Viessmann · Boiler troubleshooting

Prepare the power pump module for CombiPLUS

Vitodens 100-W WB1B

What is going on

Remove the parts that block CombiPLUS operation and the room thermostat jumper, using static-safe handling.

Check in this order

  1. Discard the static-sensitive parts carefully, following electrostatic discharge procedures.
  2. Remove the jumper pin from terminal X8 (CombiPLUS) and discard it.
  3. If a room thermostat is connected, remove the jumper cable from terminal block X4 (terminals 3 and 4) and discard it.
  4. Remove the second and fourth hole plugs from the base of the power pump module and discard them.

Applies to: Vitodens 100-W WB1B power pump module

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W WB1B installation and service instructions, p. 31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.