0-10 VDC remote modulation input
What is going on
A 0-10 VDC signal can be used for remote modulation. It uses the INPUT 2 heat demand, so the same input cannot be used for a dry contact. The remote target and remote modulation inputs cannot both be used on the same control.
Check in this order
- Wire the 0-10 VDC input positive to J16 terminal 6 and common to J16 terminal 5.
- Do not wire any device to INPUT 2 when remote modulation is used.
- If Indirect DHW is needed, connect the DHW aquastat to INPUT 3 or INPUT 4 and assign it to PRIORITY 2.
- Assign INPUT 2 to PRIORITY 3 for the space heating system to be modulated. Accept the defaults for INPUT 2 during the WIZARD.
- After the WIZARD, go to SYSTEM SETTINGS, INPUT USAGE, and change the INPUT 2 SOURCE to 0-10V (default is TT1).
- Check that the boiler turns on at 0.9 VDC and off at 0.5 VDC. These thresholds are fixed and cannot be adjusted.
- Confirm OUTPUT 2 (120VAC) switches on and off with the heat demand.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
- Access and clean heat exchanger, Ultra-80 and Ultra-105
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 73. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.