Viessmann · technician tips

Viessmann service menus, test modes and resets

5 tips for boiler: access codes, button combinations, test modes and the resets you need at the appliance.

Jump to: Access & passwords (1) · Service & test modes (1) · Reset & cancel (1) · Settings shortcuts (1) · Commissioning (1)

Access & passwords

Installer and service menu codes, and how to get into them.

Open the Service menu (password viservice)

Boiler · Vitodens 200-W B2HE

The touchscreen Service menu holds diagnosis, actuator test, parameters, message history and service functions. It closes on its own after 30 minutes.

  1. Menu > Service
  2. Enter the password viservice (factory default)
  3. If passwords were changed and lost, Viessmann Technical Service issues a master password

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Service menu. Written in our own words; check the manual for your exact model.

Service & test modes

Forced fan, low and high fire, test and diagnostic modes, error history and live data.

Actuator test: drive fan, burner, pump and 3-way valve by hand

Boiler · Vitodens 200-W B2HE

Each actuator test function runs for 30 s: fan rpm, burner Off / Min / Max heating / Max DHW, 3-way valve Heating / Centre / DHW, pump speeds, mixers, zone pumps.

  1. Service menu > Actuator test
  2. Pick the group (Boiler, Heating, DHW, Solar) and the function
  3. Function stays active 30 s, then drops out

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Actuator test. Written in our own words; check the manual for your exact model.

Reset & cancel

Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.

Clear the service message (P.1 / P.8)

Boiler · Vitodens 200-W B2HE

A service message you acknowledge without resetting comes back the next Monday. Reset it through parameter 1411.0.

  1. Service menu > System configuration > Boiler
  2. Set parameter 1411.0 Clear maintenance messages to ON
  3. Set the next interval in 521.0 (burner hours) or 522.3 (months)

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Parameters: Boiler; P.1/P.8. Written in our own words; check the manual for your exact model.

Settings shortcuts

Where the useful parameters live and what they are set to from the factory.

Where the fault history lives

Boiler · Vitodens 200-W B2HE

The message history keeps the 10 most recent faults with their subscriber numbers (CAN 1 HMU, CAN 50 BCU, CAN 59 HMI, CAN 60 fan, 81 MZIO).

  1. Service menu > Message history

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Message history. Written in our own words; check the manual for your exact model.

Commissioning

Start-up and set-up steps that are easy to miss.

Filling and purging programs (20 min auto-stop)

Boiler · Vitodens 200-W B2HE

Purging cycles the pump 30 s on/off and toggles the diverter valve for 20 min with the burner off. Filling parks the diverter valve in the middle and runs the pump; both stop by themselves after 20 min.

  1. Service menu > Service functions > Filling or Purging
  2. Program ends automatically after 20 min; exit Service to stop earlier

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions (6167 813-24), Function description p.82. Written in our own words; check the manual for your exact model.

Same tips in your pocket

The HVACopedia app has these tips, every error code and the settings tables offline.

Open the app

For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.