Weil-McLain · Boiler troubleshooting

0-10 VDC remote target input wiring and setup

SlimFit Series 2

What is going on

Optional remote target. A 0-10 VDC signal on P15-5/6 (positive on terminal 6, common on terminal 5) adjusts the supply target temperature through the TARGET ADJUST setting. It replaces the outdoor sensor as the target modifier. The control does not control the target itself. A dry contact heat demand must still be wired to an input to start a call for heat.

Check in this order

  1. Wire the 0-10 VDC signal to P15 terminal 6 (positive) and terminal 5 (common).
  2. Assign the heat demand dry contact to an unused input and its pump or valve to the matching output.
  3. Assign a priority to that input in the Wizard or contractor menu.
  4. Use PRIORITY 1 for DHW if used, and PRIORITY 2 for space heating.
  5. Set TARGET ADJUST to 0-10V in the PRIORITY 2 menu.
  6. Set VOLTS FOR MAX and SUPPLY MAX for the highest target temperature.
  7. Set VOLTS FOR MIN and SUPPLY MIN for the lowest target temperature.
  8. Voltages between the two points give a proportional target between SUPPLY MIN and SUPPLY MAX.

Applies to: SF1000L/R, SF1500L/R, SF2000L/R

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 57. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.