Annual maintenance checklist
What is going on
Yearly service checks for the boiler. Vent and screens, fan and motor, controller, pressure, relief valve, dirt trap, DHW filter, expansion tank, condensate trap and drain. Fan motors are permanently lubricated and do not need oil. Clean the controller with a soft damp cloth only, no solvents. Pressure relief valve test must be done only by a licensed professional because the discharge is scalding.
Check in this order
- Inspect the vent system for blockages or damage. Clean the vent screen or room air filter if used.
- Clean dust and dirt from the fan and motor.
- Clean the controller with a soft damp cloth.
- Confirm the system pressure is between 17 and 26 PSI. If low, add water until it is in range.
- Operate the pressure relief valve manually once a year with safe discharge.
- Close the shutoff valves under the boiler, clean the heating system dirt trap, then purge the air.
- If DHW flow drops, close the DHW shutoff valves and clean the DHW inlet filter.
- Perform expansion tank checks as the manufacturer recommends.
- Check the condensate trap for sediment. Unplug the bottom, remove sediment, and replace the plug. Do not use a wrench on the condensate drain.
- Confirm the condensate drain is not blocked and the condensate pump (if used) works.
Applies to: All I-Series Plus condensing combi boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 120. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.