Weil-McLain · Boiler troubleshooting
Motorized air damper interlock on combustion air openings
What is going on
If combustion air openings have motorized dampers, the boiler must not fire unless the damper is fully open, and must shut down if the damper closes during operation. The SlimFit control has a Proof of Closure function for this. The manual calls for an isolated proving contact wired in series with the thermostat input.
Check in this order
- Fit an isolated end switch that proves the damper is open.
- Wire that contact in series with the thermostat input to the boiler.
- Confirm the boiler does not start with the damper closed.
- Confirm the boiler shuts down if the damper closes during operation.
Applies to: Boiler rooms with motorized air dampers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.