Viessmann · Boiler troubleshooting
Oil piping to the burner
What is going on
Piping must meet local codes, the burner and pump instructions, and CSA B139 in Canada or NFPA 31 in the USA. Oil supply pressure to the fuel unit must not exceed 3 psig.
Likely causes
- Oil pressure above 3 psig can damage the fuel unit
- Teflon tape or compression fittings can cause valve failure or leaks
Check in this order
- Use a pressure-limiting device on the oil supply.
- Do not use Teflon tape as pipe sealant. Use non-hardening joint compound on all threads.
- Do not use compression fittings.
- Run underground oil lines in encasement to prevent leaks into the ground.
- If any part of the tank is above burner level, install an anti-siphon device.
- Use swing joints or copper tubing at the tank connections.
- Connect the burner oil line with a flare fitting, leaving the burner door free to swing fully open.
Applies to: Oil supply to the VR1 burner
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service manual, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.