Output activation rule for zone and DHW circulators

Evergreen Series 2

What is going on

Each 120VAC output only energizes when its input is calling and that input's priority is active. A zone can call without the pump running if the boiler is not on that priority.

Check in this order

  1. Wire each zone or DHW circulator to its matching output.
  2. Wire the matching thermostat or aquastat contact to its input.
  3. Confirm the priority for that input/output pair is active when testing, since the pump stays off if the boiler is running another priority.
  4. If an output must drive a low-voltage circuit or an isolated contact, add an isolation relay.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.