Thermostat and zone valve wiring
What is going on
Thermostat circuits are dry contacts. Never apply 24VAC to them.
Check in this order
- Do not supply 24-volt power to the thermostat circuits or any other application.
- If a thermostat needs continuous 24VAC, connect its common wire ('C') as shown in the wiring diagram.
- Keep the total draw at 120 mA or less at 24VAC per thermostat.
- For 3-wire zone valves, use relays to give the control dry contacts. Valve end switches carry 24VAC from the valve.
- Set the thermostat anticipator to 0.1 A.
Applies to: Evergreen 110/155/220/299/300/399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.