Weil-McLain · Boiler troubleshooting

Place and level the boiler on its legs

SlimFit Series 2

What is going on

Set the boiler in position using only the jacket corner posts. Casters are for moving only and must not carry the boiler weight.

Check in this order

  1. Roll the boiler down the ramp and move it into position, pushing only on the jacket corner posts.
  2. Adjust the leveling legs down until they contact the floor.
  3. Keep adjusting the legs until the bottom of the base is 5¼ inches above the floor.
  4. Check level and extend the legs further as needed until the boiler is level.
  5. Confirm the boiler is not resting on the casters.

Applies to: SlimFit 1000-2000 Series 2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.