Check flue gas collector and boiler body for leakage
What is going on
Flue gas leaks must be ruled out during commissioning at full load. Gaskets can be checked with a dew point hygrometer. Condensed water on the outside of the flue gas collector or on the thermal insulation also indicates a leak.
Likely causes
- Gasket leaks at the flue gas collector or boiler body
- Leaking seals on the boiler body
Check in this order
- Run the boiler at full load.
- Detach thermal insulation parts if necessary to reach the gaskets.
- Check gaskets with a dew point hygrometer.
- Look for traces of condensed water on the flue gas collector or insulation.
- Confirm all flue gases are safely vented to the outdoors.
Applies to: Vitocrossal 300 CA3B Dual Fuel boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.