Dismantling the burner

Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

What is going on

Removing the upper burner section and the burner tube.

Check in this order

  1. Close the gas shut-off valve and let the system cool. Follow the preparing-for-service section on page 51.
  2. Disconnect the burner gas line and the connectors on the burner control unit.
  3. Pull off the ignition electrode connectors.
  4. Remove 2 screws from the ignition electrode block and lift the block up and out.
  5. Remove the 6 nuts around the burner mounting plate and remove the upper burner section.
  6. Secure lifting chains at 3 points on the frame of the upper burner section.
  7. Remove the 8 nuts from the combustion chamber cover plate.
  8. Lift out the mounting plate with the burner tube using a lifting device, following the lifting device instructions.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 69-70. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.