Weil-McLain · Boiler troubleshooting

Thermostat and zone valve wiring

Evergreen Series 2

What is going on

Thermostat circuits are dry contacts. Never apply 24VAC to them.

Check in this order

  1. Do not supply 24-volt power to the thermostat circuits or any other application.
  2. If a thermostat needs continuous 24VAC, connect its common wire ('C') as shown in the wiring diagram.
  3. Keep the total draw at 120 mA or less at 24VAC per thermostat.
  4. For 3-wire zone valves, use relays to give the control dry contacts. Valve end switches carry 24VAC from the valve.
  5. Set the thermostat anticipator to 0.1 A.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.