Piping the boiler in a heating/cooling system with a chiller

Vitocrossal 300 CA3B Dual Fuel

What is going on

When the boiler shares a system with a chiller, the chilled water must be piped in parallel with the boiler and isolated by valves so chilled water cannot enter the boiler. Coils in the air handlers can expose the boiler loop to refrigerated air, so flow control or another automatic method is needed to stop gravity circulation during cooling. Follow the chiller maker's requirements as well.

Check in this order

  1. Pipe the chilled water in parallel with the boiler.
  2. Install valves so chilled water cannot enter the boiler.
  3. Fit flow control valves or another automatic means to stop gravity circulation of boiler water during cooling.
  4. Set valve V2 open and V1 closed for cooling season, and V1 open and V2 closed for heating season.
  5. Attach metal tags to the changeover valves.
  6. Run the system circulating pump from its own on/off switch, not from the boiler control.

Applies to: Vitocrossal 300 CA3B Dual Fuel with chiller or cooling coils

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.