Navien · Boiler troubleshooting

Adjust gas/air ratio with digital manometer

NFC-H

What is going on

Alternate method to check the gas/air ratio when no analyzer is available.

Check in this order

  1. Connect the digital pressure manometer to the port as shown in the manual (Figure 8). Use the positive side of a dual port manometer.
  2. Activate multiple zones and set the boiler to the required mode.
  3. Compare the reading with the value in the pressure table (-0.02 in ±0.01 in for propane).
  4. If the value is out of range, locate the set screw and turn it no more than 1/4 turn clockwise to adjust the gas valve.
  5. Use a 5/32 in or 4 mm Allen wrench. Remove the screw-on cap to reach the set screw.

Applies to: Propane gas/air ratio check

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NFC-H propane and high altitude conversion guide, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.