Weil-McLain · technician tips
Weil-McLain service menus, test modes and resets
368 tips for boiler, water heater: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Access & passwords (10) · Service & test modes (24) · Reset & cancel (23) · Settings shortcuts (13) · Commissioning (86) · Other (212)
Access & passwords
Installer and service menu codes, and how to get into them.
Access Modbus settings for BMS
Boiler · Evergreen Series 2
Modbus settings are in the contractor menu. Adjust them to match the BMS.
- From the home screen, press and hold the WM logo to open the contractor menu.
- Open the Modbus Setting screen.
- Set all Modbus values to match the BMS being used.
- If the BMS uses BACnet, install a BACnet converter between the BMS and the JP4 Modbus terminals.
Applies to: Evergreen Pro control with BMS
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 55. Written in our own words; check the manual for your exact model.
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
3-way valve test (combi models only)
Boiler · ECO Tec Series 3
Tests whether the DHW/heating 3-way valve actuator moves and the valve shaft works.
- Go to DIAGNOSTICS, Manual Test Mode.
- Make sure the boiler is in Standby with no heat calls active.
- Press edit and select the desired 3-way valve position.
- Remove the actuator (procedure in Figure 138, p. 158) and watch the motor shaft as you change position.
- The shaft should slide in and out with no play in the extended position.
- Push the shaft in the sanitary shutter with a blunt object; it should compress against the valve spring.
- If the shaft will not move or sticks compressed, follow the flow manifold cleaning procedure on p. 158.
Applies to: Combi models 110, 150, 199
Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words; check the manual for your exact model.
Combustion adjustment screw directions
Boiler · ECO Tec Series 3
Use the throttle screw for high fire and the offset screw for low fire. Adjust in the direction that changes CO2 as needed.
- Throttle screw: turn counterclockwise to increase CO2, clockwise to decrease CO2.
- Offset screw (80 and 110 only, under sealed cap): turn clockwise to increase CO2, counterclockwise to decrease CO2.
- Adjust high fire first with the throttle screw, then force low fire and adjust the offset screw.
- Reinstall the cap over the offset screw after adjusting.
Applies to: ECO Tec 80/110/150/199 gas valve
Source: ECO Tec Series 3 Boiler Manual, p. 22-23. Written in our own words; check the manual for your exact model.
Connect to the boiler over Bluetooth
Boiler · ECO Tec Series 3
Bluetooth is needed to access configuration settings. Bluetooth stays on for 30 minutes of inactivity.
- Swipe right on the display to reach the Menu screen.
- Press the BLUETOOTH button.
- Toggle Bluetooth on with the blue toggle.
- Turn on Bluetooth on the smartphone.
- Open the WM ProTools app, press Connect, then Connect to Boiler, and select the WM boiler.
- If no boiler appears, toggle the boiler Bluetooth off and on again. Wait for the display to connect before leaving that screen.
Applies to: ECO Tec Series 3 boilers with WM ProTools app
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 187. Written in our own words; check the manual for your exact model.
Diagnostics readouts for troubleshooting
Boiler · Ultra Series 4
Live readings found under Diagnostics. Use them to see what the boiler sees.
- Temperatures: System Supply, System Return, Boiler Out1 and Out2, Boiler In1, Flue1 and Flue2, Outdoor.
- Inputs: Priority 1, 2 and 3 calls, Analog Input (0-10 VDC on P15 #5 and #6), Manual Limit (P13-1 and P13-2), Auto Limit (P13-3 and P13-4), Low Water Cutoff (P12-3 and P12-4), Blower Tach rpm, Flame Signal.
- Outputs: Gas Valve, Circulators 1-3, Blower Signal (% of rate), Additional Heat Demand, Alarm contact, Analog Output (P16 #1 and #2).
- Errors: Control Fault count, Ignition Retries, Manual Reset count, Auto Reset count.
- Software Versions: Display, Main Micro and Second Micro.
Applies to: Ultra Series 4 boilers, U-Control
Source: Ultra Series 4 gas-fired water boiler manual, p. 106-107. Written in our own words; check the manual for your exact model.
Do not measure gas valve outlet pressure
Boiler · Ultra Series 4
Manometer fluid can contaminate and damage the gas valve. Outlet pressure must not be checked during conversion.
- Do not connect a manometer to the gas valve outlet.
Applies to: All Ultra boilers during propane conversion
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 49. Written in our own words; check the manual for your exact model.
Force a firing rate for testing
Boiler · Evergreen Pro Series 2
Manual Test Mode lets you force a modulation rate during a call for heat. Return it to auto afterward.
- Open DIAGNOSTICS and go to Manual Test Mode.
- Set Force Rate to the rate needed for the test.
- When testing is finished, set Force Rate back to auto.
Applies to: Evergreen Pro Series 2 boilers
Source: Series 2 Advanced Manual 550-100-581, p. 85. Written in our own words; check the manual for your exact model.
Force a firing rate in Manual Test Mode
Boiler · Ultra Series 4
Forces a fixed firing rate during a call for heat. Leave it on Auto for normal operation.
- Open Manual Test Mode in the U-Control menu.
- Select Force Rate and choose Low, Med, High or Auto (default Auto).
- Watch Status, Target, Flame Signal, Blower Signal and Blower Tach while forced.
- Return Force Rate to Auto when testing is done.
Applies to: Ultra Series 4 boilers, U-Control
Source: Ultra Series 4 gas-fired water boiler manual, p. 107. Written in our own words; check the manual for your exact model.
Force firing rate in manual test mode
Boiler · Ultra Series 4
Manual test mode lets the technician hold the burner at high fire, low fire or normal auto control for combustion checks.
- Enter the installer menus and go to Manual test mode (menu location shown in Figure 115, page 102).
- Force firing rate to MAX (high fire) and check the flame and combustion.
- Force firing rate to MIN (low fire) and check again.
- Set firing rate back to AUTO (normal operation) when finished.
Applies to: U-Control on Ultra Series 4
Source: Weil-McLain Ultra Series 4 boiler manual, p. 40. Written in our own words; check the manual for your exact model.
Ignition difficulty after coarse adjustment
Boiler · ECO Tec Series 3
If the boiler will not light after coarse gas valve settings, add throttle opening in small steps. Do not exceed one full turn in total.
- Turn the throttle screw counterclockwise an additional 1/4 turn and try to light again.
- Repeat up to a total of one full turn.
- If the boiler still will not ignite, or the analyzer reads below 10% O2 during combustion analysis, contact WM Technologies Technical Services.
Applies to: ECO Tec gas valve
Source: ECO Tec Series 3 Boiler Manual, p. 23. Written in our own words; check the manual for your exact model.
Integrated low water cutoff test button
Boiler · CGa Series 4, CGi Series 5, EG Series 7, PEG Series 7
Test the integrated low water cutoff using the control's LWCO TEST button while the burner is firing.
- With the burner firing, press the LWCO TEST button on the control.
- Confirm the burner shuts off.
Applies to: Integrated type low water cutoff
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 21. Written in our own words; check the manual for your exact model.
LWCO TEST button check
Boiler · EG, PEG
Use the LWCO TEST button on the control to confirm the low water cutoff shuts the burners down and restarts them.
- With the burners operating, press and hold the LWCO TEST button on the control.
- Confirm the burners go off, the circulator keeps running and LWCO is displayed.
- Release the LWCO TEST button and confirm the ignition sequence resumes.
Applies to: EG and PEG Series 7 boilers with Unity-CI control
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 65. Written in our own words; check the manual for your exact model.
Manual test mode (force firing rate)
Boiler · ECO Tec Series 3
Forces the boiler to a set firing rate for testing.
- Go to DIAGNOSTICS and open Manual Test Mode.
- Call for heat and wait until the burner is lit.
- Press EDIT and select the FORCE RATE.
- The rate is held for 30 minutes.
- Test mode resets at the end of the heat demand.
- If the timer runs out, the boiler returns to AUTO and keeps running if demand still exists.
Applies to: ECO Tec Series 3 gas boilers
Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words; check the manual for your exact model.
Manual test mode for firing rate
Boiler · Ultra Series 4
Forces the boiler to low, medium (ignition) or high fire for checks. Low fire is adjusted in the boiler setup menu.
- Navigate to Manual test mode on the U-Control (see Figure 115, page 102).
- Set the firing rate to MINIMUM, MEDIUM or MAXIMUM as needed for the check.
- Return to normal operation after testing.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Source: Ultra Series 4 gas-fired water boiler manual, p. 113. Written in our own words; check the manual for your exact model.
Manual Test Mode for forcing firing rates
Boiler · SVF Series 1
Manual Test Mode locks the boiler at low or high fire so combustion and rpm can be checked. Use it for combustion checks and gas valve adjustment.
- Navigate to DIAGNOSTICS and select Manual Test Mode.
- Lock the boiler at low or high fire.
- Check the rpm shown against the blower speed table.
- Return the firing rate to Auto when finished.
Applies to: SVF 1500-3000
Source: SVF Series 1 boiler manual, p. 88-89. Written in our own words; check the manual for your exact model.
Manual Test Mode for pump voltage and firing rate
Boiler · Evergreen Series 2
Manual Test Mode shows live readings and lets you force the firing rate. It is also used to save the variable pump max and min voltages.
- Open PUMP SETTINGS from the contractor menus and select Manual Test.
- Read status, inputs, modulation source, temperatures, blower signal and speed, flame signal, and pump volts on the screen.
- To set the max pump voltage, force rate to HIGH and save as MAX VOLTS.
- To set the min pump voltage, force rate to LOW and save as the min voltage.
Applies to: Evergreen Series 2 with variable speed pump output
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 73. Written in our own words; check the manual for your exact model.
Manual test of the relief valve
Boiler · Ultra Series 4
Checks that the relief valve opens and reseats properly. The discharge line must be piped to a safe place before testing.
- Confirm the relief valve outlet is piped to a safe discharge location where scalding is not possible.
- Read the pressure/temperature gauge and confirm the system is pressurized.
- Lift the relief valve top lever slightly so water flows through the valve and discharge piping.
- If water flows freely, release the lever and let the valve seat.
- Watch the discharge pipe after it has drained. If the valve weeps, lift the lever again to try to clean the seat.
- If the valve still weeps, have a qualified service technician inspect the valve and system.
- If no water flows when the lever is fully lifted, the valve or discharge line may be blocked. Shut the boiler down per page 9 and call a qualified service technician.
Applies to: Ultra Series 4 gas-fired water boiler relief valve
Source: Weil-McLain Ultra Series 4 user's information manual, p. 8. Written in our own words; check the manual for your exact model.
Read live operating data on the boiler information screen
Boiler · ECO Tec Series 3
The homeowner boiler information screen shows the current sequence status and sensor values useful for field checks.
- From the home screen, open the menu and select the boiler information screen.
- Check STATUS for the current sequence and active priority.
- Check INPUT STATUS for each call for heat and the 0-10V value if used.
- Check PUMPS/AUX for active outputs and BOILER OUT/IN for water temperatures.
- Check TARGET TEMP and MODULATION RATE (blower speed).
- Check DHW FLOW and DHW TEMP on combi models only.
Applies to: ECO Tec control
Source: ECO Tec Series 3 boiler manual, p. 112. Written in our own words; check the manual for your exact model.
Read pilot flame sense value
Boiler · EG / PEG Series 7
The Advanced Menu shows the pilot flame signal the control measures. A value of 60 or higher means no flame. A good flame reads below 60, and a stronger flame gives a lower number.
- Open the Advanced Menu.
- Go to Diagnostics, then Inputs & Outputs.
- Select Flame Sense to read the pilot flame value.
- Compare the reading with the threshold: 60 is no flame, and lower values mean better flame quality.
Applies to: EG water boilers, pilot ignition
Source: EG / PEG Series 7 Boiler Manual, p. 48. Written in our own words; check the manual for your exact model.
Read the last six lockouts (fault history)
Boiler · ECO Tec Series 3
Shows counts and details of recent lockouts, useful before clearing or resetting anything.
- Open DIAGNOSTICS in the Contractor Menus.
- Select FAULT HISTORY and press the right arrow key.
- Record Ignition Retries, Manual Reset Count and Auto Reset Count.
- Select LOCKOUT HISTORY # and press the right arrow key for details, up to six.
Applies to: ECO Tec Series 3 control display
Source: ECO Tec Series 3 boiler manual, p. 162. Written in our own words; check the manual for your exact model.
Read the last three lockout histories
Boiler · Ultra Series 4
Lockout history is stored in the U-Control. Record the first four data records before clearing anything.
- Scroll to DIAGNOSTICS and press enter.
- Scroll to ERRORS and press enter.
- Scroll to LOCKOUT HISTORY # and press enter.
- Choose MANUAL RESET or AUTO RESET and press enter to see the fault recorded.
- Press the left arrow to return to the lockout history list, then select another history to see boiler conditions at that lockout.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Source: Ultra Series 4 gas-fired water boiler manual, p. 118. Written in our own words; check the manual for your exact model.
Start blower calibration from the wizard
Boiler · Evergreen Series 2
Blower calibration optimises the blower to the boiler and shows progress on screen.
- Open the blower calibration screen in the wizard.
- Select Start Calibration.
- Watch the percentage completion and green progress bar on the top banner until the process finishes.
Applies to: Series 2 boilers with Evergreen Pro control
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 18. Written in our own words; check the manual for your exact model.
Use a bubble test for gas leaks
Boiler · ECO Tec Series 3
Never check for gas leaks with an open flame.
- Check all gas connections with a bubble test solution.
- Confirm all connections are sealed before running the boiler.
Applies to: Gas piping and venturi connections
Source: ECO Tec Series 3 Boiler Manual, p. 22. Written in our own words; check the manual for your exact model.
Use manual test mode to force firing
Boiler · SVF Series 1
MANUAL TEST MODE shows live readings and lets the technician set a target and force a firing rate. Use it only during supervised testing.
- Open DIAGNOSTICS > MANUAL TEST MODE.
- Check STATUS, TARGET, MODULATION and the temperature and blower readings.
- Set FORCE RATE from AUTO to the required test rate, if needed.
- Return FORCE RATE to AUTO when testing is complete.
Applies to: Single boiler or network shadow boiler
Source: SVF Series 1 boiler manual, p. 80. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Blocked combustion air or vent lockout
Boiler · CGa, CGi, EG, PEG
The boiler shuts down automatically when combustion air or the vent is blocked and shows a manual reset lockout.
- Remove any easily accessible blockage in the combustion air or vent.
- On the control display, select <Reset Lockout>.
- If the blockage cannot be removed, have a qualified service technician check the system.
Applies to: All listed boiler series
Source: Gas-Fired Boilers User Manual, p. 4. Written in our own words; check the manual for your exact model.
Clear all history counters
Boiler · ECO Tec Series 3
Pressing reset in the fault history menu deletes all history, not just the counter you are viewing. To keep history, clear counters one at a time instead.
- Open the FAULT HISTORY menu.
- To clear everything, press the reset button. This deletes all history.
- To keep history, select each counter (for example Ignition Retries) and reset only that one.
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec Series 3 boiler manual, p. 128. Written in our own words; check the manual for your exact model.
Clear all lockout histories
Boiler · ECO Tec Series 3
Erases the recorded lockout history.
- On the FAULT HISTORY screen, hold the reset button until the history is cleared.
Applies to: ECO Tec Series 3 control display
Source: ECO Tec Series 3 boiler manual, p. 162. Written in our own words; check the manual for your exact model.
Clear an ignition lockout
Boiler · SVF Series 1
After an ignition lockout, the display turns red. Clear it from the Diagnostic Menu.
- Open the Diagnostic Menu.
- Select Manual Reset.
- Open the manual gas valve if it was closed.
Applies to: SVF 1500-3000
Source: SVF Series 1 boiler manual, p. 89. Written in our own words; check the manual for your exact model.
Manual reset after lockout
Boiler · Ultra Series 4
A high limit lockout or a manual reset limit lockout requires a manual reset. The reset is done from the control and can be done by a homeowner or service technician.
- Find the cause of the lockout first.
- Enter the MANUAL RESET menu.
- Press ENTER to reset the listed errors.
- Confirm the boiler restarts normally.
Applies to: Ultra U-Control manual reset lockout
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98, p. 103 and p. 104. Written in our own words; check the manual for your exact model.
Manual reset of an ignition lockout
Boiler · EG, PEG, Series 7
An ignition fault must be reset by hand from the fault screen. The fault clears only if the underlying condition has been corrected.
- Go to the fault indication screen.
- Press and release the enter button. A confirmation screen appears.
- Answer Yes and press and release enter to clear the fault, but only after the cause is fixed.
Applies to: EG / PEG Series 7 boilers with Unity-CI control
Source: EG / PEG Series 7 boiler manual, p. 35. Written in our own words; check the manual for your exact model.
Manual reset procedure for ignition lockout
Boiler · EG / PEG Series 7
Use this procedure to clear a manual reset lockout caused by an ignition fault.
- Make sure the ignition fault has been corrected first.
- On the fault indication screen, press and release the enter button to open the confirmation screen.
- The reset question shows NO on line 2. Press enter to change it.
- Press the up or down arrow to change the answer to YES, then press enter again.
- The display background turns green and returns to the main screen.
Applies to: EG and PEG Series 7 water boilers
Source: EG / PEG Series 7 Boiler Manual, p. 74. Written in our own words; check the manual for your exact model.
Reset a boiler lockout at the U-Control display
Boiler · Ultra Series 4
When the boiler locks out, the U-Control display turns red.
- Check the U-Control display. A red display means the boiler has locked out.
- Select MANUAL RESET on the U-Control display to reset the boiler (shown in Figure 4, page 10).
Applies to: Ultra Series 4 boiler with U-Control display
Source: Weil-McLain Ultra Series 4 user's information manual, p. 10. Written in our own words; check the manual for your exact model.
Reset all history counters
Boiler · Evergreen Pro Series 2
Clears all boiler history at once. Deletes every history record, so only use it when the full history is no longer needed.
- Open the DIAGNOSTICS menu and go to Fault History.
- Press the reset button.
- To keep some history, reset the individual counters instead.
Applies to: Evergreen Pro Series 2 boilers
Source: Series 2 Advanced Manual 550-100-581, p. 85. Written in our own words; check the manual for your exact model.
Reset all history counters to zero
Boiler · ECO Tec Series 3
Deletes all history. To keep history, reset counters one at a time.
- Enter the FAULT HISTORY menu.
- Press the reset button. All history is deleted.
Applies to: ECO Tec Series 3 80/110/150/199
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 128. Written in our own words; check the manual for your exact model.
Reset control to factory default
Boiler · SVF Series 1
Restores all control settings to the factory values. Previous settings cannot be recovered.
- Go to the BOILER SETTINGS menu (see page 75).
- Select Reset to Factory Default.
- Hold Enter for the specified time to confirm.
- Confirm this is really wanted before continuing, since previous settings are lost.
Applies to: SVF 1500-3000 Series 1 boiler
Source: Weil-McLain SVF Series 1 boiler manual, p. 102. Written in our own words; check the manual for your exact model.
Reset error counters
Boiler · Ultra Series 4
ERRORS screen counts: control faults, ignition retries (shows current sequence), manual reset count and auto reset count.
- Go to DIAGNOSTICS > ERRORS.
- Select the Control Fault count or the Manual Reset / Auto Reset count and press enter to reset it.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Source: Ultra Series 4 gas-fired water boiler manual, p. 118. Written in our own words; check the manual for your exact model.
Reset ignition retries at yearly maintenance
Boiler · Evergreen Pro Series 2
The ignition retry count is cumulative. The manual recommends resetting it during yearly service.
- Open DIAGNOSTICS > Fault History.
- Select Ignition Retries.
- Press the Reset button.
Applies to: Evergreen Pro Series 2 boilers
Source: Series 2 Advanced Manual 550-100-581, p. 85. Written in our own words; check the manual for your exact model.
Reset ignition retries counter at yearly service
Boiler · SVF Series 1
The manual recommends resetting the ignition retries counter during yearly maintenance so the new count starts from zero.
- Open DIAGNOSTICS and go to PAST ERRORS, then IGNITION RETRIES.
- Either hold the left and right arrows, or select the IGNITION RETRIES line and press Enter.
Applies to: SVF 1500, 2000, 2500, 3000
Source: SVF Series 1 boiler manual, p. 82. Written in our own words; check the manual for your exact model.
Reset ignition retry count
Boiler · ECO Tec Series 3
Ignition retries should be reset during yearly maintenance.
- On the FAULT HISTORY screen, select the Ignition Retries parameter and press enter to reset the count.
- Or press the reset button to reset the count.
Applies to: ECO Tec Series 3 control display
Source: ECO Tec Series 3 boiler manual, p. 162. Written in our own words; check the manual for your exact model.
Reset pressure switch fault
Boiler · CGi, LGB Series 3
Pressure switch cuts off gas flow when the vent system is blocked. Reset only after the blockage is cleared.
- Resolve the cause of the fault first
- Press Enter (square symbol)
- Use the arrow keys to select YES
- Confirm the error screen returns to the default display
- If the fault returns, contact a service technician
Applies to: CGi and LGB Series 3 boilers with pressure switch
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 12. Written in our own words; check the manual for your exact model.
Reset the maintenance reminder
Boiler · Evergreen Series 2
When maintenance is due, a wrench icon shows on the main screen. A qualified technician should inspect the boiler first. Maintenance intervals should be set by a qualified technician at installation.
- Open the User Menu and select Maintenance to view contractor and maintenance information.
- After the technician inspection, reset the maintenance reminder to clear it.
Applies to: Evergreen Pro control display
Source: Weil-McLain Condensing Gas Boiler User's Information Manual, p. 12. Written in our own words; check the manual for your exact model.
Reset to factory default
Boiler · ECO Tec Series 3
Returns control settings to factory values. Previous settings cannot be recovered.
- Hold the button for the specified time, or use Contractor Menu, Boiler Settings, Reset Factory Default.
- On 199 and 199C models, select the correct blower motor after checking the blower label (see page 115).
- Confirm this action is really needed before continuing.
Applies to: ECO Tec Series 3 control
Source: ECO Tec Series 3 boiler manual, p. 162. Written in our own words; check the manual for your exact model.
Restart the Wizard after it was bypassed
Boiler · Evergreen Series 2
If the Wizard was skipped by mistake, the boiler setup must be started over from the beginning.
- Go to the Boiler Settings menu.
- Select RESET FACTORY DEFAULTS.
- Select RESTART Wizard and follow the screens.
Applies to: Evergreen Series 2 control
Source: Series 2 Advanced Manual, p. 14. Written in our own words; check the manual for your exact model.
Restart the wizard or reset to factory defaults
Boiler · Evergreen Series 2
The Restart Wizard option keeps contractor data. Reset Factory Defaults clears everything, including the model number.
- Open BOILER SETTINGS from the contractor menus and select RESET FACTORY DEFAULTS.
- Choose RESTART WIZARD to keep contractor information, time and date, run times, errors and boiler model, then run the wizard again.
- Choose RESET FACTORY DEFAULTS only if you need to clear all information and return the control to its as-shipped state. The model must be set again.
Applies to: Evergreen Series 2 with Evergreen Pro control
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 72. Written in our own words; check the manual for your exact model.
Restart Wizard
Boiler · ECO Tec Series 3
Erases user-specific settings and takes the user back through the wizard. Previous settings cannot be recovered.
- Hold the button for the specified time.
- Confirm this action is really needed before continuing.
Applies to: ECO Tec Series 3 control
Source: ECO Tec Series 3 boiler manual, p. 162. Written in our own words; check the manual for your exact model.
Review lockout history
Boiler · Ultra Series 4
The U-Control stores the last three lockouts with time, status and detail menus. Use them to see what happened before the lockout.
- Open Errors and select Lockout History 1 for the most recent lockout.
- Check Time and Date and Status to see the boiler state at the time of the lockout.
- Open Manual Reset or Auto Reset to see the detail for that lockout type.
- Open Inputs, Outputs or Temperatures to see the state at the time of the error.
- Repeat for Lockout History 2 and 3.
- Manual Reset Cnt and Auto Reset Cnt show counts since last cleared.
Applies to: Ultra Series 4 boilers, U-Control
Source: Ultra Series 4 gas-fired water boiler manual, p. 106-107. Written in our own words; check the manual for your exact model.
Wizard use, skip and restart
Boiler · ECO Tec Series 3
The setup wizard guides the install step by step and is recommended. Skipping it requires manual setup of every setting and is not recommended.
- Press USE WIZARD to run the guided setup. USE APP can load a settings file from the app.
- If you press SKIP WIZARD, the wizard can be restarted later from Reset to Factory Defaults in the Boiler Settings menu in the Contractor menu.
- If the boiler model shown does not match the installed model, perform a FACTORY RESET and select the correct model.
Applies to: ECO Tec Series 3 control setup
Source: ECO Tec Series 3 boiler manual, p. 100-101. Written in our own words; check the manual for your exact model.
