Rinnai · technician tips

Rinnai service menus, test modes and resets

111 tips for air handler, boiler, combi boiler, tankless water heater, wall furnace: access codes, button combinations, test modes and the resets you need at the appliance.

Jump to: Access & passwords (10) · Button combinations (10) · Service & test modes (14) · Reset & cancel (14) · Settings shortcuts (15) · Commissioning (23) · Other (25)

Access & passwords

Installer and service menu codes, and how to get into them.

Enter the Installer menu (password)

Air handler · Canadian Air Handler

Password-protected menu for changing operating parameters.

  1. Enter the password with the buttons in this order: down, center, up, center.
  2. Up/down change menu, line or value; center selects or validates.

Applies to: Rinnai Canadian hydronic air handler (CAH)

Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), Software Settings p.41-42. Written in our own words; check the manual for your exact model.

Enter the Troubleshoot menu (password)

Air handler · Canadian Air Handler

Password-protected menu that shows operating parameters, reached from the Configuration menu.

  1. From the Configuration menu open Troubleshoot.
  2. Enter the password with the buttons in this order: down, center, up, center.

Applies to: Rinnai Canadian hydronic air handler (CAH)

Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), Software Settings p.41-42. Written in our own words; check the manual for your exact model.

Enter parameter setting mode on the PC board

Boiler · I-Series Plus

Hold the left PC board button to reach the parameter menu, then leave it the same way to return to normal operation.

  1. Locate the PC board on the lower left side of the unit.
  2. Press and hold the left PC board button for five seconds until 00-A appears.
  3. Scroll to the required parameter and press Select.
  4. When settings are finished, press the left PC board button to return to normal operation.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 136. Written in our own words; check the manual for your exact model.

Enter parameter settings from the PC board

Boiler · I-Series Plus

Parameters are reached by pressing and holding the left PC board button for five seconds, after the front panel is removed.

  1. Remove the front panel (two screws on the panel for the CH/DHW settings).
  2. Find the PC board at the lower left side of the unit.
  3. Press and hold the left PC board button for five seconds.
  4. Change the parameter and replace the front panel when finished.

Applies to: I-Series Plus Condensing Combi Boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 103. Written in our own words; check the manual for your exact model.

Enter parameter settings mode

Boiler · I-Series Plus

Parameter settings are changed from the PC board, not the controller display buttons. Use the left PC board button to enter and exit.

  1. Remove the boiler front panel by taking out the two securing screws.
  2. Locate the PC board on the lower left side of the unit.
  3. Press and hold the left PC board button for five seconds. Parameter 00-A appears on the display.
  4. Use the Up or Down arrows to select a parameter number, then press Select.
  5. Use the Up or Down arrows to change the setting for that parameter, then press Select.
  6. To exit parameter settings and return to normal operation, press the PC board button.

Applies to: I-Series Plus condensing combi boiler parameter settings

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 89. Written in our own words; check the manual for your exact model.

Open the installer level (code C123)

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

The Control Tower hides installer chapters behind an access code. Once entered, PARA, SERV and the rest become available; the control drops back to user level after 20 minutes without a key press.

  1. Hold MODE for 5 seconds until COdE shows
  2. Use + and - to dial C123
  3. Press STORE to confirm

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.56 (10.1). Written in our own words; check the manual for your exact model.

Open the parameter settings menu on the PC board

Boiler · I-Series Plus 150K and smaller, I-Series Plus 175K and higher

Installer menu for changing boiler parameters; only change what an instruction tells you to change.

  1. Remove the front panel; the PC board is at the lower left.
  2. Press and hold the left SW1 button for 5 seconds.
  3. Use the up and down arrows to scroll to the parameter, then press Select.
  4. Change the value and press Select to store it.
  5. Press the left SW1 button to leave the menu.

Applies to: Rinnai I-Series Plus boilers and combis (150K and smaller, 175K and higher)

Source: Rinnai Troubleshooting I-Series Plus Diagnostic Codes (800000375), Code 540 steps 2-5 p.31. Written in our own words; check the manual for your exact model.

Turn child lock on or off

Boiler · I-Series Plus

Locks the controller buttons. With child lock on, the only function left is turning off central heating, and only if Parameter 71 is set to b. With multiple controllers, child lock is set only on the priority controller. Pressing a locked button shows LOC on the display.

  1. Press the Select button.
  2. Press the Mode button three times. The display shows 3:off.
  3. Use the Up or Down arrows to select OFF (child lock off) or LOC (child lock on).
  4. Press Select to confirm.

Applies to: I-Series Plus condensing combi boiler, controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 84. Written in our own words; check the manual for your exact model.

Open the parameter settings menu on the PC board

Combi boiler · I-Series Plus 150K and smaller, I-Series Plus 175K and higher

Installer menu for changing boiler parameters; only change what an instruction tells you to change.

  1. Remove the front panel; the PC board is at the lower left.
  2. Press and hold the left SW1 button for 5 seconds.
  3. Use the up and down arrows to scroll to the parameter, then press Select.
  4. Change the value and press Select to store it.
  5. Press the left SW1 button to leave the menu.

Applies to: Rinnai I-Series Plus boilers and combis (150K and smaller, 175K and higher)

Source: Rinnai Troubleshooting I-Series Plus Diagnostic Codes (800000375), Code 540 steps 2-5 p.31. Written in our own words; check the manual for your exact model.

Enter installer parameter mode (A button on the PC board)

Tankless water heater · SENSEI RX / CX

Parameter mode changes numbered settings such as max temperature, recirculation mode, pump speed and the Service Soon interval.

  1. Press the A button on the PC board for 1 s
  2. Pick the setting number with the controller up / down arrows
  3. Press On/Off on the controller to step through the option letters (01A, 01b...)
  4. Press the A button 1 s again to exit

Applies to: SENSEI RX and CX series tankless

Source: Rinnai SENSEI RX technical guide (en-CA), Parameter settings. Written in our own words; check the manual for your exact model.

Button combinations

Key presses that open menus, show readouts or switch modes.

Boost mode

Boiler · I-Series Plus

Overrides the outdoor reset target and raises the target to the Parameter 01 curve maximum after a continuous run time or interval set in Parameter 02. Stays active until the call for heat is satisfied or the boiler cycles off.

  1. Press the Boost button on the controller to start boost mode.
  2. Set Parameter 02 for the run time or interval that triggers the boost.

Applies to: I-Series Plus Condensing Combi Boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 98. Written in our own words; check the manual for your exact model.

Enter and exit parameter settings using SW1 left button

Boiler · I-Series Plus

The SW1 left button on the PC board is used to enter parameter settings and to return to normal operation.

  1. Remove the front panel by taking out the two securing screws.
  2. Locate the PC board on the lower left side of the unit.
  3. Press the SW1 left button to enter parameter settings.
  4. When finished, press the SW1 left button again to exit to normal operation.
  5. Reinstall the front panel with its two screws.

Applies to: I-Series Plus PC board

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 24. Written in our own words; check the manual for your exact model.

View the last nine error codes (DHW + Up)

Boiler · I-Series Plus 150K and smaller, I-Series Plus 175K and higher

Shows the stored error history on the I-Series Plus controller.

