Weil-McLain · Boiler troubleshooting

Radiant heating with zone valves, primary/secondary piping

SlimFit Series 3

What is going on

Typical radiant layout. The boiler works in condensing mode, so return water temperature does not need regulating. A high limit protects the radiant tubing.

Check in this order

  1. Size system piping and circulators for the flow and pressure drop needed.
  2. Add a high limit control (Fig. 10, item 22) set to protect the radiant tubing.
  3. Wire the high limit to the manual reset or automatic reset external limit circuit on the control.
  4. Install the flow/check valve on the boiler outlet.
  5. Provide an expansion tank per p. 14.
  6. Assign DHW and space heating priorities as needed. Priority 3 is the DHW choice when space heating has priority. The control will not run DHW in that case.
  7. Connect zone valve end switches to a space heating priority input (default Priority 2). Use isolation relays for 3-wire end switches.

Applies to: SF-550 and SF-750

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.