Viessmann · Boiler troubleshooting
Boiler hot but heating circuit pumps not running
What is going on
Check whether the pump is being called on, then check voltage and fuses.
Likely causes
- Pump not activated by control logic
- Faulty pump connection or pump
- Additional control such as a high limit aquastat blocking the pump
- Blown fuse F2 in the Vitotronic
- Blown fuses F1 to F4 in the Power Pump Module
- Defective mixing valve motor or pump connector
Check in this order
- Turn the emissions test switch to the position shown in the manual so the pumps run.
- If the pumps run the pump is not being called. Check heating curves, desired values, heating circuit pump logic, external equipment (such as Switching Module-V) and high domestic hot water demand.
- If the pumps do not run measure voltage between L and N on the connector in the Power Pump Module.
- If voltage is present check the pump connection and the pump, then check any added control equipment such as a high limit aquastat.
- If voltage is not present check fuse F2 in the Vitotronic and fuses F1 to F4 in the Power Pump Module.
- If a fuse is defective disconnect all pump and mixing valve motor connectors, replace the fuse, then reconnect one unit at a time to find the defective unit.
Applies to: Vitotronic 200 KW2 heating circuit pumps
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 200 service instructions, p. 43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.