Settings shortcuts
Where the useful parameters live and what they are set to from the factory.
0-10VDC remote modulation input setup and operation
Boiler · SVF Series 1
Remote modulation works only on a single boiler, not one in a network. It replaces the INPUT 1 heat demand, and the control cannot use both 0-10VDC target and modulation.
- Set up the boiler as a single boiler in the Unity control.
- Connect the signal positive to terminal 6 and common to terminal 5 on P15.
- Assign INPUT 1 to PRIORITY 2 during the WIZARD.
- In the ASSIGN INPUTS menu for INPUT 1, change SOURCE from TT1 to 0-10V.
- Expect a heat demand at 0.9 VDC, which turns off at 0.8 VDC.
- 2 VDC equals 10% input and 10 VDC equals 100% input. These voltage points are fixed.
- OUTPUT 1 energizes with the heat demand and can drive the system pump.
Applies to: Single boiler remote modulation
Source: SVF Series 1 boiler manual, p. 64. Written in our own words; check the manual for your exact model.
Change fuel type in Boiler Settings
Boiler · ECO Tec Series 3
The control shows Fuel Type under Boiler Settings. It must match the gas the boiler is running on.
- Open the Contractor menu, then Boiler Settings.
- Select Fuel Type and set it to Propane or Natural Gas to match the installed venturi and orifice.
Applies to: ECO Tec control
Source: ECO Tec Series 3 Boiler Manual, p. 22-23. Written in our own words; check the manual for your exact model.
Check the control date and time
Boiler · Evergreen Series 2
Confirm the date and time on the control so faults are logged correctly. Check it from the Date/Time screen under the Menu. If wrong, change it in the USER MENU.
- From the Home screen, swipe to the Menu screen.
- Select Date/time and read the displayed date and time.
- If incorrect, open the USER MENU and change the date and/or time.
Applies to: Evergreen Pro control on Series 2 boilers
Source: Weil-McLain Condensing Gas Boiler User's Information Manual, p. 8. Written in our own words; check the manual for your exact model.
DHW priority settings on zone valve systems
Boiler · ECO Tec Series 3
Priority 1 is the default for DHW and turns off lower priorities during DHW calls. Max on time can limit this.
- Keep Priority 1 for DHW if DHW should take precedence.
- Use Priority 2 or 3 for DHW if priority is not wanted.
- Set max on time to limit how long DHW priority runs.
- Avoid overriding Outdoor Reset to DHW mode when the system is for space heating; this may violate Section 303 of the 2007 Energy Act.
Applies to: Zone valve DHW tank
Source: ECO Tec Series 3 boiler manual, p. 56. Written in our own words; check the manual for your exact model.
Disable FREEZE PROTECT when not used
Boiler · EG / PEG Series 7
If freeze protection or circulator exercising is not used, FREEZE PROTECT must be turned off in the Advanced Menu.
- Open the Advanced Menu.
- Go to the CIRCULATOR settings.
- Set FREEZE PROTECT to disabled.
Applies to: All EG / PEG Series 7 boilers
Source: EG / PEG Series 7 Boiler Manual, p. 56. Written in our own words; check the manual for your exact model.
Reset maintenance reminder
Boiler · ECO Tec Series 3
The display shows a maintenance reminder (default 12 months). The contractor resets it after service.
- Open the SERVICE menu and go to Service Info.
- Select RESET REMINDER to update the last maintenance date and next due date.
- Homeowner can use reset to only update the next due date.
Applies to: ECO Tec Series 3 80/110/150/199
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 129. Written in our own words; check the manual for your exact model.
Set date, time and auto DST
Boiler · ECO Tec Series 3
The date and time are set with slide wheels. Accurate time matters for maintenance intervals and troubleshooting records.
- Select DATE/TIME from the boiler settings screen.
- Set the date with the slide wheels, then press the blue TIME button.
- Set the time with the slide wheels; press the blue AM/PM button to change AM or PM.
- Check the AUTO DST box so the control changes time for daylight saving.
- Press the back arrow when done, then confirm all settings and press the right arrow.
Applies to: ECO Tec control date and time setup
Source: ECO Tec Series 3 boiler manual, p. 91. Written in our own words; check the manual for your exact model.
Set the date and time
Boiler · SVF Series 1
Date and time feed the maintenance timing and the lockout history time stamps.
- Open the Set Time and Date menu.
- Set year, month, day, hour and minute.
- Confirm the display shows the correct time.
Applies to: Date and time setup
Source: SVF Series 1 boiler manual, p. 84. Written in our own words; check the manual for your exact model.
Set up 0-10VDC remote target input
Boiler · SVF Series 1
A 0-10VDC signal adjusts the supply target temperature through the TARGET ADJUST setting. The control interpolates the target between the set voltage and temperature points.
- Use PRIORITY 1 for DHW if used, and verify its settings.
- Use PRIORITY 2 for heating and set TARGET ADJUST to 0-10V.
- Set VOLTS FOR MAX to the voltage that calls for the highest target, and set SUPPLY MAX to that temperature.
- Set VOLTS FOR MIN to the voltage that calls for the lowest target, and set SUPPLY MIN to that temperature.
- Connect the signal positive to P15 terminal 6 and common to terminal 5.
- A dry contact heat demand must still be wired to an input to start a call for heat.
Applies to: Remote target input in PRIORITY SETTINGS
Source: SVF Series 1 boiler manual, p. 63. Written in our own words; check the manual for your exact model.
Wizard help and input locator
Boiler · ECO Tec Series 3
Each wizard step has HELP and WHERE buttons. WHERE shows a control diagram and the location of the input and output being set.
- Press HELP for an explanation of the selected line.
- Press WHERE on any input/output screen to find the matching input and output on the control diagram.
Applies to: ECO Tec Control wizard
Source: ECO Tec Series 3 boiler manual, p. 102-103. Written in our own words; check the manual for your exact model.
Commissioning
Start-up and set-up steps that are easy to miss.
AL29-4C stainless vent requires manufacturer adapter
Boiler · Ultra Series 4
AL29-4C vent pipe cannot connect to the boiler with a generic fitting.
- Use only the PVC-to-vent pipe adapter made by the vent pipe manufacturer.
- Install that adapter at the boiler vent connection.
- Install the same adapter at the termination if using the Weil-McLain plate or concentric termination.
Applies to: Ultra AL29-4C vent installations
Source: Weil-McLain Ultra Series 4 boiler manual, p. 91. Written in our own words; check the manual for your exact model.
Alternate DHW piping: enable the aux pump output
Boiler · Evergreen Series 2
If the DHW circuit is piped elsewhere in the system, the control only works if the system pump runs during DHW calls.
- Set PRIORITY 2 - NETWORK 1 with RUN AUX PUMP/OUTPUT set to YES instead of NO.
Applies to: Example B DHW piping when DHW is not directly connected
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 23. Written in our own words; check the manual for your exact model.
Altitude derate for input rate
Boiler · SVF Series 1
In the USA, input is derated 4% for each 1000 ft above sea level beyond 2000 ft. In Canada, input is derated 10% for 2000 to 4500 ft. Use the high altitude fan speed settings. Above 4500 ft in Canada, follow provincial authorities. Above 10,000 ft contact Weil-McLain.
- Check the elevation of the install.
- Apply the derate rule for the country.
- Use the high altitude rpm column from the blower speed tables.
Applies to: SVF 1500-3000
Source: SVF Series 1 boiler manual, p. 88. Written in our own words; check the manual for your exact model.
Anti-scald valve required for Combi DHW
Boiler · ECO Tec Series 3
The DHW outlet of a Combi must have an anti-scald thermostatic mixing valve. Without one, DHW can cause scalding.
- Confirm the anti-scald thermostatic mixing valve is installed, set and working before operating the boiler.
- If no mixing valve is installed, select DISABLE DHW to keep Combi features off while finishing setup.
- After the valve is installed, press ACCEPT. Combi features can be re-enabled later.
Applies to: ECO Tec 110 Combi and other Combi models
Source: ECO Tec Series 3 boiler manual, p. 100. Written in our own words; check the manual for your exact model.
Boiler ships for natural gas only
Boiler · ECO Tec Series 3
Propane requires the propane mixer (venturi) and orifice to be installed before connecting to propane.
- Install the propane mixer (venturi) and orifice before connecting to propane (see page 19 of the manual).
Applies to: ECO Tec Series 3 all models
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 64. Written in our own words; check the manual for your exact model.
Calculate natural gas input from meter
Boiler · Ultra Series 4
Measure time for one cubic foot of gas with other appliances off and the boiler running for 10 minutes. Result should be close to the input on the rating label.
- Run the boiler for 10 minutes.
- Turn off other gas appliances.
- At the gas meter, time how many seconds one cubic foot takes.
- Calculate Btuh = 3600 × 1000 divided by the seconds measured.
- Compare with the input rating on the boiler label.
Applies to: Ultra Series 4 gas boilers
Source: Weil-McLain Ultra Series 4 boiler manual, p. 40. Written in our own words; check the manual for your exact model.
Calls for heat during blower calibration
Boiler · ECO Tec Series 3
While the blower calibrates, calls for heat are ignored and the boiler stays in standby. A red warning shows on the homeowner screen until calibration ends. After the warning clears, the boiler runs on the wizard settings.
- Do not expect burner operation while the calibrating warning is showing.
- Wait for the red warning to clear before checking heat operation.
- Once cleared, check that the boiler responds to a call for heat.
Applies to: ECO Tec control during blower calibration
Source: ECO Tec Series 3 boiler manual, p. 96. Written in our own words; check the manual for your exact model.
Carbon monoxide alarm before startup
Boiler · CGa, CGi, EG, PEG
The installer must confirm at least one carbon monoxide alarm is installed in the living space before the boiler is put into operation.
- Confirm at least one CO alarm is installed in the living space before startup.
- Install, maintain and replace alarms per the alarm maker's instructions and local codes.
Applies to: All listed boiler series
Source: Gas-Fired Boilers User Manual, p. 3. Written in our own words; check the manual for your exact model.
Carbon monoxide alarm required before operation
Boiler · EG / PEG Series 7
The installer must confirm that at least one carbon monoxide alarm is installed and working in the living space, following the alarm maker's instructions and local codes, before the boiler is put into service.
- Install at least one CO alarm in the residential living space following the alarm maker's instructions and local codes.
- Confirm the alarm works before starting the boiler.
Applies to: Residential installations
Source: EG / PEG Series 7 Boiler Manual, p. 6. Written in our own words; check the manual for your exact model.
Check for gas leaks before startup
Boiler · EG / PEG Series 7
Check for gas leaks before starting the boiler and during first operation. Do not start if there is any sign of a gas leak.
- Before starting, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor.
- Do not continue start-up if there is any sign of a gas leak.
- Repair any leak right away.
Applies to: All EG / PEG Series 7 boilers
Source: EG / PEG Series 7 Boiler Manual, p. 56. Written in our own words; check the manual for your exact model.
Check the boiler location before installing
Boiler · ECO Tec Series 3
Confirm the site meets code, has suitable wall or floor support, is indoors only, and has nearby water, gas, vent, electrical and condensate connections.
- Confirm local, state, provincial and national codes are followed (NFPA 54 / CSA B149 and NEC / CSA C22.1).
- Confirm the wall can carry the boiler and components, or use a floor stand.
- Confirm the location is indoors only.
- Check nearby connections for system water, gas, venting, electrical power and condensate drain.
- Remove combustibles, gasoline and flammable liquids from the area.
- Protect gas controls from dripping or spraying water during operation or service.
- On a replacement, check and correct sediment, leaks, expansion tank sizing and freeze protection, and flush piping before connecting the new boiler.
Applies to: All ECO Tec Series 3 installations
Source: ECO Tec Series 3 boiler manual, p. 11. Written in our own words; check the manual for your exact model.
Check the derate before setting the boiler
Boiler · SVF Series 1
Vent and air piping length reduces the maximum input. Work out the equivalent length, apply the derate for your model and vent type, and check the input against the site before startup.
- Find the vent/air piping equivalent length in feet.
- Pick the derate formula for the model and vent type (direct exhaust or direct vent).
- Calculate the derate percentage and reduce the maximum input by that amount.
- For elevations above 5,500 ft, follow the high altitude section of the manual for control parameter changes.
Applies to: SVF 1500-3000 boilers
Source: SVF Series 1 boiler manual, p. 120. Written in our own words; check the manual for your exact model.
Circulator and air separator placement
Boiler · EG / PEG Series 7
The circulator is supplied by the installer, but wiring is provided with the boiler. Locate it in return or supply piping as needed.
- Supply the circulator separately. Wiring is in the boiler, so it can go in return or supply piping.
- Pipe the expansion tank to the suction side of the circulator when possible.
- Install an air separator in the supply piping.
- Connect the expansion tank to the air separator only if the separator is on the circulator suction side.
- Make the system fill connection at the same point as the expansion tank connection.
Applies to: EG water boilers, forced hot water systems
Source: EG/PEG Series 7 boiler manual, p. 20. Written in our own words; check the manual for your exact model.
Circulator flow rate formula
Boiler · Ultra Series 4
Size circulators from the flow needed for the wanted temperature change. Use the flow formula, or the shortcut for a 20 °F drop.
- Flow (gpm) = BTUH / (TD x 500), where TD is the temperature rise or drop in °F.
- Example: 210,000 Btuh at a 20 °F drop gives 21 gpm.
- Shortcut for a 20 °F drop: flow (gpm) = MBH / 10.
- Example: 35,000 Btuh gives 35 / 10 = 3.5 gpm.
Applies to: Ultra Series 4 boilers, space heating circuits
Source: Ultra Series 4 boiler manual, p. 10. Written in our own words; check the manual for your exact model.
Circulator load limits: external relay and power needed
Boiler · Evergreen Series 2
Boiler circulators and system circulators above the listed ratings need an external relay and separate power from the boiler.
- Provide an external relay and external power to the boiler circulator if its load exceeds 2.2 A FLA, 3.6 A locked rotor, or 16.4 A inrush.
- Provide an external relay and external power to a system circulator if its load exceeds 2.0 A FLA.
Applies to: Boiler and system circulator wiring in multi-boiler layouts
Source: Series 2 Condensing Gas Boiler Advanced Manual, pp. 20-23. Written in our own words; check the manual for your exact model.
Complete the installation and service certificate
Boiler · Ultra Series 4
The certificate records start-up data, U-Control settings and the boiler identity for the owner.
- Record CO2 and CO at high and low fire, and the fuel type.
- Record the U-Control set-up values for each priority used.
- Record the boiler model, series, CP number and date installed.
- Confirm the installation instructions and check-out sequence were completed.
- Leave the completed certificate with the owner or maintenance person.
Applies to: Ultra Series 4 start-up
Source: Weil-McLain Ultra Series 4 boiler manual, p. 140. Written in our own words; check the manual for your exact model.
Concentric assembly: install rain cap and bird screen last
Boiler · ECO Tec Series 3
Do not install the rain cap or bird screen until the assembly is through the roof or wall and all supports are in. Inner and outer pipes must butt correctly at both ends when shortened.
- Partially assemble the termination in the order shown in the manual figure.
- Cover the end of the assembly with plastic before insertion.
- Install the bird screen and rain cap only after supports are installed.
- If shortening the inner and outer pipes, confirm they butt correctly at both ends.
Applies to: PVC concentric termination
Source: ECO Tec Series 3 Boiler Manual, p. 46. Written in our own words; check the manual for your exact model.
Confirm boiler model, altitude and fuel type first
Boiler · Evergreen Pro, Series 2
Boiler model, altitude and fuel type are critical control settings. Setting them wrong can cause severe injury, death or substantial property damage.
- Set the boiler model, altitude and fuel type correctly during setup, either in the WIZARD or manually in the control menus.
- Verify all three settings before leaving the boiler running.
Applies to: All Series 2 110/155/220/299/300/399 boilers with Evergreen Pro control
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 64. Written in our own words; check the manual for your exact model.
Control features for multi-boiler and external inputs
Boiler · Evergreen Series 2
The control has three priority assignments for up to four heat inputs, an outdoor sensor (shipped with boiler), 0-10 VDC input for remote target or modulation, 0-10 VDC output for lead/lag or variable speed pumps, Modbus, and an alarm relay for error/fault.
Applies to: Evergreen Series 2 Pro control
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 8. Written in our own words; check the manual for your exact model.
Control setup Wizard at first startup
Boiler · SVF Series 1
The control setup Wizard is in the BOILER SETTINGS menu that appears at initial startup. It walks through setup for the chosen application, and context-sensitive help explains key items.
- At initial startup, open the BOILER SETTINGS menu.
- Follow the Wizard steps for the application.
- Use context-sensitive help to check the purpose of setup items.
Applies to: SVF 1500-3000 Series 1 single boiler
Source: SVF Series 1 Boiler Manual, p. 2. Written in our own words; check the manual for your exact model.
Critical boiler model and altitude settings
Boiler · SVF Series 1
Boiler model and altitude must be set correctly. Incorrect settings can cause severe injury, death or substantial property damage.
- Verify the boiler model on the power-up screen.
- Set the altitude correctly in the Wizard Boiler Settings.
- Set the fuel type (natural gas or propane). The control pauses until fuel is selected.
Applies to: SVF Series 1 startup
Source: SVF 1500-3000 Series 1 boiler manual, p. 68-69. Written in our own words; check the manual for your exact model.
Critical settings before operation
Boiler · ECO Tec Series 3
Boiler model, altitude and fuel type must be set correctly; wrong values can cause severe injury, death or property damage. Also set the water temperatures for the system, because excessive temperature can damage property. Protect low-temperature circuits with external limits.
- Set boiler model, altitude and fuel type first. The control pauses until fuel type is selected.
- Confirm the target water temperatures suit the system.
- On multi-temperature systems (radiant slab with baseboard or DHW), wire external limit controls to the low-temperature circuits.
Applies to: ECO Tec Series 3 control setup
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 84. Written in our own words; check the manual for your exact model.
Critical Wizard entries
Boiler · Evergreen Series 2
ALTITUDE and FUEL TYPE are critical and must be entered for each boiler before continuing.
- Enter the correct altitude band for each boiler.
- Select the correct fuel type for each boiler.
- Set WWSD temperature and manual reset high temperature limit as required.
Applies to: Each boiler in the installation
Source: Series 2 Advanced Manual, p. 14. Written in our own words; check the manual for your exact model.
DHW tank sizing and flow in direct-piped layouts
Boiler · Evergreen Series 2
DHW tanks piped this way must be sized for the load and use a DHW pump that keeps flow through the boiler and tank in the allowable range.
- Size the DHW tank for the required load.
- Select a DHW pump that gives flow within the allowable range from the pipe sizing table.
- Make sure the DHW circulator handles the pressure drop through the indirect water heater and piping, and gives equal or greater flow than the boiler circulator.
- For some large indirect water heaters, the required flow may need different water heater piping.
Applies to: Example A DHW piping
Source: Series 2 Condensing Gas Boiler Advanced Manual, pp. 20-21. Written in our own words; check the manual for your exact model.
Do not use petroleum-based sealing compounds
Boiler · EG, PEG
Petroleum-based sealing compounds in the system cause severe boiler damage and property damage.
- Use an approved sealant for system joints. Do not use petroleum-based compounds.
Applies to: Boiler system piping
Source: EG / PEG Series 7 Boiler Manual, p. 15. Written in our own words; check the manual for your exact model.
Express Setup Example A - application summary
Boiler · ECO Tec Series 3
Example A is a multi-zone space heating system with circulators that have no circulator relays, plus direct-piped indirect DHW. The default control settings only apply if the indirect water heater is direct piped to the boiler. Relief valve must be piped to the boiler In connection.
- Confirm the indirect water heater is direct piped to the boiler before relying on default settings.
- Pipe the boiler relief valve to the Boiler In connection, and run relief piping to drain.
- Wire the 120VAC supply to the boiler and install the outdoor sensor.
- Confirm supply and return temperature sensors and the low water cut-off are installed.
Applies to: Single boiler, multi-zone space heating with indirect DHW, Express Setup Example A
Source: ECO Tec Series 3 boiler manual, p. 89. Written in our own words; check the manual for your exact model.
Fill the condensate trap before operation
Boiler · Ultra Series 4
The condensate trap must hold water whenever the boiler runs, otherwise flue gas can escape through the condensate drain.
- Loosen the hose clamp at the right end of the condensate trap, at the PVC reducing elbow.
- Slide the trap hose off the elbow.
- Fill the trap with fresh water to within an inch of the hose end.
- Reconnect the hose to the elbow and tighten the clamp.
- If the boiler has been out of service a long time, prime the trap by pouring water into the outlet tee while restricting flow in the drain tube.
Applies to: Ultra Series 4 condensate system
Source: Weil-McLain Ultra Series 4 boiler manual, p. 37. Written in our own words; check the manual for your exact model.
Fill the condensate trap before startup
Boiler · ECO Tec Series 3
The trap must hold water whenever the boiler runs, or flue gas can come out of the condensate drain.
- Remove the test port cap on the vent adapter.
- Pour one cup of clean water into the test port.
- Confirm the condensate trap is full of water.
- Reinstall the test port cap.
Applies to: ECO Tec Series 3 80/110/150/199
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 132. Written in our own words; check the manual for your exact model.
Flush the system and protect the heat exchanger from sediment
Boiler · EG / PEG Series 7
Flush the whole system before connecting the boiler to remove sediment. Install a strainer or other sediment removal device if needed. Sediment build-up or corrosion can damage the cast iron heat exchanger.
- Thoroughly flush the system before connecting the boiler.
- Install a strainer or other sediment removal equipment if needed.
Applies to: Water boiler piping
Source: EG / PEG Series 7 Boiler Manual, p. 6. Written in our own words; check the manual for your exact model.
Freeze protection fluid requirements
Boiler · EG / PEG Series 7
Never use automotive antifreeze or standard ethylene glycol in the boiler system. Use only freeze protection fluids made for hydronic systems and follow the fluid maker's instructions. Thoroughly clean and flush any old system that used glycol before connecting a new boiler.
- Use only freeze protection fluid made for hydronic systems.
- Follow the antifreeze manufacturer's guidelines.
- Clean and flush the system thoroughly before installing a new boiler if glycol was used before.
Applies to: Hydronic boiler systems using antifreeze
Source: EG / PEG Series 7 Boiler Manual, p. 6. Written in our own words; check the manual for your exact model.
Full startup check after any maintenance
Boiler · Ultra Series 4
Removing and reinstalling components can change boiler behavior, so operation must be proven after any maintenance.
- Follow the complete boiler and system startup procedure, beginning on page 35.
- Confirm the boiler operates correctly before leaving the job.
Applies to: All Ultra Series 4 boilers
Source: Ultra Series 4 boiler manual, p. 125. Written in our own words; check the manual for your exact model.
Fused disconnect and field wiring
Boiler · EG, PEG, Series 7
A 15 A fused disconnect or service switch is recommended for the 120 VAC supply. If local code does not allow a switch on the boiler, fit a 2x4 cover plate on the boiler junction box and mount the switch remotely.
- Check local code before mounting the disconnect on the boiler.
- If a remote switch is required, cover the boiler junction box with a 2x4 plate.
Applies to: EG / PEG Series 7 boilers
Source: EG / PEG Series 7 boiler manual, p. 32. Written in our own words; check the manual for your exact model.
Indirect water heater piping for default settings
Boiler · ECO Tec Series 3
The default control settings for Example B only apply if the indirect water heater is direct piped to the boiler.
- Pipe the indirect water heater directly to the boiler.
- Install the DHW temperature and pressure relief valve per the piping diagram.
- If the water heater cannot be direct piped, the default settings are not valid and must be set manually.
Applies to: ECO Tec 110 Combi and indirect water heater applications
Source: ECO Tec Series 3 boiler manual, p. 99. Written in our own words; check the manual for your exact model.
Install a 100% lockup regulator when inlet pressure can exceed 14 in.
Boiler · ECO Tec Series 3
If the supply pressure can go above 14" w.c. at any time, a 100% lockup gas pressure regulator must be installed in the supply line.
- Install a 100% lockup regulator in the supply line.
- Adjust the lockup regulator to 14" w.c. maximum.
Applies to: ECO Tec Series 3 gas supply
Source: ECO Tec series 3 boiler manual, p. 24. Written in our own words; check the manual for your exact model.
Install the jacket before the return piping
Boiler · EG / PEG Series 7
Jacket and piping order, plus knockouts that must be removed first.
- Remove the knockout discs listed in Table 4 (page 15) before jacket installation.
- On EG boilers with optional tankless or storage heaters, remove the tankless and storage heater knockouts before installing the jacket.
- Install the jacket before connecting return piping. Supply piping may go in before or after the jacket.
- Connect controls after all piping is connected.
Applies to: EG and PEG boilers
Source: EG/PEG Series 7 boiler manual, p. 18, 20. Written in our own words; check the manual for your exact model.
