Viessmann · Boiler troubleshooting
Primary circuit flow and low-loss header
What is going on
The boiler is for closed-loop, forced-circulation hot water systems only. A low-loss header is strongly preferred.
Check in this order
- Size the pipe with the standard friction loss method.
- Keep the flow within the boiler's maximum and minimum flow rate.
- Install a low-loss header if the system flow exceeds the boiler maximum, falls below the minimum, or is unknown.
- Connect the low-loss header; the boiler's built-in logic then keeps the required flow across the system via sensor communication.
- Refer to the Technical Data manual for low-loss header details.
Applies to: Vitodens 222-F, B2TB primary circuit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F, B2TB installation instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.