Navien · Boiler troubleshooting
Connecting the vent pipe to the vent collar
What is going on
Correct insertion and clamping of the exhaust pipe onto the boiler collar.
Check in this order
- Cut the vent pipe square (90°) and deburr it.
- Lubricate the pipe end with water only. Do not use grease, primer or cement on the appliance connection.
- Mark the pipe 2-3/4 in (70 mm) from its end.
- Start the run with straight pipe. Do not use a street elbow at the collar.
- Push the pipe in with a twisting motion until it bottoms in the collar, leaving the mark hidden.
- Tighten the clamp with an 8 mm socket.
- Turn on the boiler and bubble-test all exhaust joints for gas leaks.
Applies to: NCB700 series
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 61-62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.