
  4. Use a stack thermometer from 0 to 500 °F (0 to 260 °C).
  5. Use a combustion efficiency calculator or suitable tables.
  6. Use carbon monoxide measuring equipment from 0 to 400 ppm.
  7. Clean with a plastic hand brush and rags.
  8. Use an approved leak detection fluid for natural gas and liquid propane, and pipe joint sealant.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 6. Written in our own words; check the manual for your exact model.

Touchscreen navigation and screensaver

Boiler · Vitocrossal 300 CA3B

The control has a touchscreen. The screensaver appears after a period with no input, and footer buttons move through the menu.

  1. If the screensaver is active, tap the screen to return to the default display or home screen.
  2. Use the footer buttons to return to the home screen, go back one menu level or cancel a setting, call up help text, call up fault or service messages, and scroll.
  3. From anywhere in the menu, tap the home button to return to the default display.

Applies to: Vitotronic 300 GW6C with HI932 Graphical User Interface

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 15. Written in our own words; check the manual for your exact model.

Transformer and zone valve wiring option

Boiler · Vitocrossal 300 CU3A

If a field-supplied 24 V transformer is not wanted, a multi-zone valve control can be used instead.

Applies to: Vitocrossal CU3A Application 2 wiring

Source: Vitocrossal 300 CU3A application guide, p. 27. Written in our own words; check the manual for your exact model.

Turn off gas to the appliance

Boiler · Vitodens 200-W B2HA

Used before service work or when the appliance will not run.

  1. Set thermostat or operating control to lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed.
  3. Close the main gas shut-off valve.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 98. Written in our own words; check the manual for your exact model.

Two-wrench method for connections

Boiler · Vitodens 100-W B1HE/B1KE

Support the boiler connector while tightening pipe fittings to avoid damaging the boiler's internal piping.

  1. Use one wrench on the boiler connector and a second on the fitting or pipe.
  2. Do not use pliers on the gas pipe.

Applies to: All piping connections

Source: Vitodens 100-W, B1HE/B1KE Installation/Service, p. 17. Written in our own words; check the manual for your exact model.

Two-wrench method on boiler connections

Boiler · Vitodens 100-W WB1B

Support the boiler connection while tightening fittings. Without support the boiler internal piping or the pressure gauge can be damaged.

  1. Use one wrench to hold the boiler connector.
  2. Use a second wrench to tighten the fitting or pipe.
  3. Support all piping with hangers, not the boiler.

Applies to: Heating water and gas connections

Source: Vitodens 100-W WB1B installation manual, p. 20. Written in our own words; check the manual for your exact model.

Unboxing and box contents

Boiler · Versatronik 200

The box holds the manual, outdoor temperature sensor, DHW sensor, common supply/LLH sensor, two CoCo OT communication modules, plug-in terminals and fuses. Check the quantities against the list before you start.

  1. Check the box contents against the packing list.
  2. Confirm you have 2 CoCo OT modules for each OpenTherm boiler, or order extra modules.

Applies to: Versatronik 200 control

Source: Versatronik 200 installation manual, p. 8. Written in our own words; check the manual for your exact model.

Underfloor heating and setback savings

Boiler · Vitotronic 300-K

Underfloor heating responds very slowly to short temperature changes. Reduced heating at night or Economy mode during short absences saves little energy on these systems.

Applies to: Underfloor heating systems

Source: Vitotronic 300-K, MW2C Operating Instructions, p. 33. Written in our own words; check the manual for your exact model.

Underfloor heating high-limit protection

Boiler · Vitodens 200-W B2HA

Underfloor loops can overheat concrete slabs if not protected.

  1. Install an immersion or strap-on aquastat in the low temperature underfloor loop, downstream of the mixing valve.
  2. Set it to de-energize the pump and/or boiler on high temperature.

Applies to: Vitodens 200-W B2HA 45, 60 underfloor heating

Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 32. Written in our own words; check the manual for your exact model.

Underfloor heating high-temperature protection

Boiler · Vitocrossal 300

Underfloor loops are damaged by high water temperature, so an extra aquastat is needed to stop the pump and boiler if the loop overheats.

  1. Install an immersion or strap-on aquastat in the low-temperature underfloor loop, downstream of the mixing valve.
  2. Set it to de-energize the pump and/or boiler when the loop overheats.

Applies to: Vitocrossal 300 CU3A with underfloor heating

Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 43. Written in our own words; check the manual for your exact model.

Underfloor heating limit thermostat

Boiler · Vitotronic 300

The electronic maximum limit does not replace the limit thermostat required for underfloor heating. The limit thermostat switches the heating circuit pump off when supply temperature exceeds its preset value. Supply cools slowly, so automatic restart can take several hours.

  1. Confirm the separate underfloor limit thermostat is installed.
  2. Warn the user that restart after a trip can take several hours.

Applies to: Underfloor heating circuits

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 89. Written in our own words; check the manual for your exact model.

Underfloor heating overheating protection

Boiler · Vitocrossal 200 CI2

Underfloor loops need an extra immersion or strap-on aquastat in the low temperature loop after the mixing valve. The aquastat de-energizes the pump and/or boiler to stop overheating. High water temperature can damage concrete slabs. System separation is required where non-oxygen diffusion barrier tubing is used, and all secondary-side components must be corrosion resistant.

  1. Install an immersion or strap-on aquastat in the low temperature underfloor loop, downstream of the mixing valve.
  2. Wire the aquastat to de-energize the pump and/or boiler on high temperature.
  3. Separate the system where non-oxygen diffusion barrier tubing is used.
  4. Use corrosion-resistant materials on the secondary side of the heat exchanger.

Applies to: Vitocrossal 200 CI2 399 to 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 41. Written in our own words; check the manual for your exact model.

Underfloor plastic tubing and oxygen diffusion barrier

Boiler · Vitorond 200 VD2

Underfloor plastic tubing without an oxygen diffusion barrier can corrode the system. The warranty does not cover those leaks.

  1. Use underfloor tubing with an oxygen diffusion barrier, which Viessmann recommends.
  2. If tubing without a barrier is used, separate it from the boiler with a heat exchanger.

Applies to: Vitorond 200 VD2 hydronic systems

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data, p. 17. Written in our own words; check the manual for your exact model.

Underfloor plastic tubing without oxygen barrier

Boiler · Vitorond 200 VD2A

Underfloor plastic tubing without an oxygen diffusion barrier can cause corrosion. Such a system must be separated from the boiler with a heat exchanger. The warranty does not cover resulting leaks.

  1. Separate non-barrier underfloor tubing from the boiler with a heat exchanger.
  2. Use underfloor tubing with an oxygen diffusion barrier where possible.

Applies to: Vitorond 200 VD2A hydronic system

Source: Vitorond 200 VD2A technical data manual, p. 25. Written in our own words; check the manual for your exact model.

Use a 1 in. full port drain if local code requires it

Boiler · Vitorond 200 VD2A

The boiler has a 1 in. wash-out opening that is reduced to a ¾ in. fill/drain faucet. If local codes need a full-port drain, a 1 in. field-supplied tee is installed at the wash-out opening.

  1. Connect the ¾ in. fill/drain faucet with a 1 in. x ¾ in. reducing coupling.
  2. If local code requires a full-port drain, fit a 1 in. tee at the wash-out opening.

Applies to: Boiler wash-out and drain

Source: Vitorond 200, VD2A Series Installation, p. 22. Written in our own words; check the manual for your exact model.

Use a soap solution for gas leak checks

Boiler · Vitocrossal 200 CI2

Do not use open flame or matches to check for gas leaks.

  1. Keep open flame and other ignition sources out of the room.
  2. Use a soap-and-water solution to check gas connections.
  3. Never purge a gas line into the combustion chamber.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 service instructions, p. 24. Written in our own words; check the manual for your exact model.

Use only original Viessmann parts

Boiler · Vitorond 200 VD2A

Replacement parts must be original Viessmann components. Wrong parts can make the boiler operate unsafely and void the warranty. Order replacement parts through a Viessmann distributor and use the Parts List in the manual.

  1. Check the Parts List before ordering any replacement.
  2. Order parts from a Viessmann distributor.
  3. Do not fit non-Viessmann parts.

Applies to: Vitorond 200 VD2A boilers

Source: Vitorond 200 VD2A service instructions, p. 8. Written in our own words; check the manual for your exact model.

Use only original Viessmann replacement parts

Boiler · Vitorond 200 VD2A

Installing incorrect replacement parts can cause hazardous operation and will void the warranty.

  1. Order replacement components from your Viessmann distributor.
  2. Use only original Viessmann components when replacing defective parts.
  3. Use the Parts List (starting page 17) to identify the correct component.

Applies to: Vitorond 200 VD2A

Source: Vitorond 200, VD2A Series Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

Use only Viessmann replacement parts

Boiler · Vitocrossal 200 CM2

Non-approved parts can cause hazardous operation and void the warranty. The full parts list starts on page 50.

  1. Order replacement components from a Viessmann distributor.
  2. Use only original Viessmann recommended components when replacing defective parts.
  3. Do not repair safety-function components; replace them.

Applies to: All Vitocrossal 200 CM2 units

Source: Vitocrossal 200 CM2 service instructions, p. 3 and p. 8. Written in our own words; check the manual for your exact model.

Use the 4th DHW time phase for higher DHW temperature

Boiler · Vitocrossal 300 CA3B

The heating contractor can enable a second, higher DHW set temperature. It runs during time phase 4. The 2nd and 3rd time phases must have start and stop times set.

  1. Ask the heating contractor to enable the second DHW set temperature.
  2. Set start and stop times for time phase 4.

Applies to: Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Source: Vitocrossal 300 CA3B operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Use two-hand wrench method on boiler and CombiPLUS connections

Boiler · Vitodens 100-W WB1B

Support the connector with one wrench while tightening the fitting or pipe with the second. Failing to support the connections can damage the boiler or the CombiPLUS internal piping.

Applies to: Boiler and CombiPLUS fittings and piping

Source: Vitodens 100-W WB1B installation and service instructions, p. 25. Written in our own words; check the manual for your exact model.

Using the screen, rotary knob and function keys

Boiler · Versatronik 200

The large screen shows four lines: day/date/time, favourites, heat generator or low loss header temperature, and central operating mode. The screen also shows fault indications and a relay test. Menus are moved through with the rotary knob, and a selection is confirmed with a function button. The Home button switches between the information screen and the main menu.

  1. Press Home to switch between the information screen and the main menu.
  2. Turn the rotary knob to move through menus or change a value.
  3. Press the function button beside a line to adjust that value or open its extra displays.
  4. Confirm the selection with the function button marked OK.

Applies to: Versatronik 200 System Control user interface

Source: Versatronik 200 manual, p. 66. Written in our own words; check the manual for your exact model.

UV resistant PP(s) pipe outdoors

Boiler · Vitocrossal 200 CI2

Outside exposed PP(s) exhaust and intake pipe must be UV resistant.

  1. Use UV resistant polypropylene for all exposed exhaust and air intake piping and elbows.
  2. Use the vent manufacturer's supplied material.

Applies to: PP(s) vent systems

Source: Vitocrossal 200 CI2 Installation manual, p. 56, 57, 60. Written in our own words; check the manual for your exact model.

Vacation schedule (holiday program)

Boiler · Vitotrol 300A

Applies to all heating circuits. With Heating and DHW selected, the rooms go to the reduced temperature and DHW heating is off. With Only DHW selected, boiler and DHW tank frost protection is on. The program is only enabled after the departure and return dates are confirmed with OK. Contractor help is needed to change the program.

  1. Open the extended menu and select Heating.
  2. Select Vacation schedule.
  3. Set the departure and return dates and confirm with OK.
  4. To remove it, select Delete schedule and confirm with OK.

Applies to: All heating circuits

Source: Vitotrol 300A operating instructions, p. 12. Written in our own words; check the manual for your exact model.

Vent clearance to combustibles

Boiler · Vitocrossal 300 CA3B Dual Fuel

Vent clearances to combustibles for stainless steel and polypropylene systems follow the vent manufacturer's requirements.

  1. Check the vent manufacturer's clearance requirements before installing the vent.

Applies to: Stainless steel and polypropylene venting

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 6. Written in our own words; check the manual for your exact model.

Vent pipe adaptor by model size

Boiler · Vitorond 100 VR1

A 5 in vent pipe adaptor ships with VR1 22 to 33 and 91 to 140. The adaptor is not supplied with VR1 40 to 63 and 161 to 245.

Applies to: VR1 22 to 33, 91 to 140, 40 to 63, 161 to 245

Source: Vitorond 100 VR1 technical data manual, p. 4. Written in our own words; check the manual for your exact model.

Vent routing and combustion air seal

Boiler · Vitodens 100-W WB1B

The boiler has a factory fitted vent adaptor. Route the vent to the outdoors on the shortest path with a rising slope. Use the separate venting manual for the vent system itself.

  1. Run single-pipe, two-pipe or coaxial venting through the side wall, roof or chimney by the shortest route.
  2. Keep the vent rising at least 3 degrees.
  3. On coaxial installs, remove the plastic centre of the combustion air inlet seal and leave the rubber seal in place.
  4. Follow the Vitodens Venting System Installation Instructions.

Applies to: Venting for Vitodens 100-W WB1B

Source: Vitodens 100-W WB1B installation manual, p. 17. Written in our own words; check the manual for your exact model.

Vent termination spacing for multiple boiler installations

Boiler · Vitocrossal 300 CA3B Dual Fuel

Keep the vent terminations of multiple boilers apart by the minimum distances shown.

  1. For horizontal vent terminations, keep at least 36 in. (915 mm) between them.
  2. For vertical vent terminations, keep at least 4 in. (100 mm) between them.
  3. The page also shows a 6 in. (150 mm) minimum dimension without a label. Check the full venting section before relying on it.

Applies to: Multiple Vitocrossal 300 CA3B Dual Fuel boiler installations

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation manual, p. 65. Written in our own words; check the manual for your exact model.

Vent wall penetration and insulation for polypropylene systems

Boiler · Vitocrossal 300 CA3B Dual Fuel

These rules apply to polypropylene venting only. The wall thickness range and insulation rule are below. The insulation thickness value is garbled in the source, so confirm it in the full manual.

  1. Keep the horizontal vent-air intake wall thickness between 1 in. (25.4 mm) and 30 in. (762 mm).
  2. Seal the vent-air intake system properly.
  3. Insulate polypropylene venting that passes through an unheated space such as an attic, with enough R-value to prevent condensate freezing.
  4. Install the vent termination on the leeward side of the building where possible.
  5. Protect nearby building surfaces from flue products with corrosion-resistant material if needed.

Applies to: Polypropylene (PP(s)) venting

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 6. Written in our own words; check the manual for your exact model.

Ventilation and radiator tips

Boiler · Vitotrol 300A

Simple habits that help the system keep energy use low.

  1. Open windows fully for a short time while closing the thermostatic valves.
  2. Close roller shutters at dusk, if installed.
  3. Set thermostatic valves correctly.
  4. Do not cover radiators or thermostatic valves.

Applies to: Vitotrol 300A users

Source: Vitotrol 300A operating instructions, p. 4. Written in our own words; check the manual for your exact model.

Venting and combustion air

Boiler · Vitodens 200-W

Never run the boiler without an installed venting system, because an improper vent can cause carbon monoxide poisoning. The boiler needs adequate combustion and ventilation air and must not be run where the combustion air is contaminated with dust, lint or chemicals.

  1. Confirm a complete venting system is installed before firing the boiler.
  2. Check that combustion air is not contaminated by dust, lint or chemicals.
  3. Check that the mechanical room has adequate combustion and ventilation air.

Applies to: All Vitodens 200-W B2HB models

Source: Vitodens 200-W B2HB Service Instructions, p. 2. Written in our own words; check the manual for your exact model.

Venting and common-vent limits

Boiler · Vitodens 200-W B2HA

Do not common-vent the Vitodens 200-W with any other appliance. Side wall coaxial vent installs must include the Viessmann protective screen. Do not exceed the maximum equivalent vent length in the Venting System installation instructions.

  1. Confirm the vent run does not exceed the maximum equivalent length in the Venting System installation instructions.
  2. Confirm no other appliance is connected to the vent.
  3. Confirm the Viessmann protective screen is fitted on a side wall coaxial vent.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 96. Written in our own words; check the manual for your exact model.

Venting and flue checks

Boiler · Vitocrossal 200 CI2

Blocked venting can cause flue gases to leak into the building.

  1. Check regularly for debris that could block the vent or chimney.
  2. Have any blockage removed by a qualified heating contractor.
  3. Check flue pipes, joints, vent dampers and side wall terminals for moisture or rust.
  4. Never operate the boiler without an installed venting system.

Applies to: Vitocrossal 200 CI2

Source: Vitocrossal 200 CI2 operating instructions, p. 2, 6. Written in our own words; check the manual for your exact model.

Venting approval and combustion air

Boiler · Vitorond 200 VD2

Venting limits and air quality rules apply at installation.

  1. Do not use side wall venting; this boiler is not approved for it.
  2. Do not install the boiler where chlorine, bromine, fluorine or other corrosive chemicals are stored or used.
  3. Keep combustion air free of corrosive chemicals and dust.
  4. Provide combustion and ventilation air at installation per local code and the referenced installation codes.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 15-16. Written in our own words; check the manual for your exact model.

Venting connection and building protection

Boiler · Vitodens 100-W WB1B

Follow the separate Vitodens venting system installation instructions supplied with the boiler for all venting requirements. Flue products can stain or damage nearby building surfaces, so shield exposed surfaces with corrosion-resistant material such as aluminum sheeting if needed.

  1. Attach and seal any protective material to the building before fitting the vent termination.
  2. Install the vent termination on the leeward side of the building where possible.

Applies to: Vitodens 100-W WB1B venting

Source: Viessmann Vitodens 100-W WB1B installation and service manual, p. 50. Written in our own words; check the manual for your exact model.

Venting in marine or salt-air locations

Boiler · Vitodens 100-W WB1B

Boilers in damp, salty coastal areas corrode faster. Direct vent (outdoor combustion air) systems are not allowed there, so use room-air-dependent venting.

  1. Do not install direct vent systems in marine environments.
  2. Use a room-air-dependent vent system so the boiler takes combustion air from the room.

Applies to: Vitodens 100-W WB1B in coastal areas

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 9. Written in our own words; check the manual for your exact model.

Venting length and common venting limits

Boiler · Vitodens 200-W B2HB

Vent length can go up to 180 ft (55 m). Common venting rules differ by size. B2HB 19-35 and 68-125 may not be common vented with any other appliance. B2HB 45, 57, 160 and 199 may only be common vented with other Vitodens 200-W boilers of the same size and series.

  1. Follow the Installation Instructions for the Vitodens 200-W B2HB Venting System for maximum equivalent length.
  2. For side wall coaxial installs, a Viessmann protective screen must be installed.
  3. Do not common vent B2HB 19-35 or 68-125 with other appliances.
  4. Only common vent B2HB 45, 57, 160 and 199 with the same size and series Vitodens 200-W boilers.

Applies to: Vitodens 200-W B2HB

Source: Vitodens 200-W B2HB technical data manual, p. 2, 5. Written in our own words; check the manual for your exact model.

Venting must always be installed

Boiler · Vitotronic 300-K

Never run the boiler without an installed venting system. Improper venting can cause carbon monoxide poisoning.

  1. Confirm the venting system is installed before operation.
  2. Refer to the Installation Instructions for venting and chimney requirements.

Applies to: Vitotronic 300-K MW2C boiler system

Source: Vitotronic 300-K MW2C operating instructions, p. 2. Written in our own words; check the manual for your exact model.

Venting near building surfaces

Boiler · Vitodens 200-W

Flue products from close-by vent terminations can stain or damage some building materials. Protect exposed surfaces with corrosion-resistant material if needed.

  1. Shield or seal exposed building surfaces with corrosion-resistant material such as aluminum sheeting if needed.
  2. Attach and seal the protective material to the building before fitting the vent termination.
  3. Install the vent termination on the leeward side of the building where possible.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 45. Written in our own words; check the manual for your exact model.

Venting options and vent length

Boiler · Vitocrossal 300 CU3A

Vent length can be up to 198 ft (60 m). Coaxial, double-pipe and single-wall venting are permitted, with the vent system supplied by the installer. Zero clearance to combustibles applies when vented with a listed single-wall special venting system.

  1. Select a venting type from the approved options: sealed combustion coaxial, double-pipe, or single-wall.
  2. Keep the total vent length within the limit given in the venting installation instructions.
  3. Install the Viessmann protective screen on side wall coaxial installations.

Applies to: Vitocrossal 300 CU3A 26 to 199

Source: Vitocrossal 300 CU3A 26 to 199 Technical Data Manual, p. 2, p. 5, p. 7. Written in our own words; check the manual for your exact model.

Venting restrictions

Boiler · Vitodens 200-W B2HA

Do not common-vent this boiler with any other appliance. Side wall coaxial installs need the Viessmann protective screen and must not exceed the maximum equivalent length in the venting instructions.

