Route boiler flue (venting) through wall or roof
What is going on
Single-wall or coaxial venting can exit through the side wall or the roof. The boiler ships with a pre-installed vent adaptor.
Check in this order
- Run the venting system (single-wall or coaxial) by the shortest practical route.
- Keep a rising slope of at least 3 degrees toward the outlet.
- Support the piping so it does not rest on or load the boiler. Use only a moderate amount of pipe dope.
- For single-wall venting in a room-air-dependent installation, remove the outer gasket.
- If using the combustion air inlet seal, remove the seal, tear out the centre section and refit the remaining rubber seal into the air inlet opening.
Applies to: Vitodens 200-W B2HB venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.