Viessmann · Boiler troubleshooting

Cascade strategy: net calorific 2

Vitocontrol-S VD2/CT3/CM2

What is going on

An extra boiler starts only when all active burners at maximum output cannot reach the set supply temperature. A boiler shuts down when its burner is at minimum output because of a large negative deviation and output is still too high. Gives long burner run times. Net calorific 2 is the only strategy suitable for series arrangements.

Check in this order

  1. Start-up the start-up integral must exceed the limit set in coding 45. The next boiler in the sequence then starts.
  2. Shutdown the shutdown integral must exceed the limit set via coding 3d: 1, then the last boiler started is shut down.

Applies to: Vitocontrol-S VD2/CT3/CM2 cascade, series arrangement

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 125, 127. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.