  1. Hold the DHW button for 2 s, then press Up as well (both together).
  2. Repeat the same press to exit.

Applies to: I-Series Plus Solo (heat-only) boilers IP060S, IP090S, IP120S, IP150S, IP175S, IP199S

Source: Rinnai Troubleshooting I-SERIES Plus Boiler Diagnostic Codes (800000375), PC Board Buttons table (code 520) p.30; Appendix F p.58; code 710 p.40. Written in our own words; check the manual for your exact model.

View the last nine error codes (DHW + Up)

Combi boiler · I-Series Plus 150K and smaller, I-Series Plus 175K and higher

Shows the stored error history on the I-Series Plus controller.

  1. Hold the DHW button for 2 s, then press Up as well (both together).
  2. Repeat the same press to exit.

Applies to: I-Series Plus Combi boilers IP060160C, IP090099C, IP090160C, IP090199C, IP120199C, IP150199C, IP175199C, IP199199C

Source: Rinnai Troubleshooting I-SERIES Plus Boiler Diagnostic Codes (800000375), PC Board Buttons table (code 520) p.30; Appendix F p.58; code 710 p.40. Written in our own words; check the manual for your exact model.

Lock or unlock the controller (key symbol)

Tankless water heater · SENSEI RX/CX, SENSEI

While locked, the set temperature cannot be changed; RX/CX outdoor units lock themselves after 30 minutes without use.

  1. To lock: press and hold Priority, then press Up as well until a beep sounds (about 5 seconds), and let go of both together.
  2. To unlock: repeat the same steps.

Applies to: Rinnai SENSEI tankless (RU, RUR, RSC, CU) and SENSEI RX/CX (RX, RXP, CX, CXP)

Source: Rinnai N-Series Residential (100000467) / with Pump (100000508) / Commercial (100000504) / RSC SENSEI (100000773) Installation and Operation Manuals, 5.3.2 Locking the Controller p.68-69; Rinnai SENSEI RX Residential Installation and Operation Manual (100000839), 5.3 p.56. Written in our own words; check the manual for your exact model.

Lock or unlock the KCM controller (LOC)

Tankless water heater · KCM (RUCS/RUS)

Locking one controller locks every controller in the system.

  1. To lock: press Priority and Up together for 5 seconds; a beep confirms it.
  2. To unlock: press Priority and Up together for 5 seconds again.

Applies to: Rinnai KCM tankless with MC-601-US controller

Source: Rinnai KCM Series Manual (U328-0700X04), p.55. Written in our own words; check the manual for your exact model.

Performance data readout (items 01 to 24)

Tankless water heater · SENSEI RX / CX

Live and lifetime values: flow, temperatures, run hours, cycles, fan frequency, as numbered items on the controller.

  1. Hold the down arrow; after about 2 s also hold On/Off until 01 shows
  2. Scroll with up / down to the item wanted
  3. See the Performance data table under Settings for the item list

Applies to: SENSEI RX and CX series tankless

Source: Rinnai SENSEI RX technical guide (en-CA), Performance data. Written in our own words; check the manual for your exact model.

Show live flow and outlet temperature on the KCM controller

Tankless water heater · KCM (RUCS/RUS)

Information mode on the MC-601-US shows water flow and outgoing temperature.

  1. Press and hold Down for 2 seconds and, without letting go, press On/Off. Repeat the same press to leave.
  2. Press Up or Down until 01 shows: the water flow follows in 0.1 gal/min (58 means 5.8 gal/min).
  3. Press Up or Down until 02 shows: the outgoing water temperature follows in °F.

Applies to: Rinnai KCM tankless (RUCS65i/75i, RUS65e/75e)

Source: Rinnai KCM Series Manual (U328-0700X04), p.56. Written in our own words; check the manual for your exact model.

Show the last 9 stored codes (diagnostic history)

Tankless water heater · SENSEI RX / CX

The controller plays back the nine most recent maintenance codes one after another. LC shows as 00 in this list.

  1. Switch the heater off with On/Off
  2. Hold On/Off 2 s, then press the up arrow while still holding
  3. The codes flash in sequence
  4. Repeat the same hold to leave, then switch back on

Applies to: SENSEI RX and CX series tankless

Source: Rinnai SENSEI RX technical guide (en-CA), Diagnostic history. Written in our own words; check the manual for your exact model.

Lock or unlock the control panel

Wall furnace · EX DT

The lock indicator lights and a beep sounds when the lock is on.

  1. Press Lock to activate.
  2. Hold Lock for about 2 seconds to release; the indicator goes out and a beep sounds.

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces

Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Lock p.31. Written in our own words; check the manual for your exact model.

Service & test modes

Forced fan, low and high fire, test and diagnostic modes, error history and live data.

Combustion analysis port access

Boiler · I-Series Plus

Combustion analysis must be done by a trained and qualified professional. The CO2 or O2 reading is taken in the exhaust with the boiler held at forced high or low fire.

  1. Remove the front panel by removing the two screws that hold it.
  2. Remove the clamp holding the combustion analysis port cap.
  3. Remove the cap and insert the gas analyzer probe into the port.
  4. Put the boiler into forced high fire or low fire as needed (see section 12.12 Forced Hi/Low Fire Modes).
  5. Measure CO2 or O2 in the exhaust.
  6. Remove the probe, refit the cap and clamp, then reinstall the front panel with the two screws.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 137. Written in our own words; check the manual for your exact model.

Display diagnostic codes

Boiler · I-Series Plus

Shows the last nine maintenance codes one after the other.

  1. Press and hold the Domestic Hot Water button for two seconds, then the Up button, holding both at the same time.
  2. The last nine maintenance codes display and flash one after the other.
  3. To exit, press and hold the Domestic Hot Water button and the Up button together for two seconds.

Applies to: I-Series Plus combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 113. Written in our own words; check the manual for your exact model.

Force the burner on for combustion checks (SERV function 1)

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

SERV chapter test functions: 1 = burner at adjustable load, 2 = fan, 3 = pump, 4 = showroom mode. Function 1 is what you use for the O2 / CO2 check and the ionization reading.

  1. Enter C123, press MODE until SERV
  2. Press STEP to pick function 1
  3. Raise the load with +; hold - to go down to OFF, which ends the test
  4. Target O2 at minimum 4.4 % on natural gas, 4.8 % on propane; ionization at least 4 uA

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.58, 61-63. Written in our own words; check the manual for your exact model.

Forced high and forced low fire test modes

Boiler · I-Series Plus

Licensed professional test mode for forcing the burner to high or low fire.

  1. Remove the front panel by removing the two screws.
  2. Locate the PC board on the lower left side.
  3. Press and hold the right-side black button to show FL (forced low fire).
  4. Press the right-side black button again to show FH (forced high fire).
  5. Press the right-side black button again to return to normal operation.
  6. Note: the first steps for entering this mode are not fully legible on the extracted page.

Applies to: I-Series Plus combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 114. Written in our own words; check the manual for your exact model.

Ignition safety test (forced E02 lockout)

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

Proves the flame-failure lockout works. Expect one start plus four retries, then a flashing E02.