  1. Do not common-vent with any other appliance.
  2. Install the Viessmann protective screen on side wall coaxial vents.
  3. Keep the coaxial run within the maximum equivalent length in the Venting System instructions.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Source: Vitodens 200-W B2HA service instructions, p. 96. Written in our own words; check the manual for your exact model.

Venting: make sure all flue gases exit outdoors

Boiler · Vitocrossal 300 CU3A

Flue gases can contain carbon monoxide. Failing to vent all flue gases safely to the outdoors can cause property damage, serious injury or death. Never run the boiler without an installed venting system.

  1. Verify the venting system is complete and vents all flue gases to the outdoors before commissioning.

Applies to: Vitocrossal 300 CU3A venting

Source: Vitocrossal 300 CU3A Installation Instructions, p. 53. Written in our own words; check the manual for your exact model.

Versatronik 200 control overview

Boiler · Versatronik 200

Controls up to 8 boilers through CoCo communication modules, a stand-by demand on/off boiler, DHW production, and 2 mixing valves. The screen shows 4 lines, and menus are moved with a rotary dial and confirmed with a function button.

Applies to: Versatronik 200 System Control

Source: Versatronik 200 installation and operating manual, p. 64. Written in our own words; check the manual for your exact model.

Versatronik 200 menu structure overview

Boiler · Versatronik 200

The control menu is split into a User level and an Expert level. The Expert level holds the Configuration and Heat Source Settings branches, plus Heating Circuit 1 and 2, DHW, Solar/MF, Cooling operation and Slab curing. Sub-options listed in the tree include Cascade, Tank, 0-10 I/O, HC Function (Standard* or Const supply), Pool and Return Flow. Pages 80-88 show the tree only, with no values or codes.

Applies to: Versatronik 200 System Control, all menu levels

Source: Versatronik 200 installation and operating manual, p. 80-88. Written in our own words; check the manual for your exact model.

Vibration and noise control

Boiler · Vitorond 200 VD2A

Vibration and noise from the boiler and pumps can carry into the building. Measures are needed at the design stage. Attic installations need particular care.

  1. When sizing anti-vibration supports, include the full operating weight of the boiler system.
  2. Install compensators in the boiler flow, return and safety pipes, as close to the boiler as possible.
  3. Insulate braces or hangers against sound and vibration transfer.
  4. Consider silencer hoods, sound-insulated air inlets and room for a flue gas silencer behind the boiler.
  5. Include the silencer's exhaust pressure drop in the vent size calculation.

Applies to: Vitorond 200 VD2A installations

Source: Vitorond 200 VD2A technical data manual, p. 26-27. Written in our own words; check the manual for your exact model.

View 7-day solar energy yield graph

Boiler · Vitotronic 300-K

The graph shows solar energy yield for the past 7 days. A flashing line means the current day is not finished yet.

  1. Open the extended menu.
  2. Select "Solar energy".

Applies to: Vitotronic 300-K with solar thermal system

Source: Vitotronic 200 and 300-K Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

View fault and message history

Boiler · Vitodens 100-W B1HE, Vitodens 100-W B1KE

The 10 most recent faults, including remedied ones, and service messages are stored, sorted by date.

  1. Enter the service menu.
  2. Select Message history, then OK.
  3. Select the category: Faults, Service messages, Status, Warnings or Information.
  4. Select the message, then OK.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 69. Written in our own words; check the manual for your exact model.

View help messages

Boiler · Vitodens 100-W B1HE/B1KE

Help text is available for some displays and functions.

  1. Within the menu, select Help if shown.
  2. Confirm with OK.
  3. Exit the screen.

Applies to: Control unit help

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 23. Written in our own words; check the manual for your exact model.

View licences for the programming unit

Boiler · Vitocrossal 200 CI2

Shows the open source licence for the programming unit.

  1. Go to the home screen.
  2. Open the menu and select 'Information'. Confirm with OK.
  3. Select 'Open source licences'. Confirm with OK.
  4. Hold the exit control for about 4 seconds to leave the menu.

Applies to: Control panel

Source: Vitocrossal 200 CI2 operating instructions, p. 31. Written in our own words; check the manual for your exact model.

View message history

Boiler · Vitodens 100-W B1HE/B1KE

Shows past faults, warnings, notes, status and information messages.

  1. Call up the home screen and open the menu.
  2. Select Information, then tap OK.
  3. Select System information, then tap OK.
  4. Select Message history, then tap OK.
  5. Select the message group: fault, warning, note, status or information, then tap OK.
  6. Select the message and tap OK to view it.
  7. Hold the exit button for about 4 seconds to leave the menu.

Applies to: Vitodens 100-W B1HE/B1KE

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 26. Written in our own words; check the manual for your exact model.

View solar energy yield

Boiler · Vitotronic 200 and 300-K

The solar energy yield for the past 7 days is shown as a graph. The flashing line marks the current day, which is not finished yet.

  1. Open the extended menu.
  2. Select "Solar energy".

Applies to: Vitotronic 300-K with solar thermal system

Source: Viessmann Vitotronic 200 and 300-K Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Viewing actual temperatures and status

Boiler · Versatronik 200

Use the Display menu to check live temperatures and status for the DHW, heating circuits and system. A value shows only if its sensor is connected and reading. Otherwise the screen shows "----" or nothing.

  1. Press the Home button to open the Main Menu.
  2. Turn the rotary dial until Display is on screen.
  3. Press the key beside Display to open it.
  4. Select DHW, Heating Circuit 1 or System to view that circuit's temperatures and status.
  5. Press Cancel to leave the current screen.

Applies to: Versatronik 200 system control

Source: Versatronik 200 installation and operating manual, p. 96. Written in our own words; check the manual for your exact model.

Viewing service contact details

Boiler · Vitotronic 300-K

The heating contractor's details can be read on the display if they have been entered.

  1. From the home screen tap Menu.
  2. Tap Information.
  3. Tap Service contact details.
  4. If no details are entered, tap the white field to open the keyboard. Each text box holds up to 45 characters.

Applies to: Vitotronic 300-K MW2C

Source: Vitotronic 300-K MW2C operating instructions, p. 25. Written in our own words; check the manual for your exact model.

Viewing the service address

Boiler · Vitocrossal 300 CA3B Dual Fuel

The heating contractor can enter their contact details here. If no details are entered, the field is blank and the keypad can be used to enter them.

  1. From the home screen, tap Menu.
  2. Tap Information.
  3. Tap Service address.
  4. If no details are shown, tap the white field to open the keypad and enter the contact details.

Applies to: Vitocrossal 300 CA3B Dual Fuel boiler

Source: Vitocrossal 300 Dual Fuel Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

Vitocontrol-S must be set as fault manager for maintenance messages

Boiler · Vitocontrol-S VD2/CT3/CM2

Vitocontrol-S shows maintenance messages from a connected Vitotronic 100 GC1 only when it is encoded as fault manager.

  1. Check that coding 79 is set to 1 on Vitocontrol-S.

Applies to: Vitocontrol-S VD2/CT3/CM2 control unit

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 112. Written in our own words; check the manual for your exact model.

Vitodens 222-F key components

Boiler · Vitodens 222-F

Main features of the Vitodens 222-F boiler.

  1. Stainless steel Inox-Radial heat exchanger.
  2. Modulating MatriX cylinder gas burner.
  3. Integral diaphragm expansion tank.
  4. Digital boiler control unit.
  5. Integral 3-speed high efficiency circulation pump.
  6. Stainless steel DHW primary storage tank.

Applies to: Vitodens 222-F B2TB

Source: Vitodens 222-F application guide, p. 12. Written in our own words; check the manual for your exact model.

Vitotronic 100 display symbols

Boiler · Vitotronic 100 (GC1B), Vitotronic 300-K (MW1B)

Symbols do not always show and depend on system version and operating state. Flashing symbols mean a value can be changed. Menu, information and further-adjustment icons appear on the display. Symbol S means emissions test mode, a heating program symbol shows the active program, and symbol 9 means standby with frost protection monitoring. In standby the boiler is available to the cascade control for heat production. If a boiler is not operational, the Vitotronic 100 shows a message on its display. In multi-boiler systems each Vitotronic 100 shows its boiler number on the standard display. Service message: service interval has expired. Fault message: a fault is present. Other symbols show a circulation pump running at a given output and a burner in operation. A D symbol indicates factory settings.

  1. If the standard display shows a service symbol, the service interval has expired; arrange service.
  2. If the standard display shows a fault symbol, scan the fault messages and act on them.

Applies to: Vitotronic 100 GC1B

Source: Viessmann Vitotronic 100 GC1B / Vitotronic 300-K MW1B Operating Instructions, p. 8. Written in our own words; check the manual for your exact model.

Vitotronic 100 keys

Boiler · Vitotronic 100 GC1B

Function of each key on the Vitotronic 100 programming unit.

  1. Back key: goes to the previous menu step or cancels a started setting.
  2. Cursor keys: scroll the menu and set values.
  3. OK key: confirms the selection or saves the setting.
  4. Menu key: opens the menu for settings and scanning.
  5. Question mark key: no function.

Applies to: Vitotronic 100 GC1B

Source: Viessmann Vitotronic 100 GC1B / 300-K MW1B operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Vitotronic 200 control keys

Boiler · Vitotronic 200

The Vitotronic 200 has a back key, cursor keys, an OK key and a menu key. The question mark key has no function.

  1. Press the back key to return to the previous menu step or cancel a setting that was started.
  2. Use the cursor keys to scroll through the menu or change values.
  3. Press OK to confirm a selection or save a setting.
  4. Press the menu key to open the settings and scanning menu.
  5. Do not expect the question mark key to do anything.

Applies to: Vitotronic 200 type H01B

Source: Vitotronic 200 and 300-K Operating Instructions, p. 8. Written in our own words; check the manual for your exact model.

Wake the cascade control screen

Boiler · Vitotronic 300-K

The touchscreen goes into screensaver mode after a period of no use. Any touch wakes it up.

  1. Tap anywhere on the screen to wake the screensaver.
  2. Tap the on-screen buttons to make adjustments or scan information.

Applies to: Vitotronic 300-K cascade control programming unit

Source: Vitotronic 300-K MW2C operating instructions, p. 7. Written in our own words; check the manual for your exact model.

Wake the touchscreen and reach the home screen

Boiler · Vitocrossal 300 CA3B

The control unit shows a screensaver after a period of no use. Tap the display to wake it. From any menu level, the home button returns you to the home screen. Use the on-screen buttons for all adjustments and scans.

  1. If the screensaver is active, tap the display anywhere.
  2. From anywhere in the menu, tap the home button to return to the home screen.
  3. To open the main menu from the home screen, tap the menu button. From elsewhere in the menu, tap the menu button, then the main menu button.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0 with Vitotronic 300 GW6C / HI932

Source: Vitocrossal 300 CA3B operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Wake up display on lag boiler (lead cascade only)

Boiler · Vitocrossal 200 CI2

Used from the lead boiler to wake the display of a lag boiler in a cascade.

  1. Select 'Wake up display'.
  2. Select and confirm the lag boiler.

Applies to: Lead boiler in a cascade

Source: Vitocrossal 200 CI2 operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Wall mounting the boiler

Boiler · Vitodens 100-W B1HE/B1KE

The wall bracket is supplied for concrete walls. Other materials need anchors rated for 190 lb (86 kg).

  1. Mark the rawl plug holes on the wall.
  2. Drill the holes and insert the rawl plugs.
  3. Fasten the bracket tightly with the supplied screws.
  4. Hang the boiler and confirm all four bracket tabs are locked in.
  5. Remove the plastic caps only just before connecting pipes.

Applies to: Vitodens 100-W wall mounting

Source: Vitodens 100-W, B1HE/B1KE Combi Technical Data, pp. 13-14. Written in our own words; check the manual for your exact model.

Warm-up optimization

Boiler · Versatronik COMO OT

Automatic advance starts heating earlier, based on weather and room temperature, so the room reaches setpoint at the programmed time. The maximum advance is set separately. The required advance shows for information only.

  1. Turn warm-up optimization ON.
  2. Set the maximum time advance.
  3. Check the required time advance display if needed.

Applies to: Versatronik COMO OT

Source: Versatronik COMO OT installation and operating manual, p. 29. Written in our own words; check the manual for your exact model.

Warn the user about high DHW outlet temperature

Boiler · Vitocrossal 200 CI2

Raised DHW temperatures at draw-off points can scald. This applies when the DHW target is raised, including during hygiene runs.

  1. Inform the system user of the scald risk from the higher outlet temperature at draw-off points.

Applies to: DHW tank heating and hygiene function

Source: Vitocrossal 200 CI2 service instructions, p. 90. Written in our own words; check the manual for your exact model.

Warranty exclusion for low return temperatures

Boiler · Vitorond 200 VD2

Warranty does not cover flue gas condensation corrosion caused by low boiler or return water temperatures.

  1. Maintain the minimum boiler and return water temperatures listed for the fuel and control mode.
  2. Use clean fill and make-up water.

Applies to: Vitorond 200 VD2 boilers

Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 16. Written in our own words; check the manual for your exact model.

Water condition log

Boiler · Vitocrossal 300 CA3B

Water condition log on the page records counter reading, fill and make-up water, total water quantity, total hardness, feed water and boiler water pH, and the date.

  1. Record counter reading, fill and make-up water quantity and total water quantity.
  2. Record total hardness of the feed water and boiler water.
  3. Record pH of feed water and boiler water with the date.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

Source: Vitocrossal 300 CA3B service instructions, p. 161. Written in our own words; check the manual for your exact model.

Water damage to boiler or controls

Boiler · Vitotronic 200, Vitotronic 300-K

Do not use the boiler if any part has been under water. The control system and any gas control that was under water must be replaced by a qualified heating contractor.

  1. Do not run the boiler if any part has been flooded.
  2. Have a qualified heating contractor inspect the boiler.
  3. Replace the control system parts and any gas control that were under water.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 6. Written in our own words; check the manual for your exact model.

Water exposure

Boiler · Vitocrossal 300 CA3B

A boiler exposed to water must not be run until a qualified contractor has inspected it.

  1. Do not operate the boiler if any part has been under or exposed to water.
  2. Have a qualified heating contractor inspect the boiler.
  3. Replace any control or gas control part that was under or exposed to water.

Applies to: Vitocrossal 300 CA3B

Source: Vitocrossal 300 CA3B operating instructions, p. 8. Written in our own words; check the manual for your exact model.

Water quality

Boiler · Vitocrossal 300 CA3B

Water quality affects the life of the whole system. Hard water causes deposits on heat exchanger surfaces.

  1. Avoid hard water (calcium carbonate) conditions.
  2. Use a water treatment system to protect against corrosion and lime formation.
  3. If unsure of water quality, have a water analysis done.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B operating instructions, p. 42. Written in our own words; check the manual for your exact model.

Water quality and hard water

Boiler · Vitocrossal 200 CM2

Water quality affects system life. Water treatment protects against corrosion and lime. Hard water (calcium carbonate) deposits on heat exchanger surfaces and should be avoided. If unsure, get a water analysis.

  1. Use a water treatment system to prevent corrosion and lime formation.
  2. Get a water analysis if water quality is in doubt.

Applies to: Vitocrossal 200 CM2 186 to 620

Source: Vitocrossal 200 CM2 operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Water quality for the heating system

Boiler · Vitocrossal 300 CA3B Dual Fuel

Water quality affects the life of the whole system. Hard water causes scale on heat exchanger surfaces, and corrosion is a risk without treatment.

  1. Avoid hard water (calcium carbonate) in the heating system.
  2. If in doubt, have a water analysis done.
  3. Use a water treatment system to protect against corrosion and lime formation.

Applies to: Heating system water

Source: Vitocrossal 300 CA3B Dual Fuel operating instructions, p. 42. Written in our own words; check the manual for your exact model.

Water treatment and fill water

Boiler · Vitorond 200 VD2A

Treat boiler feed water where high mineral content or hardness is known. Warranty does not cover damage from contaminated fill or supplementary feed water.

  1. Consider water treatment in areas with known high mineral content or hardness.
  2. Do not operate with contaminated fill or supplementary feed water.

Applies to: Vitorond 200 VD2A hydronic system

Source: Vitorond 200 VD2A technical data manual, p. 25-26. Written in our own words; check the manual for your exact model.

Water-damaged appliance

Boiler · Vitodens 200-W

Do not use the appliance if any part has been under water. A qualified technician must inspect it and replace the control parts and any gas control that was under water.

  1. Do not run the appliance after water exposure.
  2. Call a qualified service technician to inspect the appliance and replace affected control and gas parts.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

Source: Vitodens 200-W B2HB installation manual, p. 61. Written in our own words; check the manual for your exact model.

Weather-compensated mode

Boiler · Vitotrol 300A

The heating flow temperature follows the outside temperature, so no extra heat is made beyond what the room set point needs.

  1. The outside temperature is measured by a sensor mounted outside the building and sent to the control unit.

Applies to: Vitotrol 300A

Source: Vitotrol 300A Remote Control Operating Instructions, p. 27. Written in our own words; check the manual for your exact model.

What the remote control can adjust

Boiler · Vitotrol 300

Only the normal room temperature setting is kept on the remote itself. The other adjustments are sent to the Vitotronic control unit and back. Changes to the domestic hot water temperature range may need coding by the heating contractor.

Applies to: Vitotrol 300 with Vitotronic control unit

Source: Vitotrol 300 operating instructions, p. 5. Written in our own words; check the manual for your exact model.

Where settings are made

Boiler · Vitotronic 200, Vitotronic 300-K

Each boiler has its own Vitotronic 200 constant temperature control. A higher-level Vitotronic 300-K weather-compensated cascade control regulates these boiler controls. All heating system settings can be changed centrally at the Vitotronic 300-K programming unit, or at remote control units if the system has them.

  1. Make system-wide changes at the Vitotronic 300-K programming unit.
  2. Use remote control units for changes if the system has them.
  3. Use the Vitotronic 200 operating instructions for settings at the boiler control.

Applies to: Vitotronic 200 and 300-K

Source: Vitotronic 200 and 300-K Operating Instructions, p. 8. Written in our own words; check the manual for your exact model.

Where this control is approved for use

Boiler · Vitotronic 100 GC1

The Vitotronic 100 GC1 is certified only as a component of Viessmann boilers. It covers single-boiler systems and multi-boiler systems with an external building automation system. It does not apply to multi-boiler systems that use the Vitocontrol-S (VD2/CT3/CM2).

Applies to: Vitotronic 100 GC1, control part nos. 7134 553 / 7134 554 / 7511361 from serial no. 7143 002

Source: Vitotronic 100 GC1 installation and service instructions, p. 4. Written in our own words; check the manual for your exact model.

Wiring accessory terminals on the DIN rail

Boiler · Vitocrossal 200 CI2

The accessory terminals are push-in type. Press the orange button before inserting or removing any wire. Solid, stranded, or stranded with ferrule wire can be used; a ferrule helps prevent stranded wire from fraying.

  1. Press the orange push-in button for the terminal.
  2. Insert or remove the wire.
  3. Use a ferrule on stranded wire where possible.

Applies to: DIN rail accessory connections

Source: Vitocrossal 200 CI2 installation instructions, p. 32. Written in our own words; check the manual for your exact model.

Wiring and reconnection precautions

Boiler · Vitodens 200-W B2HA

Replace any original wire only with an exact equivalent. Label all wires before disconnecting them. Each connection can have only one function or accessory assigned.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before removing them.
  3. Reconnect using the exact equivalent wire.
  4. Verify proper operation after servicing.

Applies to: Boiler wiring and controls

Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 88. Written in our own words; check the manual for your exact model.

Wiring caution during service

Boiler · Vitocrossal 300 CU3A

Label every wire before disconnecting controls, because wiring errors can cause improper and dangerous operation. Replace any original wire only with an exact equivalent. Verify correct operation after servicing. Disconnect power before servicing.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnection.
  3. Replace any original supplied wire only with the exact equivalent.
  4. Verify proper operation after servicing.

Applies to: Vitocrossal 300 CU3A wiring

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 101. Written in our own words; check the manual for your exact model.

Wiring changes and servicing

Boiler · Vitodens 200-W

Replacement wires must be exact equivalents. Wiring errors can cause improper and dangerous operation.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Verify proper operation after servicing.
  4. Each connection can have only one function or accessory assigned.

Applies to: Vitodens 200-W B2HA wiring

Source: Vitodens 200-W B2HA service instructions, p. 95. Written in our own words; check the manual for your exact model.

Wiring noise and shielding

Boiler · Versatronik 585, Versatronik 585D

Keep low-voltage communication wiring away from 120/240 VAC conductors to avoid electromagnetic interference. If that cannot be avoided, use stranded twisted-pair shielded cable and ground only one end of the shield.

  1. Route communication wires away from 120/240 VAC conductors where possible.
  2. If they must run close, use stranded twisted-pair shielded wire.
  3. Ground only one end of the shield.

Applies to: Versatronik 585 and 585D wiring

Source: Versatronik 585 and 585D BACnet IP gateway manual, pp. 4-5. Written in our own words; check the manual for your exact model.

