Pre-troubleshooting checks before diagnosing a fault
What is going on
Basic checks before working on the control or components. Turn off power before servicing and never jumper a device except for momentary testing.
Check in this order
- Use Figure 139 tools and kits (see the tools tip).
- Measure supply voltage to the boiler 120VAC, with a range of 102VAC minimum to 132VAC maximum.
- Review the control's last six lockout histories in the DIAGNOSTICS menu under FAULT HISTORY. Record Ignition Retries, Manual Reset Count and Auto Reset Count.
- Confirm the thermostat is calling for heat and its contacts, including any zone controls, are closed. Check for 24VAC between the thermostat wire nuts and ground.
- Confirm all external limit controls are installed and closed, or temporarily jumpered for testing only.
- Confirm connectors are fully seated at the module and at the originating control.
- Check gas pressures. Lockup pressure with no flow must not exceed 14 in w.c. (355 mm). On high fire, inlet pressure must not drop below the minimum on page 24.
- Record the boiler size and CP number from the right side exterior of the jacket before calling for assistance.
- Reinstall the jacket door securely after servicing so the boiler does not draw room air.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 159. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.