Monthly checks by owner/operator

Vitocrossal 300 CA3B Dual Fuel

What is going on

Monthly inspection items the owner or operator should check.

Check in this order

  1. Check system pressure frequently.
  2. Confirm the boiler control operates correctly per the control's operating instructions.
  3. Inspect all seals and retighten or replace as needed.
  4. Confirm adequate combustion and ventilation air into and out of the mechanical room.
  5. Confirm nothing blocks combustion and ventilation air, and no chemicals, garbage, gasoline, combustibles, flammable vapors or liquids are stored near the boiler.
  6. Check for water on the floor from the relief valve discharge or any pipe, joint, valve or air vent.
  7. Test the pressure relief valve and confirm it operates correctly, per the valve instructions.
  8. Check all operating high limits.
  9. If used, check the condensate neutralization system and the condition and fill level of the media.
  10. Check the pH of the flue gas condensate (minimum 6.5).
  11. Check external vent pipe joints for moisture and check for ice on the vent pipe or chimney outlet in winter.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service, p. 157. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.