Install the termination plate before the piping and support the run
Boiler · Ultra Series 4
The Weil-McLain termination plate must be mounted before piping is run from the boiler to the termination. Support the piping so it stays sloped and does not sag.
- Install pipe supports every 5 feet on both horizontal and vertical runs.
- Install a hanger support within 6 inches of any upturn in the piping.
- Slope horizontal piping downward toward the boiler at least 1/4 inch per foot.
Applies to: Weil-McLain sidewall termination plate
Source: Ultra Series 4 boiler manual, p. 70. Written in our own words; check the manual for your exact model.
Installation and service certificate: fields to complete
Boiler · ECO Tec Series 3
Record the boiler model/series, install date, Consumer Protection (CP) number, fuel (natural or LP), and Btu input. Confirm the installation instructions were followed and the check-out sequence was performed. Leave the information with the owner or maintenance person. Mark whether the system was assembled from tested components or tested as a complete system.
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 186. Written in our own words; check the manual for your exact model.
Installer and maintenance information in wizard
Boiler · ECO Tec Series 3
The last wizard screens hold installer and boiler information for the homeowner and contractor. The Consumer Protection number is preloaded and should be verified. The interval set controls when the maintenance reminder appears.
- Enter the installer name and phone number accurately.
- Verify the CP number is correct; it is preloaded and normally should not be changed.
- Set the maintenance interval to match the normal maintenance schedule.
- Confirm all information and press the right arrow to finish the wizard.
Applies to: ECO Tec control wizard final screens
Source: ECO Tec Series 3 boiler manual, p. 95. Written in our own words; check the manual for your exact model.
Leak check before starting the boiler
Boiler · Ultra Series 4
Check for gas odour and gas leaks before and during first start-up. Do not start if a leak is suspected.
- Use a leak detector or smell near the floor and around the boiler.
- Remove the boiler front door and smell inside the enclosure.
- Do not proceed if there is any sign of a gas leak; repair it at once.
- Check every gas connection with a bubble test and repair any leak before restarting.
- Propane only: have the supplier confirm the odorant level before startup and periodically after.
Applies to: All Ultra Series 4 gas boilers
Source: Weil-McLain Ultra Series 4 boiler manual, p. 37-38. Written in our own words; check the manual for your exact model.
Low water cutoff and high limit requirements
Boiler · EG / PEG Series 7
For ASME or Canadian installs, an external high limit is needed. The boiler has a built-in water temperature and low-water sensor on EG water boilers.
- Install the external high limit in the supply piping between the boiler and the isolation valve.
- Set the external high limit at least 20°F above the operating setpoint. The maximum external high limit setting is 240°F.
- The maximum operating limit is 210°F.
- Install a low water cutoff when the boiler sits above radiation level or when local codes or insurers require it. An extra external LWCO may be used alongside the built-in monitoring.
- Wire per page 31.
Applies to: EG water boilers
Source: EG/PEG Series 7 boiler manual, p. 20. Written in our own words; check the manual for your exact model.
Multi-boiler network addressing and detection
Boiler · Evergreen Pro, Series 2
The Master detects the other boilers on the network, but shadow boilers can take 30 seconds to 1 minute to appear. Each shadow boiler needs its own unique network address from 2 through 8.
- Wait 30 seconds to 1 minute after powering the network before expecting the Master to show the shadow boilers.
- Assign each shadow boiler a unique network address from 2 through 8. Do not reuse an address.
- If a boiler drops off the network, leave it connected. The Master reassigns it to its previous position when communication returns.
Applies to: Multiple boiler networks on Evergreen Pro control
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 63. Written in our own words; check the manual for your exact model.
Multiple boiler placement
Boiler · SVF Series 1
Several boilers can be placed side by side using the layout in Figure 3 or another layout that keeps all required clearances. Leave room for venting, air and gas piping, condensate components, expansion tank and pump.
- Chalk-line boiler locations on the foundation or floor.
- Build a foundation sized for the spacing shown if the floor is uneven or flooding is possible.
- Uncrate and assemble boilers following the manual.
- Maintain service clearances, or at least the minimum clearances on page 7.
Applies to: SVF 1500-3000 Series 1
Source: SVF Series 1 Boiler Manual, p. 8. Written in our own words; check the manual for your exact model.
Multiple boiler venting
Boiler · ECO Tec Series 3
Each ECO Tec needs its own separate vent pipe and termination. Vent piping cannot be manifolded. Combustion air piping may be individually piped or manifolded.
Applies to: ECO Tec Series 3 boilers in multi-boiler installs
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 185. Written in our own words; check the manual for your exact model.
Multiple-zone wiring with 3-wire zone valves
Boiler · EG / PEG Series 7
Do not wire 3-wire zone valves straight to the boiler T-T terminals. Use an isolation relay to protect boiler components.
- Do not connect 3-wire zone valves directly to the boiler T-T terminals.
- Install an isolation relay.
- Connect the zone valve end switch wires to the isolation relay coil.
- Connect the isolation relay contact across the boiler T-T terminals.
Applies to: Multi-zone systems
Source: EG/PEG Series 7 boiler manual, p. 21. Written in our own words; check the manual for your exact model.
Name the zones during setup
Boiler · ECO Tec
The control lets you name each hydronic zone or circuit. Clear names make the system easier to trace on later service visits.
- Name each zone or circuit on the touchscreen during commissioning.
- Confirm the names match the actual circuits before leaving the job.
Applies to: ECO Tec Series 3 boilers with Unity 2.0 control
Source: ECO Tec Value Comparison Guide, p. 2. Written in our own words; check the manual for your exact model.
Near-boiler piping connections and isolation valves
Boiler · EG / PEG Series 7
Connection layout and valve placement for EG water boilers.
- On EG boilers, connect supply and return to the left end.
- Plug all unused connections.
- Install isolation valves so the boiler temperature sensor can be serviced. Follow the piping diagram used for the installation.
Applies to: EG water boilers
Source: EG/PEG Series 7 boiler manual, p. 20. Written in our own words; check the manual for your exact model.
Network mode selection on first power-up
Boiler · ECO Tec Series 3
The first screen after power-up sets whether the boiler works alone or in a multi-boiler network. Only one master is allowed per multi-boiler system.
- For a stand-alone boiler choose SINGLE BOILER.
- For a multi-boiler network, set one boiler as ON NETWORK AS MASTER. The master controls firing rate and burner-on commands for the network.
- Set the other boilers as ON NETWORK AS SHADOW. They follow the master for network calls for heat and control themselves for local calls for heat.
- Press the right arrow to continue after selecting.
Applies to: ECO Tec Series 3 control configuration
Source: ECO Tec Series 3 boiler manual, p. 100. Written in our own words; check the manual for your exact model.
Network priorities are set on the master boiler only
Boiler · Evergreen Series 2
The wizard only lets you configure network priorities on the master. Shadow boilers skip that setup.
- Make all network priority settings on the master boiler's wizard.
- Check on a shadow boiler that network priority screens are skipped.
- Local priorities are set on the boiler the input is wired to.
Applies to: Multi-boiler network
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 16. Written in our own words; check the manual for your exact model.
Never combine vent piping
Boiler · Evergreen Series 2
Only combustion air piping may be combined on a manifold. Combined vent piping causes flue gas leakage and boiler component damage.
Applies to: Multiple Evergreen boilers with combined air
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 6. Written in our own words; check the manual for your exact model.
Outdoor sensor mounting and wiring
Boiler · Ultra Series 4
The outdoor sensor ships with the boiler. It is not required, but it must be installed to use WWSD or outdoor reset. Mount it out of direct sun and away from other heat or cooling sources. Thermostat wire is acceptable.
- Mount the sensor on an exterior wall, shielded from sun and from heat or cooling sources.
- Connect the sensor leads to P10 terminals 1 and 2.
- Use thermostat wire if needed.
Applies to: Outdoor reset and WWSD
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98 and p. 99. Written in our own words; check the manual for your exact model.
Outdoor sensor requirement
Boiler · ECO Tec Series 3
The outdoor sensor supplied with the boiler must be installed unless one of the listed exemptions applies.
- Install the supplied outdoor sensor.
- Only skip it if an exemption in the manual applies.
Applies to: ECO Tec 80/110/150/199 Series 3
Source: ECO Tec Series 3 boiler manual, p. 184. Written in our own words; check the manual for your exact model.
Pitch, support and clearance of vent and air piping
Boiler · Ultra Series 4
Correct slope and support keep condensate draining back to the boiler and keep the pipe away from combustibles.
- Slope vent and air piping continuously toward the boiler at least 1/4 inch per foot of run.
- Avoid any sags along the run.
- Keep at least 3/16 inch clearance between vent pipe and any combustible wall or material.
- Install pipe supports as shown in the figures for the termination type.
- Seal wall and floor penetrations per local code.
Applies to: Direct vent piping
Source: Ultra Series 4 boiler manual, p. 82. Written in our own words; check the manual for your exact model.
Priority timing (MAX ON and MIN ON)
Boiler · ECO Tec Series 3
Priorities decide which system runs first. MAX ON TIME is how long a priority can run before a lower priority's call is served. MIN ON TIME is how long a priority must run before a higher priority or the next lower priority can take over. DHW on priority 1 is a typical example.
- Set MAX ON TIME for each priority so no system is held off too long.
- Set MIN ON TIME so the boiler does not switch priorities too quickly.
- Each priority keeps its own parameters, and the system type sets the defaults. Choose CUSTOM to create a new system type.
Applies to: ECO Tec Series 3 multi-system heating
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 85. Written in our own words; check the manual for your exact model.
Protect the air inlet with a bird screen
Boiler · Ultra Series 4
The air inlet opening needs a screen to keep foreign objects out.
- Get a bird screen sized for the air inlet opening from WM Technologies.
- Insert the screen into the air inlet opening.
Applies to: Ultra air intake
Source: Weil-McLain Ultra Series 4 boiler manual, p. 91. Written in our own words; check the manual for your exact model.
Relief valve and pressure/temperature gauge limits
Boiler · SVF
The maximum allowed relief valve setting is 160 PSIG and the boiler ships with a 30 PSIG relief valve. The gauge shipped with the boiler reads to 75 psig and meets ASME requirements only up to a 50 psig relief valve. A higher-rated relief valve needs a gauge with a higher range, and a gauge needing a larger tapping than the 1/4 inch NPT supply tap needs an extra tap placed before any isolation valve.
- Never install a relief valve rated above 160 PSIG.
- For a relief valve above 50 psig, fit a P/T gauge with a higher pressure range.
- If a larger gauge tapping is needed, add the tap in the near-boiler piping before any isolation valve.
Applies to: All SVF 1500-3000 models
Source: SVF 1500-3000 Series 1 boiler manual, p. 12. Written in our own words; check the manual for your exact model.
Relief valve installation
Boiler · EG / PEG Series 7
Install the relief valve only in the tapping on top of the boiler, in the vertical position. The valve may discharge large amounts of steam or hot water, so the discharge line is mandatory.
- Clean the valve inlet and all connections; remove foreign matter.
- Mount the relief valve vertically, connected directly to the top tapping designated in the manual.
- Use pipe compound sparingly, or tape, on external threads only.
- Use a proper wrench on the wrench pads only; do not use a pipe wrench on the valve body.
- Pipe the discharge from the outlet to a safe point with no valve in between.
- Make sure the discharge line drains fully and is independently supported and anchored.
- End the discharge freely to atmosphere where it is visible and cannot freeze.
- Use schedule 40 metal pipe, at least the valve outlet size over its full length. Do not use schedule 80 or extra strong pipe.
- Do not cap, plug or obstruct the discharge pipe outlet.
- If the discharge is piped upward, provide a condensate drain in the elbow below the vertical run.
Applies to: EG/PEG steam boilers
Source: EG/PEG Series 7 boiler manual, p. 25. Written in our own words; check the manual for your exact model.
Relief valve installation and discharge line
Boiler · EG / PEG Series 7
Relief valve is installed vertically in the 3/4 in. tapping on the side of the boiler. A discharge line is mandatory and must follow these rules.
- Install the relief valve vertically in the 3/4 in. side tapping.
- Follow the manufacturer's tag on the valve.
- Keep the discharge line as short as possible and the same size as the valve outlet over its full length.
- Pitch the discharge line downward from the valve. End it at least 6 in. above a floor drain where discharge is visible.
- End the line plain (not threaded), rated for at least 375°F.
- Do not route the discharge where freezing can occur.
- Do not put a shutoff valve between the relief valve and boiler or in the discharge line. Do not plug or obstruct the line.
- After filling and pressurizing, test the valve by lifting the lever. Confirm it discharges freely. Replace the valve if it does not operate correctly.
Applies to: EG water boilers
Source: EG/PEG Series 7 boiler manual, p. 20. Written in our own words; check the manual for your exact model.
Relief valve maximum setting
Boiler · Ultra Series 4
Do not install a relief valve rated above 30 psig. That is the highest allowable relief valve setting for the Ultra boiler.
- Check the relief valve pressure rating before installing it on the boiler supply tee.
Applies to: All Ultra Series 4 models
Source: Ultra Series 4 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Relief valve rating limit
Boiler · ECO Tec Series 3
Never install a relief valve rated above 50 psig, which is the maximum allowed for this boiler. Install the relief valve only after the hydrostatic test.
- Use a relief valve rated 50 psig or lower.
- Fit the relief valve in the 3/4 in elbow on the air elimination/relief valve water pipe connection, with discharge piping per the venting section.
Applies to: ECO Tec 80/110/150/199 Series 3
Source: ECO Tec Series 3 Boiler Manual, p. 17. Written in our own words; check the manual for your exact model.
Required codes for installation
Boiler · EG / PEG Series 7
Installation must follow local, state, provincial and national codes. In the US this includes the National Fuel Gas Code (ANSI Z223.1/NFPA 54), the National Electrical Code (ANSI/NFPA 70), and ANSI/ASME CSD-1 where the authority having jurisdiction requires it. In Canada use CAN/CSA B149.1 or B149.2.
- Confirm which codes the local authority requires.
- Follow NFPA 54 and NEC in the US, or CAN/CSA B149.1/B149.2 in Canada.
- Apply ANSI/ASME CSD-1 if the authority having jurisdiction requires it.
Applies to: All installations
Source: EG / PEG Series 7 Boiler Manual, p. 8. Written in our own words; check the manual for your exact model.
Return water temperature and low-temperature systems
Boiler · EG / PEG Series 7
Figures 16 and 17 apply only when return water is at least 130°F. Systems with low return temperature need bypass piping to prevent condensation and corrosion.
- Use the Figure 16 or 17 piping only for systems designed for at least 130°F return water.
- For converted gravity systems, radiant systems or other low-return systems, install bypass piping (page 22).
- If the system has radiant circuits, add piping and controls to regulate the supply temperature to them.
Applies to: Low-temperature and radiant systems
Source: EG/PEG Series 7 boiler manual, p. 21-22. Written in our own words; check the manual for your exact model.
Review with owner at startup
Boiler · SVF Series 1
Points to cover with the owner at the end of startup.
- Review the SVF User's Information Manual with the owner.
- Stress the maintenance schedule in the User's Information Manual.
- Tell the owner to call a licensed contractor if the boiler or system behaves unusually.
- Tell the owner to follow the proper shutdown procedure.
- Schedule an annual startup at the start of the next heating season.
Applies to: SVF 1500-3000 Series 1 boiler
Source: Weil-McLain SVF Series 1 boiler manual, p. 98. Written in our own words; check the manual for your exact model.
Sensor placement for system supply and return
Boiler · Evergreen Series 2
Supply and return sensors are strapped to the system piping away from the boiler tees.
- Strap the system supply and return sensors to the lines at least 6 pipe diameters from the boiler connection tees.
- Do not put the sensors more than 3 feet from the tees.
- For redundancy, install a supply and return sensor for each boiler.
Applies to: Multi-boiler piping with system sensors
Source: Series 2 Condensing Gas Boiler Advanced Manual, pp. 19, 22. Written in our own words; check the manual for your exact model.
Sentinel X100 inhibitor is required
Boiler · ECO Tec Series 3
The ECO Tec boiler must have Sentinel X100 in the system to protect the heat exchanger.
- After filling as directed, add X100 aerosol following the container instructions.
- Let the water circulate and mix.
- Check the inhibitor level and add more if needed.
- Check the inhibitor level annually with the Sentinel test kit.
Applies to: ECO Tec Series 3 80/110/150/199
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 131. Written in our own words; check the manual for your exact model.
Set boiler model, altitude and fuel type first
Boiler · ECO Tec Series 3
Boiler model, altitude and fuel type are critical control settings. Wrong values can cause severe injury, death or property damage. Confirm them before adjusting any priority settings.
- Verify the boiler model, installation altitude and fuel type on the control.
- Correct any mismatch before changing priority or pump settings.
Applies to: All ECO Tec Series 3 boilers
Source: ECO Tec Series 3 boiler manual, p. 120-126. Written in our own words; check the manual for your exact model.
Set maintenance reminder and contractor info
Boiler · SVF Series 1
The display shows a maintenance reminder, default 12 months. Set it up with the contractor details and reset it at each service visit.
- Open MAINTENANCE and enter contractor name, CP number and install date.
- Set the maintenance interval based on service history.
- At each service visit, choose RESET REMINDER to update Last and Next dates.
- Enter the current date and time so lockout records are time-stamped.
Applies to: Maintenance Info menu
Source: SVF Series 1 boiler manual, p. 84. Written in our own words; check the manual for your exact model.
Set water temperatures to suit the system
Boiler · Evergreen Pro, Series 2
Excessive water temperature can cause significant property damage in some applications. Set the control for the water temperatures the system can safely handle.
- Check the system's maximum safe water temperature before setting the control.
- Set the control to match that temperature limit.
Applies to: All Series 2 boilers with Evergreen Pro control
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 64. Written in our own words; check the manual for your exact model.
Setup wizard options
Boiler · ECO Tec Series 3
The wizard walks through setup step by step and is recommended. USE APP sends a settings file from the app for a faster setup. SKIP WIZARD skips all setup and requires manual entry of every setting, which is not recommended.
- Press USE WIZARD for a guided setup (recommended).
- To use the app, press USE APP and send the settings file from the app.
- Avoid SKIP WIZARD unless the full manual setup is intended.
- If the wizard was skipped, use RESTART WIZARD under Reset to Factory Defaults in the Boiler Settings menu, reached via the Contractor menu.
Applies to: ECO Tec control first setup
Source: ECO Tec Series 3 boiler manual, p. 91. Written in our own words; check the manual for your exact model.
Sizing system and zone circulator flow
Boiler · ECO Tec Series 3
Flow in gpm equals heat load in Btuh divided by (temperature drop x 500). For a 20°F drop, flow equals MBH divided by 10. The circulator must deliver this flow against the calculated head loss.
- Calculate flow: FLOW = BTUH / (TD x 500).
- Example: 210,000 Btuh load with 20°F drop gives about 20 gpm.
- Find pipe size and head loss using accepted engineering methods.
- Select a circulator that meets the flow at that head loss.
Applies to: System and zone circulators supplied by installer
Source: ECO Tec Series 3 boiler manual, p. 59. Written in our own words; check the manual for your exact model.
Skipping blower calibration during the wizard
Boiler · ECO Tec Series 3
Choosing SKIP CALIBRATION lets you continue the wizard, but the boiler will not operate until calibration is done. Run it later from the Boiler Settings screen in the Contractor menu. Calls for heat are ignored and the boiler stays in standby until calibration is complete.
- Open the Contractor menu (see access tip).
- Go to the Boiler Settings screen.
- Select the blower calibration option and run it.
Applies to: ECO Tec control, wizard blower calibration
Source: ECO Tec Series 3 boiler manual, p. 106. Written in our own words; check the manual for your exact model.
Stability warning for floor stand installs
Boiler · ECO Tec Series 3
A boiler on a pedestal stand can be top-heavy and tip before the piping is connected.
- Do not leave the boiler unsupported on the stand until the flue and water pipe connections are made.
- Once the flue and water connections are complete, the boiler is stable.
- An unsupported boiler can fall and cause severe injury or death.
Applies to: Pedestal floor stand installations
Source: ECO Tec Series 3 boiler manual, p. 15. Written in our own words; check the manual for your exact model.
Startup screen - select control configuration
Boiler · ECO Tec Series 3
On first power-up the control asks for the configuration. Single Boiler is for a stand-alone boiler. On Network as Master controls the firing rate and burner-on commands for a multi-boiler network, and only one master is allowed. On Network as Shadow is controlled by the master for network heat calls and runs itself for local calls.
- Choose Single Boiler for a stand-alone installation and press the right arrow.
- For a multi-boiler network, choose Master on one boiler only and Shadow on the others.
- Check the boiler model on the startup screen matches the actual boiler.
- If the model does not match, perform a factory reset as described in the manual.
- Check the system and outdoor sensor status shows as expected; check sensors if not.
Applies to: ECO Tec control first power-up
Source: ECO Tec Series 3 boiler manual, p. 90. Written in our own words; check the manual for your exact model.
Steam boiler piping layout
Boiler · EG / PEG Series 7
Connection rules for steam boilers. Proper piping prevents operating faults and boiler damage.
- Connect the steam supply on the same end as the controls. Return may connect at either end.
- Install the boiler jacket before connecting return piping. Connect controls after all piping is connected.
- Keep at least 24 in. from the waterline to the bottom of the header.
- Use an offset header so it does not bend at the section tappings.
- For counterflow systems, connect the boiler steam supply into the top of the counterflow header (Figure 22, page 25).
Applies to: EG and PEG steam boilers
Source: EG/PEG Series 7 boiler manual, p. 24. Written in our own words; check the manual for your exact model.
System supply and return sensor placement
Boiler · Ultra Series 4
Two strap-on sensors ship with the boiler and can attach to pipe up to 3 inches in diameter. The supply sensor must be at least six pipe diameters but no more than 3 feet downstream of the boiler connection. The return sensor is used for display and for sensor-failure checks. For multiple boilers, the lead boiler needs both sensors.
- Strap the system supply sensor on the main piping at least six pipe diameters, and no more than 3 feet, downstream of the boiler connection.
- Strap the system return sensor on the return piping.
- For multiple boiler applications, wire both sensors to the LEAD boiler.
- Confirm the sensors are wired with thermostat wire or equivalent.
Applies to: Ultra U-Control system temperature sensing
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98 and p. 11. Written in our own words; check the manual for your exact model.
Thermostat anticipator setting
Boiler · ECO Tec Series 3
Thermostat anticipator is set to 0.1 A on these pages.
- Set the thermostat anticipator to 0.1 amps.
Applies to: ECO Tec Series 3 all models
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 69. Written in our own words; check the manual for your exact model.
Use sweep elbows on all vent and air piping
Boiler · ECO Tec Series 3
Short radius elbows reduce boiler performance. Sweep elbows are required on all vent and air piping, including the direct exhaust installs.
- Use sweep elbows for all vent and air piping.
- Do not use short radius elbows anywhere in vent or air runs.
Applies to: All direct vent and direct exhaust installs
Source: ECO Tec Series 3 Boiler Manual, p. 41, 43, 45. Written in our own words; check the manual for your exact model.
Use the Setup Wizard and a preloaded system type
Boiler · ECO Tec
The Unity 2.0 touchscreen has a Setup Wizard that walks through installation. It includes ten preloaded system types, which cuts setup time and guesswork.
- Start the Setup Wizard on the Unity 2.0 touchscreen.
- Select the preloaded system type that matches the hydronic layout.
- Work through each wizard screen in order to finish the setup.
Applies to: ECO Tec Series 3 boilers with Unity 2.0 control
Source: ECO Tec Value Comparison Guide, p. 1-2. Written in our own words; check the manual for your exact model.
Use two wrenches on water pipe connections
Boiler · ECO Tec Series 3
When tightening any pipe connection to the boiler, hold the boiler pipe with a second wrench so it does not turn. Turning it can damage the pipe or heat exchanger.
- Use two wrenches on every boiler pipe connection.
Applies to: ECO Tec 80/110/150/199 Series 3
Source: ECO Tec Series 3 Boiler Manual, p. 17. Written in our own words; check the manual for your exact model.
Vent and air pipe requirements
Boiler · ECO Tec Series 3
ECO Tec needs direct venting as a Category IV boiler. Use only the vent materials and methods in this manual. Vent and air pipes can be 2 in or 3 in with an adapter for 2 in. Air intake must be 3 in PVC at the adapter. Exhaust must be 3 in PVC, PP or SS at the adapter. All elbows must be sweep elbows, not short-radius. Direct exhaust venting is possible only with the kit option.
- Confirm vent and air pipe size (2 in or 3 in).
- Use a 2 in to 3 in adapter at the boiler for 2 in venting.
- Check that air intake is 3 in PVC and exhaust is 3 in PVC, PP or SS at the adapter.
- Use sweep elbows only.
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 184. Written in our own words; check the manual for your exact model.
