CSD-1 fixed high limit test, simulation #2 (closed boiler valve)

Vitodens 200-W B2HA

What is going on

Alternate field test of the fixed high limit with the boiler valve closed. Overheating is possible.

Check in this order

  1. Close the boiler valve.
  2. Jumper across the flow switch.
  3. Run the boiler at high fire. On B2TB models, set coding address 06 to maximum.
  4. Keep the boiler running until the fixed high limit trips.
  5. Once the limit has tripped, slowly open the boiler valve to cool the boiler down.

Applies to: Vitodens 200-W B2HA boilers, where required by law

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA installation manual, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.