  1. Unplug the ionization cable
  2. Start SERV function 1
  3. Wait for the start attempts to finish and E02 to flash
  4. Reconnect the cable and reset the boiler

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.63. Written in our own words; check the manual for your exact model.

Read the technical read-out and error history

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

Hold STEP 5 s to switch the display to the technical read-out (status digit left, supply temperature / water pressure right). The ERRO chapter stores the last error (Err.L) and five earlier ones (Err.1 to Err.5) with status, T1, T2, kW and pump %.

  1. Hold STEP 5 s to toggle the technical read-out
  2. For history: enter C123, press MODE until ERRO, STEP through Err.L to Err.5

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.54, 59. Written in our own words; check the manual for your exact model.

Start deaeration on the PC board

Boiler · I-Series Plus

Deaeration purges air from the boiler and system after filling or service. Use the SW2 button on the PC board, or the control panel on first install.

  1. Press and hold the SW2 button on the PC board.
  2. Wait for the Maintenance Mode icon to show on the controller. Deaeration starts.
  3. On first install you can instead press and hold the DHW button, then press the CH button at the same time, without removing the front panel.

Applies to: I-Series Plus IP060160C

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 69-70. Written in our own words; check the manual for your exact model.

SW3 button on PC board for descaling mode

Boiler · I-Series Plus

The SW3 button on the PC board (lower left side) starts and stops the descaling mode. Press it again to cancel. You can also cancel using the Switching Operation Mode button on the controller.

  1. Remove the boiler front panel by removing the two screws.
  2. Locate the PC board on the lower left side of the unit.
  3. Press SW3 to enter descaling mode, or press again to return to normal mode.

Applies to: All I-Series Plus condensing combi boilers

Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 122, p. 123. Written in our own words; check the manual for your exact model.

SW3 button starts and exits descaling mode

Boiler · I-Series Plus

The SW3 button on the PC board is used to enter descaling mode and to return the unit to normal mode after the cycle.

  1. Press SW3 on the PC board to start descaling mode.
  2. Press SW3 again after the rinse to return to normal mode.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, pp. 128, 130. Written in our own words; check the manual for your exact model.

View boiler performance data

Boiler · I-Series Plus

Enters the performance data view so you can scroll through the data numbers listed in the performance data table.

  1. Press and hold the Down button, then press and hold the Domestic Hot Water button at the same time.
  2. Press and hold the Down button for two seconds.
  3. Use the Up and Down buttons to scroll to the data number you need.
  4. The value for the selected data number shows automatically on the display.
  5. To exit, hold the Down button and press and hold the Domestic Hot Water button together.

Applies to: I-Series Plus condensing combi boiler, controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 81. Written in our own words; check the manual for your exact model.

Enter performance data view

Tankless water heater · Non-SENSEI, SENSEI

Opens the performance data list so you can read live operating values from the unit.

  1. Press and hold the Down button.
  2. While holding Down for 2 seconds, press and hold the On/Off button too (both buttons held together).
  3. Use the Up and Down buttons to scroll to the data item you need.
  4. Read the value shown for that item. Units are listed in the performance data table.

Applies to: Rinnai tankless water heaters (SENSEI and Non-SENSEI series)

Source: Troubleshooting Tankless Water Heater Diagnostic Codes manual, p. 64. Written in our own words; check the manual for your exact model.

Start descaling (vinegar flush) mode on the PC board

Tankless water heater · SENSEI RX/CX

Button B on the PC board brings up dES; pressing A starts the flush cycle.

  1. Remove the front panel and locate pushbuttons A and B on the PC board (controller blank).
  2. Press B for 1 second and release when dES appears.
  3. Press A: dES starts blinking and the flush cycle is running.
  4. Circulate vinegar through the unit; the display then counts down from 60 (minutes), shows rnS (rinse), then End.

Applies to: Rinnai SENSEI RX/CX tankless (RX, RXP, CX, CXP)

Source: Rinnai SENSEI RX Residential Installation and Operation Manual (100000839), 6.3 Flushing the Heat Exchanger, Quick-Flush p.67-68; Rinnai Troubleshooting TWH Diagnostic Codes (100000652), Code 17 reset table p.29. Written in our own words; check the manual for your exact model.

View diagnostic code history

Tankless water heater · Non-SENSEI, SENSEI

Shows the last 9 maintenance codes, which flash one after another.

  1. Turn the water heater off with the On/Off button.
  2. Press and hold On/Off for 2 seconds, then press Up at the same time.
  3. The last 9 maintenance codes display and flash in turn.
  4. To exit, press and hold On/Off for 2 seconds, then press Up at the same time.
  5. Turn the water heater on with the On/Off button.

Applies to: SENSEI and Non-SENSEI series

Source: Troubleshooting Tankless Water Heater Diagnostic Codes, p. 63. Written in our own words; check the manual for your exact model.

Set low and high fire gas pressure with the Test Switch

Wall furnace · EX DT

PL is the low-fire setting screen and PH the high-fire one; adjust with the up and down buttons against the manometer.

  1. In the gas pressure setting procedure, press the Test Switch twice while the furnace is on: PL shows.
  2. Compare the manometer reading with the table for the gas, altitude and vent length; adjust with the up and down buttons.
  3. Press the Test Switch to move to PH.
  4. Compare the manometer reading with the table; adjust with the up and down buttons.
  5. Press ON/OFF to finish; the display goes blank and the furnace returns to normal off mode.

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces

Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Gas pressure setting steps 10-11 p.26. Written in our own words; check the manual for your exact model.

Reset & cancel

Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.

Cancel the descaling cycle

Boiler · I-Series Plus

Descaling can be stopped at any point during the flush.

  1. Press the Settings Menu button on the controller, or press SW3 on the PC board.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 129. Written in our own words; check the manual for your exact model.

End deaeration and return to normal operation

Boiler · I-Series Plus

Deaeration takes about 15 minutes. When finished the display shows End.

  1. Wait about 15 minutes for deaeration to finish, until the display shows End.
  2. To stop it early, press and hold SW2 on the PC board.
  3. Press the top left black button on the PC board to return to normal operation.
  4. Run domestic hot water or central heating to check the boiler runs correctly.
  5. Close the air vent on the pump after deaeration.

Applies to: I-Series Plus IP060160C

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 69-70. Written in our own words; check the manual for your exact model.

Reset diagnostic codes

Boiler · I-Series Plus

When a code is reset, the CH or DHW button flashes.

  1. Look for the flashing Central Heating or Domestic Hot Water button.
  2. Press the flashing button to reset the code.
  3. If the code will not reset, some codes need a service provider, so call for help.

Applies to: I-Series Plus combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 113. Written in our own words; check the manual for your exact model.

Reset Service Soon (SS) indicator

Boiler · I-Series Plus

Clears the SS reminder on the controller. It will return after the next selected service interval.

  1. Press the Central Heating (CH) button 5 times to reset SS.

Applies to: I-Series Plus Condensing Combi Boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 96. Written in our own words; check the manual for your exact model.

Reset the SERVICE reminder (8000 h counter)

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

After 8000 burner hours the display scrolls SERVICE alternating with Good. The counter is reset from the SERV chapter.

