Viessmann · Boiler troubleshooting

Check and adjust CO2 at lower heating output

Vitocrossal 200 CM2

What is going on

Set the boiler to low fire and adjust CO2 with the lower-output screw. Recheck both points after any change.

Check in this order

  1. Press the B G button until the service display counts down to 0 (lower output).
  2. Measure CO2 at the flue pipe.
  3. If CO2 must be adjusted, remove cover B.
  4. Turn adjusting screw A with a Torx 40 in small steps. Clockwise raises CO2 (more gas). Counter-clockwise lowers CO2 (less gas).
  5. Record the actual value on the maintenance record (page 64).
  6. Recheck the upper and lower outputs through the burner programming unit and repeat if needed.
  7. Press S F and B G together for more than 2 seconds to return the burner to operating mode.

Applies to: Vitocrossal 200 CM2 186 to 311

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.