Wiring practice for low voltage and line voltage

Boiler · Vitotronic 300

Keep low voltage and line voltage leads separate. Strip insulation close to the terminal and bundle tightly. Secure cables with cable ties.

  1. Route low voltage leads and line voltage cables separately.
  2. Strip the insulation as close to the terminals as possible.
  3. Bundle the wires tightly to the matching terminals.
  4. Secure the cables with cable ties.

Applies to: Vitotronic 300 GW6B wiring

Source: Vitotronic 300 GW6B Installation and Service Instructions, p. 21. Written in our own words; check the manual for your exact model.

Wiring safety before servicing controls

Boiler · Vitodens 222-F, B2TB

Disconnect power before working on the boiler. Label every wire before removing it, because wiring errors can cause improper and dangerous operation. Replace any original supplied wire only with an exact equivalent. Verify correct operation after servicing.

  1. Disconnect power to the boiler.
  2. Label all wires before disconnecting them.
  3. Replace damaged original wires only with the exact equivalent.
  4. Reconnect and verify correct operation before leaving the boiler.

Applies to: Vitodens 222-F, B2TB (19, 35, 68, 125)

Source: Vitodens 222-F, B2TB installation instructions, p. 41. Written in our own words; check the manual for your exact model.

Wiring safety during service

Boiler · Vitodens 200-W

Wiring errors can cause improper and dangerous operation.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any original wire only with the exact equivalent.
  4. Verify proper operation after servicing.

Applies to: Vitodens 200-W B2HA 80 to 100

Source: Vitodens 200-W B2HA Service Instructions, p. 92. Written in our own words; check the manual for your exact model.

Wiring service precautions

Boiler · Vitodens 200-W

Label all wires before disconnecting. Wrong wiring can cause dangerous operation. Replace any original wire only with an exact equivalent, and verify proper operation after servicing.

  1. Disconnect power before servicing the boiler.
  2. Label every wire before removing it.
  3. Replace damaged wires only with exact equivalents.
  4. Check operation after reconnecting.

Applies to: Boiler wiring and controls

Source: Vitodens 200-W B2HB service manual, p. 91. Written in our own words; check the manual for your exact model.

Wiring work and verification

Boiler · Vitodens 200-W B2HA

Wiring errors can cause improper and dangerous operation.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any original wire only with the exact equivalent.
  4. Verify proper operation after servicing.

Applies to: Boiler wiring

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 86. Written in our own words; check the manual for your exact model.

Without function display

Boiler · Vitotronic 200-H

Flashes when a button with no assigned function is pressed. Example: the DHW button when no DHW tank is connected.

Applies to: Vitotronic 200-H HK1S/HK3S

Source: Vitotronic 200-H operating instructions, p. 28. Written in our own words; check the manual for your exact model.

Work on the boiler only with power and fuel off

Boiler · Vitorond 200 VD2

Only a licensed professional heating contractor may install, adjust, service or maintain the boiler. There are no user serviceable parts on the boiler, burner or control.

  1. Turn off main power to the boiler, heating system and all external controls.
  2. Close the main gas or oil supply valve.
  3. Take steps to prevent power being restored during service work.
  4. Verify field-supplied controls such as low water cut-offs, staging controls, pumps, motorized valves, air vents and thermostats.

Applies to: All service work

Source: Vitorond 200 VD2 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Working on the boiler: isolate power and fuel

Boiler · Vitorond 100 VR1

Before any service, make sure power cannot be applied accidentally to the boiler, heating system or external controls.

  1. Shut off main power to the boiler, the heating system and all external controls.
  2. Close the main fuel supply valve. The manual text says gas supply valve; for this oil-fired boiler, confirm the correct oil shutoff.
  3. Take precautions to prevent accidental power activation during service work.

Applies to: Vitorond 100 VR1 boilers

Source: Vitorond 100 VR1 installation and service manual, p. 5. Written in our own words; check the manual for your exact model.

Working on the equipment

Boiler · Vitocrossal 300 CA3B

Only qualified, licensed personnel may work on the boiler or heating system.

  1. Disconnect main power to the boiler, heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take precautions so power cannot be restored accidentally during service.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

Source: Vitocrossal 300 operating instructions, p. 6. Written in our own words; check the manual for your exact model.

Working on the equipment: isolate before service

Boiler · Vitodens 200-W B2HB

Only a licensed professional heating contractor should install, adjust, service or maintain the boiler. There are no user-serviceable parts. Power and gas must be off before work begins.

  1. Switch off main power to the boiler, the heating system and all external controls.
  2. Close the main gas supply valve.
  3. Take steps so power cannot come back on accidentally during service.

Applies to: Vitodens 200-W B2HB, all models

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 6. Written in our own words; check the manual for your exact model.

Yearly and two-yearly service

Boiler · Vitocrossal 300 CA3B

Boiler must be cleaned at least once a year by a qualified heating contractor. The heating system must be serviced by an authorized contractor at least every 2 years.

  1. Clean the boiler at least once a year.
  2. Have the system serviced by an authorized contractor at least every 2 years.
  3. Refer to the installation and service instructions for the full service schedule.

Applies to: Vitocrossal 300 CA3B

Source: Viessmann Vitocrossal 300 CA3B operating instructions, p. 41. Written in our own words; check the manual for your exact model.

Zone circuit pump connection

Boiler · Vitodens 222-F, B2TB

A maximum of 2 zone circuit pumps can connect directly to the boiler. More pumps need an AM1 extension module. Pump output assignment is done in the set-up wizard.

  1. Connect up to 2 zone circuit pumps directly to the boiler.
  2. For additional pumps, install an AM1 extension module and connect the pumps there.
  3. Assign the pump outputs in the set-up wizard.
  4. Refer to the AM1 Installation Instructions for details.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB Installation Instructions, p. 52. Written in our own words; check the manual for your exact model.

Zone circuit thermostat connections

Boiler · Vitodens 222-F, B2TB

Each zone circuit takes a dry-contact room thermostat. Up to three zone circuits are shown, and the EA1 module is integrated into the boiler.

  1. Connect the dry-contact room thermostat for zone circuit 1 to the EA1 module.
  2. Connect the dry-contact room thermostat for zone circuit 2 to the EA1 module.
  3. Connect the dry-contact room thermostat for zone circuit 3 to the EA1 module.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Source: Vitodens 222-F, B2TB Installation Instructions, p. 51. Written in our own words; check the manual for your exact model.

Zone control operational screen indications

Boiler · Vitodens 222-F

What the home screen shows when a zone control circuit is active or configured.

  1. Check which ZC circuit (ZC1, ZC2 or ZC3) is shown, selected with the left or right arrows.
  2. An r on the display means a ZC call is present.
  3. A p symbol means that ZC circuit has an associated pump output.
  4. Read the actual boiler water temperature from the display.
  5. A flame symbol with a percentage shows burner ON and modulation level.
  6. Read the target zone temperature. Fixed Setpoint shows the configured temperature. Weather Compensated shows the target based on slope and shift.
  7. When Weather Compensated is set, the outdoor temperature is also shown.

Applies to: Vitodens 222-F B2TB 68 and 125 with zone control

Source: Vitodens 222-F application guide, p. 25. Written in our own words; check the manual for your exact model.

Zone control operational screen indicators

Boiler · Vitocrossal 300 CU3A

The zone control screen shows: 1) the ZC circuit selected (left/right arrows to change); 2) an r when a zone call is present; a p when that circuit has a pump output configured; 3) actual boiler water temperature; 4) flame symbol and modulation percentage when the burner is on; 5) target zone temperature (fixed setpoint, or calculated from slope and shift); 6) outdoor temperature when weather compensated control is configured.

  1. Use the left and right arrows to pick the ZC circuit to view.
  2. Look for r for an active zone call and p for a configured zone pump.
  3. Read flame and modulation % when the burner is firing.

Applies to: Vitocrossal 300 CU3A zone control

Source: Vitocrossal 300 CU3A application guide, p. 21. Written in our own words; check the manual for your exact model.

Δt control for condensing

Boiler · Vitocrossal 200 CI2

Δt control keeps a fixed spread between supply and return. At low load the pump speed is reduced so return temperature stays low. The target spread is interpolated between two points: at 68°F (20°C) supply it uses parameter 2779.0 (factory 9°F / 5 K), and at 194°F (90°C) supply it uses parameter 2779.1 (factory 36°F / 20 K).

Applies to: Vitocrossal 200 CI2 boilers

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 81. Written in our own words; check the manual for your exact model.

120VAC version: terminal, button and LED layout

General · Versatronik 535 Solar

Board connections on the 120VAC version: 120VAC supply, fuse, service button, LON link to the BMS, RJ45 BACnet link to the BMS, multi-module addressing selector, COM3 for multiple bus connections, COM4 RJ45 link to the control, power LED and service LED.

  1. Wire 120VAC supply to the power connection and check the 160mA time-delay fuse.
  2. Connect the BMS by LON or RJ45 BACnet, depending on the network in use.
  3. Connect the solar control to the COM4 RJ45 port.
  4. Set the addressing selector if more than one module is installed.
  5. Use the power LED to confirm supply and the service LED to check status.

Applies to: 120VAC version

Source: Versatronik 535 Solar BACIP manual, p. 16. Written in our own words; check the manual for your exact model.

24VAC version: terminal, button and LED layout

General · Versatronik 535 Solar

Board connections on the 24VAC version: 24VAC supply, power LED, BACnet RJ45 BMS link, addressing dial, COM4 RJ45 link to the control, COM3 for multiple bus connections, service button, service LED and LON link to the BMS. This version has no fuse.

  1. Wire 24VAC supply to the power connection. No fuse is fitted or listed for this version.
  2. Connect the BMS by BACnet RJ45 or LON.
  3. Connect the solar control to the COM4 RJ45 port.
  4. Set the addressing dial if more than one unit is installed.
  5. Use the power LED to confirm supply and the service LED to check status. Press the service button for service functions.

Applies to: 24VAC version

Source: Versatronik 535 Solar BACIP manual, p. 17. Written in our own words; check the manual for your exact model.

Applicable solar controls

General · Versatronik 535 Solar

The gateway works with these controls: Resol Deltasol M, BS Plus, BS1/2/3/4, BX/BXL, E/ES/BX/MX/SKSC3, and Viessmann Vitosolic 200, SCU 124, SCU 224 and SCU 345.

Applies to: Versatronik 535 Solar gateway, 704065 and 704066

Source: Versatronik 535 Solar BACnet IP manual, p. 1. Written in our own words; check the manual for your exact model.

Check the heating system and message channels at regular intervals

General · Vitoconnect

The system relies on working message channels and Internet access, so check them periodically. Supplementary measures such as frost protection or water damage monitoring are recommended.

  1. Check the heating system and the operability of the message channels at regular intervals.
  2. Recommend frost protection or water-damage monitoring to the owner.
  3. Confirm Internet access is available at all times, since remote functions depend on it.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 Installation and Operating Instructions, p. 3. Written in our own words; check the manual for your exact model.

Choose a frost-protected installation room

General · Vitocell 100-E

The tank must be in a room that never gets freezing temperatures. If the room may freeze and the tank is not in use, drain the tank.

  1. Install the tank in a frost-protected, draft-free room.
  2. Drain the tank when it is not in use and freezing is possible.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation manual, p. 4, p. 7. Written in our own words; check the manual for your exact model.

Cleaning and maintenance

General · Vitoconnect OPTO2

The Vitoconnect needs no maintenance.

  1. Wipe the surface of the unit with a microfibre cloth.
  2. Do not use any cleaning agents.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 17. Written in our own words; check the manual for your exact model.

COM4 port LED blips

General · Versatronik 522 OT

COM4 has two LEDs. Orange blip means a packet is received. Green blip means the gateway has sent a response.

  1. Use these blips to confirm that the master is talking to the gateway.

Applies to: Versatronik 522 OT Modbus gateway

Source: Versatronik 522 OT Modbus manual, p. 10. Written in our own words; check the manual for your exact model.

Connections for 120VAC wall-mount gateway

General · Versatronik 522

The 120VAC unit has three connections: the OpenTherm 2-wire link to the boiler, the Modbus RJ45 port, and the plug-in power cord.

  1. Connect the OpenTherm 2-wire link to the OT-enabled boiler, using the boiler manual for the correct terminal.
  2. Connect the Modbus RJ45 port to the BMS.
  3. Plug in the 120VAC power cord.

Applies to: Versatronik 522 OT/Modbus, P/N 704054

Source: Versatronik 522 and 522D OT Modbus gateway manual, p. 7. Written in our own words; check the manual for your exact model.

Connections for 24VAC DIN rail gateway

General · Versatronik 522

The 522D connects to the boiler through OT terminals A and B and to the BMS through Modbus RJ45. It is powered by a field-supplied 24VAC supply.

  1. Wire the OpenTherm 2-wire connection to terminals A and B.
  2. Connect the Modbus RJ45 port to the BMS.
  3. Connect the field-supplied 24VAC supply to the gateway.

Applies to: Versatronik 522D OT/Modbus, P/N 704077

Source: Versatronik 522 and 522D OT Modbus gateway manual, p. 8. Written in our own words; check the manual for your exact model.

DIN rail unit connection overview

General · Versatronik 522

The DIN rail unit has extra model-specific network ports (BACnet IP and LON) and a parallel LON bus in addition to the OT and 24VAC connections.

  1. Connect the BACnet IP RJ45 port, if fitted on this model.
  2. Connect the LON RJ45 port, if fitted on this model.
  3. Connect the parallel LON bus where used.
  4. Connect OT terminals A and B to the boiler.
  5. Connect the 24VAC power supply.

Applies to: Versatronik 522D OT/Modbus, P/N 704077

Source: Versatronik 522 and 522D OT Modbus gateway manual, p. 6. Written in our own words; check the manual for your exact model.

Do not fit batteries to the programming unit

General · Vitotrol 300A

The programming unit is powered by the control unit and does not take batteries. Remove it with a flat-head screwdriver by releasing the wall plate latch and unhooking the interface.

  1. Do not insert batteries into the programming unit.
  2. To remove, use a flat-head screwdriver to release the latch on the left side of the wall mounting plate.
  3. Pull out the left side of the interface, then unhook the right side and remove it.
  4. Release the latch on the right side of the wiring cover plate if it needs to come off too.

Applies to: Vitotrol 300A programming unit

Source: Vitotrol 300A installation and service instructions, p. 7. Written in our own words; check the manual for your exact model.

Do not open the injection process plug

General · Vitocell 100-E

The injection process plug is for the factory process only.

  1. Do not open the injection process plug (F).
  2. Do not connect anything to the injection process plug.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 Technical Data Manual, p. 4. Written in our own words; check the manual for your exact model.

Do not wrap insulating tape on the tank sensor

General · Vitocell 100-E

Insulating tape around the sensor is not permitted.

  1. Never wrap insulating tape around the sensor.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation, service and operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Gateway board connection points

General · Versatronik 532

The board has nine numbered connection points and indicators. Use these to wire power, the BMS, the controls and the service functions.

  1. Connect the 24 VAC supply to connection 1.
  2. Check the power LED (2) lights when power is applied.
  3. Connect the BMS over BACnet at the RJ45 port (3).
  4. Set the addressing dial (4) when several units share a bus.
  5. Connect the control to the COM4 RJ45 port (5).
  6. Connect additional BUS devices to COM3 (6).
  7. Use the service button (7) for service functions; the service LED (8) shows its status.
  8. Connect LON to the BMS at the LON terminals (9).

Applies to: Versatronik 532 Solar/Modbus gateway PCB

Source: Versatronik 532 Solar/Modbus manual, p. 16. Written in our own words; check the manual for your exact model.

Gateway LEDs and service button

General · Versatronik 521 OT/LON, Versatronik 521D OT/LON

The board has a power LED, an OT indicator LED and a service button. The 120VAC board also has a rotary dial, which is not used.

  1. Check the power LED to confirm the gateway has power.
  2. Check the OT indicator LED to confirm OpenTherm communication with the boiler.
  3. Use the service button on the board for service functions.

Applies to: 120VAC and 24VAC boards

Source: Versatronik 521 & 521D OT/LON technical information, p. 11-12. Written in our own words; check the manual for your exact model.

Handle the board to prevent static damage

General · Versatronik 532 Solar/Modbus

Static-sensitive components can be damaged by poor handling or work inside the control.

  1. Take all reasonable steps to prevent static build-up before handling the board or working inside the control.

Applies to: Versatronik 532 Solar/Modbus and 532D

Source: Versatronik 532 Solar Modbus manual, p. 2. Written in our own words; check the manual for your exact model.

Heat quantity counter roll-over

General · Versatronik 531 Solar/LON

The heat quantity objects (Wh, kWh, MWh) roll over to the next unit at 1000. For example, 999 Wh becomes 0 Wh and adds 1 kWh.

Applies to: nvoHQ_Wh, nvoHQ_KWh, nvoHQ_MWh

Source: Versatronik 531 Solar/LON gateway technical information, p. 13. Written in our own words; check the manual for your exact model.

Improve Wi-Fi range for the Vitoconnect

General · Vitoconnect

Walls, ceilings, furniture, metal parts and nearby electronics weaken the Wi-Fi signal. Keep the Vitoconnect close to the router and away from interference sources.

  1. Keep the Vitoconnect as close to the Wi-Fi router as practical.
  2. Add a commercially available Wi-Fi repeater if the signal is weak.
  3. Keep at least 6.5 ft (2 m) from computers, audio and video systems, radio signals, electronic transformers and ballasts.
  4. Avoid placing it behind reinforced walls, metallic foil insulation, metallized thermo-glass, or supply blocks and lift shafts.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 Installation and Operating Instructions, p. 8. Written in our own words; check the manual for your exact model.

Installation code requirements

General · Versatronik 525 OT/BACIP

Installation and wiring must follow local codes. Work must be done by a licensed heating contractor or qualified person. The control has no user-serviceable parts.

  1. Wire to CSA C22.1 Part 1 or the NEC (ANSI/NFPA 70), and to local codes.
  2. Where required, meet ANSI/ASME CSD-1 for automatically fired boilers.
  3. Verify the completeness and function of any field-supplied electrical controls.

Applies to: All Versatronik 525 gateways

Source: Versatronik 525 & 525D OT Communication Gateway BACnet IP manual, p. 3. Written in our own words; check the manual for your exact model.

Installation must be done by qualified personnel

General · Versatronik 521

There are no user-serviceable parts on this control. Installation, adjustment, service and maintenance are for licensed heating contractors or qualified installers.

  1. Check that field-supplied electrical controls and components are verified by the installer before commissioning.
  2. Follow local codes and the National Electrical Code (ANSI/NFPA 70) in the U.S., or CSA C22.1 Part 1 in Canada.

Applies to: All Versatronik 521 and 521D gateways

Source: Versatronik 521 OT LON manual, p. 3. Written in our own words; check the manual for your exact model.

Intended use limits

General · Vitocell 100-E

The tank is for sealed unvented systems and holds potable-quality water only. It is for heating or cooling water with heat pumps and has connections for a back-up heat generator. It is not suitable for steam heating. Commercial or industrial use other than building heating is not allowed without manufacturer approval.

  1. Confirm the system is a sealed unvented system.
  2. Confirm the application is not steam heating.
  3. Do not use the tank beyond its intended use without manufacturer approval.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation manual, p. 7. Written in our own words; check the manual for your exact model.

Isolate power and fuel before service

General · Vitocell 100-E

Service must be done by a licensed professional heating contractor. The unit has no user-serviceable parts.

  1. Switch off main power to the equipment, heating system and all external controls.
  2. Close the main oil or gas supply valve.
  3. Take steps to prevent accidental power-up during service work.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation manual, p. 4. Written in our own words; check the manual for your exact model.

Isolate power before servicing

General · Versatronik 521

The unit has more than one live circuit. Contact with live components can cause serious injury or death.

  1. Turn off the power supply to the control and to the damper or blower before servicing.
  2. Check the wiring diagram in the manual before working on the unit.

Applies to: All Versatronik 521 and 521D gateways

Source: Versatronik 521 OT LON manual, p. 3. Written in our own words; check the manual for your exact model.

Keep gateway wiring away from high voltage

General · Versatronik 532 Solar/Modbus

Low-voltage gateway wiring can pick up electrical interference when it runs near high-voltage conductors.

  1. Keep extension wire away from 120/240 VAC conductors where possible.
  2. If that is not possible, use stranded twisted-pair or shielded wire.
  3. Ground only one end of the shield.

Applies to: Versatronik 532 Solar/Modbus and 532D

Source: Versatronik 532 Solar Modbus manual, p. 4. Written in our own words; check the manual for your exact model.

Keep low-voltage wiring away from 120/240 VAC

General · Versatronik 531 Solar/LON

Long wire runs can pick up electromagnetic interference, so keep them clear of high-voltage conductors.

  1. Keep the communication wires away from 120/240 VAC conductors.
  2. If they must run close, use stranded twisted-pair shielded cable.
  3. Ground only one end of the shield.