  1. Enter C123, press MODE until SERV
  2. Hold STORE until SERV flashes once
  3. The hour counter returns to 8000

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.69 (13.3.1). Written in our own words; check the manual for your exact model.

Reset the Service Soon (SS) indicator

Boiler · I-Series Plus

After the SS service reminder has been shown and the boiler has been serviced, the indicator is cleared from the controller.

  1. Press the Central Heating (CH) button 5 times to reset the SS indicator.

Applies to: I-Series Plus controller display

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 96. Written in our own words; check the manual for your exact model.

Restore factory parameters (Copy)

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

All parameters of the current access level go back to factory values; the display shows Copy to confirm.

  1. Enter C123 and go to the PARA chapter
  2. Press STORE (the green button) while in PARA
  3. Copy appears; the factory settings are now active

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.58. Written in our own words; check the manual for your exact model.

Venturi reset on the PC board (code 170)

Boiler · I-Series Plus 150K and smaller, I-Series Plus 175K and higher

Holding SW2 and SW3 together shows P, then PCL on a second hold.

  1. Press SW2 and SW3 together until P appears.
  2. Hold SW2 and SW3 together a second time until PCL appears.

Applies to: Rinnai I-Series Plus boilers and combis (150K and smaller, 175K and higher)

Source: Rinnai Troubleshooting I-Series Plus Diagnostic Codes (800000375), Code 170 step 7 p.13. Written in our own words; check the manual for your exact model.

Venturi reset on the PC board (code 170)

Combi boiler · I-Series Plus 150K and smaller, I-Series Plus 175K and higher

Holding SW2 and SW3 together shows P, then PCL on a second hold.

  1. Press SW2 and SW3 together until P appears.
  2. Hold SW2 and SW3 together a second time until PCL appears.

Applies to: Rinnai I-Series Plus boilers and combis (150K and smaller, 175K and higher)

Source: Rinnai Troubleshooting I-Series Plus Diagnostic Codes (800000375), Code 170 step 7 p.13. Written in our own words; check the manual for your exact model.

Code 52 / 17 reset sequence on temperature controller

Tankless water heater · SENSEI, Non-SENSEI

Button sequence used to clear code 52 (and code 17) from the temperature controller. Disconnect power and gas before starting the work that leads to the reset.

  1. Start with the controller off (blank display).
  2. Press button B for 1 second until the display shows "t".
  3. Press button B for 1 second until the display shows "F".
  4. Press button B for 1 second until the display shows "S".
  5. Press button B for 1 second until the display shows "E". Only do this step if code 17 or 52 is showing.
  6. Press buttons A and B together for 10 seconds until the display shows "ECL". Reset is complete.

Applies to: Code 52 and code 17 on SENSEI and Non-SENSEI series

Source: Troubleshooting Tankless Water Heater Diagnostic Codes, p. 40. Written in our own words; check the manual for your exact model.

Controller reset sequence after venturi cleaning (code 17)

Tankless water heater · SENSEI

Run this sequence after the venturi is cleaned and reinstalled to return the water heater to normal operation.

  1. Start with the temperature controller off (blank display).
  2. Press button B for 1 second until the display shows "t".
  3. Press button B for 1 second until the display shows "F".
  4. Press button B for 1 second until the display shows "S".
  5. If code 17 or 52 is occurring, press button B for 1 second until the display shows "E".
  6. Press buttons A and B together for 10 seconds. The display shows "ECL" when the reset is complete.

Applies to: SENSEI Series, codes 17 and 52

Source: Troubleshooting Tankless Water Heater Diagnostic Codes, p. 26. Written in our own words; check the manual for your exact model.

Reset after cleaning the venturi or replacing the gas valve (codes 17 / 52)

Tankless water heater · SENSEI RX/CX, SENSEI

Step through the reset screens with button B on the PC board, then finish with A and B together.

  1. With the controller blank, press B for 1 second at a time to advance: SENSEI shows t, F, S, E; RX/CX shows dES, t, AdJ, F, A, E.
  2. E appears only while code 17 or 52 is active.
  3. Finish by pressing A and B together for 10 seconds until ECL shows.

Applies to: Rinnai SENSEI and SENSEI RX/CX tankless

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), Code 17 and Code 52 reset procedure p.28-29. Written in our own words; check the manual for your exact model.

Reset procedure for code 52 (and code 17)

Tankless water heater · SENSEI, Non-SENSEI

Used to clear code 52, and code 17 when it is occurring. Start with the controller off (blank display). Use buttons on the PC board or temperature controller as shown in the manual. Shut off gas and water before service.

  1. With the controller off (blank), press button B for 1 second. Display shows "t".
  2. Press button B for 1 second. Display shows "F".
  3. Press button B for 1 second. Display shows "S".
  4. Press button B for 1 second. Display shows "E" (only needed if code 17 or 52 is occurring).
  5. Press buttons A and B together for 10 seconds. Display shows "ECL" when reset is complete.

Applies to: Code 52 and code 17

Source: Troubleshooting Tankless Water Heater Diagnostic Codes, p. 40. Written in our own words; check the manual for your exact model.

Reset the Service Soon (SS) reminder

Tankless water heater · SENSEI

Clears the Service Soon reminder on the residential, pump and commercial models.

  1. Press On/Off 5 times.

Applies to: RU199i/e, RU180i/e, RU160i/e, RU130i/e

Source: Rinnai Tankless Water Heater (Residential) Installation and Operation Manual (100000467), Table 30 Parameter Settings, p.61-62. Written in our own words; check the manual for your exact model.

Settings shortcuts

Where the useful parameters live and what they are set to from the factory.

Adjust the central heating setpoint temperature

Boiler · I-Series Plus

Changes the CH target temperature. In outdoor reset control the CH setpoint is locked unless the custom curve is selected, and the target will not follow this setting when outdoor reset is active.

  1. Press the Switch Operation Mode button until the Central Heating Active button shows on the home screen.
  2. Use the Up or Down arrows to set the wanted temperature.
  3. Press Select to confirm. The setting shows for a few seconds, then the controller returns to standby.

Applies to: I-Series Plus condensing combi boiler, controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 81. Written in our own words; check the manual for your exact model.

Adjust the DHW setpoint temperature

Boiler · I-Series Plus

Changes the domestic hot water target temperature from the controller.

  1. If the DHW button backlight is off, press the DHW button. If it is already lit, go to the next step.
  2. Press the Switch Operation Mode button until the DHW Active icon shows on the home screen.
  3. Use the Up and Down arrows to set the wanted temperature.
  4. Press Select to confirm. The setting shows for a few seconds, then the controller returns to standby.

Applies to: I-Series Plus condensing combi boiler, controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 80. Written in our own words; check the manual for your exact model.

Change a parameter in the PARA chapter

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

Installer parameters live in the PARA chapter. Navigation is MODE for chapter, STEP for the item, + / - for the value and STORE to save.

  1. Enter the installer code C123
  2. Press MODE until PARA appears
  3. Press STEP to reach the parameter number
  4. Adjust with + or -, then press STORE
  5. Press MODE until StBY or Good shows to leave; it also times out after 20 min

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.56-58. Written in our own words; check the manual for your exact model.

