Viessmann · Boiler troubleshooting

Wire space heating pump output to zone controller (outdoor reset with Como OT)

Versatronik 10.WB1

What is going on

For a Vitodens 100-W (WB1A/B) with Versatronik Como OT for outdoor reset and no room thermostat. The 120 VAC space heating pump output feeds the zone controller. When the output is on, the zone controller sees the signal and any zone with a call will run its pump or valve. With no signal, no zone starts on a thermostat call.

Check in this order

  1. Disconnect power to the Versatronik 10.WB1 and the zone controller.
  2. Remove the ZC/ZR jumper from the zone controller.
  3. Connect the L output of the Versatronik space heating pump output to the ZC terminal of the zone controller.
  4. Power both devices and test operation.

Applies to: Versatronik 10.WB1 with Versatronik Como OT outdoor reset

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 10.WB1 installation and operating manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.