Applies to: Versatronik 531 Solar/LON and 531D wiring

Source: Versatronik 531 Solar LON manual, p. 4. Written in our own words; check the manual for your exact model.

Keep low-voltage wiring away from mains

General · Versatronik 535 Solar

Long low-voltage runs can pick up electromagnetic interference from nearby 120/240VAC wiring.

  1. Keep wires away from 120/240VAC conductors where possible.
  2. If that is not possible, use stranded twisted-pair or shielded wire.
  3. Ground only one end of the shield.

Applies to: Versatronik 535 Solar gateway

Source: Versatronik 535 Solar BACnet IP manual, p. 4. Written in our own words; check the manual for your exact model.

Keep messages working during power failures

General · Vitoconnect

Messages can still reach the user during a power cut if the Vitoconnect and the Wi-Fi router run on an uninterruptible power supply.

  1. Fit an uninterruptible power supply to the Vitoconnect.
  2. Fit an uninterruptible power supply to the Wi-Fi router.

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 Installation and Operating Instructions, p. 3. Written in our own words; check the manual for your exact model.

Mount the tank on a suitable floor

General · Vitocell 100-E

The floor or foundation must be able to carry the weight of the tank when it is full of water.

  1. Position the tank carefully and remove the packaging.
  2. Confirm the flooring or foundation supports the filled tank weight.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation manual, p. 7. Written in our own words; check the manual for your exact model.

Power off before servicing

General · Versatronik 532 Solar/Modbus

More than one live circuit is present. Contact with live parts can cause serious injury or death.

  1. Turn off power to the control and to the damper or blower before servicing.
  2. Check the wiring diagram in the manual before working on the unit.

Applies to: Versatronik 532 Solar/Modbus and 532D

Source: Versatronik 532 Solar Modbus manual, p. 3. Written in our own words; check the manual for your exact model.

Protect static-sensitive parts

General · Versatronik 525 OT/BACIP

Static discharge can damage components inside the control.

  1. Take precautions to remove static charge before handling the control internals.

Applies to: All Versatronik 525 gateways

Source: Versatronik 525 & 525D OT Communication Gateway BACnet IP manual, p. 2. Written in our own words; check the manual for your exact model.

Protect the board from static

General · Versatronik 521

Static-sensitive components can be damaged by careless handling inside the control.

  1. Take all reasonable steps to avoid static build-up before working inside the control.

Applies to: All Versatronik 521 and 521D gateways

Source: Versatronik 521 OT LON manual, p. 2. Written in our own words; check the manual for your exact model.

Protect the control from static

General · Versatronik 531 Solar/LON

Static can damage the control's components during handling or work inside it.

  1. Take steps to remove static build-up before touching the inside of the control.

Applies to: Versatronik 531 Solar/LON gateway

Source: Versatronik 531 Solar LON manual, p. 2. Written in our own words; check the manual for your exact model.

Qualified installer and power-off before service

General · Versatronik 535 Solar

Only licensed or qualified heating contractors should install, adjust or service the gateway. There are no user-serviceable parts. The unit has more than one live circuit, so cut power to the control and damper/blower before working on it.

  1. Turn off power to the control and damper/blower before servicing.
  2. Check local codes and CSA C22.1 or NEC ANSI/NFPA 70 for wiring.

Applies to: Versatronik 535 Solar gateway

Source: Versatronik 535 Solar BACnet IP manual, p. 3. Written in our own words; check the manual for your exact model.

RJ45 adapter wiring for Modbus

General · Versatronik 522 OT

The Modbus version ships with an RJ45 adapter and cable.

  1. Connect the supplied RJ45 cable between the gateway and the adapter.
  2. Connect the field RS485 wiring to terminal X1 on the adapter.

Applies to: Versatronik 522 OT Modbus gateway

Source: Versatronik 522 OT Modbus manual, p. 9. Written in our own words; check the manual for your exact model.

RS-485 bias and termination on the gateway

General · Versatronik

The gateway has no termination resistor installed. Two 4.7 kΩ pull-up/pull-down resistors on the lines provide bias.

Applies to: Versatronik 532 Solar/Modbus and 532D Solar/Modbus gateways

Source: Versatronik 532 Solar/Modbus manual, p. 12. Written in our own words; check the manual for your exact model.

Shield wiring near high voltage

General · Versatronik 525 OT/BACIP

Long low-voltage runs can pick up electromagnetic interference.

  1. Keep low-voltage wiring away from 120/240VAC conductors.
  2. If that is not possible, use stranded twisted-pair shielded cable.
  3. Ground only one end of the shield.

Applies to: All Versatronik 525 gateways

Source: Versatronik 525 & 525D OT Communication Gateway BACnet IP manual, p. 5. Written in our own words; check the manual for your exact model.

Static sensitivity

General · Versatronik 535 Solar

The control contains static-sensitive components that can be damaged by poor handling.

  1. Take all practical steps to prevent static build-up before working inside the control.

Applies to: Versatronik 535 Solar gateway

Source: Versatronik 535 Solar BACnet IP manual, p. 2. Written in our own words; check the manual for your exact model.

Static-sensitive components

General · Versatronik 531 Solar/LON

The control board and its components can be damaged by static discharge. Take steps to prevent static build-up before handling or working inside the control.

  1. Discharge static before touching the board.
  2. Handle the board by its edges and avoid static build-up.

Applies to: Versatronik 531 Solar/LON gateway, all versions

Source: Versatronik 531 Solar/LON gateway technical information, p. 2, 14-15. Written in our own words; check the manual for your exact model.

Thread protectors are not watertight

General · Vitocell 100-E

Unused connections must be sealed on site.

  1. Seal every unused connection on site after removing the thread protectors.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation, service and operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Turn off power before servicing

General · Versatronik 525 OT/BACIP

The control has more than one live circuit. Contact with live parts can cause serious injury or death.

  1. Turn off the power to the control and to any damper or blower before servicing.
  2. Check the wiring diagram in the manual before working on the unit.

Applies to: All Versatronik 525 gateways

Source: Versatronik 525 & 525D OT Communication Gateway BACnet IP manual, p. 3. Written in our own words; check the manual for your exact model.

Typical 24VAC wiring overview

General · Versatronik 522 OT

The gateway is powered by a field-supplied 24VAC supply. It connects to the boiler OT bus on terminals A and B. It connects to the BMS on the Modbus RJ45 port.

  1. Wire the boiler OpenTherm connection to terminals A and B.
  2. Connect the field 24VAC supply to the gateway.
  3. Connect the BMS through the Modbus RJ45 connection and adapter.

Applies to: Versatronik 522 OT Modbus gateway, 24VAC

Source: Versatronik 522 OT Modbus manual, p. 8. Written in our own words; check the manual for your exact model.

Unavailable Modbus values

General · Versatronik 522 OT

Values that the boiler or thermostat does not supply are shown as -99.

  1. Do not treat -99 as a real reading. Check whether the connected boiler supports that variable.

Applies to: Versatronik 522 OT Modbus gateway

Source: Versatronik 522 OT Modbus manual, p. 11. Written in our own words; check the manual for your exact model.

Use only permitted antifreeze in the heating system

General · Vitocell 100-E

If glycol or other antifreeze is added to the heating system, it must be non-toxic or food grade. Give the owner a Safety Data Sheet for the fluid. Viessmann Tyfocor-HTL is the recommended fill for the solar circuit.

  1. Use only non-toxic or food grade antifreeze.
  2. Provide the owner with the Safety Data Sheet (SDS).

Applies to: Vitocell 100-E MSCA-20-S2 in heating systems with antifreeze

Source: Vitocell 100-E MSCA-20-S2 installation manual, p. 4. Written in our own words; check the manual for your exact model.

Verify field-supplied controls

General · Vitocell 100-E

The heating contractor must check that field-supplied electrical controls and components work. These include low-water cutoffs, flow switches if used, staging controls, pumps, motorized valves, air vents, thermostats and temperature controls.

  1. Check low-water cutoffs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats and temperature controls for completeness and function.

Applies to: Vitocell 100-E MSCA-20-S2

Source: Vitocell 100-E MSCA-20-S2 installation manual, p. 4. Written in our own words; check the manual for your exact model.

View acknowledged faults

General · Vitotrol

Acknowledged fault messages can be called up from the extended menu.

  1. Open the extended menu.
  2. Select 'Fault'.

Applies to: Vitotrol 300A

Source: Vitotrol 300A installation and service instructions, p. 9. Written in our own words; check the manual for your exact model.

View open source licences

General · Vitoconnect

Licence information is available through the access point.

  1. Activate access point mode for the Vitoconnect.
  2. Connect a smartphone or PC to the Viessmann-<xxxx> Wi-Fi network.
  3. Enter the WPA2 password from the enclosed label.
  4. Open http://vitoconnect.gateway or http://169.254.11.1 and follow the link "Open Source Components Licenses".

Applies to: Vitoconnect OPTO2

Source: Vitoconnect OPTO2 installation and operating instructions, p. 14. Written in our own words; check the manual for your exact model.

After refrigerant circuit damage: vent hydronic side

Heat pump · Vitocal 100-AW

Refrigerant can get into the water side if the refrigerant circuit is damaged.

  1. After the work is finished, vent the hydronic system correctly.
  2. Make sure the area is well ventilated while venting.

Applies to: Vitocal 100-AW AM2V hydronic circuit

Source: Vitocal 100-AW AM2V installation manual, p. 6. Written in our own words; check the manual for your exact model.

Antifreeze selection and handover when filling with glycol

Heat pump · Vitocal 100-AW AM2V

Only use antifreeze made for hot water heating systems. Automotive silicate-based antifreeze must not be used. Inform the owner that the system contains a glycol mix and provide the antifreeze Safety Data Sheet.

  1. Confirm the antifreeze is made for hot water heating systems and is not automotive silicate-based.
  2. Keep glycol at or below 50% in the system water.
  3. Check pH and the system frequently after filling with antifreeze.
  4. Give the system owner the antifreeze Safety Data Sheet and tell them the system contains glycol.

Applies to: Filling and antifreeze protection

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 44. Written in our own words; check the manual for your exact model.

Built-in protection and diagnostics

Heat pump · Vitocal 100-S

The unit includes controls and safeties that protect the outdoor fan, compressor and system.

  1. Check the time delay control sequence run by the fan coil board when the unit restarts.
  2. Check outdoor fan motor protection if the fan does not run.
  3. Use the system diagnostics when a fault is suspected.
  4. Check compressor motor current and temperature overload protection if the compressor trips.

Applies to: DLCURA outdoor units

Source: DLCURA technical data manual, p. 96. Written in our own words; check the manual for your exact model.

Built-in protection features on heat pumps

Heat pump · DLFSDAH / DLFLDAH

Indoor units include freeze protection and high coil temperature protection in heating mode. Cold blow protection and freeze protection mode are also standard.

Applies to: Heat pump indoor units

Source: Vitocal IND-D technical data manual, p. 2 and p. 4. Written in our own words; check the manual for your exact model.

Built-in protection functions

Heat pump · D5CSRA

The factory-set minimum protections are: time delay control sequence through the fan control board, compressor discharge over-temperature, system low voltage, compressor overload, compressor over-current, outdoor fan failure, and system diagnostics.

Applies to: All D5CSRA outdoor units

Source: Carrier D5CSRA Product Data, p. 191. Written in our own words; check the manual for your exact model.

Capacitors stay charged after power off

Heat pump · Vitocal 100-S

Electricity remains in the capacitors after the power supply is off. Fully discharge them before troubleshooting the outdoor PCB or IPM.

  1. Discharge the capacitors fully before any troubleshooting on the outdoor PCB or IPM.

Applies to: Outdoor unit

Source: Viessmann DLCURA service manual, p. 52. Written in our own words; check the manual for your exact model.

Check capacitor discharge before troubleshooting or board work

Heat pump · Vitocal 100-S, DLCSRB

Capacitors keep a charge after the power is off. Confirm they are discharged before working on the boards.

  1. Turn off all power supplies or disconnect all wires.
  2. Measure the voltage between P and N on the back of the main PCB with a multimeter.
  3. If the reading is below 36 V, the capacitors are fully discharged.
  4. Wear anti-static gloves or a wrist strap when handling the indoor or outdoor PCB.

Applies to: DLCSRB indoor and outdoor PCBs

Source: Vitocal 100-S DLCSRB service manual, p. 79. Written in our own words; check the manual for your exact model.

Cleaning the unit

Heat pump · Vitocal 100-WA

Use only approved cleaning methods. Commercial and special heat exchanger cleaners can damage the heat pump.

  1. Clean the unit surfaces with a damp cloth only.
  2. Clean the air coil shutters with a long bristle brush.
  3. Brush the air coil only from top to bottom or bottom to top, never side to side.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 50. Written in our own words; check the manual for your exact model.

Compressor and back-up heater indicators

Heat pump · Vitocal 100-AW

A solid compressor symbol means the compressor is running. A flashing compressor symbol means the compressor is running and outdoor temperature is low enough for electric heating element activation. The electric heating element symbol shows when it is active, and the back-up heating symbol shows when back-up heating is on.

  1. Check the compressor symbol on the display to confirm compressor operation.
  2. Check the back-up heating and electric element symbols when the unit is in low outdoor temperature.

Applies to: Vitocal 100-AW AM2V indoor unit display

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 50. Written in our own words; check the manual for your exact model.

Condensate drain in cold climates

Heat pump · Vitocal 100-S

In cold climates, keep the drain hose as vertical as possible so water drains quickly. Slow drainage can freeze in the hose and flood the unit.

  1. Connect the drain joint with an extension hose so condensate does not drip off during heating mode.
  2. Check the drain hose slope and direction before leaving the site.

Applies to: DLCURA outdoor unit

Source: DLCURA installation instructions, p. 11. Written in our own words; check the manual for your exact model.

Defrost parameter guidance for heavy snow areas

Heat pump · Vitocal 100-AW

Standard defrost settings may not be enough in heavy snowfall. Raising S12 and S13 and lowering S14 can help.

  1. Increase S12 (defrost duration) and S13 (defrost water entering temperature).
  2. Decrease S14 (defrost interval).

Applies to: Vitocal 100-AW AM2V outdoor unit defrost

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 64. Written in our own words; check the manual for your exact model.

Display symbols on the operating screen

Heat pump · Vitocal 100-AW AM2V

Symbols show the running program (schedule, disinfection, defrost, party, holiday, frost protection, manual), heat take-up for central heating or hot tap water, cooling operation, error and warning, electric heating element active, compressor running (flashing means bivalent mode) and back-up heating on.

  1. Check the symbols on the home screen to confirm the active program and heat source.
  2. A flashing compressor symbol means bivalent mode is active.

Applies to: Vitocal 100-AW AM2V controller display

Source: Vitocal 100-AW AM2V Technical Data Manual, p. 35. Written in our own words; check the manual for your exact model.

Do not leak test with air or oxygen-containing gas

Heat pump · Vitocal 100-S

Pressurized air or gas mixtures containing oxygen can explode. Use dry nitrogen or another inert gas for leak testing and never for operating compressors.

  1. Do not use air or oxygen-containing gas for pressure or leak testing.
  2. Use an approved inert gas for leak testing.

Applies to: Refrigerant system leak testing

Source: Viessmann DLCURA installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Drain heating water before removing refrigerant

Heat pump · Vitocal 100-WA

Hydronic components can freeze when refrigerant is removed.

  1. Drain the heating water from the heat pump before refrigerant is removed.
  2. After the refrigerant work, vent the hydronic system properly and make sure the area is well ventilated, since refrigerant may have entered the water side.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, p. 5. Written in our own words; check the manual for your exact model.

Electrical entry points and DHW pump switch

Heat pump · Vitocal 100-WA

Each corner post has two openings for routing wiring. Knockouts in the junction box provide cable restraints. The DHW desuperheater pump switch is at the top of the junction box. The unit has outputs for a closed-loop source pump and an open-loop source valve.

  1. If DHW is not connected to this unit, set the desuperheater DHW pump switch to OFF.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, p. 21. Written in our own words; check the manual for your exact model.

Electrical installation rules

Heat pump · Vitocal 100-WA

The control must be grounded. L1, L2 and G must not be swapped. Size all wire to the local electrical code. Each circuit needs its own disconnect near the unit. A licensed electrician must do line voltage work; the certified contractor may do only Class 2 low voltage wiring such as the thermostat.

  1. Ground the control.
  2. Confirm L1, L2 and G are wired correctly and not interchanged.
  3. Size wire per NEC/CEC or local code.
  4. Provide a separate disconnect for the circuit near the unit.

Applies to: All models

Source: Vitocal 100-WA technical data manual, p. 11. Written in our own words; check the manual for your exact model.

Electrical shock hazard before service

Heat pump · Vitocal 100-S, DLCLRC

Main disconnect must be off before installing, modifying or servicing the system.

  1. Switch off the main electrical disconnect. There may be more than one disconnect.
  2. Lock out and tag the switch with a suitable warning label.

Applies to: DLCLRC

Source: Vitocal 100-S DLCLRC service instructions, p. 1. Written in our own words; check the manual for your exact model.

Errors and warnings on the home screen

Heat pump · Vitocal 100-AW

When an error or warning is present, the home screen shows an error indicator or a warning indicator. The list of detected errors and warnings is opened from the navigation dial. Error code values are not listed on these pages.

  1. Press the navigation dial to open the list of detected errors and warnings.
  2. Record the codes shown and check the fault tables in the full manual.

Applies to: Vitocal 100-AW AM2V indoor unit

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 49-50. Written in our own words; check the manual for your exact model.

Fibreglass and ceramic fibre handling

Heat pump · Vitocal 100-AW

Fibreglass wool and ceramic fibre materials are a possible cancer hazard by inhalation.

  1. Avoid breathing dust and contact with skin and eyes.
  2. Wear a NIOSH-approved dust/mist respirator, long-sleeved clothing, gloves and eye protection.
  3. Wash work clothes separately and rinse the washer well.
  4. Rinse eyes with water to remove dust; wash skin with soap and cool water.
  5. Move anyone with respiratory irritation to a dust-free area.

Applies to: Installation and service work with insulation materials

Source: Vitocal 100-AW AM2V installation manual, p. 4. Written in our own words; check the manual for your exact model.

Field wiring safety checks

Heat pump · D5CSRA

Every wire must be firmly connected, since loose wiring can overheat terminals, cause malfunction or create a fire hazard. No wire may touch refrigerant tubing, the compressor or moving parts. A disconnect must be provided within sight of the air conditioner and be readily accessible. Follow local code when running wire from the indoor to the outdoor unit.

  1. Tighten every wire connection.
  2. Route wires so none touch tubing, the compressor or moving parts.
  3. Install a disconnect within sight of the unit and easy to reach.
  4. Follow local code for the indoor-to-outdoor run.

Applies to: All D5CSRA systems

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

Field wiring workmanship

Heat pump · Vitocal 100-S, DLCLRC

Loose connections can overheat terminals, cause malfunction and create a fire hazard. Wires must not touch refrigerant tubing, the compressor or moving parts. A disconnecting means must be within sight of and readily accessible from the air conditioner. Route the connecting cable through the hole in the conduit panel.

  1. Tighten every field wire connection firmly.
  2. Keep all wires clear of refrigerant lines, compressor and moving parts.
  3. Install a disconnect within sight of the unit.
  4. Run the connecting cable through the conduit panel hole.

Applies to: DLCLRC sizes 36K-58K

Source: Viessmann DLCLRC service manual, p. 4 of 60. Written in our own words; check the manual for your exact model.

Filter and construction dust

Heat pump · Vitocal 100-WA

Use a high-efficiency air filter in tight buildings and tell the owner it needs regular changes, usually monthly. Do not run the unit during construction or remodeling, as dust can clog the coil and condensate drain and will void the warranty.

  1. Install a high-efficiency filter.
  2. Tell the owner the filter schedule.
  3. Do not run the system during construction or remodeling.

Applies to: All ducted installs

Source: Vitocal 100-WA technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Filter and panel removal

Heat pump · Vitocal IND-O

Removal method depends on whether the panel has a lift function.

  1. If the panel has a lift function, grab the air grille with your fingers and pull it out slowly.
  2. If the panel has no lift function, push one side of the grille clamp on both sides of the grille.
  3. Remove the 2 screws, then remove the grille.

Applies to: Indoor unit filter and panel

Source: Vitocal IND-O DLFSOAH service instructions, p. 40. Written in our own words; check the manual for your exact model.

Flammable R32 refrigerant: ignition control before work

Heat pump · Vitocal 100-AW

The outdoor unit uses flammable R32. A leak can form a flammable or explosive mix with air, so keep ignition sources away from the work area.

  1. Keep flames, hot surfaces, non-certified electrical devices and battery-powered devices away from the work area.
  2. Use only tools rated for A2L/A3 refrigerants, such as brushless tools, non-sparking mechanical tools and suitable vacuum pumps.
  3. Touch earthed metal such as heating or water pipes to discharge static before starting.
  4. Do not use sprays or other flammable materials.
  5. Post no-smoking signs and have a CO2 or dry powder extinguisher at hand when draining, topping up or doing hot work.