Change altitude setting (parameter A3)

Boiler · I-Series Plus

Set parameter A3 to match the installation elevation. When the altitude is set with the PC board buttons, the high altitude gas pressure adjustment is not needed.

  1. Remove the boiler front panel by taking out the two securing screws.
  2. Locate the PC board (lower left side of unit).
  3. Press the SW1 left button on the PC board.
  4. Scroll to parameter A3.
  5. Set A3 to the level that matches the installation altitude (see the A3 altitude setting table).

Applies to: I-Series Plus, all altitudes

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 88. Written in our own words; check the manual for your exact model.

Change display units (F/C)

Boiler · I-Series Plus

Changes the units shown on the boiler display.

  1. Press the Select button.
  2. Use the Up or Down arrows to choose F (degrees F and PSI) or C (degrees C and bar).
  3. Press the Settings button to confirm.

Applies to: I-Series Plus condensing combi boiler, controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 83. Written in our own words; check the manual for your exact model.

Change the DHW setpoint temperature

Boiler · I-Series Plus

Adjust the hot water temperature from the controller.

  1. If the DHW button backlight is off, press the DHW button.
  2. Press the Switch Operation Mode button until the DHW Active icon shows on the home screen.
  3. Use the Up and Down arrows to set the temperature.
  4. Press Select to confirm. The setting shows for a few seconds, then the boiler returns to standby.

Applies to: I-Series Plus IP060160C

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 76. Written in our own words; check the manual for your exact model.

Correct gas type or venting after first setup

Boiler · I-Series Plus

Gas type and venting can be changed later through the parameter menu, not just the first-time setup.

  1. Open the parameter settings as described in section 12.4.
  2. Change parameter A0 for gas type.
  3. Change parameter A2 for venting type.
  4. Confirm the new settings match the installed gas and venting.

Applies to: I-Series Plus condensing combi boilers

Source: Rinnai I-Series Plus IP060160C installation manual, p. 67. Written in our own words; check the manual for your exact model.

Switch DHW comfort mode (Eco or Comfort)

Boiler · I-Series Plus

Eco mode is the default and saves energy but gives slower hot water. Comfort mode keeps the primary heat exchanger warm for faster hot water and uses more energy. The Eco icon is always on during DHW recirculation.

  1. Press the Settings button.
  2. Use the Up or Down arrows to select the unit for Eco mode.
  3. Set On for Eco mode or OFF for Comfort mode.
  4. To enable Comfort mode, press the Eco button on the controller.

Applies to: I-Series Plus condensing combi boiler, controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 82. Written in our own words; check the manual for your exact model.

Turn the control panel click sound on or off

Boiler · I-Series Plus

Turns the key click sound on the controller on or off.

  1. Press the Select button.
  2. Press the Mode button twice. The display shows 2:on.
  3. Use the Up or Down arrows to select ON or OFF.
  4. Press Select to confirm.

Applies to: I-Series Plus condensing combi boiler, controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 83. Written in our own words; check the manual for your exact model.

Switch the controller between Celsius and Fahrenheit

Tankless water heater · SENSEI RX/CX, SENSEI, KCM (RUCS/RUS)

Changes the temperature units shown on the controller.

  1. With the water heater OFF, press and hold On/Off on the controller for 5 seconds.
  2. The display switches between °C and °F. Repeat to switch back.

Applies to: Rinnai SENSEI, SENSEI RX/CX and KCM tankless with a controller

Source: Rinnai N-Series Residential (100000467) / with Pump (100000508) / Commercial (100000504) / RSC SENSEI (100000773) Installation and Operation Manuals, 5.4.1 p.71; Rinnai SENSEI RX Residential Installation and Operation Manual (100000839), 5.4 p.58; Rinnai KCM Series Manual (U328-0700X04), p.55. Written in our own words; check the manual for your exact model.

Turn controller key beeps on or off

Tankless water heater · SENSEI RX/CX, SENSEI, KCM (RUCS/RUS)

Switches the beep that sounds when controller keys are pressed.

  1. Press and hold Up and Down together until a beep is heard (about 3 seconds on SENSEI and RX/CX, about 5 seconds on the KCM MC-601-US), then release.
  2. Repeat the same press to turn the beeps back on.

Applies to: Rinnai SENSEI, SENSEI RX/CX and KCM tankless with a controller

Source: Rinnai N-Series Residential (100000467) / with Pump (100000508) / Commercial (100000504) / RSC SENSEI (100000773) Installation and Operation Manuals, 5.3.1 p.68; Rinnai KCM Series Manual (U328-0700X04), p.55. Written in our own words; check the manual for your exact model.

Select remote thermostat mode (01) or control panel mode (02)

Wall furnace · EX DT

Control mode 00 is the factory default; 01 is for a wall thermostat kit (do not select without the connection parts); 02 returns to the furnace's own panel. Do not unplug the furnace within two hours of entering remote thermostat mode or it reverts to the factory default.

  1. Furnace plugged in but OFF, Set back feature OFF.
  2. Hold Economy + Up + Program for 2.5 seconds, then release: 00 shows.
  3. Press Up to move to 01 or 02.
  4. Press ON/OFF; the display goes blank and the mode is stored.

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces

Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Remote thermostat p.32. Written in our own words; check the manual for your exact model.

Select the gas code (gas type, altitude, vent length)

Wall furnace · EX DT

A codes are natural gas, L codes are propane; digits 1 to 4 pick the altitude band.

  1. With the furnace off, hold the Test Switch on the PC board until it beeps.
  2. Pick the code with the up and down buttons.
  3. Press the Test Switch twice to store it; the display goes blank.

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces

Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Table 8 Gas Pressure p.25-26. Written in our own words; check the manual for your exact model.

Switch the display between Fahrenheit and Celsius

Wall furnace · EX DT

Factory default is Fahrenheit.

  1. Furnace must be off.
  2. Press Timer 1 and Timer 2 together for about 5 seconds: the display shows ºC or ºF.
  3. Use the arrow keys to select the scale.
  4. Press ON/OFF to store it.

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces

Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Fahrenheit or Celsius p.30. Written in our own words; check the manual for your exact model.

Turn Set back (frost protection) on or off

Wall furnace · EX DT

Set back starts heating whenever room temperature drops below the preset minimum (38 to 78 F, default 60 F); it is on from the factory.

  1. With the furnace OFF, press Set back (light comes on).
  2. Adjust the minimum temperature with the up/down buttons.
  3. Press Set back again to turn the feature off.

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces

Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Set back p.35. Written in our own words; check the manual for your exact model.

Commissioning

Start-up and set-up steps that are easy to miss.

Set Furnace Model after replacing the control board

Air handler · Air handler

After a control board replacement the System menu Furnace Model entry must be set to CAH050E.

  1. Open the Installer menu with the password: down, center, up, center.
  2. Go to System menu > Furnace Model.
  3. Set it to CAH050E.

Applies to: CAH050E, CAH050CE hydronic air handlers

Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), 8.3 Controller Input Options p.40; menus p.41-42; sequence of operation p.36. Written in our own words; check the manual for your exact model.

