Weil-McLain · Boiler troubleshooting
Access and clean heat exchanger, Ultra-80 and Ultra-105
What is going on
Removes the blower, venturi, gas valve and cover plate as one assembly for pin-side cleaning.
Check in this order
- Close the external manual gas valve.
- Disconnect the flexible gas line at its flare fitting.
- Remove the air silencer from the air adapter on the blower inlet.
- Disconnect gas valve plug, blower power plug, blower control connector, ignition cable and ground wire.
- Remove the nuts holding the heat exchanger cover plate and release the plate.
- Pull the blower/venturi/gas valve/cover plate assembly out of the boiler.
- Vacuum the heating surfaces. Do not use solvent.
- If needed, wash with clean warm water. For further cleaning use the heat exchanger cleaning tool or 20-gauge or lighter sheet metal, 3/4 in wide by about 18 in long.
- Inspect the cover plate insulation and replace it if damaged. Read the ceramic fiber warning on page 109 first.
- Reinstall the assembly. Tighten cover nuts in two or three passes to the sequence in Figure 126; final torque must not exceed 50 in-lb (±10 in-lb).
- Make sure the O-ring in the gas valve inlet adapter block is in good condition and installed if the block was removed. Without it a gas leak can occur.
- Reconnect the wiring, flexible gas line and air silencer.
- Perform a soap suds leak test on all interior gas piping after starting the boiler.
Applies to: Ultra-80 and Ultra-105 only
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 126. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.