Air handler interface operation
What is going on
With a thermostat and air handler, the boiler's A/H contacts stop air handler operation when space heating is not running because of DHW demand, boiler errors, or low water conditions.
Likely causes
- DHW supply demand
- Boiler error
- Low water condition
- Thermostat satisfied
- Boiler turned off
Check in this order
- Set PCB DIP SW2 #7 to OFF to use a thermostat with the air handler.
- Wire the air handler per the space heating installation guidelines (section 3.1.1, p. 50).
- Confirm the air handler stops when DHW demand, errors or boiler off occur, as expected for the interface.
Applies to: NCB700 with air handler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.