Add device profiles in web configurator
What is going on
Select the profile for each attached device and assign its Node-ID. Repeat for all devices.
Check in this order
- Set the field protocol by entering its number in the Protocol Selector Value and clicking Submit; wait for the reset.
- Under Active Profiles, click the add button.
- Select the device profile from the drop-down list.
- Enter the device Node-ID assigned in the device communication settings.
- Click Submit to add the profile; repeat for each device.
- Confirm the profile appears under Active Profiles.
- If more than one device is connected, set BACnet Virtual Server Nodes to yes; otherwise leave it at No.
Applies to: Gateway profile setup
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien Modbus/BACnet gateway installation and operation manual, p. 12-13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.