Venting fittings and vent sizes
Boiler · ECO Tec Series 3
ECO Tec boilers need Category IV venting. Use only the vent materials and methods in the manual. Vent and air pipe can be 2" or 3"; a 2" run needs an adapter. Air intake must be 3" PVC at the adapter; exhaust must be 3" PVC/PP/SS at the adapter. Use sweep elbows only, not short-radius elbows. Direct exhaust venting is possible with the kit option.
- Confirm the vent is Category IV-rated material and method.
- Use an adapter if running 2" vent.
- Install 3" PVC air intake at the adapter and 3" PVC/PP/SS exhaust at the adapter.
- Use sweep elbows on all vent and air elbows.
Applies to: ECO Tec 80/110/150/199 Series 3
Source: ECO Tec Series 3 boiler manual, p. 184. Written in our own words; check the manual for your exact model.
Verify propane conversion and blower model
Boiler · ECO Tec Series 3
Boilers ship ready for natural gas only. For propane, confirm the conversion. On the 199, confirm the blower model is selected.
- For propane, verify the boiler was converted per page 19 before startup.
- On the 199, check the blower label (Figure 158, page 177).
- Confirm the correct model is selected on the Boiler Settings Blower Model screen.
- Verify this again after a factory reset, control replacement or blower replacement.
Applies to: ECO Tec Series 3 80/110/150/199
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 133. Written in our own words; check the manual for your exact model.
Verify propane or natural gas venturi label
Boiler · ECO Tec Series 3
Each gas type uses a different venturi label. Confirm the label matches the gas and model before installing.
- Propane venturi has a black label marked LP.
- Natural gas venturi has a white label.
- Confirm the label part number matches the model size from the venturi table.
Applies to: ECO Tec 80/110/150/199
Source: ECO Tec Series 3 Boiler Manual, p. 19-20. Written in our own words; check the manual for your exact model.
Verify the boiler model setting before startup
Boiler · Ultra Series 4
The U-Control model setting must match the rating plate. A wrong model setting can cause severe injury, death or property damage. The model is also shown on the display at power-up.
- Read the model on the boiler rating plate.
- Check the BOILER MODEL setting in the contractor menu (80, 105, 155, 230, 299 or 399).
- Change the setting if it does not match.
- Confirm the model shown on the display at power-up.
Applies to: All Ultra models
Source: Weil-McLain Ultra Series 4 boiler manual, p. 99, p. 102 and p. 104. Written in our own words; check the manual for your exact model.
Water chemistry and system cleaning for stainless heat exchanger
Boiler · SVF Series 1
The stainless steel heat exchanger needs system pH between 7.0 and 8.5, checked water chemistry and chemical treatment. Sediment can damage it, and make-up water adds minerals and oxygen. Use the boiler only in a closed-loop system.
- Flush the system with the boiler disconnected to remove sediment.
- Install a strainer or other sediment removal if needed.
- Check pH is between 7.0 and 8.5 and treat the water chemistry.
- Do not use petroleum-based cleaning or sealing compounds.
- Repair leaks right away to stop make-up water entering the system.
- Do not add cold water to a hot boiler.
Applies to: SVF 1500-3000 Series 1
Source: SVF Series 1 Boiler Manual, p. 5; see p. 85-86 for details. Written in our own words; check the manual for your exact model.
Water chemistry for stainless steel heat exchanger
Boiler · Evergreen Series 2
The heat exchanger is stainless steel, so check water chemistry. System pH must be 7.0 to 8.5. Chemical treatment may be needed.
- Flush the system before connecting the boiler and install a strainer or sediment separator if needed.
- Do not use petroleum-based cleaning or sealing compounds.
- Use the boiler in a closed-loop system only.
- Repair leaks at once, since make-up water shortens boiler life.
- Do not add cold water to a hot boiler.
Applies to: Evergreen boiler water side
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 4. Written in our own words; check the manual for your exact model.
Wizard sequence order
Boiler · SVF Series 1
The Wizard walks through boiler settings, inputs/outputs, priorities, system settings and types, output activation, priority switching, date/time and installer information.
- Boiler Settings: altitude, fuel, WWSD.
- Inputs/Outputs: usage of inputs 1-3 and outputs 1-3.
- Set Priorities: assign priorities 1-3 to the inputs.
- System Settings and System Types: keep defaults or change, and set the operating temperature type for each output.
- Output Activation: select AUX PUMP/OUTPUT activation when applicable.
- Priority Switching: set max and min times.
- Date/Time: set the clock for diagnostic logging.
- Information: set installer contact, CP#, install and maintenance dates, and maintenance notification timing.
Applies to: SVF Series 1 Unity Wizard
Source: SVF 1500-3000 Series 1 boiler manual, p. 69. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Additional heat demand (AHD) behaviour
Boiler · ECO Tec Series 3
AHD can be set to 1st, 2nd or Outdoor Temperature. With 1st, the contact closes at once on a call and the boiler starts only if the call is still active when RESPONSE TIME expires and the system is below target minus system-on differential. With 2nd, the boiler starts immediately and the AHD contact closes after RESPONSE TIME. TEMP DEPENDENT = YES requires system supply below target before the AHD contact and 0-10V output act; this needs a valid supply and return sensor pair. The outdoor setpoint option needs a valid outdoor sensor. A master boiler cannot use AHD on a local priority; network AHD must be wired to the master.
Applies to: ECO Tec Series 3 priority menus
Source: ECO Tec Series 3 boiler manual, p. 122. Written in our own words; check the manual for your exact model.
Air inlet is not a forced-air intake
Boiler · ECO Tec Series 3
The boiler air inlet is part of a direct vent connection. Spacing from adjacent boiler vents is not judged as a forced-air intake.
Applies to: Multiple boiler and adjacent appliance spacing
Source: ECO Tec Series 3 boiler manual, p. 33, 35, 37, 39. Written in our own words; check the manual for your exact model.
AL29-4C stainless vent pipe adapter
Boiler · Ultra Series 4
AL29-4C stainless vent pipe needs the vent pipe maker's PVC adapter when joining to the concentric vent attachment.
- Use the vent pipe manufacturer's PVC adapter at the concentric vent attachment.
Applies to: Concentric vent with AL29-4C stainless vent pipe
Source: Ultra Series 4 boiler manual, p. 74, 77. Written in our own words; check the manual for your exact model.
AL29-4C stainless vent pipe requires a manufacturer adapter
Boiler · Ultra Series 4
When using AL29-4C stainless vent pipe, a PVC-to-vent adapter is needed at the boiler vent connection, and also at the termination when using the Weil-McLain plate or the concentric termination.
- Use only the adapter made by the vent pipe manufacturer.
- Install the adapter at the boiler vent connection.
- Install a second adapter at the termination when using the Weil-McLain plate or concentric termination.
Applies to: AL29-4C vent pipe on Ultra boilers
Source: Ultra Series 4 boiler manual, p. 71. Written in our own words; check the manual for your exact model.
Alarm and additional heat demand dry contacts
Boiler · Ultra Series 4
The alarm contact on P16 terminals 4 and 5 closes when the boiler enters lockout, for remote alarm notification. The additional heat demand contact on P16 terminals 6 and 7 starts another heat source. Both are low voltage only.
- Connect the remote alarm to P16 terminals 4 and 5 if notification is needed.
- Connect the next heat source to P16 terminals 6 and 7 if using additional heat demand.
Applies to: Ultra U-Control dry contacts
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98. Written in our own words; check the manual for your exact model.
Altitude derate
Boiler · ECO Tec Series 3
From sea level to 2,000 ft the boiler needs no changes and derates itself about 4% per 1,000 ft above sea level. Ratings in the table are for sea level only.
- Check the installation altitude.
- Use the sea-level ratings only at sea level; above that, expect the automatic derate.
Applies to: ECO Tec 80/110/150/199 Series 3
Source: ECO Tec Series 3 boiler manual, p. 184. Written in our own words; check the manual for your exact model.
Altitude derate and high altitude settings
Boiler · SVF Series 1
Above 5,500 ft the control parameters must be changed as the high altitude section of the manual describes. Below that, no change is needed.
- Check the site elevation.
- Above 5,500 ft, follow the high altitude section and change the listed control parameters.
- Record the high altitude setting on the data collection sheet.
Applies to: SVF 1500-3000 Series 1
Source: Weil-McLain SVF Series 1 boiler manual, p. 120, 122. Written in our own words; check the manual for your exact model.
Aluminum heat exchanger water chemistry
Boiler · Ultra Series 4
The Ultra heat exchanger is aluminum. System pH must stay between 7.0 and 8.5 and water chemistry must be checked. Chemical treatment may be needed. Sediment and scale can damage the heat exchanger, and fresh make-up water shortens boiler life.
- Flush the system thoroughly before connecting the boiler to remove sediment.
- Install a strainer or other sediment removal if needed.
- Check water pH and chemistry and treat as needed (see page 35).
- Repair leaks at once to stop make-up water from entering.
- Use the boiler only in a closed-loop system.
- Do not add cold water to a hot boiler.
Applies to: Ultra Series 4 boilers
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 4. Written in our own words; check the manual for your exact model.
Antifreeze use in hydronic systems
Boiler · EG, PEG
Use only antifreeze made for hydronic systems; inhibited propylene glycol is recommended. Ethylene glycol, automotive or undiluted antifreeze must not be used. A 50% propylene glycol/water solution gives protection to about -30°F. Boiler water content is listed on page 89 and the expansion tank volume must be included.
- Calculate antifreeze quantity from total system water content, including the expansion tank.
- Follow the antifreeze manufacturer's instructions.
- If an automatic fill is used, install a water meter to monitor makeup water because glycol leaks before water does.
- If freeze protection or circulator exercising is not used, disable FREEZE PROTECT in the ADVANCED MENU under CIRCULATOR settings.
- Install a backflow preventer or disconnect from city supply if local codes require it.
Applies to: Freeze protection in water boilers
Source: EG / PEG Series 7 boiler manual, p. 56. Written in our own words; check the manual for your exact model.
Approved vent and air materials and assembly rules
Boiler · ECO Tec Series 3
Use only materials approved for this boiler. Mixing manufacturers, using the wrong plastics, or insulating plastic vent pipe can cause failure.
- Use only the materials in Figure 31 (PVC, PVC-DWV, CPVC, ABS for intake only, polypropylene from Simpson-Duravent or Centrotherm, and AL29-4C stainless from approved makers).
- Use cement and primer suited to the piping material.
- Do not mix pipe from different manufacturers unless using an adapter made for that purpose.
- Use a locking collar on every polypropylene joint.
- Do not use cellular core PVC, cellular core CPVC or Radel (polyphenolsulfone) in venting.
- Do not cover plastic vent pipe or fittings with thermal insulation.
- Use the boiler's 3" 3-in-1 vent adapter for 3" PVC, CPVC, PVC-DWV, Simpson-Duravent AL29-4C, and Simpson-Duravent or Centrotherm polypropylene. The air inlet adapter takes 3" PVC only.
- Install a bird screen at every vent and air termination. Weil-McLain sidewall vent caps include the screen.
Applies to: ECO Tec Series 3 vent and air piping materials
Source: ECO Tec series 3 boiler manual, p. 28. Written in our own words; check the manual for your exact model.
Avoid petroleum-based compounds in the system
Boiler · Ultra Series 4
Petroleum-based cleaning or sealing compounds can damage gaskets and seals in the system and cause property damage.
- Use only water-compatible cleaners and sealers in the boiler system.
Applies to: All Ultra Series 4 models
Source: Ultra Series 4 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Bird screens and vent connections for direct exhaust
Boiler · Ultra Series 4
Bird screens are not supplied and must be bought separately, and each Ultra needs its own vent.
- Install a bird screen in every vent pipe termination.
- Buy bird screens separately from WM Technologies.
- Use the same vent material throughout; do not mix piping types.
- Do not connect any other appliance to a boiler vent pipe.
- Do not connect multiple boilers to a common vent pipe.
Applies to: Direct exhaust and direct vent
Source: Ultra Series 4 boiler manual, p. 83, 88. Written in our own words; check the manual for your exact model.
Bird screens are purchased separately
Boiler · ECO Tec Series 3
Bird screens are not included with the vent terminations and must be bought separately. Part numbers are on the parts list at the end of the manual.
- Order bird screens separately before installing terminations.
- Install a bird screen in each vent and air termination.
Applies to: All direct vent terminations
Source: ECO Tec Series 3 Boiler Manual, p. 40, 43. Written in our own words; check the manual for your exact model.
Bird screens at vent terminations
Boiler · SVF Series 1
Each vent termination needs a bird screen from the vent manufacturer. Do not use a generic screen.
- Buy the bird screen from the vent or air piping supplier.
- Install one bird screen at each vent termination.
Applies to: All vent terminations
Source: SVF Series 1 Boiler Manual, p. 26. Written in our own words; check the manual for your exact model.
Bluetooth status and FCC/IC information
Boiler · ECO Tec Series 3
Bluetooth can be turned on or off, and the FCC and IC identifiers are shown on the Bluetooth screen.
- Swipe right from HOME.
- Press BLUETOOTH to view or change status.
- Read FCC and IC information on the same screen if needed.
Applies to: ECO Tec control with Bluetooth
Source: ECO Tec Series 3 boiler manual, p. 113. Written in our own words; check the manual for your exact model.
Boiler circulator relay rating
Boiler · SVF Series 1
The expansion module relay that drives the boiler pump has a 10 A maximum rating.
- Use external 120VAC single phase power for the pump, sized for the pump load.
- Interrupt the pump hot line or enable circuit at the EP7 rear terminal block.
- Keep the pump load within the 10 A relay limit.
Applies to: Boiler circulator wiring
Source: SVF Series 1 boiler manual, p. 49. Written in our own words; check the manual for your exact model.
Boiler information screen readouts
Boiler · ECO Tec Series 3
The information screen shows live status and temperatures. Items include the sequence status and active priority, each input status, 0-10V input value, pump and aux outputs, additional heat demand, combi DHW flow and temperature, outdoor temperature, system supply and return, boiler out and in, target temperature, and blower modulation rate. Some readouts appear only on combi models or when the feature is selected.
- Swipe left or press the right-side bubble next to the home symbol to open the boiler information screen.
- Check the status, input status and modulation rate when diagnosing operation.
Applies to: ECO Tec control, all models
Source: ECO Tec Series 3 boiler manual, p. 112. Written in our own words; check the manual for your exact model.
Boiler location and installation precautions
Boiler · SVF Series 1
Keep gas controls protected from dripping or spraying water. Never install on carpet, even over a foundation. Combustible flooring is allowed. Keep the area clear of combustible materials, gasoline and flammable liquids. In a garage, mount the boiler at the height required by the fuel gas code and protect it from vehicles.
- Check nearby water piping, venting, gas, electrical power and condensate drain location before placing the boiler.
- Keep combustion and ventilation air openings unblocked.
- Install in a garage only at the code-required height and protected from moving vehicles.
Applies to: SVF 1500-3000 Series 1
Source: SVF Series 1 Boiler Manual, p. 5-6. Written in our own words; check the manual for your exact model.
Boiler receptacle and output ratings
Boiler · Evergreen Pro Series 2
Electrical limits for the on-board receptacle and the 120 VAC outputs.
- The boiler right-side receptacle is rated 2.0 A max at 120 VAC. It can power a condensate pump.
- Each circulator output is rated 2.0 A max. The 120 VAC auxiliary outputs are also limited to 2.2 A.
- For any voltage other than 120 VAC, or for loads above these ratings, use an external relay.
Applies to: Evergreen Pro Series 2 boilers
Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 48. Written in our own words; check the manual for your exact model.
Boiler room negative pressure and exhaust fans
Boiler · SVF Series 1
The appliance space must never be under negative pressure unless all appliances are direct vent. Air openings must also handle the airflow of any exhaust fans or air movers that draw from the space.
- Size air openings for the boiler firing rate and for all exhaust fans or air movers drawing from the space.
- Do not let exhaust fans or mechanical ventilation pull the room into negative pressure.
Applies to: SVF 1500-3000 Series 1
Source: Weil-McLain SVF Series 1 boiler manual, p. 32, p. 38. Written in our own words; check the manual for your exact model.
Boiler water after water contact
Boiler · CGa, CGi, EG, PEG
Do not run the boiler if any part of the boiler, burner or controls has been sprayed or submerged. Saltwater or polluted water contact voids warranty. Electrical components or wiring contacted by water require boiler replacement.
- Do not operate the boiler if water has contacted any part of the boiler, burner or controls.
- Replace the boiler or completely repair and inspect it before operation.
- Replace the boiler if wiring or electrical components were in contact with water.
- Replace the boiler if it was contaminated with saltwater or polluted water.
Applies to: All listed boiler series
Source: Gas-Fired Boilers User Manual, p. 4. Written in our own words; check the manual for your exact model.
Boiler water chemistry and make-up water
Boiler · CGa, CGi, EG, PEG
Water chemistry should be checked at least annually. Fresh make-up water and oxygen shorten boiler life. Mineral buildup reduces heat transfer and causes failure.
- Have the boiler water chemistry checked at least once a year by a qualified technician.
- Repair leaks in the boiler or piping at once to stop make-up water.
- Do not use petroleum-based cleaning or sealing compounds.
- Do not use homemade cures or boiler patent medicines.
- Never use automotive or standard glycol antifreeze, including hydronic glycol.
- Do not add cold water to a hot boiler, because thermal shock can crack the heat exchanger.
Applies to: All listed boiler series
Source: Gas-Fired Boilers User Manual, p. 4. Written in our own words; check the manual for your exact model.
Boiler water chemistry and makeup water
Boiler · EG / PEG Series 7
Do not use petroleum-based cleaning or sealing compounds, which damage gaskets and seals. Do not use homemade cures or boiler patent medicines. Constant fresh makeup water shortens boiler life: mineral build-up overheats cast iron and oxygen causes internal corrosion. Repair leaks in the boiler or piping right away.
- Do not use petroleum-based cleaners or sealers in the boiler system.
- Do not add homemade cures or patent medicines.
- Repair leaks at once to limit makeup water.
Applies to: Water boilers
Source: EG / PEG Series 7 Boiler Manual, p. 6. Written in our own words; check the manual for your exact model.
Boiler water quality and system fill
Boiler · ECO Tec Series 3
The stainless steel heat exchanger needs water chemistry inside the manual limits. Scale, sediment, make-up water and oxygen all shorten boiler life.
- Flush the system thoroughly before connecting the boiler to remove sediment.
- Install a strainer or other sediment removal device if needed.
- Check water chemistry against the limits in the manual and add chemical treatment if needed (see page 130).
- Do not use petroleum-based cleaning or sealing compounds in the system.
- Repair leaks at once to limit make-up water.
- Use the boiler only in a closed-loop system.
- Never add cold water to a hot boiler, to avoid cracking the heat exchanger.
Applies to: ECO Tec Series 3 hydronic piping and fill
Source: ECO Tec Series 3 boiler manual, p. 6. Written in our own words; check the manual for your exact model.
Breeching installation rules
Boiler · EG / PEG Series 7
Sizing and slope rules for the breeching from the draft hood or damper outlet to the chimney or vent.
- Use breeching the same size as the draft hood or damper outlet.
- Run vertical to the outside where possible for best performance.
- For horizontal runs, slope upward at least 1/4 in. per lineal foot toward the chimney or vent.
- Support horizontal breeching with hangers to prevent sagging.
- Do not connect the breeching to any part of a mechanical draft system under positive pressure.
Applies to: All Series 7 boilers
Source: EG/PEG Series 7 boiler manual, p. 19. Written in our own words; check the manual for your exact model.
Built-in zone control: up to four inputs and four outputs
Boiler · ECO Tec
The boiler control runs up to four circulators without an external zone control. It supports up to four inputs and four outputs.
- Plan the zone wiring for up to four inputs and four outputs.
- Check each zone circulator output against the zone naming before finishing setup.
Applies to: ECO Tec Series 3 boilers with Unity 2.0 control
Source: ECO Tec Value Comparison Guide, p. 1-2. Written in our own words; check the manual for your exact model.
Carbon monoxide alarm and installer requirements
Boiler · ECO Tec Series 3
The installer must confirm a working CO alarm before the boiler is put into use.
- Confirm at least one carbon monoxide alarm is installed and working in the living space or home, per the alarm maker's instructions and local codes, before starting the boiler.
- Have the installer read all manual and shipped instructions before installing, and follow steps in the order given.
- Record the CP number on the installation certificate on page 186 if it is not already shown.
- Have the boiler serviced and inspected by a qualified technician at least once a year.
Applies to: Installation and annual service
Source: ECO Tec Series 3 boiler manual, p. 6. Written in our own words; check the manual for your exact model.
Carbon monoxide detector
Boiler · Ultra Series 4
A CO detector on the same circuit as the boiler is strongly recommended. The installer must confirm at least one CO alarm is installed and working in the living space before the boiler is put into service.
- Install a CO alarm in the living space per the alarm maker's instructions and local codes.
- Confirm the alarm works before starting the boiler.
Applies to: Ultra Series 4 boilers
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 4. Written in our own words; check the manual for your exact model.
Ceramic fiber handling
Boiler · Ultra Series 4
The boiler contains ceramic fiber materials that need careful handling.
- Read the ceramic fiber warning on page 109 before handling or disposing of ceramic fiber materials.
- Handle insulation and cover plate materials with care.
Applies to: All Ultra Series 4 boilers
Source: Ultra Series 4 boiler manual, p. 125. Written in our own words; check the manual for your exact model.
Ceramic fiber handling during cover plate and burner work
Boiler · ECO Tec Series 3
Cover plate components, refractory insulation and gaskets contain ceramic fiber that can be hazardous to breathe.
- Avoid breathing dust and avoid skin and eye contact.
- Wear an N95 NIOSH-certified respirator or the respirator required for the site.
- Wear long-sleeved loose clothing, gloves and eye protection.
- Handle carefully to limit dust from abrasion.
- Place removed refractory in a sealed plastic bag for disposal.
- Wash contaminated clothes separately and rinse the washer thoroughly.
Applies to: ECO Tec Series 3 gas boilers
Source: ECO Tec series 3 boiler manual, p. 139. Written in our own words; check the manual for your exact model.
Ceramic fiber materials inside the boiler
Boiler · ECO Tec series 3
The boiler contains ceramic fiber materials. Handle them carefully and follow the handling instructions on page 139.
- Follow the ceramic fiber handling instructions on page 139 before handling these materials.
Applies to: ECO Tec series 3 80/110/150/199
Source: ECO Tec Series 3 boiler manual, p. 169. Written in our own words; check the manual for your exact model.
CGa component locations
Boiler · CGa
Numbered components on the CGa boiler diagram.
- 1) Gas valve
- 2) Pilot burner (not shown)
- 3) Main burners
- 4) Gas manifold/orifices
- 5) Control module
- 7) Vent damper
- 8) Water temperature/LWCO sensor
- 9) Transformer
- 10) Spill switch
- 12) Rollout thermal fuse element
- 13) Draft hood
- 14) Circulator
- 15) Relief valve
- 16) Gauge (pressure/temperature)
- 17) Drain valve
Applies to: CGa boiler
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 13. Written in our own words; check the manual for your exact model.
CGi component locations
Boiler · CGi
Numbered components on the CGi boiler diagram.
- 1) Gas valve
- 2) Pilot burner (not shown)
- 3) Main burners
- 4) Gas manifold/orifices
- 5) Control module
- 6) Inducer
- 8) Water temperature/LWCO sensor
- 9) Transformer
- 11) Air pressure switch
- 12) Rollout thermal fuse element
- 14) Circulator
- 15) Relief valve
- 16) Gauge (pressure/temperature)
- 17) Drain valve
Applies to: CGi boiler
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 14. Written in our own words; check the manual for your exact model.
Check domestic hot water temperatures
Boiler · ECO Tec Series 3
Check the thermostatic mixing valve at all domestic hot fixtures to confirm correct temperatures, using the procedure on page 137. If a recirculation loop is installed, confirm the recirculation pump works. Also check the aquastat, timer or occupancy sensor if one is used.
- Check the thermostatic mixing valve at each domestic hot fixture per page 137.
- Confirm the recirculation pump runs, if a loop is installed.
- Check the aquastat, timer or occupancy sensor if used.
Applies to: All ECO Tec Series 3 models with domestic hot water
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
Check system status summary screen
Boiler · ECO Tec Series 3
The summary screen shows current boiler operation. Use it to confirm the settings you chose match what is installed.
- Swipe left or press the right bubble beside the home symbol to open the summary screen.
- Check status, demand, input status, pump/aux state, outdoor temperature, supply/return and boiler out/in temperatures, and modulation rate.
- If any value does not match the setup, press that item and correct it.
Applies to: ECO Tec Control, ECO Tec Series 3
Source: ECO Tec Series 3 boiler manual, p. 97. Written in our own words; check the manual for your exact model.
