Radiant heating with zone valves, primary/secondary piping
What is going on
Typical radiant layout. The boiler works in condensing mode, so return water temperature does not need regulating. A high limit protects the radiant tubing.
Check in this order
- Size system piping and circulators for the flow and pressure drop needed.
- Add a high limit control (Fig. 10, item 22) set to protect the radiant tubing.
- Wire the high limit to the manual reset or automatic reset external limit circuit on the control.
- Install the flow/check valve on the boiler outlet.
- Provide an expansion tank per p. 14.
- Assign DHW and space heating priorities as needed. Priority 3 is the DHW choice when space heating has priority. The control will not run DHW in that case.
- Connect zone valve end switches to a space heating priority input (default Priority 2). Use isolation relays for 3-wire end switches.
Applies to: SF-550 and SF-750
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.