Viessmann · Boiler troubleshooting
Check and adjust CO2 at lower heating output
What is going on
Set the boiler to low fire and adjust CO2 with the lower-output screw. Recheck both points after any change.
Check in this order
- Press the B G button until the service display counts down to 0 (lower output).
- Measure CO2 at the flue pipe.
- If CO2 must be adjusted, remove cover B.
- Turn adjusting screw A with a Torx 40 in small steps. Clockwise raises CO2 (more gas). Counter-clockwise lowers CO2 (less gas).
- Record the actual value on the maintenance record (page 64).
- Recheck the upper and lower outputs through the burner programming unit and repeat if needed.
- Press S F and B G together for more than 2 seconds to return the burner to operating mode.
Applies to: Vitocrossal 200 CM2 186 to 311
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.