Display normal but no heat to the space
What is going on
The boiler looks fine but the heating loop stays cold.
Likely causes
- No thermostat/end switch call on terminals 9-10
- Outdoor temperature above warm weather shutdown (2.025)
- Supply already above CH setpoint
- CH pump not running or not wired to 7-8
- DHW priority active
Check in this order
- Make a call the radiator icon flashes during a CH demand. If unsure about the thermostat, jumper terminals 9 and 10.
- No radiator icon read outdoor temperature at 1.004 and compare with the warm weather shutdown (2.025); above it the boiler will not heat.
- Icon flashing but no fire compare the main-screen supply temperature against the CH setpoint (0.003 / 2.003). The burner waits until supply drops below the setpoint by the differential. Raise 2.003 if it is too low.
- Make sure the CH pump runs and is wired to terminals 7 and 8.
- Radiator icon steady and faucet icon flashing means a DHW call has priority. If this lasts too long, raise the DHW setpoint or shorten the DHW priority time (2.043).
Applies to: B85, B120, B160 (NG and LP)
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, 13.2.2 p.67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.