Rinnai · Boiler troubleshooting
Test the condensate pump safety switch
What is going on
Confirms the boiler faults when the reservoir float closes the circuit and clears once the pump runs again. The switch is normally open and faults when it closes.
Likely causes
- Condensate reservoir full, float switch closed
Check in this order
- Unplug the condensate pump.
- Fill the condensate reservoir with water until the float switch closes.
- Turn the boiler on. Expect diagnostic code 250.
- Plug the pump back in and confirm condensate is leaving the reservoir.
- Press the On/Off button to turn the boiler off, wait 5 seconds, then turn the power back on to clear code 250.
Applies to: I-Series Plus condensing combi boilers with a condensate pump
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation manual, p. 65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.