ECO Tec S2 manual reset high temperature limit

Weil-McLain ECO Tec Series 2

What is going on

The control has a manual reset high limit set on the Boiler Settings screen (shown at 200 F on the setting screen in the manual). If boiler water goes over it, the boiler locks out.

Likely causes

  • Low or no water flow through the heat exchanger
  • Circulator not running or air-bound
  • Zone valves closed with no by-pass
  • Limit set lower than the system needs

Check in this order

  1. Check the boiler circulator runs and the system is full and purged of air.
  2. Check flow on direct-connect piping the rise across the heat exchanger at high fire should be about 20 to 35 F, not more.
  3. Zone valve systems need a by-pass pressure regulator unless the pump is protected against dead-heading.
  4. Check the setting under Boiler Settings. It can be lowered for some systems but is a safety setting.
  5. Fix the cause, then reset the control.

Applies to: ECO Tec 80/110/150/199 Series 2 heating only

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Boiler settings screen Figure 20 p.17; Wizard boiler settings p.78-80; Direct connect piping p.47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.