Applies to: Vitocal 100-AW AM2V outdoor unit (R32)

Source: Vitocal 100-AW AM2V installation manual, p. 4-5. Written in our own words; check the manual for your exact model.

FOLLOW ME function

Heat pump · Vitocal IND-O

When active, the unit controls to the room temperature sent by the remote and ignores its own room sensor. The function ends automatically if no remote signal arrives for 7 minutes, or when FOLLOW ME is pressed again.

  1. Press FOLLOW ME on the wireless or wired remote to start it.
  2. Press FOLLOW ME again to stop it.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH service manual, PDF p. 10. Written in our own words; check the manual for your exact model.

Freeze protection during refrigerant work

Heat pump · Vitocal 100-AW

Hydronic parts can freeze when refrigerant is removed, and frost protection needs power.

  1. Drain the heating water from the heat pump before removing refrigerant.
  2. Thermally insulate all hydronic lines.
  3. Connect the heat pump electrically and switch on the power before filling the secondary circuit, so frost protection works.

Applies to: Vitocal 100-AW AM2V hydronic circuit

Source: Vitocal 100-AW AM2V installation manual, p. 5-6. Written in our own words; check the manual for your exact model.

Freeze stat lockout

Heat pump · Vitocal 100-WA

The freeze stat protects the liquid-to-refrigerant heat exchanger. In heating mode it reads refrigerant temperature leaving the water coil. If that drops below the freeze set point, the system activates freeze protection and locks out until manually reset.

  1. Check water flow and groundwater temperature if the freeze stat trips.
  2. Correct the cause before resetting.
  3. Reset the lockout manually.

Applies to: Open loop heating mode

Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Frequent defrost cycles

Heat pump · Vitocal 100-S, DLCURA

If the outdoor unit defrosts often, the thermal balance point can be adjusted to reduce cycling and cold air during defrost.

  1. Adjust the thermal balance point to a temperature that reduces defrost recurrence.
  2. The thermal balance point is the outdoor ambient temperature at which the heat pump can no longer provide enough heat alone without compromising compressor reliability.

Applies to: Outdoor unit sizes 18K to 60K

Source: DLCURA installation instructions, p. 20. Written in our own words; check the manual for your exact model.

Heat pump operating principle

Heat pump · Vitocal 100-AW

The outdoor unit holds the whole refrigerant circuit with an inverter-driven compressor and an electronic expansion valve. The indoor unit holds the controller, secondary pump, electric auxiliary heater and a 3-way diverter valve for space heating or DHW. In cooling mode the refrigerant circuit reverses.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Hot and cold surfaces and fluids

Heat pump · Vitocal 100-AW

Hot heating water and cold refrigerant surfaces can cause scalds, burns or frostbite.

  1. Switch off the equipment and let it cool down or warm up before servicing.
  2. Do not touch hot or cold surfaces on the appliance, fittings or pipework.
  3. If water leaks, isolate the heating system at the external isolator before touching anything, and never touch hot heating water.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V installation manual, p. 5, 7. Written in our own words; check the manual for your exact model.

How to read the DLCURA cooling and heating performance tables

Heat pump · Vitocal 100-S

Cooling tables are split by airflow (CFM). Each block lists outdoor dry bulb temperature down the side. Across the top are indoor wet bulb groups (60.8, 64.4, 66.2, 71.6 F) and, under each, indoor dry bulb values (73.4, 77.0, 80.6, 84.2 F). TC is total cooling capacity in BTU/hr, S/T is sensible-to-total ratio, and PI is total power input in kW. Heating tables list TC (total capacity, BTU/hr) and PI (total power, kW) against indoor dry bulb (60.8, 68.0, 71.6, 75.2 F) for each airflow block. Gray shaded cells are extrapolated data, not tested points.

  1. Pick the airflow block that matches the indoor blower CFM.
  2. Find the outdoor dry bulb row, then the indoor wet bulb and dry bulb column.
  3. Read TC for capacity, S/T for the sensible share, and PI for power draw.
  4. Treat gray shaded values as estimates only.

Applies to: DLCURA 18K HH and 24K outdoor units (cooling and heating performance)

Source: DLCURA technical data manual, p. 16-24. Written in our own words; check the manual for your exact model.

Ice build-up on outdoor unit

Heat pump · Vitocal 100-AW

Ice in the condensate pan or fan area can damage the unit.

  1. Do not use mechanical items or aids to remove ice.
  2. Check the refrigerant circuit for leaks before using any electric heating appliance nearby, and make sure the heater is not an ignition source.
  3. Where ice builds up often, fit fan ring heating suitable for R32 and/or an electric ribbon heater in the condensate pan (accessory or factory-fitted).

Applies to: Vitocal 100-AW AM2V outdoor unit

Source: Vitocal 100-AW AM2V installation manual, p. 7. Written in our own words; check the manual for your exact model.

Installation room and location

Heat pump · Vitocal 100-WA

Place the unit in a heated indoor area near a floor drain and an outside wall where practical.

  1. Keep the mechanical room at or above 60°F (15°C).
  2. Locate the unit near a floor drain.
  3. Place the unit near an outside wall so ground loop connections are easy.
  4. Do not install in an area subject to freezing.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 10, 13, 15. Written in our own words; check the manual for your exact model.

Installation rules for A2L refrigerant rooms

Heat pump · Vitocal 100-WA

Rules for ignition sources and room size where A2L refrigerant appliances are installed or ducted.

  1. If the room is smaller than the minimum area (Amin) or has an effective dispersal volume below the minimum, keep the room free of continuously operating open flames and other potential ignition sources.
  2. A flame-producing device may stay in the same space only if it has an effective flame arrest.
  3. Confirm a leak detection system is installed. The unit must stay powered except during service.
  4. Use non-sparking tools for A2L refrigerants and check for leaks with a refrigerant detector before and during installation.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, pp. 6-7. Written in our own words; check the manual for your exact model.

Interconnection cable length

Heat pump · Vitocal 100-AW

Short cables let leaked refrigerant reach the building interior.

  1. Use an electrical connecting cable between indoor and outdoor unit of at least 3 m.

Applies to: Indoor unit to outdoor unit wiring

Source: Vitocal 100-AW AM2V installation manual, p. 6. Written in our own words; check the manual for your exact model.

Isolate power before service

Heat pump · Vitocal 100-S, DLCLRC

Before installing, modifying or servicing, the main electrical disconnect must be OFF. There may be more than one disconnect. Lock out and tag each switch with a suitable warning label.

  1. Switch off every main disconnect for the system.
  2. Lock out and tag each switch.
  3. Verify the unit is de-energized before touching wiring.

Applies to: DLCLRC sizes 36K-58K

Source: Viessmann DLCLRC service manual, p. 2 of 60. Written in our own words; check the manual for your exact model.

Isolate power before service work

Heat pump · Vitocal 100-WA

There are no user serviceable parts on the heat pump. Service must be done by a licensed contractor.

  1. Deactivate the main power supply to the heat pump, the heating system and all external controls.
  2. Take precautions so power cannot be switched on accidentally during service.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 10. Written in our own words; check the manual for your exact model.

Limit the tilt angle when moving the outdoor module

Heat pump · Vitocal 100-AW AM2V

Excess tilt can send compressor oil into the refrigerant circuit and cause a failure at start-up.

  1. Do not tilt the module more than 30°.
  2. If a tilt beyond 30° is needed, limit it to 45° for no more than about 4 minutes.

Applies to: Handling the outdoor module

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 37. Written in our own words; check the manual for your exact model.

Live components: wait before opening covers

Heat pump · Vitocal 100-AW

Some PCB components stay live after power is removed.

  1. Switch off and isolate the power supply, and safeguard it against reconnection.
  2. Wait at least 4 minutes after power-off before removing any covers, so the voltage fully drops out.
  3. Wear suitable personal protective equipment.

Applies to: Indoor and outdoor units

Source: Vitocal 100-AW AM2V installation manual, p. 5. Written in our own words; check the manual for your exact model.

Lock out power before working on the system

Heat pump · Vitocal 100-S

Turn off the main electrical disconnect before installing, modifying or servicing. There may be more than one disconnect. Lock and tag each one.

  1. Switch off the main disconnect.
  2. Check for additional disconnects.
  3. Lock out and tag each switch with a warning label.

Applies to: All DLCURA units

Source: Viessmann DLCURA installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Louver position memory

Heat pump · Vitocal IND-O

After power is restored, the louver returns to the angle set by the user if it is within the allowed range. If the angle is outside the range, the unit uses the maximum allowed angle. If power fails or the unit is shut down during TURBO, the louver returns to the default angle.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH service manual, PDF p. 10. Written in our own words; check the manual for your exact model.

Maintenance and installation precautions

Heat pump · Vitocal 100-WA

Key service precautions for the unit and its plumbing.

  1. Keep chemicals that corrode copper out of the water loops and out of the equipment room.
  2. Keep the unit out of freezing and unconditioned spaces; it is not for outdoor installation.
  3. Cover the unit during dust-producing work and never run it during construction.
  4. Never lay the unit on its side or drop it; check refrigerant charge after reinstalling.
  5. Use copper tubing only for repairs to the water plumbing; do not use PVC, CPVC, PEX or other plastic pipe.
  6. Check the drain pans and condensate tubing at both ends during annual maintenance.
  7. Keep a service record with this manual.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 51. Written in our own words; check the manual for your exact model.

Never pressurize with oxygen-containing gas

Heat pump · Vitocal 100-S, DLCLRC

Never use air or gases containing oxygen for leak testing or for operating refrigerant compressors. Pressurized mixtures containing oxygen can explode.

  1. Use dry nitrogen or an approved refrigerant-compatible gas for leak testing.
  2. Do not pressurize the system with air.

Applies to: DLCLRC refrigerant circuit service

Source: Viessmann DLCLRC service manual, p. 2 of 60. Written in our own words; check the manual for your exact model.

Never pull a vacuum with the compressor or use oxygen

Heat pump · Vitocal 100-S, DLCLRC

The compressor is not a vacuum pump, and oxygen-containing gas must never be used for leak testing or operation.

  1. Do not run the system compressor as a vacuum pump.
  2. Do not use air or any oxygen-containing gas for leak testing or to operate refrigerant compressors.
  3. Break vacuum with dry nitrogen only.

Applies to: DLCLRC outdoor units

Source: Vitocal 100-S DLCLRC service instructions, p. 1, 9. Written in our own words; check the manual for your exact model.

Order parts with the serial number

Heat pump · Vitocal 100-WA

Some replacement parts are not reverse compatible with earlier versions.

  1. Find the 16-digit serial number on the Vitocal rating plate.
  2. Give the serial number when ordering replacement parts.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 11. Written in our own words; check the manual for your exact model.

Ordering parts requires the 16-digit serial number

Heat pump · Vitocal 100-WA

The 16-digit serial number is on the Vitocal rating plate. Provide it when ordering replacement parts, because some parts are not reverse compatible with previous versions.

  1. Read the 16-digit serial number from the rating plate.
  2. Give the serial number when ordering parts.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 3. Written in our own words; check the manual for your exact model.

Ordering replacement parts

Heat pump · Vitocal 100-AW

Replacement parts need the 16-digit serial number from the indoor or outdoor unit rating plate. Some new parts do not fit earlier versions of the AM2V.

  1. Read the 16-digit serial number from the indoor or outdoor unit rating plate.
  2. Give the serial number when ordering parts.
  3. Check part compatibility before fitting a part to an older unit.

Applies to: Vitocal 100-AW AM2V indoor and outdoor units

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 15. Written in our own words; check the manual for your exact model.

Outdoor temperature operating limits

Heat pump · Vitocal 100-AW AM2V

The air-to-water heat pump only runs efficiently within a set outdoor temperature range. Outside the upper or lower limit it switches off periodically and the controller shows a notification. The controller then brings in available auxiliary heating (e.g. electric auxiliary heater) for space heating and DHW.

  1. Check the outdoor temperature range against the design conditions for the building.
  2. If the controller reports the heat pump is off, confirm the outdoor temperature is outside the limits before investigating further.

Applies to: Outdoor unit, all models

Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 16. Written in our own words; check the manual for your exact model.

Piping and air connection locations

Heat pump · Vitocal 100-WA

Connection legend for the Vitocal 100-WA. Letters refer to the piping connections diagram in the manual.

  1. A: return to ground loop.
  2. B: supply from ground loop.
  3. C: condensate line connection.
  4. D: return air.
  5. E: DHW supply to the DHW tank.
  6. F: DHW tank return to the DHW desuperheater.
  7. G: supply air.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 6. Written in our own words; check the manual for your exact model.

Power and communication wiring between units

Heat pump · D5CSRA

Size wires per NEC or CEC and local codes, using the MCA and MOP values from the electrical data table to size the wires and the disconnect fuse or breaker. Power and communication run as 14/3 field wire: two high-voltage AC wires, one communication wire and one ground. The wiring is polarity sensitive. BX cable is not recommended. In high EMF areas with communication problems, 14/2 stranded shielded wire can replace L2 and S, with the shield grounded at the outdoor unit only. Power is a single-point connection to the outdoor unit.

  1. Size wires and the disconnect using the MCA and MOP values.
  2. Run 14/3 power and communication wire with two AC wires, one communication wire and one ground.
  3. Keep polarity correct between indoor and outdoor units.
  4. Do not use BX cable.
  5. In high EMF areas, use 14/2 stranded shielded wire and ground the shield at the outdoor unit only.

Applies to: All D5CSRA systems

Source: Carrier D5CSRA Product Data, p. 188. Written in our own words; check the manual for your exact model.

Power wiring checks

Heat pump · Vitocal 100-WA

Wrong wiring can injure people and damage the unit.

  1. Confirm L1, L2 and G are not interchanged.
  2. Ground the control.
  3. Use a licensed electrician for line voltage; the certified contractor may do Class 2 low-voltage wiring.

Applies to: All Vitocal 100-WA units

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 24. Written in our own words; check the manual for your exact model.

Preparing for service on flammable refrigerant systems

Heat pump · Vitocal 100-WA

Charging and handling precautions before work starts.

  1. Make sure charging equipment is not contaminated by other refrigerants.
  2. Keep hoses and lines as short as possible to limit the refrigerant held in them.
  3. Keep cylinders in the correct position as per their instructions.
  4. Earth the refrigerating system before charging it with refrigerant.
  5. Label the system when charging is complete.
  6. Take great care not to overfill the refrigerating system.
  7. Do not install auxiliary devices that are potential ignition sources in the ductwork. Hot surfaces above 700°C (1292°F) and electrical switching devices are examples. Only devices declared suitable for R-454B may be installed in connected ductwork.
  8. Do not use means to speed up defrosting or cleaning other than those the manufacturer recommends.
  9. Store the appliance in a room without continuously operating ignition sources such as open flames, operating gas appliances or electric heaters.
  10. Do not pierce or burn the refrigerant circuit. Refrigerants may have no odour.

Applies to: Vitocal 100-WA, R-454B refrigerant

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 56. Written in our own words; check the manual for your exact model.

Provide clearance for service and ductwork

Heat pump · Vitocal 100-WA

Clearances are needed for service access, piping, ductwork and wiring.

  1. Keep at least 24 in. (600 mm) of service clearance.
  2. Leave room for piping, ductwork and electrical connections.
  3. If installed in a closet, provide adequate return air flow to the unit.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 13, 15. Written in our own words; check the manual for your exact model.

Purge air from the heat pump system

Heat pump · Vitocal 100-AW AM2V

Air must be removed through air vents in the system supply. Restrictive piping can trap air and prevent full purging.

  1. Install air vents in the system supply.
  2. Route supply and return lines so no restrictive piping can trap air.

Applies to: Heating water circuit

Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 24. Written in our own words; check the manual for your exact model.

Qualification and work area

Heat pump · Vitocal 100-AW

Work affecting safety must be done by competent persons, under a controlled procedure.

  1. Only competent, licensed persons may open the refrigerant circuit, sealed components or ventilated enclosures.
  2. Work in the open or in a well-ventilated area and avoid confined spaces.
  3. Keep a dry powder or CO2 extinguisher next to the charging area when doing hot work.
  4. Keep all possible ignition sources, including smoking, well away from the work site.

Applies to: Vitocal 100-AW AM2V service work

Source: Vitocal 100-AW AM2V installation manual, p. 8. Written in our own words; check the manual for your exact model.

Ratings lookup for crossover systems

Heat pump · Vitocal 100-S, DLCURA

AHRI ratings for combinations with approved furnaces or cased coils are listed in the AHRI directory.

  1. Check the AHRI directory for ratings certificates.
  2. Check the manufacturer's rating database for additional system combinations.

Applies to: Outdoor unit sizes 18K to 60K

Source: DLCURA installation instructions, p. 20. Written in our own words; check the manual for your exact model.

Reading system information and software versions

Heat pump · Vitocal 100-AW

The System Information menu shows software versions for the indoor unit interface and control board, and lets you restart the indoor unit.

  1. Open the System Information menu.
  2. Read S.W. Ver. HMI for the indoor unit interface software.
  3. Read ODU Software Version for the outdoor unit.
  4. Read S.W. Ver. PCB for the control board software.
  5. Use Control Reboot IDU to restart the indoor unit if needed.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 58. Written in our own words; check the manual for your exact model.

Reading the indoor unit model number

Heat pump · DLFSHCH, Vitocal IND-H

The model code breaks down into: DLF = indoor unit, S = model, voltage (J = 115-1-60, K = 208/230-1-60), H = high wall fan coil, H = heat pump, then nominal capacity (06 = 1/2 ton up to 36 = 3 tons), then major series (A = standard) and variation (X = 1:1, max one fan coil per outdoor unit).

Applies to: DLFSHCH high wall indoor units

Source: Vitocal IND-H DLFSHC service manual, p. 2. Written in our own words; check the manual for your exact model.

Reduce vibration and noise

Heat pump · Vitocal 100-WA

Heat pumps, pumps and fans transmit noise and vibration into the building.

  1. Use flexible ducting or duct connectors to separate the unit from the building.
  2. Place a shock-absorbing pad under the heat pump and associated pumps.
  3. Keep the unit clear of water spray and splashing.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 12, 13, 15. Written in our own words; check the manual for your exact model.

Refrigerant circuit work: checks before starting

Heat pump · Vitocal 100-AW

Checks needed before opening the refrigerant circuit so the risk of ignition is minimised.

  1. Switch off power to the indoor and outdoor units and confirm the system is dead; there may be more than one power circuit.
  2. Check the refrigerant circuit for leaks.
  3. Ventilate well, especially near the floor, and keep it ventilated for the whole job.
  4. Check the area around the heat pump for flammable material and ignition sources, and remove them.
  5. Check the surrounding air with a sparkless, sealed R32-suitable refrigerant detector before, during and after the work.
  6. Inform maintenance staff and people nearby about the work.

Applies to: Vitocal 100-AW AM2V refrigerant circuit

Source: Vitocal 100-AW AM2V installation manual, p. 5. Written in our own words; check the manual for your exact model.

Refrigerant handling and mechanical loads

Heat pump · Vitocal 100-AW

Refrigerant is under pressure and direct contact can cause frostbite, burns or asphyxiation.

  1. Avoid direct contact with liquid and gaseous refrigerant and never breathe in vapours.
  2. Wear personal protective equipment when handling refrigerant.
  3. Do not load lines or components with tools or supports, as this can cause leaks.
  4. Label, store and transport refrigerant-containing components in well-ventilated areas.

Applies to: Vitocal 100-AW AM2V refrigerant circuit

Source: Vitocal 100-AW AM2V installation manual, p. 6. Written in our own words; check the manual for your exact model.

Refrigerant leak: making the area safe

Heat pump · Vitocal 100-AW

Steps to take if a refrigerant leak is suspected in the outdoor unit.

  1. Clear people from the danger zone.
  2. From a safe position, switch off power to all system components.
  3. Ventilate the floor area of the outdoor unit very well.
  4. Remove all ignition sources and tell the system user that no ignition source may be brought in during the repair.
  5. Have an authorised contractor carry out the repair, then recommission only after repair.

Applies to: Vitocal 100-AW AM2V outdoor unit

Source: Vitocal 100-AW AM2V installation manual, p. 7. Written in our own words; check the manual for your exact model.

Refrigerant pipe burial limits

Heat pump · Vitocal 100-S, DLCLRC

Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any section is buried, it needs a 6 in. (152 mm) vertical rise to the outdoor unit valve connections. Longer buried runs let refrigerant migrate to the cold section during shutdown, which can cause slugging and compressor damage at start-up.

  1. Limit buried refrigerant pipe to 36 in. (914 mm).
  2. Provide a 6 in. (152 mm) vertical rise to the outdoor valve connections where any pipe is buried.

Applies to: DLCLRC sizes 36K-58K refrigerant piping

Source: Viessmann DLCLRC service manual, p. 2 of 60. Written in our own words; check the manual for your exact model.

