Output activation rule for zone and DHW circulators
What is going on
Each 120VAC output only energizes when its input is calling and that input's priority is active. A zone can call without the pump running if the boiler is not on that priority.
Check in this order
- Wire each zone or DHW circulator to its matching output.
- Wire the matching thermostat or aquastat contact to its input.
- Confirm the priority for that input/output pair is active when testing, since the pump stays off if the boiler is running another priority.
- If an output must drive a low-voltage circuit or an isolated contact, add an isolation relay.
Applies to: Evergreen 110/155/220/299/300/399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 49. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.