Air handler and cooling coil piping

NCB700

What is going on

When the boiler feeds heating coils in air handlers that may be exposed to chilled air, the coil piping must prevent cooling fluid from entering the boiler. Gravity circulation during cooling must also be prevented.

Likely causes

  • Cooling fluid entering the boiler through shared piping
  • Gravity circulation of boiler water through coils during the cooling cycle

Check in this order

  1. Run cooling piping parallel to the boiler piping.
  2. Install the correct valves to stop cooling fluid from reaching the boiler.
  3. Use flow check valves or other automatic devices to prevent gravity flow from the boiler through coils during cooling.
  4. Wire the air handler and thermostat as shown in the wiring section.
  5. Do not energize the boiler until electrical wiring is complete.

Applies to: NCB700 with air handler or cooling system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 196. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.