Refrigerant safety before brazing (R32 and R290)

Heat pump · Vitocal 100-S, DLCLRC

Before brazing or removing the four-way valve or compressor, make sure the system holds no refrigerant. For R32 and R290 the method is different.

  1. Evacuate the system and confirm no refrigerant is left.
  2. For R32 and R290, evacuate with a vacuum pump.
  3. Flush the system with nitrogen.
  4. Repeat the evacuation and flush steps before heating brazed parts.

Applies to: DLCLRC 36K-58K, R32 and R290 systems

Source: DLCLRC service manual, p. 53-54. Written in our own words; check the manual for your exact model.

Remove ground loop caps before installing

Heat pump · Vitocal 100-WA

Ground loop connections ship with caps fitted.

  1. Remove the caps from the ground loop connections before installing the piping.

Applies to: Vitocal 100-WA ground loop connections

Source: Vitocal 100-WA installation, service and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Repairs and genuine parts

Heat pump · Vitocal 100-AW

Safety-function components and inverter repairs are restricted.

  1. Replace faulty components only with genuine Viessmann spare parts.
  2. Do not repair the inverter; replace it if it is defective.
  3. Do not drill, heat or otherwise modify a refrigerant circuit that is filled with refrigerant.
  4. Do not operate Schrader valves unless a fill valve or extraction equipment is attached.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V installation manual, p. 6. Written in our own words; check the manual for your exact model.

Scalding risk from high DHW temperature

Heat pump · Vitocal 100-AW

DHW temperatures above 140°F (60°C), such as during the hygiene function, can cause scalding. Mix with cold water at the draw-off points.

  1. Install mixing with cold water at draw-off points before running hygiene function.

Applies to: DHW storage tank and hygiene function

Source: Vitocal 100-AW AM2V Installation, Service and Operating Instructions, p. 56. Written in our own words; check the manual for your exact model.

Serial number needed for replacement parts

Heat pump · Vitocal 100-AW

Indoor and outdoor units each have their own 16-digit serial number on the rating plate. Some replacement parts are not reverse compatible with earlier versions.

  1. Read the 16-digit serial number from the indoor unit or outdoor unit rating plate.
  2. Provide the serial number with the parts order.
  3. Indoor serial prefixes: AM2V 020028 = 7228973, AM2V 034043 = 7228974, AM2V 051078 = 7228975.
  4. Outdoor serial prefixes: AM2V 020028 = 7986309, AM2V 034043 = 7986310, AM2V 051078 = 7986311.

Applies to: Vitocal 100-AW AM2V

Source: Vitocal 100-AW AM2V technical data manual, p. 3. Written in our own words; check the manual for your exact model.

Service clearance

Heat pump · Vitocal 100-WA

The recommended service clearance is 24 in. (600 mm). Leave extra room for piping, ductwork and electrical connections. The side the clearance applies to is not clear in the manual text.

  1. Keep at least 24 in. (600 mm) of service clearance.
  2. Allow extra space for piping, ductwork and electrical connections.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Site selection and high wind

Heat pump · Vitocal 100-S

Place the unit where it is level, can carry its weight and is sheltered from strong wind. In high wind, set the air inlet side facing the wall. Keep snow from blocking the air intake.

  1. Use a rigid base with the unit level.
  2. Use tie-down bolts through the base pan knockouts when a pad or local code requires it.
  3. Do not install where combustible gas could collect.

Applies to: DLCURA outdoor unit

Source: DLCURA installation instructions, p. 10. Written in our own words; check the manual for your exact model.

Storage conditions for the unit

Heat pump · Vitocal 100-WA

Storage temperature limits and conditions for the indoor unit before installation.

  1. Store the unit between -13 °F and 158 °F (-25 °C and 70 °C).
  2. Make sure the storage location has sufficient ventilation.
  3. Have an explosion prevention plan in place for storage.
  4. Protect the unit from damage.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, p. 6. Written in our own words; check the manual for your exact model.

Storage of outdoor unit

Heat pump · Vitocal 100-AW

Storage conditions for the outdoor unit, which is charged with R32 at the factory.

  1. Keep an explosion prevention plan in place for the storage site and make sure it is well ventilated.
  2. Store between -25 °C and 70 °C (-13 °F to 158 °F).
  3. Keep the unit in its factory protective packaging and protect it from damage.
  4. Limit the number of units stored in one place according to local conditions.

Applies to: Vitocal 100-AW AM2V outdoor unit

Source: Vitocal 100-AW AM2V installation manual, p. 7. Written in our own words; check the manual for your exact model.

Support piping and use isolation valves

Heat pump · Vitocal 100-WA

The unit must not carry the weight of the piping.

  1. Support all piping with hangers.
  2. Do not support piping by the Vitocal or its components.
  3. Install isolation valves so system components can be isolated.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Thermostat mounting

Heat pump · Vitocal 100-WA

Mount the thermostat on foam tape to seal the wire hole; silicone can also be used. This keeps drafts off the thermistor and helps prevent short cycling.

  1. Seal the wire penetration behind the thermostat with foam tape or silicone.
  2. Keep the thermostat away from drafts.

Applies to: Thermostat installation

Source: Vitocal 100-WA technical data manual, p. 12. Written in our own words; check the manual for your exact model.

Thermostat terminal use on the terminal strip

Heat pump · Vitocal 100-WA

Y2 is used for optional stage 2 heating or cooling. On a single speed system nothing is wired to the B terminal. E is used for an optional strip heater; leave it unwired if there is no strip heat or aux heat.

  1. Wire stage 2 heat/cool to Y2 if the system has it.
  2. Leave B unwired on single speed systems.
  3. Wire strip heat to E only if the system has strip or aux heat.

Applies to: Terminal strip wiring

Source: Vitocal 100-WA technical data manual, p. 12. Written in our own words; check the manual for your exact model.

Thread sealing on water fittings

Heat pump · Vitocal 100-WA

Thread prep is specified for the installation fittings on the DHW and ground loop connections.

  1. Use an approved pipe sealant or Teflon tape on the installation fittings.
  2. Use a moderate amount of pipe dope.
  3. Leave two threads bare at the end of the thread.
  4. Expect two imperfect threads at the end of the pipe.

Applies to: Vitocal 100-WA water connections

Source: Vitocal 100-WA installation, service and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Two-wrench method for fittings

Heat pump · Vitocal 100-WA

Turning a fitting onto the heat pump connector without support can twist the internal piping and damage the unit.

  1. Use one wrench to hold the heat pump connector so the pipe does not twist.
  2. Use a second wrench to tighten the fitting or piping.
  3. Do not exceed the pressures and temperatures listed for the unit.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA installation, service and operating instructions, p. 16. Written in our own words; check the manual for your exact model.

Unit configuration features

Heat pump · Vitocal 100-WA

The Vitocal 100-WA is a two-stage packaged water source heat pump for heating or cooling and domestic hot water. It supports closed or open loop, uses an integrated desuperheater with pump for DHW, and has a flexible junction box mounting and an information display panel.

Applies to: Vitocal 100-WA

Source: Vitocal 100-WA technical data manual, p. 2-3. Written in our own words; check the manual for your exact model.

Use only dry nitrogen for testing

Heat pump · Vitocal 100-S

Never use air or oxygen-containing gas for leak testing, because it can explode. Only use dry nitrogen to pressure test refrigerant systems. Never use the compressor as a vacuum pump.

Applies to: DLCURA refrigerant circuit

Source: DLCURA installation instructions, p. 16. Written in our own words; check the manual for your exact model.

Use the refrigerant service ports

Heat pump · Vitocal 100-S

The outdoor unit has service ports on the liquid and suction lines, and Schrader gauge ports on the compressor suction and discharge lines.

  1. Locate the liquid line service valve and the suction line service valve.
  2. Connect gauges to the Schrader ports on the compressor suction and discharge lines.
  3. Use the brass service caps when the ports are not in use.

Applies to: DLCURA outdoor units

Source: DLCURA technical data manual, p. 96. Written in our own words; check the manual for your exact model.

Wait before opening covers after power-off

Heat pump · Vitocal 100-WA

Some PCB components stay live after the supply is switched off.

  1. Switch off the power at the breaker and confirm the system is dead.
  2. Remember that a control circuit and possibly several power circuits may be present.
  3. Wait at least 4 minutes after switching off before removing any covers.
  4. Lock out the system against reconnection and wear suitable PPE.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, p. 4. Written in our own words; check the manual for your exact model.

Water supply and potable water connection

Heat pump · Vitocal 100-WA

The unit needs a water supply. Potable water is not recommended for it.

  1. Refer to the Water Quality section for the required water quality.
  2. If potable water is used, protect the supply against back-siphonage at the equipment.

Applies to: Vitocal 100-WA

Source: vitocal_100-wa_ap1t_ios.pdf, p. 6. Written in our own words; check the manual for your exact model.

Wiring alternative in high EMF areas and multi-zone matches

Heat pump · Vitocal 100-S, DLCSRB

In high electromagnetic field areas with communication problems, a 14/2 stranded shielded wire may replace L2 and (S). Multi-family and residential fan coil matches need separate power for the indoor and outdoor units and a 24V interface kit.

  1. Replace L2 and (S) with 14/2 stranded shielded wire between the outdoor and indoor units if EMF communication problems exist.
  2. Ground the shield at the outdoor unit only.
  3. For multi-family or residential fan coil matches, provide separate power to the indoor and outdoor units.
  4. Install the 24V interface kit and follow its installation manual.

Applies to: DLCSRB outdoor units with indoor fan coil matches

Source: DLCSRB Service Manual, p. 3. Written in our own words; check the manual for your exact model.

Discharge the inverter capacitors before service

Mini split · Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor, Viessmann DLFSHB high wall indoor

The big electrolytic capacitors on the outdoor board stay charged after power-off.

  1. Turn power off and lock out.
  2. Put a resistor of about 100 ohm 40 W (or a soldering iron plug) across the + and - capacitor terminals before touching the board.

Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)

Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Troubleshooting Safety p.16. Written in our own words; check the manual for your exact model.

46 F (8 C) heating freeze protection

Mini-split · DLFSHC

When the compressor runs, the indoor fan runs without the anti-cold air function. When the compressor is off, the indoor fan is off. The owner manual Freeze Protection section explains how to enable this feature.

  1. Enable the 46 F (8 C) heating feature using the owner manual Freeze Protection instructions.

Applies to: HEATING mode freeze protection

Source: DLFSHC service manual, p. 12. Written in our own words; check the manual for your exact model.

Agency listings and coil testing

Mini-split · Vitocal 100-S

The unit meets ANSI/ASHRAE 15 and the NEC. It is evaluated to UL 60335-2-40 and listed in the CEC directory. The cabinet is rated for a 500-hour salt spray test. Air-cooled condenser coils are leak tested at 550 psig.

Applies to: DLCURA outdoor units

Source: Vitocal 100-S DLCURA technical data manual, p. 96. Written in our own words; check the manual for your exact model.

Air filter and carbon filter care

Mini-split · Vitocal IND-F

Clean the air filter monthly. Wash the carbon filter every 6 months. The manufacturer recommends replacing it yearly.

  1. Turn off the breaker before opening the front panel.
  2. Open the front panel and remove the air filter.
  3. Remove the carbon filter by holding the frame tabs and releasing the four claws.
  4. Vacuum the air filter with the air-in side facing up, or wash it in water with the air-in side facing down.
  5. For heavy dust, use a soft brush and mild detergent, then dry in a cool place.
  6. Refit the filters as they were and close the front panel. Never run the unit without the air filters.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 14. Written in our own words; check the manual for your exact model.

Air sweep and louver settings

Mini-split · Vitocal IND-C

The indoor unit has a motor driven vertical air sweep and motor driven louvers. The louvers adjust for 2, 3 or 4 way discharge. The air sweep operation is user selectable.

Applies to: DLFSCBH and DLFLCBH

Source: Vitocal IND-C technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Anti-static protection for electrical parts

Mini-split · Vitocal IND-O, DLFSOAH

Wear anti-static gloves when handling the electronic control box and control boards.

  1. Put on anti-static gloves before touching the electrical parts.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK

Source: DLFSOAH Service Manual, p. 44-46. Written in our own words; check the manual for your exact model.

AUTO mode on multi-zone systems

Mini-split · DLFSDAH, DLFLDAH

AUTO changeover is meant for single-zone use. On multi-zone systems it can put an indoor unit into STANDBY, shown as two dashes (--), which keeps it off until all indoor units run the same mode (COOL or HEAT). HEAT is the priority mode, and simultaneous HEAT and COOL is not allowed.

  1. On multi-zone systems, set all indoor units to the same mode (COOL or HEAT).
  2. Use AUTO only on single-zone installs.

Applies to: All indoor units in multi-zone systems

Source: Viessmann Vitocal IND-D Owner's Manual, p. 3. Written in our own words; check the manual for your exact model.

AUTO-RESTART after power failure

Mini-split · Vitocal IND-F

An auto-restart module stores the settings before a power loss and resumes them 3 minutes after power returns (SWING excluded). If FORCED COOLING was stored, the unit runs COOLING for 30 minutes then AUTO at 75°F (24°C). If the unit was off and must start, the compressor delays 1 minute; otherwise it waits 3 minutes.

Applies to: Power restore

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 11. Written in our own words; check the manual for your exact model.

Battery life and when to replace batteries

Mini-split · Vitocal IND-O

Average battery life under normal use is about 6 months. Remove batteries if the remote will sit unused for several weeks to prevent leakage damage.

  1. Replace batteries when the indoor unit does not give an audible beep after a remote command.
  2. Replace batteries if the remote's Transmission Indicator does not light.
  3. Remove batteries if the remote will not be used for several weeks.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-O DLFSOAH owner's manual, p. 6. Written in our own words; check the manual for your exact model.

Board measurement procedure

Mini-split · Vitocal IND-F

Measure board signals with power on only when needed. Pulsating DC signals should move constantly when a signal is present.

  1. Disconnect main power.
  2. Remove outdoor top cover (outdoor board) or front and control box covers (indoor board).
  3. Reconnect power and probe inputs and outputs with the multimeter; red probe to hot signal, black to ground or negative.
  4. Disconnect main power before reinstalling any board.

Applies to: Outdoor and indoor control boards

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 13. Written in our own words; check the manual for your exact model.

Boost mode for faster temperature change

Mini-split · Vitocal IND-F

BOOST helps the unit reach the set point in the shortest possible time.

  1. Press BOOST on the remote to reach the preset temperature faster.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 5. Written in our own words; check the manual for your exact model.

Built-in protections on DLCLRC units

Mini-split · Vitocal 100-S

The control board stops the unit and shows an error code when it detects abnormal conditions. Protections listed include compressor overcurrent and overload, high discharge temperature, IPM module, and low voltage protection, plus a 3 minute compressor time delay.

  1. Check the error display on the indoor or outdoor control for the code.
  2. Look up the code in the manual's error code table if one is provided for this model.
  3. Do not bypass the compressor time delay; wait out the 3 minute delay before restarting.

Applies to: DLCLRC outdoor units

Source: DLCLRC technical data manual, p. 2, p. 4. Written in our own words; check the manual for your exact model.

Buried refrigerant pipe warning

Mini-split · Vitocal IND-F

If any section of pipe is buried, there must be a vertical rise to prevent refrigerant migration and slugging.

  1. Do not bury more than 36 in (914 mm) of refrigerant pipe.
  2. Provide at least 6 in (152 mm) of vertical rise to the outdoor unit valve connections.

Applies to: Refrigerant piping

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 2. Written in our own words; check the manual for your exact model.

Buried refrigerant piping limits

Mini-split · DLFSHC

Do not bury more than 36 in (914 mm) of refrigerant pipe. If any section is buried, it needs a 6 in (152 mm) vertical rise to the outdoor unit valve connections. Excess buried length can let refrigerant migrate to the cold section and cause slugging that may damage the compressor at start-up.

  1. Limit buried refrigerant pipe to 36 in (914 mm) maximum.
  2. If any pipe is buried, provide a 6 in (152 mm) vertical rise to the outdoor valve connections.

Applies to: DLFSHC refrigerant piping

Source: DLFSHC installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Check the airflow and table title before using a performance value

Mini-split · D5CSRA

Several performance tables appear on the same page and carry similar layouts. The airflow in CFM and the indoor unit type decide which block to use. A value from the wrong airflow or indoor unit will give a wrong capacity or power reading.

  1. Confirm the indoor unit model and capacity size before reading any matrix.
  2. Confirm the airflow setting on site matches the CFM value of the block.
  3. Compare the measured outdoor and indoor conditions with the row and column headings before reading TC, S/T or PI.

Applies to: D5CSRA cooling performance tables, pages 64 to 72

Source: D5CSRA Product Data, p. 64-72. Written in our own words; check the manual for your exact model.

CLEAN (self-clean evaporator) function

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Available on sizes 18 to 24 only. Cleans and dries the evaporator. Only works in COOL or DRY mode.

  1. Press CLEAN in COOL or DRY mode to start.
  2. Cycle runs 16 minutes, then the unit shuts off by itself.
  3. Press CLEAN during the cycle to cancel and turn off the unit.

Applies to: Sizes 18 to 24

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 10. Written in our own words; check the manual for your exact model.

Clean the air filter

Mini-split · Vitocal Ind-O

Clean every two weeks, or more often in dusty areas. Replace the filter if it is heavily clogged and cannot be cleaned. Disconnect power first, except when only cleaning the filter.

  1. Press the circular position to open the two screw covers, then remove the two screws.
  2. Hold and open the air grille, then remove the air filter.
  3. Clean with a vacuum cleaner (intake side facing up) or with clean water (intake side facing down). For heavy dust, use a soft brush and natural detergent, then dry in a cool place.
  4. Do not dry the filter in direct sunlight or near heat or fire.
  5. Re-install the filter and reset the air grille.

Applies to: Indoor unit air filter

Source: Viessmann DLFSOAH Owner's Manual, p. 14-15. Written in our own words; check the manual for your exact model.

Cleaning precautions for the indoor unit

Mini-split · Vitocal Ind-O

Water and chemicals can damage the unit and create electrical hazards.

  1. Turn off the indoor unit circuit breaker before cleaning.
  2. Use only a soft dry cloth, or a cloth with warm water (not above 104°F / 40°C) on the front panel.
  3. Do not use chemicals, benzene, paint thinner or polishing powder.
  4. Do not wash the unit under running water or use water inside the unit.

Applies to: Indoor unit exterior and interior

Source: Viessmann DLFSOAH Owner's Manual, p. 14-15. Written in our own words; check the manual for your exact model.

Cleaning the coil and front panel

Mini-split · Vitocal IND-F

Clean the coil at the start of each cooling season. Use only mild methods on the panel.

  1. Clean the indoor coil with a vacuum or long-bristle brush to avoid damaging the fins.
  2. Wear cut protection when cleaning the coil fins.
  3. Wipe the front panel with a soft, dry cloth.
  4. Do not use water hotter than 105°F (40.6°C), do not pour water onto the fan coil, and do not use abrasive or petroleum cleaners.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 14, p. 15. Written in our own words; check the manual for your exact model.

Communication and wiring hazards

Mini-split · Vitocal 100-S

Wiring safety points from the manual.

  1. Make sure every wire is tightly connected. Loose wiring can overheat the terminal or cause a malfunction.
  2. Keep all wires away from the refrigerant tubing, compressor and moving parts.
  3. Provide a disconnect within sight of and readily accessible from the unit.
  4. Route the connecting cable through the hole in the conduit panel.

Applies to: DLCURA outdoor units

Source: DLCURA technical data manual, p. 83. Written in our own words; check the manual for your exact model.

Control features and fan speed options

Mini-split · Vitocal IND-C

Microprocessor control holds room temperature, selects the best fan speed and runs self diagnostics. The fan speed can be set to high, medium, low or automatic. Automatic heating to cooling changeover applies in heat pump mode, with a deadband to prevent rapid mode cycling. Other functions include automatic restart after power failure, a 24 hour timer, indoor coil freeze protection, indoor coil high temperature protection in heat pump mode, dehumidification, fan only operation and wireless set point control.

Applies to: DLFSCBH and DLFLCBH

Source: Vitocal IND-C technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Control system and sensors

Mini-split · Vitocal IND-C

Thermistors in the indoor air inlet and indoor coil feed the indoor board. Heat pumps add an outdoor coil thermistor.

  1. Check the indoor air inlet thermistor and indoor coil thermistor when checking control readings.
  2. On heat pumps, also check the outdoor coil thermistor.
  3. Outdoor units also run their own microprocessor.

Applies to: Heat pump cassette systems

Source: Viessmann Vitocal IND-C ductless technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Controller behavior after power failure

Mini-split · DLFSDAH and DLFLDAH

The unit includes automatic restart. After a power failure it returns to the same operating conditions it was running at the time of failure.

Applies to: DLFSDAH and DLFLDAH indoor ducted fan coils

Source: Viessmann Vitocal IND-D DLFSDAH & DLFLDAH technical data manual, p. 32. Written in our own words; check the manual for your exact model.

