Reinstalling the burner after service

Vitodens 100-WWB1B

What is going on

Burner refit sequence with torque values and gas connection checks.

Check in this order

  1. Replace the electrical cables from the fan motor, mount the burner, and diagonally tighten the 4 Torx T-30 screws to 4 Nm (35 lb.in.).
  2. Insert a new gasket and tighten the gas connection pipe fitting to 15 Nm (132 lb.in.).
  3. Plug the Venturi extension into the fan.
  4. Replace the electrical cables from the gas valve and the electrode block.
  5. Open the gas shutoff valve and switch on the power supply.
  6. Check the gas connection for tightness.
  7. Install the front panel (see page 52).

Applies to: Vitodens 100-W WB1B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W WB1B installation and service instructions, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.