Accessory power supply and cabling
What is going on
Accessory power is connected at the control and switched by the system on/off switch. The Vitotronic 200-H HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control need a separate 120 VAC supply from a wall receptacle. Only one accessory part or switch contact can be connected to a plug contact at a time. Cabling may be needed for an outdoor sensor, HK1B control, mixing valve kit, remote operating mode switching, remote disable, alarm output, wall-mount base, circulating pump and zone thermostats. Cables near the control must not be secured to the control bracket, and cable temperature ratings must not be exceeded.
Check in this order
- Connect accessory power at the control; it switches with the system on/off switch.
- Provide a separate 120 VAC wall receptacle supply for HK1B, mixing valve kit and Solartrol.
- Connect only one accessory or switch contact per plug contact.
- Do not secure connecting cables to the control unit bracket.
Applies to: Vitocrossal 300 CU3A electrical connections
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A Installation Instructions, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.