0-10VDC output for lead/lag and variable speed pump

Evergreen Series 2

What is going on

The 0-10VDC output can drive lead/lag systems or a variable speed boiler pump.

Check in this order

  1. For lead/lag, set MAX RATE VOLTS and MIN RATE VOLTS to the desired output range.
  2. The output only works when AHD is in use, an AHD call is active, Temp Dependent is set to Yes, and valid sensors are present.
  3. For a variable speed pump, connect the output to the pump's 0-10VDC input.
  4. Set VARIABLE SPEED MAX RATE VOLTS for high fire, VARIABLE SPEED MIN RATE VOLTS for low fire, and VOLTS WHEN BURNER OFF for burner-off operation.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.