Weil-McLain · Boiler troubleshooting
0-10VDC output for lead/lag and variable speed pump
What is going on
The 0-10VDC output can drive lead/lag systems or a variable speed boiler pump.
Check in this order
- For lead/lag, set MAX RATE VOLTS and MIN RATE VOLTS to the desired output range.
- The output only works when AHD is in use, an AHD call is active, Temp Dependent is set to Yes, and valid sensors are present.
- For a variable speed pump, connect the output to the pump's 0-10VDC input.
- Set VARIABLE SPEED MAX RATE VOLTS for high fire, VARIABLE SPEED MIN RATE VOLTS for low fire, and VOLTS WHEN BURNER OFF for burner-off operation.
Applies to: Evergreen 110/155/220/299/300/399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
- Access and clean heat exchanger, Ultra-80 and Ultra-105
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.