Controller temperature display and automatic airflow limits

Mini-split · DLFSDAH, DLFLDAH

The wired controller can show °F or °C and changes temperature in 1 degree steps. Do not use automatic airflow with booster fans, an outdoor air processing unit or a duct HRV.

  1. Set the display to °F or °C on the wired controller as needed.
  2. Do not run AF with booster fans, outdoor air processing units or duct HRVs; use manual SP settings instead.
  3. If the ductwork or static pressure changes, redo the SP or AF setup.

Applies to: Ducted indoor units

Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, pp. 11 and 14. Written in our own words; check the manual for your exact model.

Crankcase and base pan heaters

Mini-split · Vitocal 100-S

Crankcase heater is standard on all sizes; its clamps must be placed around the compressor oil sump. Base pan heater is standard on all sizes. The base pan has multiple drain holes for defrost drainage; seal them with rubber plugs only where the condensate drain must be redirected.

  1. Place the crankcase heater clamps around the compressor oil sump.
  2. If the condensate must be redirected, seal the base pan drain holes with the rubber plugs listed for the model.

Applies to: All DLCURAH outdoor units

Source: DLCURAH Technical Data Manual, p. 3. Written in our own words; check the manual for your exact model.

Discharge capacitors before servicing the outdoor PCB

Mini-split · Vitocal 100-S

Electrolytic capacitors keep a charge after power is removed. Discharge them before touching the outdoor board. The manual gives the discharge resistor value as 100 ohm, 40 W (the ohm symbol is missing in the printed text).

  1. Shut off power and lock out the disconnect.
  2. Connect a discharge resistor (about 100 ohm, 40 W) or a soldering iron plug across the + and - terminals of the electrolytic capacitor. On some units the terminals are on the back side of the outdoor PCB.
  3. Confirm the capacitor is discharged before handling the board.

Applies to: DLCSRB outdoor units

Source: DLCSRB service manual, p. 25. Written in our own words; check the manual for your exact model.

Display indicators on the indoor unit

Mini-split · DLFSHC

The display window shows temperature, operating feature and error codes. Some indicators light for 3 seconds when a feature is turned on or off, such as ECO, defrost, timer, Active Clean, self clean, or 46°F (8°C) heating mode.

  1. Read the display window for temperature, feature and error information.
  2. Note which feature indicator lights for 3 seconds when a mode is changed.

Applies to: DLFSHC indoor unit display

Source: DLFSHC installation instructions, p. 5. Written in our own words; check the manual for your exact model.

Do not release refrigerant before evacuation

Mini-split · Vitocal IND-F

Evacuation instructions are in the outdoor unit manual. Keep the outdoor refrigerant charge until evacuation is finished.

  1. Follow the outdoor unit installation instructions for system evacuation.
  2. Do not release the refrigerant charge from the outdoor unit until evacuation is complete.

Applies to: All sizes

Source: DLFSFA and DLFLFA installation instructions, p. 13. Written in our own words; check the manual for your exact model.

Do not use automatic airflow adjustment in these cases

Mini-split · DLFSDAH and DLFLDAH

Automatic airflow adjustment should be avoided when the duct system has added equipment or changed.

  1. Do not adjust dampers while automatic airflow adjustment is running.
  2. Do not run automatic airflow adjustment from the remote when booster fans, an outdoor air processing unit or an HRV via duct are fitted.
  3. If the ventilation paths have changed, repeat the adjustment from step 3 of the airflow procedure.

Applies to: Ducted indoor units

Source: Vitocal IND-D technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Do not use oxygen-containing gas for leak testing

Mini-split · Vitocal IND-O

Never use air or gases containing oxygen for leak testing or for running refrigerant compressors. Mixtures can explode.

Applies to: Leak testing and system pressurising

Source: DLFSOAH Service Manual, p. 1-2. Written in our own words; check the manual for your exact model.

Do not use oxygen-containing gases for leak testing

Mini-split · Vitocal IND-F

Air or other gases containing oxygen must not be used for leak testing or running refrigerant compressors. Mixtures with oxygen can explode.

  1. Use dry nitrogen or an approved gas for pressure and leak testing.
  2. Never run the compressor with air or oxygen-containing gas.

Applies to: All DLFSFBH units

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 1. Written in our own words; check the manual for your exact model.

DRYING mode behaviour and low room temperature protection

Mini-split · Vitocal IND-F

Indoor fan is fixed at breeze and cannot be changed. In DRYING mode the compressor stops if room temperature is below 50°F (10°C) and restarts only after the room exceeds 53.6°F (12°C).

Applies to: DRYING mode

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 10. Written in our own words; check the manual for your exact model.

Electrical shock hazard before service

Mini-split · Vitocal IND-F

Power to the unit must be off before installing, modifying or servicing it.

  1. Turn the main electrical disconnect to OFF. There may be more than one disconnect.
  2. Lock out and tag each disconnect with a warning label.

Applies to: All DLFSFBH units

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 1. Written in our own words; check the manual for your exact model.

Energy saving recommendations

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Owner guidance to improve efficiency.

  1. Pick a comfortable set point and avoid constant changes.
  2. Keep the filter clean.
  3. Use drapes or shades on very hot days.
  4. Limit run time with the TIMER function.

Applies to: All models

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 12. Written in our own words; check the manual for your exact model.

FAN mode operation

Mini-split · Vitocal IND-F

In FAN mode the outdoor fan and compressor are off. Temperature setting is disabled.

  1. Select high, medium, low or auto indoor fan speed.
  2. Louver operates the same as in COOLING mode.
  3. Auto fan control is available in this mode.

Applies to: DLFSFBH 12K

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 8. Written in our own words; check the manual for your exact model.

Field wiring between indoor and outdoor unit

Mini-split · Vitocal IND-F

Power and communication run as four conductors. Two are line voltage, one is the communication (S) wire, and one is ground. The polarity matters. Do not use BX cable.

  1. Use 14/3 stranded wire with ground, rated 600 V, for the outdoor-to-indoor run.
  2. If there is high EMF interference and communication problems, you may use 14/2 stranded shielded wire in place of L2 and S. Land the shield to ground at the outdoor unit only.
  3. Size wire per NEC/CEC and local code, using the outdoor unit MCA and MOCP values.
  4. Make every connection firmly. Keep wires away from refrigerant tubing, the compressor and moving parts.
  5. Provide a disconnect within sight of and readily accessible from the unit.

Applies to: DLFSFBH 12K ductless system field wiring

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 4. Written in our own words; check the manual for your exact model.

Final tubing check before charge

Mini-split · Vitocal IND-O

Check that the factory tubing on both indoor and outdoor units has not shifted in shipping.

  1. Make sure tubes do not rub against each other or sheet metal.
  2. Check the wire ties on the feeder tubes are secure and tight.

Applies to: Factory tubing on indoor and outdoor units

Source: DLFSOAH Service Manual, p. 7. Written in our own words; check the manual for your exact model.

Final tubing check before charging

Mini-split · Vitocal IND-F

Factory tubing can shift in shipping and cause rubbing and vibration.

  1. Check that factory tubing on the indoor and outdoor units has not moved.
  2. Make sure no tubes rub against each other or against sheet metal.
  3. Check that feeder tube wire ties are secure and tight.
  4. Never use the system compressor as a vacuum pump.

Applies to: Refrigerant circuit

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 7. Written in our own words; check the manual for your exact model.

FOLLOW ME function

Mini-split · Vitocal IND-F

Pressing FOLLOW ME on the remote or wired controller makes the buzzer sound and the PCB uses the remote's room temperature, shielding the unit's own room sensor. Repeated remote signals every 3 minutes do not beep. If no remote signal for 7 minutes, or FOLLOW ME is pressed again, it turns off and the unit uses its own room sensor.

Applies to: FOLLOW ME

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 11. Written in our own words; check the manual for your exact model.

FORCED COOLING and FORCED AUTO modes

Mini-split · Vitocal IND-F

FORCED COOLING: compressor runs at F2 frequency and indoor fan runs BREEZE; after 30 minutes the unit enters AUTO at 75.2°F (24°C). FORCED AUTO is normal AUTO with a 75.2°F (24°C) setpoint.

Applies to: Forced operation

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 10. Written in our own words; check the manual for your exact model.

Heating performance in cold weather

Mini-split · Vitocal IND-F

The HEAT function performance drops as outdoor temperature falls.

  1. In very cold outdoor conditions, use this unit together with other heating appliances.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 8. Written in our own words; check the manual for your exact model.

How to read the cooling capacity tables

Mini-split · D5CSRA

Each cooling table is set up by airflow (CFM), outdoor dry bulb and indoor wet bulb. Find the block for your airflow and outdoor temperature, then read the column for your indoor dry bulb. TC is total cooling capacity in Btu/h, S/T is sensible-to-total ratio, and PI is power input in kW. Only highlighted values are tested; the rest are simulated for reference.

  1. Pick the table for your indoor unit type and capacity (Tables 14 to 71).
  2. Select the airflow block that matches the fan speed.
  3. Find the outdoor dry bulb row for the actual outdoor temperature.
  4. Match the indoor wet bulb column and the indoor dry bulb sub-column.
  5. Read TC, S/T and PI from that cell and use highlighted values as tested data.

Applies to: D5CSRA cooling performance tables

Source: D5CSRA Product Data, pp. 13 to 16. Written in our own words; check the manual for your exact model.

How to read the D5CSRA cooling performance grids

Mini-split · D5CSRA

Each grid gives total cooling (TC), sensible/total ratio (S/T) and power input (PI) for one capacity and indoor unit type. Read them by outdoor dry bulb and indoor wet/dry bulb conditions at a stated airflow.

  1. Find the table for the capacity (9K, 12K, 18K, 24K, 30K or 36K) and the indoor unit type (high wall, one-way cassette, 4-way cassette, AE console, ceiling and floor console, low or high static slim duct, AHU2).
  2. Note the airflow (CFM) printed at the start of the block.
  3. Find the outdoor dry bulb (DB) row, from -22°F (-30°C) up to 122°F (50°C).
  4. Find the column for the indoor wet bulb (WB) and indoor dry bulb (DB) pair.
  5. Read TC, S/T and PI from the same row and column.
  6. Check that the reading is for the correct airflow block, because each block repeats the same conditions for another CFM value.

Applies to: D5CSRA cooling performance tables, Tables 14 to 42 (pages 13 to 130)

Source: D5CSRA Product Data, p. 72-80. Written in our own words; check the manual for your exact model.

How to read the D5CSRA cooling performance tables

Mini-split · Vitocal 100 D5CSRA

Each cooling table is split into blocks. Every block is headed by an airflow in CFM. Inside a block, rows are outdoor dry-bulb temperatures and columns are indoor wet-bulb and dry-bulb temperatures. Each cell holds three values labelled TC, S/T and PI. The pages do not define these three abbreviations.

  1. Pick the cooling table that matches the indoor unit type and nominal size (for example Table 16, 12K cooling, high wall).
  2. Find the airflow block that matches the CFM you are using.
  3. Go to the outdoor dry-bulb row for the outdoor temperature you are working at.
  4. Read across to the indoor wet-bulb group, then to the indoor dry-bulb column for the room conditions.
  5. Read the TC, S/T and PI values from that cell. Check the table footnotes for the definition of each value.

Applies to: D5CSRA cooling performance tables, Tables 14 to 42 (pages 16 to 24 contain Tables 14 to 16 and the start of Table 15 and 16 blocks)

Source: Viessmann Vitocal 100 D5CSRA product data, p. 16-24. Written in our own words; check the manual for your exact model.

Indoor unit clearances

Mini-split · DLFSHC

Keep the top clearance at 5.9 in (15 cm) minimum for proper return airflow. The top clearance may be reduced to 2 in (50 mm) only if the left and right clearances are met. Reduced top clearance can lower unit performance. Keep 4.75 in (12 cm) minimum at the sides, and keep 6 ft (1.8 m) clearance as marked in the clearance figure.

  1. Allow space for airflow and service.
  2. Check top clearance: 5.9 in (15 cm) minimum.
  3. If top clearance is reduced to 2 in (50 mm), confirm the left and right clearances are met.
  4. Check side clearance: 4.75 in (12 cm) minimum.

Applies to: DLFSHC indoor units, sizes 06K-36K

Source: DLFSHC installation instructions, p. 7. Written in our own words; check the manual for your exact model.

Indoor unit does not respond to the remote

Mini-split · Vitocal 100-S

Use the remote controller to check the indoor unit first. The manual says a non-responding unit points to the indoor PCB, while a responding unit with a display fault points to the display board.

  1. Operate the unit with the remote controller.
  2. If the unit does not respond to the remote, replace the indoor PCB.
  3. If the unit responds to the remote but the display shows a fault, replace the display board.

Applies to: DLCSRB indoor high wall units

Source: DLCSRB service manual, p. 26. Written in our own words; check the manual for your exact model.

Indoor unit filter access

Mini-split · Vitocal IND-C

The grille hinges open for access to the cleanable filters, indoor fan motor and control box. The filter track is at the top of the unit and factory supplied filters are cleanable.

  1. Open the hinged grille.
  2. Remove the cleanable filters from the filter track at the top of the unit and clean them.

Applies to: DLFSCBH and DLFLCBH

Source: Vitocal IND-C technical data manual, p. 13. Written in our own words; check the manual for your exact model.

Indoor-to-outdoor wiring rules

Mini-split · Vitocal IND-F

Connections between indoor and outdoor units are polarity sensitive. Wrong termination causes a fault code.

  1. Do not use thermostat wire for any connection between indoor and outdoor units.
  2. Connect the indoor and outdoor units exactly as the connection diagram shows.
  3. Check polarity on every connection, since improper termination gives a fault code.

Applies to: All sizes

Source: DLFSFA and DLFLFA installation instructions, p. 12. Written in our own words; check the manual for your exact model.

Installation prerequisites: disconnect and leak test gas

Mini-split · DLFSHC

Lock out the main electrical disconnect before installing, modifying or servicing. Never use air or oxygen-containing gases for leak testing or running refrigerant compressors.

  1. Switch off the main electrical disconnect and lock and tag it before work starts.
  2. Do not use air or oxygen-containing gas for leak testing.

Applies to: DLFSHC installation and service

Source: DLFSHC installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Isolate power before servicing

Mini-split · Vitocal IND-O

Main electrical disconnect must be OFF before installing, modifying or servicing the unit. There may be more than one disconnect.

  1. Switch off all disconnects.
  2. Lock out and tag each switch with a warning label.

Applies to: All service work on the indoor unit

Source: DLFSOAH Service Manual, p. 1-2. Written in our own words; check the manual for your exact model.

Leak testing and pressurising

Mini-split · Vitocal 100-S

Never use air or gases containing oxygen for leak testing or running refrigerant compressors. Mixtures of air and oxygen can explode.

Applies to: DLCURA refrigerant circuit

Source: Viessmann DLCURA Service Manual, p. 1. Written in our own words; check the manual for your exact model.

LED display light on/off

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Turns the display light on or off from the remote.

  1. Press LED to toggle the display light.

Applies to: Wireless remote

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 10. Written in our own words; check the manual for your exact model.

Lock out power before service

Mini-split · Vitocal 100-S

Before installing, modifying or servicing the system, the main electrical disconnect must be OFF. There may be more than one disconnect.

  1. Switch off the main disconnect.
  2. Check for additional disconnects.
  3. Lock out and tag each switch with a warning label.

Applies to: DLCURA system

Source: Viessmann DLCURA Service Manual, p. 1. Written in our own words; check the manual for your exact model.

Louver position memory

Mini-split · DLFSHC

When restarted, the louver returns to the angle the user set if it is within range. If the louver exceeds range, the unit stores the maximum allowed angle. After power failure or a shutdown in TURBO mode, the louver returns to the default angle.

  1. Confirm louver angle after restart.
  2. Expect the default angle after power failure or TURBO shutdown.

Applies to: Louver control

Source: DLFSHC service manual, p. 12. Written in our own words; check the manual for your exact model.

Never use the compressor as a vacuum pump

Mini-split · Vitocal IND-F

Running the system compressor to pull a vacuum can damage equipment or cause improper operation.

  1. Do not use the system compressor as a vacuum pump.

Applies to: All sizes

Source: DLFSFA and DLFLFA installation instructions, p. 13. Written in our own words; check the manual for your exact model.

Outdoor unit compatibility

Mini-split · DLFSDAH, DLFLDAH

The indoor units are backward compatible with listed single zone and multi-zone outdoor units. Check the current compatibility chart before pairing.

  1. Pair with 38MAQ sizes 09K to 24K, 38MBQ sizes 36K to 48K, or 38MGQ multi-zone systems.
  2. Check the current compatibility chart for the exact indoor and outdoor match-up.

Applies to: DLFSDAH and DLFLDAH indoor units

Source: Viessmann DLFSDAH & DLFLDAH Technical Data Manual, p. 9. Written in our own words; check the manual for your exact model.

Outdoor unit service access and coil cleaning

Mini-split · Vitocal 100-S

Removing the top panel (36K) or side panel (48K and 58K) gives access to the control compartment. Coils are draw-thru and can be cleaned from the inside with a pressure hose and detergent.

  1. Remove the top panel on the 36K or the side panel on the 48K and 58K to reach the control compartment.
  2. Clean the coil from the inside outward with a pressure hose and detergent.
  3. Check that base pan drain holes are open, or use the RCD rubber plugs if the condensate must be redirected.

Applies to: DLCLRC outdoor units

Source: DLCLRC technical data manual, p. 2, p. 4. Written in our own words; check the manual for your exact model.

Performance tables on pages 72 to 80 are for the AE Console

Mini-split · D5CSRA

Pages 72 to 80 contain the 9K, 12K, 18K and AE console cooling grids. The table titles and CFM values change from page to page, so confirm the table title on each page before taking a reading.

  1. Confirm the table title (Table 28, 29 or 30 - AE Console) at the top of each page.
  2. Confirm the capacity in the title (9K, 12K or 18K) matches the outdoor unit you are checking.
  3. Use the continued-table pages with the same title and the matching airflow block.

Applies to: D5CSRA AE Console cooling performance

Source: D5CSRA Product Data, p. 72-80. Written in our own words; check the manual for your exact model.

Periodic maintenance schedule

Mini-split · Vitocal IND-F

The schedule covers indoor and outdoor unit tasks. Increase the frequency in dusty areas. Outdoor tasks marked with a dagger need qualified service personnel.

  1. Indoor unit: clean the air filter monthly (more often in dusty zones).
  2. Indoor unit: replace the carbon filter, washing it every 6 months and replacing it yearly.
  3. Indoor unit: change the remote control batteries.
  4. Outdoor unit: clean the coil from the outside, and clean the drain pans and fan wheel by qualified personnel.
  5. Outdoor unit: qualified personnel should blow air over electric parts, check electrical connections and fan tightening, and clean the coil from the inside.
  6. Refer to the Installation Manual for qualified service work.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 15, p. 16. Written in our own words; check the manual for your exact model.

Piping routing when outdoor unit is higher than indoor unit

Mini-split · DLFSHC

If the outdoor unit sits higher than the indoor unit, install an inverted trap in the connection pipe. This keeps rain from running into the wall before it reaches the indoor unit.

  1. Place an inverted trap in the connection pipe when the outdoor unit is above the indoor unit.
  2. Check that rain drips from the connection pipe before it enters the wall.

Applies to: DLFSHC refrigerant piping

Source: DLFSHC installation instructions, p. 4. Written in our own words; check the manual for your exact model.

Power and communication wiring between indoor and outdoor unit

Mini-split · DLFSHC

Main power is supplied to the outdoor unit. The field-supplied 14/3 cable carries four wires: two high-voltage AC, one communication and one ground. Wiring is polarity sensitive. Do not use BX cable. Disconnecting the outdoor unit also de-energizes the indoor unit.

  1. Size wires per NEC or CEC and local codes, using the outdoor unit MCA and MOCP.
  2. Use 14/3 cable with four wires: two AC power, one communication, one ground.
  3. Keep the polarity of the indoor-to-outdoor wiring correct.
  4. Do not use BX cable.
  5. Where EMF interference causes communication faults, 14/2 stranded shielded wire may replace wires 2 and 3, with the shield grounded at the outdoor unit only.
  6. Make every connection tight and keep wires away from refrigerant tubing, the compressor and moving parts.

Applies to: DLFSHC indoor and outdoor unit interconnect

Source: DLFSHC installation instructions, p. 7. Written in our own words; check the manual for your exact model.

Power wiring procedure

Mini-split · Vitocal 100-S

Field power connection to the outdoor unit.

  1. Remove the electrical cover of the outdoor unit.
  2. Connect each fork terminal to its matching terminal, matching the wire labels.
  3. Tighten each fork terminal firmly to its terminal.
  4. Insulate unused wires with electrical tape and keep them clear of electrical and metal parts.
  5. Reinstall the electrical control box cover.

Applies to: DLCURA outdoor units

Source: DLCURA technical data manual, p. 82. Written in our own words; check the manual for your exact model.

Pre-season and long non-use inspection

Mini-split · Vitocal Ind-O

Do this after long periods of non-use or before frequent use.

