Viessmann · Boiler troubleshooting

Boiler hot but heating circuit pumps not running

Vitotronic 200

What is going on

Check whether the pump is being called on, then check voltage and fuses.

Likely causes

  • Pump not activated by control logic
  • Faulty pump connection or pump
  • Additional control such as a high limit aquastat blocking the pump
  • Blown fuse F2 in the Vitotronic
  • Blown fuses F1 to F4 in the Power Pump Module
  • Defective mixing valve motor or pump connector

Check in this order

  1. Turn the emissions test switch to the position shown in the manual so the pumps run.
  2. If the pumps run the pump is not being called. Check heating curves, desired values, heating circuit pump logic, external equipment (such as Switching Module-V) and high domestic hot water demand.
  3. If the pumps do not run measure voltage between L and N on the connector in the Power Pump Module.
  4. If voltage is present check the pump connection and the pump, then check any added control equipment such as a high limit aquastat.
  5. If voltage is not present check fuse F2 in the Vitotronic and fuses F1 to F4 in the Power Pump Module.
  6. If a fuse is defective disconnect all pump and mixing valve motor connectors, replace the fuse, then reconnect one unit at a time to find the defective unit.

Applies to: Vitotronic 200 KW2 heating circuit pumps

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 200 service instructions, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.