Viessmann · Boiler troubleshooting

Replace ionization electrode block

Vitocrossal 200 CM2

What is going on

Replaces the flame sensing electrode block on the burner door. Use only the new parts from the kit.

Check in this order

  1. Disconnect the ionization cable from the electrode terminal.
  2. Remove the four M12 burner door bolts and washers. Disconnect the gas line and plugs 40/156, 53 and 40 from the burner control bracket, and plugs 90 and 41 from the burner control.
  3. Open the burner door.
  4. Remove the electrode terminal nut, serrated washer and O-ring. Remove the inner electrode.
  5. Remove the two M6 screws and washers, then the electrode block and gasket. Discard the block.
  6. Fit the new block and gasket with new parts from the kit.
  7. Check the electrode-to-burner dimension against the drawing and adjust carefully if needed.
  8. Tighten the M12 burner door bolts and the M6 electrode screws to the torque in the torque table.
  9. Leak test the reconnected gas line.

Applies to: Ionization electrode

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.