Pre-troubleshooting checks before diagnosing a fault

ECO Tec Series 3

What is going on

Basic checks before working on the control or components. Turn off power before servicing and never jumper a device except for momentary testing.

Check in this order

  1. Use Figure 139 tools and kits (see the tools tip).
  2. Measure supply voltage to the boiler 120VAC, with a range of 102VAC minimum to 132VAC maximum.
  3. Review the control's last six lockout histories in the DIAGNOSTICS menu under FAULT HISTORY. Record Ignition Retries, Manual Reset Count and Auto Reset Count.
  4. Confirm the thermostat is calling for heat and its contacts, including any zone controls, are closed. Check for 24VAC between the thermostat wire nuts and ground.
  5. Confirm all external limit controls are installed and closed, or temporarily jumpered for testing only.
  6. Confirm connectors are fully seated at the module and at the originating control.
  7. Check gas pressures. Lockup pressure with no flow must not exceed 14 in w.c. (355 mm). On high fire, inlet pressure must not drop below the minimum on page 24.
  8. Record the boiler size and CP number from the right side exterior of the jacket before calling for assistance.
  9. Reinstall the jacket door securely after servicing so the boiler does not draw room air.

Applies to: 80/110/150/199 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 159. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.