Altitude and venting limits

Boiler · I-Series Plus

Do not install the boiler above 10,200 ft (3,109 m). Venting must be installed per local and national codes. Failure to vent properly can cause death, injury or property damage. Do not block combustion air to the boiler.

  1. Check the install site elevation is 10,200 ft or lower.
  2. Install the vent system per local and national codes.
  3. Keep combustion air openings to the boiler unobstructed.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Apply LPG conversion label

Boiler · I-Series Plus

Needed only when the boiler is set to propane.

  1. Place the supplied gas conversion label in an open spot above the existing label on the left side of the boiler.

Applies to: I-Series Plus condensing combi boilers set to LPG

Source: Rinnai I-Series Plus IP060160C installation manual, p. 67. Written in our own words; check the manual for your exact model.

Automatic de-aeration program (A xx, 17 min)

Boiler · E-Combi (E50CRN, E75CRN/E75CRP, E110CRN/E110CRP)

After power-up or a reset the boiler runs a 17-minute air purge, shown as A followed by the countdown. Block 85 (no flow) also triggers it. The manual gives no key combination to skip it; wait it out or power-cycle and it restarts.

  1. Display A xx = purge in progress, counting down
  2. Burner is released as soon as flow is detected during the cycle

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.50-54, 72. Written in our own words; check the manual for your exact model.

Carbon monoxide alarm before start-up

Boiler · I-Series Plus

The installer must confirm at least one carbon monoxide alarm is installed in the living space before the appliance is put into operation. Rinnai recommends a CO alarm in the hallway near each sleeping area.

  1. Install at least one CO alarm in the residential living space per the alarm maker's instructions and local code before start-up.
  2. Tell the owner to check CO alarm batteries monthly and replace them yearly.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Change altitude setting on the PC board

Boiler · I-Series Plus

Sets Parameter A3 for high altitude. Gas pressure does not need to be changed for high altitude when this parameter is used.

  1. Remove the front panel by taking out the two screws that hold it.
  2. Locate the PC board on the lower left side of the unit.
  3. Locate the PC board buttons.
  4. Press the SW1 left button.
  5. Scroll to Parameter A3.
  6. Set Parameter A3 to the letter that matches the site altitude in the altitude table.

Applies to: I-Series Plus PC board, Parameter A3

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 84. Written in our own words; check the manual for your exact model.

Combustion air and venting checklist

Boiler · I-Series Plus

Confirm these items before leaving the job.

  1. Verify all combustion air opening sizes are correct.
  2. Confirm combustion air requirements are met for the appliance.
  3. Confirm the air is not corrosive. If it is, do not use room air.
  4. Confirm adequate combustion air is available for all appliances in the space.
  5. Confirm the installation meets the National Fuel Gas Code (ANSI Z223.1/NFPA 54) and local and state rules.

Applies to: All venting and combustion air installations

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 43. Written in our own words; check the manual for your exact model.

Connect a Rinnai BLE push button

Boiler · I-Series Plus

Pairs a push button that starts recirculation on the boiler.

  1. Press and hold the Bluetooth button on the controller until the Bluetooth LED starts blinking.
  2. Press and hold the Rinnai BLE push button until its green light flashes.
  3. Wait for one beep (paired) or two beeps (pairing expired).
  4. Pressing the BLE push button starts recirculation.

Applies to: I-Series Plus Condensing Combi Boiler with BLE

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 108. Written in our own words; check the manual for your exact model.

Do not bypass deaeration

Boiler · I-Series Plus

Deaeration must not be skipped during commissioning, after any part of the system is opened or disconnected, or if system pressure has dropped below 13 PSI. Skipping it can damage the boiler, and that damage is not covered by the warranty.

Applies to: I-Series Plus IP060160C

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 70, 72. Written in our own words; check the manual for your exact model.

Fill the condensate collector before operation and before venting

Boiler · I-Series Plus

The condensate collector must be filled with water before the boiler runs and before the vent system is installed, otherwise exhaust gas can enter the building. Failure to fill it can cause severe injury or death.

  1. Pour approximately 10 oz (1.25 cups) of water directly into the boiler exhaust port.
  2. Do this with the 2 in. PVC adapter still fitted to the exhaust port.
  3. Complete this before installing the vent system.

Applies to: I-Series Plus before first start and venting

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 25. Written in our own words; check the manual for your exact model.

Fill the condensate trap before startup

Boiler · I-Series Plus

The manual calls for water to be poured into the exhaust port to prime the condensate trap.

  1. Pour approximately 10 ounces (1.25 cups) of water directly into the boiler's exhaust port before startup.

Applies to: Condensate trap priming

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 60. Written in our own words; check the manual for your exact model.

Installer qualifications

Boiler · I-Series Plus

A trained and qualified professional must install, inspect and leak test the boiler. Installation must follow this manual exactly, or the warranty is void. The installer is responsible for proper installation and should leave the manual with the boiler or give it to the owner.

  1. Confirm the installer has gas line sizing, gas/water/electrical connection, local code and vent-through-wall-or-roof skills.
  2. Confirm the installer has training on Rinnai I-Series Plus condensing boilers.
  3. Leave this manual with the boiler or give it to the consumer when installation is complete.

Applies to: IP060160C, IP090099C, IP090160C, IP090199C, IP120199C, IP150199C

Source: Rinnai I-Series Plus IP060160C installation manual, p. 8. Written in our own words; check the manual for your exact model.

Pair the boiler with the Rinnai Central app over Bluetooth

Boiler · I-Series Plus

Pairing uses the Bluetooth button on the controller. Your phone or tablet must support Bluetooth 4.0 or newer.

  1. Press and release the Bluetooth button on the controller; the Bluetooth LED turns solid blue.
  2. Log into the Rinnai Central app with a professional account and choose Connect to a Rinnai Boiler.
  3. Wait for the boiler to beep once (paired) or twice (pairing mode expired).
  4. Follow the app steps to set up the boiler.

Applies to: I-Series Plus Condensing Combi Boiler with BLE

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 108. Written in our own words; check the manual for your exact model.

Parameter changes need trained technician

Boiler · I-Series Plus

Rinnai strongly recommends that only a trained and qualified professional who has attended a Rinnai installation class adjusts parameter settings. Any alteration to the appliance or its controls can be dangerous and will void the warranty.

  1. Only change parameters if you have Rinnai installation training.
  2. Do not modify the appliance or its controls.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Power and fill rules before first firing

Boiler · I-Series Plus

Do not fill the boiler unless permanent power is available. Freeze protection does not work until the boiler is filled, air purged, and supplied with power and gas. Before the first firing, make sure the system is fully deaerated, the gas line is purged, and the pump is primed.

Applies to: I-Series Plus IP060160C

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 68. Written in our own words; check the manual for your exact model.

Prime condensate trap before first firing

Boiler · I-Series Plus

Add water to the exhaust port so the integrated condensate trap is primed.

  1. Pour about 10 oz (1.25 cups) of water directly into the boiler exhaust port.

Applies to: I-Series Plus condensing combi boilers

Source: Rinnai I-Series Plus IP060160C installation manual, p. 64. Written in our own words; check the manual for your exact model.

