Weil-McLain · Boiler troubleshooting
0-10 VDC remote modulation input wiring and setup
What is going on
Remote modulation from an external controller on P15-5/6 (positive on terminal 6, common on terminal 5). This works only with a single boiler, not a boiler in a network. Using 0-10 VDC replaces INPUT 1 as the heat demand. The control can use 0-10 VDC for either target adjust or modulation, but not both.
Check in this order
- Wire the external controller signal to P15-5/6 with positive on terminal 6 and common on terminal 5.
- If DHW is used, connect the DHW aquastat to INPUT 2 or INPUT 3 and assign it to PRIORITY 1.
- Use PRIORITY 2 for the modulated system. The default settings suit space heating.
- After the Wizard, go to ASSIGN INPUTS and change INPUT 1 SOURCE from TT1 to 0-10V.
- Expect OUTPUT 1 (120 VAC) to switch on and off with the heat demand. This output can run the system pump.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R (single boiler only)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 Vdc output for lead/lag and variable speed pump
- 0-10 VDC remote modulation input
- 0-10 VDC remote target input wiring and setup
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 58. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.