Viessmann · Boiler troubleshooting

Route boiler flue (venting) through wall or roof

Vitodens 200-W

What is going on

Single-wall or coaxial venting can exit through the side wall or the roof. The boiler ships with a pre-installed vent adaptor.

Check in this order

  1. Run the venting system (single-wall or coaxial) by the shortest practical route.
  2. Keep a rising slope of at least 3 degrees toward the outlet.
  3. Support the piping so it does not rest on or load the boiler. Use only a moderate amount of pipe dope.
  4. For single-wall venting in a room-air-dependent installation, remove the outer gasket.
  5. If using the combustion air inlet seal, remove the seal, tear out the centre section and refit the remaining rubber seal into the air inlet opening.

Applies to: Vitodens 200-W B2HB venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB installation manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.