0-10 Vdc output for lead/lag and variable speed pump

SVF 500/600 Series 1

What is going on

The 0-10 Vdc output (J16 terminals 7 and 8) can drive a lead/lag partner or a variable speed boiler pump. The output follows the firing rate.

Check in this order

  1. For lead/lag connect the output on the Master or Shadow boiler.
  2. For lead/lag on a multi-boiler system, assign Local 1 or Local 2 to use Additional Heat Demand (AHD).
  3. For a single boiler, connect the output to any input and assign Priority 1, 2 or 3 to use AHD.
  4. Set MAX RATE VOLTS and MIN RATE VOLTS to the desired output range.
  5. For a variable speed pump, connect the output to the pump's 0-10 Vdc input.
  6. Set VARIABLE SPEED MAX RATE VOLTS (voltage at high fire), VARIABLE SPEED MIN RATE VOLTS (voltage at low fire) and VOLTS WHEN BURNER OFF.
  7. Refer to page 87 for the variable speed pump settings.

Applies to: SVF 500/600 Series 1 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual 550-100-273/1224, p. 78. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.