Twin pipe elbow selection

Boiler · I-Series Plus

Use long sweep or short sweep 90 degree elbows in twin pipe venting. Do not use close turn elbows.

  1. Use 90 degree long sweep elbows where possible.
  2. Short sweep 90 degree elbows are also acceptable.
  3. Do not use 90 degree close turn elbows.

Applies to: Twin pipe venting

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 40. Written in our own words; check the manual for your exact model.

Vent material and solvent rules

Boiler · I-Series Plus

Exhaust piping must be solid core. Use the PVC or CPVC fitting, solvent and joining method given by the pipe manufacturer.

  1. Use solid core exhaust piping only.
  2. In Canada, thermoplastic vent pipe must be certified to ULC S636.
  3. Intake pipe may use any material listed in the approved materials table.
  4. Use PVC cement and primer that match the pipe material (PVC D2564, CPVC F493).
  5. Install 2 in vent screens (IPEX 196050) or 3 in vent screens (IPEX 196051) at the termination where the table calls for them.

Applies to: PVC/CPVC venting

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 36. Written in our own words; check the manual for your exact model.

When primary/secondary piping is required

Boiler · I-Series Plus

Primary/secondary piping is needed in these applications: external pumps, large zoned systems, high flow, high differential pressure, and high pressure drop systems.

  1. Check the CH pressure drop and flow curve (Appendix 14.8) and the DHW pressure drop and flow curve (Appendix 14.9) before sizing the system.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 127. Written in our own words; check the manual for your exact model.

Balance hot water risers after install

Tankless water heater · HE, HE+, SE, Sensei

Balancing of the hot water risers may be needed after installation to keep hot water delivery consistent.

Applies to: HE, HE+, SE and Sensei models, three unit circulation layout

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Circulation pump control

Tankless water heater · HE, HE+, SE, Sensei

Control the circulation pump with an aquastat, a timer, or a combination aquastat and timer.

Applies to: Recirculation loop with three unit circulation

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Circulation pump sizing

Tankless water heater · HE, HE+, SE, Sensei

Size the pump to hold the loop at temperature and to overcome the pressure loss through the tankless heater, supply and return piping. Use the Rinnai Hot Water System Design Manual for sizing guidance.

Applies to: Recirculation loop with three unit circulation

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

First power-up setup: gas type and indoor/outdoor (RX/CX)

Tankless water heater · SENSEI RX/CX

At first power-up the controller asks for gas type then installation location; gas type can also be changed later with parameter 10, only within 20 minutes after power is supplied.

  1. At first power-up SEt shows and the Priority LED blinks. Press Priority: nG appears.
  2. Press On/Off to confirm natural gas. For propane, press Up or Down to change to LPG, then On/Off.
  3. To redo, press Up to go back to the first step; to accept, press Priority.
  4. The gas type can also be changed later with parameter 10, but only within 20 minutes after power is supplied.
  5. Press On/Off to confirm indoor.
  6. For an outdoor installation with the Versa-Vent outdoor vent cap, press Up or Down to change to Out first.
  7. From the In screen press Up or Down: Out appears.
  8. Press On/Off to confirm outdoor.

Applies to: Rinnai SENSEI RX/CX tankless (RX, RXP, CX, CXP)

Source: Rinnai SENSEI RX Residential Installation and Operation Manual (100000839), 4.12 Initial Settings p.46-47. Written in our own words; check the manual for your exact model.

Other

Everything else worth knowing at the appliance.

Boiler that was under water

Boiler · I-Series Plus

Do not use the boiler if any part has been under water. A licensed professional must inspect it and replace any control system part and any manual gas control valve that was under water.

  1. Do not run the boiler.
  2. Have a licensed professional inspect the boiler.
  3. Replace the control system parts and manual gas control valve that were under water.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Do not install in restricted or unsafe areas

Boiler · I-Series Plus

Keep the boiler out of areas where it can be damaged or where airflow is restricted.

  1. Do not install where leakage would damage the area or lower floors. If that cannot be avoided, install a drained drain pan that does not block combustion air.
  2. Do not install under negative air pressure.
  3. Do not block combustion or ventilation air.
  4. Do not install on carpeting.
  5. Do not install outdoors.
  6. Do not use parts that are not authorized for this boiler.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation manual, p. 15. Written in our own words; check the manual for your exact model.

Do not run without front panel and watch burn hazard

Boiler · I-Series Plus

Do not operate the boiler without the front panel installed. Exhaust, vent and supply/return/DHW pipes can be hot enough to cause serious burns. Keep children and animals away.

  1. Reinstall the front panel before operation. Remove it only for service or internal component replacement.
  2. Keep people and pets clear of the boiler and hot vent.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Domestic hot water expansion control

Boiler · I-Series Plus

If the DHW system connects to a closed supply such as one with a backflow preventer, thermal expansion must be controlled.

  1. Ask the water supplier or local plumbing inspector how to control thermal expansion.
  2. Confirm the DHW relief valve is rated for 150 PSI (1,034 kPa).

Applies to: DHW piping

Source: Rinnai I-Series Plus IP060160C installation manual, p. 14. Written in our own words; check the manual for your exact model.

Gas conversion safety precautions

Boiler · I-Series Plus

Some PC board areas carry 120 V AC. Do not touch any area of the PC board other than the described buttons while power is on. Keep clear of the heat exchanger and hot water lines, which can cause burns. Conversion must be checked in operation before the job is complete.

  1. Shut off gas and disconnect power before opening the PC board for conversion.
  2. Check the converted appliance operates correctly as the kit instructions specify before handing over.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 131. Written in our own words; check the manual for your exact model.

Gas pipe sizing worked example

Boiler · I-Series Plus

The manual example adds the boiler input (65,000 Btu/hr) to the additional appliance input (199,000 Btu/hr) for a total of 264,000 Btu/hr. Divide by the gas heating value (1,000 Btu/ft3) to get 264 CFH. At 264 CFH the pipe must be at least 3/4 in nominal size for 10 ft run.

  1. Add all gas input in Btu/hr: boiler plus other appliances.
  2. Divide total input by the gas heating value (Btu/ft3) to get CFH.
  3. Pick the table for your gas type and pipe type, then find the size that meets the CFH at your run length.

Applies to: Natural gas sizing worksheet

Source: Rinnai I-Series Plus IP060160C installation manual, p. 53. Written in our own words; check the manual for your exact model.

Gas supply pressure testing

Boiler · I-Series Plus

Protect the boiler and its gas valve during gas line pressure tests.

  1. If the test pressure is above 1/2 PSI (3.5 kPa / 13.84 in. W.C.), disconnect the boiler and its main gas valve from the supply piping first.
  2. If the test pressure is at or below 1/2 PSI, close the boiler's individual manual shutoff valve to isolate it.

Applies to: Gas supply piping

Source: Rinnai I-Series Plus IP060160C installation manual, p. 14. Written in our own words; check the manual for your exact model.

Hard water and DHW scale

Boiler · I-Series Plus

Hard water or high setpoints increase scale and may need treatment and more frequent flushing.