Check the boiler relief valve
Boiler · ECO Tec Series 3
Inspect the relief valve and lift the lever to confirm flow. Before lifting the lever, make sure a discharge line is connected to a safe drain, because hot water will come out. If no water flows, the valve is inoperative and the boiler must stay shut down until a new valve is installed. Relief valves must be inspected by a licensed plumbing contractor or authorized inspection agency at least every three years, and the lever must be operated at least once a year. If the valve weeps or will not seat, replace it, but first confirm the cause is the valve and not over-pressurization from a waterlogged or undersized expansion tank.
- Confirm the discharge line is piped to a safe disposal point.
- Lift the lever and check that water flows.
- If no water flows, shut the boiler down and replace the relief valve.
- If the valve weeps or will not seat, check the expansion tank before replacing the valve.
- Remind the owner that the lever must be operated at least once a year.
Applies to: Boiler relief valve, all ECO Tec Series 3 models
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
Check the combi 3-way valve and DHW function
Boiler · ECO Tec Series 3
Applies to combi models only. Cycle the 3-way valve by calling for space heat, then calling for domestic hot water at a faucet. The valve and boiler should switch from space heating to domestic and hot water should be delivered. If the change does not happen, run the 3-way valve test listed on page 143. Also check for water leaks at the 3-way valve, the brazed plate and the brazed plate manifold fittings.
- Start a space heating call to the boiler.
- Open a domestic hot water faucet to create a DHW call.
- Confirm the valve and boiler operation change to domestic and hot water is delivered.
- If the change does not happen, run the 3-way valve test on page 143.
- Check the 3-way valve, brazed plate and manifold fittings for leaks.
Applies to: Combi models only
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
Check U-Control date and time
Boiler · Ultra Series 4
Confirm the time on the U-Control display is correct.
- Check the time shown on the U-Control display.
- If the time is wrong, set the correct date and time as shown on pages 10 and 11 of the manual.
Applies to: Ultra Series 4 U-Control display
Source: Ultra Series 4 user's information manual, p. 7. Written in our own words; check the manual for your exact model.
Check valve on DHW mixing valve outlet
Boiler · ECO Tec Series 3
Reverse flow can open the flow switch after a draw ends, so a check valve is required.
- Install a field supplied check valve on the outlet of the mixing valve.
- Confirm the flow switch does not activate after the cold draw ends.
Applies to: Combi DHW piping
Source: ECO Tec Series 3 boiler manual, p. 49. Written in our own words; check the manual for your exact model.
Choose operating instructions by gas valve
Boiler · CGa, CGi, EG, PEG
The operating instructions depend on the boiler series and the gas valve installed. Spark-ignited pilot boilers are covered in this manual.
- Identify the boiler model and series from the rating label.
- For CGa-25 to CGa-8, EG-30 to EG-75 and PEG-30 to PEG-65 with spark-ignited pilot and Resideo VR8204 or VR8304 gas valve, use the operating instructions on p. 6.
- For LGB Series 2, use the instructions on p. 7.
- For LGB Series 3, use the instructions on p. 8.
Applies to: CGa, EG, PEG, LGB spark-ignited pilot models
Source: Gas-Fired Boilers User Manual, p. 5. Written in our own words; check the manual for your exact model.
Circulator exercising
Boiler · Evergreen Series 2
After 72 hours of boiler inactivity, the selected circulator outputs energize briefly.
- Select the circulator outputs to exercise in Pump Settings.
Applies to: Evergreen Series 2 pump settings
Source: Series 2 Advanced Manual, p. 14. Written in our own words; check the manual for your exact model.
Circulator LED status
Boiler · ECO Tec Series 3
The circulator LED shows its operating state. Orange means on, flashing white means air bound or cavitation, red means blocked, and off means the circulator is off.
- If the LED is flashing white, purge air from the system and check for cavitation.
- If the LED is red, check for a blockage in the circulator.
Applies to: Internal Taco 0015e3 circulator
Source: ECO Tec Series 3 boiler manual, p. 48. Written in our own words; check the manual for your exact model.
Circulator lubrication
Boiler · Ultra Series 4
The Ultra circulator is water-lubricated and needs no oil. Other circulators in the system may need oil.
- Do not oil the Ultra circulator; it is water-lubricated.
- Check other system circulators and oil only those that need it, following the circulator maker's instructions.
- Do not over-oil; over-oiling will damage the circulator.
Applies to: Ultra Series 4 boilers and system circulators
Source: Ultra Series 4 boiler manual, p. 125. Written in our own words; check the manual for your exact model.
Circulator output load limits
Boiler · SVF Series 1
Each 120VAC pump output handles only 2.2 A. Larger circulators need a relay or starter, with only the relay coil wired to the boiler terminal.
- Check the circulator amp rating before connecting it to Output 1, 2 or 3.
- If the circulator draws more than 2.2 A, install a circulator relay or starter.
- Connect only the 120VAC coil to the boiler circulator terminals.
- Use an isolation relay if a device needs a different voltage or an isolated contact.
Applies to: Output 1, 2 and 3 circulator and auxiliary loads
Source: SVF Series 1 boiler manual, p. 58. Written in our own words; check the manual for your exact model.
Clean the DHW external filter and combi manifold filters
Boiler · ECO Tec Series 3
Clean the domestic inlet water filter installed in the piping near the boiler, following the manufacturer's recommended cleaning procedure. On combi models, also clean the combi manifold DHW flow switch filter and the bypass filter. The DHW brazed plate should be cleaned annually, and more often if water quality requires it.
- Clean the domestic inlet filter in the piping near the boiler using the filter maker's procedure.
- On combi models, clean the DHW flow switch filter and bypass filter per page 157.
- Clean the DHW brazed plate annually per page 154, or more often for poor water quality.
Applies to: Combi models for manifold filters; all models for the external inlet filter
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
Combi-only components
Boiler · ECO Tec Series 3
These parts are present only on Combi models (DHW side of the boiler).
- Brazed plate heat exchanger (item 33) transfers heat from boiler water to domestic water.
- DHW outlet temperature sensor (item 34) controls input based on how close the water is to set point.
- DHW 3-way valve (item 35) and actuator (item 36) route boiler water through the brazed plate or bypass it to the heating system.
- DHW flow sensor (item 37) starts the boiler and lets it modulate when flow of 0.5 GPM or more is detected.
- DHW inlet and outlet pipes (items 39 and 40): 199 uses 3/4 inch NPT; 150 and 110 use 1/2 inch NPT.
Applies to: ECO Tec Series 3 Combi models
Source: ECO Tec Series 3 boiler manual, p. 8-10. Written in our own words; check the manual for your exact model.
Combustion air and surge protection
Boiler · ECO Tec Series 3
Keep combustion air clean and protect the control from power surges.
- Do not place the combustion air intake where contamination of the combustion air is possible.
- Install surge protection on the boiler power supply to reduce the chance of control board damage.
Applies to: ECO Tec Series 3 installation
Source: ECO Tec Series 3 boiler manual, p. 6. Written in our own words; check the manual for your exact model.
Combustion air and vent piping rules at the boiler
Boiler · ECO Tec Series 3
The air inlet must be piped unless a Weil-McLain Direct Exhaust kit is used and its requirements are met. The air inlet connection at the boiler is 3" PVC only. The vent may use 3" PVC, CPVC, stainless or polypropylene, with approved adapters.
- Pipe combustion air to the boiler air intake, not a room air opening, unless using the Direct Exhaust kit.
- Use 3" PVC at the air inlet connection.
- Use a 3" transition at the boiler if running 2" pipe.
- Use only approved adapters; a PP adapter with its own seal that interferes with the boiler seal must not be used.
- Use a tapered reducer with a 3" PVC nipple (at least 6" long) for 3" to 2" transitions. Do not use a bushing.
- Use only the approved parts listed in the parts section (Figure 152, page 171).
Applies to: ECO Tec Series 3 vent and air piping
Source: ECO Tec series 3 boiler manual, p. 26. Written in our own words; check the manual for your exact model.
Concentric termination warnings
Boiler · ECO Tec Series 3
Do not alter or cut the concentric assembly. Blocked air passages stop the boiler, and a cut or altered assembly can allow flue gas recirculation and toxic emissions. Pipes must butt correctly at both ends to prevent recirculation.
- Shorten inner and outer pipes only if both still butt correctly at each end.
- Protect the exposed end of the assembly with wrap while it is fed through the wall to keep debris out.
- Use the maker's PVC adapter if connecting AL29-4C stainless vent to a PVC concentric attachment.
Applies to: Concentric sidewall termination
Source: ECO Tec Series 3 boiler manual, p. 36. Written in our own words; check the manual for your exact model.
Condensate drain trap
Boiler · ECO Tec Series 3
The condensate trap is field installed and connects to the boiler condensate tube at the bottom of the boiler.
- Connect the field-supplied condensate drain trap assembly to the condensate tube at the bottom of the boiler (see installation section).
Applies to: ECO Tec Series 3 installation
Source: ECO Tec Series 3 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Condensate is acidic
Boiler · Ultra Series 4
Condensate typically has a pH of 3.2 to 4.5. Install a neutralizing filter where local code requires it. The Weil-McLain neutralizer kit is listed in the replacement parts section.
- Check local code for neutralizer requirements.
- Fit the Weil-McLain neutralizing kit if required.
Applies to: All Ultra models with condensate drain
Source: Weil-McLain Ultra Series 4 boiler manual, p. 28. Written in our own words; check the manual for your exact model.
Condensate line requirements
Boiler · SVF Series 1
Keep condensate flowing freely or the boiler can lock out.
- Use 3/4 in PVC or CPVC pipe to a drain or condensate pump.
- Use materials that meet ASTM D1785, F441 or D2665, and cement that meets ASTM D2564 or F493. In Canada use CSA or ULC certified pipe, fittings and cement.
- Keep the line clear so condensate cannot freeze or back up into the boiler.
- Expect acidic condensate (about pH 3.2 to 4.5); install a neutralizer where local code requires it.
- Keep the trap float in place to prevent flue gas leakage through the drain.
Applies to: SVF 1500-3000
Source: SVF Series 1 boiler manual, p. 46. Written in our own words; check the manual for your exact model.
Control display status screens
Boiler · Evergreen Series 2
The Status screen shows the active sequence of operation and its priority. Other display screens show live readings: 0-10V input value from an external device; inputs 1 to 4 with assignment, custom name and status; which aux/pump outputs are on; Additional Heat Demand on or off (only if a priority uses it); outdoor temperature (only if used); system supply and return temperatures (only if used); target temperature of the active priority; boiler out and boiler in temperatures; and blower modulation rate.
Applies to: Evergreen Pro control display, Figure 9
Source: Weil-McLain Condensing Gas Boiler User's Information Manual, p. 11. Written in our own words; check the manual for your exact model.
Control feature summary
Boiler · ECO Tec Series 3
Options available in the control: PREHEAT (Off, Economy, High Performance), ECO BOOST (recharges boiler water once after a combi DHW draw), blower calibration (faster purge speeds), Fahrenheit or Celsius units, manual reset high limit, and daylight saving time.
- Select PREHEAT mode if faster combi DHW response is needed.
- Enable ECO BOOST if the burner should keep firing after combi flow ends to recover heat exchanger temperature.
- Use blower calibration to fine-tune purge speed if time to heat delivery is too long.
Applies to: ECO Tec Series 3 control
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 85. Written in our own words; check the manual for your exact model.
DHW piped in system: no DHW redundancy
Boiler · Evergreen Series 2
When DHW is supplied from boiler 2 in a direct-piped layout, DHW is lost if boiler 2 is not running.
- Tell the owner that DHW can only be supplied when Boiler 2 is operational.
- Do not rely on this layout for DHW backup.
Applies to: Multi-boiler Example A piping (DHW directly connected)
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 19. Written in our own words; check the manual for your exact model.
DHW priority setup
Boiler · ECO Tec Series 3
Priority 1 is the default for DHW and turns off lower priorities during DHW calls. MAX ON TIME can limit that. Use Priority 2 or 3 for DHW if DHW should not take priority. Overriding outdoor reset by setting DHW mode for space heating may violate Section 303 of the 2007 Energy Act (see page 184 for exemptions).
- Wire the DHW aquastat to Input 1 and assign it to Priority 1 for DHW priority.
- On combi models, use INPUT2/PRIORITY 2 for an indirect DHW system.
- Adjust MAX ON TIME if the DHW priority call must be shortened.
- Do not set DHW mode to override outdoor reset on a space heating system.
Applies to: Direct connect and primary/secondary piping with DHW tank
Source: ECO Tec Series 3 boiler manual, p. 56, p. 60. Written in our own words; check the manual for your exact model.
DHW priority turns off space heating
Boiler · Ultra Series 4
When DHW is priority 1, the U-Control turns off space heating and the boiler circulator during DHW heating. An optional timeout setting can override this. The flow/check valve on the boiler outlet stops gravity circulation during DHW heating.
- Set the DHW input to priority 1 when space heating should pause during DHW heating.
- Set the optional timeout if space heating must continue during DHW heating.
Applies to: Systems with indirect DHW tank
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 52. Written in our own words; check the manual for your exact model.
Direct vent air duct installation
Boiler · SVF Series 1
For direct vent, combustion air is ducted directly from outside to the boiler air intake fitting. Sidewall or vertical direct vent options are available.
- Duct combustion air from outside directly to the boiler air intake fitting.
- Keep boiler room air openings separate and sized for other appliances and ventilation (see Figure 33).
Applies to: SVF 1500-3000 Series 1, direct vent
Source: Weil-McLain SVF Series 1 boiler manual, p. 38. Written in our own words; check the manual for your exact model.
Disconnect power before maintenance
Boiler · Ultra Series 4
Electrical shock hazard. All electrical power must be off before maintenance.
- Disconnect all electrical power to the boiler before any maintenance procedure.
Applies to: All Ultra Series 4 boilers
Source: Ultra Series 4 boiler manual, p. 125. Written in our own words; check the manual for your exact model.
Display backlight colours
Boiler · EG, PEG, Series 7
The two-line display backlight shows operating state. No backlight means standby. Green means powered on or buttons in use, and it turns off after 20 minutes without button activity. Blue means initialization or a CH call. Purple means a DHW call. Red means an unconfigured control or an active fault.
- Check backlight colour first to identify the operating state.
- On a red fault, use the Advanced Menu to view parameter states while the fault is active.
Applies to: Unity-CI control, EG / PEG Series 7 boilers
Source: EG / PEG Series 7 boiler manual, p. 39. Written in our own words; check the manual for your exact model.
Display banner colour meanings
Boiler · ECO Tec Series 3
Blue banner means a heating call or a maintenance screen. Red means an error or limit event. The warm weather shut down (WWSD) blocks space heating above the set outdoor temperature but does not block DHW.
- If the banner is red, check the error or limit event on the display before resetting.
- If the banner is blue and the maintenance screen toggles in standby, the maintenance timer has run out. The boiler still operates normally.
- If space heating does not fire on a mild day, check whether WWSD is active and whether the outdoor temperature is above the WWSD setting.
Applies to: ECO Tec Series 3 control display
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 84. Written in our own words; check the manual for your exact model.
Do not add cold water to a hot boiler
Boiler · EG / PEG Series 7
Adding cold water to a hot boiler causes thermal shock, which can crack the heat exchanger.
- Do not add cold water to a hot boiler.
Applies to: Water boilers
Source: EG / PEG Series 7 Boiler Manual, p. 6. Written in our own words; check the manual for your exact model.
Do not adjust or measure gas valve outlet pressure
Boiler · Ultra Series 4
The gas valve outlet pressure is factory set for natural gas and propane and must not be changed in the field. Throttle screw adjustment is only for qualified technicians with calibrated instruments.
- Do not measure or change gas valve outlet pressure.
- Use the throttle screw adjustment only if combustion is outside range and only with calibrated combustion test instruments.
Applies to: All Ultra Series 4 gas boilers
Source: Weil-McLain Ultra Series 4 boiler manual, p. 37-40. Written in our own words; check the manual for your exact model.
Do not override outdoor reset for space heating
Boiler · Ultra Series 4
Setting the control to DHW mode when the system is meant for space heating may violate Section 303 of the 2007 Energy Act. See page 137 for compliance information and exemptions.
- Keep the outdoor reset active when the system is intended for space heating.
- Check page 137 of the manual before changing DHW mode for a space heating system.
Applies to: All Ultra boilers with outdoor reset
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 52-55. Written in our own words; check the manual for your exact model.
Do not power external devices from 24V transformer
Boiler · SVF Series 1
The 24V transformer in the boiler is only for listed boiler functions.
- Do not use the 24V transformer output to power any external device not listed in the manual.
Applies to: All SVF boilers
Source: SVF Series 1 boiler manual, p. 49. Written in our own words; check the manual for your exact model.
Do not service the boiler without a maintenance kit
Boiler · ECO Tec series 3
Have the correct ECO Tec maintenance kit on hand before accessing or taking apart the boiler. Replace any damaged components and use only parts intended for this boiler.
- Have the model-specific maintenance kit on hand before starting work.
- Replace components that are damaged or that must be removed to access parts.
Applies to: ECO Tec series 3 80/110/150/199
Source: ECO Tec Series 3 boiler manual, p. 169. Written in our own words; check the manual for your exact model.
Do not use closed-type tank with AQUA PLUS
Boiler · Ultra Series 4
The automatic air vent on the AQUA PLUS water heater removes air from the system, which waterlogs a closed-type expansion tank.
- Use only a diaphragm or bladder type expansion tank suitable for automatic air vent applications.
Applies to: Systems with AQUA PLUS water heaters
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 53. Written in our own words; check the manual for your exact model.
Domestic hot water scald and T&P relief valve warning
Boiler · EG, PEG
Domestic hot water above 130°F can scald. A temperature and pressure (T&P) relief valve is required for protection against excessive temperature and pressure. Automatic mixing valves must follow the valve maker's instructions.
- Hot water above 130°F scalds quickly
- Children, elderly or physically handicapped persons are at higher risk
- Set domestic hot water to 130°F or less, or the lowest practical setting.
- If installing an automatic mixing valve, follow the valve maker's selection and installation instructions.
- Check water temperature immediately after the first heating cycle and after any adjustment.
- Install a T&P relief valve; it is required.
Applies to: EG / PEG boilers with domestic hot water
Source: EG / PEG Series 7 boiler manual, p. 64. Written in our own words; check the manual for your exact model.
Domestic hot water scald protection and T&P relief valve
Boiler · EG, PEG
Hot water can scald. Set the domestic hot water temperature with scald risk in mind and make sure a temperature and pressure relief valve is installed.
- Use a domestic hot water temperature of 130 F or less, which the manual cites as the Consumer Product Safety Commission and some state recommendation.
- If an automatic mixing valve is installed, select and install it per the valve maker's instructions and local standards.
- Use the lowest practical temperature setting for the building's occupants.
- Check the water temperature at a tap right after the first heating cycle and after any adjustment.
- Confirm a temperature and pressure (T&P) relief valve is installed; the manual says this is required.
Applies to: EG and PEG Series 7 boilers with domestic hot water
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 64. Written in our own words; check the manual for your exact model.
Domestic water filtration and hardness
Boiler · ECO Tec Series 3
Filtering and softening protect the DHW flow sensor and brazed plate heat exchanger.
- Install a 25 micron or finer filter on the cold line feeding the combi boiler.
- Use a finer filter or water softener in harsh water conditions.
- Install a water softener if water hardness is above 50 ppm calcium carbonate.
- Install drain and isolation valves on the DHW inlet and outlet so the heat exchanger can be flushed.
Applies to: Combi DHW supply
Source: ECO Tec Series 3 boiler manual, p. 49. Written in our own words; check the manual for your exact model.
EG and PEG component locations (water and steam diagram)
Boiler · EG, PEG
Numbered components on the EG/PEG diagram. Items 13 (low water cutoff) and 19 (gauge glass) apply to steam boilers only. The page labels EG Water and PEG/EG Steam are not clearly matched to this diagram.
- 1) Gas valve
- 2) Pilot burner
- 3) Main burners
- 4) Gas manifold/orifices
- 5) Control module
- 7) Vent damper
- 9) Transformer
- 10) Spill switch
- 12) Rollout thermal fuse element
- 13) Low water cutoff (steam boilers)
- 14) Limit control(s)
- 15) Draft hood
- 18) Gauge (pressure or pressure/temperature)
- 19) Gauge glass (steam only)
Applies to: EG and PEG boilers
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 15. Written in our own words; check the manual for your exact model.
EG and PEG wiring and harness component list
Boiler · EG, PEG
Unlabeled component list on the same page as the EG/PEG diagram. The model it applies to is not stated on the page.
- 1) Vent damper
- 2) Draft hood
- 3) Spill switch wires
- 4) Circulator (by others)
- 5) Junction box
- 6) Transformer
- 7) Wiring harness
- 8) Rollout thermal fuse element
- 9) Main burners
- 10) Gas valve
- 11) Ignition control
- 12) Damper harness
Applies to: Boiler model not stated on page; likely EG/PEG
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 15. Written in our own words; check the manual for your exact model.
Electrical entrances and wiring knockouts
Boiler · ECO Tec Series 3
Knockouts are separated by voltage type. Keep line and low voltage wiring in their own areas.
- Use the front left knockouts for line voltage and external pump voltage only; they lead to the high voltage junction box (item 20).
- Use the bottom right and top right knockouts for low voltage wiring only.
- Seal all wiring entrances.
Applies to: Field wiring
Source: ECO Tec Series 3 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Electrical safety before wiring
Boiler · SVF Series 1
Power must be off before any wiring work, and the boiler must be grounded and bonded.
- Turn off electrical power at the service entrance panel before making connections.
- Wire to N.E.C. Class 1 and use 105 °C wire if original wire is replaced.
- Electrically ground and bond the boiler per NEC ANSI/NFPA 70 or CSA C22.1 and local authority requirements.
- Provide a fused disconnect or service switch sized to code.
Applies to: All SVF boiler wiring
Source: SVF Series 1 boiler manual, p. 49. Written in our own words; check the manual for your exact model.
Energy saving reset override conditions
Boiler · EG, PEG, Series 7
The override that lets boiler water temperature track the heating load may be used only when at least one of these is true: an external energy management system reduces water temperature with load, the boiler is part of a modular or multiple system with 300,000 BTU/hr or more total input, or the boiler has a tankless coil.
- Confirm one of the listed conditions applies before using the override.
Applies to: EG water boilers, DOE compliance
Source: EG / PEG Series 7 boiler manual, p. 39. Written in our own words; check the manual for your exact model.
Energy-saving reset override: when it may be used
Boiler · ECO Tec Series 3
The boiler lowers water temperature as the heating load drops, per the 2007 Energy Act. The override is only for use when at least one of these is true: an external energy management system lowers water temperature with load; the boiler does no space heating; the boiler is part of a modular or multiple system rated 300,000 BTU/hr or more total input. (The tankless coil option does not apply to ECO Tec.)
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 184. Written in our own words; check the manual for your exact model.
Energy-saving temperature reduction override
Boiler · ECO Tec Series 3
The boiler reduces water temperature as heating load drops (Section 303, 2007 Energy Act). The override that bypasses this is for use only in the listed cases.
- Use the override only if an external energy management system already lowers boiler water temperature as load drops.
- Use it if the boiler is not used for space heating.
- Use it if the boiler is part of a modular or multiple boiler system with total input of 300,000 BTU/hr or more.
- Do not use the override in any other case. The tankless coil condition does not apply to ECO Tec.
Applies to: ECO Tec 80/110/150/199 Series 3
Source: ECO Tec Series 3 boiler manual, p. 184. Written in our own words; check the manual for your exact model.
Energy-saving water temperature override limits
Boiler · EG, PEG
The boiler reduces water temperature as heating load drops. The override is meant for external energy management systems and must only be used if one of the listed conditions is true.
- Use the override only if an external energy management system reduces boiler water temperature as load drops.
- Use the override only if the boiler is part of a modular or multiple boiler system of 300,000 BTU/hr or more.
- Use the override only if the boiler is equipped with a tankless coil.
Applies to: EG / PEG water boilers
Source: EG / PEG Series 7 boiler manual, p. 58. Written in our own words; check the manual for your exact model.
External limit wiring for lockout and auto reset
Boiler · Ultra Series 4
External limits can be added to the U-Control. Manual reset limits require a manual reset from the control even after the limit closes. Automatic reset limits reset the control when the limit closes again. The factory jumper must be removed when these terminals are used.
- For manual reset limits, wire the external limit across P13 terminals 1 and 2 and remove the factory jumper.
- For automatic reset limits, wire the external limit across P13 terminals 3 and 4 and remove the factory jumper.
- After a manual reset limit opens, the control locks out and activates the alarm contacts until reset.
Applies to: Ultra U-Control external limits
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98. Written in our own words; check the manual for your exact model.
Flood-damaged or water-contacted components
Boiler · EG / PEG Series 7
Do not run a boiler, burner or controls that were sprayed with or submerged in water until the boiler is replaced or fully repaired and checked. Equipment exposed to saltwater is no longer covered by warranty and should be replaced. If any electrical component or wiring touched water or may have, replace the boiler.