  1. Clean all filters.
  2. Run FAN function until the unit dries out completely.
  3. Turn off the unit and disconnect the power.
  4. Check for damaged wires.
  5. Check for leaks.
  6. Make sure nothing blocks the air inlets and outlets.

Applies to: Indoor and outdoor units

Source: Viessmann DLFSOAH Owner's Manual, p. 15. Written in our own words; check the manual for your exact model.

Preparing for extended shutdown

Mini-split · Vitocal IND-F

Dry the internal parts before the unit is left idle for a long time.

  1. Clean the filters and refit them in the unit.
  2. Run the unit in FAN ONLY mode for 12 hours to dry the internal parts.
  3. Turn the main power supply off.
  4. Remove the batteries from the remote control.

Applies to: Vitocal IND-F floor console, Size 12 (12XAK)

Source: Vitocal IND-F floor console ductless system owner's manual, p. 15. Written in our own words; check the manual for your exact model.

Protection features built into the system

Mini-split · DLFSDAH, DLFLDAH

The indoor units have freeze and high temperature protection. Heat pumps also have cold blow protection, freeze protection mode and auto restart.

Applies to: All DLFSDAH and DLFLDAH systems

Source: Viessmann vitocal_ind_dlfsda_hk_tdm Technical Data Manual, p. 2. Written in our own words; check the manual for your exact model.

Rain protection when the outdoor unit is higher than the indoor unit

Mini-split · VITOCAL IND-F

Stop rain running down the connection pipe into the indoor unit.

  1. Form a downward arc in the connection pipe before it enters the wall to the indoor unit so rain drips off before reaching the wall.

Applies to: Field-installed refrigerant piping

Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 3. Written in our own words; check the manual for your exact model.

Reading the serial number

Mini-split · Vitocal 100-S

The serial is built from week of manufacture, year of manufacture, a model letter (V = all models) and a sequential serial number. The manual's example reads 49 22 V 10001.

Applies to: DLCURA outdoor units

Source: Viessmann DLCURA Service Manual, p. 2. Written in our own words; check the manual for your exact model.

Refrigerant service access points

Mini-split · Vitocal 100-S

The refrigerant circuit has a brass external liquid line service valve with a gauge port, a suction line service valve with a gauge port, and Schrader-type gauge ports with brass caps on the compressor suction and discharge lines. The liquid line also has pressure taps.

  1. Use the liquid line service valve and suction service valve gauge ports to read system pressures.
  2. Use the compressor suction and discharge Schrader ports for compressor-side readings.
  3. Replace the brass caps on the Schrader ports after service.

Applies to: DLCURA outdoor units

Source: Vitocal 100-S DLCURA technical data manual, p. 96. Written in our own words; check the manual for your exact model.

Relocate IR receiver for wireless remote

Mini-split · DLFSDAH, DLFLDAH

The factory IR receiver sits inside the control box. If the wireless remote is used, move the receiver into line of sight of the remote position using the 6 ft cable. A wired controller IR can be used together with the wireless remote.

  1. Route the IR receiver to a spot in line of sight of the remote position using the 6 ft cable.

Applies to: Wireless remote control with IR receiver

Source: Viessmann Vitocal IND-D Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.

Remote control range and timer limits

Mini-split · Vitocal IND-F

The remote works up to 26 ft (8 m) with no obstructions. Timer use requires the remote to stay within 26 ft of the unit.

  1. Keep the remote within 26 ft (8 m) with a clear line of sight.
  2. Keep the remote near the unit when using the timer.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-F DLFSFBH owner's manual, p. 7. Written in our own words; check the manual for your exact model.

Replace remote control batteries

Mini-split · DLFSDAH, DLFLDAH

Use two new AAA 1.5 V alkaline batteries. Remote settings are erased when the batteries are removed, so reprogram the remote after new batteries go in. Replace batteries when the unit gives no beep or the transmission indicator does not light.

  1. Slide the back cover off the remote.
  2. Insert two AAA alkaline batteries, matching the polarity marks.
  3. Replace the battery cover.
  4. Reprogram the remote settings.
  5. Remove batteries if the remote will sit unused for several weeks.

Applies to: Wireless remote control

Source: Viessmann Vitocal IND-D Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.

Run the unit in AUTO mode

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

In AUTO the unit picks COOL, FAN or HEAT on its own based on the set point. Fan speed cannot be set in AUTO. Manual says AUTO is for single-zone use only.

  1. Press MODE until AUTO is selected.
  2. Set the temperature with TEMP up or down.
  3. Press ON/OFF to start the unit.

Applies to: Single-zone installs

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 8-9. Written in our own words; check the manual for your exact model.

Run the unit in COOL mode from the remote

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Basic cooling operation from the wireless remote. Make sure the unit is plugged in and has power first.

  1. Press MODE until COOL is selected.
  2. Set the room temperature with the TEMP up or down buttons.
  3. Press FAN to pick a fan speed (AUTO, LOW, MED, HIGH, TURBO).
  4. Press ON/OFF to start the unit.

Applies to: All sizes, wireless remote

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.

Run the unit in DRY (dehumidify) mode

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Dries and slightly cools the air. It is not a substitute for a dehumidifier.

  1. Press MODE until DRY is selected.
  2. Set the temperature with TEMP up or down.
  3. Press ON/OFF to start the unit.

Applies to: All sizes

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.

Run the unit in FAN-only mode

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Filters and circulates room air without changing room temperature.

  1. Press MODE until FAN is selected.
  2. Press FAN to pick the speed.
  3. Press ON/OFF to start the unit.

Applies to: All sizes

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 9. Written in our own words; check the manual for your exact model.

Run the unit in HEAT mode from the remote

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Heating operation from the wireless remote. Heating output drops as outdoor temperature falls, so the manual recommends pairing it with other heating appliances in cold weather.

  1. Press MODE until HEAT is selected.
  2. Set the room temperature with TEMP up or down.
  3. Press FAN to pick a fan speed.
  4. Press ON/OFF to start the unit.

Applies to: Heat pump models

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.

Serviceability and diagnostics

Mini-split · DLFSDAH, DLFLDAH

Remove the top panel on the outdoor unit to reach the control compartment. Clean the outdoor coil from the inside with a pressure hose and detergent. Indoor units have easy access service panels and self-diagnostics.

  1. Remove the top panel on the outdoor unit to access the control box.
  2. Clean the outdoor coil from the inside with a pressure hose and detergent.

Applies to: Outdoor and indoor units

Source: Viessmann vitocal_ind_dlfsda_hk_tdm Technical Data Manual, p. 2. Written in our own words; check the manual for your exact model.

Shipping, storage and handling

Mini-split · Vitocal 100-S

Units ship in one piece. Store and handle them according to the manufacturer's recommendations.

  1. Keep the unit upright and store it per the manufacturer's handling instructions.

Applies to: DLCURA outdoor units

Source: Vitocal 100-S DLCURA technical data manual, p. 96. Written in our own words; check the manual for your exact model.

SILENCE operation

Mini-split · Vitocal IND-F

Press SILENCE on the remote. Compressor frequency stays below F2 and the indoor unit gives a faint breeze to lower noise.

Applies to: Remote control SILENCE button

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 11. Written in our own words; check the manual for your exact model.

SLEEP function

Mini-split · Vitocal IND-F

Works in COOLING, HEATING or AUTO. In cooling the setpoint rises 2°F (1°C) per hour up to 86°F (30°C), stopping after two hours with fan on low. In heating the setpoint drops 2°F (1°C) per hour down to 62°F (17°C), stopping after two hours with fan on low (anti-cold wind has priority). Sleep runs 7 hours then the unit powers off.

Applies to: SLEEP mode

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 10. Written in our own words; check the manual for your exact model.

Small filter installation on the air filter

Mini-split · DLFSHC

A small filter is supplied and must be fitted to the back of the main air filter by an authorized technician during installation. Quantity is 1 or 2 depending on model.

  1. Fit the small filter to the back of the main air filter.
  2. Confirm the quantity supplied for the model (1 or 2).

Applies to: DLFSHC indoor units

Source: DLFSHC installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Standard features of DLCURAH outdoor units

Mini-split · Vitocal 100-S

Standard on all sizes: inverter compressor, microprocessor controls, auto changeover and auto restart, 46°F heating setback (only with wireless remote used alongside wired controller KSACN1001), 3-minute compressor delay, high discharge temperature, low voltage, overload, over-current and IPM module protection, condenser high temperature protection in cooling, anti-corrosive coating, diagnostics, liquid line pressure taps, crankcase heater and base pan heater. Low voltage controls are standard.

Applies to: All DLCURAH outdoor units

Source: DLCURAH Technical Data Manual, p. 3. Written in our own words; check the manual for your exact model.

Stop using the unit immediately if warning signs appear

Mini-split · Vitocal IND-O

Turn the unit off right away if the power cord is damaged or abnormally warm, if there is a burning smell, loud or abnormal sounds, a fuse blows or the breaker keeps tripping, or water or objects get into or out of the unit. Do not try to fix these yourself.

  1. Turn the unit off immediately.
  2. Contact an authorized service provider.

Applies to: Vitocal IND-O DLFSOAH, models 09XAK and 18XAK

Source: Vitocal IND-O DLFSOAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.

System operation recommendations

Mini-split · Vitocal IND-D, DLFSDAH, DLFLDAH

Owner guidance for reliable operation.

  1. Replace both remote batteries at the same time.
  2. Point the remote at the unit display when sending commands.
  3. Keep doors and windows closed while running.
  4. Do not clean or service the unit while it is on.
  5. Keep the unit display away from direct sunlight and heat, which can disrupt the remote.
  6. Do not block air intakes or outlets on indoor or outdoor units.

Applies to: All models

Source: Vitocal IND-D DLFSDAH/DLFLDAH owner's manual, p. 12. Written in our own words; check the manual for your exact model.

Troubleshooting tools and approach

Mini-split · Vitocal IND-F

Tools: digital multimeter, Phillips and straight screwdrivers, needle-nose pliers, refrigeration gauges. Check indoor codes first, then consult the troubleshooting flowcharts (Table 6) and diagnosis pages. Problems without a code are covered by the flowcharts.

  1. Pick the problem from Table 6 and go to the matching diagnosis chart.
  2. Check the indoor unit display code first.
  3. Check the outdoor board first when measuring board signals.

Applies to: Troubleshooting

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 13. Written in our own words; check the manual for your exact model.

Unit protection and controls

Mini-split · Vitocal 100-S

The unit has a time delay control sequence on the fan coil board and automatic outdoor fan motor protection. Safeties include system diagnostics, compressor motor current and temperature overload protection, and outdoor fan failure protection.

  1. If the compressor will not start, check for the time delay sequence before condemning parts.
  2. If the outdoor fan stops, check the fan motor's internal thermal protection and the fan failure safety.
  3. Use the system diagnostics on the control to find which safety has tripped.

Applies to: DLCURA outdoor units

Source: Vitocal 100-S DLCURA technical data manual, p. 96. Written in our own words; check the manual for your exact model.

Wireless remote control

Mini-split · Vitocal IND-C

The wireless infrared remote is battery operated and supplied with all in-ceiling cassette units. One remote can control more than one indoor unit.

Applies to: DLFSCBH and DLFLCBH

Source: Vitocal IND-C technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Wireless remote use

Mini-split · Vitocal IND-C

One battery-powered infrared remote can control more than one indoor unit.

  1. Use the wireless remote supplied with each cassette system.
  2. One remote can be assigned to multiple units.

Applies to: All cassette ductless systems

Source: Viessmann Vitocal IND-C ductless technical data manual, p. 8. Written in our own words; check the manual for your exact model.

Wiring and installation rules before power-up

Mini-split · VITOCAL IND-F

Check these points before energising the system.

  1. Use the electrical data table to size the disconnect fuse or breaker (MOCP) and the wire (MCA).
  2. Keep at least 10 ft (3 m) of refrigerant line between the indoor and outdoor units.
  3. Insulate the liquid and suction lines separately.

Applies to: All sizes

Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 4. Written in our own words; check the manual for your exact model.

Antifreeze in the heating system

Water heater · Vitocell 100-V

Any glycol or antifreeze used in the heating system must be non-toxic or food grade. Give the owner a copy of the Safety Data Sheet. Viessmann Tyfocor-HTL is recommended for the solar circuit.

  1. Select a non-toxic or food grade antifreeze for the system fill.
  2. Give the owner or operator a copy of the Safety Data Sheet.
  3. Use Tyfocor-HTL for the solar heating circuit if solar fill is needed.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC installation manual, p. 4. Written in our own words; check the manual for your exact model.

Avoid overtightening the tank adaptors

Water heater · Vitocell 100-V CVWC

Overtightening can crack the glass lining on the potable side or damage the gasket on the heating side. Either one voids the warranty.

  1. Tighten BSPT adaptors until snug, and do not overtighten them.
  2. Tighten G adaptors until snug, and do not overtighten them, to protect the gasket.

Applies to: All Vitocell 100-V CVWC sizes

Source: Vitocell 100-V CVWC installation manual, p. 15. Written in our own words; check the manual for your exact model.

Do not wrap insulating tape around the temperature sensor

Water heater · Vitocell 100-V

Insulating tape on the tank temperature sensor affects its reading. Manual says never to do it.

Applies to: Vitocell 100-V CVWC DHW tank temperature sensor

Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 19. Written in our own words; check the manual for your exact model.

Freeze protection for the tank

Water heater · Vitocell 100-V

The tank must sit in a frost-protected, draft-free room. If that cannot be guaranteed, drain the tank whenever it is not in use.

  1. Confirm the mechanical room never sees freezing temperatures.
  2. Drain the tank if it is out of use and freezing is possible.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC installation manual, p. 4, p. 7. Written in our own words; check the manual for your exact model.

Heat coil temperature limit during welding or brazing

Water heater · Vitocell 100-V

The heating coil uses a rubber seal and glue inside the tank, so it cannot take high heat. Do not let the NPT fitting area exceed 302°F (150°C) during welding or brazing.

  1. Keep the NPT fitting area at or below 302°F (150°C) during any welding or brazing.
  2. Use caution around the coil seal and glue when doing hot work near the tank.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC installation manual, p. 4. Written in our own words; check the manual for your exact model.

Heat exchanger self-venting and self-draining

Water heater · Vitocell 100-V CVWC

The tubular coil is self-venting at the top and self-draining at the bottom, so air lock or deposits should not cut heat transfer. The coil reaches the bottom of the tank so the whole water volume is heated.

Applies to: Vitocell 100-V CVWC, all sizes

Source: Vitocell 100-V CVWC technical data manual, p. 2. Written in our own words; check the manual for your exact model.

Heat transfer medium requirements

Water heater · Vitocell 100-V

The heat coil medium must be potable water or substances FDA-recognized as safe. It must also be non-toxic with a toxicity class of 1. Keep its pressure below the minimum operating pressure of the potable water system, and limit it to a maximum of 30 psig with an approved safety or relief valve.

  1. Use potable water or an FDA-safe, non-toxic fluid in the heating circuit.
  2. Keep the heat transfer medium pressure below the domestic water minimum operating pressure.
  3. Limit the heat transfer medium to 30 psig maximum with an approved safety or relief valve.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC installation manual, p. 2. Written in our own words; check the manual for your exact model.

Intended use limits

Water heater · Vitocell 100-V

The tank is for sealed unvented systems and stores only potable water. It is not for steam heating. Do not use it for commercial or industrial purposes beyond building heat or DHW without manufacturer approval. Do not modify components, for example direct DHW heating in the collector.

  1. Confirm the system is sealed and unvented.
  2. Do not install the tank in a steam heating system.
  3. Do not modify the tank or its connections for uses outside the intended design.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC installation manual, p. 7. Written in our own words; check the manual for your exact model.

Not for steam heating

Water heater · Vitocell 100-V CVWC

This tank version must not be used on steam heating systems.

Applies to: Vitocell 100-V CVWC, all sizes

Source: Vitocell 100-V CVWC technical data manual, p. 1. Written in our own words; check the manual for your exact model.

Recirculation tapping

Water heater · Vitocell 100-V

The recirculation connection is on its own tapping. Cap it if the tank is installed without a recirculation line.

  1. Cap the recirculation tapping if no recirculation line is installed.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC Technical Data Manual, p. 18. Written in our own words; check the manual for your exact model.

Scald risk from hot domestic water

Water heater · Vitocell 100-V CVWC

DHW above 125°F (52°C) can cause severe burns almost instantly or death from scalds, and children, disabled and elderly people are most at risk. Temperature limiting valves must be used wherever the storage tank temperature can exceed 140°F (60°C). Advise the owner to feel the water before bathing or showering.

  1. Install temperature limiting valves or a tempering valve where the tank can exceed 140°F (60°C).
  2. Tell the owner to test water temperature before bathing or showering.

Applies to: Vitocell 100-V CVWC

Source: Viessmann Vitocell 100-V CVWC installation, service and operating instructions, p. 26. Written in our own words; check the manual for your exact model.

Seal unused connections

Water heater · Vitocell 100-V CVWC

The protective covers are not watertight, so unused connections must be sealed during installation.

  1. Seal every unused connection on the tank before filling or pressurizing the system.

Applies to: All Vitocell 100-V CVWC sizes

Source: Vitocell 100-V CVWC installation manual, p. 14. Written in our own words; check the manual for your exact model.

Standard equipment on each CVWC tank

Water heater · Vitocell 100-V

Every CVWC tank ships with the same standard kit: a welded sensor well for the tank temperature sensor or controller, a temperature and pressure relief valve, installation fittings, a technical literature set, adjustable feet and factory insulation. The casing is epoxy-coated sheet steel in Vitopearl white.

Applies to: Vitocell 100-V CVWC 200 L, 250 L and 300 L

Source: Vitocell 100-V CVWC Technical Data Manual, p. 16. Written in our own words; check the manual for your exact model.

Standard equipment, Vitocell 100-V CVWC 53, 66 and 79 USG

Water heater · Vitocell 100-V CVWC

Each size ships with a steel DHW tank with enamel coating, an integral welded sensor well for the tank temperature sensor or controller, a temperature and pressure relief valve, installation fittings, a technical literature set, adjustable feet and fitted insulation. Casing is epoxy-coated sheet steel in Vitopearlwhite.

Applies to: Vitocell 100-V CVWC 53, 66 and 79 USG

Source: Vitocell 100-V CVWC technical data manual, p. 16. Written in our own words; check the manual for your exact model.

Start one-off DHW heating

Water heater · Vitodens 100-W B1HE/B1KE

Heats the DHW tank once to the set DHW temperature, outside the time program. This has higher priority than the time program. It ends when the target temperature is reached.

  1. Call up the home screen.
  2. Select DHW, then confirm with OK.
  3. Select One-off heating, then confirm with OK.
  4. Select to activate, then confirm with OK.
  5. Acknowledge the information with OK.

Applies to: One-off DHW heating

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 17. Written in our own words; check the manual for your exact model.

Switch on the DHW hygiene program

Water heater · Vitodens 100-W B1HE/B1KE

Heats the DHW tank above 140°F (60°C) once a week, or for an hour every day, at the set time. Scald risk: mix with cold water at draw-off points. Not valid for systems with a DHW tank thermostat (Aquastat-type).

  1. Call up the home screen.
  2. Select DHW, then confirm with OK.
  3. Select Time program, then confirm with OK.
  4. Select DHW, then confirm with OK.
  5. Select DHW, then confirm with OK.
  6. Select Hygiene program, then confirm with OK.
  7. Select the required day or everyday, then confirm with OK.
  8. Select the required hour, then confirm with OK.
  9. Select the required minutes, then confirm twice with OK.
  10. Press and hold the exit button for about 4 sec to leave the menu.

Applies to: DHW hygiene program

Source: Vitodens 100-W B1HE/B1KE operating instructions, p. 18. Written in our own words; check the manual for your exact model.

Tank layout: anode, clean-out port and DCW diffuser

Water heater · Vitocell 100-V CVWC

The tank has an impressed current anode, an enamel-lined steel shell with foam-in-place insulation, and an inspection and clean-out port. The cold water diffuser is positioned with the coil so 82 to 97 percent of tank volume can be drawn at constant temperature.

Applies to: Vitocell 100-V CVWC, all sizes

Source: Vitocell 100-V CVWC technical data manual, p. 2-3. Written in our own words; check the manual for your exact model.

Water quality and chloride/sulfate limits

Water heater · Vitocell 100-V

The tank must heat drinking (potable) water only. Chloride and sulfate levels are limited. In areas with high levels, consult Viessmann before installing. Water treatment equipment must work correctly. Heating other media voids the warranty.

  1. Confirm the water is drinking quality.
  2. Check chloride and sulfate levels against the limits.
  3. Consult Viessmann if levels are high.

Applies to: Vitocell 100-V CVWC

Source: Vitocell 100-V CVWC Technical Data Manual, p. 18. Written in our own words; check the manual for your exact model.

Same tips in your pocket

The HVACopedia app has these tips, every error code and the settings tables offline.

Open the app

For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.