Weil-McLain · Boiler troubleshooting
Tight construction and exhaust fan air rules
What is going on
Tight buildings and mechanical exhaust can starve the boiler of air. The room must never run under negative pressure unless every appliance is direct vent.
Likely causes
- Continuous vapor retarder, weatherstripping, and sealed penetrations making the building tight
- Exhaust fans or air movers pulling room air faster than the openings supply
Check in this order
- If the building is tight, provide outside air openings sized from Figure 25 for inside-air use.
- Size openings for the exhaust fan airflow as well as the boiler firing rate.
- Do not let the boiler room go negative unless all appliances are direct vent.
Applies to: Direct exhaust installations
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.