- Do not operate a boiler or controls that were submerged or sprayed with water.
- Replace boilers exposed to saltwater or polluted water.
- Replace the boiler if any electrical component or wiring contacted water.
Applies to: Boilers exposed to water
Source: EG / PEG Series 7 Boiler Manual, p. 6. Written in our own words; check the manual for your exact model.
Four-zone space heating without DHW (Example A)
Boiler · ECO Tec Series 3
If DHW is not used, the boiler can run a fourth space heating zone from Input/Output 1.
- Set Input/Output 1 exactly the same as Input/Output 2.
- Assign Input/Output 1 to PRIORITY 2.
- Wire the fourth zone thermostat to J17 terminals 1 and 2.
- Wire the fourth zone circulator to T2 terminals 4, 5 and 6.
Applies to: ECO Tec Series 3, Express Setup Example A
Source: ECO Tec Series 3 boiler manual, p. 98. Written in our own words; check the manual for your exact model.
Freeze protection and antifreeze
Boiler · Evergreen Series 2
Do not use automotive or standard glycol antifreeze, including hydronic glycol. Use only freeze-protection fluids listed in the boiler manual. In Massachusetts, a reduced pressure backflow preventer is required if antifreeze is used.
- Thoroughly clean and flush any old system that used glycol before installing the new boiler.
Applies to: Evergreen boiler hydronic system
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 4. Written in our own words; check the manual for your exact model.
Freeze protection circulators
Boiler · Evergreen Series 2
Selected circulators run when the boiler in or boiler out sensor drops below 40°F. Turning off the boiler circulators disables this feature.
- Select which circulators should run for freeze protection in Pump Settings.
- Keep boiler circulators on where freeze protection is required.
Applies to: Evergreen Series 2 pump settings
Source: Series 2 Advanced Manual, p. 14. Written in our own words; check the manual for your exact model.
Freeze protection fluids
Boiler · ECO Tec Series 3
Standard or automotive glycol damages the boiler and system. Only hydronic freeze protection fluids are allowed.
- Do not use automotive or standard glycol antifreeze.
- Use only freeze protection fluids made for hydronic systems and follow the fluid maker's rules.
- Thoroughly clean and flush any old system that used glycol before installing the new boiler.
- Use only products listed by WM Technologies for this boiler (see page 109).
Applies to: ECO Tec Series 3 hydronic systems
Source: ECO Tec Series 3 boiler manual, p. 6. Written in our own words; check the manual for your exact model.
Freeze protection fluids and cleaners
Boiler · Ultra Series 4
Never use automotive or standard glycol antifreeze. Use only hydronic freeze-protection fluids recommended in the manual (see page 140). Do not use petroleum-based cleaning or sealing compounds, as they damage gaskets and seals.
- Use only hydronic-rated freeze-protection fluid listed in the manual.
- Clean and flush any replacement system that used glycol before installing the new boiler.
Applies to: Ultra Series 4 boilers
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 4. Written in our own words; check the manual for your exact model.
Freezing condensate and exposed vent length
Boiler · Ultra Series 4
Long exposed vent sections can freeze condensate and shut the boiler down.
- Keep exposed vent length within the Figure 15 and Figure 21 maximums.
- In extremely cold climates install an insulated chase around the vent piping, allowing inspection, with insulation protected from water.
- Locate terminations away from prevailing winds that could freeze condensate on surfaces or plants.
Applies to: Ultra outdoor vent and air terminations
Source: Weil-McLain Ultra Series 4 boiler manual, p. 20-21. Written in our own words; check the manual for your exact model.
Freezing risk during power loss
Boiler · CGa, CGi, EG, PEG
Power outages or electrical failures in cold weather can freeze plumbing and cause water damage within hours.
- Consider a security system that runs during power outages, senses low temperature and starts a protective action.
- Consult the boiler contractor about preventive measures for unattended buildings.
Applies to: All listed boiler series
Source: Gas-Fired Boilers User Manual, p. 4. Written in our own words; check the manual for your exact model.
Front door must be installed during operation
Boiler · ECO Tec Series 3
The jacket door must be in place and fastened during operation. It is only removed for inspection and testing.
- Reinstall the front door after service and fasten it securely to the frame.
- Do not run the boiler with the door off except for inspection or testing.
Applies to: ECO Tec 80/110/150/199
Source: ECO Tec Series 3 Boiler Manual, p. 22-23. Written in our own words; check the manual for your exact model.
Front door security check
Boiler · Ultra Series 4
The front door must seal all around and stay fastened so the boiler does not draw room air from inside the boiler room.
- Visually check that the front door is sealed around its full perimeter.
- Make sure the two lower thumb screws are tight.
- Reinstall the jacket front door after any service.
- If the door does not sit correctly or the gaskets are damaged, contact the installer or technician immediately.
Applies to: Ultra Series 4 boiler front door and jacket
Source: Ultra Series 4 user's information manual, p. 6. Written in our own words; check the manual for your exact model.
Fuel shipping setting and propane orifice
Boiler · Ultra Series 4
Ultra boilers ship set for natural gas only. The Ultra-80LP is propane-ready. Any other model needs the propane orifice installed before it runs on propane.
- Confirm the boiler fuel before firing.
- For propane, install the propane orifice first (see page 48).
Applies to: All Ultra models; Ultra-80LP is propane-ready
Source: Weil-McLain Ultra Series 4 boiler manual, p. 29. Written in our own words; check the manual for your exact model.
Gas leak testing and pipe dope
Boiler · Ultra Series 4
Use bubble test only and never an open flame. Above 13 in w.c. test pressure, disconnect the boiler and gas valve from the line. Below 13 in w.c., close the manual main shutoff valve.
- Use a bubble test on all gas connections.
- For pressure tests below 13 in w.c., close the manual main shutoff valve.
- For pressure tests above 13 in w.c., disconnect the boiler and gas valve from the supply piping.
- Use pipe dope compatible with propane, applied sparingly only to the male threads so it does not block gas flow.
Applies to: Gas piping at Ultra boilers
Source: Weil-McLain Ultra Series 4 boiler manual, p. 29. Written in our own words; check the manual for your exact model.
Gas line sizing reference
Boiler · ECO Tec Series 3
Boiler gas connection is 1/2 in NPT. Size the line from meter to boiler for total input of all connected appliances. Use the capacity table for natural gas. For other requirements refer to ANSI Z223.1/NFPA 54 or CAN/CSA B149.1/B149.2.
- Size the gas line for total connected input.
- Use the equivalent length from the fitting table to convert fittings to pipe length.
Applies to: ECO Tec gas piping
Source: ECO Tec Series 3 Boiler Manual, p. 24. Written in our own words; check the manual for your exact model.
Gas supply piping cautions
Boiler · SVF Series 1
Key gas piping rules from the install section.
- Install a union for servicing where needed and a manual shutoff valve within 6 ft of the boiler.
- In Canada, the installer must identify the manual gas valve.
- Support gas piping with hangers, not with the boiler or its accessories.
- Use two wrenches when tightening gas piping at the boiler so the boiler connection does not turn.
- Use pipe dope that works with propane, applied lightly to male threads only.
- These boilers ship set for natural gas only. Install the propane conversion kit before connecting propane (see page 12).
- Use a 100% lock-up gas pressure regulator (ANSI Z21.80) if inlet pressure can exceed 14 in w.c.
- Set the lock-up regulator for inlet pressure below 10 in w.c. with the boiler at minimum input so there is margin under the high gas pressure switch.
Applies to: SVF 1500-3000
Source: SVF Series 1 boiler manual, p. 47. Written in our own words; check the manual for your exact model.
Gas valve and venturi operating principle
Boiler · Ultra Series 4
Gas flows only when air is moving through the venturi. The gas valve senses venturi vacuum. Flue gas dual sensor shuts the boiler down if flue temperature is too high.
- If there is no air flow through the venturi, gas will not flow. Check blower operation and air path first.
- If the flue gas dual sensor trips, check flue temperature and venting before resetting.
Applies to: Ultra-80 through Ultra-399 gas valve and venturi
Source: Ultra Series 4 gas-fired water boiler manual, pp. 44, 46. Written in our own words; check the manual for your exact model.
Glycol is a fire hazard
Boiler · EG / PEG Series 7
Glycol is flammable when hot. Do not store glycol near the boiler or any ignition source. Check the system and boiler often for leaks and fix any leak right away so glycol does not build up.
- Keep glycol stored away from the boiler and any ignition source.
- Check the system and boiler regularly for leaks.
- Repair leaks immediately.
Applies to: Boilers with glycol in the system
Source: EG / PEG Series 7 Boiler Manual, p. 5. Written in our own words; check the manual for your exact model.
Handling ceramic fiber parts (burner gasket, cover plate insulation, combustion chamber lining)
Boiler · Ultra Series 4
Burner gaskets (models 80 and 105) and cover plate insulation contain ceramic fiber that can become cristobalite at high temperature. Treat it as a carcinogen hazard.
- Avoid breathing dust and avoid skin and eye contact.
- Wear an N95 NIOSH-certified respirator (other types may be needed by job site conditions), long-sleeved loose clothing, gloves and eye protection.
- Wet the combustion chamber lining or base insulation before removing it to prevent airborne dust.
- Place removed lining or insulation in a plastic bag for disposal.
- Wash contaminated clothes separately and rinse the washer thoroughly.
- First aid: eyes, irrigate immediately. Breathing, move to fresh air.
Applies to: Ultra Series 4 boilers
Source: Ultra Series 4 gas-fired water boiler manual, p. 109. Written in our own words; check the manual for your exact model.
Hazard levels used in this manual
Boiler · ECO Tec Series 3
The manual uses four hazard levels. The top two warn of severe injury, death or major property damage. The third warns of minor injury or property damage. The fourth gives important install, operation or service notes that are not about injury.
Applies to: All ECO Tec Series 3 work
Source: ECO Tec Series 3 boiler manual, p. 5. Written in our own words; check the manual for your exact model.
Heat exchanger coating: cleaning limits
Boiler · Ultra Series 4
The heat exchanger is coated to stop aluminum oxide forming. Mechanical cleaning can shorten the coating life. Heat exchanger inspection is recommended yearly.
- For the first 5 years, vacuum or rinse the heat exchanger with water only. No tool cleaning is needed.
- Clean only when soiling is clearly present, and flush only with water and mild detergent.
- From the cover plate opening, check the collection area and under the vent pipe for debris.
- Cleaning should not be needed until 5 years after the commissioning date.
Applies to: Ultra Series 4 boilers with coated heat exchangers
Source: Ultra Series 4 boiler manual, p. 126. Written in our own words; check the manual for your exact model.
High altitude propane orifice above 5,500 ft
Boiler · Ultra Series 4
Installations above 5,500 feet need the special-order high altitude propane orifice kit. The orifice stamping must match the boiler size.
- Confirm the installation altitude before ordering the orifice.
- Order the high altitude propane orifice kit for altitudes above 5,500 ft.
- Check that the orifice stamping matches the boiler size before installing it.
Applies to: All Ultra boilers installed above 5,500 ft
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 48. Written in our own words; check the manual for your exact model.
How priority timing and boost work
Boiler · ECO Tec Series 3
BOOST TIME raises the target up to 10°F each time a call for heat lasts longer than the set time, capped at MAX TARGET TEMP. SYSTEM OFF DIFF is how far above target the water must rise to turn the boiler off. SYSTEM ON DIFF is how far below target it must drop before network modulation starts. BOILER ON/OFF DIFF set the boiler's own cycling around target or Boiler Max. MAX ON TIME limits how long the boiler runs on a priority while another priority is calling. MIN ON TIME holds the boiler on a priority before it can drop to a lower one; a new higher priority overrides it immediately.
Applies to: ECO Tec Series 3 priority menus
Source: ECO Tec Series 3 boiler manual, p. 120-121. Written in our own words; check the manual for your exact model.
Identify propane-ready boilers
Boiler · Ultra Series 4
Boilers with an LP suffix after the model number are built for propane. All other Ultra boilers must be converted before running on propane.
- Check the model number on the rating plate for an LP suffix.
- If there is no LP suffix, convert the boiler with the propane orifice before startup.
Applies to: Ultra-80 through Ultra-399
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 48. Written in our own words; check the manual for your exact model.
Input derate for vent length and altitude
Boiler · ECO Tec Series 3
Input de-rates automatically as vent/air pipe length increases because of pipe pressure loss. Use the derate table for the maximum length. For shorter runs: derate = listed % times vent length divided by 100 (199 with 2 in venting: 13 % times vent length divided by 50). For altitude from sea level to 2,000 ft, no change is needed; the boiler derates itself about 4 % per 1,000 ft above sea level.
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 184. Written in our own words; check the manual for your exact model.
Inside air vs direct vent decision
Boiler · SVF Series 1
The boiler may use inside air only if the boiler space has no contaminants. If contaminants are likely, install it as a direct vent appliance.
- Check the boiler space for contaminants before choosing inside air.
- If contaminants are likely, plan a direct vent installation with outside combustion air ducted to the boiler.
Applies to: SVF 1500-3000 Series 1
Source: Weil-McLain SVF Series 1 boiler manual, p. 32. Written in our own words; check the manual for your exact model.
Inspect burners on PEG boilers
Boiler · EG / PEG Series 7
PEG boilers ship factory assembled, but burners and base panels should still be checked before use.
- Remove the access panel (Figure 12).
- Inspect the burners using step 6 of the burner drawer procedure (page 16).
- Reinstall the access panel.
Applies to: PEG-30 through PEG-65
Source: EG/PEG Series 7 boiler manual, p. 17. Written in our own words; check the manual for your exact model.
Install piping unions near the boiler
Boiler · ECO Tec Series 3
Installing 1 in NPT piping unions on the boiler outlet and return makes future service easier. Unions are not included with the boiler.
- Buy 1 in NPT unions separately.
- Install unions on the boiler outlet and return.
Applies to: All ECO Tec Series 3 boilers
Source: ECO Tec Series 3 Boiler Manual, p. 47. Written in our own words; check the manual for your exact model.
Installer conversion label
Boiler · ECO Tec Series 3
After any propane or natural gas conversion, complete the label from the kit and attach it next to the rating label on the right side of the cabinet.
- Fill in the conversion date, combustion CO2 and CO, technician name, address and kit part number.
- Attach the label next to the rating label.
Applies to: ECO Tec gas conversion
Source: ECO Tec Series 3 Boiler Manual, p. 23. Written in our own words; check the manual for your exact model.
Keep contaminants out of the combustion air
Boiler · ECO Tec Series 3
Contaminated combustion air will damage the boiler. Do not pipe combustion air from areas with the contaminants listed below.
- Do not draw air near swimming pools, laundry exhaust, dry cleaning, beauty shops, auto body, plastics or metal fabrication, photo processing, refrigeration repair, or remodeling and construction areas.
- Keep chloro/fluorocarbon sprays, permanent wave solutions, chlorinated waxes, pool chemicals, calcium or sodium chloride, refrigerant leaks, paint or varnish removers, hydrochloric/muriatic acid, cements and glues, fabric softeners, chlorine bleaches and solvents, and building adhesives away from the intake.
- Keep the intake clear of excessive dust and dirt.
Applies to: ECO Tec Series 3 combustion air intake
Source: ECO Tec series 3 boiler manual, p. 25-26. Written in our own words; check the manual for your exact model.
Key boiler components and what they do
Boiler · ECO Tec Series 3
Reference for the main parts a technician will see on the ECO Tec Series 3 boiler. Item numbers match the manual's component drawing.
- Blower (item 3): pulls air through the silencer and venturi and pushes it to the burner through the cover plate.
- Gas valve (item 4): references cabinet pressure and opens gas flow when the control applies power. It has an on/off switch for shutdown or service.
- Venturi (item 6): creates negative pressure to draw gas into the air stream before the blower.
- Boiler circulator (item 7): moves hot water from the boiler to the heating system or the brazed plate heat exchanger.
- Boiler out dual sensor (item 8): controls firing rate to hit the outlet target temperature.
- Boiler in sensor (item 9): control may reduce input if the in/out temperature difference is too large.
- Air pressure switch (item 19): monitors maximum flue pressure.
- Flue gas temperature sensor (item 30): control shuts the boiler down if flue gas gets too hot.
- Ignition electrode/flame sensor (item 28): high voltage across the electrode creates the spark; after ignition it reads the flame signal.
- Transformer (item 31): 120V to 24V for low voltage controls. Do not splice wiring into it.
- Condensate tube (item 24) and condensate trap assembly (item 25): field-installed trap connects to the condensate tube.
Applies to: ECO Tec Series 3 80/110/150/199 boilers
Source: ECO Tec Series 3 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Large space exception for combustion air openings
Boiler · SVF Series 1
No combustion air openings are needed if the space volume is at least 50 cubic feet per 1,000 Btuh of all appliances in the space and the building is not tight construction.
- Total the input of all appliances in MBH (thousands of Btuh).
- Multiply the total by 50 to get the minimum room volume in cubic feet.
- Confirm the building is not tight construction.
- Example from manual: 1500 MBH with 8 ft ceiling needs 50 x 1500 = 75,000 cubic feet.
Applies to: SVF 1500-3000 Series 1
Source: Weil-McLain SVF Series 1 boiler manual, p. 33, p. 39. Written in our own words; check the manual for your exact model.
LGB Series 2 component locations
Boiler · LGB Series 2
Numbered components on the LGB Series 2 diagram. Items 20 to 22 are shown separately from the main diagram.
- 1) Gas valve
- 2) Pilot burner (with flame sense)
- 3) Main burners
- 4) Gas manifold/orifices
- 5) Control module
- 6) Inducer (with vent adapter)
- 9) Transformer
- 11) Air pressure switch
- 13) Low water cutoff (steam shown)
- 14) Limit control(s)
- 18) Gauge (pressure or pressure/temperature)
- 19) Gauge glass (steam only)
- 20) Water temperature/LWCO sensor (water only)
- 21) Main flame sense
- 22) Flue temperature switch
Applies to: LGB Series 2 boiler
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 16. Written in our own words; check the manual for your exact model.
LGB Series 3 component locations
Boiler · LGB Series 3
Numbered components on the LGB Series 3 diagram.
- 1) Gas valve
- 2) Pilot burner
- 3) Main burners
- 4) Gas manifold/orifices
- 5) Control module
- 7) Vent damper
- 9) Transformer
- 10) Spill switch
- 12) Rollout thermal fuse element
- 13) Low water cutoff (steam boilers)
- 14) Limit control(s)
- 15) Draft hood
- 18) Gauge (pressure or pressure/temperature)
- 19) Gauge glass (steam only)
Applies to: LGB Series 3 boiler
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 16. Written in our own words; check the manual for your exact model.
Lock the screen for cleaning
Boiler · ECO Tec Series 3
The CLEAN function locks the display so presses are ignored while the screen is wiped.
- Open MENU and select CLEAN.
- Clean the screen within the 10 second lock period.
Applies to: ECO Tec control
Source: ECO Tec Series 3 boiler manual, p. 112. Written in our own words; check the manual for your exact model.
Low water cutoff test
Boiler · Ultra Series 4
If the system has a low water cutoff, test it during the heating season using the cutoff manufacturer's instructions.
- Test the low water cutoff periodically during the heating season, following the cutoff manufacturer's instructions.
- Reset the boiler control after the test.
Applies to: Ultra Series 4 boilers with a low water cutoff
Source: Ultra Series 4 user's information manual, p. 7. Written in our own words; check the manual for your exact model.
Maintenance log: columns to record
Boiler · ECO Tec Series 3
Log each visit with these columns: date, high fire / low fire, O2, CO, CO2, stack temperature, pH, action taken, and technician.
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 189. Written in our own words; check the manual for your exact model.
Maintenance reminders and contractor contact screen
Boiler · ECO Tec
The control gives the homeowner automatic maintenance reminders and a contractor-contact screen showing the service professional's information.
- Confirm the maintenance reminder is set on the control at commissioning.
- Enter the service contractor's contact information on the contractor screen.
Applies to: ECO Tec Series 3 boilers with Unity 2.0 control
Source: ECO Tec Value Comparison Guide, p. 1-2. Written in our own words; check the manual for your exact model.
Maintenance screen: record installer and service interval
Boiler · Evergreen Series 2
The maintenance screen stores contractor data and the maintenance schedule.
- Enter the installer name and contact data in the maintenance screen.
- Check the last maintenance date, the interval set (example shows 12 months), and the last calibration date.
- Use the rotate and interval values to plan the next service.
Applies to: Series 2 boilers with Evergreen Pro control
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 18. Written in our own words; check the manual for your exact model.
Manifolded combustion air for multiple boilers
Boiler · Ultra Series 4
Several boilers may share one combustion air duct, but vent pipes must never be combined.
- Only air piping may be combined. Do not combine vent piping; flue gas leakage and component damage can occur.
- Each boiler must have its own individually routed and terminated vent.
- Size the duct: minimum area in square inches = total MBH input divided by 2 (example: six Ultra-155 = 930 MBH, minimum 465 sq in).
- Provide at least 1 sq in of free area per 2,000 Btuh total input, adjusted for louver restriction.
- Keep 12 in minimum above grade or snow line, and at least 3 ft below any vent termination within 10 ft.
- If a combustion air damper is used, wire it so the boilers cannot fire until the damper is open.
Applies to: Multiple Ultra boilers using a common combustion air manifold
Source: Weil-McLain Ultra Series 4 boiler manual, p. 59. Written in our own words; check the manual for your exact model.
Manifolded combustion air sizing for multiple boilers
Boiler · SVF Series 1
Multiple SVF boilers can share a common combustion air manifold. Only air piping may be combined; Category IV vent piping must never be combined.
- Size the duct at least 1 sq in per 2,000 Btuh of total connected boiler input.
- Set minimum free area in the duct (after louver restriction) at 1 sq in per 2,000 Btuh, or divide total MBH by 2.
- Example: 3,000 MBH total input gives 1,500 sq in minimum combined air duct.
- Never combine Category IV vent piping; flue gas leakage and component damage can result.
Applies to: SVF 1500-3000 Series 1, multiple boilers
Source: Weil-McLain SVF Series 1 boiler manual, p. 38. Written in our own words; check the manual for your exact model.
Manifolded gas supply for multiple boilers
Boiler · SVF Series 1
Layout rules when several boilers share one gas line.
- Size the gas piping as for a single boiler, using the total input of all appliances.
- At each boiler, install a manual shutoff gas valve, a union, and a sediment trap at least 3 in below the tee.
- Make sure minimum pressure at each boiler is 3.5 in w.c. with all connected appliances firing.
Applies to: SVF 1500-3000 multiple boiler gas supply
Source: SVF Series 1 boiler manual, p. 48. Written in our own words; check the manual for your exact model.
Manual reset limit tripped
Boiler · EG / PEG Series 7
Do not reset a tripped manual reset limit until the cause has been found and fixed. Never bypass a safety limit device, as this can cause unsafe operation.
- Find and correct the cause of the trip before resetting.
- Never bypass a safety limit device.
Applies to: All EG / PEG Series 7 boilers
Source: EG / PEG Series 7 Boiler Manual, p. 48. Written in our own words; check the manual for your exact model.
Manual section map
Boiler · Ultra Series 4
Basic installation covers pages 4 to 42 for conventional systems with the Weil-McLain sidewall termination cap. Advanced installation covers pages 44 to 107. Maintenance, parts, dimensions and ratings are on pages 108 to 140.
- Read and follow the basic section first.
- Use the advanced section for multiple boilers, other system types and alternative vent/air methods.
Applies to: Ultra Series 4 boilers
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 3. Written in our own words; check the manual for your exact model.
Model number suffix codes
Boiler · EG / PEG Series 7
Suffixes on EG-30 to EG-75 model numbers show the ignition type, fuel, boiler type and tankless heater option.
- Add PID or PI for electronic ignition. The PID/PI suffix is required with a damper in the US (EG-30 to EG-65) and optional in Canada.
- Add N for natural gas.
- Add W for a water boiler, or S for a steam boiler.
- Add T for a tankless heater, or P for a provisional tankless heater.
- For a package boiler, add the P prefix (for example PEG-30-S through PEG-65-S).
Applies to: EG-30 to EG-75 and PEG package models
Source: EG / PEG Series 7 Natural Gas-Fired Boiler Manual, p. 89. Written in our own words; check the manual for your exact model.
Motorized combustion air damper interlock
Boiler · Ultra Series 4
If combustion air openings use motorized dampers, the boiler must not fire unless the damper is proven open.
- Wire an isolated contact that proves the damper open in series with the thermostat input to the boiler.
- Confirm the boiler will not start with the contact open.
- Confirm the boiler shuts down if the damper closes during operation.
Applies to: Direct exhaust combustion air openings with motorized dampers
Source: Ultra Series 4 boiler manual, p. 84. Written in our own words; check the manual for your exact model.
