Rinnai · Boiler troubleshooting
Condensate drain installation
What is going on
Rules for routing the condensate drain so it does not freeze, clog, or back up. Do not share the drain with the pressure relief valve or an AC evaporator coil drain. The boiler has an built-in condensate trap, so do not add an external trap.
Likely causes
- Drain line sized smaller than 1/2 in. MNPT
- Drain line frozen or pitched upward
- Drain submerged in water or closed to atmosphere
- Drain shared with the relief valve or AC coil drain
Check in this order
- Use only corrosion-resistant pipe such as PVC or plastic hose, at least 1/2 in. MNPT along its full length.
- Slope the drain toward a floor drain or condensate pump, keep it as short as possible, and pitch it downward.
- Leave the outlet open to atmosphere, not under water or other fluid.
- Route outdoor runs through an interior wall or between insulation and an interior wall, and wrap freeze-prone sections with an approved heat source.
- Install a condensate pump if no floor drain is available or the drain sits above the boiler outlet.
- Install a condensate neutralizer kit where local codes require pH treatment, following its manual.
- Do not install an external condensate trap.
Applies to: I-Series Plus condensing combi boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.