Annual maintenance checks

I-Series Plus

What is going on

Yearly service tasks for owner and licensed professional.

Check in this order

  1. Inspect the vent system for blockages or damage, and clean the vent screen or room air filter if used.
  2. Clean dust and dirt from the fan and motor (motors are lubricated for life, no oiling).
  3. Clean the controller with a soft, damp cloth. Do not use solvents.
  4. Confirm pressure is 17-26 PSI; if low, add water until it is in range.
  5. Operate the pressure relief valve manually once a year, taking care with scalding discharge and making sure the discharge has a safe place to flow.
  6. Clean the heating system dirt trap, close the shut-off valves under the boiler first, then purge the air after reinstalling the filter.
  7. Clean the DHW inlet filter if DHW flow is dropping; close the DHW shut-off valves first.
  8. Check the expansion tank as recommended by the manufacturer.
  9. Check the condensate trap for sediment and remove it through the bottom plug without using a wrench on the drain.
  10. Confirm the condensate drain line is not blocked and the drain pump (if used) works.
  11. Flush the DHW plate heat exchanger in hard water areas, or when LC appears.
  12. For seasonal shutdown, close the shut-off valves below the boiler and drain the boiler to prevent freeze damage.

Applies to: I-Series Plus combi boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 116. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.