Rinnai · Boiler troubleshooting
Burner flame visual inspection
What is going on
The flame must cover the burner surface and burn clear, blue and stable. A yellow or green flame is unsatisfactory. Check the flame through the view ports on the burner.
Likely causes
- Dirty burner or main burner or fan blades
- Flame color not clear blue
Check in this order
- Turn off and disconnect electrical power and allow the boiler to cool.
- Remove the front panel.
- Use a vacuum to remove dust from the main burner and fan blades. Do not use a wet cloth or spray cleaners.
- Do not open the burner cabinet or touch the burner surface.
- Restore power, fire the boiler and confirm a clear blue stable flame covers the burner surface.
- Clean the condensate trap and external drain of debris.
Applies to: All I-Series Plus condensing combi boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 117, p. 118. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.