Viessmann · Boiler troubleshooting

Low water cut-off connection (CM2)

Vitocontrol-S VD2/CT3/CM2

What is going on

Wire an external low water cut-off device to the control.

Check in this order

  1. Remove the jumper between terminals 21 and 22.
  2. Connect the LWCO device as shown in the diagram, and check its own manual for the interconnection details.

Applies to: CM2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.