Weil-McLain · Boiler troubleshooting

0-10 VDC remote modulation input

ECO Tec Series 3

What is going on

A 0-10 VDC signal can be used for remote modulation. It uses the INPUT 2 heat demand, so the same input cannot be used for a dry contact. The remote target and remote modulation inputs cannot both be used on the same control.

Check in this order

  1. Wire the 0-10 VDC input positive to J16 terminal 6 and common to J16 terminal 5.
  2. Do not wire any device to INPUT 2 when remote modulation is used.
  3. If Indirect DHW is needed, connect the DHW aquastat to INPUT 3 or INPUT 4 and assign it to PRIORITY 2.
  4. Assign INPUT 2 to PRIORITY 3 for the space heating system to be modulated. Accept the defaults for INPUT 2 during the WIZARD.
  5. After the WIZARD, go to SYSTEM SETTINGS, INPUT USAGE, and change the INPUT 2 SOURCE to 0-10V (default is TT1).
  6. Check that the boiler turns on at 0.9 VDC and off at 0.5 VDC. These thresholds are fixed and cannot be adjusted.
  7. Confirm OUTPUT 2 (120VAC) switches on and off with the heat demand.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 73. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.