Viessmann · Boiler troubleshooting

Individual burner combustion air intake ducting

Vitocrossal 300 CA3B Dual Fuel

What is going on

Each burner has its own combustion air intake. Size the ducting from the single intake pipe with the longest equivalent length, which is the one shaded grey on the drawing. The burner cannot carry the duct weight.

Check in this order

  1. Calculate the equivalent length of the longest single intake pipe.
  2. Check the calculated length against the maximum equivalent length tables on pages 58 to 61.
  3. Check the roof and vent spacing on the vertical installation drawing.
  4. Connect the intake duct to the boiler using the Combustion Air Intake Kit instructions.
  5. Fully support the combustion air intake ducting so the burner does not carry its weight.

Applies to: Multi-burner combustion air intake

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.