CSD-1 fixed high limit test, simulation #2 (closed boiler valve)
What is going on
Alternate field test of the fixed high limit with the boiler valve closed. Overheating is possible.
Check in this order
- Close the boiler valve.
- Jumper across the flow switch.
- Run the boiler at high fire. On B2TB models, set coding address 06 to maximum.
- Keep the boiler running until the fixed high limit trips.
- Once the limit has tripped, slowly open the boiler valve to cool the boiler down.
Applies to: Vitodens 200-W B2HA boilers, where required by law
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA installation manual, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.