Multi-boiler outputs are limited to 120 VAC and 2.0 A
Boiler · Evergreen Series 2
The multi-boiler outputs are 120 VAC maximum at 2.0 A. For any other voltage or higher amperage, use a relay.
- Confirm the load voltage and amperage before connecting to an output.
- If the load is above 120 VAC or above 2.0 A, add a relay.
Applies to: Multi-boiler outputs, Example C and all multi-boiler examples
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 28. Written in our own words; check the manual for your exact model.
Multiple boiler and BMS connections are in the Advanced Manual
Boiler · SVF Series 1
Expansion module terminal strips EP11 and EP12 (right side) handle multiple boiler communication (up to eight boilers) and BMS communication. Multiple boiler setup is not covered in this manual.
- Refer to the SVF Advanced Manual for multi-boiler and BMS wiring and setup.
Applies to: SVF Series 1 multi-boiler and BMS installs
Source: SVF 1500-3000 Series 1 boiler manual, p. 65. Written in our own words; check the manual for your exact model.
Multiple boiler placement and wall-mount spacing
Boiler · Ultra Series 4
Clearance and spacing for side-to-side, back-to-back and wall-mounted Ultra boilers.
- Use the side-to-side (Figure 56) or back-to-back (Figure 57) layout, or wall mount (Figure 58).
- Keep the indicated access clearances. If not possible, use at least the minimum clearances on page 5 and follow local codes.
- Build a foundation if the floor is uneven or flooding is possible, sized to the spacing shown.
- For wall-mounted boilers, leave about 6 inches between boilers so the jacket door can be removed.
- Verify the wall can carry the structural load (see page 50).
- Keep a minimum 30-inch walkway or follow local code.
Applies to: Ultra models 80–399 in multiple boiler rooms
Source: Weil-McLain Ultra Series 4 boiler manual, p. 58. Written in our own words; check the manual for your exact model.
Multiple boiler vent terminations
Boiler · SVF Series 1
Each boiler vent connection is terminated separately using the clearances in the manual. Canadian installs need additional code clearances and a ULC S636 kit.
- Terminate each vent connection as described in the manual; see Figure 30 (page 37) for typical sidewall layout.
- Place wall penetrations to give the minimum clearances in Figure 29 (U.S.) or the CAN/CSA B149.1 clearances (Canada).
Applies to: SVF 1500-3000 Series 1, multiple boilers
Source: Weil-McLain SVF Series 1 boiler manual, p. 34, p. 36, p. 37. Written in our own words; check the manual for your exact model.
Multiple Ultra boiler venting and circulator rules
Boiler · Ultra Series 4
Rules for installing several Ultra boilers together.
- Provide a separate vent pipe and termination for each boiler.
- Do not manifold the vent piping.
- Combustion air piping may be individually piped or manifolded, per the manifolded air duct figure in the manual.
- Keep total circulator amps within the limit: up to three circulators at no more than 2.2 amps each.
Applies to: Multiple Ultra Series 4 boiler installations
Source: Weil-McLain Ultra Series 4 boiler manual, p. 139. Written in our own words; check the manual for your exact model.
Network priority is set from the Master only
Boiler · Evergreen Pro, Series 2
Each of the four inputs on the Master or any shadow boiler can be assigned as Network Priority 1 or 2, or Local Priority 1 or 2. Network priority settings are common to all boilers and can only be changed at the Master. When a Local Priority input closes, that boiler modulates from its own inlet and outlet sensors instead of being controlled by the Master.
- Make all Network Priority 1 and 2 changes at the Master boiler.
- Assign Local Priority inputs on the boiler that should respond to them locally.
Applies to: Multiple boiler networks on Evergreen Pro control
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 63-64. Written in our own words; check the manual for your exact model.
Never common vent the ECO Tec with another appliance
Boiler · ECO Tec Series 3
The ECO Tec cannot share a common vent with any other appliance. When an old boiler is replaced, the ECO Tec must have its own vent and air piping. The remaining appliances on the old common vent may then be oversized and need to be checked.
- Do not connect the ECO Tec to an existing common vent.
- Install new vent and air piping as specified in this manual.
- Check the remaining appliances on the old vent for proper venting (see the vent verification guide).
Applies to: ECO Tec Series 3 replacing a boiler on a common vent
Source: ECO Tec series 3 boiler manual, p. 25. Written in our own words; check the manual for your exact model.
Orifice sizing is critical; check the orifice table
Boiler · EG / PEG Series 7
Only the orifices listed for the model and elevation may be used. Wrong orifices cause unsafe firing and property damage. The orifice drill-size table is printed on page 17 but its values did not extract clearly, so read it from the printed page.
- Confirm boiler model and altitude before selecting orifices.
- Use only the orifice drill size listed for that model and elevation (Table 5, page 17).
Applies to: EG 30-75 natural gas, including Canada altitude table
Source: EG/PEG Series 7 boiler manual, p. 16-17. Written in our own words; check the manual for your exact model.
Outdoor reset and DHW mode
Boiler · Ultra Series 4
Setting the control to DHW mode when the system is meant for space heating may violate Section 303 of the 2007 Energy Act. Exemptions are listed on page 137 of the manual.
- Do not override outdoor reset for a space heating system by selecting DHW mode.
Applies to: Zone valve and circulator zoning with DHW piping
Source: Ultra Series 4 boiler manual, p. 12. Written in our own words; check the manual for your exact model.
Outdoor sensor and energy saving override
Boiler · Ultra Series 4
The energy saving feature lowers boiler water temperature as the load drops. The override is only for specific cases.
- Install the outdoor sensor supplied with the boiler unless one of the listed exemptions applies.
- Do not use the override unless an external energy management system reduces water temperature with load, the boiler does no space heating, the boiler is part of a modular or multiple system of 300,000 Btuh or more, or the boiler has a tankless coil (not applicable to Ultra).
Applies to: Ultra Series 4 boilers
Source: Weil-McLain Ultra Series 4 boiler manual, p. 137. Written in our own words; check the manual for your exact model.
Outdoor sensor must be installed
Boiler · ECO Tec Series 3
The outdoor sensor shipped with the boiler must be installed unless one of the exemptions applies.
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 184. Written in our own words; check the manual for your exact model.
Overheating or gas shutoff failure
Boiler · CGa, CGi, EG, PEG
If the boiler overheats or the gas supply does not shut off, the pump must stay powered.
- Do not turn off or disconnect the electrical supply to the pump.
- Shut off the gas supply at a location external to the appliance.
Applies to: All listed boiler series
Source: Gas-Fired Boilers User Manual, p. 4. Written in our own words; check the manual for your exact model.
Overheating or gas supply fails to shut off
Boiler · Ultra Series 4
If the boiler overheats or the gas does not shut off, do not cut power to the pump.
- Shut off the gas supply at a point outside the appliance.
- Leave the pump electrical supply on.
Applies to: Ultra Series 4 boilers
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 4. Written in our own words; check the manual for your exact model.
Overheating or gas supply that will not shut off
Boiler · ECO Tec Series 3
If the boiler overheats or the gas supply does not shut off, do not cut the power to the circulator. Shut off the gas at a location outside the appliance.
- Do not turn off or disconnect the electrical supply to the circulator in this case.
- Shut off the gas supply at a point outside the boiler.
- Do not block combustion or ventilation air to the boiler.
Applies to: ECO Tec Series 3 operation
Source: ECO Tec Series 3 boiler manual, p. 6. Written in our own words; check the manual for your exact model.
Piping connection sizes and required fittings
Boiler · ECO Tec Series 3
Pipe sizes and the fittings needed for the low water cut-off and air relief.
- Boiler water outlet and inlet (items 14 and 15): all heat only models and 199 Combi use 1 inch male NPT; 150 and 110 Combi use 3/4 inch male NPT.
- Install a tee for the low water cut-off (LWCO) at item 16.
- Gas line connection at item 17 is 1/2 inch male NPT.
- Air elimination/relief valve (item 38): 3/4 inch male NPT. Use a 3/4 inch tee and 3/4 inch street elbow for the relief valve. Connecting an automatic air vent to the top tee is recommended.
- Boiler drain valve (item 23) is shipped loose; pipe it on a reducing tee at the lowest point of the return piping.
Applies to: ECO Tec Series 3 piping
Source: ECO Tec Series 3 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Pressure/temperature gauge limit
Boiler · Ultra Series 4
Daily reading must stay at or below 25 psig. Call a technician if the problem persists.
- Read the pressure/temperature gauge daily.
- Confirm the pressure does not exceed 25 psig.
- If the reading stays high, contact a qualified service technician.
Applies to: Ultra Series 4 pressure/temperature gauge
Source: Ultra Series 4 user's information manual, p. 6. Written in our own words; check the manual for your exact model.
Priority MAX and MIN on-time behavior
Boiler · SVF Series 1
MAX ON TIME limits how long a priority can run before a lower priority's call takes over. MIN ON TIME sets how long a priority must run before a higher priority or the next lower priority can take over. Inputs on the same priority run together when active.
- Set MAX ON TIME and MIN ON TIME for each priority in the Priority Switching settings.
- Set Blr Circ to OFF for DHW that is directly piped with its own DHW circulator.
Applies to: SVF Series 1 priorities
Source: SVF 1500-3000 Series 1 boiler manual, p. 69. Written in our own words; check the manual for your exact model.
Propane conversion requirement
Boiler · Ultra Series 4
Ultra boilers must be converted for propane unless made for propane. Propane-ready models carry an LP suffix after the model number. All other models need conversion.
- Check the model number for an LP suffix.
- If there is no LP suffix, convert the boiler for propane using page 48 before operating.
Applies to: Ultra Series 4 boilers
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 7. Written in our own words; check the manual for your exact model.
Propane-ready and factory propane models
Boiler · Ultra Series 4
Ultra boilers ship ready for natural gas only, unless the model is propane-ready. Propane-ready units have LP after the model number. Ultra-80LP is factory-equipped for propane.
- Check the model suffix before firing on propane.
- For non-LP models other than Ultra-399, install the propane orifice or conversion kit before propane firing.
- Ultra-80 natural gas units needing a burner conversion must use the special-order conversion kit instructions, not this manual.
Applies to: Ultra-80, 105, 155, 230, 299, 399 and 80LP
Source: Ultra Series 4 gas-fired water boiler manual, pp. 42, 48. Written in our own words; check the manual for your exact model.
Protect exposed vent pipe from freezing
Boiler · ECO Tec Series 3
Do not extend exposed vent pipe outside the building beyond the length shown in the manual. Condensate can freeze and block the vent.
- Keep exposed vent pipe outside the building within the length shown in the manual.
- Check that condensate cannot freeze and block the vent pipe.
Applies to: Direct vent terminations
Source: ECO Tec Series 3 Boiler Manual, p. 40. Written in our own words; check the manual for your exact model.
Protect low-temperature circuits on multi-temperature systems
Boiler · Evergreen Pro, Series 2
If the system has both low-temperature and high-temperature circuits, the low-temperature circuits need their own limit controls. Without them, property damage can occur.
- Wire limit controls on each low-temperature circuit to an external limit circuit.
- Confirm the limit controls regulate those circuits before commissioning.
Applies to: Multi-temperature heating systems on Series 2 boilers
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 64. Written in our own words; check the manual for your exact model.
Protecting and capping the concentric termination during install
Boiler · Ultra Series 4
Blocked air passages will stop the boiler from running, and cemented parts cannot be repaired. Keep debris out during installation, and do not alter the assembly.
- Wrap plastic or other protection over the end of the exposed assembly before inserting it through the roof or wall.
- Do not cement the rain cap until the assembly is through the penetration and all supports are installed.
- After positioning, place the bird screen on the end of the inner pipe, then cement the rain cap in place.
- Do not cut or alter the termination assembly. A cut part cannot be cleaned and must be replaced.
Applies to: 3 in or 4 in concentric termination assembly
Source: Ultra Series 4 boiler manual, p. 74, 76-77. Written in our own words; check the manual for your exact model.
ProTools app: clone settings and update software over Bluetooth
Boiler · ECO Tec
The ProTools app connects over Bluetooth. Its clone-to-phone feature copies settings from one boiler to another, and it can also update the boiler software.
- Connect the phone to the boiler over Bluetooth using the ProTools app.
- Use clone-to-phone to copy settings from one boiler to another.
- Update the boiler software through the app to get the latest features.
Applies to: ECO Tec Series 3 boilers with Unity 2.0 control
Source: ECO Tec Value Comparison Guide, p. 1-2. Written in our own words; check the manual for your exact model.
Purchased items needed for termination
Boiler · ECO Tec Series 3
Bird screens, the concentric termination kit and the 45-degree elbow for concentric runs are not supplied with the boiler and must be bought separately.
- Check parts before starting. Concentric kit needs a separate 45-degree elbow in the piping.
- Maximum vent and air lengths already include the 45-degree elbow allowance.
Applies to: Sidewall and vertical terminations
Source: ECO Tec Series 3 boiler manual, p. 33, 35, 39. Written in our own words; check the manual for your exact model.
Read and save boiler configuration with WM ProTools
Boiler · ECO Tec Series 3
The app can load, save and view the boiler configuration. Saved files are stored on the phone only, so uninstalling the app deletes them. Save the information for your records.
- In the app, choose READ/WRITE Configuration.
- Press READ Configuration and wait several seconds for the data to load.
- Review the information, then press Save Configuration.
- Enter a descriptive name and press Save.
Applies to: ECO Tec Series 3 boilers with WM ProTools app
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 187. Written in our own words; check the manual for your exact model.
Read software versions
Boiler · SVF Series 1
The SOFTWARE VERSIONS screen shows the display version, main micro and second micro.
- Open DIAGNOSTICS > SOFTWARE VERSIONS.
- Record DISPLAY, MAIN MICRO and SECOND MICRO versions.
Applies to: Unity control, SVF Series 1
Source: SVF Series 1 boiler manual, p. 80. Written in our own words; check the manual for your exact model.
Reinstall door and check gaskets after service
Boiler · Ultra Series 4
The boiler door must be sealed and fastened so the boiler does not draw air from the boiler room.
- Reinstall the boiler jacket front door after startup or service.
- Inspect the door gaskets; replace them if torn or gapped.
- Make sure the door is securely fastened.
Applies to: All Ultra Series 4 boilers
Source: Ultra Series 4 boiler manual, p. 125. Written in our own words; check the manual for your exact model.
Reinstall jacket door after servicing
Boiler · ECO Tec Series 3
A properly sealed jacket door keeps the boiler from drawing air from the room.
- Reinstall the jacket door after start-up or service.
- Make sure it is securely fastened.
- Check the jacket door gaskets for tears or gaps and replace if needed.
Applies to: ECO Tec Series 3 gas boilers
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
Reinstall the jacket door after service
Boiler · ECO Tec Series 3
The jacket door must be fastened securely after start-up or any service so the boiler does not pull air from the boiler room. This matters most when other appliances share the room. Check the door gasket on the cabinet front. It must have no tears or gaps and should be replaced if damaged.
- Reinstall the jacket door after start-up or servicing.
- Confirm the door is fastened securely.
- Inspect the door gasket for tears or gaps and replace it if needed.
Applies to: All ECO Tec Series 3 models
Source: ECO Tec series 3 boiler manual, p. 144. Written in our own words; check the manual for your exact model.
Relief valve and by-pass regulator piping
Boiler · ECO Tec Series 3
The relief valve is supplied with the boiler and must be field piped to the boiler In connection. Relief valve piping runs to a drain. A by-pass pressure regulator is required in zone valve systems.
- Pipe the supplied relief valve to the boiler In connection; see Figure 12 on page 18.
- Run relief valve discharge piping to a drain.
- In zone valve systems, install a by-pass pressure regulator.
Applies to: Express Setup Examples C and D piping
Source: ECO Tec Series 3 boiler manual, p. 108. Written in our own words; check the manual for your exact model.
Remote 0-10 VDC modulation input
Boiler · Ultra Series 4
The U-Control accepts a remote 0-10 VDC signal on P15 terminal 6 (positive) and terminal 5 (common). The boiler starts above 1.0 VDC, shuts off below 0.5 VDC, stays at low fire until 2.0 VDC, then increases firing rate up to full input at 10.0 VDC. The control still monitors temperatures using the Priority 1 settings.
- Connect the positive 0-10 VDC wire to P15 terminal 6.
- Connect the signal common to P15 terminal 5.
- Set the boiler as Type 4 (SHADOW) if a separate controller is providing the signal.
Applies to: Ultra U-Control remote modulation
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98. Written in our own words; check the manual for your exact model.
Replace flue gas temperature sensor after combustion test
Boiler · Ultra Series 4
A flue gas temperature sensor left out or badly seated can let flue gas spill into the boiler enclosure.
- Remove the rubber grommet from the probe.
- Insert the rubber grommet into the flue pipe.
- Insert the probe into the rubber grommet.
- Confirm the sensor is fully replaced before running the boiler.
Applies to: All Ultra Series 4 models after combustion testing
Source: Ultra Series 4 gas-fired water boiler manual, pp. 40-41. Written in our own words; check the manual for your exact model.
Reset the maintenance reminder after service
Boiler · Evergreen Pro Series 2
Resets the maintenance reminder to the next service date.
- Open SERVICE > SERVICE INFO.
- Select Reset Reminder.
- Confirm that the Last Maintenance and Next Due dates updated.
Applies to: Evergreen Pro Series 2 boilers
Source: Series 2 Advanced Manual 550-100-581, p. 86. Written in our own words; check the manual for your exact model.
Rollout thermal fuse element has cut off gas flow
Boiler · CGa, CGi, EG, PEG
The rollout thermal fuse cuts gas flow if flame rollout occurs. The boiler must not be restarted until a service technician has checked it.
- Do not attempt to place the boiler in operation
- Call a service technician immediately
Applies to: CGa, CGi, EG and PEG boilers
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 12. Written in our own words; check the manual for your exact model.
Rollout thermal fuse on EG-30 to EG-75
Boiler · EG / PEG Series 7
The rollout thermal fuse element mounts on the front access panel for EG-30 through EG-75.
- Install the rollout thermal fuse element with the wire terminals facing up on the front access panel (Figure 40, page 49).
- Wire it per the appropriate wiring diagram.
Applies to: EG-30 through EG-75
Source: EG/PEG Series 7 boiler manual, p. 17. Written in our own words; check the manual for your exact model.
Secure the boiler door after servicing
Boiler · Ultra Series 4
The door must be fastened to stop the boiler drawing air from the boiler room, which matters most when other appliances share the room.
- Reinstall the boiler door after servicing and fasten it securely.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Source: Ultra Series 4 gas-fired water boiler manual, p. 115. Written in our own words; check the manual for your exact model.
Secure the front door after any service
Boiler · Ultra Series 4
The front door must be fastened tightly so the boiler does not draw air from the boiler room.
- Reinstall the jacket front door after servicing.
- Make sure the door is securely fastened to the boiler.
- If the door does not sit correctly or the door gaskets are damaged, contact the installer or technician immediately.
Applies to: Ultra Series 4 gas-fired water boiler
Source: Weil-McLain Ultra Series 4 user's information manual, p. 8. Written in our own words; check the manual for your exact model.
Service safety: power off and cool down
Boiler · EG / PEG Series 7
Disconnect all electrical supplies before maintenance to avoid electric shock. Let the boiler cool before maintenance to avoid burns. The boiler contains ceramic fiber and fiberglass material, so follow the handling warning on page 91.
- Disconnect all electrical power to the boiler before servicing.
- Allow the boiler to cool before servicing.
- Follow the ceramic fiber and fiberglass handling instructions.
Applies to: All service work
Source: EG / PEG Series 7 Boiler Manual, p. 6. Written in our own words; check the manual for your exact model.
Set date and time
Boiler · SVF Series 1
Set the date and time in the SET TIME & DATE menu. Fault occurrences are time- and date-stamped, so the clock must be correct for lockout history to be useful.
- Open the SET TIME & DATE menu from the main menu.
- Enter the current date and time.
Applies to: Unity control, SVF Series 1
Source: SVF Series 1 boiler manual, p. 74. Written in our own words; check the manual for your exact model.
Set outputs to CAD interlock mode
Boiler · Evergreen Series 2
When Input 3 is used with a CAD, set the output mode so the damper opens on every call to fire.
- Assign Input 3 as AUX PUMP/OUTPUT.
- Set the operating mode to local or System Damper.
- Confirm Output 3 supplies 120VAC to the damper motor.
Applies to: Evergreen 110/155/220/299/300/399
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 52. Written in our own words; check the manual for your exact model.
Set user mode to Basic before setup
Boiler · SVF Series 1
Screens in this section assume USER MODE is BASIC, which is the default. Advanced options are in the separate Advanced Manual.
- Confirm USER MODE is set to BASIC.
- Use the Advanced Manual for multi-boiler networks or advanced features.
Applies to: Unity control, SVF Series 1
Source: SVF Series 1 boiler manual, p. 74. Written in our own words; check the manual for your exact model.
Sidewall direct exhaust termination assembly
Boiler · SVF Series 1
Sidewall terminations use a down-turned 90-degree elbow and vent manufacturer stop plates so the vent cannot be pushed inward.
- Cut the vent hole at least 3/8 in larger than the vent pipe diameter for combustible construction, or as the vent maker specifies.
- Insert a corrosion-resistant metal thimble in the hole.
- Install vent manufacturer stop plates with holes just larger than the vent pipe; get them only from the vent manufacturer.
- Insert the last vent pipe length from outside until its female shoulder rests on the outer stop plate.
- Insert the down-turned 90-degree termination elbow and install a bird screen in its open end.
- Seal exterior openings thoroughly with exterior caulk.
Applies to: SVF 1500-3000 Series 1, direct exhaust sidewall
Source: Weil-McLain SVF Series 1 boiler manual, p. 36, p. 37. Written in our own words; check the manual for your exact model.
Single combustion air opening and large space exception
Boiler · Ultra Series 4
One combined opening or no openings can be used in some cases, but only under the conditions below.
- For a single opening, make sure it opens directly to outdoors, or to a space that opens directly to outdoors, not to an interior space.
- Put the top of the single opening within 12 inches of the ceiling.
- Make the free area at least equal to the total area of all equipment vent connectors in the space.
- For large spaces, total the input of all appliances in MBH and multiply by 50 to get the minimum room volume in cubic feet.
- Use no openings only if the room volume meets that minimum and the building is not of tight construction.
- Example: 1500 MBH with an 8 foot ceiling needs 60,000 cubic feet (50 x 1500 x 8).
Applies to: Ultra direct exhaust boiler rooms
Source: Ultra Series 4 boiler manual, p. 85. Written in our own words; check the manual for your exact model.
Slope, clearance and sealing of vent and air piping
Boiler · Ultra Series 4
Keep vent and air piping sloped back to the boiler with no sags, keep combustible materials away from the vent, and seal wall and floor openings.
- Slope vent and air piping continuously toward the boiler, at least 1/4 inch drop per foot of run.
- Keep at least 3/16 inch clearance between the vent pipe and any combustible wall or material.
- Seal wall and floor penetrations following local code.
Applies to: Ultra vent and air piping
Source: Ultra Series 4 boiler manual, p. 71. Written in our own words; check the manual for your exact model.
Solvent-cement joints in concentric termination assembly
Boiler · Ultra Series 4
Assemble the termination dry first, then cement each joint in the correct order. Too much cement inside a socket can build up and block the air passages.
- Deburr the inside and outside of each pipe end.
- Chamfer the outside of each pipe end so cement spreads evenly.
- Clean all pipe ends and fittings, then let them dry thoroughly.
- Dry-fit the whole vent or air assembly before cementing any joint.
- Brush primer on both the pipe end and the fitting socket while it is liberal.
- While the primer is still damp, apply cement to both surfaces, then a second coat.
- Insert the pipe fully into the fitting while the cement is wet, twisting about 1/4 turn.
- Handle fittings carefully to keep the joint surfaces clean.
Applies to: Concentric termination assembly, 3 in or 4 in
Source: Ultra Series 4 boiler manual, p. 76. Written in our own words; check the manual for your exact model.
Spacing between multiple vent or air terminations
Boiler · Ultra Series 4
When several Ultra boilers share a wall or roof, each vent and air connection needs its own termination, spaced as below.
- Terminate each vent and air connection separately; do not common vent.
- Keep adjacent vent terminations at least 6 inches apart.
- Keep adjacent air inlets at least 6 inches apart.
- Combustion air piping may be manifolded; vent piping may not.
- Build wall penetrations to meet minimum clearances in this manual.
Applies to: Multiple Ultra boilers, direct vent
Source: Ultra Series 4 boiler manual, p. 80-81. Written in our own words; check the manual for your exact model.
Spill switch has cut off gas flow
Boiler · CGa, EG, PEG, LGB Series 2
The spill switch cuts gas flow if the vent system becomes blocked. The boiler must not be restarted until a service technician has checked it.
