Navien · Boiler troubleshooting
Adjust gas/air ratio (CO2) with combustion analyzer
What is going on
Check and adjust CO2 at MIN and MAX firing using the emissions port.
Check in this order
- Loosen the screw, rotate the plate and remove the gasket to reach the emissions monitoring port.
- Insert the analyzer probe into the port.
- Activate multiple zones and set the boiler to 1-stage MIN mode. Measure CO2.
- Compare the reading with the CO2 table. If it is not within 0.5% of the listed value, adjust the set screw.
- Activate multiple zones and set the boiler to 2-stage MAX mode. Measure CO2 again.
- If the reading is out of range, adjust the set screw.
- To adjust, use a 5/32 in or 4 mm Allen wrench and turn the set screw no more than 1/4 turn. Clockwise raises CO2; counterclockwise lowers CO2.
- Set screw is behind the screw-on cap; remove the cap to reach it. Figure reference is 7 or 9.
Applies to: Propane gas/air ratio check
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NFC-H propane and high altitude conversion guide, p. 2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.