0-10 Vdc output for lead/lag and variable speed pump
What is going on
The 0-10 Vdc output (J16 terminals 7 and 8) can drive a lead/lag partner or a variable speed boiler pump. The output follows the firing rate.
Check in this order
- For lead/lag connect the output on the Master or Shadow boiler.
- For lead/lag on a multi-boiler system, assign Local 1 or Local 2 to use Additional Heat Demand (AHD).
- For a single boiler, connect the output to any input and assign Priority 1, 2 or 3 to use AHD.
- Set MAX RATE VOLTS and MIN RATE VOLTS to the desired output range.
- For a variable speed pump, connect the output to the pump's 0-10 Vdc input.
- Set VARIABLE SPEED MAX RATE VOLTS (voltage at high fire), VARIABLE SPEED MIN RATE VOLTS (voltage at low fire) and VOLTS WHEN BURNER OFF.
- Refer to page 87 for the variable speed pump settings.
Applies to: SVF 500/600 Series 1 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual 550-100-273/1224, p. 78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.