- Do not attempt to place the boiler in operation
- Call a service technician immediately
Applies to: CGa, EG, PEG and LGB Series 2 boilers
Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 12. Written in our own words; check the manual for your exact model.
Standard and optional equipment
Boiler · EG / PEG Series 7
Standard equipment differs for EG/PEG boilers, EG water boilers and EG/PEG steam boilers. Use this list to confirm what should be on a boiler when servicing it.
- EG/PEG boilers: combination gas valve for 24 volt, rollout thermal fuse element, spill switch, and on the highest efficiency models a PID intermittent electronic ignition with automatic vent damper.
- EG water boilers: Unity-CI ignition module, temperature/LWCO sensor, built-in air eliminator, 30 PSI relief valve, combination pressure temperature gauge, and 50 VA transformer.
- EG/PEG steam boilers: 15 PSI relief valve, steam pressure gauge, high-limit pressure control, syphon, gauge cocks, gauge glass, probe-type low-water cutoff, and 40 VA transformer.
- Standard on all: factory-assembled section block, insulated extended jacket, draft hood, aluminized steel burners, non-linting pilot burner, heater cover plates (for boilers with tankless heater openings), control wire, and electrical junction box.
- EG additional equipment: water tankless heater kits and steam tankless heater kits (EG-35 to EG-75).
Applies to: EG and PEG Series 7 boilers
Source: EG / PEG Series 7 Natural Gas-Fired Boiler Manual, p. 90. Written in our own words; check the manual for your exact model.
Steam boiler water chemistry limits
Boiler · EG, PEG
Chlorides above 200 ppm accelerate water-side corrosion. Treatment should be considered if chloride in makeup water is above 30 ppm. Chloride above 400 ppm or TDS above 1000 ppm requires drain and refill.
- If chloride is above 200 ppm, expect accelerated water-side corrosion and consider treatment.
- If makeup water chloride is above 30 ppm, consider boiler water treatment.
- If there is no chemical treatment and chloride is above 400 ppm or TDS is above 1000 ppm, drain and refill with fresh water.
- After refilling, bring the boiler to pressure for 15 minutes to drive off excess oxygen.
Applies to: EG / PEG steam boilers
Source: EG / PEG Series 7 boiler manual, p. 61-62. Written in our own words; check the manual for your exact model.
Support vent and air piping so it does not load the boiler
Boiler · ECO Tec Series 3
Vent and air piping must be securely supported and must not rest its weight on the boiler fittings. Improper support can damage the vent piping.
- Support vent and air piping independently of the boiler.
- Do not drill or screw into vent or air pipe or fittings.
- Wrap the open end of the assembly with plastic while inserting it through the roof to keep debris out.
Applies to: Vertical concentric and vent/air installs
Source: ECO Tec Series 3 Boiler Manual, p. 42. Written in our own words; check the manual for your exact model.
Tankless heater application limits
Boiler · EG / PEG Series 7
EG boilers can be ordered with a tankless heater only as factory-installed optional equipment. Standard boilers cannot be adapted. The heater can only be used in a steam boiler or forced hot water system.
- Confirm the boiler was ordered with the factory tankless heater option.
- Install the heater only in a steam boiler or forced hot water system.
- Install the piping as shown in Figure 26 for water boilers or Figure 27 for steam boilers.
- Install an automatic mixing valve per the mixing valve maker's instructions.
- Install a flow regulating valve sized to the heater's intermittent draw from Table 10.
- Install the operating control (small differential recommended) in the temperature control tapping in the heater plate.
- In hard water areas, soften the cold domestic supply to the heater to prevent lime buildup.
- Use brass plugs in tees and crosses to make cleaning easier in hard water areas.
Applies to: EG boilers with optional tankless heater
Source: EG/PEG Series 7 boiler manual, p. 28. Written in our own words; check the manual for your exact model.
Tight construction and air movers
Boiler · Ultra Series 4
Tight buildings and exhaust fans can starve the boiler room of combustion air.
- Check whether the building meets the tight construction definition (vapor retarder, gasketed openings, weatherstripping, caulking).
- If tight, provide air openings from outside sized per Figure 96.
- Size openings for the exhaust fan or air mover flow rate as well as firing rate.
- Do not let the appliance space go under negative pressure unless all appliances are direct vent.
Applies to: Boiler rooms with inside air combustion
Source: Ultra Series 4 boiler manual, p. 84. Written in our own words; check the manual for your exact model.
Tight construction requires outside air openings
Boiler · SVF Series 1
Buildings with continuous vapor retarder, weather-stripped openings and sealed penetrations are considered unusually tight. In these buildings, outside air openings into the building must be sized for the appliances.
- Check whether the building meets the tight construction definition in the National Fuel Gas Code.
- If tight, size outside air openings per Figure 26 or Figure 33 for the case that applies.
Applies to: SVF 1500-3000 Series 1
Source: Weil-McLain SVF Series 1 boiler manual, p. 32, p. 38. Written in our own words; check the manual for your exact model.
Tighten heat exchanger cover nuts to torque sequence
Boiler · Ultra Series 4
Cover plate nuts must be tightened gradually, in the sequence shown, to a limited final torque.
- Tighten in two or three passes using a torque wrench.
- Follow Figure 126 for Ultra-80 and -105, or Figure 128 for Ultra-155 through -399.
- Do not exceed 50 in-lb (±10 in-lb) final torque.
Applies to: Ultra Series 4 boilers, heat exchanger cover plate
Source: Ultra Series 4 boiler manual, p. 126. Written in our own words; check the manual for your exact model.
Tools for troubleshooting
Boiler · Ultra Series 4
Tools recommended for troubleshooting Ultra boilers (Figure 122).
- #2 Phillips screwdriver: remove 4 screws for the top front cover.
- U-Control screwdriver or 1/16 in. flat blade: terminal block wiring.
- 1/8 in. Allen wrench: add orifice when changing natural to propane.
- 7 mm nut driver (155/230/299/399) or #2 Phillips (80/105): change the burner.
- 11 mm nut driver: remove the burner front cover plate.
- 4 mm long Allen wrench: remove the blower from the heat exchanger.
- Multimeter, manometer (incline or digital), combustion analyzer, contact thermometer.
- Keep maintenance kit 383-500-605 (80/105) or 383-500-620 (155/230/299/399) on hand for annual service.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Source: Ultra Series 4 gas-fired water boiler manual, p. 115. Written in our own words; check the manual for your exact model.
Tools needed for flue side service
Boiler · ECO Tec Series 3
Tools for opening the flue side and accessing the burner: long-handled #20 Torx driver for burner screws, 3mm Allen wrench for ignition electrode screws, 8mm wrench for blower lock nuts, 10mm wrench or socket for heat exchanger cover nuts, torque wrench, large crescent wrench and pipe wrench for gas valve removal, and a flathead screwdriver.
Applies to: ECO Tec Series 3 boilers
Source: ECO Tec series 3 boiler manual, p. 150. Written in our own words; check the manual for your exact model.
Tools needed for install and maintenance
Boiler · ECO Tec Series 3
Tools listed for install (I) and maintenance (M) work on the ECO Tec Series 3.
- Have a flat blade and Phillips screwdriver, 5/16 in socket and 2.5 and 4 mm Allen wrenches for install and gas valve work.
- Have a 3 mm Allen wrench for ignition electrode screws (maintenance).
- Have an 8 mm wrench for the blower and a 10 mm wrench for the heat exchanger cover plate (maintenance).
- Have a T20 long-handled Torx driver for burner screws and mixer/venturi (maintenance).
- Have a large crescent wrench for the gas valve (maintenance).
- Have a multimeter to check sensors and electrical parts (maintenance).
- Have an inclined or digital manometer to measure INLET gas pressure (install and maintenance).
- Have a digital combustion analyzer for combustion testing and adjustments (install and maintenance).
- Have a contact thermometer to check heat exchanger and pipe surface temperatures (install and maintenance).
- Have pipe wrenches for gas train installation (install and maintenance).
- Always keep the maintenance kit on hand for maintenance work in case parts need replacing.
Applies to: ECO Tec Series 3 install and maintenance
Source: ECO Tec Series 3 boiler manual, p. 3. Written in our own words; check the manual for your exact model.
Tools needed for installation and service
Boiler · EG / PEG Series 7
Standard hand tools are needed for this boiler: a 1/16" flat blade screwdriver for terminal block wiring, a flat blade screwdriver for the gas valve adjustment, a 5/16" socket for the burner access shield, a Phillips screwdriver for jacket screws, pipe wrenches for the gas train, and an inclined or digital manometer to measure incoming gas pressure.
Applies to: EG / PEG Series 7 boilers
Source: EG / PEG Series 7 Boiler Manual, p. 3. Written in our own words; check the manual for your exact model.
Troubleshooting tools and kits
Boiler · ECO Tec Series 3
Tools recommended for troubleshooting the ECO Tec boiler, with their purposes.
- Phillips screwdriver #2: multiple uses.
- 2.5 and 4mm Allen wrench: adjust gas valve settings.
- 3mm Allen wrench: remove ignition electrode screws.
- 8mm wrench: remove blower.
- 10mm wrench: remove heat exchanger cover plate.
- T20 long-handled Torx driver: remove burner screws and mixer/venturi.
- Large crescent wrench: remove gas valve.
- Multimeter: measure sensors and electrical components.
- Manometer (inclined or digital): measure INLET gas pressure to the boiler.
- Combustion analyzer (digital preferred): combustion testing and adjustments.
- Contact thermometer: check surface temperatures of heat exchanger and pipes.
- Maintenance kit: always keep on hand in case replacement is needed.
Applies to: 80/110/150/199 Series 3
Source: ECO Tec series 3 boiler manual, p. 159. Written in our own words; check the manual for your exact model.
Turn off all power before servicing
Boiler · Ultra Series 4
The boiler ON/OFF switch does not cut all power. Internal wiring stays live when the switch is off.
- Turn off all power to the boiler at the external switch or breaker before servicing.
- Label all wires before disconnecting control wiring.
- Never jumper a device except for momentary testing.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Source: Ultra Series 4 gas-fired water boiler manual, p. 115. Written in our own words; check the manual for your exact model.
Turn power off before service and label wires
Boiler · ECO Tec series 3
Power must be off before servicing or making connections to prevent electrical surges that can damage components. Label all wires before disconnecting them.
- Turn power off to the boiler before servicing or making connections.
- Label every wire before disconnecting it.
- Verify wiring after reconnecting to avoid unsafe operation.
Applies to: ECO Tec series 3 80/110/150/199
Source: ECO Tec Series 3 boiler manual, p. 169. Written in our own words; check the manual for your exact model.
Two types of lockouts
Boiler · EG / PEG Series 7
The control has manual reset lockouts, which need the operator to reset them at the display, and automatic reset lockouts, which clear by themselves once the fault condition goes away.
- For a manual reset lockout, go to the reset screen and answer the reset question.
- For an automatic reset lockout, correct the condition and wait for the control to clear it.
Applies to: EG and PEG Series 7 boilers
Source: EG / PEG Series 7 Boiler Manual, p. 74. Written in our own words; check the manual for your exact model.
U-Control display colors and symbols
Boiler · Ultra Series 4
Blue means space heating, purple means DHW, and red means maintenance or an error. A wrench symbol shows that scheduled maintenance is due. An exclamation mark shows that a problem was detected. A flashing display is a lockout.
- Blue: space heating call.
- Purple: DHW call.
- Red toggling between graphic and maintenance screens: maintenance due, shown during standby only.
- Red with exclamation mark: error or limit event.
- Flashing red: lockout; check the three screens (Figure 124, page 117).
Applies to: U-Control on Ultra Series 4
Source: Weil-McLain Ultra Series 4 boiler manual, p. 32. Written in our own words; check the manual for your exact model.
U-Control display colours and symbols
Boiler · Ultra Series 4
Blue means space heating or a button was pressed. Purple means DHW. Red means an error or limit event. A solid red screen with the exclamation mark is a non-shutdown failure such as an outdoor or system sensor. A flashing red display means lockout and needs attention to restart. A wrench symbol means maintenance is due and shows only in standby.
- Blue backlight: space heating active or a button was pressed.
- Purple backlight: DHW heating.
- Red backlight with exclamation mark: non-shutdown failure, boiler still runs.
- Flashing red display: lockout, check the boiler before restarting.
- Wrench symbol: maintenance date reached, tell the homeowner to call for service.
Applies to: U-Control on Ultra Series 4
Source: Weil-McLain Ultra Series 4 boiler manual, p. 32-33. Written in our own words; check the manual for your exact model.
Ultra-399 propane conversion uses the gas valve throttle screw
Boiler · Ultra Series 4
The Ultra-399 is converted by adjusting the gas valve throttling screw rather than changing the orifice. A flue gas analyzer is required to set the valve correctly. Improper settings can cause severe injury, death or property damage.
- Use a flue gas analyzer to set the gas valve throttling screw.
- Follow the Ultra-399 throttle adjustment procedure on page 41 of the manual.
Applies to: Ultra-399
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 49. Written in our own words; check the manual for your exact model.
Ultra-80 natural gas boilers need a burner kit for propane
Boiler · Ultra Series 4
Converting a natural gas Ultra-80 to propane also needs a burner in addition to the orifice change. The general instructions in this manual do not apply to this conversion.
- Use only the instructions included in the special-order conversion kit for Ultra-80 natural gas to propane.
Applies to: Ultra-80 natural gas boilers
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 48. Written in our own words; check the manual for your exact model.
Use only approved vent dampers
Boiler · EG / PEG Series 7
Only the dampers listed in the replacement parts tables are approved for EG and PEG Series 7 boilers. Any other damper can cause severe injury or death.
- Check the damper part number against the approved list before installing.
- Replace the damper with an approved size and type for the boiler model and steam or water application.
Applies to: EG 30 through EG 75 and PEG Series 7 boilers
Source: EG/PEG Series 7 boiler manual, p. 85. Written in our own words; check the manual for your exact model.
Use only genuine replacement parts
Boiler · ECO Tec series 3
Buy replacement parts through a local WM Technologies distributor. Modified or non-approved parts are not covered by warranty and can damage the boiler or impair operation.
- Order parts with the boiler model, size, part description and part number.
Applies to: ECO Tec series 3 80/110/150/199
Source: ECO Tec Series 3 boiler manual, p. 169. Written in our own words; check the manual for your exact model.
Use sweep elbows only in vent and air piping
Boiler · ECO Tec Series 3
Short-radius elbows affect boiler performance and are not allowed in vent or air piping.
- Use sweep 90° or 45° elbows for every elbow in vent and air piping.
- Count each elbow against the maximum equivalent length.
Applies to: ECO Tec Series 3 vent and air piping
Source: ECO Tec series 3 boiler manual, p. 26-32. Written in our own words; check the manual for your exact model.
Use sweep elbows only in vent and air runs
Boiler · ECO Tec Series 3
Short radius elbows reduce boiler performance. Use sweep elbows for all vent and air piping, including the horizontal, vertical and termination runs.
Applies to: All direct vent layouts
Source: ECO Tec Series 3 boiler manual, p. 32, 33, 35, 37, 39. Written in our own words; check the manual for your exact model.
Vent adapter and air intake fittings
Boiler · ECO Tec Series 3
Fittings for direct vent air and flue connections.
- Flue adapter (item 11) fits 3 inch PVC, 3 inch PP, and 3 inch SS.
- Air intake adapter (item 21) fits 3 inch PVC only.
- Internal flue pipe (item 12) carries exhaust from the heat exchanger to the flue adapter.
Applies to: Direct vent installations
Source: ECO Tec Series 3 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Vent damper clearances and harness rules
Boiler · EG / PEG Series 7
Clearance and harness-disconnect rules for the vent damper. Bypassing the damper lets carbon monoxide into the building.
- Keep at least 6 in. between the vent damper and any combustible material.
- Keep at least 46 in. between the jacket top and a combustible ceiling.
- Never jumper or bypass the vent damper.
- After the boiler has run once, disconnecting either end of the harness causes a safety shutdown. The boiler will not restart until the harness is reconnected.
Applies to: Boilers with vent damper
Source: EG/PEG Series 7 boiler manual, p. 18-19. Written in our own words; check the manual for your exact model.
Vent fittings and reducers
Boiler · Ultra Series 4
Fitting rules for vent and air piping. Use sweep elbows only and reducers in place of bushings.
- Use sweep elbows only in vent and air piping. Do not use short-radius elbows.
- When stepping down from 4 in to 3 in or 3 in to 2 in, use a tapered reducer with a PVC nipple at least 6 in long.
- Do not use a bushing. A bushing will not seal in the boiler flue/exhaust adapter.
- Put a 3x2 reducer at the boiler and at the termination for 2 in runs; put a 4x3 reducer at the boiler and at the termination for 3 in runs.
- Do not mix plastic piping types. Do not use cellular core pipe.
- Stainless AL29-4C vent: install a PVC-to-stainless adapter at the boiler, and at the termination unless using separate-pipe termination.
Applies to: All Ultra vent and air piping
Source: Weil-McLain Ultra Series 4 boiler manual, p. 18-19. Written in our own words; check the manual for your exact model.
Vent material limits and bird screens
Boiler · Ultra Series 4
Approved vent materials and the screens that must go on each termination.
- Use only the vent and air materials listed in Figure 13. Use only PVC Schedule 40 with concentric terminations; DWV, CPVC and ABS are not allowed there.
- Use locking collars on every joint of polypropylene vent systems.
- Put a bird screen on every vent and air termination. Screens are sold separately and most kits do not include them.
- For flex polypropylene, convert length with the listed equivalent factors (e.g., Duravent 4 in: 3.0 equivalent ft per ft). Keep the total equivalent length within the Figure 12 limits.
- Stainless AL29-4C vent must be installed with the certified manufacturer adapter.
Applies to: All Ultra vent and air piping
Source: Weil-McLain Ultra Series 4 boiler manual, p. 18-19. Written in our own words; check the manual for your exact model.
Vent piping installation practices
Boiler · SVF Series 1
Use sweep elbows where possible. Short-radius elbows add pressure loss and reduce allowable vent length.
- Install the vent manufacturer's adapter and reducer (if needed) at the boiler vent connection.
- Slope horizontal vent piping toward the boiler at least 1/4 in per foot.
- Support piping independently of the boiler every 5 ft on horizontal and vertical runs.
- Install a hanger within 6 in of any upturn in the piping.
- Use a locking collar on every joint of polypropylene vent piping.
- Keep total vent length within the maximum in Figure 25 (page 31).
Applies to: SVF 1500-3000 Series 1, Category IV venting
Source: Weil-McLain SVF Series 1 boiler manual, p. 34, p. 36. Written in our own words; check the manual for your exact model.
Venting must be Category IV
Boiler · SVF Series 1
SVF boilers need special venting for a Category IV boiler. Direct vent or direct exhaust is allowed through a side wall or roof. Category II venting is a different method covered on pages 27-28.
- Use only the vent materials and methods listed in the manual.
- Confirm the vent type (direct vent or direct exhaust) and pipe size before installing.
- Follow local codes and the National Fuel Gas Code or CSA B149.1 for the installation.
Applies to: SVF 1500-3000 Series 1
Source: Weil-McLain SVF Series 1 boiler manual, p. 120. Written in our own words; check the manual for your exact model.
Venting options and lengths
Boiler · ECO Tec
ECO Tec can be direct vent or direct exhaust. Direct vent runs out a sidewall, through the roof, or through dual pressure zones. Direct exhaust runs out a sidewall or through the roof. The vent can run up to 100 ft in PVC, CPVC, PP or stainless steel.
- Choose direct vent or direct exhaust based on the install location.
- Select a sidewall or through-the-roof termination for the chosen mode.
- Keep total vent length within 100 ft using PVC, CPVC, PP or SS pipe.
Applies to: ECO Tec Series 3 boilers, direct vent or direct exhaust
Source: ECO Tec Value Comparison Guide, p. 2. Written in our own words; check the manual for your exact model.
Vertical direct exhaust termination
Boiler · SVF Series 1
Vertical terminations use a coupling or open-end pipe termination and are kept clear of snow and debris.
- Locate the termination away from stones, foreign objects, leaves and sediment buildup.
- Keep the termination at least 12 in above grade and snow line.
- Install a vent manufacturer's bird screen in the open end.
- Keep exposed outside vent length to the maximum in Figure 27 to avoid condensate freezing.
Applies to: SVF 1500-3000 Series 1, direct exhaust vertical
Source: Weil-McLain SVF Series 1 boiler manual, p. 34. Written in our own words; check the manual for your exact model.
W-M plate orientation
Boiler · ECO Tec Series 3
The plate may be mounted in any of three listed orientations. Do not mount the plate vertical with the vent outlet pointing down.
Applies to: W-M sidewall vent/air plate
Source: ECO Tec Series 3 boiler manual, p. 37-38. Written in our own words; check the manual for your exact model.
Warm weather shutdown (WWSD)
Boiler · Evergreen Series 2
The boiler will not fire for space heating when outdoor temperature is above the WWSD setting. DHW operation is not affected.
Applies to: Evergreen Series 2 control
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 8. Written in our own words; check the manual for your exact model.
Wire entrances and strain relief
Boiler · SVF Series 1
Knockouts are in the rear of the terminal box. Strain relief is mandatory.
- Use the twelve rear knockouts in the terminal box for line and low voltage wiring.
- Install strain relief at every jacket knockout used.
- Do not run field wiring without strain relief; this can cause severe injury or damage.
Applies to: Boiler terminal box wiring
Source: SVF Series 1 boiler manual, p. 49. Written in our own words; check the manual for your exact model.
Wiring entrances and knockouts
Boiler · ECO Tec Series 3
The boiler has separate line voltage and low voltage entry points.
- Use the front left knockouts for line voltage and external pump voltage only; these lead to the high voltage box.
- Use the bottom right and top right knockouts for low voltage wiring only.
- Seal all wiring entrances when finished.
Applies to: ECO Tec Series 3 field wiring
Source: ECO Tec Series 3 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
Wiring notes for spark-ignited pilot ladder diagram
Boiler · EG, PEG, Series 7
Wiring must follow NEC and local codes. Pilot lead wires are not field replaceable, so replace the pilot assembly if they fail. Field replacement wire must be at least 105°C rated, except wires to a rollout TFE, which must be 200°C. Ladder diagram notes also cover zoning and configuration plug settings.
- Replace the pilot assembly if the pilot lead wires are damaged.
- Use at least 105°C wire when replacing original wire. Use 200°C wire for the rollout TFE wires.
- Use zone valves or circulators for multiple zoning, following the component manufacturer's instructions.
Applies to: EG water boilers, spark-ignited pilot system
Source: EG / PEG Series 7 boiler manual, p. 37. Written in our own words; check the manual for your exact model.
Write configuration: caution
Boiler · ECO Tec Series 3
Do not write a saved configuration file unless you are sure it is correct for the application. Write only works if the model number and Master/Shadow/Single setting match the boiler. To view saved files, use WRITE Configuration in the app instead of READ.
Applies to: ECO Tec Series 3 boilers with WM ProTools app
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 187. Written in our own words; check the manual for your exact model.
Zone circulator relay requirement and wiring limits
Boiler · ECO Tec Series 3
A circulator whose load is above the rated limits must be run through an external relay with its own power supply. The rating values on the page are garbled in the source, so confirm the exact figures from the wiring section of the manual.
- Check each circulator's full load amps, locked rotor amps and inrush amps against the limits in the manual.
- Provide an external relay and external power to any circulator that exceeds the limits.
- For DHW direct piping, confirm the DHW circulator handles the water heater and piping pressure drop.
Applies to: ECO Tec Series 3 circulator wiring
Source: ECO Tec Series 3 boiler manual, p. 98. Written in our own words; check the manual for your exact model.
Zone valve wiring warning
Boiler · ECO Tec Series 3
Three-wire zone valves must not be used. The voltage on the valve end switch will damage the control. Use only four-wire zone valves with isolated end switches.
- Confirm all zone valves are four-wire with isolated end switches before wiring.
- Replace any three-wire zone valves before powering the control.
Applies to: Zone valve systems on the ECO Tec control
Source: ECO Tec Series 3 boiler manual, p. 111. Written in our own words; check the manual for your exact model.
AQUA PLUS water heater piping rules
Water heater · Ultra Series 4, AQUA PLUS
AQUA PLUS indirect water heaters need a diaphragm or bladder expansion tank and an automatic air vent. Connect the water heater loop per the AQUA PLUS manual.
- Use a diaphragm or bladder expansion tank with AQUA PLUS water heaters. Do not use a closed-type tank.
- Install the DHW relief valve in the top tapping of the AQUA PLUS water heater.
- Keep the water heater loop within 12 in. apart at the primary/secondary tees where shown.
- With DHW as priority 1, the U-Control turns off space heating during DHW heating. The boiler circulator stops, unless a timeout setting overrides it.
Applies to: Ultra boilers with AQUA PLUS water heaters
Source: Ultra Series 4 boiler manual, p. 14. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.