  1. Treat the water where hard water or scale is known to occur.
  2. Consider a Scale Cutter filter and refill cartridge to reduce scale.

Applies to: Domestic hot water

Source: Rinnai I-Series Plus IP060160C installation manual, p. 17. Written in our own words; check the manual for your exact model.

Installer qualifications and warranty

Boiler · I-Series Plus

Only a trained and qualified installer should install, inspect and leak test the boiler. Improper installation voids the warranty.

  1. Before use, have the installer inspect the boiler and leak test it.

Applies to: I-Series Plus condensing combi boiler

Source: Rinnai I-Series Plus IP060160C installation manual, p. 14. Written in our own words; check the manual for your exact model.

Isolate power, gas and water before maintenance

Boiler · I-Series Plus

Before any maintenance, shut off electrical power, the gas supply and the incoming water. The boiler controller does not control electrical power.

  1. Unplug the power cord or turn off the electricity at the circuit breaker.
  2. Turn off the gas at the gas control, usually directly below the boiler.
  3. Turn off domestic cold water at the isolation valve below the boiler.
  4. Turn off central heating water at the system filling station shut-off valve or building main supply.
  5. Turn the manual gas control valve by hand only. Never use tools. If it will not turn by hand, call a trained professional and do not force it.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Keep corrosive compounds away from combustion air

Boiler · I-Series Plus

Chemicals in the air can corrode internal parts and shorten boiler life.

  1. Keep aerosols, detergents, bleach, solvents, oil-based paints and refrigerants away from the air supply.
  2. In salons, spas, dry cleaners, photo labs and pool storage, prefer an outdoor or sealed direct-vent installation.
  3. Place the boiler and vent termination away from air inlets, exhaust hoods and dryer vents.
  4. In coastal areas, shelter the boiler from salt spray and sea breeze.
  5. Do not use room air where indoor air is corrosive. Use direct vent in a sealed closet instead.

Applies to: Air supply and vent termination

Source: Rinnai I-Series Plus IP060160C installation manual, p. 18. Written in our own words; check the manual for your exact model.

MC-601 priority during technician work

Boiler · I-Series Plus

The MC-601 should not be used while a technician is servicing the unit. Pressing its Priority button switches priority back to the boiler's built-in controller.

  1. Do not use the MC-601 during maintenance.
  2. To return priority to the boiler controller, press the Priority button on the MC-601.
  3. To give priority back to the MC-601, press the Priority button again.

Applies to: MC-601 remote temperature controller

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 138. Written in our own words; check the manual for your exact model.

Overheating or gas shutoff failure

Boiler · I-Series Plus

If overheating occurs or the gas supply does not shut off, close the manual gas control valve to the appliance.

  1. Close the manual gas control valve to the boiler.
  2. Call a trained and qualified professional.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Scald risk at domestic hot water temperatures

Boiler · I-Series Plus

Hot water can cause first-degree burns in as little as 3 seconds at 140 F (60 C), 20 seconds at 130 F (54 C), or 8 minutes at 120 F (49 C). Water over 125 F (52 C) can cause severe burns or death. Children, disabled and elderly people are most at risk.

  1. Check the DHW setting and warn occupants about scald risk.
  2. Have users feel the water before bathing or showering.

Applies to: DHW temperature settings

Source: Rinnai I-Series Plus IP060160C installation manual, p. 51. Written in our own words; check the manual for your exact model.

Substitute parts and electrical extension cords

Boiler · I-Series Plus

Use only parts certified for the appliance. Do not use an extension cord or adapter plug with the boiler.

  1. Use only certified replacement parts.
  2. Plug the boiler directly into a suitable outlet without an extension cord or adapter.

Applies to: All I-Series Plus models

Source: Rinnai I-Series Plus IP060160C installation manual, p. 10. Written in our own words; check the manual for your exact model.

Wall strength

Boiler · I-Series Plus

The wall must carry the boiler, piping and components.

  1. If the wall is not strong enough, reinforce it before mounting.

Applies to: Wall mounting

Source: Rinnai I-Series Plus IP060160C installation manual, p. 15. Written in our own words; check the manual for your exact model.

Water fill and flushing rules

Boiler · I-Series Plus

Keep the heating system water clean and suitable for the boiler.

  1. Flush the system thoroughly before filling, with the boiler isolated.
  2. Do not add system cleaner to the boiler. Flush all cleaner out before filling.
  3. Do not fill the heating system with reverse osmosis, deionized or distilled water.
  4. Do not use oxygen-permeable or rubber tubing in the heating system unless a plate heat exchanger separates it from the boiler.
  5. Use only Rinnai-approved antifreeze, at no more than 40% concentration.
  6. Use only products on the approved cleaners, inhibitors and antifreezes list in the appendix.

Applies to: Central heating system

Source: Rinnai I-Series Plus IP060160C installation manual, p. 17. Written in our own words; check the manual for your exact model.

Alternate piping arrangements

Tankless water heater · HE, HE+, SE, Sensei

If a piping arrangement other than the drawing is planned, contact Rinnai's Application Engineering Center before installing it.

Applies to: HE, HE+, SE and Sensei models, three unit circulation layout

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Common venting reference

Tankless water heater · HE, HE+, SE, Sensei

For common vent options, use the Common Vent Installation Manual. The air intake shown on the drawing applies to direct vent installations only.

Applies to: HE, HE+, SE and Sensei models

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Condensate disposal

Tankless water heater · HE, HE+, SE, Sensei

Dispose of condensate according to local codes.

Applies to: HE, HE+, SE and Sensei models

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Condensate piping material and size

Tankless water heater · HE, HE+, SE, Sensei

Condensate piping and all drain components must be CPVC or PVC, rated for the pressure and temperature of the installation. The pipe must not be smaller than the appliance drain connection.

Applies to: HE, HE+, SE and Sensei models

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Gas orifice identification

Tankless water heater · SENSEI, Non-SENSEI

The gas orifice in the gas valve shows the gas type.

  1. Red orifice means propane (L.P.).
  2. Blue orifice means natural gas.
  3. Confirm the orifice matches the gas type on the rating plate.

Applies to: Gas valve orifice check, Code 11

Source: Troubleshooting Tankless Water Heater Diagnostic Codes, p. 15. Written in our own words; check the manual for your exact model.

Manifolded condensate drains

Tankless water heater · HE, HE+, SE, Sensei

When several units drain into one condensate line, size the pipe by an approved method set by local code.

Applies to: HE, HE+, SE and Sensei models

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Piping heaters in parallel

Tankless water heater · HE, HE+, SE, Sensei

Install the tankless heaters in parallel to get the most output from the system.

Applies to: HE, HE+, SE and Sensei models, three unit circulation layout

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Pump materials

Tankless water heater · HE, HE+, SE, Sensei

The circulation pump should be bronze or stainless steel.

Applies to: Recirculation loop with three unit circulation

Source: System Design Manual - WH-3-CIRC - English, p. 1. Written in our own words; check the manual for your exact model.

Same tips in your pocket

The HVACopedia app has these tips, every error code and the settings tables offline.

Open the app

For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.